RFI 19 -20 MH Sheets.pdf
PDF 3 MB Posted
- Attached to
- Z2DZ--Renovate And Replace Pharmacy AHUs Federal contract opportunity
- Solicitation number
- 36C24620R0152
About this file
This document package includes mechanical drawings and specifications for a federal contract opportunity to renovate and replace pharmacy air handling units at a Department of Veterans Affairs medical center. The scope of work involves demolishing existing AHUs in buildings F1204 and N1004, installing new AHUs on the roof, and upgrading related ductwork, piping, controls, and HVAC equipment. The drawings depict proposed mechanical plans by floor and provide notes on specifications, materials, clearances, and coordination requirements. The federal opportunity is solicited under solicitation number 36C24620R0152 to renovate pharmacy spaces and replace aged HVAC infrastructure to meet current standards.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24620R0152 0002.docx | DOCX document | |
| RFI 10 A101A and A600.pdf | ||
| Interstitial 2nd Floor.pdf | ||
| A102.pdf | ||
| RFI 001 Response Review VA Comments.pdf | ||
| RFI 25 Attachment 2.pdf | ||
| RFI 16 -17 - 18- M-001.pdf | ||
| RFI 12 A600.pdf | ||
| RFI 11-13 -A121A -A121B.pdf | ||
| RFI 05 A122.pdf | ||
| RFI 22 A051.pdf | ||
| RFI 15 M-701.pdf | ||
| 36C24620R0152 0001.docx | DOCX document | |
| 36C24620R0152_3.docx | DOCX document | |
| Past Performance Questionnaire.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OFFICE
F1217C
SHARED
OFFICE
F1217B
HAZARDOUS
COMPOUNDING
F1204L
HAZARDOUS
STORAGE
F1204J
ANTE
ROOM
F1204K
NON
HAZARDOUS
COMPOUNDING
F1204M
STERILE
STORAGE
F1204N
PHARMACY
F1204
OMNICELL/795
AREA
F1204D
PHARMACY
F1204
RELOCATED
VAV-30-2-16
B-325 B-325
D-225 ø
12x12
10ø 10ø
10x10
MH201
ETR
F1204 30-2-14
18x1215x1212x10
ETR
VAV-30-2-12
ETR
VAV-30-2-10
12x10
/2 x
18x12
32x20
/1 x
30x16
16x14
24x10
/2 x
18x12
D-N/A D-N/A ø
12ø ø ø x x ø
ETR
325 CFM
ETR
325 CFM
ETR
325 CFM
ETR
325 CFM
/1
33/16
/1
PHARMACY
F1204
CONTROLLED
SUBSTANCES
VAULT
00000
INVESTIGATIONAL
PHARMACIST
F1204
STORAGE
F1204F
V ADD
F1204A
HSK
F1204B
TOILET
F1204C
CHIEF
F1215
16 16
17 17
B-300
10ø
12x8
VAV-30-2-11
10ø 6ø
H W
S
H W
R
H W
S
H W
R
H W
S
H W
R
2 1/2" HWS
1 1/2" HWR
/4
H
W R
/4
H
W S
/4
H
W S
/4
H
W R ø ø 21
AHU-F1204-01
C W
R
C W
S
E F -F
-0 x
70x30
8ø
/2 x x
34x20 x
34x20
4" CWR
4" CWS
6" CWR
ETR
RELIEF
AIR
FAN
36/18
44x30
2" MPS 2 1/2" MPS 3" MPS
2" MPR2" MPR
C W
S
C W
R
2" MPS
/2
M P R
1 1/2" MPR
2" MPS
ø x
24x16
ETR
EXHAUST
LOUVER
x x
2" MPS2" MPS
/2
M P R
M P S
CD
18ø x
12 12
15 15
INTERSTITIAL
MECHANICAL
SPACE
F2121
INTERSTITIAL
MECHANICAL
SPACE
F2121
/4
M
P S
/4
M
P R
SMOKE TIGHT PARTITION
RATED WALL LEGEND
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management
102 THIRD AVENUE NORTHEAST
HICKORY, NORTH CAROLINA 28601
PHONE: 828.315.9962
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
CHARLOTTE | 704.295.4263
705 EAST MOREHEAD STREET, 28202
NC License No: C-2848
AME Project No: 18104
VA FORM 08-6231
F
E
D
C
B
A
PLAN NORTH TRUE NORTH
558-17-233
Durham VAMC Durham NC
REPLACE PHARMACY AHUS
RENOVATE F1204 & N1004
COMPOUNDING PHARMACIES
- MH101
WEBFFR
MECHANICAL - NEW WORK PLAN - LEVEL 01 &
LEVEL 02 - F1204
FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY
1/4" = 1'-0"
MECHANICAL - NEW WORK PLAN - LEVEL 01 - F1204
1/4" = 1'-0"
MECHANICAL - NEW WORK PLAN - LEVEL 02 - F1204
KEY NOTESX
1 RELOCATED ZONE TEMPERATURE SENSOR "30-2-16" SERVING RELOCATED VAV-30-2-16.
2 RELOCATED VAV-30-2-16. TIE NEW HWS & HWR PIPING INTO EXISTING AND ROUTE TO
RELOCATED VAV-30-2-16. CONTRACTOR SHALL VERIFY AND MATCH PRIOR RUNOUT
SIZES, MATCH EXISTING INSULATION TYPE, AND REUSE EXISTING CONTROL VALVE
ASSEMBLY.
3 ROUTE NEW 12" ROUND MEDIUM PRESSURE SA DUCT TO RELOCATED VAV-30-2-16.
FIELD VERIFY ROUTING WITH EXISTING CONDITIONS.
4 REBALANCE RELOCATED VAV-30-2-16 FOR 650 CFM (PRIMARY MAX) AND 200 CFM
(PRIMARY MIN.).
5 REBALANCE ETR VAV-30-2-10 FOR 1,275 CFM (PRIMARY MAX) AND 400 CFM (PRIMARY
MIN. AND HEATING).
6 THIS ROOM WILL BE RENOVATED AT A FUTURE TIME.
7 INSTALL NEW AHU-F-1204 ON 4" THICK CONCRETE PAD - REFER TO STRUCTURAL
DRAWINGS.
8 ROUTE 30"x18" SA DUCT DOWN THRU INTERSTITIAL FLOOR.
9 ROUTE 18"x18" RA DUCT DOWN THRU INTERSTITIAL FLOOR.
10 ROUTE 24"x16" OA DUCT TO EXISTING OUTDOOR AIR INTAKE PLENUM.
11 TIE NEW 3" CWS & CWR PIPING INTO EXISTING 4" CWS & CWR MAINS. DO NOT TIE
NEW PIPES INTO EXISTING PIPES THAT ARE SMALLER IN SIZE, CLOSER, MORE
CONVENIENT, ETC. FIELD VERIFY AND COORDINATE EXACT TIE-IN LOCATIONS WITH
EXISTING CONDITIONS. MATCH EXISTING PIPE MATERIALS AND INSULATION SYSTEMS.
