Fire Protection Drawing.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24620R0119
About this file
This document package includes architectural drawings and specifications for renovations to Patient Wing J at the Department of Veterans Affairs Medical Center in Salem, Virginia. The project involves demolishing existing walls and ceilings, and constructing new patient rooms, bathrooms, offices, and support spaces. Key project details include installing new fire alarm, fire suppression, flooring, casework, and equipment. The scope of work affects Zones 4-2 and 4-3 of the existing sprinkler system. The contract opportunity is solicitation number 36C24620R0119 for project number 658-18-101 to upgrade patient privacy in Wing J, issued by the VA Veterans Health Administration VISN 6. The package provides plans, schedules, sections, and 3D renderings of the proposed renovations.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E
F
G
H
I
J
K
L
7 8 9 10 11 13 8.2
6 12
H.6
MATCH LINE
OFFICE
NURSE MGR
4J-108
MEDICATION
4J-121
EQUIPMENT
STORAGE
4J-109
EQUIPMENT
STORAGE
4J-117
ELECTRICAL
CLOSET
4J-119
IRM
TELEPHONE
4J-106
STAFF TOILET
4J-104
EQUIP
STORAGE
4J-122A
STAFF
LOUNGE
4J-120
DIRTY UTILITY
/ OXYGEN
STORAGE
4J-132
KITCHEN
4J-122B
BPO
4J-138
CLEAN
SUPPLY
4J-122
BATH RM
4J-150A
ON CALL
4J-150
ON CALL
4J-151
BATH RM
4J-142B
ANTE RM
4J-142A
SOCIAL
WORKER
4J-143
BATH RM
4J-141A
BATH RM
4J-139A
BATH RM
4J-136A
PATIENT RM
4J-137
BATH RM
4J-131A
EQUIPMENT
STORAGE
4J-133
GENERAL
STORAGE
4J-127
WHCH BATH
RM
4J-125A
BATH RM
4J-123A
MECH SHAFT
4J-M2
PATIENT RM
4J-114
WHCH BATH
RM
4J-112A
BATH RM
4J-110A
BATH RM
4J-107A
WORK RM
4J-102
MENS
TOILETS
4J-100
WOMENS
TOILET
4J-101
WAITING /
DAY RM
4J-103
PATIENT RM
4J-124
OFFICE
4J-110
PATIENT RM
4J-107
ISOLATION -
PATIENT RM
4J-105
STAIR
S-2
HOUSE
KEEPING
4J-153
ELEVATOR
E-1
ELEVATOR
E-2
ELEVATOR
E-3
SOILED LINEN
4J-155
TRASH
4J-154
ELEVATOR
E-6
ELEVATOR
E-4
ELEVATOR
E-5
ELECTRICAL
4J-156
MALE
LOCKER
4J-146A
FEMALE
LOCKER
4J-146C
BATH RM
4J-146B
LOCKER
4J-147
CONFERENCE
RM
4J-148
STORAGE
4J-148A
FEMALE
TOILET
4J-146D
S ELEVATOR
LOBBY
CJ4-11
LOUNGE
4J-146
PATIENT RM
4J-139
MECH CHILL
4J-145
PATIENT RM
4J-136
PATIENT RM
4J-134
WHCH BATH
RM
4J-134A
PATIENT RM
4J-135
CLEAN LINEN
4J-130
BATH RM
4J-128A
BATH RM
4J-129A
PATIENT RM
4J-129
PATIENT RM
4J-126
PATIENT RM
4J-125
BATH RM
4J-151A
OFFICE
4J-152
DUMP
WAITER 2
4J-D2
BATH RM
4J-105B
PATIENT RM
4J-112
PATIENT RM
4J-113
HAC
4J-116
BATH RM
4J-114A
STAIR
S-1
MECH
RM/SVC BAY
4J-118
CORRIDOR
CJ4-5
ISOLATION
RM
4J-142
PATIENT RM
4J-141
PATIENT RM
4J-131
PATIENT RM
4J-128
PATIENT RM
4J-123
PATIENT RM
4J-115
CORRIDOR
CJ4-13
CORRIDOR
CJ4-1
NURSE
STATION
CJ4-8
CORRIDOR
CJ4-9
CORRIDOR
CJ4-10
NURSE
STATION
CJ4-4
CORRIDOR
CJ4-12
DIETITIAN
4J-144
EQUIPMENT
STORAGE
4J-111
CORRIDOR
CJ4-6
CORRIDOR
CJ4-7
NURSE
STATION
CJ4-4A
NURSE
STATION
CJ4-4B
VIS LOUNGE
CJ4-2
CORRIDOR
CJ4-3
ANTE RM
4J-105A
HEALTH CARE SLEEPING DEPARTMENT
FULLY SPRINKLERED
SP SP
SP
SP
SPSP
SP
SP
SP
SSSS
SS SS
SS
SS
SS
M
M
AI AI
VTWF
DSS
DSS
AR
M
CEILING MOUNTED FIRE ALARM SPEAKER/STROBE
DEVICE KEY
CEILING MOUNTED FIRE ALARM SPEAKER
FIRE ALARM SPEAKER/STROBE
LEGEND
ALARM PRESSURE SWITCH
MANUAL FIRE ALARM BOX
HEAT DETECTOR
SMOKE DETECTOR
FIRE ALARM LIGHT
WATERFLOW SWITCH
MINIMUM CANDELA RATING
(NOTIFICATION APPLIANCES ONLY)
CEILING MOUNTED FIRE ALARM STROBE
N - NEW DEVICE
ED - EXISTING TO BE DELETED
ER - EXISTING TO BE REPLACED
E - EXISTING TO BE RE-USED
L - LOCAL SYSTEM-DO NOT MODIFY
WF
APS
M
SP
SS
L
FIRE ALARM STROBE
N(30)
VALVE TAMPER SWITCH
VT
AR
DSS
DUCT SMOKE DETECTOR SUPPLY
ADDRESSABLE RELAY MODULE
INDICATES EXISTING AREA
OUTSIDE OF PROJECT WORK AREA.
