About this file

36C24718B0636 0005 Final Asbestos Survey_Part3.pdf

View the file

Other files for this federal contract opportunity

Other files attached to #521-16-101 Replace Pressure Piping and Hot Water Distribution System, newest first.
File Type Posted
36C24718B0636-0008001.pdf PDF
36C24718B0636-0008000.docx DOCX document
36C24718B0636-0007001.pdf PDF
36C24718B0636-0007000.docx DOCX document
36C24718B0636-0006002.pdf PDF
36C24718B0636-0006001.pdf PDF
36C24718B0636-0006000.docx DOCX document
36C24718B0636-0006003.pdf PDF
36C24718B0636-0005019.pdf PDF
36C24718B0636-0005016.docx DOCX document
36C24718B0636-0005018.pdf PDF
36C24718B0636-0004000.docx DOCX document
36C24718B0636-0004005.pdf PDF
36C24718B0636-0004003.pdf PDF
36C24718B0636-0004002.pdf PDF
36C24718B0636-0004001.pdf PDF
36C24718B0636-0004004.pdf PDF
36C24718B0636-0003000.docx DOCX document
36C24718B0636-0003002.pdf PDF
36C24718B0636-0003004.pdf PDF
36C24718B0636-0003003.pdf PDF
36C24718B0636-0003006.pdf PDF
36C24718B0636-0003001.pdf PDF
36C24718B0636-0003005.pdf PDF
36C24718B0636-0002004.pdf PDF
36C24718B0636-0002003.pdf PDF
36C24718B0636-0002000.docx DOCX document
36C24718B0636-0002001.pdf PDF
36C24718B0636-0002005.pdf PDF
36C24718B0636-0002006.pdf PDF
36C24718B0636-0002002.pdf PDF
36C24718B0636-0001002.pdf PDF
36C24718B0636-0001000.docx DOCX document
36C24718B0636-0001001.pdf PDF
36C24718B0636-001.docx DOCX document
36C24718B0636-000.docx DOCX document
Show all 36

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

266-PR26-3 – 2nd floor mechanical room SP2319-BH – pipe run insulation sample

267-PR27-1 – 2nd floor mechanical room SP2319-BH – pipe run insulation sample

268-RI1 – 2nd floor mechanical room SP2319-BH – roof insulation sample

2nd floor mechanical room SP2332-BH

269-PR28-1 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample

269-PR28-2 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample

269-PR28-3 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample

270-PR29-1 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample

270-PR29-2 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample

270-PR29-3 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample

271-PR30 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample location

271-PR30-1 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample

271-PR30-2 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample

271-PR30-3 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample

272-FP9 – 2nd floor mechanical room SP2332-BH – fire proofing samples

560-CT1 – 5th floor mechanical room 5403-BH – ceiling tile and black mastic sample location

560-CT1 – 5th floor mechanical room 5403-BH – ceiling tile and black mastic sample

561-FP6 – 5th floor mechanical room 5D103 – fire proofing samples

562-FP7 – 5th floor mechanical room 5D104 – fire proofing samples

563-FP8 – 5th floor mechanical room 5D107 – fire proofing samples

564-VJ2 – 5th floor mechanical room 5D107 – vibration joint

565-FT8-1 – 5th floor chase next to service elevator – 12” x 12” floor tile with black mastic – CONTAINS

ASBESTOS

952-FP5 – 9th floor mechanical room off of patient care service main office – fire proofing samples

953-PR23-1 – 9th floor chase access next to service elevator – pipe run insulation sample

953-PR23-2 – 9th floor chase access next to service elevator – pipe run insulation sample

953-PR23-3 – 9th floor chase access next to service elevator – pipe run insulation sample

954-PR24 – 9th floor chase access next to service elevator – pipe run insulation sample

955-PR25-1 – 9th floor chase access next to service elevator – pipe run insulation sample

955-PR25-2 – 9th floor chase access next to service elevator – pipe run insulation sample

955-PR25-3 – 9th floor chase access next to service elevator – pipe run insulation sample

956-FT5-1 – 9th floor mechanical/electrical closet 9209-BH – floor tile sample – similar floor tile throughout 9th floor corridors

957-FT6 – 9th floor electrical closet 9207-BH – floor tile samples

958-WM1 – 9th floor electrical closet 9207-BH – wall mastic – assumed to be on all exterior walls –

CONTAINS ASBESTOS

958-WM1 – 9th floor electrical closet 9207-BH – wall mastic – assumed to be on all exterior walls –

CONTAINS ASBESTOS

959-FT7-1 – 9th floor electrical closet 9207-BH – floor tile sample

1049-FT4 – 10th floor closet SP10THA-BH – floor tile and mastic samples – CONTAINS ASBESTOS