PROVIDE NEW ISOLATION VALVES. ROUTE NEW 3" CWS & CWR PIPING TO NEW
AHU-F1204-01. FIELD VERIFY ROUTING WITH EXISTING CONDITIONS.
12 TIE NEW 2" MPS & 1-1/2" MPR PIPING INTO EXISTING 3" MPS & 2" MPR MAINS. DO NOT
TIE NEW PIPES INTO EXISTING PIPES THAT ARE SMALLER IN SIZE, CLOSER, MORE
CONVENIENT, ETC. FIELD VERIFY AND COORDINATE EXACT TIE-IN LOCATIONS WITH
EXISTING CONDITIONS. MATCH EXISTING PIPE MATERIALS AND INSULATION SYSTEMS.
PROVIDE NEW ISOLATION VALVES. ROUTE NEW 2" MPS & 1" MPR PIPING TO NEW
AHU-F1204-01. FIELD VERIFY ROUTING WITH EXISTING CONDITIONS.
13 ROUTE 18" ROUND EA DUCT UP INTO CHASE ON LEVEL 03 ABOVE.
14 ROUTE 12"x12" EA DUCT TO EXISTING EXHAUST/RELIEF AIR LOUVER.
15 TEMPORARILY REMOVE EXISTING EXHAUST/RELIEF AIR LOUVER FOR INSTALLATION OF
AHU-F1204-01.
16 FIRE DAMPER NOT REQUIRED FOR DUCT PENETRATION OF 1-HOUR FIRE BARRIER PER
2018 IMC 607.5.2 EXCEPTION 3.
17 RE-ROUTE EXISTING SUPPLY DUCT AS REQUIRED TO ACCOMMODATE NEW SMOKE TIGHT
PARTITION.
18 ALL EXHAUST DUCTWORK ASSOCIATED WITH BIOLOGICAL SAFETY CABINETS SHALL BE
WELDED 316-L STAINLESS STEEL ROUND DUCT PER VA STANDARDS. SUBSTITUTION
REQUESTS FOR ANY OTHER MATERIAL OR SEALING METHOD WILL NOT BE ACCEPTED.
19 PROVIDE TRAP AND ROUTE CONDENSATE DRAIN PIPING (BY GRAVITY) TO NEAREST
FLOOR DRAIN OR DOWN THRU FLOOR TO EXISTING MOP SINK IN F1204B HSK - REFER
TO DETAIL SHEETS AND INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
CONTRACTOR SHALL FIELD VERIFY TO DETERMINE ROUTING AND DRAIN DISCHARGE
LOCATION BASED ON EXISTING CONDITIONS. CONDENSATE DRAIN PIPE SHALL MATCH
CONNECTION SIZE ON AHU-F1204-01.
20 ROUTE 3" CWS, 3" CWR, 2" MPS, & 1-1/2" MPR PIPING TO CHILLED WATER COOLING
COIL, STEAM PRE-HEAT COIL, STEAM RE-HEAT COIL, AND HUMIDIFIER ON NEW AHU.
MATCH CONNECTION SIZES ON AHU.
21 TIE NEW 3/4" HWS & HWR INTO EXISTING HWS & HWR MAINS AND ROUTE TO NEW
VAV-30-2-11. MATCH EXISTING PIPE MATERIALS AND INSULATION TYPE.
22 RELOCATED ZONE TEMPERATURE SENSOR "30-2-10" SERVING ETR VAV-30-2-10.
GENERAL NOTES
1. REFER TO OVERALL PLAN OF CAMPUS FOR AREAS OF WORK ON A011.
2. REFER TO PHASING & PRE-CONSTRUCTION NOTES ON M-001.
3. EXISTING CONDITIONS, EQUIPMENT, MATERIALS, LOCATIONS, AND SIZES ARE SHOWN
FOR REFERENCE ONLY. THE CONTRACTOR IS RESPONSIBLE TO VERIFY ALL EXISTING
CONDITIONS/SIZES AND NOTIFY ENGINEER OF ANY DISCREPANCIES IN WRITING
PRIOR TO STARTING WORK.
4. CAP AND REPAIR EXISTING DUCT & PIPE OPENINGS FROM DEMOLITION NOT USED.
SEAL AIR/WATER TIGHT AND PATCH INSULATION.
5. PIPING IS SHOWN SPACED APART FOR CLARITY PURPOSES ONLY.
6. INSTALL 90° RADIUS ELBOWS WHERE SHOWN. INSTALL TURNING VANES ON ALL 90°
MITERED ELBOWS.
7. DUCTWORK SHOWN IS SIZED AND ROUTED TO MAINTAIN ARCHITECT'S DESIRED
CEILING HEIGHTS. THE CONTRACTOR IS RESPONSIBLE TO NOTIFY ENGINEER OF ANY
DISCREPANCIES WHERE ARCHITECT'S DESIRED CEILING HEIGHTS CANNOT BE
OBTAINED PRIOR TO DUCT FABRICATION/INSTALLATION.
8. CLEAN EXISTING DUCTWORK & INSULATION WITHIN THE SCOPE OF PROJECT TO LIKE-
NEW CONDITION.
9. NOT USED.
10. COORDINATE ZONE TEMPERATURE SENSOR & HUMIDITY SENSOR LOCATIONS WITH
THE CONTRACTOR AND EQUIPMENT PLANS.
11. MAINTAIN MANUFACTURER'S RECOMMENDED SERVICE CLEARANCES ON ALL
MECHANICAL EQUIPMENT. ALL EQUIPMENT MUST BE ACCESSIBLE FOR MAINTENANCE.
12. INSTALL AIR CONTROL VALVES WITH CONTROLS ENCLOSURE FACING DOWN TOWARDS
FLOOR FOR ACCESSIBILITY.
AHU-F1204-01 INSTALLATION NOTES
1. THE INTERSTITIAL FLOOR OF LEVEL 02 HAS VARIOUS STRUCTURAL SUPPORT
LIMITATIONS (LBS/SF) THROUGHOUT THE FLOOR. NEW AHU-F1204-01 SHOWN ON
THESE DRAWINGS IS LOCATED IN AN AREA WITH HIGHER SUPPORT CAPACITY.