AI
ADDRESSABLE INTERFACE MODULE
EXISTING FIRE ALARM ZONE BOUNDARY
FAD101
1/8" = 1'-0"
FIRE ALARM DEMOLITION PLAN - ZONE J
FIRE ALARM DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
GENERAL NOTES
1. THE AREAS OF WORK FOR MODIFICATIONS TO THE FIRE ALARM
SYSTEM ARE INDICATED ON THIS SHEET.
2. EXISTING SUSPENDED CEILING SYSTEMS THROUGHOUT THE AREA
OF WORK WILL BE REMOVED AND REPLACED. EXISTING CEILING
MOUNTED DEVICES AND APPLIANCES SHALL BE REMOVED OR
TEMPORARILY RELOCATED AS NOTED TO ACCOMMODATE REMOVAL
OF SUSPENDED CEILING SYSTEMS.
3. ALL INITIATING DEVICES AND NOTIFICATION APPLIANCES NOT
INDICATED FOR REMOVAL SHALL BE MAINTAINED IN-SERVICE.
COORDINATE TEMPORARY IMPAIRMENTS WITH THE GENERAL
CONTRACTOR.
4. REFER TO DRAWING FA101 FOR THE NEW LAYOUT FOR EXISTING (TO
REMAIN) AND NEW DEVICES AND APPLIANCES.
5. EXISTING CONDUIT SYSTEMS MAY BE REUSED TO ACCOMMODATE
THE NEW FIRE ALARM SYSTEM LAYOUT SHOWN ON DRAWING FA101.
6. THE SCOPE OF THIS PROJECT INCLUDES DEMOLITION AND
REPLACEMENT OF THE ZONE J AUTOMATIC SPRINKLER PIPING
SYSTEM. THE FIRE ALARM CONTRACTOR SHALL INSTALL TEMPORARY
AREA HEAT DETECTION MONITORED BY THE BUILDING FIRE ALARM
SYSTEM THROUGHOUT THE DEMOLITION AREA DURING THE PERIOD
OF IMPAIRMENT TO THE SPRINKLER SYSTEM. COORDINATE THE
IMPAIRMENT PERIOD WITH THE GENERAL CONTRACTOR.
7. ALL MODIFICATIONS TO THE FIRE ALARM SYSTEM SHALL BE IN
ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM CODE, 2016
EDITION AND SPECIFICATION 28 31 00.
KEYED NOTES
TEMPORARILY REMOVE EXISTING SMOKE DETECTOR AND REINSTALL IN
NEW CEILING.
KEY PLAN
PLAN
NORTH
J o n e e i g h t h i n c o e f o t t h r e e i n c h e s o t o n e a d a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Date
Project No.
Drawing No.
