36C24718B0635 0010 2018-02-06 VA Birmingham Switchgear Structural Drawings.pdf
View the file
Other files for this federal contract opportunity
Show all 30
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Department of
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
FOR CONSTRUCTION
590 MEANS ST NW N/A
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
STRUCTURAL NOTES REPLACE/UPGRADE
ELECTRICAL SWITCHGEAR
PHASE 3
BIRMINGHAM, AL
S001
521-16-103
SLW SLM02-09-2018
UP
VTS
W
X
W8X10
W18X35
W8X10
W18X35
W16X31
W
X
W18X35
REF
30' - 0"
REF.
30' - 0"
4'
1"
2'
/4
2'
S501
S501
TYP
FACE OF BRICK FACADE
S501
W16X26
S501
S501
RAILING,
SEE 5/S501
TYP
S501
L3x3x1/4
HORIZONTAL
BRACING TYP
FACE OF BUILDING BELOW
FACE OF
BUILDING
BELOW
2'
3/ 4"
5'
NEW BACK UP GENERATOR
4'
W 8X
W 8X
W 8X
W
X
W8X10
W8X10
W
X
W8X10
W8X10 W8X10
W8X10
4' - 0"
4'
3' - 0"
FACE OF BUILDING BELOW
W8X10
W8X10
8'
17.9
L4x4x1/4 VERTICAL
KNEE BRACEING TYP.
S501
S501
S501
LADDER SEE ARCH DRAWINGS
S101
VENDOR DESIGNED EQUIPMENT SUPPORT
RAILS REFER TO ARCH AND MECHANICAL
DRAWINGS FOR LOCATION. SEE NOTE 6
SIM
PLAN
NORTH
TRUE
NORTH
PLATFORM FRAMING PLAN NOTES
1. T/GRATING = +4'-1" ABOVE EXISTING CONCRETE ROOF DECK.
2. REF. DENOTES FOR REFERENCE ONLY FIELD VERIFY
3. FIELD VERIFY EXISTING CONDITIONS PRIOR TO FABRICATION.
4. GRATING SHALL BE W19-4 (1" x 1/8") GALVANIZED STEEL GRATING U.N.O.
5. ANCHORAGE OF EQUIPMENT TO PLATFORM BY EQUIPMENT SUPPLIER
6. ANCHORAGE OF EQUIPMENT TO EQUIPMENT RAILS AND EQUIPMENT
RAILS TO EXISTING STRUCTURE BY VENDOR.
EXISTING ROOF FRAMING PLAN NOTES
1. REF. DENOTES FOR REFERENCE ONLY FIELD VERIFY
2. FIELD VERIFY EXISTING CONDITIONS PRIOR TO FABRICATION.
3. REFER TO 9/S501 FOR DETAILS AT ALL EXISTING FLOOR PENETRATIONS.
DENOTES GRATING SPAN DIRECTION
DENOTES EXTENTS OF GRATING
DENOTES VERTICAL BRACING
DENOTES HORIZONTAL BRACING
DENOTES EXISTING WIDE FLANGE BEAM
DENOTES NEW WIDE FLANGE BEAM
PLATFORM FRAMING PLAN LEGEND
WXxXX
WXxXX
KEY PLAN
PROJECT
AREA
VTS
REF
30' - 0"
REF.
30' - 0"
W18X46 W14X30
W
X
W
X
W14X30
W14X30
W16X26
W18X46
W18X46
W18X46 W14X30
W
X
W16X26
HSS4X4X1/2
HSS14X14X1/2 HSS14X14X1/2
W14X43
W14X43
W14X74 W14X48R
E F
4'
W
X
REF.
4' - 5 7/8"
EDGE OF ROOF DECK
NEW EXISTING BEAM
REINFORCING
S501
S501
S501
2'
2'
EXISTING 3" COMPOSITE DECK
WITH 3.25" CONCRETE FILL
S501
TYP
HSS4X4X1/2
HSS4X4X1/2
HSS4X4X1/2
17.9
S501
S501
2'
2'
NEW EXISTING
BEAM REINFORCING
S501
S501
R E
F
S101
LADDER SEE ARCH
DRAWINGS
EXISTING CONCRETE
COLUMN WRAP TYP
S502
S502
VENDOR DESIGNED LADDER. REFER
TO ARCH DRAWINGS FOR
ADDITIONAL DETAILS AND
REQUIREMENTS
HSS 3x2x1/4 LSH EA SIDE OF LADDER
L4x4x1/4 BETWEEN HSS TYP
VENDOR DESIGNED LADDER
ATTACHMENT (CLIP AND
CONNECTOR TO ANGLE) TYP W/
VERT LONG SLOTTED HOLES
EXISTING METAL STUD AND BRICK
EXTERIOR WALL TO REMAIN
DEMO EXISTING BRICK AS REQUIRED TO
INSTALL TUBE, REFER TO ARCH FOR REPAIR
AND CLOSURE REQUIREMENTS. COORDINATE
TUBE LOCATIONS WITH EXISTING BACK UP
METAL STUD WALL PRIOR TO FABRICATION.
