20180509R1 BES-SVAMC Bldg. 143 4th Floor Limited Hazardous Materials Survey Report.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24620R0119
About this file
This document contains the results of a limited hazardous materials survey conducted at the Salem Veterans Affairs Medical Center in Salem, Virginia. One hundred and eighty-five samples of suspect asbestos containing materials were collected from patient rooms and support areas in Buildings 143 H and J wings and submitted for laboratory analysis. No asbestos was detected in any of the materials sampled. However, some materials such as concealed pipe insulation should be presumed positive for asbestos unless subsequently tested. The report provides guidance on regulatory requirements for handling asbestos containing materials under the National Emission Standards for Hazardous Air Pollutants and Occupational Safety and Health Administration regulations during any renovation or demolition work.
The related federal contract opportunity is to renovate patient privacy areas in Wing J of the Salem Veterans Affairs Medical Center under solicitation number 36C24620R0119 as part of project 658-18-101. The solicitation from the Department of Veterans Affairs seeks offers for renovations that will involve materials identified in the hazardous materials survey report. Offerors must consider any asbestos abatement or special handling needs based on the survey results.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5238 VALLEYPOINTE PARKWAY
SUITE 2B, BUILDING C
ROANOKE, VA 24019
800-242-4906 TOLL FREE
540-521-1008 MAIN
www.HandP.com
ENGINEERING • SURVEYING • PLANNING • ENVIRONMENTAL • GIS
HURT & PROFFITT
Inspired | Responsive | Trusted
Original Issue: June 15, 2018 Revised Issue: August 12, 2020
BES Design/Build LLC 766 Middle Street Fairhope, Alabama 36532
Attention: Richard F. Holihan and Katie Sharples Phone: 843.522.2094 Email: rholihan@besbeaufort.com, ksharpless@besdesignbuild.com
Subject: Limited Hazardous Materials Survey Building 143, 4th Floor 1970 Roanoke Boulevard Salem, Virginia H&P Project 20180509
Mr. Holihan, Hurt & Proffitt, Inc. (H&P) was requested to conduct sampling of suspect asbestos containing materials (ACM) and lead containing painted building materials and to identify potential mercury and PCB containing components in Building 143 on the 4th Floor at Salem Veterans Affairs Medical Center in Salem, Virginia. The sampling and review was performed by H&P representatives Roy Wriston (Virginia Asbestos Inspector License number is 3303 003648) and Mary Beth Wriston (Virginia Asbestos Inspector License number is 3303 003466) on May 31 and June 1, 2018. The subject site is the 4th floor of Building 143 which houses patient rooms and associated medical support facilities and comprises two separate wings (H and J). The central section was excluded from H&P’s scope of work.
1.0 Asbestos Sampling Procedures and Findings
The intent of the asbestos sampling was to identify asbestos containing materials (ACM) in the effected portions of the building within both wings that could be disturbed by planned renovation work. Materials sampled included floor tiles and associated mastics, drywall, and joint compound, ceiling plasters, ceiling tiles, piping and duct insulations and mastics and vapor barriers located below ceramic tile flooring. We note that this was a limited invasive survey of accessible materials that could be sampled without damaging surfaces and systems components. The areas of focus were occupied during the survey which limited our ability to access and sample all potential concealed materials. If materials are encountered that were not represented during this limited survey; they must be sampled and analyzed for asbestos prior to disturbance.
The survey included collection of one hundred and eighty five (185) individual samples and layers of suspect asbestos containing materials (ACMs) that were submitted for analysis of asbestos. The suspect ACM samples were submitted to SanAir Technologies Laboratory an NVLAP accredited and Virginia licensed asbestos laboratory in Powhatan, Virginia, for analysis by Polarized Light Microscopy (PLM) mailto:rholihan@besbeaufort.com mailto:ksharpless@besdesignbuild.com following EPA Method 600/R-93/116. The analytical results are shown in the following table. Copies of the laboratory Asbestos Analysis Report and Chain of Custody forms are included as an attachment to this report.
