Architectural Drawing.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24620R0119
About this file
This document package includes architectural drawings and specifications for a renovation project at a Department of Veterans Affairs medical center. The project scope involves renovating patient rooms and support spaces in Zone J to improve patient privacy. Key project details include renovating 13,267 square feet of existing space to include 30 patient rooms, support areas, and associated demolition work. The construction drawings provide floor plans, reflected ceiling plans, building and wall sections, and architectural and casework details. Finishes, furniture, and equipment are specified. Signage and interior views are included. Enlarged plans and elevations provide additional details for selected areas.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DURING DEMOLITION WORK, THE CONTRACTOR MUST KEEP ALL EMERGENCY SYSTEMS ON-LINE AND IN OPERATION INCLUDING THE EXISTING SECURITY SYSTEM, FIRE ALARM, ETC. SEE ADDITIONAL REQUIREMENTS BY MECHANICAL, ELECTRICAL, AND PLUMBING.
THE SCOPE OF DEMOLITION WORK IS DEFINED BY THE EXISTING BUILDING CONSTRUCTION AS WELL AS THE CONTRACTOR'S ON SITE OBSERVATION OF THE EXISTING CONDITIONS. THE CONTRACTOR SHALL REMOVE EVERYTHING IN THE WAY OF NEW CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR DEMOLITION OF ALL ITEMS INDICATED AND AS REQUIRED FOR RENOVATION SHOWN. WALLS AND PARTITIONS SHALL BE REMOVED FULL HEIGHT, UNLESS INDICATED OTHERWISE.
THE ARCHITECT IS NOT RESPONSIBLE FOR COORDINATING DETAILS RELATING TO EXISTING UNKNOWN CONDITIONS. THE GENERAL CONTRACTOR SHALL COORDINATE THE NEW CONSTRUCTION WITH THE EXISTING CONSTRUCTION AND INVESTIGATE AND VERIFY AS NECESSARY REGARDING EXISTING, UNKNOWN CONDITIONS. NO CLAIM FOR EXTRA COMPENSATION WILL BE CONSIDERED DUE TO DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD
SUCH AN EXAMINATION OF THE SITE BEEN MADE.
DEMOLITION WORK IS TO BE COORDINATED WITH THE EXISTING CONDITIONS AND SEQUENCED WITH THE OWNER AND/OR PER THE PROJECT PHASING. WHEN UNFORESEEN CONDITIONS ARE ENCOUNTERED, THE ARCHITECT SHALL BE NOTIFIED AND CONSULTED IF THESE CONDITIONS AFFECT THE NEW DESIGN OR IF THESE CONDITIONS ADVERSELY IMPACT THE
CONSTRUCTION PROGRESS.
ALL EXISTING CONDITIONS THAT ARE TO REMAIN SHALL BE PROTECTED FROM DAMAGE AT ALL TIMES. ANY ITEMS TO REMAIN THAT ARE DAMAGED DURING CONSTRUCTION BY TRADES CONTRACTED TO THE GENERAL CONTRACTOR SHALL BE REPAIRED TO AN ACCEPTABLE LEVEL NOT LESS THAN EQUAL TO THAT PRIOR TO THE DAMAGE AT NO ADDITIONAL COST TO THE OWNER.
ALL DEMOLISHED MATERIALS THAT ARE NOT SPECIFICALLY REQUIRED TO BE REUSED OR MARKED FOR SALVAGE BY THE OWNER SHALL BE REMOVED FROM THE SITE AND DISPOSED OF IN A LEGAL MANNER. THE PROJECT SHALL BE POLICED AND
CLEANED AS REQUIRED EACH DAY.
DUST BARRIERS CONSISTING OF TEMPORARY PARTITIONS SHALL BE PROVIDED, WHERE DETERMINED BY THE CONTRACTOR, TO ELIMINATE ANY AND ALL CONSTRUCTION RELATED DUST OR DEBRIS FROM ENTERING ADJACENT OCCUPIED OR
UNOCCUPIED SPACES THAT ARE TO REMAIN UNTOUCHED, PRIOR TO BEGINNING CONSTRUCTION.