11th floor fire proofing

11th floor tank room

1145-PR18-1 – 11th floor tank room – pipe run insulation sample

1145-PR18-2 – 11th floor tank room – pipe run insulation sample

1145-PR18-3 – 11th floor tank room – pipe run insulation sample

1146-PR19-1 – 11th floor tank room – pipe run insulation sample

1146-PR19-2 – 11th floor tank room – pipe run insulation sample

1146-PR19-3 – 11th floor tank room – pipe run insulation sample

1147-PR20-1 – 11th floor tank room – pipe run insulation sample

1147-PR20-2 – 11th floor tank room – pipe run insulation sample

1147-PR20-3 – 11th floor tank room – pipe run insulation sample

1148-PR21-1 – 11th floor tank room – pipe run insulation sample

1148-PR21-2 – 11th floor tank room – pipe run insulation sample

1148-PR21-3 – 11th floor tank room – pipe run insulation sample

1151-PR22-1 – 11th floor tank room – pipe run insulation sample

1151-PR22-2 – 11th floor tank room – pipe run insulation sample

1151-PR22-3 – 11th floor tank room – pipe run insulation sample

BBIIRRMMIINNGGHHAAMM VVAAMMCC AASSBBEESSTTOOSS SSUURRVVEEYY RREEPPOORRTT

Fidelis Project No.: 2013-09-001 March 2014 Appendix D

Appendix D Summary of Asbestos Laboratory

Analytical Results

Material

Sampled

And Description

SB1CH1-1-Wrap ND Yes Fair

SB1CH1-1-Wrap ND Yes Fair

SB1CH1-1-

Insulation ND No Fair

SB1CH1-2-Wrap ND Yes Fair

SB1CH1-2-Wrap ND Yes Fair

SB1CH1-2-

Insulation ND No Fair

SB1CH1-3-Wrap ND Yes Fair

SB1CH1-3-

Insulation ND No Fair

SB2CH2-1-Wrap ND No Fair

SB2CH2-1-Wrap ND No Fair

SB2CH2-2-Wrap ND No Fair

SB2CH2-2-Wrap ND No Fair

Sub Basement SB2CH2-3

White tape wrap over mineral wool insulation

ND No Fair N/A

Sub Basement SB3CH2E-1

Woven tape and mastic over mineral wool insulation

ND No Fair N/A

Sub Basement SB3CH2E-2

Woven tape and mastic over mineral wool insulation

ND No Fair N/A

Sub Basement SB3CH2E-3

Woven tape and mastic over mineral wool insulation

ND No Fair N/A

SB4LD1-1-Wrap ND No Good

SB4LD1-1-Wrap ND No Good

SB4LD1-2-Wrap ND No Good

SB4LD1-2-Wrap ND No Good

Sub Basement SB4 LD1-3 Tape and mastic on large duct ND No Good N/A

Sub Basement SB5 CHIR-1

Woven tape and mastic over mineral wool insulation

ND No Fair N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Sub Basement

Location of

Homogeneous

Area Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Approximate

Quantity 5, 6, 7

White textured jacket over black foam insulation on chiller line joint

Sub Basement

Sub Basement

Sub Basement

Sub Basement

Sub Basement

Tape and mastic on large duct

SUB BASEMENT

White textured jacket over black foam insulation on chiller line joint

White textured jacket over black foam insulation on chiller line joint

White tape wrap over mineral wool insulation

White tape wrap over mineral wool insulation

Tape and mastic on large duct

Sub Basement

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Sub Basement

Location of

Homogeneous

Area Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Approximate

Quantity 5, 6, 7

Sub Basement SB5 CHIR-2

Woven tape and mastic over mineral wool insulation

ND No Fair N/A

Sub Basement SB5 CHIR-3

Woven tape and mastic over mineral wool insulation

ND No Fair N/A

Sub Basement SB6 FP1-1 Fire Proofing ND Yes Good N/A

Sub Basement SB6 FP1-2 Fire Proofing ND Yes Good N/A

Sub Basement SB6 FP1-3 Fire Proofing ND Yes Good N/A

Sub Basement SB6 FP1-4 Fire Proofing ND Yes Good N/A

Sub Basement SB6 FP1-5 Fire Proofing ND Yes Good N/A

Sub Basement SB6 FP1-6 Fire Proofing ND Yes Good N/A

SB7 PE1-1-Wrap ND Yes Fair

SB7 PE1-1-Wrap ND Yes Fair

Sub Basement SB8 PE2-1

Woven tape over mineral wool insulation

ND No Fair N/A

Sub Basement SB8 PE2-2

Woven tape over mineral wool insulation

ND No Fair N/A

Sub Basement SB8 PE2-3

Woven tape over mineral wool insulation

ND No Fair N/A

SB9 CHP1-1-

Wrap ND No Fair

SB9 CHP1-1-

Wrap ND No Fair

Sub Basement SB10 DW1-1 Drywall ND Yes Poor N/A

Sub Basement SB10 DW1-2 Drywall ND Yes Poor N/A

SB10 DW1-3-Joint

Compound ND Yes Poor

SB10 DW1-3-

Drywall ND Yes Poor

N/A

N/A

N/A

“A” - signifies multi-layered

ND = No asbestos detected

Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other areas that were not assessable during this survey

Friability was determined according to a material’s current condition.

It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.

It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.