Table I – 4th floor H and J Wings Building 143 Salem VAMC – Asbestos Sample Analysis Results
Sample # Sample Location Sample Type Lab Description
Analytical Results
(Estimated %
Asbestos)
4th Floor J Wing
531RW01 Room 126 Fire proofing Grey Fibrous None Detected
531RW02 Room 130 Fire proofing Grey Fibrous None Detected
531RW03 Room 107 Fire proofing Grey Fibrous None Detected
531RW04 Room 126 Fissured 2x4 ceiling tile White Fibrous None Detected
531RW05 Sample Not Submitted
531RW06 Room 107 Fissured 2x4 ceiling tile White Fibrous None Detected
531RW07 Room 126
Partition wall drywall
White Non-Fibrous None Detected
Partition wall joint compound White Non-Fibrous None Detected
Partition wall texture
White Non-Fibrous None Detected
531RW08 Room 130
Partition wall drywall
White Non-Fibrous None Detected
Partition wall joint compound White Non-Fibrous None Detected
Partition wall texture
White Non-Fibrous None Detected
531RW09 Room 112
Partition wall drywall
White Non-Fibrous None Detected
Partition wall joint compound White Non-Fibrous None Detected
531RW10 Room 126
Pipe insulation
Yellow Fibrous None Detected
Pipe wrap Various Fibrous None Detected
Pipe mastic Beige Non-Fibrous None Detected
531RW11 Room 125
Pipe insulation
Yellow Fibrous None Detected
Pipe wrap Various Fibrous None Detected
Pipe mastic Beige Non-Fibrous None Detected
Analytical Results
(Estimated %
Asbestos)
531RW12
Hallway by Room
Pipe insulation
Yellow Fibrous None Detected
Pipe mastic White Non-Fibrous None Detected
531RW13 Room 126
Drywall between metal wall studs
Beige Non-Fibrous None Detected
531RW14
Hallway by Room
Pipe insulation
Yellow Fibrous None Detected
Pipe wrap Various Fibrous None Detected
Pipe mastic White Non-Fibrous None Detected
531RW15 Room 125 Window sill caulk White Non-Fibrous None Detected
531RW16
Room 126 Bathroom
Perimeter Wall
Drywall Beige Non-Fibrous None Detected
Joint compound
White Non-Fibrous None Detected
531RW17
Room 135
Perimeter Wall
Drywall White Non-Fibrous None Detected
Joint compound
White Non-Fibrous None Detected
Texture White Non-Fibrous None Detected
531RW18
Room 103
Perimeter Wall
Drywall White Non-Fibrous None Detected
Joint compound
White Non-Fibrous None Detected
Texture White Non-Fibrous None Detected
531RW19
Room 126 Bathroom
Duct seam tape
White Fibrous None Detected
531RW20 Room 135
Duct seam tape mastic
Yellow Non-Fibrous None Detected
Duct seam insulation
Yellow Fibrous None Detected
531RW21 Room 107 Duct seam tape Cream Non-Fibrous None Detected
531RW22 Room 126 Door frame caulk White Non-Fibrous None Detected
531RW23 Room 103 Door frame caulk White Non-Fibrous None Detected
531RW24 Room 116 Door frame caulk White Non-Fibrous None Detected
531RW25 Room 126
12” White with grey streaks floor tile
Cream Non-Fibrous None Detected
Analytical Results
(Estimated %
Asbestos)
Mastic Tan Non-Fibrous None Detected
531RW26 Room 133
12” White with grey streaks floor tile
Off-White Non-Fibrous None Detected
Mastic Black Non-Fibrous None Detected
531RW27 Room 103
12” White with grey streaks floor tile
Off-White Non-Fibrous None Detected
Mastic Black Non-Fibrous None Detected
531RW28 Room 126 Grey base board mastic Off-White Non-Fibrous None Detected
531RW29 Room 103 Grey base board mastic Off-White Non-Fibrous None Detected
531RW30
Hallway near Break Room
Grey base board mastic
Yellow Non-Fibrous None Detected
531RW31 Room 126 Window caulk Grey Non-Fibrous None Detected
531RW32 Room 125 Window caulk White Non-Fibrous None Detected
531RW33 Room 124 Window caulk White Non-Fibrous None Detected
531RW34 Room 125 Elbow wrap White Non-Fibrous None Detected
Elbow insulation
Yellow Fibrous None Detected
531RW35 Room 103
Yellow duct mastic
Cream Non-Fibrous None Detected
Duct insulation
Yellow Fibrous None Detected
531RW36 Room 103 Yellow mastic on metal duct
Yellow Non-Fibrous None Detected
531RW37 Room 130 2x4 white ceiling tile
(hard) White Non-Fibrous None Detected
531RW38 Room 130 Fire caulking Brown Non-Fibrous None Detected
531RW39 Room 129 Duct mastic Off-White Non-Fibrous None Detected
Duct insulation
Pink Fibrous None Detected
531RW40 Room 139 Duct mastic Off-White Non-Fibrous None Detected
Analytical Results
(Estimated %
Asbestos)
Duct insulation
Yellow Fibrous None Detected
531RW41
Hallway by Room
Duct wrap Various Fibrous None Detected
Duct mastic Off-White Non-Fibrous None Detected
531RW42 Room 117 Ceiling Plaster-top Grey Non-Fibrous None Detected
Plaster-base White Non-Fibrous None Detected
531RW43 Room 117 Ceiling Plaster-top Grey Non-Fibrous None Detected
Plaster-base White Non-Fibrous None Detected
531RW44 Room 117 Ceiling Plaster-top Grey Non-Fibrous None Detected
Plaster-base White Non-Fibrous None Detected
531RW45 Room 117 Duct mastic Tan Non-Fibrous None Detected
531RW46 Room 117
Wall tile Grey Non-Fibrous None Detected
Wall tile mastic
Tan Non-Fibrous None Detected
Wall tile compound
White Non-Fibrous None Detected
531RW47 Room 117 Door threshold Grey Non-Fibrous None Detected
531RW48
Hallway near Break Room
Partition Wall
Drywall White Non-Fibrous None Detected
Texture White Non-Fibrous None Detected
531RW49
Break Room
Partition Wall
Drywall White Non-Fibrous None Detected
Joint compound
White Non-Fibrous None Detected
Texture White Non-Fibrous None Detected
531RW50 Break Room 2X4 White ceiling tile
Off-White Non-Fibrous None Detected
531RW51 Hallway 12’’ Green floor tile
Aqua Non-Fibrous None Detected
Mastic Black Non-Fibrous None Detected
531RW52 Hallway 12’’ Green floor tile
Aqua Non-Fibrous None Detected
Mastic Black Non-Fibrous None Detected
531RW53 Hallway 12’’ Green floor tile
Aqua Non-Fibrous None Detected
Mastic Black Non-Fibrous None Detected
531RW54 Break Room 12’’ Brown floor tile Off-White Non-Fibrous None Detected
Mastic Tan Non-Fibrous None Detected
531RW55
Drug/Medicine room 12’’ Brown floor tile Off-White Non-Fibrous None Detected
Analytical Results
(Estimated %
Asbestos)
Mastic Tan Non-Fibrous None Detected
531RW56
