266-PR26-3 – 2nd floor mechanical room SP2319-BH – pipe run insulation sample
267-PR27-1 – 2nd floor mechanical room SP2319-BH – pipe run insulation sample
268-RI1 – 2nd floor mechanical room SP2319-BH – roof insulation sample
2nd floor mechanical room SP2332-BH
269-PR28-1 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample
269-PR28-2 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample
269-PR28-3 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample
270-PR29-1 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample
270-PR29-2 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample
270-PR29-3 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample
271-PR30 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample location
271-PR30-1 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample
271-PR30-2 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample
271-PR30-3 – 2nd floor mechanical room SP2332-BH – pipe run insulation sample
272-FP9 – 2nd floor mechanical room SP2332-BH – fire proofing samples
560-CT1 – 5th floor mechanical room 5403-BH – ceiling tile and black mastic sample location
560-CT1 – 5th floor mechanical room 5403-BH – ceiling tile and black mastic sample
561-FP6 – 5th floor mechanical room 5D103 – fire proofing samples
562-FP7 – 5th floor mechanical room 5D104 – fire proofing samples
563-FP8 – 5th floor mechanical room 5D107 – fire proofing samples
564-VJ2 – 5th floor mechanical room 5D107 – vibration joint
565-FT8-1 – 5th floor chase next to service elevator – 12” x 12” floor tile with black mastic – CONTAINS
ASBESTOS
952-FP5 – 9th floor mechanical room off of patient care service main office – fire proofing samples
953-PR23-1 – 9th floor chase access next to service elevator – pipe run insulation sample
953-PR23-2 – 9th floor chase access next to service elevator – pipe run insulation sample
953-PR23-3 – 9th floor chase access next to service elevator – pipe run insulation sample
954-PR24 – 9th floor chase access next to service elevator – pipe run insulation sample
955-PR25-1 – 9th floor chase access next to service elevator – pipe run insulation sample
955-PR25-2 – 9th floor chase access next to service elevator – pipe run insulation sample
955-PR25-3 – 9th floor chase access next to service elevator – pipe run insulation sample
956-FT5-1 – 9th floor mechanical/electrical closet 9209-BH – floor tile sample – similar floor tile throughout 9th floor corridors
957-FT6 – 9th floor electrical closet 9207-BH – floor tile samples
958-WM1 – 9th floor electrical closet 9207-BH – wall mastic – assumed to be on all exterior walls –
CONTAINS ASBESTOS
958-WM1 – 9th floor electrical closet 9207-BH – wall mastic – assumed to be on all exterior walls –
CONTAINS ASBESTOS
959-FT7-1 – 9th floor electrical closet 9207-BH – floor tile sample
1049-FT4 – 10th floor closet SP10THA-BH – floor tile and mastic samples – CONTAINS ASBESTOS
11th floor fire proofing
11th floor tank room
1145-PR18-1 – 11th floor tank room – pipe run insulation sample
1145-PR18-2 – 11th floor tank room – pipe run insulation sample
1145-PR18-3 – 11th floor tank room – pipe run insulation sample
1146-PR19-1 – 11th floor tank room – pipe run insulation sample
1146-PR19-2 – 11th floor tank room – pipe run insulation sample
1146-PR19-3 – 11th floor tank room – pipe run insulation sample
1147-PR20-1 – 11th floor tank room – pipe run insulation sample
1147-PR20-2 – 11th floor tank room – pipe run insulation sample
1147-PR20-3 – 11th floor tank room – pipe run insulation sample
1148-PR21-1 – 11th floor tank room – pipe run insulation sample
1148-PR21-2 – 11th floor tank room – pipe run insulation sample
1148-PR21-3 – 11th floor tank room – pipe run insulation sample
1151-PR22-1 – 11th floor tank room – pipe run insulation sample
1151-PR22-2 – 11th floor tank room – pipe run insulation sample
1151-PR22-3 – 11th floor tank room – pipe run insulation sample
BBIIRRMMIINNGGHHAAMM VVAAMMCC AASSBBEESSTTOOSS SSUURRVVEEYY RREEPPOORRTT
Fidelis Project No.: 2013-09-001 March 2014 Appendix D
Appendix D Summary of Asbestos Laboratory
Analytical Results
Material
Sampled
And Description
SB1CH1-1-Wrap ND Yes Fair
SB1CH1-1-Wrap ND Yes Fair
SB1CH1-1-
Insulation ND No Fair
SB1CH1-2-Wrap ND Yes Fair
SB1CH1-2-Wrap ND Yes Fair
SB1CH1-2-
Insulation ND No Fair
SB1CH1-3-Wrap ND Yes Fair
SB1CH1-3-
Insulation ND No Fair
SB2CH2-1-Wrap ND No Fair
SB2CH2-1-Wrap ND No Fair
SB2CH2-2-Wrap ND No Fair
SB2CH2-2-Wrap ND No Fair
Sub Basement SB2CH2-3
White tape wrap over mineral wool insulation
ND No Fair N/A
Sub Basement SB3CH2E-1
Woven tape and mastic over mineral wool insulation
ND No Fair N/A
Sub Basement SB3CH2E-2
Woven tape and mastic over mineral wool insulation
ND No Fair N/A
Sub Basement SB3CH2E-3
Woven tape and mastic over mineral wool insulation
ND No Fair N/A
SB4LD1-1-Wrap ND No Good
SB4LD1-1-Wrap ND No Good
SB4LD1-2-Wrap ND No Good
SB4LD1-2-Wrap ND No Good
Sub Basement SB4 LD1-3 Tape and mastic on large duct ND No Good N/A
Sub Basement SB5 CHIR-1
Woven tape and mastic over mineral wool insulation
ND No Fair N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Sub Basement
Location of
Homogeneous
Area Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Approximate
Quantity 5, 6, 7
White textured jacket over black foam insulation on chiller line joint
Sub Basement
Sub Basement
Sub Basement
Sub Basement
Sub Basement
Tape and mastic on large duct
SUB BASEMENT
White textured jacket over black foam insulation on chiller line joint
