Attachment 9 - Atlanta VAMC Crawl Space ACM Survey Report.pdf
PDF 6 MB Posted
- Attached to
- 508-26-152 | Bus Duct Replacement
- Solicitation number
- 36C24726R0058
About this file
This is a Pre-Renovation Asbestos-Containing Material (ACM) Survey Report for the Joseph Maxwell Cleland Atlanta Veterans Administration Medical Center located at 1670 Clairmont Drive in Decatur, Georgia. The survey was conducted on January 29-30 and February 4-7, 2025, by the Program Support Center, Federal Occupational Health (U.S. Department of Health and Human Services) and reported on March 21, 2025, under project reference numbers A732710, S2025-0002, and SO 739208.
The survey examined approximately 230,000 square feet of crawl space beneath Buildings A, B, and C to identify asbestos-containing materials prior to renovation. The scope included visual inspection and bulk/soil sampling analyzed using PLM method EPA/600/R93/116 for building materials and CARB 435 for soil samples. The survey identified asbestos in multiple materials: Building B (accessible via mechanical rooms GC 347 and GC 346) contained pipe fitting insulation with 2% Amosite and soil with 0.5-3.8% Amosite across approximately 36,500 square feet. Building C contained mastic on fiberglass piping insulation (2% Chrysotile), canvas-wrapped piping insulation (40% Chrysotile), transite-type flue (15% Chrysotile), and pipe fitting insulation (3% Amosite). All identified materials are classified as Class I asbestos work under OSHA requirements and regulated asbestos-containing material (RACM) under NESHAP. The survey recommends development of an asbestos abatement design based on these findings. Supporting documentation includes laboratory analysis reports from Scientific Analytical Institute (NVLAP accredited), staff credentials showing EPA AHERA certification and confined space entry permits, photographic documentation of identified ACM locations, and sample location maps for each building section.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Pre-Renovation Asbestos-Containing Material (ACM) Survey (Inspection and Testing)
Survey Location:
Joseph Maxwell Cleland Atlanta VAMC Department of Veterans Affairs Crawl Space located beneath Buildings A, B, and C 1670 Clairmont Drive Decatur, GA 30033
Survey Date: January 29 & 30 and February 4 & 7, 2025 Report Date: March 21, 2025
Project Reference Numbers: A732710, S2025-0002, SO 739208
Prepared by:
Program Support Center, Federal Occupational Health U.S. Department of Health and Human Services Everett McKinley Dirksen Federal Building (Z1R) 219 South Dearborn | Room 288 Chicago, IL 60604
Table of Contents
EXECUTIVE SUMMARY
Introduction Scope of Work Building and Location Description Bulk and Soil Sampling Results Summary of Identified Asbestos-Containing Materials Sampling Protocol and Methodology Technical Requirements Findings Summary and Recommendations
Appendices
Appendix A: PLM Laboratory Report, including Chain of Custody Appendix B: Approximate Sample Locations Appendix C: Photographic Documentation Appendix D: Staff and Laboratory Credentials Appendix E: Confined Space Entry Permits
Department of Veterans Affairs Crawl Space ACM Survey
Joseph Maxwell Cleland Atlanta March 21, 2025
EXECUTIVE SUMMARY
A pre-renovation asbestos-containing materials (ACM) survey was conducted on January 29 & 30 and February 4 & 7, 2025, in the crawl spaces located beneath buildings A, B, and C of the Joseph Maxwell Cleland Atlanta Veterans Administration Medical Center (VAMC) located at 1670 Clairmont Drive in Decatur, GA. The purpose of testing was to determine if asbestos-containing materials are located in the building materials and soil in the crawl space below the hospital.
The scope of work consisted of evaluation (visual inspection) and testing in the crawl spaces located beneath buildings A, B, and C and included the following:
1. The crawl space area is an asbestos regulated area (OSHA requirements apply).
2. Collection of bulk samples for asbestos will be analyzed per PLM method EPA/600/R-
93/116 (primarily TSI maybe surfacing materials). Soil samples will be analyzed per PLM method CARB 435.
3. Soil samples throughout the crawl spaces beneath buildings A, B and C (approximately 230,000 sf) will be sectioned off into approximately 5,000 SF grids and sampled accordingly.
4. Provide an assessment report that can be used to develop an asbestos abatement cost estimate.
Survey results and findings observed and/or found during this survey identified asbestos in the following materials and locations:
Crawl Space – Building B (accessible through mechanical room GC 347)
• Pipe Fitting Insulation
• Soil
Crawl Space – Building B (accessible through mechanical room GC 346)
• Pipe Fitting Insulation
• Soil
Crawl Space – Building C
• Mastic on Fiberglass Piping Insulation
• Canvas Wrapped Piping Insulation
• Transite-Type Flue
• Pipe Fitting Insulation
Based on the above findings, an asbestos abatement design is recommended.
Joseph Maxwell Cleland Atlanta March 21, 2025
Personnel at all levels were cooperative and participated in this survey. The report that follows this Executive Summary should be read in its entirety because it includes important information not included in this summary, such as task descriptions, workspace locations, regulatory requirements, and additional recommendations.
Introduction
A representative from the Federal Occupational Health (FOH) conducted a pre-renovation asbestos-containing materials (ACM) survey on January 29 & 30 and February 4 & 7, 2025, in the crawl spaces located beneath buildings A, B, and C of the Joseph Maxwell Cleland Atlanta Veterans Administration Medical Center (VAMC) located at 1670 Clairmont Drive in Decatur, GA. This survey was performed under the Interagency Agreement established between [VAMC-Atlanta] and the U.S. Public Health Service (USPHS) Federal Occupational Health (FOH) and in accordance with a scope of work developed specifically for this project.