2. THE VA HAD CONCERNS ON USING THE FREIGHT ELEVATOR FOR THE INSTALLATION OF
NEW AHU-F1204-01 AND CROSSING PORTIONS OF THE INTERSTITIAL FLOOR WITH
LOWER STRUCTURAL SUPPORT CAPACITIES. THE VA PREFERS NEW AHU-F1204-01 BE
BROUGHT IN THROUGH AN EXISTING 17'-4" (W) x 5'-0" (H) LOUVER ON THE FRONT OF
THE BUILDING FACING ERWIN ROAD.
3. NEW AHU-F1204-01 HAS BEEN SPECIFIED WITH FULL KNOCKDOWN CONSTRUCTION TO
ALLOW THE UNIT TO BE DISASSEMBLED/REASSEMBLED IN THE FIELD AND BROUGHT
INTO THE INTERSTITIAL SPACE ON LEVEL 02 THROUGH THE EXISTING LOUVER OPENING.
4. THE CONTRACTOR SHALL TEMPORARILY REMOVE THE EXISTING LOUVER AND REINSTALL
AFTER ALL COMPONENTS OF NEW AHU-F1204-01 ARE INSIDE THE BUILDING.
5. SEE GOOGLE EARTH SCREEN SHOT BELOW FOR EXISTING LOUVER LOCATION AND
GENERAL CONCEPT.
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
1 Addendum 1 11/12/2020
1 2EF-F1204-01
ETR
EF-11
ETR
EF-9
ETR
EF-22
ETR
EF-F-TB
SMOKE TIGHT PARTITION
RATED WALL LEGEND
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management
102 THIRD AVENUE NORTHEAST
HICKORY, NORTH CAROLINA 28601
PHONE: 828.315.9962
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
CHARLOTTE | 704.295.4263
705 EAST MOREHEAD STREET, 28202
NC License No: C-2848
AME Project No: 18104
VA FORM 08-6231
F
E
D
C
B
A
PLAN NORTH TRUE NORTH
558-17-233
Durham VAMC Durham NC
REPLACE PHARMACY AHUS
RENOVATE F1204 & N1004
COMPOUNDING PHARMACIES
- MH102
WEBFFR
MECHANICAL - NEW WORK PLAN - LEVEL 03 &
ROOF - F1204
FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY
1/8" = 1'-0"
MECHANICAL - NEW WORK PLAN - LEVEL 03 - F1204
1/8" = 1'-0"
MECHANICAL - NEW WORK PLAN - ROOF - F1204
GENERAL NOTES
1. REFER TO OVERALL PLAN OF CAMPUS FOR AREAS OF WORK ON A011.
2. REFER TO PHASING & PRE-CONSTRUCTION NOTES ON M-001.
3. EXISTING CONDITIONS, EQUIPMENT, MATERIALS, LOCATIONS, AND SIZES ARE
SHOWN FOR REFERENCE ONLY. THE CONTRACTOR IS RESPONSIBLE TO VERIFY
ALL EXISTING CONDITIONS/SIZES AND NOTIFY ENGINEER OF ANY
DISCREPANCIES IN WRITING PRIOR TO STARTING WORK.
4. CAP AND REPAIR EXISTING DUCT & PIPE OPENINGS FROM DEMOLITION NOT
USED. SEAL AIR/WATER TIGHT AND PATCH INSULATION.
5. PIPING IS SHOWN SPACED APART FOR CLARITY PURPOSES ONLY.
6. INSTALL 90° RADIUS ELBOWS WHERE SHOWN. INSTALL TURNING VANES ON
ALL 90° MITERED ELBOWS.
7. DUCTWORK SHOWN IS SIZED AND ROUTED TO MAINTAIN ARCHITECT'S DESIRED
CEILING HEIGHTS. THE CONTRACTOR IS RESPONSIBLE TO NOTIFY ENGINEER OF
ANY DISCREPANCIES WHERE ARCHITECT'S DESIRED CEILING HEIGHTS CANNOT
BE OBTAINED PRIOR TO DUCT FABRICATION/INSTALLATION.
8. CLEAN EXISTING DUCTWORK & INSULATION WITHIN THE SCOPE OF PROJECT TO
LIKE-NEW CONDITION.
9. NOT USED.
10. COORDINATE ZONE TEMPERATURE SENSOR & HUMIDITY SENSOR LOCATIONS
WITH THE CONTRACTOR AND EQUIPMENT PLANS.
11. MAINTAIN MANUFACTURER'S RECOMMENDED SERVICE CLEARANCES ON ALL
MECHANICAL EQUIPMENT. ALL EQUIPMENT MUST BE ACCESSIBLE FOR
MAINTENANCE.
12. THE CONTRACTOR SHALL OBTAIN ROOF WARRANTY INFORMATION PRIOR TO
STARTING WORK. COORDINATE ALL WORK WITH ROOF INSTALLER AND FOLLOW
PROCEDURES TO MAINTAIN ROOF WARRANTY.
13. INSTALL ALL PIPING ON ROOF ON PIPE SUPPORTS - REFER TO DETAIL SHEETS.
14. INSTALL 5 WATTS/FT OF ELECTRIC HEAT TAPE ON ALL CWS, CWR, AND MDCW
PIPING ABOVE THE ROOF AND INSIDE PIPE CABINETS. HEAT TAPE SHALL BE
120/1Ø. THE CONTRACTOR SHALL PROVIDE AN ELECTRICAL CONNECTION.
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
KEY NOTESX
1 ROUTE 18" ROUND EA DUCT UP THRU CHASE TO EF-F1204-01 ON ROOF. THE CHASE
WAS SEALED DURING DESIGN AND COULD NOT VERIFY IF THERE ARE OTHER EXISTING
SYSTEMS FROM OTHER TRADES INSIDE THE CHASE. CONTRACTOR SHALL RELOCATE OR
RE-ROUTE ANY EXISTING SYSTEMS AS NECESSARY TO ACCOMMODATE THE NEW
EXHAUST DUCT.
2 ALL EXHAUST DUCTWORK ASSOCIATED WITH BIOLOGICAL SAFETY CABINETS SHALL BE
WELDED 316-L STAINLESS STEEL ROUND DUCT PER VA STANDARDS. SUBSTITUTION
REQUESTS FOR ANY OTHER MATERIAL OR SEALING METHOD WILL NOT BE ACCEPTED.
