516-CSI-142_Bay Pines_ED CT_ Drawings.pdf
PDF 19 MB Posted
- Attached to
- Z2DA--FY26: NRM (PROJ: 516-CSI-142) BB - Site Prep for Emergency Department CT Scanner Replacement
- Solicitation number
- 36C24826Q0004
About this file
These are construction documents for an AE Site Preparation project for a CT Scanner Replacement at the Department of Veterans Affairs Medical Center in Bay Pines, Florida. The project involves demolishing and replacing electrical, mechanical, plumbing, fire protection, and telecommunications systems in a CT scan room and adjacent spaces. The project number is 516-CSI-142, and the planned completion date is May 1, 2025.
The documents include detailed architectural, structural, electrical, mechanical, plumbing, fire protection, and telecommunications plans for the renovation. Key components include replacing electrical bus plugs and feeders, installing new HVAC terminal units, replacing medical gas and plumbing systems, updating fire alarm and telecommunications infrastructure, and preparing the space for a new CT scanner. The project is fully sprinklered and designed to meet various federal, state, and local building codes, with a focus on healthcare facility standards. The design was prepared by Above Group, Inc. for the VA's Office of Construction and Facilities Management.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24826Q0004 0005.pdf | ||
| WD-FL20260222 01-02-26.pdf | ||
| Guldmann_GH3_BayPines_VA_Submission_Package.pdf | ||
| 36C24826Q0004 0004.pdf | ||
| Base Offer Price Breakdown - 1 page.xlsx | XLSX spreadsheet | |
| 36C24826Q0004 0003.docx | DOCX document | |
| 516-CSI-142 - Bay Pines ED CT_ADD 1.pdf | ||
| 03 30 00-CAST-IN-PLACE CONCRETE.pdf | ||
| 01 45 29-TESTING LABORATORY SERVICES.pdf | ||
| 36C24826Q0004 0002.docx | DOCX document | |
| RFI_516-CSI-142 Pre-Bid.docx | DOCX document | |
| PAST AND PRESENT PERFORMANCE QUESTIONNAIRE.docx | DOCX document | |
| ED CT scanner site walk sign-in sheet 10-07-25.pdf | ||
| 36C24826Q0004 0001.docx | DOCX document | |
| 516-CSI-142_Bay Pines_ED CT_ Specs.pdf | ||
| VHA Infection Control Risk Assessment.pdf | ||
| 36C24826Q0004_1.docx | DOCX document | |
| EMR 1 page.pdf | ||
| WD-FL20250222 05-23-2025.pdf |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED
Department of Veterans Affairs Medical Center
ABOVE GROUP, INC.
MECHANICAL ELECTRICAL PLUMBING
305 EAST DRIVE, SUITE H
MELBOURNE, FL 32904
321.345.9026 P
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
VA Project No.
AG Project No.
Au to de sk
D oc s:
//V
AM
C
Ba y Pi ne s/
- B ay
P in es E
D C
T_ R
_M
EP
FA
FP
T.
rv t
5/ 1/
0:
:4
AM
GI001
VA COVER SHEET AE Site Prep for ED CT Replacement
BAY PINES VA
124034
05/01/2025 DTG WRH
100% CONSTRUCTION
DOCUMENTS
AE Site Prep for ED CT Replacement
VAMC - BAY PINES 10000 BAY PINES BLVD BAY PINES, FL 33744 PROJECT #: 516-CSI-142
516-CSI-142
SHEET LIST
SHEET NUMBER SHEET NAME
GENERAL
GI001 VA COVER SHEET
G100 CODE DATA
STRUCTURAL
S-001 GENERAL NOTES AND ABBREVIATIONS
SS101 FIRST FLOOR FRAMING PLAN
SS102 FIRST FLOOR INTERSTITIAL FRAMING PLAN
S-301 DETAILS AND SECTIONS
ARCHITECTURAL
A101 PLANS AND DETAILS
A401 INTERIOR FINISHES PLAN AND LEGEND
A601 DOOR SCHEDULE & DETAILS
FIRE ALARM
FA001 FIRE ALARM LEGENDS & SYMBOLS
FD101 FIRST FLOOR PLAN - FIRE ALARM - DEMOLITION
FA101 FIRST FLOOR PLAN - FIRE ALARM - NEW WORK
FA501 FIRE ALARM DETAILS
FIRE PROTECTION
FP001 FIRE PROTECTION LEGENDS & SYMBOLS
FX101 FIRST FLOOR PLAN - FIRE PROTECTION - DEMOLITION
FP101 FIRST FLOOR PLAN - FIRE PROTECTION - NEW WORK
FP501 FIRE PROTECTION DETAILS
PLUMBING
P-001 PLUMBING NOTES, LEGENDS, & SYMBOLS
PD101 FIRST FLOOR PLAN - GRAVITY PIPING - DEMOLITION
PD102 FIRST FLOOR PLAN - PRESSURE PIPING & MED GAS - DEMOLITION
PS101 FIRST FLOOR PLAN - GRAVITY PIPING - NEW WORK
PP101 FIRST FLOOR PLAN - PRESSURE PIPING & MED GAS - NEW WORK
P-501 PLUMBING DETAILS
P-801 PLUMBING SCHEDULES
MECHANICAL
M-001 MECHANICAL NOTES, LEGENDS, & SYMBOLS
MD101 FIRST FLOOR PLAN - HVAC - DEMOLITION
MD102 FIRST FLOOR PLAN - HVAC PIPING - DEMOLITION
MH101 FIRST FLOOR PLAN - HVAC - NEW WORK
MP101 FIRST FLOOR PLAN - HVAC PRESSURIZATION & PIPING - NEW WORK
M-501 MECHANICAL DETAILS
M-701 MECHANICAL CONTROLS
M-801 MECHANICAL SCHEDULES
ELECTRICAL
E-001 ELECTRICAL LEGENDS & SYMBOLS
E-002 ELECTRICAL GENERAL NOTES
ED101 FIRST FLOOR PLAN - LIGHTING - DEMOLITION
ED102 FIRST FLOOR PLAN - ELECTRICAL EQUIPMENT - DEMOLITION
EL101 FIRST FLOOR PLAN - LIGHTING - NEW WORK
EP101 FIRST FLOOR PLAN - ELECTRICAL EQUIPMENT - NEW WORK
E-401 ENLARGED CT ROOM PLAN
E-501 ELECTRICAL DETAILS
E-601 ELECTRICAL DIAGRAMS
TECHNOLOGY
T-001 TELECOM LEGEND, ABBREV & GENERAL NOTES
TD101 FIRST FLOOR PLAN - TELECOM - DEMOLITION
TN101 FIRST FLOOR PLAN - TELECOM NEW WORK
T-501 TELECOM – DETAILSPROJECT LOCATION © Google Maps
JPA
ARCHITECT
3131 NEWMARK DRIVE, SUITE 200
MIAMISBURG, OHIO 45342
937.461.3290 P
Revisions Date
PR
O
FES S I ON AL ENGI N
EE
R
L I CENSE
F LO R I D A
STATE OF
No. 100881
EL GLOVERNI
DA
EW
C
EW
C
EWC
EW
C
H O U R
FIR
E W A
LL
1 H O U R S M O K E W
A
LL
1 H O U R
FIR
E W A
LL
0.5mT
TECH
6'-7" x 9'-9"
DOCTOR
6'-7" x 9'-9"
TOILET
6'-8" x 8'-4"
WORK ROOM
15'-0" x 15'-2"
MRI
EQUIPMENT
ROOM
10'-2" x 18'-3"
HALL
28'-1" x 8'-0"
STRETCHER
10'-4" x 10'-2"
CONTROL
ROOM
10'-0" x 14'-4"MRI SCAN
ROOM
31'-6" x 17'-3"
(CLEAR)
(C
LE
AR
MRI SCAN ROOM
CONTROL ROOM
EQUIPMENT ROOM WAITING ROOM
WAITING ROOM
RECEPTION AREADRESSING ROOMDRESSING ROOMTOILET ROOMSTRETCHER ROOM
TOILET ROOM
(C
LE
AR
BREAK ROOM
213 SF
OFFICE
132 SF
OPERATORS
408 SF
COMM. CENTER
264 SF
H O
T
SE
AT
ENTRY
56 SF
1E-284
1E-285
1E-282
1E-283
1E-281
1E-280
EWC
UP
UP
SB1-10A
SB1-10C
SB1-10B
SB1-10
1E123 1E124 1E125 1E126 1E127 1E128 1E129
C1-71
1E166
C 1-
1E1621E1641E165 1E161 1E158 1E156 1E155
C1-70
C1-72
1E130 1E131
C1-70
1E152 1E151 1E149 1E147 1E1421E1431E145
1E140
1E132 1E133 1E134 1E135 1E136 1E137 1E138
C1-77
C 1-
C 1-
C1-75C1-73
C1-74
