VAMC – Birmingham 700 South 19th Street Asbestos-Re-Inspection Evaluation
Assessed by: Berej Patel / Dana Tilton
Sample Location: Homogeneous Area ID: Date:
5th Floor, Research Building R5-03 6 Feb 14
Homogeneous Area Description TSI behind access panel
Inspector Comments TSI behind locked access panel in 5th floor Research corridor. Assumed positive from previous reports.
Recommended Response Action In good condition
Physical Assessment ☒ 1. Damaged or significantly damaged thermal system insulation (TSI) ACM ☐ 2. Damaged friable surfacing ACM ☐ 3. Significantly damaged friable surfacing ACM ☐ 4. Damaged or significantly damaged friable miscellaneous ACM ☐ 5. ACBM with potential for damage ☐ 6. ACBM with potential for significant damage ☐ 7. Any remaining friable ACBM ☐ 8. No asbestos detected.
Assessed by: Berej Patel / Dana Tilton
Sample Location: Homogeneous Area ID: Date:
5th Floor, Research Building R5-04 6 Feb 14
Lab hood in SP5719
Lab hood in SP5719 assumed positive from previous reports
☐ 1. Damaged or significantly damaged thermal system insulation (TSI) ACM ☐ 2. Damaged friable surfacing ACM ☐ 3. Significantly damaged friable surfacing ACM ☐ 4. Damaged or significantly damaged friable miscellaneous ACM ☒ 5. ACBM with potential for damage ☐ 6. ACBM with potential for significant damage
Assessed by: Berej Patel / Dana Tilton
Sample Location: Homogeneous Area ID: Date:
5th Floor, Research Building R5-05 6 Feb 14
Transite pipes (cut and capped) from Lab hood in SP5719
Transite pipes (cut and capped) from Lab hood in SP5719 assumed positive from previous reports
☐ 2. Damaged friable surfacing ACM ☐ 3. Significantly damaged friable surfacing ACM ☐ 4. Damaged or significantly damaged friable miscellaneous ACM ☒ 5. ACBM with potential for damage ☐ 6. ACBM with potential for significant damage
Assessed by: Berej Patel / Dana Tilton
Sample Location: Homogeneous Area ID: Date:
5th Floor, Research Building R5-06 6 Feb 14
TSI on large vertical pipe in room 5716
TSI is on large vertical pipe in room 5716 assumed positive from previous report. Approx. 50 LF
☒ 1. Damaged or significantly damaged thermal system insulation (TSI) ACM ☐ 2. Damaged friable surfacing ACM ☐ 3. Significantly damaged friable surfacing ACM ☐ 4. Damaged or significantly damaged friable miscellaneous ACM ☐ 5. ACBM with potential for damage ☐ 6. ACBM with potential for significant damage
Assessed by: Berej Patel / Dana Tilton
Sample Location: Homogeneous Area ID: Date:
5th Floor, Research Building R5-07 6 Feb 14
Transite Wall Panels – contains more than 50% Chrysotile Asbestos
Transite wall panels on the exterior of Research wing on all levels – approximately 4,000 SF
☐ 2. Damaged friable surfacing ACM ☐ 3. Significantly damaged friable surfacing ACM ☐ 4. Damaged or significantly damaged friable miscellaneous ACM ☒ 5. ACBM with potential for damage ☐ 6. ACBM with potential for significant damage
Assessed by: Berej Patel / Dana Tilton
Sample Location: Homogeneous Area ID: Date:
Research Building - Roof RR-01 6 Feb 14
Transite Pipe (cut and capped) on roof of Research wing
Transite pipes (cut and capped) on roof of Research wing – visual inspection, in good condition
☐ 2. Damaged friable surfacing ACM ☐ 3. Significantly damaged friable surfacing ACM ☐ 4. Damaged or significantly damaged friable miscellaneous ACM ☒ 5. ACBM with potential for damage ☐ 6. ACBM with potential for significant damage
BBIIRRMMIINNGGHHAAMM VVAAMMCC AASSBBEESSTTOOSS SSUURRVVEEYY RREEPPOORRTT
Fidelis Project No.: 2013-09-001 March 2014 Appendix B
Appendix B Drawings
BBIIRRMMIINNGGHHAAMM VVAAMMCC AASSBBEESSTTOOSS SSUURRVVEEYY RREEPPOORRTT
Fidelis Project No.: 2013-09-001 March 2014 Appendix C
Appendix C Photographs
SB1-CH1-1 – Sub-basement Northwest corner – Chiller line insulation sample
SB1-CH1-2 – Sub-basement northwest corner – chiller line insulation sample