Drug/Medicine
Room
12’’ brown floor tile
Off-White Non-Fibrous None Detected
Mastic Tan Non-Fibrous None Detected
531RW57 Room 132
Large cove base
Grey Non-Fibrous None Detected
Large cove base mastic
Yellow Non-Fibrous None Detected
531RW58 Room 108 Carpet Off-White Fibrous None Detected
Carpet mastic Various Non-Fibrous None Detected
531RW59 Mechanical Room
6’’ Chilled water supply line insulation
Yellow Fibrous None Detected
Mastic Off-White Non-Fibrous None Detected
531RW60 Mechanical Room Pump box insulation
Yellow Fibrous None Detected
Mastic Off-White Non-Fibrous None Detected
531RW61 Mechanical Room
6” Heating supply line insulation
Yellow Fibrous None Detected
Mastic Off-White Non-Fibrous None Detected
531RW62 Mechanical Room
Square duct insulation
Yellow Fibrous None Detected
Square duct wrap
White Fibrous None Detected
531RW63
Mechanical Room
Chilled Water
Supply valve insulation
Yellow Fibrous None Detected
Supply valve mastic
Off-White Non-Fibrous None Detected
531RW64
Mechanical
Room@ Unit 143- AHU-4j1
Line insulation
Yellow Fibrous None Detected
Line mastic Off-White Non-Fibrous None Detected
531RW65 Mechanical Room
Low pressure steam line insulation
Yellow Fibrous None Detected
Wrap White Fibrous None Detected
531RW66 Mechanical Room Square duct insulation
Yellow Fibrous None Detected
Wrap White Fibrous None Detected
Analytical Results
(Estimated %
Asbestos)
531RW67 Mechanical Room Mastic on unit 143-PF- 4J1
Tan Non-Fibrous None Detected
531RW68 Mechanical Room
Condenser outlet insulation Yellow Fibrous None Detected
Mastic Off-White Non-Fibrous None Detected
531RW69 Mechanical Room Vibration damper cloth Black Non-Fibrous None Detected
531RW70 Mechanical Room Square duct wrap Various Fibrous None Detected
Insulation Yellow Non-Fibrous None Detected
531RW71 Mechanical Room Mastic on unit 143PF- 4J2
Brown Non-Fibrous None Detected
531RW72 Mechanical Room
Vibration Damper Cloth on Unit 143-
PF-4J2
Black Non-Fibrous None Detected
531RW73 Mechanical Room Elbow near unit 143-PF-
4J2 Yellow Fibrous None Detected
531RW74 Mechanical Room Chilled water line mastic White Non-Fibrous None Detected
Foam Black Non-Fibrous None Detected
531RW75 Mechanical Room Drywall White Non-Fibrous None Detected
Joint compound
White Non-Fibrous None Detected
4th Floor-H Wing
61RW01 Room 110 Fire proofing Grey Fibrous None Detected
61RW02 Room 157 Duct mastic Yellow Non-Fibrous None Detected
61RW03 Room 157 Drywall White Non-Fibrous None Detected
Joint compound
White Non-Fibrous None Detected
61RW04 Room 103A Ceiling tile White Fibrous None Detected
61RW05 Room 103A Window frame caulk White Non-Fibrous None Detected
61RW06 Room 103A Cove base mastic White Non-Fibrous None Detected
61RW07
Room 103 Bathroom
Plaster ceiling base coat
White Non-Fibrous None Detected
Analytical Results
(Estimated %
Asbestos)
Plaster ceiling skim coat
White Non-Fibrous None Detected
61RW08 Room 104
Patch material on piping-wrap
Tan Fibrous None Detected
Patch material on piping-insulation
Yellow Fibrous None Detected
61RW09 Room 113
White duct wrap
Tan Fibrous None Detected
White duct insulation
Yellow Fibrous None Detected
61RW10 Nurses’ Station Textured ceiling tile White Fibrous None Detected
61RW11 Room 127 Drywall White Non-Fibrous None Detected
Joint compound
White Non-Fibrous None Detected
61RW12 Room 127 White ceiling tile (hard) White Non-Fibrous None Detected
61RW13 Room 127
Sealant on wall around piping Grey Non-Fibrous None Detected
Wrap Various Fibrous None Detected
61RW14 Room 127
12’’ White with grey streaks floor tile
White Non-Fibrous None Detected
Mastic Black Non-Fibrous None Detected
61RW15 Room 131
Yellow mastic on pipe
Off-White Non-Fibrous None Detected
Pipe wrap Various Fibrous None Detected
Pipe insulation
Brown Fibrous None Detected
61RW16 Room 131 12’’ Pink floor tile Pink Non-Fibrous None Detected
Mastic Black Non-Fibrous None Detected
61RW17 Hallway
12’’ Pink floor tile
Pink Non-Fibrous None Detected
Mastic Black Non-Fibrous None Detected
Leveling compound
Off-White Non-Fibrous None Detected
Analytical Results
(Estimated %
Asbestos)
61RW18 Hallway
12’’ Pink floor tile
Pink Non-Fibrous None Detected
Mastic Black Non-Fibrous None Detected
Leveling compound
Off-White Non-Fibrous None Detected
61RW19 Break Room 12’’ Brown floor tile White Non-Fibrous None Detected
Mastic Yellow Non-Fibrous None Detected
61RW20 Mechanical Room
White duct mastic
White Non-Fibrous None Detected
White duct wrap
Various Fibrous None Detected
White duct glue
Brown Non-Fibrous None Detected
White duct insulation
Yellow Fibrous None Detected
61RW21 Mechanical Room
Glycol line mastic
White Non-Fibrous None Detected
Wrap Various Fibrous None Detected
Insulation Yellow Fibrous None Detected
61RW22 Mechanical Room Brown duct mastic on metal duct
Brown Non-Fibrous None Detected
61RW23 Mechanical Room
Chilled water supply line mastic Off-White Non-Fibrous None Detected
Wrap Various Fibrous None Detected
Insulation Yellow Fibrous None Detected
61RW24 Mechanical Room
Line mastic at Unit 143-JC-
4H1 White Non-Fibrous None Detected
Wrap Various Fibrous None Detected
Insulation Yellow Fibrous None Detected
61RW25 Mechanical Room White duct mastic Various Fibrous None Detected
Insulation Yellow Fibrous None Detected
61RW26 Mechanical Room Chilled water supply elbow
Grey Non-Fibrous None Detected
61RW27 Room 136
Drywall White Non-Fibrous None Detected
Joint compound
White Non-Fibrous
None Detected
Analytical Results
(Estimated %
Asbestos)
4th Floor-J Wing
61RW28 Room 117
Top layer of flooring-tile
Grey Non-Fibrous None Detected
Top layer of flooring-felt
Off-White Fibrous None Detected
Top layer of flooring-mortar
Grey Non-Fibrous None Detected
61RW29 Room 117 Bottom layer of flooring Tan Non-Fibrous None Detected
None Detected: No Asbestos Detected
2.0 Sample Analysis Results and Recommendations
Based on the results of analysis, asbestos was not detected in the materials sampled during this survey.
