This document is a Limited Pre-Renovation Asbestos and Lead Paint Survey Report for the James A. Haley VA Hospital in Tampa, Florida, conducted by Terracon Consultants, Inc. on November 5, 2024. The survey focused on designated interior areas of the 1st floor Wing C and the roof, specifically for planned MRI interior renovations. Terracon collected 45 bulk samples from 19 homogeneous areas, including roofing, floor tiles, ceiling tiles, drywall, joint compound, covebase, mastic, and other building materials.

Laboratory analysis by Scientific Analytical Institute revealed no asbestos or lead was detected in any of the samples. The survey was performed in accordance with EPA regulations (NESHAP and OSHA standards) to identify and classify potential asbestos-containing materials (ACM) and lead-based paint prior to renovation activities. Terracon recommended maintaining a copy of the survey onsite and contacting the Hillsborough County Environmental Protection Commission for confirmation of project requirements. The report includes detailed appendices with sample analysis results, photographs, and the inspector's certifications.

View the file

Other files

File Type Posted
673-CSI-132 SOW RFI update.docx DOCX document
first floor drawing.pdf PDF
673-CSI-132 RFI Responses.docx DOCX document
WD-FL20260208 01-02-26.pdf PDF
36C24826Q0128 0003.pdf PDF
second floor drawing - ACM.pdf PDF
sign in sheet.pdf PDF
36C24826Q0128 0002.pdf PDF
VA James A Haley1 5T MRI -90 CD Progress Specifications 12-15.pdf PDF
2510179R0-DRAWINGS.pdf PDF
36C24826Q0128 0001.pdf PDF
VA James A Haley 1 5T MRI -90 CD-Progress Drawings 12-15.pdf PDF
36C24826Q0128_1.pdf PDF
Experience information Sheet.pdf PDF
EMR 1 page.pdf PDF
Base Offer Price Breakdown - 1 page.xlsx XLSX spreadsheet
PAST AND PRESENT PERFORMANCE QUESTIONNAIRE.docx DOCX document
WD FL20250208 05232025.pdf PDF
2510179R0-DRAWINGS.pdf PDF
36C24826Q0128.docx DOCX document
673-CSI-132 SOW.docx DOCX document
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Limited Pre-Renovation

Asbestos and Lead Paint Survey Report

James A. Haley VA Hospital

13000 Bruce B. Downs Boulevard

Tampa, Florida 33612

December 9, 2024 Terracon Project No. H4247230

Prepared for:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164

Plano, Texas 75093

Prepared by:

Terracon Consultants, Inc.

Tampa, Florida

5463 West Waters Avenue, Suite 830

Tampa, Florida 33634

P (813) 221-0050

F (813) 221-0051

Terracon.com

Facilities | Environmental | Geotechnical | Materials

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164

Plano, Texas 75093

Attn: Ms. Ann Seibert

P: (855) 424-3838

E: Ann.Seibert@romanykconsulting.com

RE: Limited Pre-Renovation Asbestos and Lead Paint Survey Report

James A. Haley VA Hospital

Designated MRI and Roof Locations

13000 Bruce B. Downs Boulevard

Terracon Report No. H4247230

Dear Ms. Seibert:

Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report to Romanyk Consulting

(Client). The purpose of this report is to present the results of a limited pre-renovation asbestos and lead paint survey performed within the designated areas of the James A. Haley VA Hospital located in Tampa, Florida. This survey was conducted in general accordance with PH4247230, dated August 29, 2024.

Terracon understands this survey was requested in connection with the planned MRI interior renovations of the 1st floor areas and roof of the subject structure.

Based on the laboratory results, asbestos was not detected in the materials assessed. Laboratory analysis of the paint chip samples indicated lead was not detected in samples above the laboratory detection/reporting limit. Please refer to the attached report for further details.

Terracon appreciates the opportunity to provide this service to Romanyk Consulting Corp. If you have any questions regarding this report, or if you need assistance with project oversight and sampling during renovation, please contact the undersigned at 727-470-1104.

Sincerely, Terracon Consultants, Inc.

Florida Asbestos Business License Number ZA-337

Karl Kologiski Mark Fricke, CIH, CSP, LAC AHERA Building Inspector FL Licensed Asbestos Consultant AX132

Karl Kologiski https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAATzM0I_ohanD6J_5bRaIHwpAb5w0uGTk4 https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAATzM0I_ohanD6J_5bRaIHwpAb5w0uGTk4

TABLE OF CONTENTS

Page

1.0 INTRODUCTION

1.1 Project Objective

1.2 Reliance

2.0 BUILDING DESCRIPTION

3.0 ASBESTOS FIELD ACTIVITIES

3.1 Visual Assessment

3.2 Physical Assessment

3.3 Sample Collection

3.4 Sample Analysis

4.0 LEAD-BASED PAINT FIELD ACTIVITIES

4.1 Visual Observations

4.2 Visual Assessment

4.3 Sample Collection

4.4 Sample Analysis

5.0 ASBESTOS REGULATORY OVERVIEW

6.0 LEAD-BASED PAINT REGULATORY OVERVIEW

7.0 ASBESTOS FINDINGS AND RECOMMENDATIONS

7.1 Findings

7.2 Recommendations

8.0 LEAD-BASED PAINT FINDINGS AND RECOMMENDATIONS

8.1 Findings

8.2 Recommendations

9.0 LIMITATIONS/GENERAL COMMENTS

APPENDIX A SUMMARY OF ASBESTOS SAMPLE LAYERS BY HOMOGENEOUS AREA (HA)

APPENDIX B LEAD PAINT SUMMARY TABLE

APPENDIX C ASBESTOS ANALYTICAL LABORATORY RESULTS

APPENDIX D LEAD PAINT ANALYTICAL LABORATORY RESULTS

APPENDIX E REPRESENTATIVE PHOTOGRAPHS

APPENDIX F LICENSES AND CERTIFICATIONS

Facilities | Environmental | Geotechnical | Materials 1

Asbestos and Lead Paint Survey Report

13000 Bruce B. Downs Boulevard

Terracon Project No. H4247230

1.0 INTRODUCTION

Terracon Consultants, Inc. (Terracon) conducted a limited roofing, interior pre-renovation asbestos survey, and limited lead paint survey of the designated areas of the James A. Haley VA Hospital in

Tampa, Florida. Surveys and sampling were limited to suspect materials located within interior areas and the roof that are part of the MRI upgrades in the designated areas.