White textured jacket over black foam insulation on chiller line joint
White tape wrap over mineral wool insulation
White tape wrap over mineral wool insulation
Tape and mastic on large duct
Sub Basement
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Sub Basement
Location of
Homogeneous
Area Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Approximate
Quantity 5, 6, 7
Sub Basement SB5 CHIR-2
Woven tape and mastic over mineral wool insulation
ND No Fair N/A
Sub Basement SB5 CHIR-3
Woven tape and mastic over mineral wool insulation
ND No Fair N/A
Sub Basement SB6 FP1-1 Fire Proofing ND Yes Good N/A
Sub Basement SB6 FP1-2 Fire Proofing ND Yes Good N/A
Sub Basement SB6 FP1-3 Fire Proofing ND Yes Good N/A
Sub Basement SB6 FP1-4 Fire Proofing ND Yes Good N/A
Sub Basement SB6 FP1-5 Fire Proofing ND Yes Good N/A
Sub Basement SB6 FP1-6 Fire Proofing ND Yes Good N/A
SB7 PE1-1-Wrap ND Yes Fair
SB7 PE1-1-Wrap ND Yes Fair
Sub Basement SB8 PE2-1
Woven tape over mineral wool insulation
ND No Fair N/A
Sub Basement SB8 PE2-2
Woven tape over mineral wool insulation
ND No Fair N/A
Sub Basement SB8 PE2-3
Woven tape over mineral wool insulation
ND No Fair N/A
SB9 CHP1-1-
Wrap ND No Fair
SB9 CHP1-1-
Wrap ND No Fair
Sub Basement SB10 DW1-1 Drywall ND Yes Poor N/A
Sub Basement SB10 DW1-2 Drywall ND Yes Poor N/A
SB10 DW1-3-Joint
Compound ND Yes Poor
SB10 DW1-3-
Drywall ND Yes Poor
N/A
N/A
N/A
“A” - signifies multi-layered
ND = No asbestos detected
Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other areas that were not assessable during this survey
Friability was determined according to a material’s current condition.
It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.
It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.
Abbreviations - LF = linear feet; SF = square feet
Plastic cover over mineral wool insulation
Plaster patch over mineral wool insulation
Drywall
Sub Basement
And Description
2SB11 PE3-1-
Wrap ND No Fair
2SB11 PE3-1-
Insulation ND No Fair
2SB11 PE3-2-
Wrap ND No Fair
2SB11 PE3-2-
Insulation ND No Fair
2SB11 PE3-3-
Wrap ND No Fair
2SB11 PE3-3-
Insulation ND No Fair
2SB12 PJ1-1-
Wrap ND Yes Fair
2SB12 PJ1-1-
Insulation ND Yes Fair
Sub Basement 2 2SB12 PJ1-2
Cementisous insulation under metal jacket
ND Yes Fair N/A
2SB12 PJ1-3-
Wrap ND Yes Fair
2SB12 PJ1-3-
Insulation ND Yes Fair
Sub Basement 2 2SB13 PR1-1
Fiberous paper over mineral wool insulation
ND Yes Fair N/A
Sub Basement 2 2SB13 PR1-2
Fiberous paper over mineral wool insulation
ND Yes Fair N/A
Sub Basement 2 2SB14 PR2-1
Grey cementisous insulation covered by metal sleeve
ND Yes Poor N/A
Sub Basement 2 2SB15 PJ2-1 Putty over pipe joint ND Yes Fair N/A
Sub Basement 2 2SB15 PJ2-2 Putty over pipe joint ND Yes Fair N/A
Sub Basement 2 2SB15 PJ2-3 Putty over pipe joint ND Yes Fair N/A
2SB16 PE4-1-
Wrap ND Yes Fair
2SB16 PE4-1-
Wrap ND Yes Fair
2SB16 PE4-1-
Insulation ND Yes Fair
2SB16 PE4-2-
Wrap ND Yes Fair
2SB16 PE4-2-
Insulation ND Yes Fair
Location of
Homogeneous
Area Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Sub Basement 2
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Sub Basement 2
Sub Basement 2
Sub Basement 2
Sub Basement 2
Sub Basement 2
Sub Basement 2
N/A
N/A
N/A
N/A
N/A
N/A
Approximate
Quantity 5, 6, 7
N/A
Hard plaster over pipe elbow
Hard plaster over pipe elbow
Hard plaster over pipe elbow
Cementisous insulation under metal jacket
Cementisous insulation under metal jacket
Woven mesh pipe elbow over mineral wool insulation
Woven mesh pipe elbow over mineral wool insulation
Sub Basement 2
And Description
Location of
Homogeneous
Area Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Sub Basement 2
Approximate
Quantity 5, 6, 7
2SB16 PE4-3-
Wrap ND Yes Fair
2SB16 PE4-3-
Insulation ND Yes Fair
2SB17 PE5-1-
Wrap 4% Chrysotile Yes Poor
2SB17 PE5-1-
Wrap ND Yes Poor
2SB18 PR3-1-
Wrap ND Yes Fair
2SB18 PR3-1-
Wrap ND Yes Fair
2SB18 PR3-1-
Insulation ND Yes Fair
2SB18 PR3-2-
Wrap ND Yes Fair
2SB18 PR3-2-
Wrap ND Yes Fair
2SB18 PR3-2-
Insulation ND Yes Fair
2SB19 PE6-1-
Wrap ND No Good
2SB19 PE6-1-
Insulation ND No Good
2SB19 PE6-2-
Wrap ND No Good
2SB19 PE6-2-
Insulation ND No Good
2SB20 PR4-1-
Insulation ND Yes Fair
2SB20 PR4-1-
Insulation ND Yes Fair
2SB20 PR4-2-
Insulation ND Yes Fair
2SB20 PR4-2-
Insulation ND Yes Fair
2SB20 PR4-3-
Insulation ND Yes Fair
2SB20 PR4-3-
Insulation ND Yes Fair
Sub Basement 2 2SB21 PR5-1
Woven paper over mineral wool insulation
ND Yes Poor N/A
Sub Basement 2 2SB21 PR5-2
Woven paper over mineral wool insulation
ND Yes Poor N/A
Sub Basement 2 2SB22 DM1-1 Mastic over duct joint ND No Good N/A
Sub Basement 2 2SB22 DM1-2 Mastic over duct joint ND No Good N/A
Mastic, woven fabric, cellulose fabric over mineral wool insulation Mastic, woven fabric, cellulose fabric over mineral wool insulation Mastic, woven fabric, cellulose fabric over mineral wool insulation
N/A
4 LF
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Woven mesh pipe elbow over mineral wool insulation
Woven paper with fibers over mineral wool insulation
Woven paper over black insulation
Woven paper over black insulation
White plaster over black insulation
White plaster over black insulation
Sub Basement 2
Sub Basement 2
Sub Basement 2
Sub Basement 2
Sub Basement 2
Sub Basement 2
Sub Basement 2
And Description
Location of
Homogeneous
Area Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Sub Basement 2
Approximate
Quantity 5, 6, 7
“A” - signifies multi-layered
ND = No asbestos detected
Friability was determined according to a material’s current condition.