CONTRACTOR SHALL COVER ALL EXISTING IN-PLACE EQUIPMENT TO REMAIN WITH NON-STATIC POLYETHYLENE PRIOR TO BEGINNING CONSTRUCTION IN THAT AREA. PROTECTIVE MEMBRANE SHALL REMAIN IN-PLACE UNTIL CONTRACTOR HAS
COMPLETED ANY CONSTRUCTION WHICH COULD POSSIBLY DAMAGE EXISTING EQUIPMENT.
THE CONTRACTOR SHOULD VERIFY ANY REGULATIONS, LAWS AND/OR ORDINANCES AFFECTING THE METHODS OF DEMOLITION AND THE DISPOSAL OF WASTE MATERIALS. THE OWNER ASSUMES NO LIABILITY FOR EXTRA WORK OR ADDITIONAL COMPENSATION DUE TO FAILURE OF THE CONTRACTOR OR SUBCONTRACTORS TO COMPLY WITH APPLICABLE
REGULATIONS.
REMOVE ALL ABANDONED PIPING, CONDUITS, EXPOSED WIRES AND RELATED APPURTENANCES WHICH WOULD BE EXPOSED ON EXTERIOR, BELOW NEW SOFFIT, ABOVE NEW FLOOR OR THROUGH NEW WALL FINISHES, UNLESS INDICATED OTHERWISE.
G.C. SHALL PATCH AND REPAIR ALL AREAS OF DEMOLITION ADJACENT TO REMAINING SURFACES (INCLUDES WALLS, CEILING, DOORS AND FLOOR SURFACES). CONTRACTOR TO PREPARE SURFACES FOR A UNIFORM, FIRM, SMOOTH SURFACE FOR NEW
FINISHES AS SCHEDULED. INSTALL NEW MATERIAL TO MATCH ADJACENT EXISTING.
SEE STRUCTURAL, PLUMBING, MECHANICAL, AND ELECTRICAL FOR ADDITIONAL DEMOLITION AND DEMOLITION NOTES.17
ALL EXISTING CEILINGS TO BE REMOVED WHERE NEW CEILING ARE SCHEDULED TO BE INSTALLED. SEE REFLECTED CEILING PLAN FOR AREAS WHERE NEW CEILING TO BE INSTALLED. SEE ELECTRICAL FOR EXISTING LIGHTING TO BE SALVAGED AND
REINSTALLED.
WALLS TO BE REMOVED (SEE LEGEND) MUST BE TORN OUT WITH CAUTION. NOTIFY THE ARCHITECT IF EVIDENCE IS FOUND THAT ANY WALL TO BE REMOVED SUPPORTS STRUCTURAL LOADS. WIRING AND PLUMBING FOUND IN WALLS SCHEDULED TO
BE REMOVED SHALL BE REROUTED TO NEW PARTITIONS AS REQUIRED.
PATCH AND REPAIR ALL EXISTING WALLS & FLOORS (MATCH EXISTING SURROUNDING MATERIALS), WHERE OLD CONSTRUCTION, PLUMBING FIXTURES, DUCTS, CABINETRY, ACCESSORIES, ETC. ARE TO BE REMOVED. PROVIDE UNIFORM, FIRM, SMOOTH SURFACE FOR APPLICATION OF NEW FINISHES. SEE FINISH SCHEDULE.