The survey was conducted on November 5, 2024, by Terracon representative Mr. Karl Kologiski, an

Asbestos Hazard Emergency Response Act (AHERA)-accredited asbestos inspector in general accordance with Terracon Proposal PH4247230, dated August 29, 2024. Although reasonable effort was made to survey all accessible suspect materials within the designated interior and roof locations, additional suspect but un-sampled materials could be located in walls, in voids, or in other inaccessible or concealed areas. Applicable licenses and certifications are presented in Appendix F.

Homogeneous areas of suspect asbestos-containing materials (ACM) and suspect lead paint were visually identified, surveyed, and documented. Asbestos sampling was performed in general accordance with the United States (U.S.) Environmental Protection Agency (EPA) 40 Code of Federal Regulations

(CFR) Part 763 Subpart E 763, known as AHERA. Suspect lead paint samples were obtained from representative surfaces potentially containing lead coatings.

1.1 Project Objective

Terracon’s services were performed to accommodate planned renovation activities and to satisfy requirements of the EPA regulation 40 CFR 61, Subpart M, National Emission Standards for Hazardous

Air Pollutants (NESHAP). NESHAP regulations prohibit the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP requires that potentially regulated ACM

(RACM) be identified, classified, and quantified prior to planned disturbances or demolition activities.

Lead paint testing was performed to comply with applicable sections of the U.S. Occupational Safety and

Health Administration (OSHA) Lead Standard (29 CFR 1926.62) for disturbance of paint/coatings with lead that will be encountered during renovation or demolition activities.

1.2 Reliance

This report is for the exclusive use of Romanyk Consulting Corp (Romanyk) for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of

Terracon and Romanyk. Reliance on this report by Romanyk and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal, this report, and the existing agreement between Romanyk and Terracon. The limitations of liability defined in Terracon’s

Agreement for Services is the aggregate limit of Terracon’s liability to Romanyk.

Asbestos & Lead Paint Survey Report

James A. Haley VA Hospital ■ Tampa, Florida

December 9, 2024 ■ Terracon Proposal No. PH4247230

Facilities | Environmental | Geotechnical | Materials 2

2.0 BUILDING DESCRIPTION

The designated interior areas of the 1st floor Wing C included in the survey consisted of the following rooms: GC-26, GC-26A, GC030, GC-031, GC-045, GC-046, GC-047, and Hallway Common Area.

Interior floor finishes of the 1st floor subject areas included vinyl floor tile and bamboo flooring. Wall finishes included smooth painted drywall and joint compound, vinyl cove base, and wallpaper. Ceilings consisted of a suspended ceiling grid and ceiling tiles. The roof is steel framing with a rolled TPO membrane.

3.0 ASBESTOS FIELD ACTIVITIES

The asbestos portion of the survey was conducted on November 5, 2024, by Terracon representative Mr.

Karl Kologiski an AHERA-accredited asbestos inspector. A copy of the inspector certificates and applicable licenses are attached as Appendix F. The survey was conducted in general accordance with the sample collection protocols established in EPA 40 CFR Part 763 Subpart E 763.86, AHERA. A summary of survey activities is provided below.

3.1 Visual Assessment

Survey activities were initiated with limited visual observations of the accessible, designated areas to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application. The limited assessment was conducted in readily accessible areas of the buildings.

3.2 Physical Assessment

A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.

3.3 Sample Collection

Based on results of the visual observations, bulk samples of suspect ACM were collected in general accordance with AHERA sampling protocols. Samples of suspect materials were collected in randomly selected locations in each homogeneous area. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.

The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content. A total of forty-five (45) bulk samples were collected by Terracon from nineteen (19) homogeneous areas of suspect

ACM.

A summary of asbestos sample layers by homogeneous areas are presented in Appendix A. Asbestos laboratory data is presented in Appendix C.

Facilities | Environmental | Geotechnical | Materials 3

3.4 Sample Analysis

Bulk samples were submitted under secure chain of custody protocols to Scientific Analytical Institute

(SAI) of Greensboro North Carolina for analysis by polarized light microscopy with dispersion staining techniques per EPA methodology 600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. SAI is accredited under the National Voluntary

Laboratory Accreditation Program (NVLAP) Accreditation No. 200664-0.

4.0 LEADPAINT FIELD ACTIVITES

4.1 Visual Observations

The lead paint survey was limited to readily observable and accessible surfaces that may be disturbed during the planned renovations. Terracon cannot guarantee that all lead paint coated surfaces were identified during our survey as some lead paint may be hidden from sight or in inaccessible locations, or the homogeneous construction areas identified may not be truly homogeneous. This limited lead paint survey was not performed in accordance with U.S. Department of Housing and Urban

Development (HUD) Guidelines for the Evaluation and Control of Lead-Based Paint (LBP)

Hazards in Housing or applicable to EPA 40 CFR 745 requirements. It should be understood that this limited lead paint survey was not considered to be comprehensive in nature, and the results are not intended to be used to determine all lead hazards, develop lead abatement plans, or prepare detailed cost estimates for lead abatement.

4.2 Visual Assessment

A visual assessment of each unique combination, defined as a color, component, and substrate, of suspect lead paint was conducted in addition to an assessment of the paint condition.

4.3 Sample Collection

A total of six (6) paint chip samples of suspect lead paint were collected. Paint chip samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker. A summary of sample results is presented in Appendix B. Laboratory results are presented in Appendix D.