Location
REVISED CONSTRUCTION DOCUMENTS
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy Engineer
Approved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
A
M
Sheet of
DESIGN/BUILD
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
90Revisions: Date:
RENOVATE FOR PATIENT
PRIVACY - ZONE J
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
J UPGRADES 12-4-2019
SRMJAS
12/04/2019
ZONE
HEALTH CARE SLEEPING DEPARTMENT
FULLY SPRINKLERED
MENS
TOILETS (NIC)
WOMENS
TOILET (NIC)
HOUSE
ELEVATOR
SOILED LINEN
(NIC)
TRASH (NIC)
ELEVATOR
(NIC)
ELEVATOR
(NIC)
TEAM
SHARED
CONSULT #2
/FLEX
MECH CHILL
(NIC)
BATH RM
(NIC)
SOCIAL
WORKERS
WORKSTATION
(2 STATIONS)
CORRIDOR
(NIC)
CORRIDOR
(NIC)
BATH RM
(NIC)
ON CALL (NIC)
WAITING (NIC)
CORRIDOR
(NIC)
GENERAL
STORAGE
(NIC)
ON CALL (NIC)
CONFERENCE
RM (NIC)
FLEX OFFICE
ELEVATOR
(NIC)
CORRIDOR
(NIC)
E-1
S ELEVATOR
LOBBY (NIC)
C4-11
BATH RM
POSITIVE
ISOLATION
RM
4J-107
NURSE
STATION
CJ4-4
EXIST MECH
RM/SVC BAY
4J-118
EXIST ELECT
4J-119
STAIR (NIC)
S-1
BATH RM
4J-113A
BATH RM
4J-112A
PATIENT RM
4J-112
PATIENT RM
4J-111
PATIENT RM
4J-110
ANTE RM
4J-105A
NEGATIVE
BARIATRIC
RM
4J-105
SOCIAL
WORKERS
WORKSTATION
4J-103
PATIENT RM
4J-113
EXIST HKPG
4J-116
BATH RM
4J-142B
STORAGE 1
4J-114
PATIENT RM
4J-115
BATH RM
4J-115A
BATH RM
4J-123A
PATIENT RM
4J-128
BATH RM
4J-126A
PATIENT RM
4J-126
PATIENT RM
4J-125
BATH RM
4J-125A
BATH RM
4J-128A
BATH RM
4J-131A
BATH RM
4J-135A
BATH RM
4J-134A
PATIENT RM
4J-134
BATH RM
4J-136A
PATIENT RM
4J-137
BATH RM
4J-137A
BATH RM
4J-139A
PATIENT RM
4J-139
PATIENT RM
4J-131
BATH RM
4J-130A
BARIATRIC
RM
4J-130
BATH RM
4J-105B
PATIENT RM
4J-136
PATIENT RM
4J-129
BATH RM
4J-129A
CART /
STRETCHER
ALCOVE
4J-124
PATIENT RM
4J-135
CORRIDOR
CJ4-3B
CORRIDOR
CJ4-7
CORRIDOR
CJ4-9
CORRIDOR
CJ4-6
NURSE
STATION
CJ4-8B
SUPPLY
STORAGE
4J-141
LOUNGE
4J-121
LOCKERS
4J-121B
TLT 1
4J-120A
TLT 2
4J-120B
T E
L E
M
J
ASST NURSE
MANAGER
4J-108
NURSE
MANAGER
4J-109
NOURISH
4J-120
NUTRITIONIST
OFFICE
4J-117
CRASH
MOBILE
CARTS X-RAY
4J-140
LINEN
4J-104
MED GAS
4J-122
EX. IT
4J-106
HALLWAY
CJ4-5
CORRIDOR
CJ4-10
NURSE
STATION
CJ4-8C
NURSE
STATION
CJ4-8A
L I M
I T
S
O
F
C O
N S
T R
U C
T I O
N
STORAGE 3
4J-144
NEGATIVE
ISOLATION
RM
4J-142
PHARMACIST
OFFICE
4J-160
OMNI
4J-143
UTILITY
SOILED
4J-133
UTILITY
CLEAN
4J-132
STORAGE 2
4J-127B
LINEN
4J-159
OMNI
4J-114B
STORAGE 4
4J-145
ANTE RM
4J-107A
BATH RM
4J-107B
BATH RM
4J-111A
MECH SHAFT
4J-M1
PATIENT RM
4J-123
ANTE RM
4J-142A
STOR. 5
4J-127A
1HR1HR1HR
H
R
H
R
H R
H
R
H R
H
R
H R
2HR2HR
H
R
H R
H
R
H R
H
R
H R
2HR 2HR 2HR
H
R
H R
H
R
H R
H
R
H R
H
R
H R
2HR2HR2HR
H
R
H R
H
R
H R
H
R
H R
H
R
H R
2HR 2HR 2HR
H
R
H R
2HR2HR2HR2HR2HR2HR2HR2HR2HR
H
R
H R
2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR
H
R
S P
S P
SP
S P
S P
SP
S P
S P
S P
SP SP
S P
S P
S P
SPSP
F
S B
F
S B
F
S B
F
S B
F
S B
1FSB 1FSB
1FSB 1FSB
F
S
B
F
S
B
F
S
B
F
S B
F
S B
F
S B
F
S B
H
R
2HR 2HR 2HR 2HR 2HR
H
R
H
R
H R
2HR2HR2HR2HR2HR2HR
H
R H
R
2HR 2HR 2HR 2HR 2HR 2HR
SPSP
S P
SP SP
S P
1HR1HR1HR1HR
H
R
H R
H
R
1HR 1HR 1HR 1HR 1HR
H
R
H R
H
R
SP SP
S P
S P
SPSP
S P
S P
H
R
2HR
H
R
2HR
1HR1HR1HR
H
R
H R
H
R
1HR 1HR 1HR
H
R
H R
H
R
1HR 1HR 1HR 1HR
H
R
1HR1HR1HR1HR
SS
SS
SP
SP
SP
SP
SS
SS
SS
SS
M
M
AR
DSS
FA101
1/8" = 1'-0"
FIRE ALARM PLAN - WING J
FIRE ALARM PLAN
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
GENERAL NOTES
1. THIS DRAWING INDICATES GENERAL LAYOUT FOR NEW AND EXISTING
FIRE ALARM DEVICES AND APPLIANCES. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR DETERMINING EXACT LOCATIONS.