It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.
It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.
Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other areas that were not assessable during this survey
And Description
B23 FT1-1-Floor tile ND No Fair
B23 FT1-1-
Adhesive 9% Chrysotile No Fair
B23 FT1-2-Floor tile ND No Fair
B23 FT1-2-
Adhesive Stop Positive No Fair
Basement B24 DI2-1 Duct insulation ND No Good N/A
Basement B25 DI3-1-Wrap ND No Good
Basement B25 DI3-1-Wrap ND No Good
Basement B25 DI3-2 Duct insulation ND No Good N/A
Basement B25 DI3-3 Duct insulation ND No Good N/A
Basement B26 PR6-1
Woven paper
(purple) over mineral wool insulation
ND No Good N/A
Basement B26 PR6-2
Woven paper
(purple) over mineral wool insulation
ND No Good N/A
Basement B26 PR6-3
Woven paper
(purple) over mineral wool insulation
ND No Good N/A
Basement B27 VJ1-1
Woven fabric
(green) over vibration joint
ND No Fair N/A
Basement B27VJ1-2
Woven fabric
(green) over vibration joint
ND No Fair N/A
Basement B28 CP1-1
Thick flaking black paint with white backing on ceiling of incinerator room
ND Yes Poor N/A
Basement B28 CP1-2
Thick flaking black paint with white backing on ceiling of incinerator room
ND Yes Poor N/A
Basement B28 CP1-3
Thick flaking black paint with white backing on ceiling of incinerator room
ND Yes Poor N/A
Basement B29 PC1-1
Woven fabric on pipe run in incinerator room
ND Yes Poor N/A
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Basement
N/A
Asbestos Survey
Basement
Duct insulation
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Basement 15 SF
15 SF
12"x12" Brown floor tile with black mastic
12"x12" Brown floor tile with black mastic
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Basement
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Basement B29 PC1-2
Woven fabric on pipe run in incinerator room
ND Yes Poor N/A
Basement B29 PC1-3
Woven fabric on pipe run in incinerator room
ND Yes Poor N/A
Basement B30 PR7-1
Brown woven paper with aluminum backing over mineral wool on pipe run in incinerator room
ND Yes Poor N/A
Basement B30 PR7-2
Brown woven paper with aluminum backing over mineral wool on pipe run in incinerator room
ND Yes Poor N/A
Basement B30 PR7-3
Brown woven paper with aluminum backing over mineral wool on pipe run in incinerator room
ND Yes Poor N/A
Basement B31 PR8-1
Woven paper
(purple) with aluminum backing over fiberglass -
SPB100C-BH
ND No Fair N/A
Basement B31 PR8-2
Woven paper
(purple) with aluminum backing over fiberglass -
SPB100C-BH
ND No Fair N/A
Basement B31 PR8-3
Woven paper
(purple) with aluminum backing over fiberglass -
SPB100C-BH
ND No Fair N/A
B32 PR9-1-Wrap ND Yes Fair
B32 PR9-1-Wrap ND Yes Fair
B32 PR9-1-
Insulation ND Yes Fair
B32 PR9-2-Wrap ND Yes Fair
Basement N/A
Woven paper
(purple) with aluminum backing over hard foam insulation -
SPB100C-BHWoven paper
(purple) with
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Basement
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
B32 PR9-2-Wrap ND Yes Fair
B32 PR9-2-
Insulation ND Yes Fair
B32 PR9-3-Wrap ND Yes Fair
B32 PR9-3-Wrap ND Yes Fair
B32 PR9-3-
Insulation ND Yes Fair
B33 PR10-1-
Wrap ND No Fair
B33 PR10-1-
Wrap ND No Fair
B33 PR10-1-
Wrap ND No Fair
B33 PR10-2-
Wrap ND No Fair
B33 PR10-2-
Wrap ND No Fair
B33 PR10-2-
Wrap ND No Fair
B33 PR10-3-
Wrap ND No Fair
B33 PR10-3-
Wrap ND No Fair
N/ABasement
Basement
Basement
Basement N/A
Woven paper
(yellow) and woven cloth over mineral wool insulation -
SPB100C-BH
Woven paper
(purple) with aluminum backing over hard foam insulation -
SPB100C-BH
Woven paper
(yellow) and woven cloth over mineral wool insulation -
SPB100C-BH
Woven paper
(yellow) and woven cloth over mineral wool insulation -
SPB100C-BH
N/A
N/A
Basement N/A aluminum backing over hard foam insulation -
SPB100C-BH
“A” - signifies multi-layered
ND = No asbestos detected
Friability was determined according to a material’s current condition.