C1-72
SB1-9A
SB1-9C
SB1-9B
SB1-9
C1-72
C1-63 C1-65
C 1-
C 1-
C1-68
1E1851E1841E1831E1821E1801E1791E178
1E189
1E193 1E192 1E1911E1941E1951E1961E197
C1-66
1E177 1E176
C1-61
1E198
1E175
C1-64
1E190
1E186
1E167
1E168A
1E163
1E163
1E159
1E157 1E154
1E153 1E144A
1E187
1E188
SB1-8A
SB1-8C
SB1-8B
SB1-8
1E236
1E236I
1E236G
1E236D
1E236H
C1-46
C1-99
SB1-7A
SB1-7C
SB1-7B
SB1-7
C1-96
1E291
1E2931E2941E295
1E292
C1-97
1E301
1E300A
1E103
1E104
1E105
1E106
1E107
1E108
1E102
1E111 1E112 1E113
1E116
1E117B
1E117C1E117D1E117E
1E118 1E1191E120
1E117
1E117A
1E117F
1E121
1E122
XXX
1E236F 1E236E
1E236B
1E236A
1E109
1E109A
1E110C
1E110
1E110A
1E110 B
1E115
1E114
1E114A
1E101 1E100
1E123A
1E241
1E241C
1E240A
1E236J
1E236C
1E139
1E141
1E150
1E148
1E181
1E144
1E288
1E288A 1E288B
1E254A
1E255
1E253
1E254
C1-40
1E258
1E259
1E2571E256
1E260
1E261
1E262
1E253C
1E253A
1E253B
1E254B
1E144B
1D165 1D166
1D164
C 1-
1D161
1D162
1D163
1E286
1E286A
1E286B
1E286C
1E286D
C1-36
1E225C
1E224 1E231
1E234
1E228
1E233C
1E233B
1E233
1E233E
C1-37A
1E225
1E246
1E212
1E212A
1E226
1E212B
1E212C1E212D1E212E1E212F
1E212G
1E212H
1E212I
1E212J
1E214
1E2151E220
1E221
1E222A
1E222B
1E223B
1E223A
1E210E
1E233A
1E233D
1E2291E226A
1E225B 1E225A
1E227
C1-38
1E210D
1E232
1E233F 1E233G 1E233H
1E211
1E2171E218
1E213
1E216
C1-43
C1-44
C1-41
C1-42
C1-36A
C1-36B
C1-45
C1-45A
C1-46A
C1-37
C 1-
1E242A 1E242B 1E242C 1E242D 1E242E
C1-59
1E1991E203 1E202
1E205
C1-60
1E1741E169
1E241E
1E3
1E3 1J
1E3
MRI12MRI11MRI10MRI9MRI8
MRI1
MRI7
MRI5
MRI2
MRI4
MRI3
MRI6
1E249
1E248
1E247
1E248A
1E248B1E248C1E248D 1E289
1E292
1E295
1E296
1E297
1E297A 1E294
1E291
1E290 1E290
XXXXX
1E248E
1E293
1E238A
1E238
1E240
1E240D
1E240E
1E241E
1E241C
1E241 1E241A
1E241B
1E241D
1E240A 1E240B 1E240C
1E16
A
KE
Y
W
AT
C H
ER
"W X
"D
X
8" H
A-PHONE
A
A.5
B
B.2
C
4 5 5.2 6 6.2 7 8 98.8 10 119.7 12
A.4
A3
12.8
D
D.1
F.1
F
F.2
F.3
F.6
G
E
E.2
D.9
E.3
E.4
E.5
E.7
G
G.3
G.4
G.45
G.8
G.9
J
J.4
J.6
UP
SERVICE BAY #10
ELECTRIC POWER
FIRE ALARM
TELEPHONE
EXAM EXAM EXAM EXAM EXAM EXAM CONSULT.
EXAMEXAMEXAM EXAM EXAM EXAM CONSULT.
CONTROL
CONTROL
CONSULT. EXAM EXAM EXAM EXAMEXAMEXAM
CONSULT. EXAM EXAM EXAM EXAM EXAM EXAM
WAITING WAITING
STAFF WORKROOMSTAFF WORKROOM
UP
SERVICE BAY #9
ELECTRIC POWER
FIRE ALARM
TELEPHONE
STAFF WORKROOM
WAITINGWAITING
EXAMEXAMEXAMEXAMEXAMEXAMCONSULT.
EXAM EXAM EXAMEXAMEXAMEXAMCONSULT.
CONTROL
CONTROL
CONSULT.
CONSULT.
EXAM
EXAM
SOILED UTIL.
TOILET
CONSULTATION
CENTER
CENTER
& TREATMENT
MEDICATION
ENDOSCOPIC
M. TOILET
F. TOILET
URINE COLLECTION
STAFF TOILET
SOILED UTIL.
UP
SERVICE BAY #8
ELECTRIC POWER
FIRE ALARM
TELEPHONE
WAIT/DISPLAY
CONF. #2
VIEWING #1
P.E.R.C.
CONF. #1
H.A.C.
EMERGENCY
ENTRANCE CANOPY
RAMP DN
RAMP DN
SERVICE BAY # 7
ELECTRIC POWER
FIRE ALARM
TELEPHONE
SPD
LOADING
PLATFORM #2
CHIEF
MED. GASMED. GAS
H.A.C.
FLAMMABLE
STORAGE
PLATFORM #3
LOADING
SCANNING
OFFICE
BREAK
OFFICE
STORAGE
OFFICE
HAC
SUPRV. OFF.
PTS
STAFF
EXAM EXAM EXAM
SOFT PROSTETICS
STORAGE
CONFERENCE/BREAK
INPUT
VAULT
SUPRV.
CLNC. SUPRV.CONSULT
PHARMACY
FILES
CAGE
CONSULT
CONSULT
WAITING
P
TS
PTS
VIEWING #2 VIEWING #3
C.D.
STACKS
OPEN WORK AREA
INTERVIEW
CASHIER
PATIENT FUNDS/TRAVEL
OFFICEO
X Y G
EN
TOILET
RECEPT.
PHOTO I.D.
WAITING
VESTIBULE
SOC. WORKER
AC&P
AC&P
EXAM
SUPPORT
TRANSFER CLERK
INFO
COPIER
EXAM
EXAM
office office clerk/waiting
GENERAL STORAGE
OFFICE
P
TS
D.R.
LOUNGE
DR. WORK
DR. SLEEP
PSYCH OFFICE
OFFICE
PSYCH OFFICEHAC
OFFICE
OFFICE
OFFICE
CHANGE
LOCKERS
TOILET
DR. BATH
P
TS
MOD B
MOD DMOD C
MOD A
VENDING
H.A.C.
F. TOILET
LOCKERS
LOCKERS
M. TOILET
TOILET
POLICE
SOILED
PHARMACY
OBSERVE
OBSERVE
NURSE'S STATION
PSYCH
TUBE ROOM
PNEUMATIC
ER EXAM
RECEPTION
ER EXAM
ISOLATIONISOLATIONISOLATION
ER EXAM
ER EXAM
ER EXAM
ER EXAM
DRESS
OBSERVE
TRIAGE
TRIAGE
TRAUMA 2
TRAUMA 1
OBSERVE
TOILET
AOD
TOILET TOILET
SOILED
HAC
SOILED
RAD EXAM RM
TOILET
PSYCH PSYCH PSYCH
TOILET
507 SF
50 SF
TOILET
OFFICE
OFFICE OFFICE OFFICE
STAFF WORKROOM
EXAMEXAM EXAM
EXAMEXAM
EQUIPMENT ROOM
VIEW ROOM/
CONFERENCE ROOM
DARKROOM
RECEPTION
CLOSETLAV.DRESS.GOWN/WAIT.DRESS.
EXAM ROOM
CONTROL
CORRIDOR
P
TS
E.R.
PRIMARY CARE
NURSE MGR.
NURSE MGR.
WAITING
COPIER
OFFICE OFFICE
OFFICE
OFFICE OFFICEOFFICE
OFFICE
W A
ITIN
G
12'-0" 15'-113__16" 11'-6" 8'
1H CHL#13
1H CHL#13
1H CHL#7
1H CHL#13
1H CHL#13 1H CHL#13
1H CHL#7
1H CHL#7
1H CHL#7
1H CHL#7
1H CHL#7
1H CHL#7
1H CHL#7
1H C
H L#7
1H C
H L#7
1H C
H L#7
1H C
H L#7
1H C
H L#7
#14
#14
#39
#39
#39
#39
#39
#19
#39
#37
#37
#19 #19
#19
#19
#37
#37 #37
#37
#41 #41
#41
#41#41
#41
#40 #42
#40
#38
#21
#21
#39
#39
0-HR Smoke Partition - [OBC 710] / NFPA 101-8.4
1-HR Smoke Barrier - [OBC 709] / NFPA 101-8.5
1-HR Fire Barrier - [OBC 706] / NFPA 101-8.3
2-HR Fire Barrier - [OBC 706] / NFPA 101-8.3
Exit
Existing Wall to Remain
New Wall
Exit Access Travel Path
CODE LEGEND
CONTROL
ROOM
1E210C
CLOSET
1E210
CT SCAN
ROOM
1E210B
153' EXIT ACCESS TRAVEL DISTANCE
200' ALLOWED
Code: NFPA 101 Life Safety Code (2024 Edition) Construction Type: Type I (442) Use Group: Health Care Occupancy Area of Work: Emergency Department CT Suite, Ground Floor Protection: Fully Suppressed
Chapter - 6 Classification of Occupancy and Hazard of Content
6.1.11 - Health Care Occupancy
6.2.2.1 -Hazard classification = Ordinary
Chapter 7 - Means of Egress Table 7.3.1.2, Occupant Load Factor:
Business Use: 150 sf / person Storage Use (In other than storage and mercantile occupancies): 500 sf / person
Chapter 8 - Features of Fire Protection:
Chapter 9 - Building Service and Fire Protection Equipment
9.9 - Portable fire extinguishers shall be selected, installed, inspected, and maintained per NFPA 10.
CODE NOTES
Chapter 10 – Interior Finish, Contents, and Furnishings Table A.10.2.2 Interior Finish Classification Limitations for Health Care (Existing)
Exit Access Corridors: Class A or B.
Other Spaces: Class A or B.
10.2.3.3 – Wall and Ceiling – Classifications characteristics:
(1) Class A: Flame spread: 0-25; Smoke dev.: 0-450.