HSS 3x2x1/4 LSH EA SIDE OF LADDER
HSS 3x2x1/4 LSH EA SIDE OF LADDER
EXISTING ROOF DECK (SECOND FLOOR)
EXISTING FIRST FLOOR
EXISTING GROUND FLOOR
EXISTING COLUMN
EXISTING
COLUMN
EXISTING BEAM
PLATFORM BEAM, SEE PLAN
T/PLATFORM
RAILING SEE PLAN
WT, SEE DETAILS
3/16
TYP
1/4" CAP PLATE TYP
EXISTING CONCRETE COLUMN
COVER
VENDOR DESIGNED
LADDER BASE
CONNECTION
3/16
TYP
3/16
TYP
VENDOR DESIGNED LADDER
CONNECTION TYP
TUBE-SEE SECTION TYP
PROVIDE 1/4" CAP
PLATE EACH END OF
TUBE TYP
SEE ARCH
A
A
SECTION A-A
1' - 9"
3/16
TYP
3/16
TYP
L4x4x1/4 BETWEEN
TUBES W/ VERT.
LONG SLOTTED
HOLETYP
1 1/2" MIN
EXISTING BRACING
EXISTING
CONCRETE
COLUMN
WRAP
1/8
TYP
1/4" CAP PLATE EACH
END OF TUBE TYP
3/4" BACKER ROD & SEALANT
ALL SIDES TYP.
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Department of
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
FOR CONSTRUCTION
590 MEANS ST NW N/A
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
ROOF AND PLATFORM FRAMING
PLANS
REPLACE/UPGRADE
ELECTRICAL SWITCHGEAR
PHASE 3
BIRMINGHAM, AL
S101
521-16-103
SLW SLM02-09-2018
1/4" = 1'-0"S101
2 GENERATOR PLATFORM FRAMING PLAN
1/4" = 1'-0"S101
1 ROOF FRAMING PLAN
1 1/2" = 1'-0"S101
3 SECTION AT LADDER
BEAM-SEE PLAN
STEEL COLUMN,
SEE PLAN
BEAM
WORK POINT
3/8" GUSSET PLATE TYP.
T/ STL
SEE PLAN
CL
WORK POINT
WORK POINT
2 1 /2"
3"
2"
1/2
3/4" Ø BOLTS
L4X4X1/4
3/16
TYP
1/4
+1-4" ABOVE EXISTING
ROOF SLAB
HORIZTONAL BRACE -
SEE PLAN
3/8" STIFFENER
PLATE EA. SIDE
3/16
1/4
TYP
1/4
TYP
2"
BEAM-SEE PLAN
STEEL COLUMN,
SEE PLAN
BEAM
WORK POINT
T/ STL
SEE PLAN
CL
WORK POINT
WORK POINT
3/8" PLATE
2 1 /2"
3"
2"
1/2
3/4" Ø BOLTS
L4X4X1/4
1/4
TYP
CL
1/8
1/4" PLATE
+1-4" ABOVE EXISTING
ROOF SLAB
HORIZTONAL BRACE -
SEE PLAN
2"
1/4
TYP
1/
2" 3"
3" 3"
1/
2"
1 1/2"
2 1/2"
1/4
TYP
(4) 3/4" DIA ASTM A325 BOLTS AT W16,
(5) 3/4" DIA ASTM A325 BOLTS AT W18
3/8" PLATE
3/16
TYP
3"
3"
STEEL COLUMN,
SEE PLAN
5/16
3/4" THICK BASE PLATE, U.N.O.
CL
CL
0'-10"
0' -1
0"
EXISTING BEAM,
SEE PLAN
STEEL BEAM,
SEE PLAN
DOUBLE ANGLES (5/16"
THICKNESS MIN.)
NOTE:
QTY OF FASTENERS TO BE
BASED ON THE BEAM SIZE.