It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.
It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.
Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other
And Description
Ground Floor G34 PR11-1
4" pipe insulation
(white) woven plastic over mineral wool
ND No Fair N/A
Ground Floor G34 PR11-2
4" pipe insulation
(white) woven plastic over mineral wool
ND No Fair N/A
Ground Floor G34 PR11-3
4" pipe insulation
(white) woven plastic over mineral wool
ND No Fair N/A
G35 PR12-1-
Sealant ND No Good
G35 PR12-1-
Wrap ND No Good
G35 PR12-1-
Wrap ND No Good
G35 PR12-1-
Adhesive ND No Good
G35 PR12-2-
Wrap ND No Good
G35 PR12-2-
Wrap ND No Good
G35 PR12-2-
Adhesive ND No Good
G35 PR12-3-
Sealant ND No Good
G35 PR12-3-
Wrap ND No Good
G35 PR12-3-
Wrap ND No Good
G35 PR12-3-
Adhesive ND No Good
Ground Floor G36 FP2-1
Fire Proofing
(grey) - SPG415-
BH
9% Chrysotile Yes Fair 400 SF
Ground Floor G36 FP2-2
Fire Proofing
(grey) - SPG415-
BH
9% Chrysotile Yes Fair 400 SF
Ground Floor G36 FP2-3
Fire Proofing
(grey) - SPG415-
BH
9% Chrysotile Yes Fair 400 SF
G37 PJ3-1-
Sealant ND Yes Poor
G37 PJ3-1-Wrap ND Yes Poor
N/A
N/A
N/A
N/A
Ground Floor
Ground Floor
Ground Floor
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Ground Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Ground Floor
Woven cloth over aluminum tape over mineral wool
Orange painted mastic over aluminum tape and mineral wool -
SPGD120-BH
Woven cloth over aluminum tape over mineral wool
Woven cloth over aluminum tape over mineral wool
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Ground Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
G37 PJ3-2-
Sealant ND Yes Poor
G37 PJ3-2-Wrap ND Yes Poor
G37 PJ3-3-
Sealant ND Yes Poor
G37 PJ3-3-Wrap ND Yes Poor
Ground Floor G38 PR13-1
Woven paper
(white) with aluminum backing over mineral wool -
SPG509-BH
ND No Fair N/A
Ground Floor G38 PR13-2
Woven paper
(white) with aluminum backing over mineral wool -
SPG509-BH
ND No Fair N/A
G38 PR13-3-
Wrap ND No Fair
G38 PR13-3-
Adhesive ND No Fair
Ground Floor G39 PR14-1
Woven paper
(purple) with aluminum backing over mineral wool -
SPG509-BH
ND No Fair N/A
Ground Floor G39 PR14-2
Woven paper
(purple) with aluminum backing over mineral wool -
SPG509-BH
ND No Fair N/A
G39 PR14-3-
Sealant ND No Fair
G39 PR14-3-
Wrap ND No Fair
Ground Floor G40 PR15-1
Painted yellow mastic over pipe run insulation -
SPG509-BH
ND Yes Poor N/A
N/A
N/A
N/A
N/A
Ground Floor
Ground Floor
Ground Floor
Ground Floor
Woven paper
(white) with aluminum backing over mineral wool -
SPG509-BH
Orange painted mastic over aluminum tape and mineral wool -
SPGD120-BH
Orange painted mastic over aluminum tape and mineral wool -
SPGD120-BH
Woven paper
(purple) with aluminum backing over mineral wool -
SPG509-BH
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Ground Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Ground Floor G40 PR15-2
Painted yellow mastic over pipe run insulation -
SPG509-BH
ND Yes Poor N/A
Ground Floor G41 FP3-1
Fire Proofing
(grey) - SPG514-
BH
ND Yes Fair N/A
Ground Floor G41 FP3-2
Fire Proofing
(grey) - SPG514-
BH
ND Yes Fair N/A
Ground Floor G41 FP3-3
Fire Proofing
(grey) - SPG514-
BH
ND Yes Fair N/A
Ground Floor G41 FP3-4
Fire Proofing
(grey) - SPG514-
BH
ND Yes Fair N/A
Ground Floor G41 FP3-5
Fire Proofing
(grey) - SPG514-
BH
ND Yes Fair N/A
G42 PR16-1-
Sealant 9% Chrysotile Yes Poor
G42 PR16-1-
Wrap ND Yes Poor
G42 PR16-2-
Sealant 9% Chrysotile Yes Poor
G42 PR16-2-
Wrap ND Yes Poor
G42 PR16-3-
Sealant 9% Chrysotile Yes Poor
G42 PR16-3-
Wrap ND Yes Poor
Ground Floor G43 PR17-1
Woven paper
(orange) with aluminum backing over mineral wool -
M-R-1
ND No Fair N/A
G43 PR17-2-
Sealant ND No Fair
G43 PR17-2-
Adhesive ND No Fair
G43 PR17-2-
Wrap ND No Fair
300 LF
300 LF
Ground Floor N/A
300 LF
Woven paper
(orange) with aluminum backing over mineral wool -
M-R-1
Woven paper
(purple) with aluminum backing over mineral wool - M-
R-1
Ground Floor
Ground Floor
Ground Floor
Woven paper
(purple) with aluminum backing over mineral wool - M-
R-1
Woven paper
(purple) with aluminum backing over mineral wool - M-
R-1
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Ground Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
RE44 FT3-1-
Flooring
Compound
ND No Poor
RE44 FT3-1-
Adhesive ND No Poor
RE44 FT3-1-
Paper ND No Poor
Ground Floor N/A
Floor tile, flooring compound and adhesive from
Research
Elevator floor
“A” - signifies multi-layered
ND = No asbestos detected
Friability was determined according to a material’s current condition.
