20180509R1 BES-SVAMC Bldg. 143 4th Floor Limited Hazardous Materials Survey Report.pdf

PDF 2 MB Posted

Attached to
Y1DA--Renovate for Patient Privacy - Wing J (VA-20-00044784)
Solicitation number
36C24620R0119
Issued by

About this file

This document contains the results of a limited hazardous materials survey conducted at the Salem Veterans Affairs Medical Center in Salem, Virginia. One hundred and eighty-five samples of suspect asbestos containing materials were collected from patient rooms and support areas in Buildings 143 H and J wings and submitted for laboratory analysis. No asbestos was detected in any of the materials sampled. However, some materials such as concealed pipe insulation should be presumed positive for asbestos unless subsequently tested. The report provides guidance on regulatory requirements for handling asbestos containing materials under the National Emission Standards for Hazardous Air Pollutants and Occupational Safety and Health Administration regulations during any renovation or demolition work.

The related federal contract opportunity is to renovate patient privacy areas in Wing J of the Salem Veterans Affairs Medical Center under solicitation number 36C24620R0119 as part of project 658-18-101. The solicitation from the Department of Veterans Affairs seeks offers for renovations that will involve materials identified in the hazardous materials survey report. Offerors must consider any asbestos abatement or special handling needs based on the survey results.

View the file

Other files

File Type Posted
36C24620R0119 0005_1.docx DOCX document
36C24620R0119 0005.pdf PDF
36C24620R0119 0004.pdf PDF
36C24620R0119 0004_1.docx DOCX document
36C24620R0119 0003.pdf PDF
36C24620R0119 0003_1.docx DOCX document
102800-Toilet Bath and Laundry Accessories.pdf PDF
36C24620R0119 0002_1.docx DOCX document
S02 RFI Questions.pdf PDF
S06 36C24620R0119 0002.pdf PDF
36C24620R0119 0001_1.docx DOCX document
S04 Site Visit sign-in for Renovate Patient Privacy 8-5-2020.pdf PDF
PROPOSAL ITEM LIST 8-7-2020.pdf PDF
Plumbing B Drawing.pdf PDF
Plumbing C Drawing.pdf PDF
Plumbing E Drawing.pdf PDF
Mechanical Drawing.pdf PDF
Structural Drawing.pdf PDF
Plumbing A Drawing.pdf PDF
Plumbing D Drawing.pdf PDF
S02 36C24620R0119.pdf PDF
Interior Design Drawing.pdf PDF
Equipment Drawing.pdf PDF
Electrical A Drawing.pdf PDF
Fire Protection Drawing.pdf PDF
General Drawing.pdf PDF
658-18-101_SPECS.pdf PDF
Electrical B Drawing.pdf PDF
36C24620R0119_2.docx DOCX document
VA20200172 05-29-2020 Wage Determination.pdf PDF
Architectural Drawing.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5238 VALLEYPOINTE PARKWAY

SUITE 2B, BUILDING C

ROANOKE, VA 24019

800-242-4906 TOLL FREE

540-521-1008 MAIN

www.HandP.com

ENGINEERING • SURVEYING • PLANNING • ENVIRONMENTAL • GIS

HURT & PROFFITT

Inspired | Responsive | Trusted

Original Issue: June 15, 2018 Revised Issue: August 12, 2020

BES Design/Build LLC 766 Middle Street Fairhope, Alabama 36532

Attention: Richard F. Holihan and Katie Sharples Phone: 843.522.2094 Email: rholihan@besbeaufort.com, ksharpless@besdesignbuild.com

Subject: Limited Hazardous Materials Survey Building 143, 4th Floor 1970 Roanoke Boulevard Salem, Virginia H&P Project 20180509

Mr. Holihan, Hurt & Proffitt, Inc. (H&P) was requested to conduct sampling of suspect asbestos containing materials (ACM) and lead containing painted building materials and to identify potential mercury and PCB containing components in Building 143 on the 4th Floor at Salem Veterans Affairs Medical Center in Salem, Virginia. The sampling and review was performed by H&P representatives Roy Wriston (Virginia Asbestos Inspector License number is 3303 003648) and Mary Beth Wriston (Virginia Asbestos Inspector License number is 3303 003466) on May 31 and June 1, 2018. The subject site is the 4th floor of Building 143 which houses patient rooms and associated medical support facilities and comprises two separate wings (H and J). The central section was excluded from H&P’s scope of work.

1.0 Asbestos Sampling Procedures and Findings

The intent of the asbestos sampling was to identify asbestos containing materials (ACM) in the effected portions of the building within both wings that could be disturbed by planned renovation work. Materials sampled included floor tiles and associated mastics, drywall, and joint compound, ceiling plasters, ceiling tiles, piping and duct insulations and mastics and vapor barriers located below ceramic tile flooring. We note that this was a limited invasive survey of accessible materials that could be sampled without damaging surfaces and systems components. The areas of focus were occupied during the survey which limited our ability to access and sample all potential concealed materials. If materials are encountered that were not represented during this limited survey; they must be sampled and analyzed for asbestos prior to disturbance.

The survey included collection of one hundred and eighty five (185) individual samples and layers of suspect asbestos containing materials (ACMs) that were submitted for analysis of asbestos. The suspect ACM samples were submitted to SanAir Technologies Laboratory an NVLAP accredited and Virginia licensed asbestos laboratory in Powhatan, Virginia, for analysis by Polarized Light Microscopy (PLM) mailto:rholihan@besbeaufort.com mailto:ksharpless@besdesignbuild.com following EPA Method 600/R-93/116. The analytical results are shown in the following table. Copies of the laboratory Asbestos Analysis Report and Chain of Custody forms are included as an attachment to this report.