(2) Class B: Flame spread: 26-75; Smoke dev.: 0-450.
(3) Class C: Flame spread: 76-200; Smoke dev.: 0-450.
(4) Existing interior finish exempt from smoke dev. criteria.
10.2.7.2 – Floor finish other than carpet: Min. Rad flux: .1 W/ cm².
10.2.8.1 – Wall and Ceiling finishes, where sprinkled:
Class C permitted in any location where Class B is req’d.
Class B permitted in any location where Class A is req’d.
10.2.8.2 – Floor finishes, where sprinkled:
Class II permitted in any location where Class I is req’d.
Provisions of 10.2.7.2 shall apply where Class II is req’d.
Chapter 18 - New Health Care Occupancies
18.1.1.1.4 - The area of work is an existing hospital and therefore falls under Chapter 18.
Table 18.1.6.1 - Construction Type Limitations: Type I (442), sprinklered, no story limitations.
18.1.7 - Occupant Load per Table 7.3.1.2.
18.2.5.3 - Common path of travel shall not exceed 100’.
18.2.5.6.5 - Rooms within suites shall not be required to an exit access door leading directly to an exit access corridor.
18.2.5.7.3.1 - Patient Care Non-sleeping suites
(a) Suites shall have exit access to a corridor complying with 18.3.6 or to a horizontal exit, directly from the suites.
(b) Suites of more than 2500 SF shall have not less than two exit access doors remotely located from each other.
(c) For Suites requiring two exit access doors, one of the exit access doors, on of the access doors shall be permitted to be to one of the following:
(1) An exit stair
(2) An exit passageway
(3) An exit door to the exterior
(4) Another suite, provided that the separation between the suites complies with the corridor requirements of 18.3.6.2 through 18.3.6.5.
18.2.5.7.3.3 - Patient Care Non-sleeping suite travel distance
(a) Travel distance within a non-sleeping suite to an exit access corridor door, or a horizontal exit door and from the suite shall not exceed 100ft.
(b) Travel distance between any point in a non-sleeping suite and an exit shall not exceed 200ft.
18.2.6.2.1 - Travel distance from any point in a room to exit shall not exceed 200’.
18.3.2.1.3 - Storage rooms (clean supply and clean linen) larger than 50 SF but not exceeding 100 SF shall be protected by smoke partitions.
18.3.4.1 - Health care occupancies shall be provided with a fire alarm system IAW Section 9.6.
18.3.5.1 - Building containing health care occupancies shall be protected throughout by approved, supervised automatic sprinkler systems IAW Section 9.7.
18.3.5.12 - Portable fire extinguishers shall be provided IAW Section 9.9.
18.3.6.2.2 - No fire resistance rating is required for corridor walls.
18.3.6.2.3 - Corridor walls shall form a barrier to limit the transfer of smoke but are not required to be smoke barriers or smoke partitions.
18.3.6.3.1 - Corridor doors shall be doors constructed to resist the passage of smoke.
18.3.7.3 - Smoke barrier shall be constructed IAW Section 8.5 and shall have 1 hour fire resistive rating.
18.3.7.6 - Doors in smoke barriers shall have 20 minute fire resistive rating.
18.3.7.5.1 - Not less than 30 net SF of accumulation space per resident/patient shall be provided in smoke compartment on either side of smoke partition. - The doors shall not be required to swing in the direction of egress travel.
Chapter 43 - Building Rehabilitation
43.1.2.1 - Any building undergoing repair, renovation, modification, or reconstruction shall comply with both of the following:
(1) Req'ts of the applicable existing occupancy chapters (Chapter 39).
(2) Req'ts of the applicable section of this Chapter (Sections 43.4 and 43.5).
43.4.1 - Renovations & General Req'ts: all new work shall comply with the req'ts of other sections of this Code applicable to existing construction.
43.5.1 - Modifications & General Req'ts: all new work shall comply with the req'ts of other sections of this Code applicable to new construction.
S T
AT
E
OF FLOR
I D A
R
EGISTERED ARCH
IT
EC
T
J A
SO
N H. ROS
S
AR101907
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
ARCHITECT/ENGINEER OF RECORD
www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
4/
/2
8:
:0
AM
B100 ED Room 1E210 CT Replacement
5/1/2025
CODE DATA
G100
JWJC
516-CSI-142
VAMC, Bay Pines, FL
B100
100% CONSTRUCTION
DOCUMENTS
24127.00
Scale: 1/8" = 1'-0"1 Code Plan N N.T.S.Scale:
KEYPLAN 1ST FLOOR
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523 Revisions Date
RIGGING, HOISTING AND SCAFFOLDING REQUIREMENTS:
1. THE CONTRACTOR SHALL PREPARE AND SUBMIT TO THE COR AND
A/E OF RECORD FOR REVIEW A SITE SPECIFIC RIGGING AND HOISTING
PLAN FOR ALL MAJOR EQUIPMENT THAT WILL BE TRANSPORTED
THROUGH OR HOISTED FROM THE BUILDING. THE PLAN SHALL
INCLUDE THE SEQUENCE OF ERECTION, THE DESCRIPTION OF THE
RIGGING, HOISTING AND TRANSPORTATION EQUIPMENT AND THE SITE
PREPARATIONS THAT WILL BE NEEDED TO COMPLETE THE
INSTALLATION.
2. THE CONTRACTOR SHALL PREPARE AND SUBMIT TO THE COR AND
A/E OF RECORD FOR REVIEW A SITE SPECIFIC PLAN FOR ALL
SCAFFOLDING THAT WILL BE INSTALLED ON FRAMED FLOORS AND
ROOFS.
3. THE PROPOSED RIGGING, HOISTING OR SCAFFOLDING PLAN SHALL BE
REVIEWED BY A PROFESSIONAL ENGINEER REGISTERED IN THE
LOCAL JURISDICTION. THE PROFESSIONAL ENGINEER SHALL PROVIDE
A SIGNED AND SEALED CERTIFICATION STATING THAT THE
PROPOSED PLAN WILL NOT DAMAGE OR OVERSTRESS THE
STRUCTURE. SHORING AND SCAFFOLDING SHALL COMPLY WITH
OSHA REGULATIONS.
4. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSURE THAT THE
LOADS SUPERIMPOSED BY THE RIGGING, HOISTING OR SCAFFOLDING
SYSTEMS WILL NOT EXCEED THE FOLLOWING LOADS:
FRAMED FLOORS = 80 PSF
ROOFS = 30 PSF
5. THE CONTRACTOR SHALL PROVIDE PROTECTION FOR ALL FINISHES,
UTILITIES, AND STRUCTURE. CONTRACTOR SHALL REPLACE AT NO
COST TO THE VA ANY FINISHES DAMAGED DURING CONSTRUCTION.
CONTRACTOR SHALL SUBMIT A REPAIR DRAWING TO A/E OF RECORD
AND VA COR FOR REVIEW PRIOR TO PERFORMING ANY REPAIRS. ALL
REPAIRS SHALL BE COMPLETED AT NO COST TO THE GOVERNMENT.
GENERAL:
1. CONTRACTOR IS SOLELY RESPONSIBLE FOR MEANS AND METHODS
DURING THE COURSE OF THE WORK. DO NOT DAMAGE OR
ENDANGER THE STRUCTURAL INTEGRITY OF THE WORK.
2. LOADS GREATER THAN THE DESIGN LIVE LOADS SHALL NOT BE
PLACED ON THE STRUCTURE.
3. NOTIFY COR IN CASE OF DISCREPANCIES BETWEEN DRAWINGS,
THESE NOTES, AND PROJECT MANUAL BEFORE PROCEEDING WITH
THE WORK.
4. USE ARCHITECTURAL DRAWINGS AND DRAWINGS OF OTHER TRADES
IN CONJUNCTION WITH THE STRUCTURAL DRAWINGS TO PROPERLY
PERFORM THE WORK.
5. IF CONDITIONS DISCLOSED DURING EXCAVATION REVEAL
UNFORESEEN CONDITIONS, PROMPTLY REQUEST DIRECTION IN AN
RFI FORM FROM THE COR AND A/E OF RECORD BEFORE
PROCEEDING.
6. CONTRACTOR IS RESPONSIBLE FOR COORDINATING BETWEEN
TRADES.
7. DO NOT SCALE DRAWINGS.
8. SECTIONS AND DETAILS SHOWN, WHILE DRAWN FOR SPECIFIC
LOCATIONS, ARE INTENDED TO ESTABLISH THE GENERAL TYPES OF
DETAILS THAT WILL APPLY TO OTHER LOCATIONS.
9. THE COR AND A/E OF RECORD'S REVIEW OF A SUBMITTAL SHALL NOT
RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITY TO FOLLOW
THE INTENT OF THE CONTRACT DRAWINGS.
10. REPRODUCTION OF CONTRACT DOCUMENTS WILL NOT BE ACCEPTED
AS SHOP DRAWINGS.
GENERAL NOTES
DELEGATED DESIGN ITEMS:
1. EMPLOY OR RETAIN A LICENSED PROFESSIONAL ENGINEER IN THE
PROJECT JURISDICTION TO DESIGN AND DETAIL THE FOLLOWING
PERFORMANCE SPECIFIED STRUCTURAL COMPONENTS:
A. UNISTRUT SUPPORTS
2. SEE INDIVIDUAL MATERIAL SECTIONS FOR ADDITIONAL
REQUIREMENTS.
3. SHOP DRAWINGS AND CALCULATIONS SHALL BE SIGNED AND SEALED
BY A PROFESSIONAL ENGINEER REGISTERED IN THE LOCAL
JURISDICTION AND SUBMITTED FOR REVIEW.