It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.
It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.
Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other
And Description
2nd Floor 266 PR26-1
Woven paper with aluminum backing on purple pipe run -
SP2319-BH
ND No Fair N/A
2nd Floor 266 PR26-2
Woven paper with aluminum backing on purple pipe run -
SP2319-BH
ND No Fair N/A
2nd Floor 266 PR26-3
Woven paper with aluminum backing on purple pipe run -
SP2319-BH
ND No Fair N/A
2nd Floor 267 PR27-1
Woven paper with aluminum backing on orange pipe run -
SP2319-BH
ND No Fair N/A
2nd Floor 268 RI1-1
Roof Insulation -insulation between 2 metal layers making up the roof - SP2319-
BH
ND Yes Poor N/A
2nd Floor 268 RI1-2
Roof Insulation -insulation between 2 metal layers making up the roof - SP2319-
BH
ND Yes Poor N/A
2nd Floor 268 RI1-3
Roof Insulation -insulation between 2 metal layers making up the roof - SP2319-
BH
ND Yes Poor N/A
2nd Floor 269 PR28-1
Woven paper with aluminum backing on purple pipe run insulation -
SP2332-BH
ND Yes Poor N/A
Approximate
Quantity 5, 6, 7
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
2nd Floor
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
And Description
Approximate
Quantity 5, 6, 7
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
2nd Floor
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
2nd Floor 269 PR28-2
Woven paper with aluminum backing on purple pipe run insulation -
SP2332-BH
ND Yes Poor N/A
2nd Floor 269 PR28-3
Woven paper with aluminum backing on purple pipe run insulation -
SP2332-BH
ND Yes Poor N/A
2nd Floor 270 PR29-1
Hard plaster over mineral wool from orange pipe run -
SP2332-BH
ND Yes Poor N/A
2nd Floor 270 PR29-2
Hard plaster over mineral wool from orange pipe run -
SP2332-BH
ND Yes Poor N/A
2nd Floor 270 PR29-3
Hard plaster over mineral wool from orange pipe run -
SP2332-BH
ND Yes Poor N/A
271 PR30-1-
Wrap ND Yes Poor
271 PR30-1-
Wrap ND Yes Poor
2nd Floor 271 PR30-2
Woven paper over aluminum backing from white pipe run insulation -
SP2332-BH
ND Yes Poor N/A
2nd Floor 271 PR30-3
Woven paper over aluminum backing from white pipe run insulation -
SP2332-BH
ND Yes Poor N/A
2nd Floor 272 FP9-1
White/light grey fire proofing -
SP2332-BH
ND Yes Fair N/A
2nd Floor 272 FP9-2
White/light grey fire proofing -
SP2332-BH
ND Yes Fair N/A
Woven paper over aluminum backing from white pipe run insulation -
SP2332-BH
2nd Floor N/A
And Description
Approximate
Quantity 5, 6, 7
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
2nd Floor
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
2nd Floor 272 FP9-3
White/light grey fire proofing -
SP2332-BH
ND Yes Fair N/A
2nd Floor 272 FP9-4
White/light grey fire proofing -
SP2332-BH
ND Yes Fair N/A
2nd Floor 272 FP9-5
White/light grey fire proofing -
SP2332-BH
ND Yes Fair N/A
“A” - signifies multi-layered
ND = No asbestos detected
Friability was determined according to a material’s current condition.
It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.
It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.
Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other
And Description
560 CT1-1-
Ceiling tile ND No Good
560 CT1-1-
Adhesive ND No Good
560 CT1-2-
Ceiling tile ND No Good
560 CT1-2-
Adhesive ND No Good
5th Floor 561 FP6-1
Fire proofing
(white) -
5403-BH
ND Yes Fair N/A
5th Floor 561 FP6-1
Fire proofing
(white) -
5D103
ND Yes Fair N/A
5th Floor 561 FP6-3
Fire proofing
(white) -
5D103
ND Yes Fair N/A
5th Floor 561 FP6-4
Fire proofing
(white) -
5D103
ND Yes Fair N/A
5th Floor 561 FP6-5
Fire proofing
(white) -
5D103
ND Yes Fair N/A
5th Floor 562 FP7-1
Fire proofing
(light grey) -
5D104
ND Yes Fair N/A
5th Floor 562 FP7-2
Fire proofing
(light grey) -
5D104
ND Yes Fair N/A
5th Floor 562 FP7-3
Fire proofing
(light grey) -
5D104
ND Yes Fair N/A
5th Floor 562 FP7-4
Fire proofing
(light grey) -
5D104
ND Yes Fair N/A
5th Floor 562 FP7-5
Fire proofing
(light grey) -
5D104
ND Yes Fair N/A
5th Floor 563 FP8-1
Fire proofing
(dark grey) -
5D107
ND Yes Fair N/A
5th Floor 563 FP8-2
Fire proofing
(dark grey) -
5D107
ND Yes Fair N/A
5th Floor 563 FP8-3
Fire proofing
(dark grey) -
5D107
ND Yes Fair N/A
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
5th Floor
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Ceiling tile and mastic -
5403-BH
Ceiling tile and mastic -
5403-BH
Approximate
Quantity 5, 6, 7
5th Floor
5th Floor
N/A
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
5th Floor
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
Approximate
Quantity 5, 6, 7
5th Floor 563 FP8-4
Fire proofing
(dark grey) -
5D107
ND Yes Fair N/A
5th Floor 563 FP8-5
Fire proofing
(dark grey) -
5D107
ND Yes Fair N/A
564 VJ2-1-
Insulation ND No Fair
564 VJ2-1-Caulk ND No Fair
564 VJ2-2-
Insulation ND No Fair
564 VJ2-2-Caulk ND No Fair
565 FT 8-1-
Miscellaneous ND No Fair
565 FT8-1-Floor
Tile 4% Chrysotile No Fair
565 FT8-1-
Adhesive 9% Chrysotile No Fair
“A” - signifies multi-layered
ND = No asbestos detected
Friability was determined according to a material’s current condition.