Table I – 4th floor H and J Wings Building 143 Salem VAMC – Asbestos Sample Analysis Results

Sample # Sample Location Sample Type Lab Description

Analytical Results

(Estimated %

Asbestos)

4th Floor J Wing

531RW01 Room 126 Fire proofing Grey Fibrous None Detected

531RW02 Room 130 Fire proofing Grey Fibrous None Detected

531RW03 Room 107 Fire proofing Grey Fibrous None Detected

531RW04 Room 126 Fissured 2x4 ceiling tile White Fibrous None Detected

531RW05 Sample Not Submitted

531RW06 Room 107 Fissured 2x4 ceiling tile White Fibrous None Detected

531RW07 Room 126

Partition wall drywall

White Non-Fibrous None Detected

Partition wall joint compound White Non-Fibrous None Detected

Partition wall texture

White Non-Fibrous None Detected

531RW08 Room 130

Partition wall drywall

White Non-Fibrous None Detected

Partition wall joint compound White Non-Fibrous None Detected

Partition wall texture

White Non-Fibrous None Detected

531RW09 Room 112

Partition wall drywall

White Non-Fibrous None Detected

Partition wall joint compound White Non-Fibrous None Detected

531RW10 Room 126

Pipe insulation

Yellow Fibrous None Detected

Pipe wrap Various Fibrous None Detected

Pipe mastic Beige Non-Fibrous None Detected

531RW11 Room 125

Pipe insulation

Yellow Fibrous None Detected

Pipe wrap Various Fibrous None Detected

Pipe mastic Beige Non-Fibrous None Detected

Analytical Results

(Estimated %

Asbestos)

531RW12

Hallway by Room

Pipe insulation

Yellow Fibrous None Detected

Pipe mastic White Non-Fibrous None Detected

531RW13 Room 126

Drywall between metal wall studs

Beige Non-Fibrous None Detected

531RW14

Hallway by Room

Pipe insulation

Yellow Fibrous None Detected

Pipe wrap Various Fibrous None Detected

Pipe mastic White Non-Fibrous None Detected

531RW15 Room 125 Window sill caulk White Non-Fibrous None Detected

531RW16

Room 126 Bathroom

Perimeter Wall

Drywall Beige Non-Fibrous None Detected

Joint compound

White Non-Fibrous None Detected

531RW17

Room 135

Perimeter Wall

Drywall White Non-Fibrous None Detected

Joint compound

White Non-Fibrous None Detected

Texture White Non-Fibrous None Detected

531RW18

Room 103

Perimeter Wall

Drywall White Non-Fibrous None Detected

Joint compound

White Non-Fibrous None Detected

Texture White Non-Fibrous None Detected

531RW19

Room 126 Bathroom

Duct seam tape

White Fibrous None Detected

531RW20 Room 135

Duct seam tape mastic

Yellow Non-Fibrous None Detected

Duct seam insulation

Yellow Fibrous None Detected

531RW21 Room 107 Duct seam tape Cream Non-Fibrous None Detected

531RW22 Room 126 Door frame caulk White Non-Fibrous None Detected

531RW23 Room 103 Door frame caulk White Non-Fibrous None Detected

531RW24 Room 116 Door frame caulk White Non-Fibrous None Detected

531RW25 Room 126

12” White with grey streaks floor tile

Cream Non-Fibrous None Detected

Analytical Results

(Estimated %

Asbestos)

Mastic Tan Non-Fibrous None Detected

531RW26 Room 133

12” White with grey streaks floor tile

Off-White Non-Fibrous None Detected

Mastic Black Non-Fibrous None Detected

531RW27 Room 103

12” White with grey streaks floor tile

Off-White Non-Fibrous None Detected

Mastic Black Non-Fibrous None Detected

531RW28 Room 126 Grey base board mastic Off-White Non-Fibrous None Detected

531RW29 Room 103 Grey base board mastic Off-White Non-Fibrous None Detected

531RW30

Hallway near Break Room

Grey base board mastic

Yellow Non-Fibrous None Detected

531RW31 Room 126 Window caulk Grey Non-Fibrous None Detected

531RW32 Room 125 Window caulk White Non-Fibrous None Detected

531RW33 Room 124 Window caulk White Non-Fibrous None Detected

531RW34 Room 125 Elbow wrap White Non-Fibrous None Detected

Elbow insulation

Yellow Fibrous None Detected

531RW35 Room 103

Yellow duct mastic

Cream Non-Fibrous None Detected

Duct insulation

Yellow Fibrous None Detected

531RW36 Room 103 Yellow mastic on metal duct

Yellow Non-Fibrous None Detected

531RW37 Room 130 2x4 white ceiling tile

(hard) White Non-Fibrous None Detected

531RW38 Room 130 Fire caulking Brown Non-Fibrous None Detected

531RW39 Room 129 Duct mastic Off-White Non-Fibrous None Detected

Duct insulation

Pink Fibrous None Detected

531RW40 Room 139 Duct mastic Off-White Non-Fibrous None Detected

Analytical Results

(Estimated %

Asbestos)

Duct insulation

Yellow Fibrous None Detected

531RW41

Hallway by Room

Duct wrap Various Fibrous None Detected

Duct mastic Off-White Non-Fibrous None Detected

531RW42 Room 117 Ceiling Plaster-top Grey Non-Fibrous None Detected

Plaster-base White Non-Fibrous None Detected

531RW43 Room 117 Ceiling Plaster-top Grey Non-Fibrous None Detected

Plaster-base White Non-Fibrous None Detected

531RW44 Room 117 Ceiling Plaster-top Grey Non-Fibrous None Detected

Plaster-base White Non-Fibrous None Detected

531RW45 Room 117 Duct mastic Tan Non-Fibrous None Detected

531RW46 Room 117

Wall tile Grey Non-Fibrous None Detected

Wall tile mastic

Tan Non-Fibrous None Detected

Wall tile compound

White Non-Fibrous None Detected

531RW47 Room 117 Door threshold Grey Non-Fibrous None Detected

531RW48

Hallway near Break Room

Partition Wall

Drywall White Non-Fibrous None Detected

Texture White Non-Fibrous None Detected

531RW49

Break Room

Partition Wall

Drywall White Non-Fibrous None Detected

Joint compound

White Non-Fibrous None Detected

Texture White Non-Fibrous None Detected

531RW50 Break Room 2X4 White ceiling tile

Off-White Non-Fibrous None Detected

531RW51 Hallway 12’’ Green floor tile

Aqua Non-Fibrous None Detected

Mastic Black Non-Fibrous None Detected

531RW52 Hallway 12’’ Green floor tile

Aqua Non-Fibrous None Detected

Mastic Black Non-Fibrous None Detected

531RW53 Hallway 12’’ Green floor tile

Aqua Non-Fibrous None Detected

Mastic Black Non-Fibrous None Detected

531RW54 Break Room 12’’ Brown floor tile Off-White Non-Fibrous None Detected

Mastic Tan Non-Fibrous None Detected

531RW55

Drug/Medicine room 12’’ Brown floor tile Off-White Non-Fibrous None Detected

Analytical Results

(Estimated %

Asbestos)

