ICRA Alternative to Outdoor Air Discharge - ICRA.pdf
PDF 10 KB Posted
- Attached to
- Y1DA--Renovate Radiology Floors |658-25-103
- Solicitation number
- 36C24625B0021
About this file
This document is an Appendix A for the VHA ICRA-1.3 (December 2024) template, providing alternative requirements for interior construction space exhaust in healthcare facilities. The appendix outlines a detailed procedure for indoor exhaust when external exhaust is not possible, requiring HEPA filtration, continuous particulate monitoring, and strict control measures. Key requirements include taking baseline air sampling measurements, verifying HEPA filtration through particle counting (down to 0.3 microns), conducting verification checks three times daily, and installing monitoring devices to ensure negative pressurization. The exhaust must be directed to low-risk areas, avoiding shared HVAC systems, high-traffic zones, and areas that could create noise or airflow nuisances. Any particulate count exceedance mandates an immediate work stoppage and resolution, with all measurements requiring documentation and retrieval.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S07 SF 1409_Abstract of Offers.pdf | ||
| Amendment 0007.pdf | ||
| S07 SF 1409_Abstract of Offers (004).pdf | ||
| S07 Bid ABSTRACT.pdf | ||
| 36C24625B0021 0006.docx | DOCX document | |
| 36C24625B0021 0005.docx | DOCX document | |
| 36C24625B0021 0003.pdf | ||
| 36C24625B0021 0004.pdf | ||
| Added Spec 093013 Ceramic and Porcelain Tile 658-25-103.pdf | ||
| Questions with responses 36C24625B0021 Radiology Floors.docx | DOCX document | |
| ICRA Level IV Requirements.pdf | ||
| Balco 2HEXBF-1-2-MBF Expansion Joint.pdf | ||
| Asbestos report.pdf | ||
| 36C24625B0021 0002.pdf | ||
| 36C24625B0021 0002.docx | DOCX document | |
| 36C24625B0021 0001.docx | DOCX document | |
| S04 Renovate Radiology Flooring.pdf | ||
| 36C24625B0021_1.docx | DOCX document | |
| Specification- Final.pdf | ||
| Drawings-Final.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VHA ICRA-1.3 (December 2024)
Appendix A: Alternative To Outdoor Exhaust Requirements
This Appendix provides an equivalent ICRA control measure to requirements detailed in this VHA ICRA template (Table 5 Level III, item 5) that would allow interior construction space exhaust.
Interior Construction Space Exhaust:
If the facility is not able to exhaust to the building exterior, the Healthcare Environment and Facilities program office has identified an alternate industry-recognized standard interior exhaust procedure that is accepted as providing an equivalent level of infection prevention and control (IPC), and safety. The alternate interior exhaust procedure is implemented by completing the following:
a. If exhaust is directed indoors, then the system must be HEPA filtered. Prior to start of work, including assembly of the ICRA barriers, initial baseline air sampling measurements for particulate levels must be taken in the planned area of discharge. Once containment is erected and completed, HEPA filtration must then be verified by particulate measurement, using a particle counter with multi-channel capabilities to measure down to 0.3 microns, to confirm that the discharge of the HEPA unit does not exceed the baseline particulate count of the area to which the exhaust is directed. Verification must continue at least three times per day (once every 8 hours), 7 days per week, during the use of the negative air machine and HEPA filter.
Any exceedance must trigger a work stoppage and an immediate response and resolution. All particulate measurements, including the baseline measurement, must be documented and retrievable.
b. To accommodate the sampling, the negative air pressure machine must be fitted with a 2 ft section of rigid ductwork at the discharge. The sample port for monitoring must be in the rigid ductwork section.
c. Vapor generating processes must be assessed and appropriate filtration must be installed to mitigate transmission to the facility.
d. Engineering must do a complete flow and pressure analysis and document the area to which the air is being discharged to ensure the flow and pressure relationships in that area are not being adversely impacted by the additional flow. Ideally, this is done as part of the construction package to ensure the design is implementable and no additional HVAC changes are required to accommodate the exhaust from the negative air equipment.
e. Install device on exterior of work containment to continually monitor negative pressurization. To ensure proper pressure is continuously maintained, the device(s) shall have a visual pressure indicator, data collection and alarm.
f. Exhaust must be directed to Low Risk areas as defined in Table 3 in this VHA ICRA template.
Ideally this discharge must be located so as not to impinge on high traffic areas or create a nuisance with noise or excessive airflow.
NOTE: Exhaust into shared or recirculating HVAC systems, or other shared exhaust systems (e.g., bathroom exhaust) is not acceptable.