Mr. Ricky Garmon, Mrs. Erin Garmon, MPH, CIH, Mr. Chad Reynolds, and Mr. Clint Atkins, contractor, performed this inspection on behalf of FOH and under the direction of Ms. Michelle Stemmons, FOH Program Manager, Environmental Health, and Safety Services. Mr. Rodney Hamm, Industrial Hygienist with the Atlanta VAMC Safety Office provided agency support and assisted in the coordination and completion of this testing.
Scope of Work
The scope of work consisted of evaluation (visual inspection) and testing in the crawl spaces located beneath buildings A, B, and C and included the following:
1. The crawl space area is an asbestos regulated area (OSHA requirements apply).
2. Collection of bulk samples for asbestos will be analyzed per PLM method EPA/600/R-
93/116 (primarily TSI maybe surfacing materials). Soil samples will be analyzed per PLM method CARB 435.
3. Soil samples throughout the crawl spaces beneath buildings A, B and C (approximately 230,000 sf) will be sectioned off into approximately 5,000 SF grids and sampled accordingly.
4. Provide an assessment report that can be used to develop an asbestos abatement cost estimate.
Building and Location Description
The Joseph Maxwell Cleland Atlanta Veterans Administration Hospital is located in Decatur, GA and serves as the main VA hospital in the metro Atlanta Area. The crawl space is located under the entire hospital and is separated into sections A, B, and C, and were each constructed at different times. Each section was accessible from a different location.
Bulk and Soil Sampling Results
Tables 1 – 5 below present suspect asbestos-containing materials identified during the inspection and includes Homogeneous Area (Material) (HA) Number, Suspect Asbestos-Containing Material (ACM), Sample ID, and Asbestos Content (% and type). Materials containing asbestos are indicated in red boldface.
See Appendix A for laboratory report and chain of custody.
Table 1 Suspect Asbestos-Containing Materials
Crawl Space – Building A Atlanta VAMC, Decatur, GA
Collected on 1/30/25
Homogenous Area (Material)
(HA)
Suspect Asbestos- Containing Material
(ACM)
Sample ID
Asbestos Content
(% and type)
HA 1 Gray Duct Mastic
ADM-01 NAD
ADM-02 NAD
HA 2 Fireproofing
AFP-03 NAD
AFP-04 NAD
AFP-05 NAD
AFP-06 NAD
AFP-07 NAD
AFP-08 NAD
AFP-09 NAD
HA 3
Chill Water System Piping
Insulation
ACW-10 NAD
ACW-11 NAD
ACW-12 NAD
HA 4
Steam System
Piping Insulation
AST-13 NAD
AST-14 NAD
AST-15 NAD
HA 5
Steam Condensate Piping
Insulation
ASC-16 NAD
ASC-17 NAD
ASC-18 NAD
HA 6 Domestic Hot Water Piping Insulation
ADHW-19 NAD
ADHW-20 NAD
ADHW-21 NAD
HA 7
Domestic Cold-Water
Piping Insulation
ADCW-22 NAD
ADCW-23 NAD
ADCW-24 NAD
HA 8 Soil
AS-01 NAD
AS-02 NAD
AS-03 NAD
AS-04 NAD
AS-05 NAD
AS-06 NAD
Table 2
Crawl Space – Building B- Access through Mechanical Room GC-347 Atlanta VAMC, Decatur, GA
Collected on 2/7/25
Homogenous Area (Material)
(HA)
Suspect Asbestos- Containing Material
HA 9 Fireproofing
BFP-01 NAD
BFP-02 NAD
BFP-03 NAD
BFP-04 NAD
HA 10 Duct Mastic
BDM-05 NAD
BDM-06 NAD
HA 11 Domestic Cold Piping Insulation
BPI-07 NAD
BPI-08 NAD
BPI-09 NAD
HA 12 Domestic Cold Pipe Fittings
BPF-10 NAD
BPF-11 NAD
BPF-12 NAD
HA 13
Domestic Hot
Piping Insulation
BPI-13 NAD
BPI-14 NAD
BPI-15 NAD
HA 14 Domestic Hot Pipe Fittings
BPF-16 2% Amosite BPF-17 2% Amosite
BPF-18 NAD
HA 15
Low Pressure Steam
Piping Insulation
BPI-19 NAD
BPI-20 NAD
BPI-21 NAD
HA 16 Low Pressure Steam Pipe Fittings
BPF-22 NAD
BPF-23 NAD
BPF-24 NAD
HA 17 Soil
B1 NAD
B2 3.3% Amosite B3 3.8% Amosite B4 2.8% Amosite
Table 3
Crawl Space – Building B- Access through Mechanical Room GC-346 Atlanta VAMC, Decatur, GA
Collected on 2/7/25
Homogenous Area (Material)
(HA)
Suspect Asbestos- Containing Material
HA 18 Fireproofing
BFP-31 NAD
BFP-32 NAD
BFP-33 NAD
HA 19
Cold Water
Piping Insulation
BPI-34 NAD
BPI-35 NAD