2. EXISTING CIRCUITRY AND CONDUIT SYSTEMS SHALL BE MODIFIED FOR
A COMPLETE OPERATING SYSTEM. ALL FIRE ALARM CIRCUITRY SHALL
BE INSTALLED IN CONDUIT.
3. ALL NEW FIRE ALARM STROBES SHALL BE RATED AT THE CANDELLA
NOTED.
4. ALL NEW FIRE ALARM SPEAKERS SHALL BE TAPPED AT 1/2 WATT
UNLESS NOTED OTHERWISE.
5. ALL MODIFICATIONS TO THE FIRE ALARM SYSTEM SHALL BE IN
ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM CODE, 2019
EDITION AND SPECIFICATION 28 31 00.
KEYED NOTES
NEW SUPPLY DUCT SMOKE DETECTION AND SHUTDOWN CONTROL FOR NEW
AIR HANDLER AHU J-1. INSTALL CONTROL RELAY WITHIN 36 INCHES OF UNIT
CONTROLLER.
AREA SMOKE DETECTION FOR STORAGE OPEN TO CORRIDOR.
INSTALL NEW SMOKE DETECTOR FOR DOOR RELEASE FUNCTION. PROGRAM
FOR EXISTING DOOR RELEASE ARRANGEMENT. RE-USE EXISTING RELEASING
CONTROL DEVICES AND DOOR MAGNETS.
MANUAL PULL STATION SHALL BE LOCATED AT 48 INCHES ABOVE FINISHED
FLOOR.
LOCATION OF EXISTING DISTRIBUTED POWER SUPPLY NAC 13. NAC 13 SERVES
ALL EXISTING VISIBLE NOTIFICATION APPLIANCE CIRCUITS LOCATED ON THIS
FLOOR.
o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Date
Project No.
Drawing No.
Location
REVISED CONSTRUCTION DOCUMENTS
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy Engineer
Approved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
A
M
Sheet of
DESIGN/BUILD
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
90Revisions: Date:
RENOVATE FOR PATIENT
PRIVACY - ZONE J
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
J UPGRADES 12-4-2019
CEILING MOUNTED FIRE ALARM SPEAKER/STROBE
DEVICE KEY
CEILING MOUNTED FIRE ALARM SPEAKER
FIRE ALARM SPEAKER/STROBE
LEGEND
ALARM PRESSURE SWITCH
MANUAL FIRE ALARM BOX
HEAT DETECTOR
SMOKE DETECTOR
FIRE ALARM LIGHT
WATERFLOW SWITCH
MINIMUM CANDELA RATING
(NOTIFICATION APPLIANCES ONLY)
CEILING MOUNTED FIRE ALARM STROBE
N - NEW DEVICE
ED - EXISTING TO BE DELETED
ER - EXISTING TO BE REPLACED
E - EXISTING TO BE RE-USED
L - LOCAL SYSTEM-DO NOT MODIFY
WF
APS
M
SP
SS
L
FIRE ALARM STROBE
N(30)
VALVE TAMPER SWITCH
VT
AR
DSS
DUCT SMOKE DETECTOR SUPPLY
ADDRESSABLE RELAY MODULE
INDICATES EXISTING AREA
OUTSIDE OF PROJECT WORK AREA.