MECH
NG1008A
ETR
23-AHU-81
ETR
RF
ETR
SA-1
40x18
32x22 x
28x16 3
M P S
FD
34x16
MPR
HWR
HWS
MPS
CWS
CWR
6" CWR
6" CWS
6" CWS
6" CWR
3" CWS
3" CWR
3" MPS
1 1/2" MPR
6" CWR
6" CWS
3" MPS
1 1/2" MPR
2" MPS
1 1/2" MPR
STORAGE
N1006A
HAZARDOUS
DRUG
STORAGE
N1004B
HAZARDOUS
COMPOUNDING
N1004C
ANTE
ROOM
N1004A
VESTIBULE
N1004
VESTIBULE
N1006B
PHYSICAL
THERAPY
ROOM
N1006
CHEMOTHERAPY
N1002
WORK
AREA
N1002B
20x20
RELOCATED
650 CFM (x2) x x x x
16x8
16x8 x ø x x x
MPR
MPS
HWS
HWR
HWR
HWS
20x16 x
HWS
HWR
ETR
650 CFM
x
ETR
TB-88-01
ETR
TB-55-03
ETR
TB-88-04
RELOCATED
205 CFM
x
8x8 ø ø
14x14
RELOCATED
TB-88-02
ETR
260 CFM
ETR
260 CFM
ETR
650 CFM
x x ø ø ø ETR
205 CFM
F/S
6ø
10x10
ETR
TB-41-2-8
A-200 ø ø
8ø
A-200 ø ø
MH202
ø
3" CWR
3" CWS
2" MPS
1 1/2" MPR
8ø
12 10
MECHANICAL
N1008B
12ø
PHYSICAL
THERAPY
ROOM
N1006
PHYSICAL
THERAPY
ROOM
N1006
PHYSICAL
THERAPY
ROOM
N1006
OFFICE
N1006C
ELEVATOR
AHU-N1004-01
EF-N1004-01
ETR GRAVITY RELIEF HOOD
FROM 23-AHU-088 IN
MECHANICAL ROOM BELOW
EXISTING ROOF
ACCESS HATCH
ETR GRAVITY RELIEF HOOD
FROM 23-AHU-088 IN
MECHANICAL ROOM BELOW
EXISTING ROOF
ACCESS HATCH
EXISTING
ROOF
DRAIN
EXISTING
ROOF
DRAIN
x
3/4" MPS
3/4" MPR
3" CWR
3" CWS
2" MPS
1 1/2" MPR
12x12
OA
INTAKE
M
IN
IM
U
M
F R
O M
O A
I N
T A
K E
CD
CD
SMOKE TIGHT PARTITION
RATED WALL LEGEND
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management
102 THIRD AVENUE NORTHEAST
HICKORY, NORTH CAROLINA 28601
PHONE: 828.315.9962
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
CHARLOTTE | 704.295.4263
705 EAST MOREHEAD STREET, 28202
NC License No: C-2848
AME Project No: 18104
VA FORM 08-6231
F
E
D
C
B
A
PLAN NORTH TRUE NORTH
558-17-233
Durham VAMC Durham NC
REPLACE PHARMACY AHUS
RENOVATE F1204 & N1004
COMPOUNDING PHARMACIES
- MH103
WEBFFR
MECHANICAL - NEW WORK PLAN - LEVEL 00 &
LEVEL 01 & ROOF - N1004
FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY
1/4" = 1'-0"
MECHANICAL - NEW WORK PLAN - LEVEL 00 - N1004
1/4" = 1'-0"
MECHANICAL - NEW WORK PLAN - LEVEL 01 - N1004
1/4" = 1'-0"
MECHANICAL - NEW WORK PLAN - ROOF - N1004
1. REFER TO OVERALL PLAN OF CAMPUS FOR AREAS OF WORK ON A011.
2. REFER TO PHASING & PRE-CONSTRUCTION NOTES ON M-001.
3. EXISTING CONDITIONS, EQUIPMENT, MATERIALS, LOCATIONS, AND SIZES ARE
SHOWN FOR REFERENCE ONLY. THE CONTRACTOR IS RESPONSIBLE TO VERIFY
ALL EXISTING CONDITIONS/SIZES AND NOTIFY ENGINEER OF ANY
DISCREPANCIES IN WRITING PRIOR TO STARTING WORK.
4. CAP AND REPAIR EXISTING DUCT & PIPE OPENINGS FROM DEMOLITION NOT
USED. SEAL AIR/WATER TIGHT AND PATCH INSULATION.
5. PIPING IS SHOWN SPACED APART FOR CLARITY PURPOSES ONLY.
6. INSTALL 90° RADIUS ELBOWS WHERE SHOWN. INSTALL TURNING VANES ON ALL
90° MITERED ELBOWS.
7. DUCTWORK SHOWN IS SIZED AND ROUTED TO MAINTAIN ARCHITECT'S
DESIRED CEILING HEIGHTS. THE CONTRACTOR IS RESPONSIBLE TO NOTIFY
ENGINEER OF ANY DISCREPANCIES WHERE ARCHITECT'S DESIRED CEILING
HEIGHTS CANNOT BE OBTAINED PRIOR TO DUCT FABRICATION/INSTALLATION.
8. CLEAN EXISTING DUCTWORK & INSULATION WITHIN THE SCOPE OF PROJECT TO
LIKE-NEW CONDITION.
9. NOT USED.
10. COORDINATE ZONE TEMPERATURE SENSOR & HUMIDITY SENSOR LOCATIONS
WITH THE CONTRACTOR AND EQUIPMENT PLANS.
11. MAINTAIN MANUFACTURER'S RECOMMENDED SERVICE CLEARANCES ON ALL
MECHANICAL EQUIPMENT. ALL EQUIPMENT MUST BE ACCESSIBLE FOR
MAINTENANCE.
12. INSTALL AIR CONTOL VALVES WITH CONTROLS ENCLOSURE FACING DOWN
TOWARDS FLOOR FOR ACCESSIBILITY.
13. THE CONTRACTOR SHALL OBTAIN ROOF WARRANTY INFORMATION PRIOR TO
STARTING WORK. COORDINATE ALL WORK WITH ROOF INSTALLER AND FOLLOW
PROCEDURES TO MAINTAIN ROOF WARRANTY.
14. INSTALL ALL PIPING ON ROOF ON PIPE SUPPORTS - REFER TO DETAIL SHEETS.
15. INSTALL 5 WATTS/FT OF ELECTRIC HEAT TAPE ON ALL CWS, CWR, AND MDCW
PIPING ABOVE THE ROOF AND INSIDE PIPE CABINETS. HEAT TAPE SHALL BE
120/1Ø. THE CONTRACTOR SHALL PROVIDE AN ELECTRICAL CONNECTION.
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
GENERAL NOTES
KEY NOTESX
1 HIDDEN LINES INDICATE AN OPENING FROM NG1008A MECHANICAL ROOM UP TO CHASE
ON FLOOR ABOVE. THE OPENING IS VISIBLE INSIDE NG1008A MECHANICAL ROOM BUT
ACCESSIBILITY WILL BE DIFFICULT WITH ETR-AHU-81 DIRECTLY BELOW AND OTHER
EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. SCAFFOLDING WILL BE REQUIRED.