BCAN O TE: SHO WIN G SW INGO F DO UB LE EG RESSD OO RS.D OU BLE EG RESS D OORFR AM EN O TE: SHOW ING THE SWINGO F DO UB LE EG RESSD OO RS.JAMBJAMBSID ESECTIO NS D OU BLE EG RESSD OORS
A B
DOORSTOP(B EYON D)H EAD
P LAN
CDOORBADOOR
C
E
G
H
I
J
8 9 10 11 138.2 12
SMOKE DOORS
1.6
LIMITS OF
CONSTRUCTION
LI
M
IT
S
O F
CO
NS
TR
UC
TI
O
N
F
131313
13131313
13 13
14 14
14 14
141414141414
7 77
777777777
12 12
121212
12 12
8 10
3 3
1 1
1 1
4 5 1
151515
NOT IN
SCOPE OF
WORK
NOT IN
SCOPE OF
WORK
OFFICE
NURSE MGR
4J-108
MEDICATION
4J-121
EQUIPMENT
STORAGE
4J-109
EQUIPMENT
STORAGE
4J-117
ELECTRICAL
CLOSET
4J-119
TELE
4J-106
STAFF TOILET
4J-104
EQUIP
STORAGE
4J-122A
STAFF
LOUNGE
4J-120
DIRTY UTILITY
/ OXYGEN
STORAGE
4J-132
KITCHEN
4J-122B
BPO
4J-138
CLEAN
SUPPLY
4J-122
BATH RM
4J-142B
ANTE RM
4J-142A
SOCIAL
WORKER
4J-143
BATH RM
4J-141A
BATH RM
4J-139A
BATH RM
4J-136A
PATIENT RM
4J-137
BATH RM
4J-131A
EQUIPMENT
STORAGE
4J-133
GENERAL
STORAGE
4J-127
WHCH BATH
RM
4J-125A
BATH RM
4J-123A
MECH RM/SVC
BAY
4J-118
PATIENT RM
4J-114
WHCH BATH
RM
4J-112A
BATH RM
4J-110A
BATH RM
4J-107A
WAITING /
DAY RM
4J-103
PATIENT RM
4J-124
OFFICE
4J-110
PATIENT RM
4J-107
ISOLATION -
PATIENT RM
4J-105
PATIENT RM
4J-139
PATIENT RM
4J-136
PATIENT RM
4J-134
WHCH BATH
RM
4J-134A
PATIENT RM
4J-135
CLEAN LINEN
4J-130
BATH RM
4J-128A
BATH RM
4J-129A
PATIENT RM
4J-126
PATIENT RM
4J-125
BATH RM
4J-105B
PATIENT RM
4J-112
PATIENT RM
4J-113
HAC
4J-116
BATH RM
4J-114A
STAIR
S-1
CORRIDOR
CJ4-5
ISOLATION
RM
4J-142
PATIENT RM
4J-141
PATIENT RM
4J-131
PATIENT RM
4J-128
PATIENT RM
4J-123
CORRIDOR
CJ4-9
CORRIDOR
CJ4-10
NURSE
STATION
CJ4-4
DIETITIAN
4J-144
EQUIPMENT
STORAGE
4J-111
CORRIDOR
CJ4-6
CORRIDOR
CJ4-7
NURSE
STATION
CJ4-4A
NURSE
STATION
CJ4-4B
CORRIDOR
CJ4-3
ANTE RM
4J-105A
PATIENT RM
4J-115
NURSE
STATION
CJ4-8
PATIENT RM
4J-129
EXISTING 2 HR FIRE RATED WALL
EXISTING PARTITION TO BE REMOVED
EXISTING UNRATED PARTITION
LIMITS OF CONSTRUCTION
NOT IN CONTRACT (NIC)
EXISTING 1 HR SMOKE BARRIER
1/8" = 1'-0"
1 DEMOLITION FLOOR PLAN - ZONE J
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AD101
DEMOLITION FLOOR PLAN -
ZONE J
RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
GENERAL DEMOLITION NOTES
GRAPHIC LEGEND
J
KEY PLAN
TRUE
NORTH
H
1. ALL ITEMS SHOWN DASHED INDICATE ITEMS TO BE DEMOLISHED OR SALVAGED. SEE SPECIFIC NOTES BELOW FOR ADDITIONAL INFORMATION. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR ADDITIONAL
DEMOLITION NOTES.