Abbreviations - LF = linear feet; SF = square feet

Plastic cover over mineral wool insulation

Plaster patch over mineral wool insulation

Drywall

Sub Basement

And Description

2SB11 PE3-1-

Wrap ND No Fair

2SB11 PE3-1-

Insulation ND No Fair

2SB11 PE3-2-

Wrap ND No Fair

2SB11 PE3-2-

Insulation ND No Fair

2SB11 PE3-3-

Wrap ND No Fair

2SB11 PE3-3-

Insulation ND No Fair

2SB12 PJ1-1-

Wrap ND Yes Fair

2SB12 PJ1-1-

Insulation ND Yes Fair

Sub Basement 2 2SB12 PJ1-2

Cementisous insulation under metal jacket

ND Yes Fair N/A

2SB12 PJ1-3-

Wrap ND Yes Fair

2SB12 PJ1-3-

Insulation ND Yes Fair

Sub Basement 2 2SB13 PR1-1

Fiberous paper over mineral wool insulation

ND Yes Fair N/A

Sub Basement 2 2SB13 PR1-2

Fiberous paper over mineral wool insulation

ND Yes Fair N/A

Sub Basement 2 2SB14 PR2-1

Grey cementisous insulation covered by metal sleeve

ND Yes Poor N/A

Sub Basement 2 2SB15 PJ2-1 Putty over pipe joint ND Yes Fair N/A

Sub Basement 2 2SB15 PJ2-2 Putty over pipe joint ND Yes Fair N/A

Sub Basement 2 2SB15 PJ2-3 Putty over pipe joint ND Yes Fair N/A

2SB16 PE4-1-

Wrap ND Yes Fair

2SB16 PE4-1-

Wrap ND Yes Fair

2SB16 PE4-1-

Insulation ND Yes Fair

2SB16 PE4-2-

Wrap ND Yes Fair

2SB16 PE4-2-

Insulation ND Yes Fair

Location of

Homogeneous

Area Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Sub Basement 2

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Sub Basement 2

Sub Basement 2

Sub Basement 2

Sub Basement 2

Sub Basement 2

Sub Basement 2

N/A

N/A

N/A

N/A

N/A

N/A

Approximate

Quantity 5, 6, 7

N/A

Hard plaster over pipe elbow

Hard plaster over pipe elbow

Hard plaster over pipe elbow

Cementisous insulation under metal jacket

Cementisous insulation under metal jacket

Woven mesh pipe elbow over mineral wool insulation

Woven mesh pipe elbow over mineral wool insulation

Sub Basement 2

And Description

Location of

Homogeneous

Area Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Sub Basement 2

Approximate

Quantity 5, 6, 7

2SB16 PE4-3-

Wrap ND Yes Fair

2SB16 PE4-3-

Insulation ND Yes Fair

2SB17 PE5-1-

Wrap 4% Chrysotile Yes Poor

2SB17 PE5-1-

Wrap ND Yes Poor

2SB18 PR3-1-

Wrap ND Yes Fair

2SB18 PR3-1-

Wrap ND Yes Fair

2SB18 PR3-1-

Insulation ND Yes Fair

2SB18 PR3-2-

Wrap ND Yes Fair

2SB18 PR3-2-

Wrap ND Yes Fair

2SB18 PR3-2-

Insulation ND Yes Fair

2SB19 PE6-1-

Wrap ND No Good

2SB19 PE6-1-

Insulation ND No Good

2SB19 PE6-2-

Wrap ND No Good

2SB19 PE6-2-

Insulation ND No Good

2SB20 PR4-1-

Insulation ND Yes Fair

2SB20 PR4-1-

Insulation ND Yes Fair

2SB20 PR4-2-

Insulation ND Yes Fair

2SB20 PR4-2-

Insulation ND Yes Fair

2SB20 PR4-3-

Insulation ND Yes Fair

2SB20 PR4-3-

Insulation ND Yes Fair

Sub Basement 2 2SB21 PR5-1

Woven paper over mineral wool insulation

ND Yes Poor N/A

Sub Basement 2 2SB21 PR5-2

Woven paper over mineral wool insulation

ND Yes Poor N/A

Sub Basement 2 2SB22 DM1-1 Mastic over duct joint ND No Good N/A

Sub Basement 2 2SB22 DM1-2 Mastic over duct joint ND No Good N/A

Mastic, woven fabric, cellulose fabric over mineral wool insulation Mastic, woven fabric, cellulose fabric over mineral wool insulation Mastic, woven fabric, cellulose fabric over mineral wool insulation

N/A

4 LF

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Woven mesh pipe elbow over mineral wool insulation

Woven paper with fibers over mineral wool insulation

Woven paper over black insulation

Woven paper over black insulation

White plaster over black insulation

White plaster over black insulation

Sub Basement 2

Sub Basement 2

Sub Basement 2

Sub Basement 2

Sub Basement 2

Sub Basement 2

Sub Basement 2

And Description

Location of

Homogeneous

Area Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Sub Basement 2

Approximate

Quantity 5, 6, 7

“A” - signifies multi-layered

ND = No asbestos detected

Friability was determined according to a material’s current condition.

It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.

It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.

Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other areas that were not assessable during this survey

And Description

B23 FT1-1-Floor tile ND No Fair

B23 FT1-1-

Adhesive 9% Chrysotile No Fair

B23 FT1-2-Floor tile ND No Fair

B23 FT1-2-

Adhesive Stop Positive No Fair

Basement B24 DI2-1 Duct insulation ND No Good N/A

Basement B25 DI3-1-Wrap ND No Good

Basement B25 DI3-1-Wrap ND No Good

Basement B25 DI3-2 Duct insulation ND No Good N/A

Basement B25 DI3-3 Duct insulation ND No Good N/A

Basement B26 PR6-1

Woven paper

(purple) over mineral wool insulation

ND No Good N/A

Basement B26 PR6-2

Woven paper

(purple) over mineral wool insulation

ND No Good N/A

Basement B26 PR6-3

Woven paper

(purple) over mineral wool insulation

ND No Good N/A

Basement B27 VJ1-1

Woven fabric

(green) over vibration joint

ND No Fair N/A

Basement B27VJ1-2

Woven fabric

(green) over vibration joint

ND No Fair N/A

Basement B28 CP1-1

Thick flaking black paint with white backing on ceiling of incinerator room

ND Yes Poor N/A

Basement B28 CP1-2

Thick flaking black paint with white backing on ceiling of incinerator room

ND Yes Poor N/A

Basement B28 CP1-3

Thick flaking black paint with white backing on ceiling of incinerator room

ND Yes Poor N/A

Basement B29 PC1-1

Woven fabric on pipe run in incinerator room

ND Yes Poor N/A

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Basement

N/A

Asbestos Survey

Basement

Duct insulation

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Basement 15 SF

15 SF

12"x12" Brown floor tile with black mastic

12"x12" Brown floor tile with black mastic

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Basement

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Basement B29 PC1-2

Woven fabric on pipe run in incinerator room

ND Yes Poor N/A

Basement B29 PC1-3

Woven fabric on pipe run in incinerator room

ND Yes Poor N/A

Basement B30 PR7-1

Brown woven paper with aluminum backing over mineral wool on pipe run in incinerator room

ND Yes Poor N/A

Basement B30 PR7-2

Brown woven paper with aluminum backing over mineral wool on pipe run in incinerator room

ND Yes Poor N/A

Basement B30 PR7-3

Brown woven paper with aluminum backing over mineral wool on pipe run in incinerator room