BPI-36 NAD
HA 20
Cold Water Pipe Fittings
BPF-37 NAD
BPF-38 2% Chrysotile
BPF-39 NAD
HA 21
Hot Water
Piping Insulation
BPI-40 NAD
BPI-41 NAD
BPI-42 NAD
HA 22
Hot Water
Pipe Fittings
BPF-43 2% Amosite BPF-44 2% Amosite BPF-45 2% Amosite
HA 23 Duct Mastic
BDM-46 NAD
BDM-47 NAD
HA 24 Soil B5 3.5% Amosite B6 0.5% Amosite
B8 NAD
HA 25 Debris on Ground B7 NAD
Table 4 Suspect Asbestos-Containing Materials
Crawl Space – Building C – East Side, Accessible Near Room BC106I Atlanta VAMC, Decatur, GA
Collected on 1/29/25
Homogenous Area (Material)
(HA)
Suspect Asbestos- Containing Material
HA 26 Piping Insulation – ¾”
C-1 NAD
C-2 NAD
C-3 NAD
HA 27 Piping Insulation – 1”
C-4 NAD
C-5 NAD
C-6 NAD
C-7 NAD
C-8 NAD
C-9 4% Chrysotile – black mastic
HA 28 Piping Insulation – 2”
C-10 NAD
C-11 NAD
C-12 NAD
HA 29 Piping Insulation
C-13 NAD
C-14 NAD
C-15 NAD
HA 30 Fireproofing
C-16 NAD
C-17 NAD
C-31 NAD
HA 31 Foam Glass Piping Insulation
C-20 NAD
C-21 NAD
C-22 NAD
HA 32 Black Mastic
C-23 NAD
C-24 NAD
HA 33 Duct Insulation
C-25 NAD
C-26 NAD
C-27 NAD
HA 34 Fiberglass Piping Insulation
C-28 NAD
C-29 NAD
C-30 NAD
HA 35 Debris on Ground
C-18 NAD
C-19 NAD
C-32 NAD
C-33 NAD
C-34 NAD
C-35 NAD
C-36 NAD
C-37 NAD
C-38 NAD
C-39 NAD
C-40 NAD
Table 5
Crawl Space – Building C – West Side, Accessible through Room BA106 Atlanta VAMC, Decatur, GA
Collected on 1/30/25
Homogenous Area (Material)
(HA)
Suspect Asbestos- Containing Material
HA 36 Canvas Wrapped Piping Insulation
CCP-1 40% Chrysotile CCP-2 40% Chrysotile CCP-3 40% Chrysotile
HA 37 Gray Duct Mastic
CGD-1 NAD
CGD-2 NAD
HA 38 Transite-type Flue CTR-1 15% Chrysotile CTR-2 15% Chrysotile
HA 39 Fireproofing
CFP-1 NAD
CFP-2 NAD
CFP-3 NAD
HA 40 Fiberglass Piping Insulation
CPI-1 NAD
CPI-2 NAD
CPI-3 NAD
HA 41 Pipe Fitting Insulation CPF-1 3% Amosite CPF-2 3% Amosite CPF-3 3% Amosite
HA 42 Debris on Ground
CD-1 NAD
CD-2 NAD
CD-3 NAD
CD-4 NAD
CD-5 NAD
CD-6 NAD
CD-7 NAD
CD-8 NAD
CD-9 NAD
Notes:
1. NAD: No Asbestos Detected
2. If suspect ACM not identified in this report are encountered during disturbance activities, additional sampling may be warranted.
Summary of Identified Asbestos-Containing Materials
The results of laboratory analysis by PLM (or assumed ACM – see note 4. below) indicated asbestos was detected in the following specifically targeted suspect materials identified in tables 6-8 below.
Table 6
Identified Asbestos-Containing Materials Crawl Space – Building B- Access through Mechanical Room GC-347
Atlanta VAMC, Decatur, GA
Asbestos-Containing Material (ACM) Asbestos Content Quantity
OSHA
Class of Work (I or II)
NESHAP
Category
Pipe Fitting Insulation 2% Amosite 80-100 EA: <6” D Class I RACM
Soil
2.8 – 3.8 %
Amosite 20,000 SF Class I RACM
Table 7 Identified Asbestos-Containing Materials
Crawl Space – Building B- Access through Mechanical Room GC-346 Atlanta VAMC, Decatur, GA
Asbestos-Containing Material (ACM)
Asbestos Content Quantity
Pipe Fitting Insulation 2% Chrysotile 2% Amosite
125-150 EA: <6” D Class I RACM
Soil
0.5 – 3.5 %
Amosite 16,500 SF Class I RACM
Table 8 Identified Asbestos-Containing Materials
Crawl Space – Building C Atlanta VAMC, Decatur, GA
Asbestos-Containing Material (ACM)
Asbestos Content Quantity
Black Mastic on Fiberglass Piping
Insulation w/ Fittings 2% Chrysotile
175 LF Piping 30-50 Fittings:
<6” D
Mastic- Class II Fittings- Class I
Mastic- Cat I Fittings-
RACM
Canvas Wrapped Piping Insulation
40% Chrysotile 250 LF: 6” D Class I RACM
Transite-type Flue 15% Chrysotile
350 LF: <12” D
250 LF: >12” D Class II
RACM or Cat II
Pipe Fitting Insulation Assumed >1% 225-280 EA: <6” D Class I RACM
Notes:
1. LF – Linear Feet
2. EA – Each
3. D – Diameter
4. Quantities and Diameters are approximate.
5. Assumed >1% indicates the material tested positive in other locations or is historically presumed to contain asbestos.