2. ALL OPENINGS AND SURFACES MADE BARE BY DEMOLITION AND/OR REMOVAL OF MATERIALS SHALL BE REPAIRED AND/OR PATCHED TO MATCH ADJACENT FINISH. PREPARE SURFACES TO RECEIVE NEW FINISH(S).
3. CONTRACTOR TO DEVELOP AND PUBLISH INFECTION CONTROL PLAN AND SAFETY PLAN FOR APPROVAL BY COR PRIOR TO BEGINNING THEIR WORK. PLAN SHALL INCLUDE MEANS AND METHODS OF DEBRIS STAGING AND REMOVAL, BOTH INTERNALLY AND EXTERNALLY.
4. INSTALL TEMPORARY DUST AND DEBRIS BARRIERS AND VESTIBULES AROUND PROJECT LIMITS IN ACCORDANCE WITH INFECTON CONTROL PLAN. TEMPORARY BARRIERS ARE NOT TO RESTRICT REQUIRED MEANS OF EGRESS
PATHS AND WIDTHS.
5. NOT USED
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
1 EXISTING STRUCTURE - TO REMAIN; PROTECT DURING DEMO AND NEW
CONSTRUCTION
2 EXISTING EXTERIOR WALL - TO REMAIN; PROTECT DURING DEMO AND NEW
CONSTRUCTION
3 EXISTING INTERIOR WALL - TO REMAIN; PROTECT DURING DEMO AND NEW
CONSTRUCTION
4 EXISTING CONCRETE WALL - TO REMAIN; PROTECT DURING DEMO AND NEW
CONSTRUCTION
5 EXISTING WALL FURRING - TO BE REMOVED
6 EXISTING DOOR & FRAME - TO REMAIN; PROTECT DURING DEMO AND NEW
CONSTRUCTION
7 EXISTING EXT WINDOW - TO REMAIN; PROTECT DURING DEMO AND NEW
CONSTRUCTION
8 EXISTING FLOORING AND BASE - TO BE REMOVED, TYP THROUGHOUT
9 EXISTING FLOORING AND BASE - TO REMAIN, TYP THROUGHOUT; PROTECT
DURING DEMO AND NEW CONSTRUCTION
EXISTING CEILING SYSTEM - TO BE REMOVED, TYP THROUGHOUT;
COORDINATE REMOVAL OF ALL SYSTEMS WITHIN WITH EACH RESPECTIVE
TRADE
11 EXISTING CEILING SYSTEM - TO REMAIN, TYP THROUGHOUT; PROTECT
DURING DEMO AND NEW CONSTRUCTION
12 EXISTING PLUMBING FIXTURE - TO BE REMOVED; REF PLUMBING DEMO
SHEETS
13 EXISTING INT DOOR - TO BE REMOVED
14 EXISTING INT WALL - TO BE REMOVED
REMOVE EXISTING FLOORING AT EXISTING DEPRESSED SLAB AND/OR SLAB.
REPAIR ALL FLOOR, FLOOR SUBSTRATE AND SLAB AND PREP TO RECEIVE
NEW FINISHES.