It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.
It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.
Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other areas that were not assessable during this survey
12" x 12" floor tile with black mastic -
5th floor chase next to service elevator
Vibration Joint
10 SF
5th Floor
5th Floor
And Description
9th Floor 952 FP5-1
Fire Proofing
(light grey) - 9th floor patient care service main office mechanical room
ND Yes Fair N/A
9th Floor 952 FP5-2
Fire Proofing
(light grey) - 9th floor patient care service main office mechanical room
ND Yes Fair N/A
9th Floor 952 FP5-3
Fire Proofing
(light grey) - 9th floor patient care service main office mechanical room
ND Yes Fair N/A
9th Floor 953 PR23-1
Woven paper over aluminum backed tape over mineral wool - 9th floor chase access
ND No Fair N/A
9th Floor 953 PR23-2
Woven paper over aluminum backed tape over mineral wool - 9th floor chase access
ND No Fair N/A
9th Floor 953 PR23-3
Woven paper over aluminum backed tape over mineral wool - 9th floor chase access
ND No Fair N/A
9th Floor 954 PR24-1
Cloth fabric over mineral wool insulation - 9th floor chase access
ND Yes Poor N/A
9th Floor 954 PR24-2
Cloth fabric over mineral wool insulation - 9th floor chase access
ND Yes Poor N/A
9th Floor 954 PR24-3
Cloth fabric over mineral wool insulation - 9th floor chase access
ND Yes Poor N/A
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Ninth Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Ninth Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
9th Floor 955 PR25-1
Woven fabric over mineral wool insulation - 9th floor chase access
ND Yes Poor N/A
9th Floor 955 PR25-2
Woven fabric over mineral wool insulation - 9th floor chase access
ND Yes Poor N/A
9th Floor 955 PR25-3
Woven fabric over mineral wool insulation - 9th floor chase access
ND Yes Poor N/A
956 FT5-1-Floor
Tile ND No Good
956 FT5-1-
Adhesive ND No Good
956 FT5-1-Floor
Tile ND No Good
956 FT5-1-
Adhesive ND No Good
957 FT6-1-Floor
Tile ND No Good
957 FT6-1-
Adhesive ND No Good
957 FT6-2-Floor
Tile ND No Good
957 FT6-2-
Adhesive ND No Good
9th Floor 958 WM1-1
Wall mastic in
9th floor electrical closet
9% Chrysotile No Fair 50 SF
9th Floor 958 WM1-2
Wall mastic in
9th floor electrical closet
9% Chrysotile No Fair 50 SF
9th Floor 958 WM1-3
Wall mastic in
9th floor electrical closet
9% Chrysotile No Fair 50 SF
9th Floor 958 WM1-4
Wall mastic in
9th floor electrical closet
9% Chrysotile No Fair 50 SF
12" x 12" floor tile and adhesive in
9th floor electrical closet
12" x 12" floor tile and adhesive in
9th floor electrical closet
12" x 12" floor tile
- two layers of floor tile and adhesive -throughout 9th floor halls
9th Floor
9th Floor
9th Floor N/A
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
Ninth Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
9th Floor 958 WM1-5
Wall mastic in
9th floor electrical closet
9% Chrysotile No Fair 50 SF
959 FT7-1-Floor
Tile ND No Good
959 FT7-1-
Adhesive ND No Good
12" x 12" floor tile with black mastic over leveling compund near door jam of 9th floor electrical closet
9th Floor N/A
“A” - signifies multi-layered
ND = No asbestos detected
Friability was determined according to a material’s current condition.
It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.
It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.
Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other
And Description
1049 FT4-1-
Floor Tile 4% Chrysotile No Fair
1049 FT4-1-
Adhesive 9% Chrysotile No Fair
1049 FT4-2-
Floor Tile 4% Chrysotile No Fair
1049 FT4-2-
Adhesive 9% Chrysotile No Fair
10th Floor 1050 FP4-1
Fire proofing
(light grey) -
SP10THD-BH
ND Yes Fair N/A
10th Floor 1050 FP4-2
Fire proofing
(light grey) -
SP10THD-BH
ND Yes Fair N/A
10th Floor 1050 FP4-3
Fire proofing
(light grey) -
SP10THD-BH
ND Yes Fair N/A
10th Floor 1050 FP4-4
Fire proofing
(light grey) -
SP10THD-BH
ND Yes Fair N/A
10th Floor 1050 FP4-5
Fire proofing
(light grey) -
SP10THD-BH
ND Yes Fair N/A
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
10th Floor
“A” - signifies multi-layered
ND = No asbestos detected
Friability was determined according to a material’s current condition.
It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.
It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.
Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other areas that were not assessable during this survey
10th Floor
12" x 12" brown floor tile with black mastic -
SP10THA-BH
12" x 12" brown floor tile with black mastic -
SP10THA-BH
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area
Sample Number
Asbestos
Content 2 Friable
Condition of
Material
10th Floor
15 SF
15 SF
And Description
11th Floor 1145 PR18-1
Woven paper
(orange) with aluminum backing - 11th floor tank room
ND Yes Poor N/A
11th Floor 1145 PR18-2
Woven paper
(orange) with aluminum backing - 11th floor tank room
ND Yes Poor N/A
11th Floor 1145 PR18-3
Woven paper
(orange) with aluminum backing - 11th floor tank room
ND Yes Poor N/A
11th Floor 1146 PR19-1
Painted cloth
(yellow) over mineral wool -
11th floor tank room
ND Yes Poor N/A
11th Floor 1146 PR19-2
Painted cloth
(yellow) over mineral wool -
11th floor tank room
ND Yes Poor N/A
11th Floor 1146 PR19-3
Painted cloth
(yellow) over mineral wool -
11th floor tank room
ND Yes Poor N/A
11th Floor 1147 PR20-1
Woven cloth
(yellow) over two layers of aluminum backed taped over mineral wool -
11th floor tank room
ND Yes Poor N/A
1147 PR20-2-
Wrap ND Yes Poor
1147 PR20-2-
Wrap ND Yes Poor
N/A11th Floor
Woven cloth
(yellow) over two layers of aluminum backed taped over mineral wool -
11th floor tank room
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
11th Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area Sample Number
Asbestos
Content 2 Friable
Condition of
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
11th Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area Sample Number
Asbestos
Content 2 Friable
Condition of
Material
1147 PR20-3-
Wrap ND Yes Poor
1147 PR20-3-
Wrap ND Yes Poor
1147 PR20-3-
Wrap ND Yes Poor
11th Floor 1148 PR21-1
Woven paper
(purple) over aluminum backed tape over mineral wool - 11th floor tank room
ND Yes Poor N/A
11th Floor 1148 PR21-2
Woven paper
(purple) over aluminum backed tape over mineral wool - 11th floor tank room
ND Yes Poor N/A
1148 PR21-3-
Wrap ND Yes Poor
1148 PR21-3-
Wrap ND Yes Poor
1151 PR22-1-
Wrap ND No Fair
1151 PR22-1-
Wrap ND No Fair
1151 PR22-1-
Wrap ND No Fair
1151 PR22-2-
Wrap ND No Fair
1151 PR22-2-
Wrap ND No Fair
1151 PR22-2-
Wrap ND No Fair
1151 PR22-3-
Wrap ND No Fair
1151 PR22-3-
Wrap ND No Fair
1151 PR22-3-
Wrap ND No Fair
N/A
11th Floor N/A
N/A
N/A
N/A
11th Floor
11th Floor
11th Floor
11th Floor
Woven cloth
(white) over cardboard over woen cloth over mineral wool -
11th floor tank room
Woven cloth
(yellow) over two layers of aluminum backed taped over mineral wool -
11th floor tank room
Woven paper
(purple) over aluminum backed tape over mineral wool - 11th floor tank room
Woven cloth
(white) over cardboard over woen cloth over mineral wool -
11th floor tank room
Woven cloth
(white) over cardboard over woen cloth over mineral wool -
11th floor tank room
And Description
Sampling Results and Estimated Quantities
Birmingham VA Medical Center
Asbestos Survey
11th Floor
Approximate
Quantity 5, 6, 7
Location of
Homogeneous
Area Sample Number
Asbestos
Content 2 Friable
Condition of
Material
“A” - signifies multi-layered
ND = No asbestos detected
Friability was determined according to a material’s current condition.
It should be noted that the condition of the materials sampled is based on the top layer of the sampled materials only at the time of sampling.
It should be noted that these areas are based on the BESI/BEA JV’s observations and are approximate. The contractor must visit the site and perform an independent measurement of the quantities. The BESI/BEA JV is not responsible for any discrepancies in the estimation of quantities of materials.
Abbreviations - LF = linear feet; SF = square feet Ductwork and transite pipes may be hidden behind walls and above ceilings in the structure and the duct tape may be in other
BBIIRRMMIINNGGHHAAMM VVAAMMCC AASSBBEESSTTOOSS SSUURRVVEEYY RREEPPOORRTT
Fidelis Project No.: 2013-09-001 March 2014 Appendix E
Appendix E
Laboratory Results and Chains of Custody
EMSL Analytical, Inc.