C BEAML
BEAM SIZE
W8
W10
W12
W16
# OF 3/4" A325
BOLTS
W14
3" MAX.
3" S
P A
C E
S
3" M
A X
W18 5
4'-0" MAX. E
Q
E Q
3' -6
T
Y P
1 1/2" XS
PIPE-TYP.
BEAM, SEE PLAN
TOE PLATEGRATING - SEE PLAN
WT3x4.5xWEB HEIGHT AT W18x35 WT2.5x9.5xWEB HEIGHT AT W16x31
S501
1/4" CLOSURE PLATE
1/4"x4"XCONT.
TOE PLATE
(1/8")
1/ 4"
BEAM SEE PLAN
WT3x4.5xWEB HEIGHT AT W18x35 WT2.5x9.5xWEB HEIGHT AT W16x31
CHAMFER AS REQUIRED
CHAMFER AS REQUIRED
GUARDRAIL
1/8
3/16
1/2"
T/ ROOFING
T/ CONCRETE FILL ON METAL DECK
3" DIAMETER STD PIPE POST AT EACH
STRINGER WITH 1/2"x0'-5"x0'-5" PLATE
TOP AND BOTTOM. ANCHOR TO SLAB
WITH (2) 1/2"x2 3/4" EMBED
EXPANSION ANCHORS
4'
3'
3'
E Q
E Q
M A
X
7"
F
IE
LD
V
E R
IF
Y
1 1/2" XS PIPE TYP
1 1/2" XS PIPE TYP
S P
A C
IN
G
4" T
O 7"
E Q
MIN
11"
M
IN
1'
SEE TYPICAL WIDE
FLANGE CONNECTION
DETAILS
BEAM, SEE
PLAN
C12X20.7
CHANNEL
STRINGER TYP
L2x2x3/8
TYP
GRATING SEE
PLAN. NOTCH
AROUND RAIL
POST AS REQD
3/16
TYP
1"
GRATING
SEE PLAN
3/16
TYP
3/16
3/16
EXISTING BEAM ,
SEE PLAN
CONTINUOUS
WT8x33.5x CONT
1/4 2@12
+4" EA END, STAGGER WELD
DEMO TOP OF EXISTING WALL STUD AS
REQUIRED TO INSTALL NEW REINFORCING.
INSTALL NEW DEFLECTION TRACK TO
MATCH SIZE AND THICKNESS OF EXISTING
STUDS AND ATTACH TO STEEL WITH (2)
.145"Ø PDF @ STUD SPACING. PROVIDE A
MIN OF 1" GAP BETWEEN TOP OF STUD
AND DEFLECTION TRACK.
1"
1-1/2"x33 GAUGE STRAP
EACH SIDE WITHIN 6" OF
TOP OF STUD
POST SEE PLAN
EXISTING ROOF DECK, SEE PLAN. DEMO
ONLY AS REQUIRED TO INSTALL NEW POST
AND BASE PLATE. INFILL DEMOLISHED
CONCRETE DECK WITH NON-SHRINK
GROUT
EXISTING BEAM, SEE PLAN. DEMO
(1) HEADED STUD MAX TO INSTALL
NEW BASE PLATE
BEAM REINFORCING SEE
PLAN AND TYPICAL DETAIL
7/S501
BASE PLATE, SEE
TYPICAL BASE PLATE
DETAIL 3/S501
1/4
TYP
DEMO TOP OF EXISTING WALL STUD AS
REQUIRED TO INSTALL NEW REINFORCING.
INSTALL NEW DEFLECTION TRACK TO
MATCH SIZE AND THICKNESS OF EXISTING
STUDS AND ATTACH TO STEEL WITH (2)
.145"Ø PDF @ STUD SPACING. PROVIDE A
MIN OF 1" GAP BETWEEN TOP OF STUD AND
DEFLECTION TRACK.
3/8" STIFFNER PLATE EA SIDE
3/16
TYP
NOTE: SEE ARCH DRAWINGS
FOR FLASHING
REQUIREMENTS
1-1/2"x33 GAUGE STRAP
EACH SIDE WITHIN 6" OF
TOP OF STUD
POST SEE PLAN
EXISTING DECK, SEE PLAN.
DEMO ONLY AS REQUIRED
TO INSTALL NEW POST AND
BASE PLATE. INFILL
EXISTING CONCRETE DECK
WITH NON-SHRINK GROUT.
EXISTING BEAM, SEE PLAN.