DEMOLITION SHEET NOTES
Revisions: Date:
BCAN O TE: SHO WIN G SW INGO F DO UB LE EG RESSD OO RS.D OU BLE EG RESS D OORFR AM EN O TE: SHOW ING THE SWINGO F DO UB LE EG RESSD OO RS.JAMBJAMBSID ESECTIO NS D OU BLE EG RESSD OORS
A B
DOORSTOP(B EYON D)H EAD
P LAN
CDOORBADOOR
C
E
G
H
I
J
8 9 10 11 138.2 12
J-AE301
J-AE301
1.6
LI
M
IT
S
O F
CO
NS
TR
UC
TI
O
N
4J-142.2 4J-142.1
4J -1
.1
4J-113.1
4J-115.14J-120
4J -1
4J -1
4J -1
4J -1
4J-117
4J-123.1
4J -1
B
4J -1
A
4J -1
S-1
4J -1
.1
4J -1
.1
4J -1
.14J -1
.1
4J -1
.1
4J -1
.1
4J -1
.1
4J-136.1
4J-137.1
4J-139.1
J-AE301
4J -1
POSITIVE
ISOLATION
RM
4J-107
NURSE
STATION
CJ4-4
EXIST MECH
RM/SVC BAY
4J-118
EXIST ELECT
4J-119
STAIR (NIC)
S-1
BATH RM
4J-113A
BATH RM
4J-112A
PATIENT RM
4J-112
PATIENT RM
4J-111
PATIENT RM
4J-110
ANTE RM
4J-105A
NEGATIVE
BARIATRIC
RM
4J-105
SOCIAL
WORKERS
WORKSTATION
4J-103
PATIENT RM
4J-113
EXIST HKPG
4J-116
BATH RM
4J-142B
STORAGE 1
4J-114
PATIENT RM
4J-115
BATH RM
4J-115A
BATH RM
4J-123A
PATIENT RM
4J-128
BATH RM
4J-126A
PATIENT RM
4J-126
PATIENT RM
4J-125
BATH RM
4J-125A
BATH RM
4J-128A
BATH RM
4J-131A
BATH RM
4J-135A
BATH RM
4J-134A
PATIENT RM
4J-134
BATH RM
4J-136A
PATIENT RM
4J-137
BATH RM
4J-137A
BATH RM
4J-139A
PATIENT RM
4J-139
PATIENT RM
4J-131
BATH RM
4J-130A
BARIATRIC
RM
4J-130
BATH RM
4J-105B
PATIENT RM
4J-136
PATIENT RM
4J-129
BATH RM
4J-129A
CART /
STRETCHER
ALCOVE
4J-124
PATIENT RM
4J-135
CORRIDOR
CJ4-3B
CORRIDOR
CJ4-7
CORRIDOR
CJ4-9
CORRIDOR
CJ4-6
NURSE
STATION
CJ4-8B
SUPPLY
STORAGE
4J-141
LOUNGE
4J-121
LO
C
K
ER
S 4J
-1
B
TLT 1
4J-120A
TLT 2
4J-120B
TE
LE
M 4J
-1
58 ASST NURSE
MANAGER
4J-108
NURSE
MANAGER
4J-109
N O
U R
IS
H
4J -1
NUTRITIONIST
OFFICE
4J-117
CRASH
MOBILE
CARTS X-RAY
4J-140
LINEN
4J-104
MED GAS
4J-122
EX. IT
4J-106
HALLWAY
CJ4-5
CORRIDOR
CJ4-10
NURSE
STATION
CJ4-8C
NURSE
STATION
CJ4-8A
STORAGE 3
4J-144
NEGATIVE
ISOLATION
RM
4J-142
PH
AR
M
AC
IS
T
O
FF
IC
E
4J -1
OMNI
4J-143
14' - 5" 16' - 2" 16' - 4" 16' - 4" 16' - 4" 16' - 4" 16' - 2" 14' - 5"
7'
3"
/2
15' - 9 1/2" 16' - 10" 17' - 6" 15' - 2" 15' - 9 1/2" 14' - 9 1/2"
8' - 0" 8' - 0"
8'
- 0
8'
0"
U
TI
LI
TY
SO
IL
ED
4J
-1
U
TI
LI
TY
C
LE
AN
4J
-1
STORAGE 2
4J-127B
LINEN
4J-159
3'
5" 7'
6"
2'
3"
6'
9" 5'
1/ 2"
8'
0"
OMNI
4J-114B
STORAGE 4
4J-145
4J-116
4J -1
.1
4J -1
4J -1
4J -1
.2
