This document is a technical catalog for Eaton's Cooper Power Series four-position sectionalizing loadbreak switches designed for use in transformer oil or approved equivalent fluid-filled padmounted transformers and distribution switchgear. The switches meet IEEE and IEC standards and are available in multiple configurations, including single and three-phase systems with ratings from 200A to 630A and 15kV to 38kV. Key features include a Make-Before-Break (MBB) design that improves system reliability by eliminating momentary interruptions during switching, 360-degree rotation capability, and hotstick operability. The switches can be horizontally or vertically mounted and are tested for mechanical operations, contact resistance, and electrical performance at third-party certified laboratories, with options for V-blade, T-blade, straight blade, and selector blade types.
The catalog provides comprehensive technical details including electrical ratings tables for 12.5 kA and 16 kA applications, dimensional illustrations, wiring schematics, and a detailed catalog number selection chart that allows precise specification of switch characteristics. Mounting options include a Ring-Mount System for easy installation, and accessories like a pad-lockable handle are available separately. The switches are designed for underground residential applications, loop feed systems, and commercial/industrial installations where alternative power source switching is necessary, with all switches featuring silver-plated copper current paths and engineered to minimize cable capacitance and ferroresonance risks.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Eaton's Cooper Power™ series four-position sectionalizing loadbreak switch is designed for use in transformer (mineral) oil, Envirotemp™ FR™ fluid, or an approved equivalent fluid-filled pad-mounted transformers or distribution switchgear.
The switches meet the full requirements of the latest revision of both IEEE® and IEC standards.
Sectionalizing switches can be used on single- and three-phase grounded wye or delta systems. They are used in underground residential applications with loop feed, and in three-phase commercial industrial installations where the ability to use an alternative source of power is necessary. They can also be used to switch on and off a primary cable tap on a transformer.
The under-oil switch can be installed near the transformer core/coil assembly, thus minimizing cable capacitance. With cable capacitance minimized and all three phases switched simultaneously, the like li hood of ferroresonance is greatly reduced. All switches are hotstick operable and available in several different blade configurations (Refer to Table 4).
Eaton’s Cooper Power series sectionalizing switches rotate 360˚ in either direction for alternate source selection. An externally installed limiting plate prevents ro ta tion to positions other than the one desired. A spring-loaded activating mechanism ensures quick loadbreak action and positive contact engagement through all positions.
The Make-Before-Break (MBB) switches provide uninterrupted power during switching.
Four-position sectionalizing loadbreak switches
General
OEM Equipment Catalog Data
CA800005EN
Effective March 2025 Supersedes 800-64 June 2015
COOPER POWER
SERIES
Make-before-break features
• Improves system reliability by eliminating momentary interruptions during switching operations typically associated with Break-Before-Make (BBM) sectionalizing switches
• Replaces 2 or 3 two position loadbreak switches depending on application (choose V-blade or T-blade type)
• Simplifies operational procedures
• Make-Before-Break design is only available for V- and T-blade switch types
Attributes
• Available for both 12 kA and 16 kA applications
• Ratings from 200 A to 630 A and from 15 kV to 38 kV
• Tested in mineral oil and Envirotemp™ FR3™ fluid
• All electrical switching tests performed at third-party certified test laboratories
• 5000 mechanical operations (meets IEC class M2 switch)
• All silver plated copper current path
• Similar “footprint” as previous 10 kA switches
(See Tables 3 and 4)
• The Ring-Mount System option offers easy and fast installation
• Special vertical mounted switches available for cover mounted applications
Production tests Tests are conducted in accordance with Eaton requirements:
• Physical Inspection
• Mechanical operations
• Operating torque
• Contact pressure
• Switch contact resistance
Installation The switch is either horizontally or vertically mounted, depending on the application and the selected switch type. The vertically mounted switch is typically used in transformers/switchgear installed below grade, where the switch would be mounted in the cover of that particular equipment. All exposed parts of the vertically mounted switch are made from stainless steel or other non-corrosive materials. Both types of switches, including the mechanism, must be completely immersed under the insulating fluid.
ote: N For all mounting systems, refer to Service Information MN800002EN Sectionalizing Switch Installation Instructions for more detailed installation instructions.