DEMO (1) HEADED STUD
MAX TO INSTALL NEW BASE
PLATE
BASE PLATE, SEE
TYPICAL BASE PLATE
DETAIL 3/S501
1/4
TYP
EXIST. COLUMN,
SEE PLAN
NOTE: SEE ARCH DRAWINGS
FOR FLASHING
REQUIREMENTS
EXIST. BEAM
SEE PLAN
BEAM-SEE PLAN
STEEL COLUMN,
SEE PLAN
BEAM
WORK POINT
T/ STL
SEE PLAN
CL
WORK POINT
WORK POINT
3/8" PLATE
2 1 /2"
3"
2"
1/2
(2) 3/4" DIA ASTM A325
BOLTS TYP
L 4X4X1/4
1/4
TYP
CL
1/4
1/4" PLATE
+1-4" ABOVE EXISTING
ROOF SLAB
HORIZTONAL
BRACE -SEE
PLAN
1/4
TYP
(4) 3/4" DIA ASTM A325 BOLTS
2L4x4x1/4x1'-0" LONG
3/16
TYP
2"
1/
2"
3" 3"
3"
1/
2"
1 1/2"
2 1/2"
3/8" STIFFNER
PLATE
3/16
+1/2" RTN
TOP AND
BOTT
3/16
TYP
NOTE: PROVIDE 2L4x4x1/4x1'-3" LONG
CONNECTION WITH (5) 3/4" DIA ASTM
A325 BOLTS AT SIM CONDITION
POST SEE PLAN
EXISTING ROOF DECK, SEE PLAN. DEMO
ONLY AS REQUIRED TO INSTALL NEW
POST AND BASE PLATE. INFILL
DEMOLISHED CONCRETE DECK WITH
NON-SHRINK GROUT
EXISTING BEAM, SEE PLAN.
DEMO (1) HEADED STUD
MAX TO INSTALL NEW BASE
PLATE
BEAM REINFORCING SEE
PLAN AND DETAIL 13/S501
3/4"x6"x0'-6"BASE PLATE
1/4
TYP
EXISTING WALL STUDS TO
REMAIN
3/8" STIFFNER PLATE ONE SIDE
3/16
TYP
EXISTING BENT PLATE WITH HEADED STUD. DEMO
HORIZONTAL LEG OF BENT PLATE ONLY AT POST
BASE PLATE. LOCATE EXISTING HEADED STUD
PRIOR TO BASE PLATE AND POST FABRICATION. DO
NOT DAMAGE HEADED STUD DURING POST
INSTALLATION.
NOTE: SEE ARCH DRAWINGS
FOR FLASHING
REQUIREMENTS
5/16
T Y
P
2" M
IN
2' - 0"
CONDUIT REFER TO
ELECTRICAL DRAWINGS.
3 1/2" MAX O.D.
1'
1'
/2
A A
SECTION A-A
EXISTING COMPOSITE
FLOOR DECK
CONDUIT REFER TO
ELECTRICAL DRAWINGS.
3 1/2" MAX O.D.
EXISTING COMPOSITE
FLOOR DECK
NOTES
1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO FLOOR PENETRATION INSTALLATION.
2. DO NOT CUT VERTICAL OR BOTTOM HORIZONTAL DECK FLUTES DURING FLOOR PENETRATION INSTALLATION.
3. DO NOT DAMAGE EXISTING FLOOR BEAMS DURING FLOOR PENETRATION INSTALLATION.
4. REFER TO ARCHITECTURAL DRAWINGS FOR FIRE STOPPPING DETAILS AT PENETRATIONS.
5. REFER TO A104 AND A105 FOR LOCATION OF PENETRATIONS AT FIRST AND SECOND FLOOR
EXISTING ROOF DECK
CONTINUOUS HSS9x5x1/4
LSV BEAM REINFORCING.