EXISTING CONSTRUCTION:
1. ABOVE GROUP, INC. HAS PREPARED THESE PLANS BASED ON A
LIMITED AMOUNT OF FIELD EXPLORATION AND ON THE STRUCTURAL
INFORMATION SHOWN IN DRAWINGS PREPARED BY SHS ASSOCIATES
DATED JULY 2, 1979. THE EXISTING MEMBER SIZES ARE NOTED (E)
AND ARE SHOWN IN THE PLANS. THE CONTRACTOR SHALL FIELD
VERIFY THAT THE EXISTING MEMBERS SHOWN IN THE PLANS MATCH
EXISTING AS BUILT CONDITIONS PRIOR TO PREPARING SHOP
DRAWINGS. IF THE AS BUILT CONDITIONS DO NOT CONFORM TO THE
INFORMATION SHOWN IN THE PLANS, OR IF ANY STRUCTURAL
MEMBER IS FOUND TO BE IN POOR CONDITION, THE CONTRACTOR
SHALL INFORM THE COR OF THE ACTUAL SIZES AND/OR CONDITION.
RE-DESIGN AND ADDITIONAL FRAMING MAY BE REQUIRED IN THAT
CASE.
2. ALL NEW PENETRATIONS THROUGH THE EXISTING FRAMED FLOORS,
ROOFS AND WALLS SHALL BE ACCURATELY LOCATED BY THE
CONTRACTOR. THE CONTRACTOR SHALL PREPARE SHOP DRAWINGS
SHOWING ALL PROPOSED OPENINGS AND SHALL SUBMIT THESE FOR
REVIEW AND APPROVAL PRIOR TO CUTTING ANY OPENINGS.
3. NEW PENETRATIONS SHOWN IN THE STRUCTURAL DRAWINGS ARE
PRINCIPAL OPENINGS. THE CONTRACTOR SHALL COORDINATE WITH
THE ARCHITECTURAL, MEP AND TELECOMMUNICATION DRAWINGS
FOR ALL PENETRATIONS.
4. ALL NEW PIPE AND DUCT PENETRATIONS SHALL BE LOCATED BY THE
CONTRACTOR TO AVOID CONCRETE SLAB REINFORCEMENT AND
SUPPORTING MEMBERS UNDER THE SLAB OR ROOF. IF CUTTING OF
ANY REINFORCEMENT OR EXISTING SUPPORTING MEMBER CANNOT
BE AVOIDED, THEN PRIOR TO CUTTING, THE CONTRACTOR SHALL
PREPARE A DETAILED DRAWING SHOWING THE PROPOSED
PENETRATION AND ALL THE AFFECTED REINFORCEMENT AND
SUPPORTING MEMBERS AND SHALL SUBMIT THE DRAWING TO THE
COR FOR REVIEW AND APPROVAL. THE CONTRACTOR SHALL NOT
CUT ANY REINFORCEMENT OR MEMBER WITHOUT THE PRIOR
APPROVAL OF ENGINEER.
*WARNING* PRECAST CONCRETE JOISTS HAVE PRESTRESSED
STRANDS. SERIOUS HAZARDS AND DAMAGE CAN RESULT FROM A
STRAND BEING CUT.
DESIGN CODES:
VA DESIGN MANUAL STRUCTURAL:
PG-18-10 (OCTOBER 1, 2022 REV JULY 1, 2023)
VA SEISMIC DESIGN REQUIREMENTS:
H18-8 (JULY 1, 2023 REV NOVEMBER 1, 2024)
INTERNATIONAL BUILDING CODE:
IBC 2024
INTERNATIONAL EXISTING BUILDING CODE:
IEBC 2024
MINIMUM BUILDING DESIGN LOADS AND ASSOCIATED CRITERIA FOR
BUILDINGS AND OTHER STRUCTURES:
ASCE 7-22
BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE:
ACI 318-19
SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS:
AISC 14TH EDITION 360-22
SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS:
AISC 341-22
DESIGN CRITERIA:
RISK CATEGORY IV
FLOOR LIVE LOADS:
ADMINISTRATIVE SERVICES, OFFICE AREAS 80 PSF
CLINICAL AND SUPPORT SERVICES 80 PSF
CORRIDOR 100 PSF
LIGHT STORAGE 125 PSF
SUPPLY SERVICE STORAGE 150 PSF
MECHANICAL ROOMS 150 PSF
PARTITIONS 20 PSF
(NOT REQUIRED WITH LIVE LOAD OF 100 PSF OR HIGHER)
EQUIPMENT LOADS AND LAYOUT BASED ON EQUIPMENT DRAWING FOR
REVOLUTION APEX ELITE POWER PRO BY GE DATED 3/31/2025.
SEISMIC DESIGN DATA:
EQUIVALENT LATERAL FORCE PROCEDURE
SOIL SITE CLASS ASSUMED 'D'
SEISMIC DESIGN CATEGORY A
SEISMIC IMPORTANCE FACTOR, Ie = 1.5
MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:
Ss = 0.063g S1 = 0.029g
DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:
Sds = 0.056g Sd1 = 0.041g
POST-INSTALLED ANCHORS:
1. DRILL AND INSTALL POST-INSTALLED ANCHORS ACCORDING TO
MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS AND PER
MANUFACTURER'S ON-SITE TRAINING.
2. ALL INSTALLERS OF POST-INSTALLED ANCHORS SHALL BE ACI/CRSI
ADHESIVE ANCHOR INSTALLER CERTIFIED. SUBMIT CERTIFICATES FOR
RECORD.
3. ALL POST-INSTALLED ANCHORS SHALL MEET ICC-ES COMPLIANCE
FOR EACH TYPE OF APPLICATION.
4. SUBMIT PRODUCT INFORMATION AND ICC-ES EVALUATION REPORT
FOR EACH ANCHOR.
5. ALL ANCHOR DESIGNS ARE FOR INSTALLATION IN THE FOLLOWING
CONDITIONS, UNLESS NOTED OTHERWISE. WRITTEN APPROVAL MUST
BE RECEIVED FROM ENGINEER PRIOR TO INSTALLATION OF ADHESIVE
ANCHORS IN ALTERNATE CONDITIONS.
A. DRY CONCRETE, UNLESS NOTED OTHERWISE.
B. CONCRETE TEMPERATURE AT TIME OF INSTALLATION MUST BE
BETWEEN 14° F AND 104° F. SEE MANUFACTURER’S PRINTED
INSTALLATION INSTRUCTION FOR ADHESIVE GEL AND CURE
TIMES.
C. ANCHOR HOLES TO BE HAMMER DRILLED.
D. ANCHOR HOLES TO BE CLEANED PER MANUFACTURER’S PRINTED
INSTALLATION INSTRUCTIONS PRIOR TO ADHESIVE INJECTION.
E. ANCHORS/POST-INSTALLED REINFORCING SHALL NOT BE LOADED
UNTIL CONCRETE OR GROUT HAS BEEN ALLOWED TO CURE FOR
21 DAYS AND/OR HAS ATTAINED 70% OF ITS DESIGN STRENGTH.
6. ALL POST-INSTALLED ANCHORS IN CONCRETE SHALL BE SUITED FOR
USE IN SEISMIC AND CRACKED CONCRETE APPLICATIONS.
7. ADHESIVE ANCHORS IN CONCRETE SHALL BE HILTI HIT HY-200, OR
APPROVED EQUAL.
8. EXPANSION ANCHORS IN CONCRETE SHALL BE HILTI KWIK BOLT TZ2,
OR APPROVED EQUAL.
9. PROVIDE STANDARD AISC HOLES IN ALL STEEL MEMBERS RECEIVING
POST-INSTALLED ANCHORS. IF OVERSIZED HOLES ARE PROVIDED TO
EASE INSTALLATION OF THE ANCHORS, A PLATE WASHER (1/4"X2"X2")
WITH AN AISC STANDARD HOLE SHALL BE INSTALLED AND 1/8" FILLET
WELDED (ALL AROUND) TO THE MEMBER.
10. ALL ANCHORS AND REINFORCING SHALL BE INSTALLED IN
ACCORDANCE WITH THE SPACING AND EDGE DISTANCES SHOWN IN
THE DRAWINGS. THE CONTRACTOR SHALL INFORM THE COR PRIOR
TO INSTALLING THE ANCHORS IF THE SPACING AND EDGE DISTANCES
SHOWN IN THE DRAWINGS CANNOT BE ACHIEVED. IF THIS IS THE
CASE, RE-DESIGN MIGHT BE REQUIRED AND THE ANCHORS SHOULD
NOT BE INSTALLED UNTIL APPROVAL HAS BEEN PROVIDED BY THE
ENGINEER.
11. DO NOT CUT ANY REINFORCING UNLESS IT IS SPECIFICALLY
INDICATED IN THE DRAWINGS OR IS APPROVED BY THE ENGINEER.
12. POST INSTALLED ANCHORS AND REINFORCING SHALL ONLY BE USED
WHERE SPECIFIED IN THE CONTRACT DRAWINGS. THE CONTRACTOR
SHALL OBTAIN APPROVAL FROM THE ENGINEER PRIOR TO INSTALLING
POST INSTALLED ANCHORS WHERE CAST-IN PLACE ANCHORS ARE
MISSING, MISPLACED OR DAMAGED.
13. *WARNING* PRECAST CONCRETE JOISTS HAVE PRESTRESSED
STRANDS. SERIOUS HAZARDS AND DAMAGE CAN RESULT FROM A
STRAND BEING CUT. ATTACHING TO THE UNDERSIDE OF CONCRETE
JOISTS IS NOT PERMITTED AND SLAB SHALL BE GPR SCANNED TO
AVOID CUTTING STRANDS PRIOR TO INSTALLATION OF ANY POST
INSTALLED BOLTS AND ANCHORS.