4J -1
.2
4J -1
.3
4J -1
.1
4J-113.2
4J-114
4J-125.2
MECH SHAFT
4J-M1
7' - 3" 23' - 3" 22' - 6" 22' - 6" 22' - 6" 22' - 6" 8' - 0" 5' - 3"
1' - 9" 1' - 9" 1' - 9" 6' - 3"
1'
9" 1'
9"
6'
3" 1'
9"
F
6'
3" 1'
9"
1'
9" 1'
9"
1' - 9"
1' - 9"
20' - 9" 22' - 6" 20' - 9" 1' - 9" 22' - 6" 1' - 9" 6' - 3" 5' - 3"
1'
9"
1'
9"
1'
9" 6'
3"
1' - 9" 22' - 8"
4'
4"
/2
22' - 8" 1' - 9"
6'
8" 6'
1/ 2"
3'
1/
2" 8'
2" 5'
6"
5'
1/
2"
13' - 9" 8' - 1" 9' - 2 1/2" 11' - 8" 8' - 4"
4J-129.2
7'
3" 7'
3"
ANTE RM
4J-107A
BATH RM
4J-107B
BATH RM
4J-111A
4J -1
.1
4J -1
.2
4J-107.3 4J-110.3
4J -1
.1
4J -1
.1
4J-111.2
4J-131.2
4J-135.2
4J-128.2
4J-103
CJ
4-
7'
8" 7'
8"
7'
7'
7'
8"
8'
- 0
ANTE RM
4J-142A
4J -1
.2
D_4A D_4A
K_3
D_4A
B_6A
B_6A
B_6A
D_4A
D_4A
B_6A
D_4AB14B
B_4A
K_2
K_3
K_2
B_4A
B14
B14B
B14 B_4A
B_4A
B_4A
B_6A
K_2
K_2
B_6A
B_4A
4J-118
7'
1/
2" 7'
2"
7'
4J -1
.2
BATH RM
4J-110B
4J -1
.2
4J -1
.2
ST
O
R . 5
4J -1
A
4J-127A
D_4A
B_4A
K_3 D_4A
B_4A
B14
B_4A
B_4A
B14B B_4A
B14B
D_4A
B_4A B_4A K_3
D_4A D_4A
D_4A
K_3
D_4A
K_3
B_4A
B_6A
B14B_4A B_4A
K_3
K_3
D_4A
K_3 B_6A
K_2
K_2
K_3
D_4A
D_4A
B_4A
B_4A
B_4A
B_4A
B_4A
B_4A B_4A
B14
B_4A
K_2
K_3
K_2 K_2
K_3
K_3
K_2
K_2
K_2
K_2
K_3
K_2
B14
K_3
K_4
K_3
B_4A K_3 B_4A
0"
120°
120°
45° 4J-130.2
B_4A
J-AE301
W1
W2
W2
W1
W1W2
TEMPORARY 1 HR
CONSTRUCTION WALL WITH
60 MIN DOOR. SEAL TEMP.
WALL TO STRUCTURAL
ABOVE AND TO ADJACENT
EXISTING WALLS
4J -1
4J -1
4H-100.11 K_3
4H-100.12
B_4A
4H-100.17
B_4A
K_3
6' - 3" 8' - 2" 7' - 6" 8' - 8" 8' - 8" 7' - 8" 7' - 8" 8' - 8" 8' - 8" 7' - 8" 7' - 8" 8' - 8" 8' - 8" 7' - 6" 8' - 2" 6' - 3"
4H-100.24
B_4A
K_3
7' - 3 1/2" 8' - 6" 9' - 2" 7' - 8" 7' - 8" 9' - 10" 7' - 10" 7' - 4" 8' - 8" 7' - 6" 8' - 2" 6' - 3"
J-AE101
Sim
J-AE101
Sim
PATIENT RM
4J-123
J-AE101
Sim
7 1/2" 7 1/2"
13' - 0" 9' - 11"
TY
P
2'
0"
TYP
6"
4' - 6" 5' - 6 1/2" 9' - 1" 9' - 1" 9' - 1" 5' - 1" 8' - 5"
3'
0"
3'
0" 6'
0"
4'
9"
7'
1" 6'
9"
/2
12' - 1" 5' - 3" 6' - 0" 5' - 7"
6' - 0"
1' - 4"
6' - 1" 10' - 5"
1"
/2
3'
4"
1"
1"
/2
1"
/2
1"
/2
8'
0"
2'
6"
3' - 1"
6' - 3"
8'
0"
2'
6" C
LE
AR
5'
0"
10' - 0" 10' - 0"
B_4A
B_4A
NOT IN SCOPE
OF WORK
NOT IN SCOPE
OF WORK
EXISTING WALLS. CONTRACTOR VERIFY
THAT WALL MEET REQUIREMENTS OF A
1 HOUR FIRE/SMOKE BARRIER. SEAL
WALL AT FLOOR AND ROOF DECK
ABOVE. FIRE SEAL ALL OPENINGS. TYP.