Representative lead paint sample photographs are presented in Appendix E.

4.4 Sample Analysis

Paint chip samples were submitted under chain of custody to Scientific Analytical Institute (SAI) for analysis by flame atomic absorption spectrometry per EPA SW-846/3050B/7000B. SAI is accredited under the Environmental Lead Laboratory Accreditation Program (ELLAP) (Accreditation No. 173190).

Facilities | Environmental | Geotechnical | Materials 4

5.0 ASBESTOS REGULATORY OVERVIEW

The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity.

Under NESHAP, asbestos-containing building materials are classified as:

1. Friable ACM, or

2. Category I Non-Friable ACM, or

3. Category II Non-Friable ACM.

Friable materials are those that, when dry, may be crumbled, pulverized, or reduced to powder by hand pressure. Category I Non-Friable ACM includes packings, gaskets, resilient floor coverings and asphalt roofing products containing more than 1% asbestos. Category II Non-Friable ACM are any materials other than Category I Non-Friable ACM that contain more than 1% asbestos.

Under NESHAP, Regulated Asbestos-Containing Materials (RACM are classified as:

1. Friable ACM.

2. Category I Non-Friable ACM that is in poor condition and/or has become friable.

3. Category I Non-Friable ACM that will or has been subjected to sanding, grinding, cutting, or abrading.

4. Category II Non-Friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act upon the material in the course of renovation or demolition operations.

In the State of Florida, asbestos activities are regulated by the Florida Department of Environmental

Protection (FDEP). Some counties have developed an enforcement division to carry out the responsibilities of the FDEP and have developed environmental and asbestos ordinances in which additional compliance is required. Since the facility is located in Hillsborough County Florida, the NESHAP regulations are under the jurisdiction of the Hillsborough County Environmental Protection Commission

(813-627-2660).

Per the NESHAP, RACM must be removed prior to renovation or demolition activities that will disturb the materials. Removal of any ACM or RACM must be conducted by a State of Florida-licensed asbestos abatement contractor, in compliance with Florida Statute (F.S) 469.001-014. In addition, third party air monitoring should be performed during and following the abatement.

The OSHA Asbestos standard for construction (29 CFR 1926.1101) regulates employee workplace exposure to asbestos. The OSHA standard has (2) Permissible Exposure Limits (PEL) that require employee exposure to airborne asbestos fibers be maintained below 0.1 asbestos fibers per cubic centimeter of air (0.1 f/cc) for an 8-hour Time-Weighted Average (8-Hr. TWA) and 1.0 f/cc for a 30-minute TWA (Excursion Limit). The OSHA standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work.

Facilities | Environmental | Geotechnical | Materials 5

6.0 LEAD-CONTAINING PAINT REGULATORY OVERVIEW

Lead is regulated by the EPA, HUD, Florida Department of Environmental Protection (FDEP) and OSHA.

The EPA and FDEP regulate lead use, removal, and disposal, and OSHA regulates lead exposure to workers. The EPA defines Lead-Based Paint (LBP) as any paint, varnish, stain, or other applied coating that contains lead equal to or greater than 1.0 mg/cm2, 5,000 mg/kg, or 0.5% by dry weight as determined by laboratory analysis.

For the purpose of the OSHA lead standard, lead-containing materials includes any detectable concentrations of metallic lead, all inorganic lead compounds, and organic lead soaps. A synopsis of the OSHA regulations (29 CFR 1926.62) and the applicability are as follows:

The OSHA Lead Standard for Construction (29 CFR 1926.62) applies to all construction work where an employee may be occupationally exposed to lead. All work related to construction, alteration, or repair

(including painting and decorating) is included. The Lead-in-Construction standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of disturbance-removal and other workplace conditions.

Under this standard, construction includes, but is not limited to, the following:

◼ Demolition or salvage of structures where lead or materials containing lead are present

◼ Removal or encapsulation of materials containing lead

◼ New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead

◼ Installation of products containing lead

◼ Lead contamination/emergency clean-up

◼ Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed

◼ Maintenance operations associated with construction activities described above.

7.0 FINDINGS AND RECOMMENDATIONS – ASBESTOS

7.1 Findings

Based on the results of laboratory analysis of the designated suspect ACM, none of the samples obtained were found to contain asbestos.

A summary of asbestos sample layers by homogeneous areas is presented in Appendix A. Asbestos laboratory data is presented in Appendix C.

It should be noted that suspect materials other than those identified may exist. Should suspect materials other than those which were identified during this survey be uncovered prior to or during the renovation process, those materials should be assumed asbestos-containing until sampling and analysis can confirm or refute their asbestos content.

Facilities | Environmental | Geotechnical | Materials 6

7.2 Recommendations

Based on the results of laboratory analysis of the designated, suspect ACM, no materials sampled during this assessment were confirmed to contain asbestos. As such, we recommend contacting your local regulator(s) for confirmation of their project requirements and to maintain a copy of this survey onsite.

We recommend direct contact with the Hillsborough County Environmental Protection Commission (813-

627-2660) for confirmation and clarifications of their asbestos program requirements.

8.0 FINDINGS AND RECOMMENDATIONS – Lead Paint

8.1 Findings

Detectable concentrations of lead were not identified in the various coatings evaluated during the assessment. A Lead Paint Summary Table is presented in Appendix A. The following summarizes the results of the 6 paint chip samples:

Interior 1st Floor Areas

1. The six (6) paint samples collected were all below laboratory detection/reporting limits.

9.0 LIMITATIONS/GENERAL COMMENTS

This Limited Interior Pre-renovation Asbestos and Lead Paint Survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the designated areas. The information contained in this report is relevant to the date on which this survey was performed and should not be relied upon to represent conditions at a later date.

This report has been prepared on behalf of and exclusively for use by Romanyk for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may have been used in the preparation of this report. No warranty, express or implied, is made.