2 TIE NEW 3" CWS & CWR PIPING INTO EXISTING 6" CWS & CWR MAINS. DO NOT TIE
NEW PIPES INTO EXISTING PIPES THAT ARE SMALLER IN SIZE, CLOSER, MORE
CONVENIENT, ETC. FIELD VERIFY AND COORDINATE EXACT TIE-IN LOCATIONS WITH
EXISTING CONDITIONS. MATCH EXISTING PIPE MATERIALS AND INSULATION SYSTEMS.
PROVIDE NEW ISOLATION VALVES. ROUTE NEW 3" CWS & CWR PIPING UP OPENING TO
FLOOR ABOVE. FIELD VERIFY ROUTING WITH EXISTING CONDITIONS.
3 TIE NEW 2" MPS & 1-1/2" MPR PIPING INTO EXISTING 3" MPS & 1-1/2" MPR MAINS. DO
NOT TIE NEW PIPES INTO EXISTING PIPES THAT ARE SMALLER IN SIZE, CLOSER, MORE
CONVENIENT, ETC. FIELD VERIFY AND COORDINATE EXACT TIE-IN LOCATIONS WITH
EXISTING CONDITIONS. MATCH EXISTING PIPE MATERIALS AND INSULATION SYSTEMS.
PROVIDE NEW ISOLATION VALVES. ROUTE NEW 2" MPS & 1" MPR PIPING UP OPENING
TO FLOOR ABOVE. FIELD VERIFY ROUTING WITH EXISTING CONDITIONS.
4 ETR 6" CWS & CWR PIPING MAINS FROM UNDERGROUND AND FROM CENTRAL UTILITY
PLANT.
5 REBALANCE ETR TB-41-2-8 FOR 400 CFM (PRIMARY MAX) AND 120 CFM (PRIMARY MIN.)
6 RELOCATED ZONE TEMPERATURE SENSOR "41-2-8" SERVING ETR TB-41-2-8.
7 ROUTE 12"x12" RA DUCT UP TO NEW AHU-N1004-01 ON ROOF.
8 ROUTE 3" CWS, 3" CWR, 2" MPS, & 1-1/2" MPR PIPING UP THRU ROOF TO NEW
AHU-N1004-01.
9 ROUTE 3" CWS, 3" CWR, 2" MPS, AND 1-1/2" MPR PIPING DOWN CHASE TO NG1008A
MECHANICAL ROOM BELOW.
10 RELOCATED RETURN GRILLE. CONTRACTOR SHALL VERIFY AND MATCH EXISTING NECK
SIZE AND REBALANCE TO CFM INDICATED.
11 TIE NEW HWS & HWR PIPING INTO EXISTING AND ROUTE TO RELOCATED TB-88-02.
CONTRACTOR SHALL VERIFY AND MATCH PRIOR RUNOUT SIZES, MATCH EXISTING
INSULATION TYPE, AND REUSE EXISTING CONTROL VALVE ASSEMBLY.
12 RELOCATED TB-88-02. CONTRACTOR SHALL REBALANCE AS REQUIRED TO MATCH
PREVIOUS AIRFLOWS.
13 ROUTE 20"x20" SA DUCT DOWN THRU ROOF.
14 ROUTE 12"x12" RA DUCT DOWN THRU ROOF.
15 ROUTE 3" CWS, 3" CWR, 2" MPS, & 1-1/2" MPR PIPING TO CHILLED WATER COOLING
COIL, STEAM PRE-HEAT COIL, STEAM RE-HEAT COIL, AND HUMIDIFIER ON NEW AHU.
MATCH CONNECTION SIZES ON AHU.
16 PROVIDE TRAP AND ROUTE CONDENSATE DRAIN PIPING (BY GRAVITY) TO EXISTING
ROOF DRAIN - REFER TO DETAIL SHEETS AND INSTALL PER MANUFACTURER'S
RECOMMENDATIONS. CONDENSATE DRAIN PIPE SHALL MATCH CONNECTION SIZE ON
AHU-N1004-01.
HAZARDOUS
STORAGE
F1204J
134 SF
OFFICE
F1217C
NON
HAZARDOUS
COMPOUNDING
F1204M
184 SF
STERILE
STORAGE
F1204N
285 SF
ANTE
ROOM
F1204K
237 SF
HAZARDOUS
COMPOUNDING
F1204L
164 SF
SHARED
OFFICE
F1217B
PHARMACY
F1204
30x18
18x18 14x14
18x18 ø 1 ø ø ø
A C V -F
-0
A C V -F
-0
A C V -F
-1
A C V -F
-1
0A C V -F
-0
A C V -F
-0
A C V -F
-0
A C V -F
-0 ø ø ø
18ø ø ø ø ø x
FFU-F1204-01
FFU-F1204-02
FFU-F1204-03
ø
A-125
A-125 ø x ø ø
14x4
14x4
K-250
J-100
J-100
G-1250
H-800 ø
14x14
12ø ø
12x12 ø
E-550
12ø 10ø ø ø ø ø
FFU-F1204-10 FFU-F1204-11
F F U
-F -0
FFU-F1204-07
FFU-F1204-06
FFU-F1204-05
ø
ACV-F1204-09
A C V -F
-0
ACV-F1204-03
12ø ø
C-125
C-125
8ø
8ø ø
FFU-F1204-04
10ø
12ø ø ø
7 7
7 7
7 7 ø ø
F F U
-F -0
12ø
A C V -F
-1
12ø
NOTE: REFER TO F12044 PHARMACY CONTROLS
ON SHEET M-502 FOR LOCATIONS OF
TEMPERATURE SENSORS, HUMIDITY SENSORS,
AND PRESSURE MONITORS FOR ROOMS
WITHING THE PHARMACY COMPOUNDING SUITE.