EXISTING 1 HR FIRE BARRIER
NEW UNRATED PARTITION
EXISTING UNRATED PARTITION
EXISTING 1 HR SMOKE BARRIER
NEW 1 HR SMOKE BARRIER
NEW 1 HR FIRE BARRIER
EXISTING 2 HR
FIRE BARRIER
LIMITS OF
CONSTRUCTION
NOT IN CONTRACT
(NIC)
ALL EXTERIOR WALLS TO BE REPAIRED AS
REQUIRED FROM REMOVAL OF EXISTING
ADJACENT AND/OR CONNECTED DEMO'D
WALLS. ALL EXISTING WALLS SHALL BE
PREPARED IN THEIR ENTIRETY (FROM
EXISTING FLOOR DECK TO EXISTING ROOF
DECK ABOVE TO RECEIVE NEW FINISHES AS
SCHEDULED. SEE SPECIFICATIONS,
SCHEDULE AND DRAWINGS. ANY INSULATION,
CAULKING AROUND WINDOWS, SEALANTS,
WALL PENETRATIONS, ETC AND RELATED
APPURTENANCES SHALL BE
REPAIRED/REPLACED IF DAMAGED TO
MAINTAIN THE INTENDED FUNCTION OF THE
EXISTING EXTERIOR WALLS AND
RELATED/CONNECTED ELEMENTS.
CONTRACTOR TO VERIFY 3RD FLOOR
BEAM LOCATIONS PRIOR TO
CONSTRUCTION. CONDITIONS IN FIELD
MAY VARY FROM RECORD DRAWINGS.
VERIFY WALL PLACEMENTS AND
PLUMBING FIXTURE / PIPING
PLACEMENT WITH BEAMS BELOW.
FIELD VERIFY
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AE101
NEW FLOOR PLAN - ZONE J RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
1/8" = 1'-0"
1 NEW FLOOR PLAN - ZONE J
ROOM # ROOM NAME AREA
4J-103 SOCIAL WORKERS WORKSTATION 123 SF
4J-104 LINEN 18 SF
4J-105 NEGATIVE BARIATRIC RM 244 SF
4J-105A ANTE RM 71 SF
4J-105B BATH RM 63 SF
4J-106 EX. IT 15 SF
4J-107 POSITIVE ISOLATION RM 279 SF
4J-107A ANTE RM 66 SF
4J-107B BATH RM 57 SF
4J-108 ASST NURSE MANAGER 97 SF
4J-109 NURSE MANAGER 123 SF
4J-110 PATIENT RM 361 SF
4J-110B BATH RM 64 SF
4J-111 PATIENT RM 292 SF
4J-111A BATH RM 61 SF
4J-112 PATIENT RM 262 SF
4J-112A BATH RM 65 SF
4J-113 PATIENT RM 332 SF
4J-113A BATH RM 71 SF
4J-114 STORAGE 1 41 SF
4J-114B OMNI 36 SF
4J-115 PATIENT RM 271 SF
4J-115A BATH RM 96 SF
4J-116 EXIST HKPG 37 SF
4J-117 NUTRITIONIST OFFICE 90 SF
4J-118 EXIST MECH RM/SVC BAY 518 SF
4J-119 EXIST ELECT 56 SF
4J-120 NOURISH 90 SF
4J-120A TLT 1 42 SF
4J-120B TLT 2 34 SF
4J-121 LOUNGE 146 SF
4J-121B LOCKERS 61 SF