6. “OSHA Class of Work” refers to the manner in which the abatement project will be conducted based on the material being abated as defined by OSHA.
a) Class I Asbestos Work - means activities involving the removal of thermal system insulation or surfacing material and PACM.
b) Class II Asbestos Work - means activities involving the removal of ACM which is not thermal system insulation or surfacing material. This includes, but is not limited to, the removal of asbestos-containing wallboard, floor tile and sheeting, roofing and siding shingles, and construction mastics.
7. “NESHAP Category” refers to the EPAs classification of ACM which can determine the notification, disturbance, or disposal requirements.
a) Regulated asbestos-containing material (RACM) means
i. Friable asbestos material,
ii. Category I nonfriable ACM that has become friable,
iii. Category I nonfriable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or
iv. Category II nonfriable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations regulated by this subpart.
b) Category I nonfriable asbestos-containing material (ACM) means asbestos-containing packings, gaskets, resilient floor covering, and asphalt roofing products containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy.
c) Category II nonfriable ACM means any material, excluding Category I nonfriable ACM, containing more than 1 percent asbestos as determined using the methods specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
Sampling Protocol and Methodology
This survey used substantial guidance from the AHERA sampling protocol.
The AHERA sampling protocol places suspect ACM in one of the following categories, to determine sample collection criteria:
• Surfacing Materials – Material that has been sprayed on, troweled on, or otherwise applied to surfaces (structural members, walls, ceilings, etc.) for acoustical, decorative, fireproofing, or other purposes.
• Thermal System Insulation (TSI) - Insulation used to control heat transfer or prevent condensation. Examples include insulation on piping systems, tanks, etc.
• Miscellaneous Materials - Materials that are not classified under surfacing or TSI are Miscellaneous materials (floor tile / mastic, roofing materials, caulks, etc.).
The survey protocol consists of identifying suspect ACM by homogeneous area or material (the terms area and material may be used interchangeably) and sampling each in accordance with the AHERA criteria, at a minimum.
A homogeneous material is defined as having similar color, texture, and general appearance. A homogeneous material may be in one location or multiple locations throughout a facility. The use of the material and the date of installation, if known, may further define a homogeneous material. It should be noted that the same descriptive material may consist of a separate homogenous area / material based on a different application.
In accordance with the AHERA protocol, all samples collected from a homogeneous area / material must be negative for the presence of asbestos, analyzed by polarized light microscopy (PLM), for the homogeneous material to be considered a non-asbestos-containing material https://www.ecfr.gov/current/title-40/part-763 https://www.ecfr.gov/current/title-40/part-763
Based on analytical results, the AHERA Inspector may redefine the homogenous material and sample accordingly for asbestos content determination.
Bulk samples are collected from suspect ACM identified during the field inspection activities.
The number of samples collected and a description for each homogeneous material is recorded, along with an estimated quantity and condition. The location of the homogenous material and each sample is recorded on sample logs and floor plans provided by the client or field sketches.
With the owner’s approval, some suspect materials (i.e., 9” x 9” floor tile, black flooring mastic, air cell-type insulation, roofing materials, concealed insulation, wiring insulation, fire doors, etc.) may be presumed to contain asbestos based primarily on 1) historical data, 2) knowledge and experience of the accredited Inspector and 3) inaccessibility during the survey phase.
Presumed ACM may be sampled later, typically in the abatement design phase, or treated as presumed ACM.
In accordance with NESHAP, materials determined to contain 1% or less asbestos content, by polarized light microscopy (PLM), can be treated as an asbestos-containing material (> 1 %) or point counted for confirmation the material does not contain greater than one percent (> 1 %) asbestos content. Materials containing one (1) % or less asbestos content, confirmed by point counting, do not fall under NESHAP notification, disturbance, or disposal requirements but do fall under Occupational Safety and Health Administration (OSHA) and EPA worker protection requirements, and other regulations may be applicable.
Technical Requirements
Field inspection and sampling was conducted by Environmental Protection Agency (EPA) Asbestos Hazard Emergency Response Act (AHERA) accredited Inspectors. Sample analysis was performed utilizing polarized light microscopy (PLM) by a laboratory that successfully participates in the National Institute of Standards and Technology (NIST), National Voluntary Laboratory Accreditation Program (NVLAP).
PEM’s industrial hygiene asbestos program is managed by an EPA AHERA accredited Supervisor, Designer, and Inspector and Management Planner, with technical oversight by a Certified Industrial Hygienist (CIH). The project was conducted under the direction of an “Environmental Professional” meeting the definition in Appendix X2 of American Society for Testing and Materials (ASTM) international, Standard Practices E1527-21.
This inspection complied with pre-renovation / demolition inspection requirements of 40 CFR Part 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP). The survey protocol utilizes substantial guidance from ASTM International Standard Practice for Comprehensive Building Asbestos Surveys (ASTM E2356-18).
Findings Summary and Recommendations
Survey results and findings observed and/or found during this survey identified asbestos in the following materials and locations:
Crawl Space – Building B (accessible through mechanical room GC 347)
• Soil
Crawl Space – Building B (accessible through mechanical room GC 346)
• Soil
Crawl Space – Building C
• Mastic on Fiberglass Piping Insulation
• Canvas Wrapped Piping Insulation
• Transite-Type Flue
Based on the above findings, an asbestos abatement design is recommended.