Catalog Data CA800005EN Effective March 2025
Four-position sectionalizing loadbreak switches www.eaton.com/cooperpowerseries
Figure 2. Make-Before-Break switch features and description (see Table 5 for application details)
Figure 1. Switch features and description
Arc Suppressor Paddle The arc suppressor paddle forces insulating fluid across the contacts to assist in stretching and extinguishing the arc during switching.
Arc Barrier
Silver Plated Copper Contacts
SILVER PLATED COPPER BLADE
(MBB T-blade SHOWN) The MBB blade eliminates the momentary interruption during switching associated with connection type load-breaking switches. The MBB option also eliminates the need for multiple “on/off” switches required to avoid momentary switching interruptions.
SILVER PLATED COPPER BLADE
The moving blades are available in four different configurations or switch types; Straight, Selector, V-blade or T-blade. In addition the V-blade and the T-blade have a Make-Before-Break (MBB) option.
ARC BARRIER
Prevents stretched arcs from jumping across phases or phase-to-ground (earth) during switching.
(One barrier removed for illustrative purposes)
LIMIT PLATE
The limit plate can be used to assure only one operation is performed each time the switch is operated.
HANDLE
All horizontally mounted switches are furnished with cast brass handles.
Vertically mounted switches are typically used in transformers or switchgear mounted below grade and the switches are therefore furnished with brass handles and non-corrosive external parts.
ARC SUPPRESSOR
PADDLE
SWITCH MECHANISM
A spring-loaded activating mechanism ensures quick loadbreak action and positive contact engagement through all positions.
SILVER PLATED COPPER CONTACTS
Provides a low resistance connection with the moving blades.
MOUNTING PLATE (RING-MOUNT SHOWN)
The Ring-Mount System provides a fast and easy installation without additional bolts and welded couplings.
FIBERGLASS SHAFT
A fiberglass wound shaft with a solid pultruded core provides a high strength non-twisting connection between blades and the switch mechanism.
Catalog Data CA800005EN Effective March 2025
Electrical ratings
Table 1. Ratings and characteristics per IEEE Std C37.71™-2001 standard
Units
12.5 kA rated switches to IEEE Std C37.71™ - 2001 standard
Rated Voltage Maximum rating phase-to-phase Maximum rating phase-to-ground kV kV
15.5
27.8 17.2
21.9
Power Frequency Hz 60 60 60
Current rating (Continuous) A 630 300 200
Loadbreak Capability @ 0.75 Power Factor First peak min/ Time-to-peak max.
A kV µs
7.6
Magnetizing A 22 10.5 7
Cable Charging A 10 25 40
Fault Withstand Current (Momentary) 10 cycle symmetric rms 10 cycle asymmetric rms 10 cycle peak kA kA kA
12.5 18.6 32.6
12.5 18.6 32.5
12.5 18.6 32.5
Fault Withstand (Short-time) 1s rms 2s rms kA kA
12.5 12.5
12.5 12.5
12.5 12.5
Fault Close and Latch 10 cycle symmetric rms 10 cycle asymmetric rms 10 cycle peak kA kA kA
12.5 18.6 32.5
12.5 18.6 32.5
12.5 18.6 32.5
Impulse Withstand Voltage (1.2/50 µs) To ground and between phases Across open contacts kV kV
Power Frequency (1 minute) To ground and between phases Across open contacts kV kV
DC Withstand (15 minutes) To ground and between phases Across open contacts kV kV
Corona (Extinction) kV 26 26 26
Temperature Maximum at 630 A °C 75 75 75
Temp. Rise Above Ambient Air at 630 A (Max.) °K 35 35 35
Mechanical Life (Minimum Operations) 5,000 5,000 5,000
Table 2. Ratings and characteristics per
IEC 60265-1 – 1998
Units
16 kA rated switches to
IEC 60265-1 - 1998
Switch Rating kV 15 24 36
Rating voltage Maximum rating phase-to-phase Maximum rating phase-to-earth kV kV
15.5
24.9 14.4
21.9
Power Frequency Hz 50/60 50/60 50/60
No-Load Transformer Breaking Current A 6.3 4 2
Current Rating (Continuous) A 630 400 200
Mainly Active Load Breaking Current First peak min.