Mastic Tan Non-Fibrous None Detected

531RW56

Drug/Medicine

Room

12’’ brown floor tile

Off-White Non-Fibrous None Detected

Mastic Tan Non-Fibrous None Detected

531RW57 Room 132

Large cove base

Grey Non-Fibrous None Detected

Large cove base mastic

Yellow Non-Fibrous None Detected

531RW58 Room 108 Carpet Off-White Fibrous None Detected

Carpet mastic Various Non-Fibrous None Detected

531RW59 Mechanical Room

6’’ Chilled water supply line insulation

Yellow Fibrous None Detected

Mastic Off-White Non-Fibrous None Detected

531RW60 Mechanical Room Pump box insulation

Yellow Fibrous None Detected

Mastic Off-White Non-Fibrous None Detected

531RW61 Mechanical Room

6” Heating supply line insulation

Yellow Fibrous None Detected

Mastic Off-White Non-Fibrous None Detected

531RW62 Mechanical Room

Square duct insulation

Yellow Fibrous None Detected

Square duct wrap

White Fibrous None Detected

531RW63

Mechanical Room

Chilled Water

Supply valve insulation

Yellow Fibrous None Detected

Supply valve mastic

Off-White Non-Fibrous None Detected

531RW64

Mechanical

Room@ Unit 143- AHU-4j1

Line insulation

Yellow Fibrous None Detected

Line mastic Off-White Non-Fibrous None Detected

531RW65 Mechanical Room

Low pressure steam line insulation

Yellow Fibrous None Detected

Wrap White Fibrous None Detected

531RW66 Mechanical Room Square duct insulation

Yellow Fibrous None Detected

Wrap White Fibrous None Detected

Analytical Results

(Estimated %

Asbestos)

531RW67 Mechanical Room Mastic on unit 143-PF- 4J1

Tan Non-Fibrous None Detected

531RW68 Mechanical Room

Condenser outlet insulation Yellow Fibrous None Detected

Mastic Off-White Non-Fibrous None Detected

531RW69 Mechanical Room Vibration damper cloth Black Non-Fibrous None Detected

531RW70 Mechanical Room Square duct wrap Various Fibrous None Detected

Insulation Yellow Non-Fibrous None Detected

531RW71 Mechanical Room Mastic on unit 143PF- 4J2

Brown Non-Fibrous None Detected

531RW72 Mechanical Room

Vibration Damper Cloth on Unit 143-

PF-4J2

Black Non-Fibrous None Detected

531RW73 Mechanical Room Elbow near unit 143-PF-

4J2 Yellow Fibrous None Detected

531RW74 Mechanical Room Chilled water line mastic White Non-Fibrous None Detected

Foam Black Non-Fibrous None Detected

531RW75 Mechanical Room Drywall White Non-Fibrous None Detected

Joint compound

White Non-Fibrous None Detected

4th Floor-H Wing

61RW01 Room 110 Fire proofing Grey Fibrous None Detected

61RW02 Room 157 Duct mastic Yellow Non-Fibrous None Detected

61RW03 Room 157 Drywall White Non-Fibrous None Detected

Joint compound

White Non-Fibrous None Detected

61RW04 Room 103A Ceiling tile White Fibrous None Detected

61RW05 Room 103A Window frame caulk White Non-Fibrous None Detected

61RW06 Room 103A Cove base mastic White Non-Fibrous None Detected

61RW07

Room 103 Bathroom

Plaster ceiling base coat

White Non-Fibrous None Detected

Analytical Results

(Estimated %

Asbestos)

Plaster ceiling skim coat

White Non-Fibrous None Detected

61RW08 Room 104

Patch material on piping-wrap

Tan Fibrous None Detected

Patch material on piping-insulation

Yellow Fibrous None Detected

61RW09 Room 113

White duct wrap

Tan Fibrous None Detected

White duct insulation

Yellow Fibrous None Detected

61RW10 Nurses’ Station Textured ceiling tile White Fibrous None Detected

61RW11 Room 127 Drywall White Non-Fibrous None Detected

Joint compound

White Non-Fibrous None Detected

61RW12 Room 127 White ceiling tile (hard) White Non-Fibrous None Detected

61RW13 Room 127

Sealant on wall around piping Grey Non-Fibrous None Detected

Wrap Various Fibrous None Detected

61RW14 Room 127

12’’ White with grey streaks floor tile

White Non-Fibrous None Detected

Mastic Black Non-Fibrous None Detected

61RW15 Room 131

Yellow mastic on pipe

Off-White Non-Fibrous None Detected

Pipe wrap Various Fibrous None Detected

Pipe insulation

Brown Fibrous None Detected

61RW16 Room 131 12’’ Pink floor tile Pink Non-Fibrous None Detected

Mastic Black Non-Fibrous None Detected

61RW17 Hallway

12’’ Pink floor tile

Pink Non-Fibrous None Detected

Mastic Black Non-Fibrous None Detected

Leveling compound

Off-White Non-Fibrous None Detected

Analytical Results

(Estimated %

Asbestos)