APPENDIX A

LIMITED PRE-RENOVATION

ASBESTOS AND LEAD PAINT SURVEY REPORT

JAMES A. HALEY VA HOSPITAL - 1ST FLOOR WING C MRI AREAS AND ROOF

13000 BRUCE B. DOWNS BOULEVARD, TAMPA, FLORIDA 33612

TERRACON REPORT NO. H4247230

SUMMARY OF ASBESTOS SAMPLE LAYERS BY HOMOGENEOUS AREA (HA)

HA

No.

Sample No. Sample Description Sample Location Sample Layer Asbestos Content

H1

H1-1-A

Lower Roof Core

Roof Roofing None Detected

H1-1-B Roof Insulation/Foam None Detected

H1-2-A Roof Roofing None Detected

H1-2-B Roof Insulation/Foam None Detected

H2

H2-3-A

Upper Roof Core

Roof Membrane None Detected

H2-3-B Roof Insulation/Foam None Detected

H2-4-A Roof Membrane None Detected

H2-4-B Roof Insulation/Foam None Detected

H4

H4-5-A

12” Gray stone VFT

Hallway Floor Tile None Detected

H4-5-B Hallway Mastic None Detected

H4-6-A GC-026 Tile None Detected

H4-6-B GC-026 Mastic None Detected

H4-7-A GC-026A Tile None Detected

H4-7-B GC-026A Mastic None Detected

H5

H5-8-A

Bamboo Flooring

GC-045 Tile None Detected

H5-8-B GC-045 Mastic None Detected

H5-9-A GC-047 Vinyl Floor Tile None Detected

H5-9-B GC-047 Mastic None Detected

H5-10-A GC-030 Vinyl Floor Tile None Detected

H5-10-B GC-030 Mastic None Detected

Kologiski, Karl V Stamp

Limited Pre-Renovation Asbestos & Lead Paint Survey Report

Sample No. Sample Description Sample Location Sample Layer Asbestos Content

H6

H6-11 4” Black Cove Base

GC-045 Cove Base / Mastic None Detected

H6-12-A GC-047 Cove Base None Detected

H6-12-B GC-047 Mastic None Detected

H7 H7-13 24” Wormhole Ceiling Tile

GC-045 Ceiling Tile None Detected

H7-14 GC-047 Ceiling Tile None Detected

H8

H8-15

DW-JC

GC-045

Drywall/Joint

Compound None Detected

H8-16 GC-046

Drywall/Joint

Compound None Detected

H8-17 GC-026

Drywall/Joint Compound None Detected

H8-18 GC-031

Drywall/Joint Compound None Detected

H9

H9-19

Fireproofing

Hallway Fireproofing None Detected

H9-20 GC-045 Fireproofing None Detected

H9-21 GC-031 Fireproofing None Detected

H9-22 GC-026 Fireproofing None Detected

H9-23 Hallway Fireproofing None Detected

H10 H10-24 Floor Leveling Compound

GC-045 Leveling Compound None Detected

H10-25 GC-045 Leveling Compound None Detected

H11

H11-26-A 4” White Cove Base

Hallway Cove Base None Detected

H11-26-B Hallway Cove Base None Detected

H11-27 GC-026 Cove Base / Mastic None Detected

H12 H12-28

Wallpaper GC-046 Wallpaper None Detected

H12-29 GC-043 Wallpaper None Detected

H13 H13-30

24” Random Divot Ceiling Tile GC-046 Ceiling Tile None Detected

H13-31 GC-026 Ceiling Tile None Detected

H14 H14-32

Yellow Duct Mastic GC-046 Mastic None Detected

H14-33 GC-046 Mastic None Detected

H15 H15-34 White Caulking GC-026A Caulking None Detected

Limited Pre-Renovation Asbestos & Lead Paint Survey Report

Sample No. Sample Description Sample Location Sample Layer Asbestos Content

H15-35 GC-026-A Caulking None Detected

H16

H16-36-A

12” Off White VFT

GC-030 Tile None Detected

H16-36-B GC-030 Mastic None Detected

H16-37-A GC-030 Tile None Detected

H16-37-B GC-030 Mastic None Detected

H17 H17-38

Red Fire Stop GC-026 Fire Stop None Detected

H17-39 GC-026A Fire Stop None Detected

H18 H18-40

Gray Duct Mastic GC-026 Mastic None Detected

H18-41 GC-026 Mastic None Detected

H19

H19-42-A

12” Off White VFT

GC-031 Tile None Detected

H19-42-B GC-031 Mastic None Detected

H19-43-A GC-031 Tile None Detected

H19-43-B GC-031 Mastic None Detected

H20

H20-44-A

4” Tan Cove Base

GC-031 Cove Base None Detected

H20-44-B GC-031 Mastic None Detected

H20-45-A GC-031 Cove Base None Detected

H20-45-B GC-031 Mastic None Detected

APPENDIX B

LIMITED PRE-RENOVATION

ASBESTOS AND LEAD PAINT SURVEY REPORT

JAMES A. HALEY VA HOSPITAL - 1st Floor Wing C MRI Areas and Roof 13000 Bruce B. Downs Boulevard, Tampa, Florida 33612

Terracon Report No. H4247230

LEAD CONTAINING PAINT SUMMARY TABLE

Sample

ID

Sample Location Item Substrate Color

Reporting Limit

(PPM)

Concentration

(PPM)

Paint Chip

Results %

Weight

X1 GC-045 Door Frame Metal Gray 36 <36 <0.0036

X2 GC-026A Interior Wall Drywall Beige 39 <39 <0.0039

X3 GC-O45 Interior Wall Drywall White 61 <61 <0.0061

X4 GC-030 Interior Wall Drywall Blue 49 <49 <0.0049

X5 GC-031 Door Frame Metal White 38 <38 <0.0038

46 GC-031 Interior Wall Drywall White 54 <54 <0.0054

< = Below Detection Limit

Results in bold indicate quantifiable concentrations of lead

Kologiski, Karl V Stamp

APPENDIX C

ASBESTOS ANALYTICAL LABORATORY RESULTS

Bulk Asbestos Analysis By Polarized Light Microscopy EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10067758Customer: Terracon 5463 W Waters Ave Suite 830 Tampa, FL 33634-1253