3029 S. Jefferson, Saint Louis, MO 63118 Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com
391308689 CustomerID: FDLS42 CustomerPO:
ProjectID:
EMSL Order:
Attn: Dana Tilton Fidelis, LLC
1608 13TH AVE S STE 150
Birmingham, AL 35205
Received: 10/11/13 10:10 AM
2013-09-01 VA Survey
Fax:
Phone: (630) 853-5826
Project:
10/17/2013Analysis Date:
Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
SB1CH1-1-Wrap
391308689-0001
Cream None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
SB1CH1-1-Wrap
391308689-0001A
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB1CH1-1-
Insulation 391308689-0001B
Black None Detected Non-Fibrous
Homogeneous
Non-fibrous (other)100%
SB1CH1-2-Wrap
391308689-0002
Cream None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
SB1CH1-2-Wrap
391308689-0002A
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB1CH1-2-
Insulation 391308689-0002B
Black None Detected Non-Fibrous
Homogeneous
Non-fibrous (other)100%
SB1CH1-3-Wrap
391308689-0003
Cream None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
SB1CH1-3-
Insulation 391308689-0003A
Black None Detected Non-Fibrous
Homogeneous
Non-fibrous (other)100%
1Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM
Jeff Siria, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0
Initial report from 10/17/2013 15:12:04
Sue Ferrario (41) http://www.EMSL.com mailto:saintlouislab@emsl.com
Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com
391308689 CustomerID: FDLS42 CustomerPO:
ProjectID:
EMSL Order:
Attn: Dana Tilton Fidelis, LLC
1608 13TH AVE S STE 150
Birmingham, AL 35205
Received: 10/11/13 10:10 AM
2013-09-01 VA Survey
Fax:
Phone: (630) 853-5826
Project:
10/17/2013Analysis Date:
Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
SB2CH2-1-Wrap
391308689-0004
Cream None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
SB2CH2-1-Wrap
391308689-0004A
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB2CH2-2-Wrap
391308689-0005
Cream None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
SB2CH2-2-Wrap
391308689-0005A
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB2CH2-3
391308689-0006
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB3CH2E-1
391308689-0007
Cream None Detected Non-Fibrous Homogeneous
Glass19% Wollastonite4%
Non-fibrous (other)77%
SB3CH2E-2
391308689-0008
Cream None Detected Non-Fibrous Homogeneous
Glass19% Wollastonite4%
Non-fibrous (other)77%
SB3CH2E-3
391308689-0009
Cream None Detected Non-Fibrous Homogeneous
Glass19% Wollastonite4%
Non-fibrous (other)77%
2Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM
Jeff Siria, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0
Initial report from 10/17/2013 15:12:04
Sue Ferrario (41)
Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com
391308689 CustomerID: FDLS42 CustomerPO:
ProjectID:
EMSL Order:
Attn: Dana Tilton Fidelis, LLC
1608 13TH AVE S STE 150
Birmingham, AL 35205
Received: 10/11/13 10:10 AM
2013-09-01 VA Survey
Fax:
Phone: (630) 853-5826
Project:
10/17/2013Analysis Date:
Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
SB4LD1-1-Wrap
391308689-0010
Cream None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
SB4LD1-1-Wrap
391308689-0010A
Cream None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB4LD1-2-Wrap
391308689-0011
Cream None Detected Non-Fibrous Heterogeneous
Non-fibrous (other)100%
SB4LD1-2-Wrap
391308689-0011A
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB4LD1-3
391308689-0012
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB5 CHIR-1
391308689-0013
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB5 CHIR-2
391308689-0014
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB5 CHIR-3
391308689-0015
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
3Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM
Jeff Siria, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0
Initial report from 10/17/2013 15:12:04
Sue Ferrario (41)
Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com
391308689 CustomerID: FDLS42 CustomerPO:
ProjectID:
EMSL Order:
Attn: Dana Tilton Fidelis, LLC
1608 13TH AVE S STE 150
Birmingham, AL 35205
Received: 10/11/13 10:10 AM
2013-09-01 VA Survey
Fax:
Phone: (630) 853-5826
Project:
10/17/2013Analysis Date:
Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
SB6 FP 1-1
391308689-0016
Tan None Detected Non-Fibrous Homogeneous
Cellulose19% Glass9%
Mica29% Non-fibrous (other)43%
SB6 FP 1-2
391308689-0017
Tan None Detected Non-Fibrous Homogeneous
Cellulose19% Glass9%
Mica29% Non-fibrous (other)43%
SB6 FP 1-3
391308689-0018
Tan None Detected Non-Fibrous Homogeneous
Cellulose19% Glass9%
Mica29% Non-fibrous (other)43%
SB6 FP 1-4
391308689-0019
Tan None Detected Non-Fibrous Homogeneous
Cellulose19% Glass9%
Mica29% Non-fibrous (other)43%
SB6 FP 1-5
391308689-0020
Tan None Detected Non-Fibrous Homogeneous
Cellulose19% Glass9%
Mica29% Non-fibrous (other)43%
SB6 FP 1-6
391308689-0021
Tan None Detected Non-Fibrous Homogeneous
Cellulose19% Glass9%
Mica29% Non-fibrous (other)43%
SB7 PE 1-1-Wrap
391308689-0022
Various None Detected
Inseparable coating layer included in analysis.
Non-Fibrous Heterogeneous
Non-fibrous (other)100%
SB7 PE 1-1-Wrap
391308689-0022A
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
4Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM
Jeff Siria, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Saint Louis, MO NVLAP Lab Code 200742-0
Initial report from 10/17/2013 15:12:04
Sue Ferrario (41)
Phone/Fax: (314) 577-0150 / (314) 776-3313 http://www.EMSL.com saintlouislab@emsl.com
391308689 CustomerID: FDLS42 CustomerPO:
ProjectID:
EMSL Order:
Attn: Dana Tilton Fidelis, LLC
1608 13TH AVE S STE 150
Birmingham, AL 35205
Received: 10/11/13 10:10 AM
2013-09-01 VA Survey
Fax:
Phone: (630) 853-5826
Project:
10/17/2013Analysis Date:
Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
SB8 PE 2-1
391308689-0023
White None Detected Non-Fibrous Homogeneous
Glass19% Non-fibrous (other)81%
SB8 PE 2-2
391308689-0024
White None Detected Non-Fibrous Homogeneous
Glass19% Non-fibrous (other)81%
SB8 PE 2-3
391308689-0025
White None Detected Non-Fibrous Homogeneous
Glass19% Non-fibrous (other)81%
SB9 CHP 1-1-Wrap
391308689-0026
Cream None Detected Non-Fibrous Homogeneous
Glass9% Wollastonite9%
Non-fibrous (other)82%
SB9 CHP 1-1-Wrap
391308689-0026A
Various None Detected Fibrous Heterogeneous
Cellulose39% Glass19%
Non-fibrous (other)42%
SB10 DW 1-1
391308689-0027
Various None Detected Non-Fibrous Heterogeneous
Cellulose9% Glass8%
Non-fibrous (other)83%
SB10 DW 1-2
391308689-0028
Various None Detected Non-Fibrous Heterogeneous
Cellulose9% Glass8%
Non-fibrous (other)83%
SB10 DW 1-3-Joint Compound 391308689-0029
White None Detected Non-Fibrous
Homogeneous
Non-fibrous (other)100%
5Test Report PLM-7.28.9 Printed: 10/17/2013 3:12:04 PM
Jeff Siria, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request.