61RW18 Hallway

12’’ Pink floor tile

Pink Non-Fibrous None Detected

Mastic Black Non-Fibrous None Detected

Leveling compound

Off-White Non-Fibrous None Detected

61RW19 Break Room 12’’ Brown floor tile White Non-Fibrous None Detected

Mastic Yellow Non-Fibrous None Detected

61RW20 Mechanical Room

White duct mastic

White Non-Fibrous None Detected

White duct wrap

Various Fibrous None Detected

White duct glue

Brown Non-Fibrous None Detected

White duct insulation

Yellow Fibrous None Detected

61RW21 Mechanical Room

Glycol line mastic

White Non-Fibrous None Detected

Wrap Various Fibrous None Detected

Insulation Yellow Fibrous None Detected

61RW22 Mechanical Room Brown duct mastic on metal duct

Brown Non-Fibrous None Detected

61RW23 Mechanical Room

Chilled water supply line mastic Off-White Non-Fibrous None Detected

Wrap Various Fibrous None Detected

Insulation Yellow Fibrous None Detected

61RW24 Mechanical Room

Line mastic at Unit 143-JC-

4H1 White Non-Fibrous None Detected

Wrap Various Fibrous None Detected

Insulation Yellow Fibrous None Detected

61RW25 Mechanical Room White duct mastic Various Fibrous None Detected

Insulation Yellow Fibrous None Detected

61RW26 Mechanical Room Chilled water supply elbow

Grey Non-Fibrous None Detected

61RW27 Room 136

Drywall White Non-Fibrous None Detected

Joint compound

White Non-Fibrous

None Detected

Analytical Results

(Estimated %

Asbestos)

4th Floor-J Wing

61RW28 Room 117

Top layer of flooring-tile

Grey Non-Fibrous None Detected

Top layer of flooring-felt

Off-White Fibrous None Detected

Top layer of flooring-mortar

Grey Non-Fibrous None Detected

61RW29 Room 117 Bottom layer of flooring Tan Non-Fibrous None Detected

None Detected: No Asbestos Detected

2.0 Sample Analysis Results and Recommendations

Based on the results of analysis, asbestos was not detected in the materials sampled during this survey.

2.1 Presumed Asbestos Containing Materials

During the conduct of this survey, sampling was limited to those materials which were within the areas designated by the client, which were safely accessible and which were able to be sampled without damaging systems or structures. As such, some materials should be presumed to be positive, unless sampling is conducted and shown to be negative. Such presumed asbestos containing materials (PACMS) observed at the site include, but are not limited to:

1. Fire Door Interiors;

2. Electrical panel backing;

3. Concealed (above ceilings or within wall chases) piping or ducting insulation, if present.

If materials are encountered during demolition that were not sampled during this limited survey, they must be sampled and analyzed for asbestos by a Virginia licensed Inspector prior to disturbance.

Note 1: If during renovation/demolition, work is performed that will impact suspect materials that have not been sampled, it is recommended that these materials be sampled by a Virginia licensed asbestos inspector prior to disturbance.

Note 2: If asbestos abatement activities are performed within the building, all work should be performed by a Virginia licensed asbestos abatement contractor.

3.0 EPA/NESHAP Regulations for Asbestos Containing Materials

The U.S. Environmental Protection Agency promulgated the National Emission Standards for Hazardous Air Pollutants (NESHAP) [40 CFR Part 61], which addresses the application, removal, and disposal of asbestos-containing materials (ACM). Under NESHAP the following categories are defined for asbestos-containing materials:

Friable - When dry, can be crumbled, pulverized, or reduced to powder by hand pressure.

Non-friable - When dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

Category I Non-friable ACM - Packings, gaskets, resilient floor coverings, and asphalt roofing products containing more than 1% asbestos.

Category II Non-friable ACM – Any material, excluding Category I Non-friable ACM, which contains more than 1% asbestos.

Regulated Asbestos Containing Material (RACM) – One of the following:

1. Friable ACM

2. Category I Non-friable ACM that has become friable.

3. Category I Non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading.

4. Category II Non-friable ACM that has a high probability of becoming, or has become, friable by the forces expected to act on the material in the course of demolition or renovation operations.

Under NESHAP, the following actions are required:

1. Prior to the commencement of demolition or renovation activities, the building owner must inspect the affected facility or part of the facility where the demolition or renovation activities will occur for the presence of asbestos.

2. Remove all RACM from the facility before any activity begins that would break up, dislodge, or similarly disturb the material or preclude access for subsequent removal.

3. RACM need not be removed if:

a) It is Category I non-friable ACM that is not in poor condition.

b) It is on a facility component that is encased in concrete or other similar material and is adequately wet whenever exposed.

c) It was not accessible for testing and was therefore not discovered until after demolition began and because of the demolition the material cannot be safely removed.

d) It is Category II non-friable ACM and the probability is low that the material will become crumbled, pulverized, or reduced to powder during demolition.

Note: Based on our experience, we recommend that all ACM be removed prior to renovation or demolition due to the fact that disturbance can damage them, create potential exposure to workers and occupants and make them friable. This recommendation is made as a best practice to reduce potential exposure and limit liability.

4.0 OSHA

The Occupational Safety and Health Administration (OSHA) regulates employee exposure to asbestos under 29 CFR 1926.1101 and 29 CFR 1926.1001. Work associated with known or suspect asbestos containing materials (ACM), including trace (<1%) levels of asbestos, must be conducted according to these regulations in addition to the noted EPA regulations where applicable.

If the materials that have been identified as asbestos containing will be disturbed or are in poor condition, it is recommended that the asbestos be removed by an appropriately trained and licensed asbestos abatement contractor in accordance with Virginia, EPA and OSHA regulations.

If work is performed that will impact suspect materials that have not been sampled, it is recommended that they be sampled by a Virginia licensed Asbestos Inspector prior to disturbance. We note that during renovation or demolition activities, it is not uncommon to reveal materials that were not accessible during the survey or their presence could not otherwise be known.