ND Yes Poor N/A

Basement B31 PR8-1

Woven paper

(purple) with aluminum backing over fiberglass -

SPB100C-BH

ND No Fair N/A

Basement B31 PR8-2

Woven paper

(purple) with aluminum backing over fiberglass -

SPB100C-BH

ND No Fair N/A

Basement B31 PR8-3

Woven paper

(purple) with aluminum backing over fiberglass -

SPB100C-BH

ND No Fair N/A

B32 PR9-1-Wrap ND Yes Fair

B32 PR9-1-Wrap ND Yes Fair

B32 PR9-1-

Insulation ND Yes Fair

B32 PR9-2-Wrap ND Yes Fair

Basement N/A

Woven paper

(purple) with aluminum backing over hard foam insulation -

SPB100C-BHWoven paper

(purple) with

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Basement

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

B32 PR9-2-Wrap ND Yes Fair

B32 PR9-2-

Insulation ND Yes Fair

B32 PR9-3-Wrap ND Yes Fair

B32 PR9-3-Wrap ND Yes Fair

B32 PR9-3-

Insulation ND Yes Fair

B33 PR10-1-

Wrap ND No Fair

B33 PR10-1-

Wrap ND No Fair

B33 PR10-1-

Wrap ND No Fair

B33 PR10-2-

Wrap ND No Fair

B33 PR10-2-

Wrap ND No Fair

B33 PR10-2-

Wrap ND No Fair

B33 PR10-3-

Wrap ND No Fair

B33 PR10-3-

Wrap ND No Fair

N/ABasement

Basement

Basement

Basement N/A

Woven paper

(yellow) and woven cloth over mineral wool insulation -

SPB100C-BH

Woven paper

(purple) with aluminum backing over hard foam insulation -

SPB100C-BH

Woven paper

(yellow) and woven cloth over mineral wool insulation -

SPB100C-BH

Woven paper

(yellow) and woven cloth over mineral wool insulation -

SPB100C-BH

N/A

N/A

Basement N/A aluminum backing over hard foam insulation -

SPB100C-BH

“A” - signifies multi-layered

ND = No asbestos detected

Friability was determined according to a material’s current condition.

It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.

It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.

Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other

And Description

Ground Floor G34 PR11-1

4" pipe insulation

(white) woven plastic over mineral wool

ND No Fair N/A

Ground Floor G34 PR11-2

4" pipe insulation

(white) woven plastic over mineral wool

ND No Fair N/A

Ground Floor G34 PR11-3

4" pipe insulation

(white) woven plastic over mineral wool

ND No Fair N/A

G35 PR12-1-

Sealant ND No Good

G35 PR12-1-

Wrap ND No Good

G35 PR12-1-

Wrap ND No Good

G35 PR12-1-

Adhesive ND No Good

G35 PR12-2-

Wrap ND No Good

G35 PR12-2-

Wrap ND No Good

G35 PR12-2-

Adhesive ND No Good

G35 PR12-3-

Sealant ND No Good

G35 PR12-3-

Wrap ND No Good

G35 PR12-3-

Wrap ND No Good

G35 PR12-3-

Adhesive ND No Good

Ground Floor G36 FP2-1

Fire Proofing

(grey) - SPG415-

BH

9% Chrysotile Yes Fair 400 SF

Ground Floor G36 FP2-2

Fire Proofing

(grey) - SPG415-

BH

9% Chrysotile Yes Fair 400 SF

Ground Floor G36 FP2-3

Fire Proofing

(grey) - SPG415-

BH

9% Chrysotile Yes Fair 400 SF

G37 PJ3-1-

Sealant ND Yes Poor

G37 PJ3-1-Wrap ND Yes Poor

N/A

N/A

N/A

N/A

Ground Floor

Ground Floor

Ground Floor

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Ground Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Ground Floor

Woven cloth over aluminum tape over mineral wool

Orange painted mastic over aluminum tape and mineral wool -

SPGD120-BH

Woven cloth over aluminum tape over mineral wool

Woven cloth over aluminum tape over mineral wool

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Ground Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

G37 PJ3-2-

Sealant ND Yes Poor

G37 PJ3-2-Wrap ND Yes Poor

G37 PJ3-3-

Sealant ND Yes Poor

G37 PJ3-3-Wrap ND Yes Poor

Ground Floor G38 PR13-1

Woven paper

(white) with aluminum backing over mineral wool -

SPG509-BH

ND No Fair N/A

Ground Floor G38 PR13-2

Woven paper

(white) with aluminum backing over mineral wool -

SPG509-BH

ND No Fair N/A

G38 PR13-3-

Wrap ND No Fair

G38 PR13-3-

Adhesive ND No Fair

Ground Floor G39 PR14-1

Woven paper

(purple) with aluminum backing over mineral wool -

SPG509-BH

ND No Fair N/A

Ground Floor G39 PR14-2

Woven paper

(purple) with aluminum backing over mineral wool -

SPG509-BH

ND No Fair N/A

G39 PR14-3-

Sealant ND No Fair

G39 PR14-3-

Wrap ND No Fair

Ground Floor G40 PR15-1

Painted yellow mastic over pipe run insulation -

SPG509-BH

ND Yes Poor N/A

N/A

N/A

N/A

N/A

Ground Floor

Ground Floor

Ground Floor

Ground Floor

Woven paper

(white) with aluminum backing over mineral wool -

SPG509-BH

Orange painted mastic over aluminum tape and mineral wool -

SPGD120-BH

Orange painted mastic over aluminum tape and mineral wool -

SPGD120-BH

Woven paper

(purple) with aluminum backing over mineral wool -

SPG509-BH

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Ground Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Ground Floor G40 PR15-2