2.1 Presumed Asbestos Containing Materials
During the conduct of this survey, sampling was limited to those materials which were within the areas designated by the client, which were safely accessible and which were able to be sampled without damaging systems or structures. As such, some materials should be presumed to be positive, unless sampling is conducted and shown to be negative. Such presumed asbestos containing materials (PACMS) observed at the site include, but are not limited to:
1. Fire Door Interiors;
2. Electrical panel backing;
3. Concealed (above ceilings or within wall chases) piping or ducting insulation, if present.
If materials are encountered during demolition that were not sampled during this limited survey, they must be sampled and analyzed for asbestos by a Virginia licensed Inspector prior to disturbance.
Note 1: If during renovation/demolition, work is performed that will impact suspect materials that have not been sampled, it is recommended that these materials be sampled by a Virginia licensed asbestos inspector prior to disturbance.
Note 2: If asbestos abatement activities are performed within the building, all work should be performed by a Virginia licensed asbestos abatement contractor.
3.0 EPA/NESHAP Regulations for Asbestos Containing Materials
The U.S. Environmental Protection Agency promulgated the National Emission Standards for Hazardous Air Pollutants (NESHAP) [40 CFR Part 61], which addresses the application, removal, and disposal of asbestos-containing materials (ACM). Under NESHAP the following categories are defined for asbestos-containing materials:
Friable - When dry, can be crumbled, pulverized, or reduced to powder by hand pressure.
Non-friable - When dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
Category I Non-friable ACM - Packings, gaskets, resilient floor coverings, and asphalt roofing products containing more than 1% asbestos.
Category II Non-friable ACM – Any material, excluding Category I Non-friable ACM, which contains more than 1% asbestos.
Regulated Asbestos Containing Material (RACM) – One of the following:
1. Friable ACM
2. Category I Non-friable ACM that has become friable.
3. Category I Non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading.
4. Category II Non-friable ACM that has a high probability of becoming, or has become, friable by the forces expected to act on the material in the course of demolition or renovation operations.
Under NESHAP, the following actions are required:
1. Prior to the commencement of demolition or renovation activities, the building owner must inspect the affected facility or part of the facility where the demolition or renovation activities will occur for the presence of asbestos.
2. Remove all RACM from the facility before any activity begins that would break up, dislodge, or similarly disturb the material or preclude access for subsequent removal.
3. RACM need not be removed if:
a) It is Category I non-friable ACM that is not in poor condition.
b) It is on a facility component that is encased in concrete or other similar material and is adequately wet whenever exposed.
c) It was not accessible for testing and was therefore not discovered until after demolition began and because of the demolition the material cannot be safely removed.
d) It is Category II non-friable ACM and the probability is low that the material will become crumbled, pulverized, or reduced to powder during demolition.
Note: Based on our experience, we recommend that all ACM be removed prior to renovation or demolition due to the fact that disturbance can damage them, create potential exposure to workers and occupants and make them friable. This recommendation is made as a best practice to reduce potential exposure and limit liability.
4.0 OSHA
The Occupational Safety and Health Administration (OSHA) regulates employee exposure to asbestos under 29 CFR 1926.1101 and 29 CFR 1926.1001. Work associated with known or suspect asbestos containing materials (ACM), including trace (<1%) levels of asbestos, must be conducted according to these regulations in addition to the noted EPA regulations where applicable.
If the materials that have been identified as asbestos containing will be disturbed or are in poor condition, it is recommended that the asbestos be removed by an appropriately trained and licensed asbestos abatement contractor in accordance with Virginia, EPA and OSHA regulations.
If work is performed that will impact suspect materials that have not been sampled, it is recommended that they be sampled by a Virginia licensed Asbestos Inspector prior to disturbance. We note that during renovation or demolition activities, it is not uncommon to reveal materials that were not accessible during the survey or their presence could not otherwise be known.
5.0 Lead Containing Paint Testing Procedures
Testing for lead in paint was performed by sampling representative materials and components using a Niton XLp-300A X-Ray Fluorescence (XRF) Lead Paint Analyzer. The XRF contains a small radioactive source (Cadmium 109) which emits radiation when exposed to a surface. If the paint contains lead, the radiation will stimulate the lead atoms to emit characteristic x-rays, which are sensed by a detector in the unit. The XRF then converts these signals to a final reading in milligrams of lead per square centimeter of surface area tested (mg/cm2). Calibration of the Analyzer was conducted in accordance with the manufacturer’s instructions using standard reference materials with different lead concentrations. The Analyzer must indicate readings within the acceptable calibration range for the average of three readings.