5.0 Lead Containing Paint Testing Procedures

Testing for lead in paint was performed by sampling representative materials and components using a Niton XLp-300A X-Ray Fluorescence (XRF) Lead Paint Analyzer. The XRF contains a small radioactive source (Cadmium 109) which emits radiation when exposed to a surface. If the paint contains lead, the radiation will stimulate the lead atoms to emit characteristic x-rays, which are sensed by a detector in the unit. The XRF then converts these signals to a final reading in milligrams of lead per square centimeter of surface area tested (mg/cm2). Calibration of the Analyzer was conducted in accordance with the manufacturer’s instructions using standard reference materials with different lead concentrations. The Analyzer must indicate readings within the acceptable calibration range for the average of three readings.

If the average of the three readings is within the established tolerance, the unit is working properly.

Calibration checks were performed prior to and at the end of the testing. The XRF is able to accurately detect as little as 0.1 mg/cm2 of lead; the action level used during this survey. Any readings that registered a detectable level of lead with the XRF range are considered as “lead containing” for the purposes of this survey. Where components tested below the designated action level of 0.1 mg/cm² for classifying the material as lead containing; it is important to note that any painted or coated surface may contain concentrations of lead, which when disturbed, could generate lead in dust greater than the action level exposure concentration of 30 ug/m3 established by the OSHA “Lead Exposure in Construction Rule”

(29 CFR 1926.62).

5.1 Lead In Paint Testing Results

A total of seventy two (72) XRF readings, including calibrations, were collected from painted or surface coated building materials. Tested materials and components included:

Walls;

Windows and casing;

Door and door casing;

Ceiling;

Cabinets;

5.2 Lead In Paint Findings

The purpose of the screening was to identify painted surfaces and surface coatings that may contain lead at concentrations above the comparative standard. Based on the results of XRF testing, lead containing paint was not identified above the survey action level in the building materials tested.

6.0 Regulatory Compliance for Lead

H&P recommends that the contractor adhere to all applicable EPA regulations regarding disposal requirements and OSHA regulations for employee exposure.

6.1 OSHA Regulations

Where components tested below the designated action level of 1.0 mg/cm² for classifying the material as lead based paint (LBP), it is important to note that any painted or coated surface may contain concentrations of lead, which when disturbed, could generate lead in dust greater than the action level exposure concentration of 30 ug/m3 established by the OSHA “Lead Exposure in Construction Rule” (29 CFR 1926.62). The OSHA standard gives no guidance on acceptable levels of lead in coatings at which no exposure to airborne lead (above the action level) would be expected; however, OSHA defines airborne concentrations and lists specific work practices which may create a lead hazard. Therefore, personnel exposure monitoring should be performed during any removal or demolition process to establish worker exposure levels which can be used to determine appropriate personnel protection and environmental controls for the specific work practice and material type. In accordance with OSHA requirements, the Contractor performing the work will be required to conduct this monitoring.

6.2 EPA Regulations

For disposal of construction/demolition debris that have lead, the EPA requires the generator perform testing for lead content of the waste stream to determine proper disposal in accordance with the requirements of 40 CFR 261.11, Criteria for Listing Hazardous Waste.

7.0 PCB Containing Components

7.1 Methodology

During our site visit, H&P was accompanied by SVAMC facility staff who told us that just prior to our survey, they completed a lighting upgrade on the wings of the 4th floor. H&P visually reviewed accessible areas of the wings of the floor to check for electrical transformers, gear boxes, light ballasts and other components that could contain polychlorinated biphenyls (PCBs). Based on our review and the understanding that a lighting upgrade had recently been completed, obvious PCB containing ballasts and other components were not observed.

7.2 Results and Recommendations

H&P did not observe suspect PCB containing components in the areas that could be accessed for viewing.

However based on the age of the building, there could be concealed components that could contain PCB’s that may be revealed during demolition for renovation. If encountered, the component should be reviewed and assessed prior to disturbance. If found, PCB should be properly disposed following all applicable local, state and federal regulations.

8.0 Mercury Containing Thermostats, Switches and other Components

8.1 Methodology

H&P visually reviewed accessible areas of the floor wings to check for suspect mercury containing components including thermostats, switches, fluorescent lamps, mercury vapor lamps, and other components.

8.2 Results and Recommendations

H&P did not observe obvious mercury containing thermostats, switches, lighting or other components.

However various light bulbs were noted that could contain mercury, including newer fluorescent bulbs that do contain low levels. H&P recommends that these various components be reviewed at the time of removal and if found to contain mercury, be properly disposed following all applicable local, state and federal regulations. Mercury containing waste components are considered as hazardous waste materials in the Commonwealth of Virginia and should be handled accordingly.

9.0 Other Miscellaneous Materials

Medical waste collection containers are present in rooms throughout the project area. These containers should be emptied by qualified personnel and the contents disposed per established facility procedures prior to being disturbed during renovation work.

Other materials of an environmental concern that could require special handling and disposal were not observed in the areas reviewed during this survey.

10.0 Limitations

This report summarizes the results of our sample collection and analysis of the suspect ACM and lead in paint testing and review for other materials of concern based on our understanding of the requested scope of work. The findings prepared by H&P are based upon our observations and the analytical analysis of the samples collected at the time of our field inspection. The services performed were provided in accordance with generally accepted environmental industry standard practices. No warranty, expressed or implied, is made. Our observations, conclusions and recommendations are based upon conditions readily visible at the site at the time of our visit, the results of testing and analysis and information provided to us by others.

Our conclusions and recommendations are based on the guidelines presented by the EPA, Commonwealth of Virginia and OSHA. Any conditions discovered which deviate from the data contained in this report should be presented to us for our evaluation. This report has been prepared for the exclusive use of the client and/or their agents. This service was performed in accordance with generally accepted environmental practices. Our conclusions and recommendations are based, in part, upon information provided to us by others; we have not verified the completeness or accuracy of the information provided by others, unless otherwise noted.

During H&P’s non-invasive inspection, accessible areas were visually surveyed for the presence of ACM,.

Areas reviewed were limited to those identified by the Client and that could be readily and safely accessed. Our conclusions and recommendations are based on the results of our testing and cannot be used to form a professional opinion of conditions in other areas beyond those from which the samples were collected. It is possible that inaccessible areas, such as behind walls or above ceilings, may not have been surveyed and therefore conditions in these areas are unknown.