SB1-CH1-3 – Sub-basement northwest corner – chiller line insulation sample
SB2-CH2 – Sub-basement northwest corner – chiller line insulation samples
SB2-CH2-1 – Sub-basement northwest corner – chiller line insulation sample
SB2-CH2-2 – Sub-basement northwest corner – chiller line insulation sample
SB2-CH2-3 – Sub-basement northwest corner – chiller line insulation sample
SB3-CH2E – Sub-basement northwest corner – chiller line elbow insulation sample
SB3-CH2E-2 – Sub-basement northwest corner – chiller line elbow insulation sample
SB3-CH2E-3 – Sub-basement northwest corner – chiller line elbow insulation sample
SB3-CH2E-1 – Sub-basement northwest corner – chiller line elbow insulation sample
SB4-LD1 – Sub-basement northwest corner – large duct insulation sample
SB4-LD1-1 – Sub-basement northwest corner – large duct insulation sample
SB4-LD1-2 – Sub-basement northwest corner – large duct insulation sample
SB4-LD1-3 – Sub-basement northwest corner – large duct insulation sample
SB5-CH1R-1 – Sub-basement northwest corner – chiller line return pipe insulation sample
SB5-CH1R-2 – Sub-basement northwest corner – chiller line return pipe insulation sample
SB5-CH1R-3 – Sub-basement northwest corner – chiller line return pipe insulation sample
SB6-FP1-1 – Sub-basement raised electrical room in northwest section of sub-basement – fire proofing sample
SB6-FP1-2 – Sub-basement raised electrical room in northwest section of sub-basement – fire proofing
SB6-FP1-3 – Sub-basement raised electrical room in northwest section of sub-basement – fire proofing
SB6-FP1-4 – Sub-basement raised electrical room in northwest section of sub-basement – fire proofing
SB6-FP1-5 – Sub-basement raised electrical room in northwest section of sub-basement – fire proofing
SB6-FP1-6 – Sub-basement from under raised electrical room in northwest section of sub-basement – fire proofing sample
SB6-FP1-1 – Sub-basement from under raised electrical room in northwest section of sub-basement – fire proofing sample
Sub-basement – northwest corner looking southeast
Northern section of sub-basement looking towards the northwest corner of the sub-basement
SB7-PE1-1 – Sub-basement northern section of sub-basement – pipe elbow sample taken from pipe suspended from ceiling
Sub-basement northern section catwalk
SB8-PE2-1 – Sub-basement northern section catwalk – pipe elbow sample
SB8-PE2-2 – Sub-basement northern section catwalk – pipe elbow sample
SB8-PE2-3 – Sub-basement northern section catwalk – pipe elbow sample
SB9-CHP1-1 – Sub-basement northern section catwalk – plaster patch on chiller line
Dry wall from northern section of sub-basement under the raised electrical room
SB10-DW1-1 – Sub-basement northern section of sub-basement under raised electrical room – dry wall
SB10-DW1-2 – Sub-basement northern section of sub-basement under raised electrical room – dry wall
SB10-DW1-3 – Sub-basement northern section of sub-basement under raised electrical room – dry wall
Southwest corner of sub-basement
Southwest corner of the sub-basement
2SB11-PE3-1 – Sub-basement southwest corner of sub-basement – pipe elbow insulation sample
2SB11-PE3-2 – Sub-basement southwest corner of sub-basement – pipe elbow insulation sample
2SB11-PE3-3 – Sub-basement southwest corner of sub-basement – pipe elbow insulation sample
2SB12-PJ1-1 – Sub-basement in southwest corner of sub-basement – pipe joint sample
2SB12-PJ1-2 – Sub-basement in southwest corner of sub-basement – pipe joint sample
2SB12-PJ1-3 – Sub-basement in southwest corner of sub-basement – pipe joint sample
2SB13-PR1 – Sub-basement southwest section of sub-basement – pipe run sample location
2SB13-PR1-1 – Sub-basement southwest section of sub-basement – pipe run insulation sample
2SB13-PR1-2 – Sub-basement southwest section of sub-basement – pipe run insulation sample
2SB14-PR2-1 – Sub-basement southwest section of sub-basement – pipe run insulation sample