Appendix A
PLM Laboratory Report, including Chain of Custody
Bulk Asbestos Analysis By Polarized Light Microscopy EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074920Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg A Date Reported: 02/14/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
ADM-01
10074920_0002
Gray Duct Mastic
None Detected 100% Other
Non-Fibrous
Crushed, Dissolved
Gray
Homogeneous
ADM-02
10074920_0003
Gray Duct Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Gray
Homogeneous
AFP-03
10074920_0004
Fireproofing
None Detected 35% Cellulose 65% Other
Fibrous
Teased
Gray
Homogeneous
AFP-04
10074920_0005
Fireproofing
None Detected 35% Cellulose 65% Other
Fibrous
Teased
Gray
Homogeneous
AFP-05
10074920_0006
Fireproofing
None Detected 35% Cellulose 65% Other
Fibrous
Teased
Gray
Homogeneous
AFP-06
10074920_0007
Fireproofing
None Detected 35% Cellulose 65% Other
Fibrous
Teased
Gray
Homogeneous
AFP-07
10074920_0008
Fireproofing
None Detected 35% Cellulose 65% Other
Fibrous
Teased
Gray
Homogeneous
AFP-08
10074920_0009
Fireproofing
None Detected 35% Cellulose 65% Other
Fibrous
Teased
Gray
Homogeneous
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Charmel Dozier (24)
Analyst Approved Signatory
Page 1 of 3P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074920Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg A Date Reported: 02/14/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
AFP-09
10074920_0010
Fireproofing
None Detected 35% Cellulose 65% Other
Fibrous
Teased
Gray
Homogeneous
ACW-10
10074920_0011
Chill Water System Pipe Insulation
None Detected 40% 20% 5%
Fiber Glass Cellulose Wollastonite
35% Other
Fibrous
Ashed
White, Yellow
Homogeneous wrap on fiberglass insulation
ACW-11
10074920_0012
Chill Water System Pipe Insulation
None Detected 40% 20% 5%
Fiber Glass Cellulose Wollastonite
35% Other
Fibrous
Ashed
Yellow, White
Homogeneous wrap on fiberglass insulation
ACW-12
10074920_0013
Chill Water System Pipe Insulation
None Detected 15% 5% 5%
Fiber Glass Cellulose Wollastonite
75% Other
Fibrous
Ashed
White
Homogeneous wrap on wood block
AST-13
10074920_0014
Steam System Pipe Insulation
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
Yellow, White
Homogeneous wrap on fiberglass
AST-14
10074920_0015
Steam System Pipe Insulation
None Detected 50% 3% 2%
Fiber Glass Wollastonite Cellulose
45% Other
Fibrous
Ashed
White, Yellow
Homogeneous wrap on fiberglass
AST-15
10074920_0016
Steam System Pipe Insulation
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
White, Yellow
Homogeneous wrap on fiberglass
ASC-16
10074920_0017
Steam Condensate Piping
None Detected 40% 30% 3%
Fiber Glass Cellulose Wollastonite
27% Other
Fibrous
Ashed
Yellow, White
Homogeneous wrap on fiberglass
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Charmel Dozier (24)
Page 2 of 3P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074920Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg A Date Reported: 02/14/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
ASC-17
10074920_0018
Steam Condensate Piping
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
Yellow, White
Homogeneous wrap on fiberglass
ASC-18
10074920_0019
Steam Condensate Piping
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
White, Yellow
Homogeneous wrap on fiberglass
ADHW-19
10074920_0020
Domestic Hot Water Piping
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
Yellow, White
Homogeneous wrap on fiberglass
ADHW-20
10074920_0021
Domestic Hot Water Piping
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
White, Yellow
Homogeneous wrap on fiberglass
ADHW-21
10074920_0022
Domestic Hot Water Piping
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
Yellow, White
Homogeneous wrap on fiberglass
ADCW-22
10074920_0023
Domestic Cold Water Piping
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
White, Yellow
Homogeneous wrap on fiberglass
ADCW-23
10074920_0024
Domestic Cold Water Piping
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
White, Yellow
Homogeneous wrap on fiberglass
ADCW-24
10074920_0025
Domestic Cold Water Piping
None Detected 50% 30%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
White
Homogeneous wrap on fiberglass
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Charmel Dozier (24)
Page 3 of 3P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Cllent:
Contact:
Address:
Phone:
Fax:
Email:
Project:
Client Notes:
P.O.#.
Date Submitted:
Analysts:
TurnAroundTime:
ISample Number <c <<
ADM-01
ADM-02
AFP-03
AFP-04
AFP-05
AFP-06
AFP-07
AFP-08
AFP-09
ACW-10
ACW-11
ACW-12
AST-13
AST-14
AST-15
ASC-16
Relinquished By
\b"b1Uqi,o Professional Environmental Manag, •1natr11ctlons:
Erin Garmon Use Column -s• for your contact info 3915 Harrison Road, STE 400, Loganville, GA 30052 678-687 -4630 I To See an Example Click the [Enter fax here] bottom Example Tab.
engarmon@gem-en~.com
Enter samples between •cc• and ">>" Atlanta VA, Crawl Space - Bldg A peg1n Sampl• with a •c< •at,ove the first samplt Sdentfflc and end with• ">>• below the last sample. I Analytical Only Enter your data on the first sheet •sheet1 • Institute OJ>J
[Enter P.O. # Here]
PLM
5 day_
Data1
2/12/2025 0:00 Note: Data 1 and Data 2 are optional fields that do not show up on the official report, however they will be included in the electronic data returned to you to facilitate vour reintearatlon of the report data.