ø ø
12ø 14ø ø
10ø ø
12 12 12
TO
VAV-30-2-11
TO ETR
VAV-30-2-10
OMNICELL/795
AREA
F1204D
PHARMACY
F1204
16x16
SMOKE TIGHT PARTITION
RATED WALL LEGEND
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management
102 THIRD AVENUE NORTHEAST
HICKORY, NORTH CAROLINA 28601
PHONE: 828.315.9962
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
CHARLOTTE | 704.295.4263
705 EAST MOREHEAD STREET, 28202
NC License No: C-2848
AME Project No: 18104
VA FORM 08-6231
F
E
D
C
B
A
PLAN NORTH TRUE NORTH
558-17-233
Durham VAMC Durham NC
REPLACE PHARMACY AHUS
RENOVATE F1204 & N1004
COMPOUNDING PHARMACIES
- MH201
WEBFFR
MECHANICAL - ENLARGED PHARMACY PLAN -
F1204
FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY
1/2" = 1'-0"
F1204 - MECHANICAL ENLARGED F1204 PHARMACY PLAN
KEY NOTESX
1 ROUTE 30"x18" SA DUCT UP TO NEW AHU-F1204-01 ON FLOOR ABOVE.
2 ROUTE 18"x18" RA DUCT UP TO NEW AHU-F1204-01 ON FLOOR ABOVE.
3 ROUTE 18" ROUND EA DUCT UP TO LEVEL 02 ABOVE.
4 ROUTE 10" ROUND EA DUCT UP TO LEVEL 02 ABOVE.
5 INSTALL AEROSOL INJECTION PORT IN CEILING ADJACENT TO LAMINAR FLOW HEPA DIFFUSER. ROUTE
3/4" FLEXIBLE TUBING TO DUCT CONNECTION PLATE LOCATED IMMEDIATELY DOWNSTREAM OF THE
REMOTE OPERATED DAMPER. IT IS INTENDED TO PROVIDE THE MAXIMUM DISTANCE IN DUCTWORK
BETWEEN THE HEPA FILTER AND DUCT CONNECTION PLATE. AEROSOL INJECTION PORT ASSEMBLY
MANUFACTURER SHALL BE CEPA OPERATIONS INC. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS.
6 FINAL EXHAUST DUCT CONNECTION TO TOP OF BIOLOGICAL SAFETY CABINET SHALL BE CAREFULLY
COORDINATED PRIOR TO ROUTING ANY EXHAUST DUCTWORK DOWN THROUGH THE HARD CEILING.
FLEXIBLE EXHAUST DUCTWORK IS NOT ACCEPTABLE PER VA STANDARDS. CONTRACTOR SHALL
CAREFULLY COORDINATE THE EXACT LOCATION OF EACH BIOLOGICAL SAFETY CABINET AND THE
EXACT LOCATION OF THE EXHAUST DUCT CONNECTION ON TOP OF EACH CABINET. IT IS CRITICAL
FOR THE HARD EXHAUST DUCT TO BE PERFECTLY CENTERED AND ALIGNED WITH THE EXHAUST
CONNECTION ON TOP OF EACH BIOLOGICAL SAFETY CABINET TO AVOID USING FLEXIBLE DUCTWORK.
LATER CLAIMS AND REQUESTS TO SUBSTITUTE FLEXIBLE DUCTWORK TO MAKE THE FINAL
CONNECTION WILL NOT BE ACCEPTED. MAKE FINAL CONNECTION TO TOP OF BIOLOGICAL SAFETY
CABINET WITH 12" ROUND HARD EXHAUST DUCT.
7 ALL EXHAUST DUCTWORK ASSOCIATED WITH BIOLOGICAL SAFETY CABINETS SHALL BE WELDED 316-L
STAINLESS STEEL ROUND DUCT PER VA STANDARDS. SUBSTITUTION REQUESTS FOR ANY OTHER
MATERIAL OR SEALING METHOD WILL NOT BE ACCEPTED.
8 INSTALL BOTTOM OF SIDEWALL EXHAUST GRILLE 7" ABOVE FINISHED FLOOR PER VA STANDARDS.
9 INSTALL SIDEWALL EXHAUST GRILLE BEHIND HAZARDOUS DRUG REFRIGERATOR. INSTALL BOTTOM
OF GRILLE 7" ABOVE FINISHED FLOOR PER VA STANDARDS.
10 INSTALL BOTTOM OF SIDEWALL RETURN GRILLE 7" ABOVE FINISHED FLOOR PER VA STANDARDS.
11 INSTALL BALL-IN-THE-WALL VISUAL PRESSURE INDICATOR 7'-0" ABOVE FLOOR - REFER TO DETAIL
SHEETS.
12 FIRE DAMPER NOT REQUIRED FOR DUCT PENETRATION OF 1-HOUR FIRE BARRIER PER 2018 IMC
607.5.2 EXCEPTION 3.
13 ZONE TEMPERATURE SENSOR SERVING NEW VAV-30-2-11.
14 RELOCATED ZONE TEMPERATURE SENSOR "30-2-10" SERVING ETR VAV-30-2-10.
GENERAL NOTES
1. REFER TO OVERALL PLAN OF CAMPUS FOR AREAS OF WORK ON A011.
2. REFER TO PHASING & PRE-CONSTRUCTION NOTES ON M-001.
3. EXISTING CONDITIONS, EQUIPMENT, MATERIALS, LOCATIONS, AND SIZES ARE SHOWN FOR
REFERENCE ONLY. THE CONTRACTOR IS RESPONSIBLE TO VERIFY ALL EXISTING
CONDITIONS/SIZES AND NOTIFY ENGINEER OF ANY DISCREPANCIES IN WRITING PRIOR TO
STARTING WORK.
4. CAP AND REPAIR EXISTING DUCT & PIPE OPENINGS FROM DEMOLITION NOT USED. SEAL
AIR/WATER TIGHT AND PATCH INSULATION.
5. PIPING IS SHOWN SPACED APART FOR CLARITY PURPOSES ONLY.
6. INSTALL 90° RADIUS ELBOWS WHERE SHOWN. INSTALL TURNING VANES ON ALL 90°
MITERED ELBOWS.
7. DUCTWORK SHOWN IS SIZED AND ROUTED TO MAINTAIN ARCHITECT'S DESIRED CEILING
HEIGHTS. THE CONTRACTOR IS RESPONSIBLE TO NOTIFY ENGINEER OF ANY
DISCREPANCIES WHERE ARCHITECT'S DESIRED CEILING HEIGHTS CANNOT BE OBTAINED
PRIOR TO DUCT FABRICATION/INSTALLATION.
8. CLEAN EXISTING DUCTWORK & INSULATION WITHIN THE SCOPE OF PROJECT TO LIKE-NEW
CONDITION.
9. NOT USED.
10. COORDINATE ZONE TEMPERATURE SENSOR, HUMIDITY SENSOR, AND PRESSURE
MONITORING SENSOR LOCATIONS WITH THE CONTRACTOR AND EQUIPMENT PLANS.
LOCATIONS SHOWN ON THIS PLAN ARE GENERAL AND SPACED APART FOR CLARITY
PURPOSES - REFER TO F-1204 PHARMACY CONTROLS ON M-502 FOR PROPOSED LOCATIONS.