If the average of the three readings is within the established tolerance, the unit is working properly.
Calibration checks were performed prior to and at the end of the testing. The XRF is able to accurately detect as little as 0.1 mg/cm2 of lead; the action level used during this survey. Any readings that registered a detectable level of lead with the XRF range are considered as “lead containing” for the purposes of this survey. Where components tested below the designated action level of 0.1 mg/cm² for classifying the material as lead containing; it is important to note that any painted or coated surface may contain concentrations of lead, which when disturbed, could generate lead in dust greater than the action level exposure concentration of 30 ug/m3 established by the OSHA “Lead Exposure in Construction Rule”
(29 CFR 1926.62).
5.1 Lead In Paint Testing Results
A total of seventy two (72) XRF readings, including calibrations, were collected from painted or surface coated building materials. Tested materials and components included:
Walls;
Windows and casing;
Door and door casing;
Ceiling;
Cabinets;
5.2 Lead In Paint Findings
The purpose of the screening was to identify painted surfaces and surface coatings that may contain lead at concentrations above the comparative standard. Based on the results of XRF testing, lead containing paint was not identified above the survey action level in the building materials tested.
6.0 Regulatory Compliance for Lead
H&P recommends that the contractor adhere to all applicable EPA regulations regarding disposal requirements and OSHA regulations for employee exposure.
6.1 OSHA Regulations
Where components tested below the designated action level of 1.0 mg/cm² for classifying the material as lead based paint (LBP), it is important to note that any painted or coated surface may contain concentrations of lead, which when disturbed, could generate lead in dust greater than the action level exposure concentration of 30 ug/m3 established by the OSHA “Lead Exposure in Construction Rule” (29 CFR 1926.62). The OSHA standard gives no guidance on acceptable levels of lead in coatings at which no exposure to airborne lead (above the action level) would be expected; however, OSHA defines airborne concentrations and lists specific work practices which may create a lead hazard. Therefore, personnel exposure monitoring should be performed during any removal or demolition process to establish worker exposure levels which can be used to determine appropriate personnel protection and environmental controls for the specific work practice and material type. In accordance with OSHA requirements, the Contractor performing the work will be required to conduct this monitoring.
6.2 EPA Regulations
For disposal of construction/demolition debris that have lead, the EPA requires the generator perform testing for lead content of the waste stream to determine proper disposal in accordance with the requirements of 40 CFR 261.11, Criteria for Listing Hazardous Waste.
7.0 PCB Containing Components
7.1 Methodology
During our site visit, H&P was accompanied by SVAMC facility staff who told us that just prior to our survey, they completed a lighting upgrade on the wings of the 4th floor. H&P visually reviewed accessible areas of the wings of the floor to check for electrical transformers, gear boxes, light ballasts and other components that could contain polychlorinated biphenyls (PCBs). Based on our review and the understanding that a lighting upgrade had recently been completed, obvious PCB containing ballasts and other components were not observed.
7.2 Results and Recommendations
H&P did not observe suspect PCB containing components in the areas that could be accessed for viewing.
However based on the age of the building, there could be concealed components that could contain PCB’s that may be revealed during demolition for renovation. If encountered, the component should be reviewed and assessed prior to disturbance. If found, PCB should be properly disposed following all applicable local, state and federal regulations.
8.0 Mercury Containing Thermostats, Switches and other Components
8.1 Methodology
H&P visually reviewed accessible areas of the floor wings to check for suspect mercury containing components including thermostats, switches, fluorescent lamps, mercury vapor lamps, and other components.
8.2 Results and Recommendations
H&P did not observe obvious mercury containing thermostats, switches, lighting or other components.
However various light bulbs were noted that could contain mercury, including newer fluorescent bulbs that do contain low levels. H&P recommends that these various components be reviewed at the time of removal and if found to contain mercury, be properly disposed following all applicable local, state and federal regulations. Mercury containing waste components are considered as hazardous waste materials in the Commonwealth of Virginia and should be handled accordingly.
9.0 Other Miscellaneous Materials
Medical waste collection containers are present in rooms throughout the project area. These containers should be emptied by qualified personnel and the contents disposed per established facility procedures prior to being disturbed during renovation work.
Other materials of an environmental concern that could require special handling and disposal were not observed in the areas reviewed during this survey.
10.0 Limitations
This report summarizes the results of our sample collection and analysis of the suspect ACM and lead in paint testing and review for other materials of concern based on our understanding of the requested scope of work. The findings prepared by H&P are based upon our observations and the analytical analysis of the samples collected at the time of our field inspection. The services performed were provided in accordance with generally accepted environmental industry standard practices. No warranty, expressed or implied, is made. Our observations, conclusions and recommendations are based upon conditions readily visible at the site at the time of our visit, the results of testing and analysis and information provided to us by others.
Our conclusions and recommendations are based on the guidelines presented by the EPA, Commonwealth of Virginia and OSHA. Any conditions discovered which deviate from the data contained in this report should be presented to us for our evaluation. This report has been prepared for the exclusive use of the client and/or their agents. This service was performed in accordance with generally accepted environmental practices. Our conclusions and recommendations are based, in part, upon information provided to us by others; we have not verified the completeness or accuracy of the information provided by others, unless otherwise noted.
During H&P’s non-invasive inspection, accessible areas were visually surveyed for the presence of ACM,.