AB ANCHOR BOLT
ABV ABOVE
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADH ADHESIVE
ADJ ADJACENT, ADJUSTMENT
A/E ARCHITECT/ENGINEER
AESS ARCHITECTURALLY EXPOSED STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AGG AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ALT ALTERNATE
ANCH ANCHOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APA ENGINEERED WOOD ASSOCIATION
APRX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECT(URAL)
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASD ALLOWABLE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWC AMERICAN WOOD COUNCIL
AWPA AMERICAN WOOD PROTECTION AGENCY
AWS AMERICAN WELDING SOCIETY
AVG AVERAGE
B BOTTOM
B/ BOTTOM OF
B-B BACK-TO-BACK
BAL BALANCE
BEL BELOW
BF BRACED FRAME
BLDG BUILDING
BLK(G) BLOCK(ING)
BM BEAM
BOT BOTTOM
BP BASE PLATE, BEARING PLATE
BR BRACE(ING)
BRDG BRIDGING
BRG BEARING
BRK BRICK
BRKT BRACKET
BS BOTH SIDES
BSMT BASEMENT
BT BENT
BTWN BETWEEN
BYD BEYOND
C STEEL CHANNEL
CAIS CAISSON
CALC CALCULATION
CANT CANTILEVER
CAP CAPACITY
C-C CENTER-TO-CENTER
CE CONCRETE ENCASED
CFM COLD FORMED METAL
CHAM CHAMFER
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL/CONTRACTION JOINT
CL CENTERLINE, COLUMN LINE
CLG CEILING
CLR CLEAR
CM CONSTRUCTION MANAGER
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMB COMBINED
COMP COMPOSITE
CONC CONCRETE
COND CONDITION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COV COVER
CP CAP PLATE
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CSK COUNTERSUNK
CTR CENTER(ED)
CY CUBIC YARD
CYL CYLINDER
d PENNY (AS IN NAIL, Id)
DBL DOUBLE
DD DESIGN DEVELOPMENT
DEF DEFLECTION
DEG DEGREE
DEMO DEMOLITION/DEMOLISH
DEPR DEPRESS(ED)/DEPRESSION
DET(S) DETAIL(S)
DEV DEVELOP/DEVELOPMENT
DIA DIAMETER
DIAG DIAGONAL
DIM(S) DIMENSION(S)
DIR DIRECTION
DK DECK
DL DEAD LOAD
DN DOWN
do DITTO
DP DEEP
DWG(S) DRAWING(S)
DWL DOWEL
(E) EXISTING
E EAST
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT/EMBEDDED
ENGR ENGINEER
EO EDGE OF
EOD EDGE OF DECK
EOM EDGE OF MASONRY
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
STRUCTURAL ABBREVIATIONS
ES EACH SIDE
EXCAV EXCAVATE/EXCAVATION
EXP EXPANSION
EXT EXTERIOR
EXIST EXISTING
EW EACH WAY
F/ FACE OF
FAB FABRICATE
FB FLAT BAR
FBO FURNISHED BY OTHERS
FDN FOUNDATION
FFE FINISHED FLOOR ELEVATION
FIN FINISH(ED)
FL(R) FLOOR
FLG FLANGE
FND FOUNDATION
FO FACE OF
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FP FIREPROOFING
FRMG FRAMING
FRP FIBER-REINFORCED POLYMER
FRT FIRE RETARDANT TREATED
FS FAR SIDE
FT FEET
FTG FOOTING
FUT FUTURE
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZE(D)
GB GRADE BEAM
GC GENERAL CONTRACTOR
GLB GLUE LAMINATED BEAM
GR GRADE
GYP GYPSUM
HD HEAVY DUTY
HDR HEADER
HEF HORIZONTAL EACH FACE
HGR HANGER
HI HIGH
HIF HORIZONTAL INSIDE FACE
HK HOOK(ED)
HOF HORIZONTAL OUTSIDE FACE
HORIZ HORIZONTAL
HP HIGH POINT
HS HIGH STRENGTH
HT HEIGHT
H&V HORIZONTAL & VERTICAL
HVAC HEATING, VENTILATING & AIR CONDITIONING
IBC INTERNATIONAL BUILDING COUNCIL
ICC INTERNATIONAL CODE COUNCIL
ID INSIDE DIAMETER
IF INSIDE FACE
IFC ISSUE FOR CONSTRUCTION
IN INCH
INCL INCLUDE(D)(ING)
INFO INFORMATION
INSTL INSTALL/INSTALLATION
INSUL INSULATION
INT INTERIOR
INV INVERT(ED)
JST(S) JOIST(S)
JT JOINT
k KIP (THOUSAND POUNDS)
KB KNEE BRACE
KSI KIPS PER SQUARE INCH
LB, # POUND
LDGR LEDGER (BOARD)
LEN LENGTH
LG LONG
LL LIVE LOAD
LLBB LONG LEGS BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOCN LOCATION
LONGIT LONGITUDINAL
LP LOW POINT
LRFD LOAD AND RESISTANCE FACTOR DESIGN
LSL LONG SLOTTED HOLE,
LAMINATED STRAND LUMBER
LVL LAMINATED VENEER LUMBER
LW LONG WAY
LWC LIGHT WEIGHT CONCRETE
M MOMENT
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL & PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MONO MONOLITHIC
MPH MILES PER HOUR
MTL METAL
NA NOT APPLICABLE
NDS NATIONAL DESIGN SPECIFICATION FOR WOOD
CONSTRUCTION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
O-O OUT-TO-OUT
OPG OPENING
OPP OPPOSITE
OSB ORIENTED STRAND BOARD
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
OSL OUTSTANDING LEG,
ORIENTED STRAND LUMBER
OVS OVERSIZED HOLE
PAF POWDER ACTUATED FASTENER
PC PRECAST CONCRETE, PIECE
PCF POUNDS PER CUBIC FOOT
PED PEDESTAL
PERP PERPENDICULAR
PREFAB PREFABRICATE(D)
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PMF PREMOLDED FILLER
PROJ PROJECT(ION)
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT PRESERVATIVE-TREATED,
POST-TENSIONED
PVC POLYVINYL CHLORIDE
QTY QUANTITY
R RADIUS
RCMU REINFORCED CONCRETE MASONRY UNIT
RCSC RESEARCH COUNCIL ON STRUCTURAL
CONNECTIONS
RD ROOF DRAIN
RDK ROOF DECK
REF REFERENCE
REINF REINFORCE(D)/REINFORCEMENT
REQ(D) REQUIRE(D)
RET RETAINING
REV REVISE(D)/REVISION
RO ROUGH OPENING
RQMT(S) REQUIREMENT(S)
RTU ROOFTOP UNIT
RXN REACTION
SAN SANITARY
SC SLIP-CRITICAL (CONNECTION)
SCHED SCHEDULE
SECT SECTION
SD STORM DRAIN
SDI STEEL DECK INSTITUTE
SF SQUARE FOOT
SHRG SHORING
SHTHG SHEATHING
SIM SIMILAR
SL SLOPE(D)
SLBB SHORT LEGS BACK TO BACK
SLV SLEEVE
SOD SLAB ON DECK
SOG SLAB ON GRADE
SPA SPACE(S)/SPACING
SPEC(S) SPECIFICATION(S)
SQ SQUARE
SS STAINLESS STEEL
SSL SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STRUC STRUCTURAL
SUPT SUPPORT
SW SHORT WAY, SHEAR WALL
SYM SYMMETRICAL
T TOP
T/ TOP OF
T&B TOP AND BOTTOM
TB TRUSS BEARING
TC TERRA COTTA
TEMP TEMPORARY,TEMPERATURE
T&G TONGUE AND GROOVE
THD THREAD(ED)
THK THICK(NESS)
TMS THE MASONRY SOCIETY
TOS TOP OF SLAB
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
U-P UNDERPINNING
V SHEAR
VAR VARIES
VB VAPOR BARRIER
VEF VERTICAL EACH FACE
VERT VERTICAL
VIF VERTICAL INSIDE FACE,
VERIFY IN FIELD
VOF VERTICAL OUTSIDE FACE
VR VAPOR RETARDER
W/ WITH
W/O WITHOUT
WD WOOD
WI WROUGHT IRON
WP WORK POINT, WATERPROOFING
WT WEIGHT
WWF WELDED WIRE FABRIC
XS EXTRA STRONG
XXS DOUBLE EXTRA STRONG
∅ DIAMETER
± PLUS OR MINUS
ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
VA Project No.
AG Project No.
A u to d e s k D o c s /V
A M
C
B a y P in e s /0
B a y P in e E
D C
T R
S .r v t
/3
/2
:2
:1
A
M
S-001
GENERAL NOTES AND
ABBREVIATIONS
AE Site Prep for ED CT Replacement
BAY PINES VA
0124034
MAY 1, 2025 RAS SLS
100% CONSTRUCTION
DOCUMENTS
516-CSI-142
SHEET LIST
Sheet Number Sheet Name
S-001 GENERAL NOTES AND ABBREVIATIONS
SS101 FIRST FLOOR FRAMING PLAN
SS102 FIRST FLOOR INTERSTITIAL FRAMING PLAN
S-301 DETAILS AND SECTIONS
5 6 7 8
E
F.2
TOILET/DRESS
1E222E
CONTROL
1E222B
RAD EXAM
1E274B
DRESS
1E222D
ER EXAM
1E224A
F.1
(E
(E
1'
(E
22' - 10" (E)22' - 10" (E)22' - 10" (E)
E.5
CT SCAN ROOM
1E222A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
VA Project No.