Time-to-peak max.
A kV µs
25.7
65.1
Closed Loop Breaking Current A 630 400 200
Line Charging Current A 1 1.5 2
Cable Charging Current A 10 17 25
Earth Fault Switching Current A 1 10 8
Cable and Line Charging Under Earth Fault A 17.5 17 26
Short-time Withstand Current 1s rms 2s rms 3s rms kA kA kA
Short-circuit Making Current 12 cycle symmetric rms (min.)
12 cycle asymmetric rms (min.)
12 cycle max. peak (min.)
kA kA kA
24.8 41.6
24.8 41.6
24.8 41.6
Impulse Withstand Voltage (1.2/50 µs) To earth and between phases Across open contacts (isolating distance) kV kV
Power Frequency (1 Minute) To earth and between phases Across open contacts (isolating distance) kV kV
Corona (Extinction) kV 26 26 26
Temperature Maximum at 630 A °C 90 90 90
Temp. Rise Above Ambient Air at 630 A (Max.) °K 50 50 50
Mechanical Life (Minimum Operations) 5,000 5,000 5,000
Catalog Data CA800005EN Effective March 2025
Figure 3. Line illustration with dimensions of sectionalizing switch with “Ring-Mount System”
Notes:
1. Dimensions given in Figure 3 and Table 3 are for reference only.
2. Handle can be used on 14 gauge .075 inch (1.9 mm) to .25 inch (6.4 mm) thick frontplate. 14 gauge shown.
3. Optional padlock handle is available. (See Table 6, Figure 6.)
(69.85 mm) 2.75”
ALL LINE
CONNECTIONS
(10.00 mm)
0.39” HOLE
(137.16 mm) 5.400”
8.32” (211.4 mm)
8.35” (212.0 mm)
4.38” (111.15 mm)
TANK WALL
5.153” (130.89 mm)
TYP
SEE NOTE 3
ARC
BARRIER
LOCKING NUT
FURNISHED WITH SWITCH
A
D
E
BC
.891” (22.63 mm)
F
NO OUTER (LARGE) RING
FOR SINGLE-PHASE SWITCH
Dimensional information
Table 3. Dimensional information for Figures 3 and 4 (inches/mm)
No. of decks/ phases kV ratings and blade type
A
B C
D E F
Horizontal mount
Vertical mount
Horizontal mount
Vertical mount
Horizontal mount
Vertical mount
Horizontal mount
Vertical mount
1 All 8.05" 204 mm
13.3" 338 mm – – 7.16"
182 mm 12.4" 315 mm
0.75" 19 mm
6.00" 152 mm
8.46" 215 mm
13.7" 348 mm
2 All 12.1" 307 mm
17.4" 442 mm
4.09" 104 – 7.16"
182 mm 12.4" 315 mm
0.75" 19 mm
6.00" 152 mm
12.5" 318 mm
17.7" 450 mm
12 kA T-Blade 12 & 16 kA Selector, Straight, & V-Blade
16.2" 411 mm
21.5" 546 mm
4.09" 104 mm
4.09" 104 mm
7.16" 182 mm
12.4" 315 mm
0.75" 19 mm
6.00" 152 mm
16.5" 419 mm
21.7" 551 mm
3 16 kA T-Blade Only
16.7" 424 mm – 4.09"
104 mm 4.09" 104 mm
7.56" 192 mm – 0.75"
19 mm – 16.9" 429 mm –
Catalog Data CA800005EN Effective March 2025
Figure 5. Hole and weld pin placement (Ring-Mount system)
* Exterior mounting surface must be flat within .010" (0.25 mm) over entire area.