During this study, suspect asbestos samples were submitted for analysis at an NVLAP-accredited laboratory via polarized light microscopy. As with any similar survey of this nature, actual conditions exist only at the precise locations from which samples were collected. Certain inferences are based on the results of this sampling and related testing to form a professional opinion of conditions in areas beyond those from which the samples were collected. It is also understood that this is a limited survey so that it is possible that concealed materials may be present that were not accessible to us. No other warranty, expressed or implied, is made.

H&P assumes no responsibility regarding response actions initiated as a result of our findings; nor liability for the duties and responsibilities of the Client or building owner with respect to compliance with applicable regulations. Compliance with regulations are the responsibility of the Client or building owner in accordance with local, state, and/or federal requirements.

Closing

Should you have any questions please feel free to call me at (540) 521-1008 or via email at gwhitt@handp.com. It was a pleasure working with you on this project and I hope we can be of service to you in the future.

Sincerely, HURT & PROFFITT, INC

Gregory L. Whitt Mary Beth Wriston Environmental/Industrial Hygiene Manager Environmental/Industrial Hygiene Senior Roanoke Branch Office Roanoke Branch Office

Attachment: Analytical Results Chain of Custody Forms

XRF Data Tables Explanation of XRF Data Tables mailto:gwhitt@handp.com

APPENDIX I

Asbestos Analysis Bulk Report

Chain of Custody Forms

SanAir ID#: 18023648

Project #: 20180509

Project Name: 4th Floor

Report Date: 6/13/2018

Analysis Report prepared for Hurt & Proffitt, Inc.

Dear Roy Wriston, We at SanAir would like to thank you for the work you recently submitted. The 103 sample(s) were received on Wednesday, June 06, 2018 via FedEx. The final report(s) is enclosed for the following sample(s): 531RW01, 531RW02, 531RW03, 531RW04, 531RW06, 531RW07, 531RW08, 531RW09, 531RW10, 531RW11, 531RW12, 531RW13, 531RW14, 531RW15, 531RW16, 531RW17, 531RW18, 531RW19, 531RW20, 531RW21, 531RW22, 531RW23, 531RW24, 531RW25, 531RW26, 531RW27, 531RW28, 531RW29, 531RW30, 531RW31, 531RW32, 531RW33, 531RW34, 531RW35, 531RW36, 531RW37, 531RW38, 531RW39, 531RW40, 531RW41, 531RW42, 531RW43, 531RW44, 531RW45, 531RW46, 531RW47, 531RW48, 531RW49, 531RW50, 531RW51, 531RW52, 531RW53, 531RW54, 531RW55, 531RW56, 531RW57, 531RW58, 531RW59, 531RW60, 531RW61, 531RW62, 531RW63, 531RW64, 531RW65, 531RW66, 531RW67, 531RW68, 531RW69, 531RW70, 531RW71, 531RW72, 531RW73, 531RW74, 531RW75, 61RW01, 61RW02, 61RW03, 61RW04, 61RW05, 61RW06, 61RW07, 61RW08, 61RW09, 61RW10, 61RW11, 61RW12, 61RW13, 61RW14, 61RW15, 61RW16, 61RW17, 61RW18, 61RW19, 61RW20, 61RW21, 61RW22, 61RW23, 61RW24, 61RW25, 61RW26, 61RW27, 61RW28, 61RW29.

These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.

Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory

Final Report Includes:

- Cover Letter

- Analysis Pages

- Disclaimers and Additional Information

Sample conditions:

- 103 samples in Good condition.

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

434-841-3893 (c)Phone:

Analyst: Steiner, Tara | Moore, Brandi | Fleming, Christopher | Wilson, Johnathan | Pisula, Nicholas

Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW01 / 18023648-001

Room 126

Grey Fibrous

Homogeneous

95% Min. Wool 5% Other None Detected

531RW02 / 18023648-002

Room 130

Grey Fibrous

Homogeneous

95% Min. Wool 5% Other None Detected

531RW03 / 18023648-003

Room 107

Grey Fibrous

Homogeneous

95% Min. Wool 5% Other None Detected

531RW04 / 18023648-004

Room 126

White Fibrous

Homogeneous

70% Cellulose 10% Glass

20% Other None Detected

531RW06 / 18023648-005

Room 107

White Fibrous

Homogeneous

60% Cellulose 20% Glass

20% Other None Detected

531RW07 / 18023648-006

Room 126, Drywall

White Non-Fibrous

Homogeneous

3% Cellulose 97% Other None Detected

531RW07 / 18023648-006

Room 126, Joint Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW07 / 18023648-006

Room 126, Texture

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW08 / 18023648-007

Room 130, Drywall

White Non-Fibrous

Homogeneous

3% Cellulose 97% Other None Detected

531RW08 / 18023648-007

Room 130, Joint Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW08 / 18023648-007

Room 130, Texture

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW09 / 18023648-008

Hallway By Room 112, Drywall

White Non-Fibrous

Homogeneous

3% Cellulose 97% Other None Detected

531RW09 / 18023648-008

Hallway By Room 112, Joint Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW10 / 18023648-009

Room 126, Insulation

Yellow Fibrous

Homogeneous

97% Glass 3% Other None Detected

531RW10 / 18023648-009

Room 126, Wrap

Various Fibrous

Heterogeneous

60% Cellulose 10% Glass

30% Other None Detected

531RW10 / 18023648-009

Room 126, Mastic

Beige Non-Fibrous

Homogeneous

5% Wollastonite 95% Other None Detected

531RW11 / 18023648-010

Room 125, Insulation

Yellow Fibrous

Homogeneous

97% Glass 3% Other None Detected

531RW11 / 18023648-010

Room 125, Wrap

Various Fibrous

Heterogeneous

60% Cellulose 10% Glass

30% Other None Detected

531RW11 / 18023648-010

Room 125, Mastic

Beige Non-Fibrous

Homogeneous

5% Wollastonite 95% Other None Detected

531RW12 / 18023648-011

Hallway By Room 112, Insulation

Yellow Fibrous

Homogeneous

97% Glass 3% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW12 / 18023648-011