Sample Description
Grav Duct Mastic Grav Duct Mastic Fireoroofina Fireoroofina Fireoroofina Fireoroofina Fireoroofina Fireoroofina Fireoroofina Chill Water Svstem Pioe Insulation Chill Water Svstem Pioe Insulation Chill Water Svstem Pipe Insulation Steam System Pioe Insulation Steam System Pioe Insulation Steam Svstem Pioe Insulation ~ Steam Condensate PipinQ _I\ \; I;)
4604 Dundas Drive Greensboro, NC 27407 Phone: 336.292.3888
Fax: 336.292.33l3 Email: labOsailab.com
Data2
Collected 1 /30/25 Collected 1/30/25 Collected 1 /30/25 Collected 1 /30/25 Collected 1 /30/25 Collected 1 /30/25 Collected 1 /30/25 Collected 1 /30/25 Collected 1/30/25 Collected 1/30/25 Collected 1/30/25 Collected 1/30/25 Collected 1 /30/25 Collected 1 /30/25 Collected 1 /30/25 Collected 1/30/25
Received By
1,-\·i \n:WCWV\..- Ricky Garmon __________ _
~Gr,eF---:V '!.,,0~
~e\eG ~ le tr1 t;t 01 ~-o ASC-17 Steam Condensate Pipino Collected 1/30/25
ASC-18 Steam Condensate Pipino Collected 1 /30/25
ADHW-19 Domestic Hot Water Piping Collected 1/30/25
ADHW-20 Domestic Hot Water Pipino Collected 1/30/25
ADHW-21 Domestic Hot Water Pioina Collected 1 /30/25
ADCW-22 Domestic Cold Water Pipino Collected 1/30/25
ADCW-23 Domestic Cold Water Pipino Collected 1/30/25
ADCW-24 Domestic Cold Water Piping Collected 1 /30/25
Received By
Relinquished By Ricky Garmon __________ _
Determination of Asbestos Content by Polarized Light Microscopy
California Air Resources Board (CARB) Method 435; to 0.1%*
Client: Professional Environmental Management
Attn: Erin Garmon Lab Order ID: 10074929
3915 Harrison Road Suite 408 Date Received: 02/12/2025 Loganville, GA 30052 Date Reported: 02/19/2025 Project: Atlanta VA, Crawl Space - Bldg A Page: 1 of 1
Byron Stroble ___________________________________ Analyst Lab Director
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
P-F-005 EXP: 3/1/2023
Sample ID Description
ASBESTOS
Lab Sample ID Lab Notes
AS-01 Soil None Detected
AS-02 Soil
AS-03 Soil
AS-04 Soil
AS-05 Soil
AS-06 Soil
Notes: The CARB 435 method was designed as applicable to the determination of asbestos in ultramafic or serpentine rock aggregates. The detection limit of 0.1% is based on 1,000 points counted on a petrographic microscope (PLM), of a representative rock flour of the sample(s) submitted. These results apply only to the material as submitted to SAI, Inc.
Client:
Address:
Phone:
Fax:
Email:
Project:
Client Notes:
P.O.#.
Date Submitted:
Analysis:
TurnAroundTime:
[Sample Number
AS-01
AS-02
AS-03
AS-04
AS-05
AS-06
Relinquished By
Professional Environmental Manag, *Instructions:
Erin Garmon Use Column "Bn for your contact info
\tD\Yq19 3915 Harrison Road, STE 400, Loganville, GA 30052 678-687-4630 I To See an Example Click the [Enter fax here] bottom Example Tab.
engarmon@pem-env.com
Enter samples between "<<" and ">>" Atlanta VA, Crawl Space - Bldg A pegin Samples with a "<< "above the first samplE Scientific and end with a ">>" below the last sample. I Analytical
[Enter P.O. # Here] 2/12/2025 0:00
Soil 5 day
Data 1
Only Enter your data on the first sheet "Sheet1" Institute
Note: Data 1 and Data 2 are optional fields that do not show up on the official report, however they will be included in the electronic data returned to you to facilitate your reintegration of the report data.
Sampl~ .. D~scription
Soil Soil Soil Soil Soil Soil
A-
4604 Dundas Drive Greensboro, NC 27407 Phone: 336.292.3888
Fax: 336.292.3313 Email: lab@sailab.com
Data 2
Collected 2/4/25 Collected 2/4/25 Collected 2/4/25 Collected 2/4/25 Collected 2/4/25 Collected 2/4/25
J r ~ Received By
Ricky Garmon __________ _ f}j 1-i I D -?J
0CLW-J
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074918Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Date Amended:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg B. 2/7/2025 Date Reported: 02/19/2025
02/20/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
BFP-01
10074918_0002
Fireproofing
None Detected 80% Fiber Glass 20% Other
Fibrous
Teased
Gray
Homogeneous
BFP-02
10074918_0003
Fireproofing
None Detected 80% Fiber Glass 20% Other
Fibrous
Teased
Gray
Homogeneous
BFP-03
10074918_0004
Fireproofing
None Detected 80% Fiber Glass 20% Other
Fibrous
Teased
Gray
Homogeneous
BFP-04
10074918_0005
Fireproofing
None Detected 80% Fiber Glass 20% Other
Fibrous
Teased
Gray
Homogeneous
BDM-05
10074918_0006
Duct Mastic
None Detected 100% Other
Non-Fibrous
Ashed
Gray
Homogeneous
BDM-06
10074918_0007
Duct Mastic
None Detected 100% Other
Non-Fibrous
Ashed
Gray
Homogeneous
BPI-07 - A
10074918_0008
Domestic Cold
None Detected 40% 40%
Fiber Glass Cellulose
20% Other
Fibrous
Teased
White, Silver
Homogeneous wrap/mastic
BPI-07 - B
10074918_0043
Domestic Cold
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Patrick Yarnell (61)
Page 1 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074918Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Date Amended:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg B. 2/7/2025 Date Reported: 02/19/2025
02/20/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
BPI-08 - A
10074918_0009
Domestic Cold
None Detected 20% 20%
Fiber Glass Cellulose
60% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap/mastic
BPI-08 - B