** Interior mounting surface must be clear of obstructions.
Figure 4. Line illustration with dimensions of sectionalizing switch with vertical “Ring-Mount” (side view only, refer to Figure 3 for front view)
Notes: 1. Dimensions given in Figure 4 and Table 3 are for reference only.
2. Handle can be used on 14 gauge .075 inch (1.9 mm) to .25 inch (6.4 mm) thick frontplate. 14 gauge shown.
3. Optional padlock handle is available. (See Table 6, Figure 6.)
F
SEE NOTES 3+3
LOCKING NUT
FURNISHED WITH SWITCH
TANK WALL
C B
A
D
E .891”
(22.63 mm)
X = 36 Y = 0
ON EXTERIOR WALL:
Ø .312" DIAMETER X 625" LONG
(8 mm) (16 mm)
(4) WELD PINS
EXTERIOR MOUNTING SURFACE MUST BE
FLAT WITHIN .010 OVER ENTIRE AREA.
INTERIOR MOUNTING SURFACE MUST
BE CLEAR OF OBSTRUCTIONS.RADIUS.140"
(4 mm)**
3.00" (76 mm)
TYPICAL
1.50" (38 mm)
TYPICAL
3.00" (76 mm)
TYPICAL
1.50" (38 mm)
TYPICAL
.662" (17 mm)
DIAMETER 2.00"
(51 mm)*
DIAMETER
6.25"
(159 mm)
1.320" MIN.
(33.5 mm)
DIA. HOLE
Figure 6. Padlockable handle ote: N For use with interlock systems. Will not function with optional limit plate and weld pins.
2.38" (60.3 mm)
.40" (10.2 mm)
.63" (15.9 mm)
2.00" (50.8 mm)
1.50" (38.1 mm)
1.75" (44.5 mm)
Catalog Data CA800005EN Effective March 2025
V-BLADE
BREAK BEFORE MAKE
SELECTOR BLADE
STRAIGHT BLADE
C
ON-OFF
C C
C
C
C
C
CCA
A
A
A
A
A
A
A
A CB
A CB A CB A CB A CB
A CB A
A
C
C
B
B A C B
A CB
B
A
SELECTOR BLADE
1 BLADE SIDE
SELECTOR BLADE
1 BLADE CENTER
TYPICAL DECAL
STENCIL LAYOUT
VIEW OF
CONTACTS FROM
FRONT (HANDLE)
END OF SWITCH
POSITION 1
FRONT SCHEMATIC
AS SHIPPED AND AS
SHOWN AT LEFT
POSITION 2
SWITCH HANDLE
90° CLOCKWISE
FROM POSITION 1
POSITION 3
SWITCH HANDLE
90° CLOCKWISE
FROM POSITION 2
POSITION 4
SWITCH HANDLE
90° CLOCKWISE
FROM POSITION 3
CLOSE
CLOSE
OPEN OPEN OPEN
OPENOPEN
A-C B-C OPEN OPEN
A-C OPEN B-C OPEN
AB-C B-C OPEN A-C
OPEN OPEN
OPEN OPEN
LINE A TO C
OPEN LINE B TO C
LINE A TO C
CLOSE
SWITCH
TYPE
CLOSE
CLOSE
OPEN OPEN
OPEN
OPEN
LINE B TO C
LINES A & B TO C
LINE A ONLY LINE B ONLY
TO C TO C
OPEN (ALL)
BA
A
A
A
(COIL)
B
C (COIL)
C (COIL)
V-BLADE
MAKE BEFORE BREAK
A CB A CB A CB A CB
AB-C B-C OPEN A-C
LINES A & B TO C
LINE A ONLY LINE B ONLY
TO C TO C
OPEN (ALL)
BA
C (COIL)
T-BLADE
BREAK BEFORE MAKE
A C B A C BA C BA C B
AB-C B-C A-B A-C
LINES A & B TO C
LINES A TO B
C OPEN
LINE A ONLY LINE B ONLY
TO C TO C
A C
B
(COIL)
T-BLADE
MAKE BEFORE BREAK
A C B A C BA C BA C B
AB-C B-C A-B A-C
NOTE:
1. SWITCH CENTER IS PIVOT POINT. BLACK SEGMENTS OF BLADE ROTATE.
WHITE OUTLINED SEGMENTS ARE STATIONARY.