Painted yellow mastic over pipe run insulation -

SPG509-BH

ND Yes Poor N/A

Ground Floor G41 FP3-1

Fire Proofing

(grey) - SPG514-

BH

ND Yes Fair N/A

Ground Floor G41 FP3-2

Fire Proofing

(grey) - SPG514-

BH

ND Yes Fair N/A

Ground Floor G41 FP3-3

Fire Proofing

(grey) - SPG514-

BH

ND Yes Fair N/A

Ground Floor G41 FP3-4

Fire Proofing

(grey) - SPG514-

BH

ND Yes Fair N/A

Ground Floor G41 FP3-5

Fire Proofing

(grey) - SPG514-

BH

ND Yes Fair N/A

G42 PR16-1-

Sealant 9% Chrysotile Yes Poor

G42 PR16-1-

Wrap ND Yes Poor

G42 PR16-2-

Sealant 9% Chrysotile Yes Poor

G42 PR16-2-

Wrap ND Yes Poor

G42 PR16-3-

Sealant 9% Chrysotile Yes Poor

G42 PR16-3-

Wrap ND Yes Poor

Ground Floor G43 PR17-1

Woven paper

(orange) with aluminum backing over mineral wool -

M-R-1

ND No Fair N/A

G43 PR17-2-

Sealant ND No Fair

G43 PR17-2-

Adhesive ND No Fair

G43 PR17-2-

Wrap ND No Fair

300 LF

300 LF

Ground Floor N/A

300 LF

Woven paper

(orange) with aluminum backing over mineral wool -

M-R-1

Woven paper

(purple) with aluminum backing over mineral wool - M-

R-1

Ground Floor

Ground Floor

Ground Floor

Woven paper

(purple) with aluminum backing over mineral wool - M-

R-1

Woven paper

(purple) with aluminum backing over mineral wool - M-

R-1

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Ground Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

RE44 FT3-1-

Flooring

Compound

ND No Poor

RE44 FT3-1-

Adhesive ND No Poor

RE44 FT3-1-

Paper ND No Poor

Ground Floor N/A

Floor tile, flooring compound and adhesive from

Research

Elevator floor

“A” - signifies multi-layered

ND = No asbestos detected

Friability was determined according to a material’s current condition.

It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.

It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.

Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other

And Description

2nd Floor 266 PR26-1

Woven paper with aluminum backing on purple pipe run -

SP2319-BH

ND No Fair N/A

2nd Floor 266 PR26-2

Woven paper with aluminum backing on purple pipe run -

SP2319-BH

ND No Fair N/A

2nd Floor 266 PR26-3

Woven paper with aluminum backing on purple pipe run -

SP2319-BH

ND No Fair N/A

2nd Floor 267 PR27-1

Woven paper with aluminum backing on orange pipe run -

SP2319-BH

ND No Fair N/A

2nd Floor 268 RI1-1

Roof Insulation -insulation between 2 metal layers making up the roof - SP2319-

BH

ND Yes Poor N/A

2nd Floor 268 RI1-2

Roof Insulation -insulation between 2 metal layers making up the roof - SP2319-

BH

ND Yes Poor N/A

2nd Floor 268 RI1-3

Roof Insulation -insulation between 2 metal layers making up the roof - SP2319-

BH

ND Yes Poor N/A

2nd Floor 269 PR28-1

Woven paper with aluminum backing on purple pipe run insulation -

SP2332-BH

ND Yes Poor N/A

Approximate

Quantity 5, 6, 7

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

2nd Floor

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

And Description

Approximate

Quantity 5, 6, 7

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

2nd Floor

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

2nd Floor 269 PR28-2

Woven paper with aluminum backing on purple pipe run insulation -

SP2332-BH

ND Yes Poor N/A

2nd Floor 269 PR28-3

Woven paper with aluminum backing on purple pipe run insulation -

SP2332-BH

ND Yes Poor N/A

2nd Floor 270 PR29-1

Hard plaster over mineral wool from orange pipe run -

SP2332-BH

ND Yes Poor N/A

2nd Floor 270 PR29-2

Hard plaster over mineral wool from orange pipe run -

SP2332-BH

ND Yes Poor N/A

2nd Floor 270 PR29-3

Hard plaster over mineral wool from orange pipe run -

SP2332-BH

ND Yes Poor N/A

271 PR30-1-

Wrap ND Yes Poor

271 PR30-1-

Wrap ND Yes Poor

2nd Floor 271 PR30-2

Woven paper over aluminum backing from white pipe run insulation -

SP2332-BH

ND Yes Poor N/A

2nd Floor 271 PR30-3

Woven paper over aluminum backing from white pipe run insulation -

SP2332-BH

ND Yes Poor N/A

2nd Floor 272 FP9-1

White/light grey fire proofing -

SP2332-BH

ND Yes Fair N/A

2nd Floor 272 FP9-2

White/light grey fire proofing -

SP2332-BH

ND Yes Fair N/A

Woven paper over aluminum backing from white pipe run insulation -

SP2332-BH

2nd Floor N/A

And Description

Approximate

Quantity 5, 6, 7

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

2nd Floor

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

2nd Floor 272 FP9-3

White/light grey fire proofing -

SP2332-BH

ND Yes Fair N/A

2nd Floor 272 FP9-4

White/light grey fire proofing -

SP2332-BH

ND Yes Fair N/A

2nd Floor 272 FP9-5

White/light grey fire proofing -

SP2332-BH

ND Yes Fair N/A

“A” - signifies multi-layered

ND = No asbestos detected

Friability was determined according to a material’s current condition.

It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.

It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.

Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other

And Description

560 CT1-1-

Ceiling tile ND No Good

560 CT1-1-

Adhesive ND No Good

560 CT1-2-

Ceiling tile ND No Good

560 CT1-2-

Adhesive ND No Good

5th Floor 561 FP6-1

Fire proofing

(white) -

5403-BH

ND Yes Fair N/A

5th Floor 561 FP6-1

Fire proofing

(white) -

5D103

ND Yes Fair N/A

5th Floor 561 FP6-3

Fire proofing

(white) -

5D103

ND Yes Fair N/A

5th Floor 561 FP6-4

Fire proofing

(white) -

5D103

ND Yes Fair N/A

5th Floor 561 FP6-5

Fire proofing

(white) -

5D103

ND Yes Fair N/A

5th Floor 562 FP7-1

Fire proofing

(light grey) -

5D104

ND Yes Fair N/A

5th Floor 562 FP7-2

Fire proofing

(light grey) -

5D104

ND Yes Fair N/A

5th Floor 562 FP7-3

Fire proofing

(light grey) -

5D104

ND Yes Fair N/A

5th Floor 562 FP7-4

Fire proofing

(light grey) -

5D104

ND Yes Fair N/A

5th Floor 562 FP7-5

Fire proofing

(light grey) -

5D104

ND Yes Fair N/A

5th Floor 563 FP8-1

Fire proofing

(dark grey) -

5D107

ND Yes Fair N/A

5th Floor 563 FP8-2

Fire proofing

(dark grey) -

5D107

ND Yes Fair N/A

5th Floor 563 FP8-3

Fire proofing

(dark grey) -

5D107

ND Yes Fair N/A

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

5th Floor

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Ceiling tile and mastic -

5403-BH

Ceiling tile and mastic -

5403-BH

Approximate

Quantity 5, 6, 7

5th Floor

5th Floor

N/A

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

5th Floor

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

Approximate

Quantity 5, 6, 7

5th Floor 563 FP8-4

Fire proofing

(dark grey) -

5D107

ND Yes Fair N/A

5th Floor 563 FP8-5

Fire proofing

(dark grey) -

5D107

ND Yes Fair N/A

564 VJ2-1-

Insulation ND No Fair

564 VJ2-1-Caulk ND No Fair

564 VJ2-2-

Insulation ND No Fair

564 VJ2-2-Caulk ND No Fair

565 FT 8-1-

Miscellaneous ND No Fair

565 FT8-1-Floor

Tile 4% Chrysotile No Fair

565 FT8-1-

Adhesive 9% Chrysotile No Fair

“A” - signifies multi-layered

ND = No asbestos detected

Friability was determined according to a material’s current condition.

It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.

It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.

Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other areas that were not assessable during this survey

12" x 12" floor tile with black mastic -

5th floor chase next to service elevator

Vibration Joint

10 SF

5th Floor

5th Floor

And Description

9th Floor 952 FP5-1

Fire Proofing

(light grey) - 9th floor patient care service main office mechanical room

ND Yes Fair N/A

9th Floor 952 FP5-2

Fire Proofing

(light grey) - 9th floor patient care service main office mechanical room

ND Yes Fair N/A

9th Floor 952 FP5-3

Fire Proofing

(light grey) - 9th floor patient care service main office mechanical room

ND Yes Fair N/A

9th Floor 953 PR23-1

Woven paper over aluminum backed tape over mineral wool - 9th floor chase access

ND No Fair N/A

9th Floor 953 PR23-2

Woven paper over aluminum backed tape over mineral wool - 9th floor chase access

ND No Fair N/A

9th Floor 953 PR23-3

Woven paper over aluminum backed tape over mineral wool - 9th floor chase access

ND No Fair N/A

9th Floor 954 PR24-1

Cloth fabric over mineral wool insulation - 9th floor chase access

ND Yes Poor N/A

9th Floor 954 PR24-2

Cloth fabric over mineral wool insulation - 9th floor chase access

ND Yes Poor N/A

9th Floor 954 PR24-3

Cloth fabric over mineral wool insulation - 9th floor chase access

ND Yes Poor N/A

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Ninth Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Ninth Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

9th Floor 955 PR25-1

Woven fabric over mineral wool insulation - 9th floor chase access

ND Yes Poor N/A

9th Floor 955 PR25-2

Woven fabric over mineral wool insulation - 9th floor chase access

ND Yes Poor N/A

9th Floor 955 PR25-3

Woven fabric over mineral wool insulation - 9th floor chase access

ND Yes Poor N/A

956 FT5-1-Floor

Tile ND No Good

956 FT5-1-

Adhesive ND No Good

956 FT5-1-Floor

Tile ND No Good

956 FT5-1-

Adhesive ND No Good

957 FT6-1-Floor

Tile ND No Good

957 FT6-1-

Adhesive ND No Good

957 FT6-2-Floor

Tile ND No Good

957 FT6-2-

Adhesive ND No Good

9th Floor 958 WM1-1

Wall mastic in

9th floor electrical closet

9% Chrysotile No Fair 50 SF

9th Floor 958 WM1-2

Wall mastic in

9th floor electrical closet

9% Chrysotile No Fair 50 SF

9th Floor 958 WM1-3

Wall mastic in

9th floor electrical closet

9% Chrysotile No Fair 50 SF

9th Floor 958 WM1-4

Wall mastic in

9th floor electrical closet

9% Chrysotile No Fair 50 SF

12" x 12" floor tile and adhesive in

9th floor electrical closet

12" x 12" floor tile and adhesive in

9th floor electrical closet

12" x 12" floor tile

- two layers of floor tile and adhesive -throughout 9th floor halls

9th Floor

9th Floor

9th Floor N/A

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

Ninth Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

9th Floor 958 WM1-5

Wall mastic in

9th floor electrical closet

9% Chrysotile No Fair 50 SF

959 FT7-1-Floor

Tile ND No Good

959 FT7-1-

Adhesive ND No Good

12" x 12" floor tile with black mastic over leveling compund near door jam of 9th floor electrical closet

9th Floor N/A

“A” - signifies multi-layered

ND = No asbestos detected

Friability was determined according to a material’s current condition.

It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.

It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.

Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other

And Description

1049 FT4-1-

Floor Tile 4% Chrysotile No Fair

1049 FT4-1-

Adhesive 9% Chrysotile No Fair

1049 FT4-2-

Floor Tile 4% Chrysotile No Fair

1049 FT4-2-

Adhesive 9% Chrysotile No Fair

10th Floor 1050 FP4-1

Fire proofing

(light grey) -

SP10THD-BH

ND Yes Fair N/A

10th Floor 1050 FP4-2

Fire proofing

(light grey) -

SP10THD-BH

ND Yes Fair N/A

10th Floor 1050 FP4-3

Fire proofing

(light grey) -

SP10THD-BH

ND Yes Fair N/A

10th Floor 1050 FP4-4

Fire proofing

(light grey) -

SP10THD-BH

ND Yes Fair N/A

10th Floor 1050 FP4-5

Fire proofing

(light grey) -

SP10THD-BH

ND Yes Fair N/A

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

10th Floor

“A” - signifies multi-layered

ND = No asbestos detected

Friability was determined according to a material’s current condition.