11. MAINTAIN MANUFACTURER'S RECOMMENDED SERVICE CLEARANCES ON ALL MECHANICAL
EQUIPMENT. ALL EQUIPMENT MUST BE ACCESSIBLE FOR MAINTENANCE.
12. INSTALL AIR CONTROL VALVES WITH CONTROLS ENCLOSURE FACING DOWN TOWARDS
FLOOR FOR ACCESSIBILITY.
0' 1' 2' 4'
SCALE: 1/2" = 1'-0"
STORAGE
N1006A
HAZARDOUS
DRUG
STORAGE
N1004B
168 SF
HAZARDOUS
COMPOUNDING
N1004C
129 SF
ANTE
ROOM
N1004A
149 SF
VESTIBULE
N1006B
FFU-N1004-04
20x20
I-500
EF-N1004-02
RELOCATED
260 CFM
RELOCATED
260 CFM
ø x
0ETR
205 CFM
8x8
8x8
12ø
12ø
12ø ø ø
LVR-01
ø
J-100
FFU-N1004-03
x
ETR
260 CFM
ø ø
16x16 ø
12ø
10ø 10ø
12ø
12ø
12ø x x ø
10ø
FFU-N1004-01
FFU-N1004-02
HWR
HWS
12ø
12ø
8x16
F-650
16x12
12ø
FFU-N1004-07
FFU-N1004-06
FFU-N1004-05
ACV-N1004-04
ACV-N1004-05
ACV-N1004-06
A C V -N
-0
A C V -N
-0
A C V -N
-0 x
FD
D-N/A
D-N/A
10ø ø ø ø
18ø
12ø
12ø
12ø
12ø
8ø 14ø 10ø1
3 3
7 7 7
8 9
ACV-N1004-07
ACV-N1004-08
ø ø
10ø
12x12
6 6 6
VESTIBULE
N1004
2" MPS
1" MPR
M P R
M P S
NOTE: REFER TO N1004 PHARMACY CONTROLS
ON SHEET M-503 FOR LOCATIONS OF
TEMPERATURE SENSORS, HUMIDITY SENSORS,
AND PRESSURE MONITORS FOR ROOMS
WITHING THE PHARMACY COMPOUNDING SUITE.
SMOKE TIGHT PARTITION
RATED WALL LEGEND
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management
102 THIRD AVENUE NORTHEAST
HICKORY, NORTH CAROLINA 28601
PHONE: 828.315.9962
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
CHARLOTTE | 704.295.4263
705 EAST MOREHEAD STREET, 28202
NC License No: C-2848
AME Project No: 18104
VA FORM 08-6231
F
E
D
C
B
A
PLAN NORTH TRUE NORTH
558-17-233
Durham VAMC Durham NC
REPLACE PHARMACY AHUS
RENOVATE F1204 & N1004
COMPOUNDING PHARMACIES
- MH202
WEBFFR
MECHANICAL - ENLARGED PHARMACY PLAN -
N1004
FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY
1/2" = 1'-0"
N1004 - MECHANICAL ENLARGED N1004 PHARMACY PLAN
KEY NOTESX
1 ROUTE 20"x20" SA DUCT UP TO NEW AHU-N1004-01 ON ROOF.
2 ROUTE 18" ROUND EA DUCT UP TO NEW EF-N1004-01 ON ROOF.
3 INSTALL AEROSOL INJECTION PORT IN CEILING ADJACENT TO LAMINAR FLOW HEPA DIFFUSER. ROUTE
3/4" FLEXIBLE TUBING TO DUCT CONNECTION PLATE LOCATED IMMEDIATELY DOWNSTREAM OF THE
REMOTE OPERATED DAMPER. IT IS INTENDED TO PROVIDE THE MAXIMUM DISTANCE IN DUCTWORK
BETWEEN THE HEPA FILTER AND DUCT CONNECTION PLATE. AEROSOL INJECTION PORT ASSEMBLY
MANUFACTURER SHALL BE CEPA OPERATIONS INC. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS.
4 FINAL EXHAUST DUCT CONNECTION TO TOP OF BIOLOGICAL SAFETY CABINET SHALL BE CAREFULLY
COORDINATED PRIOR TO ROUTING ANY EXHAUST DUCTWORK DOWN THROUGH THE HARD CEILING.
FLEXIBLE EXHAUST DUCTWORK IS NOT ACCEPTABLE PER VA STANDARDS. CONTRACTOR SHALL
CAREFULLY COORDINATE THE EXACT LOCATION OF EACH BIOLOGICAL SAFETY CABINET AND THE
EXACT LOCATION OF THE EXHAUST DUCT CONNECTION ON TOP OF EACH CABINET. IT IS CRITICAL
FOR THE HARD EXHAUST DUCT TO BE PERFECTLY CENTERED AND ALIGNED WITH THE EXHAUST
CONNECTION ON TOP OF EACH BIOLOGICAL SAFETY CABINET TO AVOID USING FLEXIBLE DUCTWORK.
LATER CLAIMS AND REQUESTS TO SUBSTITUTE FLEXIBLE DUCTWORK TO MAKE THE FINAL
CONNECTION WILL NOT BE ACCEPTED. MAKE FINAL CONNECTION TO TOP OF BIOLOGICAL SAFETY
CABINET WITH 12" ROUND HARD EXHAUST DUCT.
5 ALL EXHAUST DUCTWORK ASSOCIATED WITH BIOLOGICAL SAFETY CABINETS SHALL BE WELDED 316-L
STAINLESS STEEL ROUND DUCT PER VA STANDARDS. SUBSTITUTION REQUESTS FOR ANY OTHER
MATERIAL OR SEALING METHOD WILL NOT BE ACCEPTED.
6 FIRE DAMPER NOT REQUIRED FOR DUCT PENETRATION OF 1-HOUR FIRE BARRIER PER 2018 IMC
607.5.2 EXCEPTION 3.
7 FIRE DAMPERS FOR BIOLOGICAL SAFETY CABINET EXHAUST ARE NOT REQUIRED PER VA STANDARDS.
8 RELOCATED ZONE TEMPERATURE SENSOR "TB-88-02" SERVING RELOCATED TB-88-02.
9 RELOCATED ZONE TEMPERATURE SENSOR "TB-88-04" SERVING ETR TB-88-04.
10 INSTALL BOTTOM OF SIDEWALL EXHAUST GRILLE 7" ABOVE FINISHED FLOOR PER VA STANDARDS.
11 INSTALL SIDEWALL EXHAUST GRILLE BEHIND HAZARDOUS DRUG REFRIGERATOR. INSTALL BOTTOM
OF GRILLE 7" ABOVE FINISHED FLOOR PER VA STANDARDS.