2. OTHER POSITION SEQUENCES AVAILABLE – CONSULT FACTORY FOR DETAILS.
LINES A & B TO C
LINE A ONLY LINE B ONLY
TO C TO C
LINES A TO B
C OPEN
A C
B
(COIL)
(COIL)C
(COIL)C
CLOSE
SCHEMATIC SCHEMATIC
A C BA C B
ROTATED ROTATED ROTATED
SCHEMATIC
Table 4. Wiring schematics
Catalog Data CA800005EN Effective March 2025
Four-position sectionalizing loadbreak switches www.eaton.com/cooperpowerseries ztolf Cloud ztolf Text Box optional loadbreak switching options ztolf Text Box ztolf Highlight
SELECTOR BLADE
1 BLADE SIDE
ztolf Highlight
SELECTOR BLADE
1 BLADE CENTER
ztolf Highlight
V-BLADE
BREAK BEFORE MAKE
ztolf Highlight
V-BLADE
MAKE BEFORE BREAK
ztolf Highlight
T-BLADE
BREAK BEFORE MAKE
ztolf Highlight
T-BLADE
MAKE BEFORE BREAK
Ordering information To order a four-position sectionalizing loadbreak switch, specify the switch type desired from Table 4 and then build the catalog number from Table 5.
Additional information Refer to the following reference literature for application recommendations:
MN800002EN, Sectionalizing Switch Installation Instructions
CP0316, Certified Test Report: 12 kA Four-Position Sectionalizing Loadbreak Switch
CP0313, Certified Test Report: 16 kA Four-Position Sectionalizing Loadbreak Switch
① Pad-lockable handle must be ordered separately.
② Recommended for usage with Fit-On™ end clampstick to provide operator with an increased level of mechanical advantage when performing switching operations.)
Table 6. Accessory parts
Description Catalog number Drawing
Pad-lockable Handle ① per Figure 6 Aluminum 2239000B14 4201093N
Clampstick Leverage Tool ② CS125UFLTOOL –
Table 5. Catalog number selection chart
L S 4 R H 3 T 1 2 B 1 2 3 4 5 6 7 8 9 10
CODE PRODUCT
L LOADBREAK
S SWITCH
4 4-POSITION
CODE INSTALLATION
R RING-MOUNT SYSTEM
CODE ORIENTATION
H HORIZONTAL
V VERTICAL
CODE NUMBER OF PHASES
1 ONE
2 TWO
3 THREE
CODE CONTACT RATING
12 12.5 kA (Table 1) 16 16 kA (Table 2)
CODE ENGAGEMENT
B BREAK BEFORE MAKE
M MAKE BEFORE BREAK*
CODE SWITCH TYPE (See Table 4)
V V - BLADE
T T - BLADE
S STRAIGHT BLADE
D SELECTOR BLADE - (SIDE)
R SELECTOR BLADE - (CENTER)
L SELECTOR BLADE - (ON-OFF)
Note: Vertical mount switches have all externally exposed parts made from stainless steel or brass. Horizontal mount switches have all externally exposed parts made from plated steel, aluminum and brass.
* Make before break switches available in V-and T-Blade only.
Eaton, Cooper Power, and Fit-On are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use these trademarks without the prior written consent of Eaton.
IEEE Std C37.71™-2001 standard is a trademark of the Institute of Electrical and Electronics Engineers, Inc., (IEEE). This publication is not endorsed or approved by the IEEE.
IEEE® is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc.
Envirotemp™ and FR3™ are licensed trademarks of Cargill, Incorporated.
Four-position sectionalizing loadbreak switches
Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com
Eaton’s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries
© 2025 Eaton All Rights Reserved Printed in USA Publication No. CA800005EN / ZD30026 March 2025
Catalog Data CA800005EN Effective March 2025