10074918_0044
Domestic Cold
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPI-09 - A
10074918_0010
Domestic Cold
None Detected 20% 20%
Fiber Glass Cellulose
60% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap/mastic
BPI-09 - B
10074918_0045
Domestic Cold
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPF-10
10074918_0011
Domestic Cold Fittings
None Detected 80% Mineral Wool 20% Other
Non-Fibrous
Dissolved
Gray
Homogeneous
BPF-11
10074918_0012
Domestic Cold Fittings
None Detected 80% Mineral Wool 20% Other
Non-Fibrous
Dissolved
Gray
Homogeneous
BPF-12 - A
10074918_0013
Domestic Cold Fittings
None Detected 95% Cellulose 5% Other
Fibrous
Teased
Tan
Homogeneous wrap/mastic 1
BPF-12 - B
10074918_0046
Domestic Cold Fittings
None Detected 80% Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous insulation
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Patrick Yarnell (61)
Page 2 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074918Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Date Amended:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg B. 2/7/2025 Date Reported: 02/19/2025
02/20/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
BPF-12 - C
10074918_0047
Domestic Cold Fittings
None Detected 40% 40%
Cellulose Fiber Glass
20% Other
Fibrous
Teased
White, Black
Homogeneous wrap/mastic 2
BPF-12 - D
10074918_0048
Domestic Cold Fittings
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation 2
BPI-13 - A
10074918_0014
Domestic Hot
None Detected 40% 40%
Mineral Wool Cellulose
20% Other
Fibrous
Ashed
Silver, White
Homogeneous wrap/mastic
BPI-13 - B
10074918_0049
Domestic Hot
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPI-14 - A
10074918_0015
Domestic Hot
None Detected 40% 40%
Mineral Wool Cellulose
20% Other
Fibrous
Ashed
Silver, White
Homogeneous wrap/mastic
BPI-14 - B
10074918_0050
Domestic Hot
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPI-15 - A
10074918_0016
Domestic Hot
None Detected 40% 40%
Cellulose Fiber Glass
20% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap/mastic
BPI-15 - B
10074918_0051
Domestic Hot
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Patrick Yarnell (61)
Page 3 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074918Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Date Amended:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg B. 2/7/2025 Date Reported: 02/19/2025
02/20/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
BPF-16
10074918_0017
Domestic Hot Fittings
78%2% Amosite Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous
BPF-17
10074918_0018
Domestic Hot Fittings
78%2% Amosite Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous
BPF-18
10074918_0019
Domestic Hot Fittings
None Detected 80% Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous
BPI-19 - A
10074918_0020
Low Pressure Steam
None Detected 20% 20%
Cellulose Fiber Glass
60% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap/mastic
BPI-19 - B
10074918_0052
Low Pressure Steam
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPI-20 - A
10074918_0021
Low Pressure Steam
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPI-20 - B
10074918_0053
Low Pressure Steam
None Detected 100% Other
Non-Fibrous
Dissolved
Black
Homogeneous tar
BPI-21 - A
10074918_0022
Low Pressure Steam
None Detected 20% 20%
Fiber Glass Cellulose
60% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap/mastic
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Patrick Yarnell (61)
Page 4 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074918Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Date Amended:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg B. 2/7/2025 Date Reported: 02/19/2025
02/20/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
BPI-21 - B
10074918_0054
Low Pressure Steam
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPF-22 - A
10074918_0023
Low Pressure Steam Fittings
None Detected 95% Cellulose 5% Other
Fibrous
Teased
Tan
Homogeneous wrap
BPF-22 - B
10074918_0055
Low Pressure Steam Fittings
None Detected 80% Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous insulation
BPF-23
10074918_0024
Low Pressure Steam Fittings
None Detected 80% Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous
BPF-24 - A
10074918_0025
Low Pressure Steam Fittings
None Detected 99% Cellulose 1% Other
Fibrous
Teased
Tan
Homogeneous wrap
BPF-24 - B
10074918_0056
Low Pressure Steam Fittings
None Detected 80% Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous insulation
BFP-31
10074918_0026
Fireproofing
None Detected 80% Mineral Wool 20% Other
Fibrous
Dissolved
Gray
Homogeneous
BFP-32
10074918_0027
Fireproofing
None Detected 80% Mineral Wool 20% Other
Fibrous
Dissolved
Gray
Homogeneous
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Patrick Yarnell (61)
Page 5 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074918Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Date Amended:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg B. 2/7/2025 Date Reported: 02/19/2025
02/20/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
BFP-33
10074918_0028
Fireproofing
None Detected 80% Mineral Wool 20% Other
Fibrous
Dissolved
Gray
Homogeneous
BPI-34 - A