AI
ADDRESSABLE INTERFACE MOSUDLE
2 HOUR FIRE RATED BARRIER
2HR 2HR
1HR 1HR
1 HOUR FIRE RATED BARRIER
SP SP
SMOKE PARTITION
1FSB 1FSB
1 HOUR FIRE RATED SMOKE BARRIER
NEW FIRE ALARM ZONE BOUNDARY
KEY PLAN
PLAN
NORTH
J
SRMJAS
E
F
G
H
I
J
K
L
7 8 9 10 11 13 8.2
6 12
H.6
OFFICE
NURSE MGR
4J-108
MEDICATION
4J-121
EQUIPMENT
STORAGE
4J-109
EQUIPMENT
STORAGE
4J-117
ELECTRICAL
CLOSET
4J-119
IRM
TELEPHONE
4J-106
STAFF TOILET
4J-104
EQUIP
STORAGE
4J-122A
STAFF
LOUNGE
4J-120
DIRTY UTILITY
/ OXYGEN
STORAGE
4J-132
KITCHEN
4J-122B
BPO
4J-138
CLEAN
SUPPLY
4J-122
BATH RM
4J-150A
ON CALL
4J-150
ON CALL
4J-151
BATH RM
4J-142B
ANTE RM
4J-142A
SOCIAL
WORKER
4J-143
BATH RM
4J-141A
BATH RM
4J-139A
BATH RM
4J-136A
PATIENT RM
4J-137
BATH RM
4J-131A
EQUIPMENT
STORAGE
4J-133
GENERAL
STORAGE
4J-127
WHCH BATH
RM
4J-125A
BATH RM
4J-123A
MECH SHAFT
4J-M2
PATIENT RM
4J-114
WHCH BATH
RM
4J-112A
BATH RM
4J-110A
BATH RM
4J-107A
WORK RM
4J-102
MENS
TOILETS
4J-100
WOMENS
TOILET
4J-101
WAITING /
DAY RM
4J-103
PATIENT RM
4J-124
OFFICE
4J-110
PATIENT RM
4J-107
ISOLATION -
PATIENT RM
4J-105
STAIR
S-2
HOUSE
KEEPING
4J-153
ELEVATOR
E-1
ELEVATOR
E-2
ELEVATOR
E-3
SOILED LINEN
4J-155
TRASH
4J-154
ELEVATOR
E-6
ELEVATOR
E-4
ELEVATOR
E-5
ELECTRICAL
4J-156
MALE
LOCKER
4J-146A
FEMALE
LOCKER
4J-146C
BATH RM
4J-146B
LOCKER
4J-147
CONFERENCE
RM
4J-148
STORAGE
4J-148A
FEMALE
TOILET
4J-146D
S ELEVATOR
LOBBY
CJ4-11
LOUNGE
4J-146
PATIENT RM
4J-139
MECH CHILL
4J-145
PATIENT RM
4J-136
PATIENT RM
4J-134
WHCH BATH
RM
4J-134A
PATIENT RM
4J-135
CLEAN LINEN
4J-130
BATH RM
4J-128A
BATH RM
4J-129A
PATIENT RM
4J-129
PATIENT RM
4J-126
PATIENT RM
4J-125
BATH RM
4J-151A
OFFICE
4J-152
DUMP
WAITER 2
4J-D2
BATH RM
4J-105B
PATIENT RM
4J-112
PATIENT RM
4J-113
HAC
4J-116
BATH RM
4J-114A
STAIR
S-1
MECH
RM/SVC BAY
4J-118
CORRIDOR
CJ4-5
ISOLATION
RM
4J-142
PATIENT RM
4J-141
PATIENT RM
4J-131
PATIENT RM
4J-128
PATIENT RM
4J-123
PATIENT RM
4J-115
CORRIDOR
CJ4-13
CORRIDOR
CJ4-1
NURSE
STATION
CJ4-8
CORRIDOR
CJ4-9
CORRIDOR
CJ4-10
NURSE
STATION
CJ4-4
CORRIDOR
CJ4-12
DIETITIAN
4J-144
EQUIPMENT
STORAGE
4J-111
CORRIDOR
CJ4-6
CORRIDOR
CJ4-7
NURSE
STATION
CJ4-4A
NURSE
STATION
CJ4-4B
VIS LOUNGE
CJ4-2
CORRIDOR
CJ4-3
ANTE RM
4J-105A
HEALTH CARE SLEEPING DEPARTMENT
FULLY SPRINKLERED
EXISTING ZONE J (4-3)
SPRINKLER VALVE STATION
2"
2"
2" 2"
2" 2"
ZONE 4-2
ZONE 4-3
2 2 2 2 2
2 2 2 2
WF
VT
EXISTING ZONE (4-2) SPRINKLER VALVE STATION
LEGEND
EXISTING SUPPRESSION PIPING
SPRINKLER SYSTEM BOUNDARY
INDICATES EXISTING AREA OUTSIDE OF
PROJECT WORK AREA.
WF
WATERFLOW SWITCH
VT
VALVE TAMPER SWITCH
EXISTING SUPPRESSION PIPING TO BE REMOVED
FXD101
1/8" = 1'-0"
FIRE SUPPRESSION DEMOLITION PLAN - ZONE J (4-3)
FIRE SUPPRESSION
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
KEYED NOTES
ZONE 4-2. REMOVE EXISTING SPRINKLER AND BRANCH LINE BACK TO CROSS
MAIN. INSTALL THREADED PLUG.
LOCATION OF EXISTING SPRINKLER CONNECTED TO CROSS MAIN TO BE
REMOVED.
GENERAL NOTES
1. THE AREA OF WORK FOR MODIFICATIONS TO THE EXISTING SPRINKLER SYSTEM ARE
INDICATED ON THIS SHEET. THE EXISTING SUSPENDED CEILING SYSTEMS THROUGHOUT THE
AREA OF WORK WILL BE REMOVED AND REPLACED WITH A NEW CEILING SYSTEM.