2SB15-PJ2 – Sub-basement southwest section of sub-basement – pipe joint sample location
2SB15-PJ2-1 – Sub-basement southwest section of sub-basement – pipe joint insulation sample
2SB15-PJ2-2 – Sub-basement southwest section of sub-basement – pipe joint insulation sample
2SB15-PJ2-3 – Sub-basement southwest section of sub-basement – pipe joint insulation sample
2SB16-PE4 – Sub-basement southeast section of sub-basement – pipe elbow sample location
2SB16-PE4-1 – Sub-basement southeast section of sub-basement – pipe elbow insulation sample
2SB16-PE4-2 – Sub-basement southeast section of sub-basement – pipe elbow insulation sample
2SB17-PE5-1 – Sub-basement in southeast section of sub-basement – pipe elbow insulation sample –
CONTAINS ASBESTOS
2SB18-PR3-2 – Sub-basement southern section of sub-basement – pipe run sample location
2SB18-PR3-1 – Sub-basement southern section of sub-basement – pipe run insulation sample
2SB18-PR3-2 – Sub-basement southern section of sub-basement – pipe run insulation sample
2SB19-PE6-1 – Sub-basement southern section of sub-basement – pipe elbow insulation sample
2SB19-PE6-2 – Sub-basement southern section of sub-basement – pipe elbow insulation sample
2SB20-PR4-1 – Sub-basement southern section of sub-basement on catwalk – pipe run insulation sample
2SB20-PR4-3 – Sub-basement southern section of sub-basement on catwalk – pipe run insulation sample
2SB21-PR5-1 – Sub-basement southern section of sub-basement on catwalk – pipe run insulation sample
2SB21-PR5-1 – Sub-basement southern section of sub-basement on catwalk – pipe run insulation sample
2SB22-DM1 – Sub-basement southern section near corridor leading to northern section of sub-basement – duct mastic sample location
2SB22-DM1-1 – Sub-basement southern section near corridor leading to northern section of sub-basement – duct mastic sample
2SB22-DM1-2 – Sub-basement southern section near corridor leading to northern section of sub-basement – duct mastic sample
Basement closet B-17A-W next to incinerator room
Basement closet next to band of 4 elevators – black mastic under 12” x 12” floor tile – assumed to contain asbestos
Basement closet – floor tiles sample location – SPB103A-BH – CONTAINS ASBESTOS
B23-FT1-1 – Basement closet – SPB103A-BH – Floor tile sample – CONTAINS ASBESTOS
B23-FT1-2 – Basement closet – SPB103A-BH – Floor tile sample – CONTAINS ASBESTOS
B24-DI2 – Basement mechanical room B103E – Duct insulation sample location
B24-DI2-1 – Basement mechanical room B103E – Duct insulation sample
B24-DI2-2 – Basement mechanical room B103E – Duct insulation sample
B25-DI3-1 – Basement mechanical room B103E – Duct insulation sample
B25-DI3-2 – Basement mechanical room B103E – Duct insulation sample
B25-DI3-3 – Basement mechanical room B103E – Duct insulation sample
B26-PR6 – Basement mechanical room B103E – pipe run insulation sample location
B26-PR6-1 – Basement mechanical room B103E – pipe run insulation sample
B26-PR6-2 – Basement mechanical room B103E – pipe run insulation sample
B26-PR6-3 – Basement mechanical room B103E – pipe run insulation sample
B27-VJ – Basement mechanical room B103E – vibration joint sample location
B27-VJ1 – Basement mechanical room B103E – vibration joint sample
Basement incinerator room
B28-CP1 – Basement incinerator room – ceiling paint sample location
B28-CP1 – Basement incinerator room – ceiling paint sample location
B28-CP1 – Basement incinerator room – ceiling paint sample
B29-PC1 – Basement incinerator room – pipe cloth insulation sample location
B29-PC1 – Basement incinerator room – pipe cloth insulation
B30-PR7 – Basement incinerator room – pipe run insulation sample location
B30-PR7 – Basement incinerator room – pipe run insulation sample
Basement mechanical room – SPB100C-BH
B31-PR8 – Basement mechanical room – SPB100C-BH – pipe run insulation sample
B32-PR9 – Basement mechanical room – SPB100C-BH – pipe run insulation sample