SEE PLAN FOR LOCATION
EXISTING WALL STUDS TO
REMAIN
(3/16) 2@12
+ 4" EA
END,
STAGGER
WELD
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Department of
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
FOR CONSTRUCTION
590 MEANS ST NW N/A
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
STEEL DETAILS REPLACE/UPGRADE
ELECTRICAL SWITCHGEAR
PHASE 3
BIRMINGHAM, AL
S501
521-16-103
SLW SLM02-09-2018
1 1/2" = 1'-0"S501
SINGLE BRACE CONNECTION DETAIL TO
COLUMN - BEAM OVER COLUMN
1 1/2" = 1'-0"S501
2 SINGLE BRACE CONNECTION DETAIL TO COLUMN
1 1/2" = 1'-0"S501
3 TYPICAL BASE PLATE DETAIL
3/4" = 1'-0"S501
4 TYPICAL BEAM TO BEAM CONNECTION
3/4" = 1'-0"S501
5 TYPICAL RAILING DETAIL
3/4" = 1'-0"S501
6 TYPICAL RAILING CONNECTION DETAIL
3/4" = 1'-0"S501
10 TYPICAL STAIR SECTION
1 1/2" = 1'-0"S501
TYPICAL BEAM REINFORCING DETAIL
ALONG GRID LINE T
3/4" = 1'-0"S501
8 SECTION AT NEW POST TO EXISTING BEAM
3/4" = 1'-0"S501
12 NEW POST TO EXISTING COLUMN DETAIL
1 1/2" = 1'-0"S501
11 SINGLE BRACE CONNECTION DETAIL TO BEAM
3/4" = 1'-0"S501
SECTION AT NEW POST TO
EXISTING SPANDREL BEAM
1" = 1'-0"S501
9 TYPICAL FLOOR PENETRATION DETAILS
3/4" = 1'-0"S501
TYPICAL BEAM REINFORCING
ALONG GRID LINE V
3/16
SEE NOTE 1
S E
E N
O T
E
1'
6" M
IN
5/16
1/2" RTN T&B. SEE NOTE 2
EXISTING BEAM
SEE PLAN
EXISTING TUBE
COLUMN SEE
PLAN
NOTES:
1. CONNECTION INFORMATION SHOWN ARE ASSUMED EXISTING CONDITIONS TO BE FIELD VERIFIED
BY THE CONTRACTOR PRIOR TO SUBMITTAL OF SHOP DRAWINGS FOR REVIEW. THE CONTRACTOR
SHALL FIELD VERIFY THE EXISTING WELD (THICKNESS, TYPE AND LENGTH), NUMBER AND SIZE OF
BOLTS AND LENGTH AND THICKNESS OF CONNECTION PLATE AND PROVIDE DETAILED AND
DIMENSIONED SKETCHES AND PHOTOGRAPHS FOR REVIEW AS PART OF THE FIELD VERIFICATION.
2. IF ALL MINIMUM REQUIREMENTS ARE MET, PROVIDE THE FILLET WELD SHOWN TO EXISTING
CONNECTION PLATE AND BEAM.
3. IF ALL MINIMUM REQUIREMENTS ARE NOT MET, THE STRUCTURAL ENGINEER WILL FURTHER
EVALUATE THE CONNECTION AND PROVIDE ADDTIONAL DETAILS DURING THE SHOP DRAWING
REVIEW PROCESS.
EXISTING 3/8"
CONNECTION
PLATE. SEE NOTE 1
(6) 3/4" DIA ASTM A325
EXISTING BOLTS. SEE
NOTE 1
3/16
SEE NOTE 1
S E
E N
O T
E
1'
6" M
IN
5/16
1/2" RTN T&B. SEE NOTE 2
EXISTING BEAM
SEE PLAN
EXISTING WF
COLUMN SEE
PLAN
NOTES:
1. CONNECTION INFORMATION SHOWN ARE ASSUMED EXISTING CONDITIONS TO BE FIELD VERIFIED
BY THE CONTRACTOR PRIOR TO SUBMITTAL OF SHOP DRAWINGS FOR REVIEW. THE CONTRACTOR
SHALL FIELD VERIFY THE EXISTING WELD (THICKNESS, TYPE AND LENGTH), NUMBER AND SIZE OF
BOLTS AND LENGTH AND THICKNESS OF CONNECTION PLATE AND PROVIDE DETAILED AND
DIMENSIONED SKETCHES AND PHOTOGRAPHS FOR REVIEW AS PART OF THE FIELD VERIFICATION.
2. IF ALL MINIMUM REQUIREMENTS ARE MET, PROVIDE THE FILLET WELD SHOWN TO EXISTING
CONNECTION PLATE AND BEAM.
3. IF ALL MINIMUM REQUIREMENTS ARE NOT MET, THE STRUCTURAL ENGINEER WILL FURTHER
EVALUATE THE CONNECTION AND PROVIDE ADDTIONAL DETAILS DURING THE SHOP DRAWING
REVIEW PROCESS.
EXISTING 3/8"
CONNECTION
PLATE. SEE NOTE 1
(6) 3/4" DIA ASTM A325
EXISTING BOLTS. SEE
NOTE 1
EXISTING
SLAB ON
GRADE.