12 INSTALL BOTTOM OF SIDEWALL RETURN GRILLE 7" ABOVE FINISHED FLOOR PER VA STANDARDS.
13 INSTALL BALL-IN-THE-WALL VISUAL PRESSURE INDICATOR 7'-0" ABOVE FLOOR - REFER TO DETAIL
SHEETS.
GENERAL NOTES
1. REFER TO OVERALL PLAN OF CAMPUS FOR AREAS OF WORK ON A011.
2. REFER TO PHASING & PRE-CONSTRUCTION NOTES ON M-001.
3. EXISTING CONDITIONS, EQUIPMENT, MATERIALS, LOCATIONS, AND SIZES ARE SHOWN FOR
REFERENCE ONLY. THE CONTRACTOR IS RESPONSIBLE TO VERIFY ALL EXISTING
CONDITIONS/SIZES AND NOTIFY ENGINEER OF ANY DISCREPANCIES IN WRITING PRIOR TO
STARTING WORK.
4. CAP AND REPAIR EXISTING DUCT & PIPE OPENINGS FROM DEMOLITION NOT USED. SEAL
AIR/WATER TIGHT AND PATCH INSULATION.
5. PIPING IS SHOWN SPACED APART FOR CLARITY PURPOSES ONLY.
6. INSTALL 90° RADIUS ELBOWS WHERE SHOWN. INSTALL TURNING VANES ON ALL 90°
MITERED ELBOWS.
7. DUCTWORK SHOWN IS SIZED AND ROUTED TO MAINTAIN ARCHITECT'S DESIRED CEILING
HEIGHTS. THE CONTRACTOR IS RESPONSIBLE TO NOTIFY ENGINEER OF ANY
DISCREPANCIES WHERE ARCHITECT'S DESIRED CEILING HEIGHTS CANNOT BE OBTAINED
PRIOR TO DUCT FABRICATION/INSTALLATION.
8. CLEAN EXISTING DUCTWORK & INSULATION WITHIN THE SCOPE OF PROJECT TO LIKE-NEW
CONDITION.
9. NOT USED.
10. COORDINATE ZONE TEMPERATURE SENSOR, HUMIDITY SENSOR, AND PRESSURE
MONITORING SENSOR LOCATIONS WITH THE CONTRACTOR AND EQUIPMENT PLANS.
LOCATIONS SHOWN ON THIS PLAN ARE GENERAL AND SPACED APART FOR CLARITY
PURPOSES - REFER TO N-1004 PHARMACY CONTROLS ON M-503 FOR PROPOSED
LOCATIONS.
11. MAINTAIN MANUFACTURER'S RECOMMENDED SERVICE CLEARANCES ON ALL MECHANICAL
EQUIPMENT. ALL EQUIPMENT MUST BE ACCESSIBLE FOR MAINTENANCE.
12. INSTALL AIR CONTROL VALVES WITH CONTROLS ENCLOSURE FACING DOWN TOWARDS
FLOOR FOR ACCESSIBILITY.
0' 1' 2' 4'
SCALE: 1/2" = 1'-0"
| MH101 |
| Sheets |
| M-001 - MECHANICAL - GENERAL NOTES AND LEGENDS |
| M-701 - MECHANICAL - DETAILS |
| MH101 - MECHANICAL - NEW WORK PLAN - LEVEL 01 & LEVEL 02 - F1204 |
| MH102 - MECHANICAL - NEW WORK PLAN - LEVEL 03 & ROOF - F1204 |
| MH103 - MECHANICAL - NEW WORK PLAN - LEVEL 00 & LEVEL 01 & ROOF - N1004 |
| MH201 - MECHANICAL - ENLARGED PHARMACY PLAN - F1204 |
| MH202 - MECHANICAL - ENLARGED PHARMACY PLAN - N1004 |
| MH102 |
| Sheets |
| M-001 - MECHANICAL - GENERAL NOTES AND LEGENDS |
| M-701 - MECHANICAL - DETAILS |
| MH101 - MECHANICAL - NEW WORK PLAN - LEVEL 01 & LEVEL 02 - F1204 |
| MH102 - MECHANICAL - NEW WORK PLAN - LEVEL 03 & ROOF - F1204 |
| MH103 - MECHANICAL - NEW WORK PLAN - LEVEL 00 & LEVEL 01 & ROOF - N1004 |
| MH201 - MECHANICAL - ENLARGED PHARMACY PLAN - F1204 |
| MH202 - MECHANICAL - ENLARGED PHARMACY PLAN - N1004 |
| MH103 |
| Sheets |
| M-001 - MECHANICAL - GENERAL NOTES AND LEGENDS |
| M-701 - MECHANICAL - DETAILS |
| MH101 - MECHANICAL - NEW WORK PLAN - LEVEL 01 & LEVEL 02 - F1204 |
| MH102 - MECHANICAL - NEW WORK PLAN - LEVEL 03 & ROOF - F1204 |
| MH103 - MECHANICAL - NEW WORK PLAN - LEVEL 00 & LEVEL 01 & ROOF - N1004 |
| MH201 - MECHANICAL - ENLARGED PHARMACY PLAN - F1204 |
| MH202 - MECHANICAL - ENLARGED PHARMACY PLAN - N1004 |
| MH201 |
| Sheets |
| M-001 - MECHANICAL - GENERAL NOTES AND LEGENDS |
| M-701 - MECHANICAL - DETAILS |
| MH101 - MECHANICAL - NEW WORK PLAN - LEVEL 01 & LEVEL 02 - F1204 |
| MH102 - MECHANICAL - NEW WORK PLAN - LEVEL 03 & ROOF - F1204 |
| MH103 - MECHANICAL - NEW WORK PLAN - LEVEL 00 & LEVEL 01 & ROOF - N1004 |
| MH201 - MECHANICAL - ENLARGED PHARMACY PLAN - F1204 |
| MH202 - MECHANICAL - ENLARGED PHARMACY PLAN - N1004 |
| MH202 |
| Sheets |
| M-001 - MECHANICAL - GENERAL NOTES AND LEGENDS |
| M-701 - MECHANICAL - DETAILS |
| MH101 - MECHANICAL - NEW WORK PLAN - LEVEL 01 & LEVEL 02 - F1204 |
| MH102 - MECHANICAL - NEW WORK PLAN - LEVEL 03 & ROOF - F1204 |
| MH103 - MECHANICAL - NEW WORK PLAN - LEVEL 00 & LEVEL 01 & ROOF - N1004 |
| MH201 - MECHANICAL - ENLARGED PHARMACY PLAN - F1204 |
| MH202 - MECHANICAL - ENLARGED PHARMACY PLAN - N1004 |
File details come from the government source that posted it. Updated .