Hallway By Room 112, Mastic

White Non-Fibrous

Homogeneous

5% Wollastonite 95% Other None Detected

531RW13 / 18023648-012

Room 126

Beige Non-Fibrous

Homogeneous

5% Cellulose 95% Other None Detected

531RW14 / 18023648-013

Hallway By Room 112, Insulation

Yellow Fibrous

Homogeneous

97% Glass 3% Other None Detected

531RW14 / 18023648-013

Hallway By Room 112, Wrap

Various Fibrous

Heterogeneous

60% Cellulose 10% Glass

30% Other None Detected

531RW14 / 18023648-013

Hallway By Room 112, Mastic

White Non-Fibrous

Homogeneous

5% Wollastonite 95% Other None Detected

531RW15 / 18023648-014

Room 125

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW16 / 18023648-015

Room 125 Bathroom, Drywall

Beige Non-Fibrous

Homogeneous

5% Cellulose 95% Other None Detected

531RW16 / 18023648-015

Room 125 Bathroom, Joint Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW17 / 18023648-016

Room 135, Drywall

White Non-Fibrous

Homogeneous

5% Cellulose 95% Other None Detected

531RW17 / 18023648-016

Room 135, Joint Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW17 / 18023648-016

Room 135, Texture

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW18 / 18023648-017

Room 103, Drywall

White Non-Fibrous

Homogeneous

5% Cellulose 95% Other None Detected

531RW18 / 18023648-017

Room 103, Joint Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW18 / 18023648-017

Room 103, Texture

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW19 / 18023648-018

Room 126 Bathroom

White Fibrous

Heterogeneous

50% Cellulose 50% Other None Detected

531RW20 / 18023648-019

Room 135, Mastic

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

531RW20 / 18023648-019

Room 135, Insulation

Yellow Fibrous

Homogeneous

98% Glass 2% Other None Detected

531RW21 / 18023648-020

Room 107

Cream Non-Fibrous

Homogeneous

40% Cellulose 60% Other None Detected

531RW22 / 18023648-021

Room 126

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW23 / 18023648-022

Room 103

White Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW24 / 18023648-023

Room 116

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW25 / 18023648-024

Room 126, Floor Tile

Cream Non-Fibrous

Homogeneous

100% Other None Detected

531RW25 / 18023648-024

Room 126, Mastic

Tan Non-Fibrous

Homogeneous

100% Other None Detected

531RW26 / 18023648-025

Room 133, Floor Tile

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW26 / 18023648-025

Room 133, Mastic

Black Non-Fibrous

Homogeneous

100% Other None Detected

531RW27 / 18023648-026

Room 103, Floor Tile

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW27 / 18023648-026

Room 103, Mastic

Black Non-Fibrous

Homogeneous

100% Other None Detected

531RW28 / 18023648-027

Room 126

Off-White Non-Fibrous

Heterogeneous

100% Other None Detected

531RW29 / 18023648-028

Room 103

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW30 / 18023648-029

Hallway Near Break Room

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW31 / 18023648-030

Room 126

Grey Non-Fibrous

Homogeneous

100% Other None Detected

531RW32 / 18023648-031

Room 125

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW33 / 18023648-032

Room 124

White Non-Fibrous

Heterogeneous

100% Other None Detected

531RW34 / 18023648-033

Room 125, Cover

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW34 / 18023648-033

Room 125, Insulation

Yellow Fibrous

Homogeneous

98% Glass 2% Other None Detected

531RW35 / 18023648-034

Room 103, Mastic

Cream Non-Fibrous

Homogeneous

100% Other None Detected

531RW35 / 18023648-034

Room 103, Insulation

Yellow Fibrous

Homogeneous

98% Glass 2% Other None Detected

531RW36 / 18023648-035

Room 103

Yellow Non-Fibrous

Homogeneous

100% Other None Detected

531RW37 / 18023648-036

Room 130

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW38 / 18023648-037

Room 130

Brown Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW39 / 18023648-038

Room 129, Mastic

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW39 / 18023648-038

Room 129, Insulation

Pink Fibrous

Homogeneous

98% Glass 2% Other None Detected

531RW40 / 18023648-039

Room 139, Mastic

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW40 / 18023648-039

Room 139, Insulation

Yellow Fibrous

Homogeneous

98% Glass 2% Other None Detected

531RW41 / 18023648-040

Hallway By Room 112, Wrap

Various Fibrous

Heterogeneous

60% Cellulose 10% Glass

30% Other None Detected

531RW41 / 18023648-040

Hallway By Room 112, Mastic

Off-White Non-Fibrous

Homogeneous

3% Wollastonite 97% Other None Detected

531RW42 / 18023648-041

Room 117, Plaster

Grey Non-Fibrous

Homogeneous

100% Other None Detected

531RW42 / 18023648-041

Room 117, Skim Coat

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW43 / 18023648-042

Room 117, Plaster

Grey Non-Fibrous

Homogeneous

100% Other None Detected

531RW43 / 18023648-042

Room 117, Skim Coat

White Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW44 / 18023648-043

Room 117, Plaster

Grey Non-Fibrous

Homogeneous

100% Other None Detected

531RW44 / 18023648-043

Room 117, Skim Coat

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW45 / 18023648-044

Room 117

Tan Non-Fibrous

Homogeneous

100% Other None Detected

531RW46 / 18023648-045

Room 117, Tile

Grey Non-Fibrous

Homogeneous

100% Other None Detected

531RW46 / 18023648-045

Room 117, Mastic

Tan Non-Fibrous

Homogeneous

100% Other None Detected

531RW46 / 18023648-045

Room 117, Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW47 / 18023648-046

Room 117

Grey Non-Fibrous

Homogeneous

100% Other None Detected

531RW48 / 18023648-047

Hallway Near Break Room, Drywall

White Non-Fibrous

Homogeneous

5% Cellulose 95% Other None Detected

531RW48 / 18023648-047

Hallway Near Break Room, Texture

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW49 / 18023648-048

Break Room, Drywall

White Non-Fibrous

Homogeneous

5% Cellulose 95% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW49 / 18023648-048