B33-PR10 – Basement mechanical room – SPB100C-BH – pipe run insulation sample
Basement crawlspace – 1 – no samples taken – similar TSI sampled elsewhere in basement or sub-basement
Basement crawlspace – 2 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 3 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 4 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 5 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 6 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 7 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 8 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 9 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 10 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 11 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement crawlspace – 12 – no samples taken – similar TSI sampled elsewhere in basement or sub-
Basement closet above drop ceiling – piping – no samples collected
Basement closet above drop ceiling – piping – no samples collected
Basement flooring layers
Basement floor tile layers
Basement - morgue
G34-PR11-1 – Ground Floor corridor outside of SPG415-BH – pipe run insulation sample – pipe
G34-PR11-2 – Ground Floor corridor outside of SPG415-BH – pipe run insulation sample – pipe
G34-PR11-3 – Ground Floor corridor outside of SPG415-BH – pipe run insulation sample – pipe
G35-PR12-1 – Ground Floor corridor outside of SPG415-BH – pipe run insulation sample – pipe
G35-PR12-2 – Ground Floor corridor outside of SPG415-BH – pipe run insulation sample – pipe
G35-PR12-3 – Ground Floor corridor outside of SPG415-BH – pipe run insulation sample – pipe
G36-FP2 – Ground floor mechanical room SPG415-BH – fire proofing sample – CONTAINS ASBESTOS
G37-PJ3-1 – Ground floor mechanical room SPGD120-BH – pipe joint insulation sample
G37-PJ3-2 – Ground floor mechanical room SPGD120-BH – pipe joint insulation sample
G37-PJ3-3 – Ground floor mechanical room SPGD120-BH – pipe joint insulation sample
G38-PR13-1 – Ground floor mechanical space SPG509-BH – pipe run insulation sample
G38-PR13-2 – Ground floor mechanical space SPG509-BH – pipe run insulation sample
G38-PR13-3 – Ground floor mechanical space SPG509-BH – pipe run insulation sample
G39-PR14-1 – Ground floor mechanical space SPG509-BH – pipe run insulation sample
G39-PR14-2 – Ground floor mechanical space SPG509-BH – pipe run insulation sample
G39-PR14-3 – Ground floor mechanical space SPG509-BH – pipe run insulation sample
G40-PR15 – Ground floor mechanical space SPG509-BH – pipe run insulation sample
G41-FP3 – Ground floor mechanical space SPG514-BH – fire proofing samples
Ground floor mechanical space under Research – M-R-1
G42-PR16-1 – Ground floor mechanical space under Research M-R-1 – pipe run insulation – CONTAINS
ASBESTOS
G42-PR16-2 – Ground floor mechanical space under Research M-R-1 – pipe run insulation – CONTAINS
G42-PR16-3 – Ground floor mechanical space under Research M-R-1 – pipe run insulation – CONTAINS
G43-PR17-1 – Ground floor mechanical space under Research M-R-1 – pipe run insulation
G43-PR17-2 – Ground floor mechanical space under Research M-R-1 – pipe run insulation
G44-FT3 – Flooring sample taken from elevator within Research
266-PR26-1 – 2nd floor mechanical room SP2319-BH – pipe run insulation sample
266-PR26-2 – 2nd floor mechanical room SP2319-BH – pipe run insulation sample
| Fidelis - Birmingham VAMC Asbestos Survey Report |
| Appendix B - Drawings |
| Figure 1 - Sub-basement |
| Figure 2 - Basement |
| Figure 3 - Ground Floor |
| Figure 4 - 1st Floor |
| Figure 5 - 2nd Floor |
| Figure 6 - 3rd Floor |
| Figure 7 - 4th Floor |
| Figure 8 - 5th Floor |
| Figure 9 - 6th Floor |
| Figure 10 - 7th Floor |
| Figure 11 - 8th Floor |
| Figure 12 - 9th Floor |
| Figure 13 - 10th Floor |
| Figure 14 - 11th Floor |
| Appendix C - Photographs |
| Sub-Basement Photographs |
| Basement Photographs |
| Ground Floor Photographs |