#4@12" O.C.
EACH WAY AT MID- DEPTH
CLEAN & ROUGHEN EXISTING SURFACE
APPLY EPOXY BONDING AGENT PRIOR
TO PLACEMENT OF FRESH CONCRETE IN
ACCORDANCE WITH MANUFACTURERS
RECOMMEMNDATIONS.
3/4" CHAMFER TYP.
SEE NOTE BELOW
F A
C E
O F
E Q
U
IP
M E
N T
F A
C E
O F
E Q
U
IP
M E
N T
4" T
Y P
6"
NOTES:
1. REFER TO SHEET E202 FOR EQUIPMENT PLAN LOCATION AND SIZE.
2. CONCRETE CONFIGURATION, LOCATION, AND SIZE OF ANCHOR BOLTS
SHALL CONFORM TO EQUIPMENT MFRS. REQUIREMENTS. VERIFY
LOCATIONS WITH MECHANICAL.
2" C
LR
M
IN
3,000 PSI NORMAL WEIGHT CONCRETE
T/ SLAB
EXISTING SLAB.
#4@12" O.C.
EACH WAY
3/4" CHAMFER TYP.
F A
C E
O F
E Q
U
IP
M E
N T
4" M
IN
M
A T
C H
E X
IS
T
IN
G 4"
2" C
LR
M
IN
. CLEAN AND ROUGHEN
EXISTING SLAB SURFACE
AND APPLY EPOXY
BONDING AGENT PRIOR TO
PLACING NEW CONCRETE
NEW 3,000 PSI NORMAL
WEIGHT CONCRETE FOR PAD
EXTENSION
EXISTING
CONCRETE PAD
DRILL HOLE INTO EXISTING SLAB 10 BAR
DIAM'S DEEP BY ONE BAR DIAM+1/4" MAX.
IN DIAMETER AND EPOXY DOWEL INTO
SLAB IN ACCORDANCE WITH
MANUFACTURERS RECOMMENDATIONS.
AS REQUIRED
NOTES:
1. REFER TO SHEET E203 FOR EQUIPMENT PLAN LOCATION.
2. CONCRETE CONFIGURATION, LOCATION, AND SIZE OF ANCHOR BOLTS
SHALL CONFORM TO EQUIPMENT MFRS. REQUIREMENTS. VERIFY
LOCATIONS WITH MECHANICAL.
T/ SLAB
EXISTING SLAB.
#4@12" O.C.
EACH WAY
3/4" CHAMFER TYP.
F A
C E
O F
E Q
U
IP
M E
N T
4" M
IN
M
A T
C H
E X
IS
T
IN
G 4"
1/2" PJF WITH SEALANT AT
NEW PAD TO EXISTING
ISOLATION PAD
NEW 3,000 PSI NORMAL
WEIGHT CONCRETE FOR PAD
EXTENSION
EXISTING
CONCRETE
ISOLATION PAD
AS REQUIRED
NOTES:
1. REFER TO SHEET E211 FOR EQUIPMENT PLAN LOCATION.
2. CONCRETE CONFIGURATION, LOCATION, AND SIZE OF ANCHOR BOLTS
SHALL CONFORM TO EQUIPMENT MFRS. REQUIREMENTS. VERIFY
LOCATIONS WITH MECHANICAL.
CLEAN & ROUGHEN EXISTING SURFACE
APPLY EPOXY BONDING AGENT PRIOR
TO PLACEMENT OF FRESH CONCRETE IN
ACCORDANCE WITH MANUFACTURERS
RECOMMEMNDATIONS.
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Department of
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
FOR CONSTRUCTION
590 MEANS ST NW N/A
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
STEEL DETAILS REPLACE/UPGRADE
ELECTRICAL SWITCHGEAR
PHASE 3
BIRMINGHAM, AL
S502
521-16-103
SLW SLM02-09-2018
1" = 1'-0"S502
1 EXISTING CONNECTION DETAIL (TUBE COLUMN)
1" = 1'-0"S502
2 EXISTING CONNECTION DETAIL (WF COLUMN)
1 1/2" = 1'-0"S502
3 EQUIPMENT PAD DETAIL
1" = 1'-0"S502
4 SECTION AT EQUIPMENT PAD EXTENSION
1" = 1'-0"S502
EQUIPMENT PAD EXTENSION AT
EXISTING ISOLATION PAD