Analysis:

Date Received:

Karl Kologiski

PLM

11/07/2024

Project: J. Haley VA MRI Renovation Date Reported: 11/14/2024

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

H1-1 - A

10067758_0001

Lower roof core

None Detected 15% Fiber Glass 85% Other

Non-Fibrous

Dissolved

Black

Homogeneous roofing

H1-1 - B

10067758_0046

Lower roof core

None Detected 30% Cellulose 70% Other

Non-Fibrous

Ashed, Dissolved

Gray, Yellow

Heterogeneous insulation/foam

H1-2 - A

10067758_0002

Lower roof core

None Detected 15% Fiber Glass 85% Other

Non-Fibrous

Dissolved

Black

Homogeneous roofing

H1-2 - B

10067758_0047

Lower roof core

None Detected 30% Cellulose 70% Other

Non-Fibrous

Ashed, Dissolved

Gray, Yellow

Heterogeneous insulation/foam

H2-3 - A

10067758_0003

Upper roof core

None Detected 100% Other

Non-Fibrous

Ashed

Black

Homogeneous membrane

H2-3 - B

10067758_0048

Upper roof core

None Detected 30% Cellulose 70% Other

Non-Fibrous

Dissolved, Ashed

Gray, Yellow

Heterogeneous insulation/foam

H2-4 - A

10067758_0004

Upper roof core

None Detected 100% Other

Non-Fibrous

Ashed

Black

Homogeneous membrane

H2-4 - B

10067758_0049

Upper roof core

None Detected 30% Cellulose 70% Other

Non-Fibrous

Dissolved, Ashed

Yellow, Gray

Heterogeneous insulation/foam

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Jalen Moore (63)

Analyst Approved Signatory

Page 1 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10067758Customer: Terracon 5463 W Waters Ave Suite 830 Tampa, FL 33634-1253

Analysis:

Date Received:

Karl Kologiski

PLM

11/07/2024

Project: J. Haley VA MRI Renovation Date Reported: 11/14/2024

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

H4-5 - A

10067758_0005

12" gray stone VFT - hallway

None Detected 100% Other

Non-Fibrous

Ashed

Gray

Homogeneous floor tile

H4-5 - B

10067758_0050

12" gray stone VFT - hallway

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic

H4-6 - A

10067758_0006

12" gray stone VFT - 026

None Detected 100% Other

Non-Fibrous

Ashed

Gray

Homogeneous tile

H4-6 - B

10067758_0051

12" gray stone VFT - 026

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous mastic

H4-7 - A

10067758_0007

12" gray stone VFT - 026A

None Detected 100% Other

Non-Fibrous

Ashed

Gray

Homogeneous tile

H4-7 - B

10067758_0052

12" gray stone VFT - 026A

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous mastic

H5-8 - A

10067758_0008

Bamboo flooring - 045

None Detected 100% Other

Non-Fibrous

Ashed

Tan

Homogeneous tile

H5-8 - B

10067758_0053

Bamboo flooring - 045

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous mastic

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Jalen Moore (63)

Page 2 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10067758Customer: Terracon 5463 W Waters Ave Suite 830 Tampa, FL 33634-1253

Analysis:

Date Received:

Karl Kologiski

PLM

11/07/2024

Project: J. Haley VA MRI Renovation Date Reported: 11/14/2024

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

H5-9 - A

10067758_0009

Bamboo flooring - 047

None Detected 100% Other

Non-Fibrous

Ashed

Tan

Homogeneous vinyl floor tile

H5-9 - B

10067758_0054

Bamboo flooring - 047

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous mastic

H5-10 - A

10067758_0010

Bamboo flooring - 030

None Detected 100% Other

Non-Fibrous

Ashed

Tan

Homogeneous vinyl floor tile

H5-10 - B

10067758_0055

Bamboo flooring - 030

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic

H6-11

10067758_0011

4" black cove base - 45

None Detected 100% Other

Non-Fibrous

Ashed

Gray, Beige

Heterogeneous cove base/mastic- layers inseparable

H6-12 - A

10067758_0012

4" black cove base - 47

None Detected 100% Other

Non-Fibrous

Ashed

Gray

Homogeneous cove base

H6-12 - B

10067758_0056

4" black cove base - 47

None Detected 100% Other

Non-Fibrous

Ashed

Beige

Homogeneous mastic

H7-13

10067758_0013

24" wormhole ceiling tile -

None Detected 60% 20%

Cellulose Mineral Wool

10% 10%

Other Perlite

Fibrous

Ashed

Beige

Homogeneous

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Jalen Moore (63)

Page 3 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10067758Customer: Terracon 5463 W Waters Ave Suite 830 Tampa, FL 33634-1253

Analysis:

Date Received:

Karl Kologiski

PLM

11/07/2024

Project: J. Haley VA MRI Renovation Date Reported: 11/14/2024

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

H7-14

10067758_0014

24" wormhole ceiling tile -

None Detected 60% 20%

Cellulose Mineral Wool

10% 10%

Other Perlite

Fibrous

Ashed

Beige

Homogeneous

H8-15

10067758_0015

DW-JC - 045

None Detected 10% Cellulose 90% Other

Non-Fibrous

Dissolved

White

Heterogeneous drywall:none detect; joint compound:none detect

H8-16

10067758_0016

DW-JC - 046

None Detected 10% Cellulose 90% Other

Non-Fibrous

Dissolved

White

Heterogeneous drywall:none detect; joint compound:none detect

H8-17

10067758_0017

DW-JC - 026

None Detected 10% Cellulose 90% Other

Non-Fibrous

Dissolved

White

Heterogeneous drywall:none detect; joint compound:none detect

H8-18

10067758_0018

DW-JC - 031

None Detected 10% Cellulose 90% Other

Non-Fibrous

Dissolved

White

Heterogeneous drywall:none detect; joint compound:none detect

H9-19

10067758_0019

Fireproofing - hallway

None Detected 95% Mineral Wool 5% Other

Fibrous

Teased

Gray

Homogeneous

H9-20

10067758_0020

Fireproofing - 045

None Detected 95% Mineral Wool 5% Other

Fibrous

Teased

Gray

Homogeneous

H9-21

10067758_0021

Fireproofing - 031

None Detected 95% Mineral Wool 5% Other

Fibrous

Teased

Gray

Homogeneous

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Jalen Moore (63)

Page 4 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10067758Customer: Terracon 5463 W Waters Ave Suite 830 Tampa, FL 33634-1253

Analysis:

Date Received:

Karl Kologiski

PLM

11/07/2024

Project: J. Haley VA MRI Renovation Date Reported: 11/14/2024

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

H9-22

10067758_0022

Fireproofing - 026

None Detected 95% Mineral Wool 5% Other

Fibrous

Teased

Gray

Homogeneous

H9-23

10067758_0023

Fireproofing - hallway

None Detected 95% Mineral Wool 5% Other

Fibrous

Teased

Gray

Homogeneous

H10-24

10067758_0024

Floor leveling compound -

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous

H10-25

10067758_0025

Floor leveling compound -

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous

H11-26 - A

10067758_0026

4" white covebsae - hallway

None Detected 100% Other

Non-Fibrous

Ashed

White

Homogeneous

H11-26 - B

10067758_0057

4" white covebase - hallway

None Detected 100% Other

Non-Fibrous

Dissolved

Tan

Homogeneous

H11-27

10067758_0027

4" white covebase - 026

None Detected 100% Other

Non-Fibrous

Ashed

White, Tan

Heterogeneous cove base/mastic- layers inseparable

H12-28

10067758_0028

Wallpaper - 046

None Detected 40% Cellulose 60% Other

Non-Fibrous

Ashed

Beige

Homogeneous

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Jalen Moore (63)

Page 5 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10067758Customer: Terracon 5463 W Waters Ave Suite 830 Tampa, FL 33634-1253

Analysis:

Date Received:

Karl Kologiski

PLM

11/07/2024

Project: J. Haley VA MRI Renovation Date Reported: 11/14/2024

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

H12-29

10067758_0029

Wallpaper - 043

None Detected 40% Cellulose 60% Other

Non-Fibrous

Ashed

Pink

Homogeneous

H13-30

10067758_0030

24" random divot ceiling tile

- 046

None Detected 60% 20%

Cellulose Mineral Wool

10% 10%

Perlite Other

Fibrous

Ashed

Gray

Homogeneous

H13-31

10067758_0031

24" random divot ceiling tile

- 026

None Detected 60% 20%

Cellulose Mineral Wool

10% 10%

Perlite Other

Fibrous

Ashed

Gray

Homogeneous

H14-32

10067758_0032

Yellow duct mastic - 046

None Detected 100% Other

Non-Fibrous

Dissolved

Tan

Homogeneous

H14-33

10067758_0033

Yellow duct mastic - 046

None Detected 100% Other

Non-Fibrous

Dissolved

Tan

Homogeneous

H15-34

10067758_0034

White caulking - 26A counter

None Detected 100% Other

Non-Fibrous

Ashed

White

Homogeneous

H15-35

10067758_0035

White caulking - 26A counter

None Detected 100% Other

Non-Fibrous

Ashed

White

Homogeneous

H16-36 - A

10067758_0036

12" off white VFT - 030 2nd layer

None Detected 100% Other

Non-Fibrous

Dissolved

White

Homogeneous tile

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Jalen Moore (63)

Page 6 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10067758Customer: Terracon 5463 W Waters Ave Suite 830 Tampa, FL 33634-1253

Analysis:

Date Received:

Karl Kologiski

PLM

11/07/2024

Project: J. Haley VA MRI Renovation Date Reported: 11/14/2024

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

H16-36 - B

10067758_0058

12" off white VFT - 030 2nd layer

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic

H16-37 - A

10067758_0037

12" off white VFT - 030 2nd layer

None Detected 100% Other

Non-Fibrous

Dissolved

White

Homogeneous tile

H16-37 - B

10067758_0059

12" off white VFT - 030 2nd layer

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic

H17-38

10067758_0038

Red fire stop - 026

None Detected 100% Other

Non-Fibrous

Ashed

Red

Homogeneous

H17-39

10067758_0039

Red fire stop - 026A

None Detected 100% Other

Non-Fibrous

Ashed

Red

Homogeneous

H18-40

10067758_0040

Gray duct mastic - 026

None Detected 100% Other

Non-Fibrous

Ashed

Gray

Homogeneous

H18-41

10067758_0041

Gray duct mastic - 026

None Detected 100% Other

Non-Fibrous

Ashed

Gray

Homogeneous

H19-42 - A

10067758_0042

12" off white VFT - 031

None Detected 100% Other

Non-Fibrous

Dissolved

Off-white

Homogeneous tile

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Jalen Moore (63)

Page 7 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10067758Customer: Terracon 5463 W Waters Ave Suite 830 Tampa, FL 33634-1253

Analysis:

Date Received:

Karl Kologiski

PLM

11/07/2024

Project: J. Haley VA MRI Renovation Date Reported: 11/14/2024

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

H19-42 - B

10067758_0060

12" off white VFT - 031

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic

H19-43 - A

10067758_0043

12" off white VFT - 031

None Detected 100% Other

Non-Fibrous

Dissolved

Off-white

Homogeneous tile

H19-43 - B

10067758_0061

12" off white VFT - 031

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic

H20-44 - A

10067758_0044

4" tan cove base - 031

None Detected 100% Other

Non-Fibrous

Ashed

Tan

Homogeneous cove base

H20-44 - B

10067758_0062

4" tan cove base - 031

None Detected 100% Other

Non-Fibrous

Dissolved

Tan

Homogeneous mastic

H20-45 - A

10067758_0045

4" tan cove base - 031

None Detected 100% Other

Non-Fibrous

Ashed

Tan

Homogeneous cove base

H20-45 - B

10067758_0063

4" tan cove base - 031

None Detected 100% Other

Non-Fibrous

Dissolved

Tan

Homogeneous mastic

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Jalen Moore (63)

Page 8 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 j}pJ Scientific Analytical Institute 4604 Dundas Dr. Greensboro, NC 27407

Phone: 336.292.3888 Fax: 336.292.3313 www.sailab.com lab@sailab.com

Company Contact Information Company: Terracon Contact: Kar 1 Kol-ogiski Address: 54 6 3 w, Waters Ave Phone 0: 727 -4 70 -11 04

Tampa, FL 33634 Fax0:

Email Ix]:

~arl_kologiski@terracon.com

Billing/Invoice Information Turn Around Times Company: same as above 90Min. • 48 Hours • Contact: 3 Hours • 72 Hours • Address: 6 Hours • 96 Hours •

12 Hours D 120 Hours Ji0 24 Hours D 144+Hours D

PO Number: j_ l,/ 'J.

Project Name/Number: VA r1Rr Rt110V',,~i'ol')

Lab Use Only / D O I .,.-1~ Lab Order ID: ___ \fl.s.__!...__ I-.)_ V Client Code: _____ _

Asbestos Test Types

PLM EPA 600/R-93/116 ~

Positive stop • PLM Point Count •

PCM NIOSH 7400 •

TEMAHERA •

TEM Level II •

TEM NIOSH 7402 •

TEM Bulk Qualitative • TEM Bulk Chatfield • TEM Bulk Quantitative • TEM Wipe ASTM D6480-99 • TEM Microvac ASTM D5755-02 • TEM Water EPA 100.2 • Other: •

Sample ID# Description/Location Volume/ Area Comments

H~I- I LoJ.Jer l?ouP Cor-t / /f'oJ/eJ H ,. ~ t, r f?oll1J

H 2-1 V pper Rur=- Core / rf'O -_t, i- .. , .J, / rf'u H4-S 12 ,, Gro S-1~,H. VFT • 1-/,,// vA 'I / , x "' / 6,k I l/ H lf-, I . 02, ,,..

l-f4,; ·- ~ - o~,A ✓ HS· i '111Mb oo /:"loot inc - O"f 5 / 10 / 1,/t;~ l'l/'17 /

HS"· Cf

- 0 c..i? ......-I

HS"·l0 -Ji oro _ -::itld t16y//

1-H- II l.f '' (11,,c.K Ct""( J;,,.s~ - 045 / t--1,,12 J, ,.., 0 L.f7 ✓

H 7- I J 2Lf II Wor,,, ho/! c~.·,,.,, t/lt- rJ'l, ✓ '-!r·'t1-y~ H ,. f'1 "'

- 0 £.(7 ✓

Total # of Samples __

Relinquished by Dateffime Dateffime

• II- S · -:J. '1 I{

Scientific Analytical Institute Page J-..:_ of J_

~~•-r. .. ted •

Sample ID#

Ht'-/5 H8-/6 Ht· /7 I-If-- I q /-/q -IQ ·,-1 q · 20 J+q . ),/ 1--1 q . ],2, /..J q ' 2-3 Hto · 2 '1 lt(O • 15 H/1 - 26 1-1- I I - :J.. 7

NI)..· 2S<'

H/2 · :zq H/s - ?O 1-1-/ ~ - ?I

/.II L( • ~ J

1-1/l-/ - ~ $ HI~ - ·p1 J.1./f -?> ilu · ?, J..1/(,, 17 ;.J11 - ~sr /.//1 . ,c, f..l IS- . t-/ tJ

I-/ ff - '-II t.J (4 - lf 2 ·1-1 I q • f,/ 7, HJO ·l/t.l 1120 -£;/5

Scientific Analytical Institute

Scientific Analytical Institute 4604 Dundas Dr. Greensboro, NC 27407

Phone: 336.292.3888 Fax: 336.292.3313 www.sailab.com /ab@sailab.com

Description/Location ov--:;c. .. 045

I (')L./~ I o:iei

0 0 11 FJ'l'e. o rqc F/Y1t; - 1/,1 /I'""" y'

I - (!)L/S , I - o? I I ... () 2'

J - N,1//""" Flo~, L-evrl,•11<, Cc,n(Pc,,,,cJ - "O '-I 5

J

11 Vh,'lt C'flveh,1-f~- ll,ll1v+-1 -JI - (;) :i. 6

V1/I P/J.Od - C)lf(,

- O't3 2t..t'' KAt1d()'/V/ D,'i-or C-t-1'/1'11r., T,h - oLf, I

- 0.26 Yellov DvcT !11t-sh'c ~ Ol/6

J,, ~

1,.,'1,'./e (,1-c.,/1<1'114 "' .21.IJ Cc1;11 -N.I' J, , J,, l2"r,FF t.,,J,,'/t_ VFT~ O?O ~11d ld'lfl' , R eJ Ff'l'c > -Jr1 P - 0:2., \L - o~,A

Gr /.1 v Dv(T /110 7 ·/.,'c - (J2 { ., , L,. ~

12 ,, oFF v>,/1-r VPT - o 11 \i . ~

'-/ r, T11-11 (oc.,f' h ,15-('. - 0 'JI \I,, ~

Lah Use Only LabOrderID: _____ ____.c

Client Code: __ 1_,~ __ -___ _

Volume/Area Comments

/>,11 '11 let/

Page ~ of~

APPENDIX D

LEAD BASED PAINT ANALYTICAL LABORATORY RESULTS

Analysis for Lead Concentration in Paint Chips by Flame Atomic Absorption Spectroscopy