Break Room, Joint Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW49 / 18023648-048

Break Room, Texture

White Non-Fibrous

Homogeneous

100% Other None Detected

531RW50 / 18023648-049

Break Room

Off-White Non-Fibrous

Homogeneous

5% Cellulose 5% Glass

90% Other None Detected

531RW51 / 18023648-050

Hallway, Tile

Aqua Non-Fibrous

Homogeneous

100% Other None Detected

531RW51 / 18023648-050

Hallway, Mastic

Black Non-Fibrous

Homogeneous

5% Cellulose 95% Other None Detected

531RW52 / 18023648-051

Hallway, Tile

Aqua Non-Fibrous

Homogeneous

100% Other None Detected

531RW52 / 18023648-051

Hallway, Mastic

Black Non-Fibrous

Homogeneous

5% Cellulose 95% Other None Detected

531RW53 / 18023648-052

Hallway, Tile

Aqua Non-Fibrous

Homogeneous

100% Other None Detected

531RW53 / 18023648-052

Hallway, Mastic

Black Non-Fibrous

Homogeneous

5% Cellulose 95% Other None Detected

531RW54 / 18023648-053

Break Room, Tile

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW54 / 18023648-053

Break Room, Mastic

Tan Non-Fibrous

Homogeneous

2% Cellulose 98% Other None Detected

531RW55 / 18023648-054

Drug/ Medicine Room, Tile

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW55 / 18023648-054

Drug/ Medicine Room, Mastic

Tan Non-Fibrous

Homogeneous

2% Cellulose 98% Other None Detected

531RW56 / 18023648-055

Drug/ Medicine Room, Tile

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW56 / 18023648-055

Drug/ Medicine Room, Mastic

Tan Non-Fibrous

Homogeneous

2% Cellulose 98% Other None Detected

531RW57 / 18023648-056

Room 132, Cove Base

Grey Non-Fibrous

Homogeneous

100% Other None Detected

531RW57 / 18023648-056

Room 132, Mastic

Yellow Non-Fibrous

Homogeneous

2% Cellulose 98% Other None Detected

531RW58 / 18023648-057

Room 108, Carpet

Off-White Fibrous

Homogeneous

85% Synthetic 15% Other None Detected

531RW58 / 18023648-057

Room 108, Pad/Glue

Various Non-Fibrous

Heterogeneous

< 1% Cellulose 100% Other None Detected

531RW59 / 18023648-058

Mechanical Room, Insulation

Yellow Fibrous

Homogeneous

95% Glass 5% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW59 / 18023648-058

Mechanical Room, Mastic

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW60 / 18023648-059

Mechanical Room, Insulation

Yellow Fibrous

Homogeneous

95% Glass 5% Other None Detected

531RW60 / 18023648-059

Mechanical Room, Mastic

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW61 / 18023648-060

Mechanical Room, Insulation

Yellow Fibrous

Homogeneous

95% Glass 5% Other None Detected

531RW61 / 18023648-060

Mechanical Room, Mastic

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW62 / 18023648-061

Mechanical Room, Insulation

Yellow Fibrous

Homogeneous

95% Glass 5% Other None Detected

531RW62 / 18023648-061

Mechanical Room, Wrap

White Fibrous

Homogeneous

50% Cellulose 50% Other None Detected

531RW63 / 18023648-062

Mechanical Room, Insulation

Yellow Fibrous

Homogeneous

95% Glass 5% Other None Detected

531RW63 / 18023648-062

Mechanical Room, Mastic

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW64 / 18023648-063

Mechanical Room, Insulation

Yellow Fibrous

Homogeneous

95% Glass 5% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW64 / 18023648-063

Mechanical Room, Mastic

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW65 / 18023648-064

Mechanical Room, Insulation

Yellow Fibrous

Homogeneous

95% Glass 5% Other None Detected

531RW65 / 18023648-064

Mechanical Room, Wrap

White Fibrous

Homogeneous

50% Cellulose 50% Other None Detected

531RW66 / 18023648-065

Mechanical Room, Insulation

Yellow Fibrous

Homogeneous

95% Glass 5% Other None Detected

531RW66 / 18023648-065

Mechanical Room, Wrap

White Fibrous

Homogeneous

50% Cellulose 50% Other None Detected

531RW67 / 18023648-066

Mechanical Room

Tan Non-Fibrous

Homogeneous

100% Other None Detected

531RW68 / 18023648-067

Mechanical Room, Insulation

Yellow Fibrous

Homogeneous

95% Glass 5% Other None Detected

531RW68 / 18023648-067

Mechanical Room, Mastic

Off-White Non-Fibrous

Homogeneous

100% Other None Detected

531RW69 / 18023648-068

Mechanical Room

Black Non-Fibrous

Homogeneous

20% Glass 80% Other None Detected

531RW70 / 18023648-069

Mechanical Room, Cover

Various Fibrous

Heterogeneous

65% Cellulose 15% Glass

20% Other None Detected

Analyst:

Analysis Date: 6/13/2018 Date: 6/13/2018

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

20180509Project Number:

20180509P.O. Number:

Project Name: 4th Floor

5/31/2018 - 6/1/2018Collected Date:

6/6/2018 10:20:00 AMReceived Date:

6/13/2018 4:29:50 PM

18023648 SanAir ID Number

FINAL REPORT

Hurt & Proffitt, Inc.Name:

Address: 2524 Langhorne Road

Lynchburg, VA 24501

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

531RW70 / 18023648-069

Mechanical Room, Insulation

Yellow Non-Fibrous

Homogeneous

98% Glass 2% Other None Detected

531RW71 / 18023648-070

Mechanical Room

Brown Non-Fibrous

Homogeneous

100% Other None Detected

531RW72 / 18023648-071

Mechanical…