10074918_0029
Cold Water Runs
None Detected 40% 40%
Cellulose Fiber Glass
20% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap/mastic
BPI-34 - B
10074918_0057
Cold Water Runs
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPI-35 - A
10074918_0030
Cold Water Runs
None Detected 40% 40%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap/mastic
BPI-35 - B
10074918_0058
Cold Water Runs
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPI-36 - A
10074918_0031
Cold Water Runs
None Detected 40% 40%
Fiber Glass Cellulose
20% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap/mastic
BPI-36 - B
10074918_0059
Cold Water Runs
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPF-37
10074918_0032
Cold Water Fittings
None Detected 80% Mineral Wool 20% Other
Fibrous
Crushed
Gray
Homogeneous
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Patrick Yarnell (61)
Page 6 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074918Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Date Amended:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg B. 2/7/2025 Date Reported: 02/19/2025
02/20/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
BPF-38
10074918_0033
Cold Water Fittings
80%2% Chrysotile Mineral Wool 18% Other
Non-Fibrous
Crushed
Gray
Homogeneous
BPF-39
10074918_0034
Cold Water Fittings
None Detected 80% Mineral Wool 20% Other
Fibrous
Crushed
Gray
Homogeneous
BPI-40 - A
10074918_0035
Hot Water Runs
None Detected 70% 10%
Cellulose Fiber Glass
20% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap
BPI-40 - B
10074918_0060
Hot Water Runs
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPI-41 - A
10074918_0036
Hot Water Runs
None Detected 70% 10%
Cellulose Fiber Glass
20% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap
BPI-41 - B
10074918_0061
Hot Water Runs
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
BPI-42 - A
10074918_0037
Hot Water Runs
None Detected 70% 10%
Cellulose Fiber Glass
20% Other
Fibrous
Ashed
White, Silver
Homogeneous wrap
BPI-42 - B
10074918_0062
Hot Water Runs
None Detected 99% Fiber Glass 1% Other
Fibrous
Teased
Yellow
Homogeneous insulation
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Patrick Yarnell (61)
Page 7 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10074918Customer: Professional Environmental Management 3915 Harrison Road Suite 400 Loganville, GA 30052
Analysis:
Date Received:
Date Amended:
Erin Garmon
PLM
02/12/2025
Project: Atlanta VA, Crawl Space - Bldg B. 2/7/2025 Date Reported: 02/19/2025
02/20/2025
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
BPF-43
10074918_0038
Hot Water Fittings
78%2% Amosite Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous
BPF-44
10074918_0039
Hot Water Fittings
78%2% Amosite Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous
BPF-45
10074918_0040
Hot Water Fittings
78%2% Amosite Mineral Wool 20% Other
Non-Fibrous
Crushed
Gray
Homogeneous
BDM-46
10074918_0041
Duct Mastic
None Detected 5% Wollastonite 95% Other
Non-Fibrous
Ashed
Red
Homogeneous
BDM-47
10074918_0042
Duct Mastic
None Detected 5% Wollastonite 95% Other
Non-Fibrous
Ashed
Red
Homogeneous
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Patrick Yarnell (61)
Page 8 of 8P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
BFP-01
BFP-02
BFP-03
BFP-04
BDM-05
BDM-06
BPl-07 BPl-08 BPl-09
BPF-10
BPF-11
BPF-12
BPl-13 BPl-14 BPl-15
BPF-16
Relinquished By Ricky Garmon
.µJ\J Professional Environmental Manag Erin Garmon 3915 Harrison Road, STE 400, Log 678-687-4630 [Enter fax here] enqarmon@pem-env.com
Atlanta VA, Crawl Space - Bldg B.
2/7/2025
[Enter P.O. # Here] 2/12/2025 0:00
I 001Lf0J/8
Fireoroofina Collected on 2/7/25 Fireoroofina Collected on 2/7 /25 Fireoroofina Collected on 2/7 /25 Duct Mastic Collected on 2/7 /25 Duct Mastic Collected on 2/7 /25 Domestic Cold Collected on 2/7 /25 Domestic Cold Collected on 2/7 /25 Domestic Cold Collected on 2/7 /25 Domestic Cold Fittinas Collected on 2/7 /25 Domestic Cold Fittinas Collected on 2/7 /25 Domestic Cold Fittings Collected on 2/7 /25 Domestic Hot Collected on 2/7 /25 Domestic Hot Collected on 2/7 /25 Domestic Hot ··· .
Collected on 2/7/25 Dome#ic Hot Fittings Collected on 2/7/25
Received By .
v(l 1 Rejected □ J-7o y ·q { §
BPF-17 Domestic Hot Fittinqs Collected on 217125 BPF-18 Domestic Hot Fittings Collected on 217125 BPl-19 Low Pressure Steam Collected on 2/7 /25 BPl-20 Low Pressure Steam Collected on 217125 BPl-21 Low Pressure Steam Collected on 217125 BPF-22 Low Pressure Steam Fittings Collected on 217125 BPF-23 Low Pressure Steam Fittings Collected on 2/7/25 BPF-24 Low Pressure Steam Fittings Collected on 2/7 /25 BFP-31 Fireproofing Collected on 2/7 /25 BFP-32 Fireproofinq Collected on 217125 BFP-33 Fireproofing Collected on 2/7 /25 BPl-34 Cold Water Runs Collected on 2/7 /25 BPl-35 Cold Water Runs Collected on 2/7 /25 BPl-36 Cold Water Runs Collected on 2/7 /25 BPF-37 Cold Water Fittings Collected on 2/7 /25 BPF-38 Cold Water Fittings Collected on 217125 BPF-39 Cold Water Fittings Collected on 2/7 /25 BPl-40 Hot Water Runs Collected on 2/7/25 BPl-41 Hot Water Runs Collected on 217125 BPl-42 Hot Water Runs Collected on 2/7125 BPF-43 Hot Water Fittings Collected on 217125 BPF-44…