2. THE LOCATIONS OF SPRINKLER SYSTEM CONTROL VALVES SUPPLYING SPRINKLER ZONES
ARE INDICATED.
3. EXISTING SPRINKLER BRANCH LINES, SPRINKLERS AND ASSOCIATED HANGERS SHALL BE
REMOVED AS INDICATED. THE LOCATION AND SIZE OF ALL PIPING INDICATED TO BE REUSED
SHALL BE FILED VERIFIED BY THE CONTRACTOR.
4. REFER TO DRAWING FX101 FOR THE CONFIGURATION OF NEW ROOMS THROUGHOUT THE
AREA OF WORK.
5. THE CONTRACTOR SHALL CONNECT NEW SPRINKLER BRANCH LINES TO THE EXISTING CROSS
MAIN OUTLETS, OR MODIFY EXISTING SPRINKLER CROSS MAINS, AND INSTALL NEW CEILING
PENDENT SPRINKLER PROTECTION FOR THE NEW ROOM CONFIGURATIONS.
KEY PLAN
PLAN
NORTH
J o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Date
Project No.
Drawing No.
Location
REVISED CONSTRUCTION DOCUMENTS
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy Engineer
Approved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
A
M
Sheet of
DESIGN/BUILD
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
90Revisions: Date:
RENOVATE FOR PATIENT
PRIVACY - ZONE J
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
J UPGRADES 12-4-2019
SRMJAS
MENS
TOILETS (NIC)
WOMENS
TOILET (NIC)
HOUSE
ELEVATOR
SOILED LINEN
(NIC)
TRASH (NIC)
ELEVATOR
(NIC)
ELEVATOR
(NIC)
TEAM
SHARED
CONSULT #2
/FLEX
MECH CHILL
(NIC)
BATH RM
(NIC)
SOCIAL
WORKERS
WORKSTATION
(2 STATIONS)
CORRIDOR
(NIC)
CORRIDOR
(NIC)
BATH RM
(NIC)
ON CALL (NIC)
WAITING (NIC)
CORRIDOR
(NIC)
GENERAL
STORAGE
(NIC)
ON CALL (NIC)
CONFERENCE
RM (NIC)
FLEX OFFICE
ELEVATOR
(NIC)
CORRIDOR
(NIC)
E-1
S ELEVATOR
LOBBY (NIC)
C4-11
BATH RM
E
F
G
H
I
J
K
L
7 8 9 10 11 13 8.2
6 12
H.6
L I M
I T
S
O
F
C O
N S
T R
U C
T I O
N
1HR 1HR 1HR 1HR 1HR 1HR 1HR 1HR 1HR
H
R
H R
H
R
H R
1HR1HR1HR1HR1HR1HR1HR1HR1HR
HEALTH CARE SLEEPING DEPARTMENT
FULLY SPRINKLERED
EXISTING ZONE J SPRINKLER
VALVE STATION
OHI
OHIOHIOHI
OHI
OHI
OHI
OHI
ZONE 4-2
ZONE 4-3
1HR1HR1HR1HR1HR1HR
H
R
H R
H
R H
R H
R
H R
2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR
H
R
H R
H
R
H R
2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
2HR2HR2HR2HR
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
2HR 2HR 2HR 2HR 2HR
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
2HR2HR2HR2HR2HR2HR
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
H R
H
R
2HR 2HR 2HR 2HR 2HR 2HR
H
R H
R H
R
H R
H
R
2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR2HR
H
R
H R
H
R
H R
H
R
2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR
H
R
H R
H
R
H
R
H R
2HR2HR2HR
H
R
H R
2HR 2HR 2HR
H
R
H R
SPSPSPSPSP
S P
S P
S P
SP SP SP SP SP
S P
S P
S P
S P
S P
S P
S P
S P
SPSPSPSP
S P
S P
S P
S P
S P
SP SP SP SP
S P
S P
S P
S P
S P
S P
S P
SP SP SP SP SP
S P
S P
S P
S P
S P
S P
S P
SPSPSPSPSP
F
S B
F
S B
F
S B
F
S B
F
S B
F
S B
F
S B
1FSB
F
S B
F
S B
F
S B
F
S B
1FSB 1FSB 1FSB 1FSB 1FSB
F
S B
1FSB 1FSB 1FSB 1FSB
F
S
B
F
S
B
F
S
B
F
S
B
F
S