Areas reviewed were limited to those identified by the Client and that could be readily and safely accessed. Our conclusions and recommendations are based on the results of our testing and cannot be used to form a professional opinion of conditions in other areas beyond those from which the samples were collected. It is possible that inaccessible areas, such as behind walls or above ceilings, may not have been surveyed and therefore conditions in these areas are unknown.
During this study, suspect asbestos samples were submitted for analysis at an NVLAP-accredited laboratory via polarized light microscopy. As with any similar survey of this nature, actual conditions exist only at the precise locations from which samples were collected. Certain inferences are based on the results of this sampling and related testing to form a professional opinion of conditions in areas beyond those from which the samples were collected. It is also understood that this is a limited survey so that it is possible that concealed materials may be present that were not accessible to us. No other warranty, expressed or implied, is made.
H&P assumes no responsibility regarding response actions initiated as a result of our findings; nor liability for the duties and responsibilities of the Client or building owner with respect to compliance with applicable regulations. Compliance with regulations are the responsibility of the Client or building owner in accordance with local, state, and/or federal requirements.
Closing
Should you have any questions please feel free to call me at (540) 521-1008 or via email at gwhitt@handp.com. It was a pleasure working with you on this project and I hope we can be of service to you in the future.
Sincerely, HURT & PROFFITT, INC
Gregory L. Whitt Mary Beth Wriston Environmental/Industrial Hygiene Manager Environmental/Industrial Hygiene Senior Roanoke Branch Office Roanoke Branch Office
Attachment: Analytical Results Chain of Custody Forms
XRF Data Tables Explanation of XRF Data Tables mailto:gwhitt@handp.com
APPENDIX I
Asbestos Analysis Bulk Report
Chain of Custody Forms
SanAir ID#: 18023648
Project #: 20180509
Project Name: 4th Floor
Report Date: 6/13/2018
Analysis Report prepared for Hurt & Proffitt, Inc.
Dear Roy Wriston, We at SanAir would like to thank you for the work you recently submitted. The 103 sample(s) were received on Wednesday, June 06, 2018 via FedEx. The final report(s) is enclosed for the following sample(s): 531RW01, 531RW02, 531RW03, 531RW04, 531RW06, 531RW07, 531RW08, 531RW09, 531RW10, 531RW11, 531RW12, 531RW13, 531RW14, 531RW15, 531RW16, 531RW17, 531RW18, 531RW19, 531RW20, 531RW21, 531RW22, 531RW23, 531RW24, 531RW25, 531RW26, 531RW27, 531RW28, 531RW29, 531RW30, 531RW31, 531RW32, 531RW33, 531RW34, 531RW35, 531RW36, 531RW37, 531RW38, 531RW39, 531RW40, 531RW41, 531RW42, 531RW43, 531RW44, 531RW45, 531RW46, 531RW47, 531RW48, 531RW49, 531RW50, 531RW51, 531RW52, 531RW53, 531RW54, 531RW55, 531RW56, 531RW57, 531RW58, 531RW59, 531RW60, 531RW61, 531RW62, 531RW63, 531RW64, 531RW65, 531RW66, 531RW67, 531RW68, 531RW69, 531RW70, 531RW71, 531RW72, 531RW73, 531RW74, 531RW75, 61RW01, 61RW02, 61RW03, 61RW04, 61RW05, 61RW06, 61RW07, 61RW08, 61RW09, 61RW10, 61RW11, 61RW12, 61RW13, 61RW14, 61RW15, 61RW16, 61RW17, 61RW18, 61RW19, 61RW20, 61RW21, 61RW22, 61RW23, 61RW24, 61RW25, 61RW26, 61RW27, 61RW28, 61RW29.
These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information
Sample conditions:
- 103 samples in Good condition.
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
434-841-3893 (c)Phone:
Analyst: Steiner, Tara | Moore, Brandi | Fleming, Christopher | Wilson, Johnathan | Pisula, Nicholas
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW01 / 18023648-001
Room 126
Grey Fibrous
Homogeneous
95% Min. Wool 5% Other None Detected
531RW02 / 18023648-002
Room 130
Grey Fibrous
Homogeneous
95% Min. Wool 5% Other None Detected
531RW03 / 18023648-003
Room 107
Grey Fibrous
Homogeneous
95% Min. Wool 5% Other None Detected
531RW04 / 18023648-004
Room 126
White Fibrous
Homogeneous
70% Cellulose 10% Glass
20% Other None Detected
531RW06 / 18023648-005
Room 107
White Fibrous
Homogeneous
60% Cellulose 20% Glass
20% Other None Detected
531RW07 / 18023648-006
Room 126, Drywall
White Non-Fibrous
Homogeneous
3% Cellulose 97% Other None Detected
531RW07 / 18023648-006
Room 126, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW07 / 18023648-006
Room 126, Texture
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW08 / 18023648-007
Room 130, Drywall
White Non-Fibrous
Homogeneous
3% Cellulose 97% Other None Detected
531RW08 / 18023648-007
Room 130, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW08 / 18023648-007
Room 130, Texture
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW09 / 18023648-008
Hallway By Room 112, Drywall
White Non-Fibrous
Homogeneous
3% Cellulose 97% Other None Detected
531RW09 / 18023648-008
Hallway By Room 112, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW10 / 18023648-009
Room 126, Insulation
Yellow Fibrous
Homogeneous
97% Glass 3% Other None Detected
531RW10 / 18023648-009
Room 126, Wrap
Various Fibrous
Heterogeneous
60% Cellulose 10% Glass
30% Other None Detected
531RW10 / 18023648-009
Room 126, Mastic
Beige Non-Fibrous
Homogeneous
5% Wollastonite 95% Other None Detected
531RW11 / 18023648-010
Room 125, Insulation
Yellow Fibrous
Homogeneous
97% Glass 3% Other None Detected
531RW11 / 18023648-010