AG Project No.
A u to d e s k D o c s /V
A M
C
B a y P in e s /0
B a y P in e E
D C
T R
S .r v t
/3
/2
:2
:1
A
M
SS101
FIRST FLOOR FRAMING PLAN AE Site Prep for ED CT Replacement
BAY PINES VA
0124034
MAY 1, 2025 RAS SLS
100% CONSTRUCTION
DOCUMENTS
516-CSI-142
CODED NOTES:
GANTRY, 5,900 LBS. BOLTED TO THE EXISTING FIRST FLOOR SLAB WITH POST INSTALLED ANCHORS
PROVIDED BY EQUIPMENT MANUFACTURER, REFER TO EQUIPMENT DRAWINGS FOR ANCHOR BOLT
LAYOUT.
PATIENT TABLE, 1,500 LBS. BOLTED TO THE EXISTING FIRST FLOOR SLAB WITH POST INSTALLED
ANCHORS PROVIDED BY EQUIPMENT MANUFACTURER, REFER TO EQUIPMENT DRAWINGS FOR
ANCHOR BOLT LAYOUT.
SYSTEM CABINET, 410 LBS.
UPS, 610 LBS.
POWER DISTRIBUTION UNIT, 1075 LBS.
STORAGE CABINET, 150 LBS.
DRAWING NOTES:
NN
0 2' 4' 8' 12'
1/4" = 1'-0"
1. TOP OF FIRST FLOOR IS 14.00' (DATUM 0.00').
2. EXISTING FIRST FLOOR IS A 10" THICK REINFORCED TWO-WAY FLAT PLATE CONCRETE SLAB. THE
CRAWL SPACE BELOW HAS BEEN INFILLED WITH SOIL.
3. CONTRACTOR TO CONFIRM FLOOR AREA AROUND GANTRY AND PATIENT TABLE MEETS THE
MANUFACTURER'S FLOOR LEVELNESS CRITERIA OF 1/4" / 10'-0" PRIOR TO INSTALLING EQUIPMENT. IF FLOOR DOES NOT MEET THE REQUIREMENT, THE TOP SURFACE WILL NEED TO BE ROUGHENED AND
PATCHED WITH LEVEL TOPPING CONCRETE, SIKA LEVEL 425.
4. CONTRACTOR TO GPR SCAN FIRST FLOOR SLAB PRIOR TO INSTALLING POST INSTALLED ANCHORS.
IF REBAR IS INDICATED WHERE A POST INSTALLED ANCHOR IS TO BE LOCATED, CONTRACTOR TO SUBMIT AN RFI PER GENERAL NOTES. EQUIPMENT MAY NEED TO BE SLIGHTLY RELOCATED TO AVOID
CUTTING EXISTING REBAR.
1/4" = 1'-0"
FIRST FLOOR FRAMING PLAN
N.T.S.
KEYPLAN 1ST FLOOR
5 6 7 8
E
F.2
CT SCAN ROOM
1E222A
TOILET/DRESS
1E222E
CONTROL
1E222B
RAD EXAM
1E274B
DRESS
1E222D
ER EXAM
1E224A
F.1
(E
1'
(E
22' - 10" (E)22' - 10" (E)22' - 10" (E)
W6X8.5 (E)
W6X8.5 (E)
W6X8.5 (E)
W6X8.5 (E)
W6X8.5 (E)
W6X8.5 (E)
W6X8.5 (E)
W6X8.5 (E)
W6X8.5 (E)
W6X8.5 (E)
W6X8.5 (E)
7' - 8" (E)7' - 6" (E)7' - 8" (E)6 1/2" (E)
TYPICAL HANGER ROD SPACING
TYPICAL SUBPURLIN SPACING
1' - 1 3/4" (E) 4 EQ SPACES AT 2' - 3 1/2" = 9' - 2" (E) 2' - 2 1/2" (E) 4 EQ SPACES AT 2' - 3 1/2" 9' - 2" (E) 1' - 1 3/4" (E)
6'
(E
1'
1"
E
4'
(E
6'
(E
6'
(E
6'
(E
6'
(E
6'
(E
6'
(E
4'
(E
1'
(E
3'
(E
13' - 1 1/2"
0".
5/ S-301
1/ S-301
4/ S-301
4/ S-301
4/ S-301
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
VA Project No.
AG Project No.
A u to d e s k D o c s /V
A M
C
B a y P in e s /0
B a y P in e E
D C
T R
S .r v t
/3
/2
:2
:1
A
M
SS102
FIRST FLOOR INTERSTITIAL
FRAMING PLAN
AE Site Prep for ED CT Replacement
BAY PINES VA
0124034
MAY 1, 2025 RAS SLS
100% CONSTRUCTION
DOCUMENTS
516-CSI-142
CODED NOTES:
CAMERA SUPPORTED BY CEILING PLATE PROVIDED BY EQUIPMENT MANUFACTURER TO (2) 7 1/2"x7 1/2"x1/2" THICK PLATES AND (4) 3/8" DIA. THREADED RODS TO P1001 UNISTRUT FRAME PROVIDED BY
CONTRACTOR FRAMED TO INTERSTITIAL STEEL BEAMS. COORDINATE LOCATION AND HOLES
REQUIRED IN PLATE WITH EQUIPMENT DRAWINGS. ADDITIONAL (4) 2'-0" LONG P1001 FOR JUNCTION
PLATE CEILING SUPPORT TO BE PROVIDED BY CONTRACTOR. REFER TO DETAIL SIM.
MEDRAD INJECTOR SUPPORTED BY (2) 15"x15"x1/2" THICK PLATES AND (4) 1/2" DIA. THREADED RODS TO P1001 UNISTRUT FRAME PROVIDED BY CONTRACTOR FRAMED TO INTERSTITIAL STEEL BEAMS.
COORDINATE LOCATION AND HOLES REQUIRED IN PLATE WITH EQUIPMENT DRAWINGS. REFER TO
DETAIL .
MONITOR SUPPORTED BY (2) 15"x15"x1/2" THICK PLATES AND (4) 1/2" DIA. THREADED RODS TO P1001
UNISTRUT FRAME PROVIDED BY CONTRACTOR FRAMED TO INTERSTITIAL STEEL BEAMS.
COORDINATE LOCATION AND HOLES REQUIRED IN PLATE WITH EQUIPMENT DRAWINGS. REFER TO
DETAIL .
BARIATRIC PATIENT LIFT, MAXIMUM LOAD OF 770 LBS. SUPPORTS TO BE PROVIDED BY
MANUFACTURER, REFER TO DETAIL WITH UNISTRUT MOUNTED TO TOP OF INTERSTITIAL
BEAMS. COORDINATE LOCATION WITH ARCHITECTURAL DRAWINGS.
DRAWING NOTES:
NN
0 2' 4' 8' 12'
1/4" = 1'-0" 1/4" = 1'-0"
FIRST FLOOR INTERSTITIAL FRAMING PLAN
1. TOP OF INTERSTITIAL FLOOR DECK IS 10.75' ABOVE FIRST FLOOR (DATUM 0.00').
2. EXISTING INTERSTITIAL FLOOR FRAMING IS 2" POURED GYPSUM REINFORCED WITH SUBPURLINS
COMPRISED OF GAGE WIRE AND GAGE ANGLES WITH A 1/2" FORMBOARD, REFER TO BEAMS ON PLAN
AND DETAIL .
N.T.S.
KEYPLAN 1ST FLOOR
EXISTING PRECAST
CONCRETE JOIST
EXISTING CONCRETE SLAB AND
CONCRETE TOPPING
NOTE:
HANGER RODS SHALL ONLY TO ATTACH TO SIDE OF PRECAST CONCRETE
JOISTS/BEAMS DUE TO THE PRESTRESSED STRANDS IN THE BOTTOM OF THE
CONCRETE JOISTS/BEAMS.
*WARNING* PRECAST CONCRETE JOISTS AND BEAMS HAVE PRESTRESSED
STRANDS. SERIOUS HAZARDS/DAMAGE CAN RESULT FROM A STRAND BEING CUT.
CLIP ANGLE BENT TO
MATCH FACE OF JOIST
3/8" MIN. DIA. EXPANSION
BOLT
3/8" THREADED ROD
Pmax=2000 lbs
3/
4"
E
EXISTING CONCRETE SLAB
3/
4"
E
3/8" THREADED ROD
Pmax=140 lbs
HILTI HDI-P TZ DROP
IN ANCHOR
NOTE:
DETAIL MAY ALSO APPLY TO THE BOTTOM OF CONCRETE BEAMS.
EXISTING PRECAST
CONCRETE JOIST
EXISTING CONCRETE SLAB
EXISTING STEEL BEAM,
REFER TO PLAN
EXISTING POURED GYPSUM ON
SHEET ROCK FORMBOARD
INTERSTITIAL T.O.S.
SEE PLAN
3/4" DIA. THREADED ROD,
WELDED TO TOP STEEL PLATE
AND THROUGH BOLTED TO
ANGLE ABOVE
2"
E
1/ 2"
E
4"
E
1/
2"
E
EXISTING STEEL WELD CLEAT
PLATE, WELDED TO BEAM
6" (E)
1/
2"
E
5"
E
1/ 2"
E
5" (E)
EXISTING STEEL PLATE,
WELDED TO BEAM
EXISTING SUBPURLINS,
WELDED TO STEEL WELD
CLEAT PLATE
2"
E
EXISTING L4"x4"x3/4" x 2'-0"
LONG ANGLE AT EACH
THREADED ROD
(2) 3/4" DIA. THRU BOLTS
1/
2"
E
1/
2"
E
UNISTRUT P1001, REFER TO PLAN
EXISTING STEEL BEAM,
REFER TO PLAN
EXISTING POURED GYPSUM ON
SHEET ROCK FORMBOARD
INTERSTITIAL T.O.S.