B
F
S
B
F
S
B
F
S
B
F
S B
F
S B
F
S B
F
S B
F
S B
F
S B
F
S B
F
S B
H
R
1HR1HR1HR1HR1HR1HR1HR1HR1HR
H
R
H R
H
R
H R
H
R
H R
H
R
1HR 1HR 1HR 1HR 1HR 1HR 1HR 1HR 1HR 1HR
H
R
H R
H
R
H R
H
R
H R
F
S B
F
S B
F
S B
F
S B
F
S B
F
S B
F
S B
F
S B
1FSB
1FSB 1FSB
F
S
B
F
S
B
F
S
B
F
S
B
F
S
B
1FSB 1FSB 1FSB 1FSB 1FSB 1FSB 1FSB
F
S B
H
R
H R
2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR
H
R
H R
SP SP SP SP SP
S P
S P
S P
S P
SPSPSPSPSP
S P
S P
S P
S P
H
R
H R
H
R
2HR2HR
H
R H
R H
R
2HR 2HR
1HR1HR1HR1HR1HR1HR1HR
H
R
H R
H
R
H R
H
R
H R
H
R
1HR 1HR 1HR 1HR 1HR 1HR 1HR
H
R
H R
H
R
H R
H
R
H R
H
R
2"
2"
2" 2"
2" 2"
1 1
1 1
1 1 1 1 1
OHI
PENDENT SPRINKLER ON DROP
SPRINKLER OR DRAIN RISER
LEGEND
PENDENT SIDEWALL SPRINKLER
ISOLATION VALVE
EXISTING SUPPRESSION PIPING
SPRINKLER SYSTEM BOUNDARY
FIRE HOSE CONNECTION
UPRIGHT SPRINKLER
ORDINARY HAZARD GROUP IOHI
SEISMIC BRACE 2 WAY
SEISMIC BRACE 4 WAY
NEW SUPPRESSION PIPING
INDICATES EXISTING AREA OUTSIDE OF
PROJECT WORK AREA.
WF WATERFLOW SWITCH
VT
VALVE TAMPER SWITCH
2 HOUR FIRE RATED BARRIER
2HR 2HR 2HR 2HR
1HR 1HR 1HR 1HR
1 HOUR FIRE RATED BARRIER
SP SP SP SP SP
SMOKE PARTITION
1FSB 1FSB 1FSB 1FSB
1 HOUR FIRE RATED SMOKE BARRIER
FX101
1/8" = 1'-0"
FIRE SUPPRESSION PLAN - ZONE J
FIRE SUPPRESSION PLAN
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
GENERAL NOTES
1. THIS DRAWING INDICATES THE EXISTING SPRINKLER PIPING CROSS
MAINS FOR USE FOR DEVELOPING THE LAYOUT FOR THE NEW ZONE J
SPRINKLER PIPING SYSTEM.
2. THE CONTRACTOR SHALL LAY-OUT AND INSTALL NEW WET PIPE
AUTOMATIC SPRINKLER PROTECTION THROUGHOUT THE AREA OF WORK
INDICATED.
3. SUBMIT COMPLETE NFPA 13 INSTALLATION PLANS AND HYDRAULIC
CALCULATIONS FOR THE SCOPE OF WORK INDICATED.
4. INSTALL NEW SEMI-RECESSED QUICK RESPONSE SPRINKLERS UNLESS
OTHERWISE NOTED. ALL NEW SPRINKLERS SHALL HAVE A WHITE FINISH
UNLESS OTHERWISE NOTED.
5. MINIMUM PIPE SCHEDULE SHALL BE SCHEDULE 10. PLAIN END FITTINGS
ARE NOT PERMITTED. PIPE 2.5 INCHES AND SMALLER SHALL BE
SCHEDULE 40.
6. PIPE AND HANGER SUPPORTS: PROVIDE PIPE SUPPORTS, HANGERS, AND
CLAMPS IN ACCORDANCE WITH NFPA 13.
7. BRANCH LINE OUTLET FITTINGS: USE THREADED OR GROOVED OUTLETS
ONLY.
8. PLAIN END FITTINGS ARE NOT PERMITTED.
9. SEISMIC BRACING PER NFPA 13, 9.3 IS REQUIRED FOR THE ZONE J
SPRINKLER ZONE. THE INSTALLED SEISMIC BRACING, INCLUDING
FLEXIBLE COUPLINGS SHALL BE DEVELOPED BY THE CONTRACTOR AND
SHOWN ON THE SUBMITTAL WORKING PLANS. SPRINKLER BRANCH LINES
SHALL BE PROVIDED WITH RESTRAINT IN ACCORDANCE WITH NFPA 13,
9.3.6. A SEISMIC DESIGN COEFFICIENT OF CP=0.35 SHALL BE USED FOR
THE CALCULATION OF HORIZONTAL SEISMIC LOADS. PROVIDE SEISMIC
CALCULATIONS FOR EACH SEISMIC BRACE IN ACCORDANCE WITH NFPA
13, 9.3.5.9.
10. NEW PENDENT SPRINKLERS SHALL BE INSTALLED WITH UL LISTED AND
FM APPROVED FLEXIBLE SPRINKLER HOSE FITTINGS.