It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.

It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.

Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other areas that were not assessable during this survey

10th Floor

12" x 12" brown floor tile with black mastic -

SP10THA-BH

12" x 12" brown floor tile with black mastic -

SP10THA-BH

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area

Sample Number

Asbestos

Content 2 Friable

Condition of

Material

10th Floor

15 SF

15 SF

And Description

11th Floor 1145 PR18-1

Woven paper

(orange) with aluminum backing - 11th floor tank room

ND Yes Poor N/A

11th Floor 1145 PR18-2

Woven paper

(orange) with aluminum backing - 11th floor tank room

ND Yes Poor N/A

11th Floor 1145 PR18-3

Woven paper

(orange) with aluminum backing - 11th floor tank room

ND Yes Poor N/A

11th Floor 1146 PR19-1

Painted cloth

(yellow) over mineral wool -

11th floor tank room

ND Yes Poor N/A

11th Floor 1146 PR19-2

Painted cloth

(yellow) over mineral wool -

11th floor tank room

ND Yes Poor N/A

11th Floor 1146 PR19-3

Painted cloth

(yellow) over mineral wool -

11th floor tank room

ND Yes Poor N/A

11th Floor 1147 PR20-1

Woven cloth

(yellow) over two layers of aluminum backed taped over mineral wool -

11th floor tank room

ND Yes Poor N/A

1147 PR20-2-

Wrap ND Yes Poor

1147 PR20-2-

Wrap ND Yes Poor

N/A11th Floor

Woven cloth

(yellow) over two layers of aluminum backed taped over mineral wool -

11th floor tank room

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

11th Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area Sample Number

Asbestos

Content 2 Friable

Condition of

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

11th Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area Sample Number

Asbestos

Content 2 Friable

Condition of

Material

1147 PR20-3-

Wrap ND Yes Poor

1147 PR20-3-

Wrap ND Yes Poor

1147 PR20-3-

Wrap ND Yes Poor

11th Floor 1148 PR21-1

Woven paper

(purple) over aluminum backed tape over mineral wool - 11th floor tank room

ND Yes Poor N/A

11th Floor 1148 PR21-2

Woven paper

(purple) over aluminum backed tape over mineral wool - 11th floor tank room

ND Yes Poor N/A

1148 PR21-3-

Wrap ND Yes Poor

1148 PR21-3-

Wrap ND Yes Poor

1151 PR22-1-

Wrap ND No Fair

1151 PR22-1-

Wrap ND No Fair

1151 PR22-1-

Wrap ND No Fair

1151 PR22-2-

Wrap ND No Fair

1151 PR22-2-

Wrap ND No Fair

1151 PR22-2-

Wrap ND No Fair

1151 PR22-3-

Wrap ND No Fair

1151 PR22-3-

Wrap ND No Fair

1151 PR22-3-

Wrap ND No Fair

N/A

11th Floor N/A

N/A

N/A

N/A

11th Floor

11th Floor

11th Floor

11th Floor

Woven cloth

(white) over cardboard over woen cloth over mineral wool -

11th floor tank room

Woven cloth

(yellow) over two layers of aluminum backed taped over mineral wool -

11th floor tank room

Woven paper

(purple) over aluminum backed tape over mineral wool - 11th floor tank room

Woven cloth

(white) over cardboard over woen cloth over mineral wool -

11th floor tank room

Woven cloth

(white) over cardboard over woen cloth over mineral wool -

11th floor tank room

And Description

Sampling Results and Estimated Quantities

Birmingham VA Medical Center

Asbestos Survey

11th Floor

Approximate

Quantity 5, 6, 7

Location of

Homogeneous

Area Sample Number

Asbestos

Content 2 Friable

Condition of

Material

“A” - signifies multi-layered

ND = No asbestos detected

Friability was determined according to a material’s current condition.

It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.

It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.

Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other

BBIIRRMMIINNGGHHAAMM VVAAMMCC AASSBBEESSTTOOSS SSUURRVVEEYY RREEPPOORRTT

Fidelis Project No.: 2013-09-001 March 2014 Appendix E

Appendix E

Laboratory Results and Chains of Custody

EMSL Analytical, Inc.

3029 S. Jefferson, Saint Louis, MO 63118 Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com

391308689 CustomerID: FDLS42 CustomerPO:

ProjectID:

EMSL Order:

Attn: Dana Tilton Fidelis, LLC

1608 13TH AVE S STE 150

Birmingham, AL 35205

Received: 10/11/13 10:10 AM

2013-09-01 VA Survey

Fax:

Phone: (630) 853-5826

Project:

10/17/2013Analysis Date:

Collected:

Sample Description Appearance % Type AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

SB1CH1-1-Wrap

391308689-0001

Cream None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

SB1CH1-1-Wrap

391308689-0001A

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB1CH1-1-

Insulation 391308689-0001B

Black None Detected Non-Fibrous

Homogeneous

Non-fibrous (other)100%

SB1CH1-2-Wrap

391308689-0002

Cream None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

SB1CH1-2-Wrap

391308689-0002A

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB1CH1-2-

Insulation 391308689-0002B

Black None Detected Non-Fibrous

Homogeneous

Non-fibrous (other)100%

SB1CH1-3-Wrap

391308689-0003

Cream None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

SB1CH1-3-

Insulation 391308689-0003A

Black None Detected Non-Fibrous

Homogeneous

Non-fibrous (other)100%

1Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM

Jeff Siria, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0

Initial report from 10/17/2013 15:12:04

Sue Ferrario (41) http://www.EMSL.com mailto:saintlouislab@emsl.com

Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com

391308689 CustomerID: FDLS42 CustomerPO:

ProjectID:

EMSL Order:

Attn: Dana Tilton Fidelis, LLC

1608 13TH AVE S STE 150

Birmingham, AL 35205

Received: 10/11/13 10:10 AM

2013-09-01 VA Survey

Fax:

Phone: (630) 853-5826

Project:

10/17/2013Analysis Date:

Collected:

Sample Description Appearance % Type AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

SB2CH2-1-Wrap

391308689-0004

Cream None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

SB2CH2-1-Wrap

391308689-0004A

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB2CH2-2-Wrap

391308689-0005

Cream None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

SB2CH2-2-Wrap

391308689-0005A

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB2CH2-3

391308689-0006

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB3CH2E-1

391308689-0007

Cream None Detected Non-Fibrous Homogeneous

Glass19% Wollastonite4%

Non-fibrous (other)77%

SB3CH2E-2

391308689-0008

Cream None Detected Non-Fibrous Homogeneous

Glass19% Wollastonite4%

Non-fibrous (other)77%

SB3CH2E-3

391308689-0009

Cream None Detected Non-Fibrous Homogeneous

Glass19% Wollastonite4%

Non-fibrous (other)77%

2Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM

Jeff Siria, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0

Initial report from 10/17/2013 15:12:04

Sue Ferrario (41)

Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com

391308689 CustomerID: FDLS42 CustomerPO:

ProjectID:

EMSL Order:

Attn: Dana Tilton Fidelis, LLC

1608 13TH AVE S STE 150

Birmingham, AL 35205

Received: 10/11/13 10:10 AM

2013-09-01 VA Survey

Fax:

Phone: (630) 853-5826

Project:

10/17/2013Analysis Date:

Collected:

Sample Description Appearance % Type AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

SB4LD1-1-Wrap

391308689-0010

Cream None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

SB4LD1-1-Wrap

391308689-0010A

Cream None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB4LD1-2-Wrap

391308689-0011

Cream None Detected Non-Fibrous Heterogeneous

Non-fibrous (other)100%

SB4LD1-2-Wrap

391308689-0011A

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB4LD1-3

391308689-0012

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB5 CHIR-1

391308689-0013

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB5 CHIR-2

391308689-0014

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB5 CHIR-3

391308689-0015

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

3Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM

Jeff Siria, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0

Initial report from 10/17/2013 15:12:04

Sue Ferrario (41)

Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com

391308689 CustomerID: FDLS42 CustomerPO:

ProjectID:

EMSL Order:

Attn: Dana Tilton Fidelis, LLC

1608 13TH AVE S STE 150

Birmingham, AL 35205

Received: 10/11/13 10:10 AM

2013-09-01 VA Survey

Fax:

Phone: (630) 853-5826

Project:

10/17/2013Analysis Date:

Collected:

Sample Description Appearance % Type AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

SB6 FP 1-1

391308689-0016

Tan None Detected Non-Fibrous Homogeneous

Cellulose19% Glass9%

Mica29% Non-fibrous (other)43%

SB6 FP 1-2

391308689-0017

Tan None Detected Non-Fibrous Homogeneous

Cellulose19% Glass9%

Mica29% Non-fibrous (other)43%

SB6 FP 1-3

391308689-0018

Tan None Detected Non-Fibrous Homogeneous

Cellulose19% Glass9%

Mica29% Non-fibrous (other)43%

SB6 FP 1-4

391308689-0019

Tan None Detected Non-Fibrous Homogeneous

Cellulose19% Glass9%

Mica29% Non-fibrous (other)43%

SB6 FP 1-5

391308689-0020

Tan None Detected Non-Fibrous Homogeneous

Cellulose19% Glass9%

Mica29% Non-fibrous (other)43%

SB6 FP 1-6

391308689-0021

Tan None Detected Non-Fibrous Homogeneous

Cellulose19% Glass9%

Mica29% Non-fibrous (other)43%

SB7 PE 1-1-Wrap

391308689-0022

Various None Detected

Inseparable coating layer included in analysis.

Non-Fibrous Heterogeneous

Non-fibrous (other)100%

SB7 PE 1-1-Wrap

391308689-0022A

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

4Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM

Jeff Siria, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0

Initial report from 10/17/2013 15:12:04

Sue Ferrario (41)

Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com

391308689 CustomerID: FDLS42 CustomerPO:

ProjectID:

EMSL Order:

Attn: Dana Tilton Fidelis, LLC

1608 13TH AVE S STE 150

Birmingham, AL 35205

Received: 10/11/13 10:10 AM

2013-09-01 VA Survey

Fax:

Phone: (630) 853-5826

Project:

10/17/2013Analysis Date:

Collected:

Sample Description Appearance % Type AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

SB8 PE 2-1

391308689-0023

White None Detected Non-Fibrous Homogeneous

Glass19% Non-fibrous (other)81%

SB8 PE 2-2

391308689-0024

White None Detected Non-Fibrous Homogeneous

Glass19% Non-fibrous (other)81%

SB8 PE 2-3

391308689-0025

White None Detected Non-Fibrous Homogeneous

Glass19% Non-fibrous (other)81%

SB9 CHP 1-1-Wrap

391308689-0026

Cream None Detected Non-Fibrous Homogeneous

Glass9% Wollastonite9%

Non-fibrous (other)82%

SB9 CHP 1-1-Wrap

391308689-0026A

Various None Detected Fibrous Heterogeneous

Cellulose39% Glass19%

Non-fibrous (other)42%

SB10 DW 1-1

391308689-0027

Various None Detected Non-Fibrous Heterogeneous

Cellulose9% Glass8%

Non-fibrous (other)83%

SB10 DW 1-2

391308689-0028

Various None Detected Non-Fibrous Heterogeneous

Cellulose9% Glass8%

Non-fibrous (other)83%

SB10 DW 1-3-Joint Compound 391308689-0029

White None Detected Non-Fibrous

Homogeneous

Non-fibrous (other)100%

5Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM

Jeff Siria, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request.