SEE PLAN
(4) THREADED RODS THROUGH BOLTED TO
PLATE BELOW, PROVIDE HEAVY HEX NUTS,
LOCK WASHERS, AND P3000 SERIES NUT IN
UNISTRUT, REFER TO PLAN FOR ROD DIA.
AND MANUFACTURER'S REQUIREMENTS FOR
LOCATIONS
2"
E
1/ 2"
E
EXISTING STEEL WELD CLEAT
PLATE, WELDED TO BEAM
EXISTING SUBPURLINS,
WELDED TO STEEL WELD
CLEAT PLATE
PROVIDE BOLTS PER
MANUFACTURER'S REQUIREMENTS
STEEL PLATE, REFER TO PLAN
MEDICAL EQUIPMENT, REFER TO
MANUFACTURER'S DRAWINGS
UNISTRUT P2786 INVERTED CLAMP
1 1/2" MIN.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
VA Project No.
AG Project No.
A u to d e s k D o c s /V
A M
C
B a y P in e s /0
B a y P in e E
D C
T R
S .r v t
/3
/2
:2
:1
A
M
S-301
DETAILS AND SECTIONS AE Site Prep for ED CT Replacement
BAY PINES VA
0124034
MAY 1, 2025 RAS SLS
100% CONSTRUCTION
DOCUMENTS
516-CSI-142
N.T.S.
SECURE HANGING RODS IN CONCRETE AT
PRECAST JOISTS
N.T.S.
SECURE HANGING RODS IN CONCRETE AT SLAB
N.T.S.
BARIATRIC PATIENT LIFT DETAIL
N.T.S.
TYPICAL EXISTING INTERSTITIAL SPACE FRAMING DETAIL
N.T.S.
EQUIPMENT UNISTRUT FRAME IN INTERSTITIAL SPACE DETAIL
CT SCAN
ROOM
1E210B
CLOSET
1E210
9.23
CONTROL
ROOM
1E210C
A401
A401
A4
A401
A4
210C
W1 S1.0-L
2'-4"
ALIGN
X-L
X-LX-L
AN
TE
R O
O M
1.03
1.03
1.03
1.03
1.03
2.51
2.52
2.52
2.53
2.56
2.59
2.59
2.52
2.58
2.52
2.53
2.58
2.59
2.58
2.59
2.55
2.55
2.05
1.03
1.03
1.03
1.03
1.03
AN
TE
R O
O M
8'-10"
9'-0"
8'-6"
ACT-2
ACT-2
1E210C
1E210
1E210B
12.04
13' - 1 1/2"3' - 0 5/8"
3'
3" 1'
3/ 4"
12' - 8 3/4"
4'
0"
10' - 6"6' - 0"
1'
1/
2" 6'
1/ 2"5' - 0"
5'
1/
8"
1' - 3 3/4"
ACT-1
REFLECTED CEILING PLAN LEGEND
Recessed downlight fixture Supply Air Diffuser
Return Air Grille(ACT-1) 2' x 2' acoustical tile ceiling
Exhaust Air Grille (ACT-2) 2' x 2' acoustical tile ceiling
DEMOLITION LEGEND
Wall to be Demolished
Existing Wall to Remain
Door and Frame to be Demolished
EXTERIOR ELEVATION
INTERIOR ELEVATION
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X X
XX.X-X
XX
X
1/A101
X
A101
XX
TOILET ACCESSORY TAGX SIGNAGE TAG
A101
SIM
X
X3145
M4255
M8826
M3070
E0954
M3150
M8810
X2100
E0945
M8825
F0340
F0360
CT SCAN
ROOM
1E210B
CONTROL
ROOM
1E210C
CLOSET
1E210
X6241
X6197
X6196
X6198
A1200
SYSTEM CABINET
SYSTEM UPS
SYSTEM POWER
DISTRIBUTION UNIT
SYSTEM MAIN
DISCONNECT
PANEL
SYSTEM STORAGE
CABINET
SYSTEM CONSOLE
SYSTEM INJECTOR
CONTROL
10'-2"
7' -6
6'
0"
16.5°
6' - 4 5/8"A5106
A5077
A5075 A5080
12.04
A5105
S1.0-L
4 7/8"
9.21
9.02
9.80
7.82
7.82
STRUCTURE ABOVE
FIN. CEILING
FLOOR SLAB
9.19
LEAD-LINED PER
PHYSICIST REPORT
REQUIREMENTS
SCANNER
ROOM SIDE
X-L
7.82
LEAD-LINED PER
PHYSICIST REPORT
REQUIREMENTS
2.03
9.19 SCANNER
ROOM SIDE
5/8"VARIES
3"
A101
Sim
A101
Sim
5/8" VARIES 5/8"
STUD, PER PARTITION TYPE
CONTINUOUS LEAD STRIP, FULL HEIGHT
AT EVERY LEAD-LINED BOARD JOINT TO
EXTEND MIN 1" PAST LEAD BACKING
EDGES ALL SIDES, TYPICAL EVERY JOINT
INCLUDING INSIDE AND OUTSIDE
CORNERS
5/8" LEAD-LINED GYPSUM BOARD
EMBED 5/16" DIA. LEAD DISC TO
COVER HEAD OF EVERY THRU-LEAD
FASTENER, INCLUDING ALL LEAD
LINED BOARD FIELD AND EDGE
FASTENER LOCATIONS
NOTES:
1. ALL LEAD COMPONENTS ARE TO MATCH OR EXCEED LEAD
BACKING THICKNESS.
2. LEAD LINE ALL BACK BOXES AND OTHER PENETRATIONS OF THE
LEAD BACKING.
M
IN1"
5/8" VARIES 5/8"
STUD, PER PARTITION TYPE
CONTINUOUS LEAD STRIP, FULL HEIGHT
AT EVERY LEAD-LINED BOARD JOINT TO
EXTEND MIN 1" PAST LEAD BACKING
EDGES ALL SIDES, TYPICAL EVERY JOINT
INCLUDING INSIDE AND OUTSIDE
CORNERS
5/8" LEAD-LINED GYPSUM BOARD
NOTES:
1. ALL LEAD COMPONENTS ARE TO MATCH OR EXCEED LEAD
BACKING THICKNESS.
2. LEAD LINE ALL BACK BOXES AND OTHER PENETRATIONS OF THE
LEAD BACKING.
M
IN1"
Scale: 1/4" = 1'-0"3 Reflected Ceiling Plan
Scale: 1/4" = 1'-0"1 Demolition Plan
S T
AT
E
OF FLOR
I D A
R
EGISTERED ARCH
IT
EC
T
J A
SO
N H. ROS
S
AR101907
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
ARCHITECT/ENGINEER OF RECORD
www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
4/
/2
8:
:5
AM
B100 ED Room 1E210 CT Replacement
5/1/2025
PLANS AND DETAILS
A101
JWJC
516-CSI-142
VAMC, Bay Pines, FL
B100
100% CONSTRUCTION
DOCUMENTS
24127.00
Scale: 1/4" = 1'-0"2 Floor Plan
A. All dimensions are taken to face of gypsum wallboard or unit masonry.
B. Edge of all door jambs at hinge side not otherwise indicated are to be 6" from the face of intersecting walls. Edge of all door jambs at strike side not otherwise located are to be 18" minimum from the face of intersecting walls.
C. Provide steel backing. No wood blocking or fire retardant treated wood blocking.
D. All partitions shall be type 'S1.0' unless noted otherwise.
1.03 Level IV ICRA barrier system. Temporary NFPA 241-compliant plastic or hard-wall critical barrier system.
2.03 Existing wall to remain.
2.05 Remove existing plumbing fixture. Refer to mechanical
drawings for details.
2.51 Remove existing frame.
2.52 Remove existing door, frame and hardware.
2.53 Remove existing interior window.
2.55 Remove all existing casework/countertops.
2.56 Remove existing wall board to prepare for new lead lined gypsum wallboard installation.
2.58 Remove existing suspended ceiling grid and tiles. Refer to MEP drawings for related ceiling items.
2.59 Remove existing floor finish and wall base. Prepare for new finishes.
7.82 Continuous acoustic sealant @ non-rated walls / fire-rated sealant @ rated walls each side.
9.02 3 5/8" non-structural metal framing @ 16" o.c.
9.19 5/8" type "X" gypsum board. Lead-lined up to min physicist-required height and 5/8" type "X" gypsum board above.
9.21 5/8" Type "X" gypsum board.
9.23 Lead-lined gypsum board and radiation shielded windows, doors and frames, full perimeter of room. Refer to physicist report requirements.
9.80 Acoustic insulation.
12.04 Cubicle curtain track (CT-1) and curtain (FAB-1), provided and installed by contractor. Refer to finish legend for details.
NOTES
GENERAL NOTES
A. Remove all existing partitions shown with dashed line. Repair wall and floor finishes to match adjacent surfaces at areas of removal or scheduled new surfaces as required.
B. Remove all existing borrowed lights, doors and hollow metal frames where indicated with dashed line. Unused hardware shall be turned over to Owner. Box hardware before giving to Owner.
C. Remove wall-hung toilet room accessories and medical equipment as required and turn over to Owner.
D. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.
E. Computer and communication cables and/or other wiring, piping, tubing, etc. serving other areas and functions located above ceiling or in walls of area to be remodeled shall be maintained during demolition/construction process. Coordinate any required changes via the RFI process.