11. THE CONTRACTOR WORKING PLAN DETAILS SHALL INDICATE
MANUFACTURER LISTING AND INSTALLATION REQUIREMENTS FOR
FLEXIBLE SPRINKLER HOSE FITTINGS.
12. ALL FLEXIBLE SPRINKLER HOSE FITTINGS SHALL BE SIZED WITH A
MINIMUM EXTRA LENGTH OF 1 FOOT TO ACCOMMODATE FUTURE
MODIFICATIONS.
13. DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13,
INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION AND
SPECIFICATION 21 13 13.
14. SEE SPECIFICATION 21 13 13 FOR WATER SUPPLY TEST INFORMATION
AND DENSITY DESIGN CRITERIA.
KEYED NOTES
LOCATION OF EXISTING OUTLET FOR CONNECTION OF NEW SPRINKLER.
EXPOSED CEILING AREA. INSTALL UPRIGHT SPRINKLERS. PROVIDE SPRINKLER
COVERAGE BELOW ALL DUCTS 48 INCHES OR WIDER.
EXTEND ZONE 4-2 COVERAGE TO 4J-103. SUPPLY NEW SPRINKLER FROM
ADJACENT ZONE 4-2 BRANCH LINE.
EXTEND ZONE 4-3 SPRINKLER COVERAGE TO ROOM 4J-142, 4J-142A AND
4J-142B.
KEY PLAN
PLAN
NORTH
J o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Date
Project No.
Drawing No.
Location
REVISED CONSTRUCTION DOCUMENTS
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy Engineer
Approved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
A
M
Sheet of
DESIGN/BUILD
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
90Revisions: Date:
RENOVATE FOR PATIENT
PRIVACY - ZONE J
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
J UPGRADES 12-4-2019
SRMJAS
| 1-GI sheets |
| J-GI001 - TITLE SHEET |
| Sheets |
| J-GI001 - TITLE SHEET |
| J-GI002 - PROJECT INFORMATION SHEET |
| Sheets |
| J-GI002 - PROJECT INFORMATION SHEET |
| J-GI003 - PARTITION TYPES - TYPICAL MOUNTING HEIGHTS |
| Sheets |
| J-GI003 - PARTITION TYPES / TYPICAL MOUNTING HEIGHTS |
| J-GI004 - STANDARD ABBREVIATION |
| Sheets |
| J-GI004 - STANDARD ABBREVIATION |
| J-GI005 - EXISTING CONDITIONS - SCOPE OF WORK |
| Sheets |
| J-GI005 - EXISTING CONDITIONS - SCOPE OF WORK |
| J-GI111 - DEPARTAMENTAL USE PLAN - ZONE J |
| Sheets |
| J-GI111 - DEPARTAMENTAL USE PLAN - ZONE J |
| J-GI112 - DEDUCTIVE ALTERNATE #1 |
| Sheets |
| J-GI112 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #1 |
| J-GI113 - DEDUCTIVE ALTERNATE #2 |
| Sheets |
| J-GI113 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #2 |
| J-GI114 - DEDUCTIVE ALTERNATE #3 |
| Sheets |
| J-GI114 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #3 |
| J-GI115- DEDUCTIVE ALTERNATE #4 |
| Sheets |
| J-GI115 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #4 |
| 2-AD sheet |
| Sheets |
| J-AD101 - DEMOLITION FLOOR PLAN - ZONE J |
| J-GI111 - DEPARTAMENTAL USE PLAN - ZONE J |
| 3-AE sheets |
| J-AE101 - NEW FLOOR PLAN - ZONE J |
| Sheets |
| J-AE101 - NEW FLOOR PLAN - ZONE J |
| J-AE102 - NEW WORK ROOF PLAN - ZONE J |
| Sheets |
| J-AE102 - NEW WORK ROOF PLAN - ZONE J |
| J-AE103 - DOOR SCHEDULE & DOOR - FRAME TYPES |
| Sheets |
| J-AE103 - DOOR SCHEDULE & DOOR / FRAME TYPES |
| J-AE111 - REFLECTED CEILING PLAN |
| J-AE111 - REFLECTED CEILING PLAN |
| Sheets |
| J-AE103 - DOOR SCHEDULE & DOOR / FRAME TYPES |
| J-AE111 - REFLECTED CEILING PLAN |
| J-AE301 - BUILDING SECTIONS |
| Sheets |
| J-AE301 - BUILDING SECTIONS |
| J-AE501 - WALL - CEILING DETAILS |
| Sheets |
| J-AE501 - WALL - CEILING DETAILS |
| J-AE502 - ARCHITECTURAL DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE503 - ARCHITECTURAL DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE504 - CASEWORK DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE505 - CASEWORK DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| 4- IN sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN102 - FINISHES SCHEDULES |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN103 - FINISH SELECTIONS |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN202 - SIGNAGE TYPES |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN301 - INTERIOR VIEWS |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| 5- QH sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
File details come from the government source that posted it. Updated .