Room 125, Wrap
Various Fibrous
Heterogeneous
60% Cellulose 10% Glass
30% Other None Detected
531RW11 / 18023648-010
Room 125, Mastic
Beige Non-Fibrous
Homogeneous
5% Wollastonite 95% Other None Detected
531RW12 / 18023648-011
Hallway By Room 112, Insulation
Yellow Fibrous
Homogeneous
97% Glass 3% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW12 / 18023648-011
Hallway By Room 112, Mastic
White Non-Fibrous
Homogeneous
5% Wollastonite 95% Other None Detected
531RW13 / 18023648-012
Room 126
Beige Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
531RW14 / 18023648-013
Hallway By Room 112, Insulation
Yellow Fibrous
Homogeneous
97% Glass 3% Other None Detected
531RW14 / 18023648-013
Hallway By Room 112, Wrap
Various Fibrous
Heterogeneous
60% Cellulose 10% Glass
30% Other None Detected
531RW14 / 18023648-013
Hallway By Room 112, Mastic
White Non-Fibrous
Homogeneous
5% Wollastonite 95% Other None Detected
531RW15 / 18023648-014
Room 125
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW16 / 18023648-015
Room 125 Bathroom, Drywall
Beige Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
531RW16 / 18023648-015
Room 125 Bathroom, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW17 / 18023648-016
Room 135, Drywall
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
531RW17 / 18023648-016
Room 135, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW17 / 18023648-016
Room 135, Texture
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW18 / 18023648-017
Room 103, Drywall
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
531RW18 / 18023648-017
Room 103, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW18 / 18023648-017
Room 103, Texture
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW19 / 18023648-018
Room 126 Bathroom
White Fibrous
Heterogeneous
50% Cellulose 50% Other None Detected
531RW20 / 18023648-019
Room 135, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
531RW20 / 18023648-019
Room 135, Insulation
Yellow Fibrous
Homogeneous
98% Glass 2% Other None Detected
531RW21 / 18023648-020
Room 107
Cream Non-Fibrous
Homogeneous
40% Cellulose 60% Other None Detected
531RW22 / 18023648-021
Room 126
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW23 / 18023648-022
Room 103
White Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW24 / 18023648-023
Room 116
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW25 / 18023648-024
Room 126, Floor Tile
Cream Non-Fibrous
Homogeneous
100% Other None Detected
531RW25 / 18023648-024
Room 126, Mastic
Tan Non-Fibrous
Homogeneous
100% Other None Detected
531RW26 / 18023648-025
Room 133, Floor Tile
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW26 / 18023648-025
Room 133, Mastic
Black Non-Fibrous
Homogeneous
100% Other None Detected
531RW27 / 18023648-026
Room 103, Floor Tile
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW27 / 18023648-026
Room 103, Mastic
Black Non-Fibrous
Homogeneous
100% Other None Detected
531RW28 / 18023648-027
Room 126
Off-White Non-Fibrous
Heterogeneous
100% Other None Detected
531RW29 / 18023648-028
Room 103
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW30 / 18023648-029
Hallway Near Break Room
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW31 / 18023648-030
Room 126
Grey Non-Fibrous
Homogeneous
100% Other None Detected
531RW32 / 18023648-031
Room 125
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW33 / 18023648-032
Room 124
White Non-Fibrous
Heterogeneous
100% Other None Detected
531RW34 / 18023648-033
Room 125, Cover
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW34 / 18023648-033
Room 125, Insulation
Yellow Fibrous
Homogeneous
98% Glass 2% Other None Detected
531RW35 / 18023648-034
Room 103, Mastic
Cream Non-Fibrous
Homogeneous
100% Other None Detected
531RW35 / 18023648-034
Room 103, Insulation
Yellow Fibrous
Homogeneous
98% Glass 2% Other None Detected
531RW36 / 18023648-035
Room 103
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
531RW37 / 18023648-036
Room 130
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW38 / 18023648-037
Room 130
Brown Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW39 / 18023648-038
Room 129, Mastic
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW39 / 18023648-038
Room 129, Insulation
Pink Fibrous
Homogeneous
98% Glass 2% Other None Detected
531RW40 / 18023648-039
Room 139, Mastic
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW40 / 18023648-039
Room 139, Insulation
Yellow Fibrous
Homogeneous
98% Glass 2% Other None Detected
531RW41 / 18023648-040
Hallway By Room 112, Wrap
Various Fibrous
Heterogeneous
60% Cellulose 10% Glass
30% Other None Detected
531RW41 / 18023648-040
Hallway By Room 112, Mastic
Off-White Non-Fibrous
Homogeneous
3% Wollastonite 97% Other None Detected
531RW42 / 18023648-041
Room 117, Plaster
Grey Non-Fibrous
Homogeneous
100% Other None Detected
531RW42 / 18023648-041
Room 117, Skim Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW43 / 18023648-042
Room 117, Plaster
Grey Non-Fibrous
Homogeneous
100% Other None Detected
531RW43 / 18023648-042
Room 117, Skim Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW44 / 18023648-043
Room 117, Plaster
Grey Non-Fibrous
Homogeneous
100% Other None Detected
531RW44 / 18023648-043
Room 117, Skim Coat
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW45 / 18023648-044
Room 117
Tan Non-Fibrous
Homogeneous
100% Other None Detected
531RW46 / 18023648-045
Room 117, Tile
Grey Non-Fibrous