F. Repair existing walls to match adjacent undisturbed wall where cabinets, countertops, etc. are shown to be removed.
G. Prepare walls and floor slabs as required to receive new finish materials where existing finish is indicated to be removed.
H. Remove existing corner guards in areas to be remodeled.
A. Provide steel backing. No wood blocking or fire retardant treated wood blocking.
B. Light fixtures, sprinkler heads, speakers, and HVAC devices shall be located as close as possible to the center of acoustical ceiling panels. Confirm any deviation from this with the Project Engineer.
C. See P, M, E and FP drawings for additional information regarding final information and quantites of fixtures/devices to be installed in ceiling.
D. See Electrical Drawings for lighting specifications.
GENERAL NOTES - RCP
GENERAL NOTES - DEMOSYMBOLS LEGEND
Scale: 1/4" = 1'-0"5 Equipment Plan
N N.T.S.Scale:
KEYPLAN 1ST FLOOR
EQUIPMENT SCHEDULE
Tag Description Supplier / Installer
A1200 Ceiling Mounted Patient Lift System VC A5075 A5075 - Dispenser, Soap, Disposable VV A5077 A5077 - Dispenser, Hand Sanitizer, Hands-Free VV A5080 A5080 - Dispenser, Paper Towel, SS, Surface Mounted VV A5105 A5105 - Waste Disposal Unit, Sharps, Container Shield VV A5106 A5106 - Waste Disposal Unit, Sharps with Glove Dispenser VV E0945 M8910 - Cart, Surgical Case VV E0954 E0954 - Cart, Emergency, Mobile, 66H x 52W x 22D VV F0340 M5030 - Stool, Surgeon, Revolving VV F0360 F0355 - Footstool, Straight VV M3070 M3070 - Hamper, Linen, Mobile, with Lid VV M3150 M3150 - Distribution System, Medication, Automatic VV M4255 M4255 - Stand, IV, Adjustable VV M7490 M7490 - Light, Surg, Ceiling Mtd, Dual, Unequal Dia Heads 2 VC M7801 M7801 - Monitor, Medical Grade 26in - 42in 2 VC M7801 M7801 - Monitor, Medical Grade 26in - 42in 2 VC M8810 M8810 - Stand, Mayo 2 VV M8825 M8825 - Table, Instrument-Dressing, CRS, approx. 36x20x34 2 VV M8826 M8840 - Table, Back, Instrument-Dressing 2 VV M8830 M8830 - Table, Instrument-Dressing, Mobile VV X2100 X2106 - Scanner, Ultrasound, Intra-Cardiac, Echo VC X3145 X3145 - Screen, X-Ray, Protective, Mobile VV X6196 Injector on Boom VC X6197 Monitor on Boom VC X6198 Patient Position Monitor, Ceiling Mounted VC X6241 CT Unit VC
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
2' 4' 8'0
2"0 1/4" = 1'-0"
4' 8' 16'0
2"0 1/8" = 1'-0"
4' 8' 16'0
2"0 1/8" = 1'-0"
4' 8' 16'0
2"0 1/8" = 1'-0"
Wall Types
Radiation Shielding Detail
WSV-1
ROOM
1E210B
CONTROL
ROOM
1E210C
CLOSET
1E210
RB-1
P-1
P-1
P-1
WSV-1
LVT-1
12'
12'
6'
CG-1
WP-1
WELDING
SEAM
P-3
9.16
9.16
12.34
CG-1
2'
" A
.F .F
4"
2'-1"
1/
4"
9.60
12.05
Drawer
B1B8
Sink
4"
3"
1"
2'
" A
.F .F
4"
2'-1"
1/
4"
4" 2'
-4
/4
1"
1'-1" 3" 8"
12.05
C1
2'
" A
.F .F
4"
2'-1"
4"
12.32
12.05
12.34
9"
W1
1'-2"
26.01
C2
3'
0" A
.F .F
4"
2'-7"
4"
12.32
12.05
12.34
T1
2'-0"
9.60
6.28
6.24
6.27
6.25
4"
3"
SCHEDULED
CEILING
4"
SE
E
EL
EV
AT
IO
N
S
SE
E
EL
EV
AT
IO
N
S
6.25
6.24
6.28
6.27
6.25
6.25
6.24
6.28
6.27
12.06
6.25
6.25
SE
E
EL
EV
AT
IO
N S
SE
E
EL
EV
AT
IO
N S
4"
6.22
SCHEDULED
CEILING
12.07
15' - 2"
3' -0
210C
C2
P-1
SS-1
WSV-1
W1
12.34 12.07
M3150 T1T1
2' - 8" 2' - 6" 2' - 6" 2' - 6" 2' - 0" 2' - 0"
P-1
WP-1
4' -0
WSV-1
2" FILLER 2' - 6" 2' - 6" 2' - 6" 2' - 6"
B8 B1 B1 C1 CG-1
W1 W1 W1 W1
2'
2'
0" 2'
6"
1'
6" A5075
A5080
P-1
WP-1
WSV-1
4' -0
A5077
A5106
A5105
210C
4' -0
P-1
WP-1
WSV-1
12.04
E0954 X3145
W1
4' -0
P-1
WP-1
WSV-1M8826 E0945 E0954
EXTERIOR ELEVATION
INTERIOR ELEVATION
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X X
XX.X-X
XX
X
1/A101
X
A101
XX
TOILET ACCESSORY TAGX SIGNAGE TAG
A101
SIM
X
Aluminum top cap
Resilient sheet vinyl integral wall base
Bonded puncture-proof aluminum reinforcement cove former
S T
AT
E
OF FLOR
I D A
R
EGISTERED ARCH
IT
EC
T
J A
SO
N H. ROS
S
AR101907
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
ARCHITECT/ENGINEER OF RECORD
www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
4/
/2
8:
:5
AM
B100 ED Room 1E210 CT Replacement
5/1/2025
INTERIOR FINISHES PLAN AND
LEGEND
A401 DesignerApprover
516-CSI-142
VAMC, Bay Pines, FL
B100
100% CONSTRUCTION
DOCUMENTS
24127.00
A. Finish tags under room name tag denotes finishes in room to receive noted material. Accent finishes to be noted on plans otherwise.
B. All hollow metal doors and frames to receive paint (P-2); unless noted otherwise.
C. All wall protection (WP-1) to be 4' A.F.F; unless noted otherwise.
D. All diffusers and vents to be painted to match adjacent wall/ceiling finish. Verify color with architect in field.
E. All casework to be (PL-1). All countertops to be (SS-1); unless noted otherwise. Contractor to field verify all measurements for casework before production.
F. All walls to be painted P-1 unless noted otherwise.
G
Provide resilient base (RB-1) at all casework toe kicks. Flooring to be installed underneath all casework. Contractor to field measure all casework dimensions before production.
H. Provide vinyl transition strips at all flooring material juntures. Material transitions, where applicable, occur at center of door panel. Refer to floor transition details for typical floor material transitions.
6.22 Plastic laminate base cabinet.
6.24 Adjustable shelf w/steel support pegs.
6.25 Plastic laminate over 3/4" plywood substrate.
6.27 Wire pull, aluminum.
6.28 Concealed hinge.
9.16 Provide 6"h welded sheet flooring (wsf-1) integral wall
base, with top cap.
9.60 Resilient base. See Room Finish Schedule.
12.04 Cubicle curtain track (CT-1) and curtain (FAB-1), provided and installed by contractor. Refer to finish legend for details.
12.05 Solid surface over 3/4" substrate, 1/4" eased edge, 4"h backsplash.
12.06 Solid surface integral sink (ss-2). Refer to finish legend for details.
12.07 Cable management tray.
12.32 Wire management grommet. Coordinate exact location
with owner.
12.34 Heavy-duty bracket, install every 48"max.
26.01 Light fixture. See Electrical Drawings.
PLAN NOTES
GENERAL FINISH PLAN NOTES
Scale: 1/4" = 1'-0"1 Finishes Plan
N.T.S.Scale:
Casework Sections
Scale: 1/4" = 1'-0"2 Control Room 1E210C
6 5 4 3
FINISH LEGEND
Tag Finish Type Manufacturer Product Description
06 41 16 Architectural Cabinets PL-1 High pressure Laminate Wilsonart Uptown Walnut 7071K-12 09 51 00 Acoustical Ceiling Tile ACT-1 Acoustical ceiling tile Armstrong Clean room VL 868B, 24” x 24” x 5/8” Thick; smooth, grid: 15/16" Prelude XL/XL
HRC, .050 white, Fire Guard ACT-2 Acoustical ceiling tile Armstrong Fine fissured 1728, 24” x 24” x 5/8” Thick, grid: 15/16" Prelude XL/XL HRC, .050 white, Fire Guard 09 65 13 Resilient base & Accessories RB-1 Rubber wall base Mannington 4"H traditional vinyl with toe, 527 Clay 09 65 16 Resilient Sheet Flooring WSV-1 Welded sheet vinyl flooring Mannington Paradigm, Flow, Color: Exemplar PAR302 09 91 00 Painting P-1 Interior paint (field) Benjamin Moore Custom Mix Coronado Paints - OW135 P-2 Interior paint (door frames) Benjamin Moore HC-86 Kingsport Gray 10 21 23 Cubicle Curtain & Track CT-1 Cubicle Track -- Barrier Free Lifts PRVC Systems cubicle curtain track FAB-1 Cubicle Curtain Arc-Com Dahlia – X AC-33285X Seafoam #6 10 26 00 Wall Protection CG-1 Corner Guard InPro Corp. 150 Surface Mount 90° Full Height, White Sand 0103 WP-1 Rigid sheet vinyl wallcovering InPro Corp.
This is the start of the file's text. The full file is on GovTribe.