EPA SW-846 3050B/6010C/7000B

Lab Order ID:Attn: 10067753Customer: Terracon 5463 W Waters Ave Suite 830 Tampa, FL 33634-1253

Analysis:

Date Received:

Karl Kologiski

PBP

11/07/2024

Project: J. Haley VA MRI Renovation Date Reported: 11/14/2024

Sample ID

Lab Sample ID

Description

Lab Notes

Concentration (ppm)

Concentration (% by weight)

Mass (g)

Reporting Limit (ppm)

X1

10067753_0001

Gray paint - metal door frame -

<36 <0.0036%360.1114

X2

10067753_0002

Beige paint - DW - 26A <39 <0.0039%390.1019

X3

10067753_0003

White paint - DW - 045 <61 <0.0061%610.0659

X4

10067753_0004

Blue paint DW - 030 <49 <0.0049%490.0811

X5

10067753_0005

White paint - metal door frame -

<38 <0.0038%380.1061

X6

10067753_0006

White-Blue paint DW - 031 <54 <0.0054%540.0736

Disclaimer: Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical Institute participates in the AIHA ELPAT program. ELPAT Laboratory ID: 173190. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. Analytical uncertainty available upon request. The quality control samples run with the samples in this report have passed all EPA required specifications unless otherwise noted. RL: (Report Limit for an undiluted 50ml sample is 4µg Total Pb). All sample dried before preparation and analysis.

Matthew Caffey (6)

Page 1 of 1L-F-021 r17 2/13/2027 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

Lab use only Lab Order ID:

Scientific Analytical Institute 4604 Dundas Dr. Greensboro, NC 27407 Phone: 336.292.3888 Fax: 336.292.3313 Client Code: ______ _ www.sailab.com lab@sailab.com

Contact Information Billin2/Invoice Information Company Name: Terracon Consultants Company: same

Address: 5463 W

• Waters Avenue , Ste. 8 30 Address:

Tampa, ., FL 33634

Contact:

Contact: Karl Kologiski Phone 0:

Phone 0: 727-470-1104 Fax0:

Fax0: Email □:

Email □ : karl.kologiski@terracon.com PO Number: J.IL-(2l/ 7 2? 0 Turn Around Times Project Name/Number: J', HI} /e If VA t1 R r R Mo1mJ,,.,,,, 3 Hours □ 72 Hours □

6 Hours □ 96 Hours □

Lead Test Tvnes 12 Hours □ 120 Hours • Paint Chips by Flame AA IX] I Soil by Flame AA D I Other □ 24 Hours □ 144+ Hours □

Wipe by Flame AA □ I Air by Flame AA □ I 48 Hours □

Sample ID# Description/Location Volume/ Area Comments

X'l Gr11 '1 Pt1i11 T • /Vlei, I OctJr Fr,,"'t· O'IS x:i. f?e,,~ P1i11T- OW - ;;,A )( 1 lv.JJ./1e l"91nT - DV - Qi/5 - 'l'1 11/ve p,..,•,,r ov • rJ10

"-~ L,h,'/e ,7,,,.,,,,- Mrl11I f71K rr/l;ttt- 011 x, IJJ.;J( - 11111-t. ,,,,1 ... r ,-,v- n 3 I

I I

A-- . .a. . rh -'"V-,_-1.cu L.::'_J

Rejio,...t-pn n .___, Total Number of Samples _1 __ _

APPENDIX E

REPRESENTATIVE PHOTOGRAPHS

Limited Interior Pre-Renovation

James A Haley VA Hospital ■ Tampa, Florida

Facilities | Environmental | Geotechnical | Materials 1

Photo #1 Ha-H1, Lower Roof Core Photo #2 Ha-H2, Upper Roof Core

Photo #3 Ha-H3, Skipped, No Sample Photo #4 Ha-H4, 12” Gray Stone Pattern Vinyl Floor Tile

Photo #5 Ha-H5, Bamboo Flooring Photo #6 Ha-H6, 4” Black Covebase

Facilities | Environmental | Geotechnical | Materials 2

Photo #7 Ha-H7, 24” Wormhole Ceiling Tile Photo #8 Ha-H8, Drywall & Joint Compound

Photo #9 Ha-H9, Fireproofing Photo #10 Ha-H10, Floor Leveling Compound

Photo #11 Ha-H11, 4” White Covebase Photo #12 Ha-H12, Wallpaper

Facilities | Environmental | Geotechnical | Materials 3

Photo #13 Ha-H13, 24” Random Divot Ceiling Tile Photo #14 Ha-H14, Yellow Duct Mastic

Photo #15 Ha-H15, White Caulking Photo #16 Ha-16, 12” Off White Vinyl Floor Tile (2nd Layer)

Photo #17 Ha-H17, Red Firestop Putty Photo #18 Ha-H18, Gray Duct Mastic

Facilities | Environmental | Geotechnical | Materials 4

Photo #19 Ha-H19, 12” Off White Vinyl Floor Tile Photo #20 Ha-20, 4” Tan Cove Base

Photo #21 Paint Sample X1, Gray Paint Metal Door Frame

Photo #22 Paint Sample X2, Beight Paint Drywall

Photo #23 Paint Sample X3, White Paint Drywall Photo #24 Paint Sample X4, Blue Paint Drywall

Facilities | Environmental | Geotechnical | Materials 5

Photo #25 Paint Sample X5, White Paint Metal Door Frame

Photo #26 Paint Sample X6, White-Blue Paint Drywall

APPENDIX F

LICENSES AND CERTIFICATIONS

2024-12-09T15:14:52-0800
Agreement certified by Adobe Acrobat Sign

File details come from the government source that posted it. Updated .