Homogeneous
100% Other None Detected
531RW46 / 18023648-045
Room 117, Mastic
Tan Non-Fibrous
Homogeneous
100% Other None Detected
531RW46 / 18023648-045
Room 117, Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW47 / 18023648-046
Room 117
Grey Non-Fibrous
Homogeneous
100% Other None Detected
531RW48 / 18023648-047
Hallway Near Break Room, Drywall
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
531RW48 / 18023648-047
Hallway Near Break Room, Texture
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW49 / 18023648-048
Break Room, Drywall
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW49 / 18023648-048
Break Room, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW49 / 18023648-048
Break Room, Texture
White Non-Fibrous
Homogeneous
100% Other None Detected
531RW50 / 18023648-049
Break Room
Off-White Non-Fibrous
Homogeneous
5% Cellulose 5% Glass
90% Other None Detected
531RW51 / 18023648-050
Hallway, Tile
Aqua Non-Fibrous
Homogeneous
100% Other None Detected
531RW51 / 18023648-050
Hallway, Mastic
Black Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
531RW52 / 18023648-051
Hallway, Tile
Aqua Non-Fibrous
Homogeneous
100% Other None Detected
531RW52 / 18023648-051
Hallway, Mastic
Black Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
531RW53 / 18023648-052
Hallway, Tile
Aqua Non-Fibrous
Homogeneous
100% Other None Detected
531RW53 / 18023648-052
Hallway, Mastic
Black Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
531RW54 / 18023648-053
Break Room, Tile
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW54 / 18023648-053
Break Room, Mastic
Tan Non-Fibrous
Homogeneous
2% Cellulose 98% Other None Detected
531RW55 / 18023648-054
Drug/ Medicine Room, Tile
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW55 / 18023648-054
Drug/ Medicine Room, Mastic
Tan Non-Fibrous
Homogeneous
2% Cellulose 98% Other None Detected
531RW56 / 18023648-055
Drug/ Medicine Room, Tile
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW56 / 18023648-055
Drug/ Medicine Room, Mastic
Tan Non-Fibrous
Homogeneous
2% Cellulose 98% Other None Detected
531RW57 / 18023648-056
Room 132, Cove Base
Grey Non-Fibrous
Homogeneous
100% Other None Detected
531RW57 / 18023648-056
Room 132, Mastic
Yellow Non-Fibrous
Homogeneous
2% Cellulose 98% Other None Detected
531RW58 / 18023648-057
Room 108, Carpet
Off-White Fibrous
Homogeneous
85% Synthetic 15% Other None Detected
531RW58 / 18023648-057
Room 108, Pad/Glue
Various Non-Fibrous
Heterogeneous
< 1% Cellulose 100% Other None Detected
531RW59 / 18023648-058
Mechanical Room, Insulation
Yellow Fibrous
Homogeneous
95% Glass 5% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW59 / 18023648-058
Mechanical Room, Mastic
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW60 / 18023648-059
Mechanical Room, Insulation
Yellow Fibrous
Homogeneous
95% Glass 5% Other None Detected
531RW60 / 18023648-059
Mechanical Room, Mastic
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW61 / 18023648-060
Mechanical Room, Insulation
Yellow Fibrous
Homogeneous
95% Glass 5% Other None Detected
531RW61 / 18023648-060
Mechanical Room, Mastic
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW62 / 18023648-061
Mechanical Room, Insulation
Yellow Fibrous
Homogeneous
95% Glass 5% Other None Detected
531RW62 / 18023648-061
Mechanical Room, Wrap
White Fibrous
Homogeneous
50% Cellulose 50% Other None Detected
531RW63 / 18023648-062
Mechanical Room, Insulation
Yellow Fibrous
Homogeneous
95% Glass 5% Other None Detected
531RW63 / 18023648-062
Mechanical Room, Mastic
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW64 / 18023648-063
Mechanical Room, Insulation
Yellow Fibrous
Homogeneous
95% Glass 5% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW64 / 18023648-063
Mechanical Room, Mastic
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW65 / 18023648-064
Mechanical Room, Insulation
Yellow Fibrous
Homogeneous
95% Glass 5% Other None Detected
531RW65 / 18023648-064
Mechanical Room, Wrap
White Fibrous
Homogeneous
50% Cellulose 50% Other None Detected
531RW66 / 18023648-065
Mechanical Room, Insulation
Yellow Fibrous
Homogeneous
95% Glass 5% Other None Detected
531RW66 / 18023648-065
Mechanical Room, Wrap
White Fibrous
Homogeneous
50% Cellulose 50% Other None Detected
531RW67 / 18023648-066
Mechanical Room
Tan Non-Fibrous
Homogeneous
100% Other None Detected
531RW68 / 18023648-067
Mechanical Room, Insulation
Yellow Fibrous
Homogeneous
95% Glass 5% Other None Detected
531RW68 / 18023648-067
Mechanical Room, Mastic
Off-White Non-Fibrous
Homogeneous
100% Other None Detected
531RW69 / 18023648-068
Mechanical Room
Black Non-Fibrous
Homogeneous
20% Glass 80% Other None Detected
531RW70 / 18023648-069
Mechanical Room, Cover
Various Fibrous
Heterogeneous
65% Cellulose 15% Glass
20% Other None Detected
Analyst:
Analysis Date: 6/13/2018 Date: 6/13/2018
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
20180509Project Number:
20180509P.O. Number:
Project Name: 4th Floor
5/31/2018 - 6/1/2018Collected Date:
6/6/2018 10:20:00 AMReceived Date:
6/13/2018 4:29:50 PM
18023648 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
531RW70 / 18023648-069
Mechanical Room, Insulation
Yellow Non-Fibrous
Homogeneous
98% Glass 2% Other None Detected
531RW71 / 18023648-070
Mechanical Room
Brown Non-Fibrous
Homogeneous
100% Other None Detected
531RW72 / 18023648-071
Mechanical…
This is the start of the file's text. The full file is on GovTribe.