4J-122 MED GAS 47 SF
4J-123 PATIENT RM 270 SF
4J-123A BATH RM 96 SF
4J-124 CART / STRETCHER ALCOVE 75 SF
4J-125 PATIENT RM 332 SF
4J-125A BATH RM 71 SF
4J-126 PATIENT RM 262 SF
4J-126A BATH RM 65 SF
4J-127A STOR. 5 26 SF
4J-127B STORAGE 2 20 SF
4J-128 PATIENT RM 308 SF
4J-128A BATH RM 64 SF
4J-129 PATIENT RM 336 SF
4J-129A BATH RM 57 SF
4J-130 BARIATRIC RM 337 SF
4J-130A BATH RM 59 SF
4J-131 PATIENT RM 318 SF
4J-131A BATH RM 64 SF
4J-132 UTILITY CLEAN 108 SF
4J-133 UTILITY SOILED 113 SF
4J-134 PATIENT RM 263 SF
4J-134A BATH RM 65 SF
4J-135 PATIENT RM 332 SF
4J-135A BATH RM 71 SF
4J-136 PATIENT RM 245 SF
4J-136A BATH RM 60 SF
4J-137 PATIENT RM 262 SF
4J-137A BATH RM 60 SF
4J-138 CRASH MOBILE CARTS X-RAY 40 SF
4J-139 PATIENT RM 264 SF
4J-139A BATH RM 60 SF
4J-140 CRASH MOBILE CARTS X-RAY 40 SF
4J-141 SUPPLY STORAGE 157 SF
4J-142 NEGATIVE ISOLATION RM 270 SF
4J-142A ANTE RM 70 SF
4J-142B BATH RM 65 SF
4J-143 OMNI 29 SF
4J-144 STORAGE 3 116 SF
4J-145 STORAGE 4 32 SF
4J-158 TELEM 118 SF
4J-159 LINEN 18 SF
4J-160 PHARMACIST OFFICE 111 SF
4J-M1 MECH SHAFT 27 SF
CJ4-3B CORRIDOR 250 SF
CJ4-4 NURSE STATION 200 SF
CJ4-5 HALLWAY 355 SF
CJ4-6 CORRIDOR 511 SF
CJ4-7 CORRIDOR 574 SF
CJ4-8A NURSE STATION 59 SF
CJ4-8B NURSE STATION 67 SF
CJ4-8C NURSE STATION 56 SF
CJ4-9 CORRIDOR 804 SF
CJ4-10 CORRIDOR 401 SF
13267 SF
NEW WORK AREA SHEDULE - ZONE J
GRAPHIC LEGEND
J
KEY PLAN
TRUE
NORTH
H
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
4J-114 STORAGE 1 41 SF
4J-127B STORAGE 2 20 SF
4J-141 SUPPLY STORAGE 157 SF
4J-144 STORAGE 3 116 SF
4J-145 STORAGE 4 32 SF
365 SF
STORAGE AREA TOTALS
FLOOR PLAN KEYED NOTES
1/8" = 1'-0"
2 3RD FLOOR BEAM LOCATIONS - FIELD VERIFY
E
G
H
I
J
8 9 10 11 138.2 12 1.6
LI
M
IT
S
O F
CO
NS
TR
UC
TI
O
N
F
FOR MECHICAL AND
ROOFING WORK ON ROOF -
SEE MECHANICAL
FOR MECHICAL WORK IN
PENTHOUSE - SEE
MECHANICAL
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AE102
NEW WORK ROOF PLAN -
ZONE J
RENOVATE FOR PATIENT
PRIVACY -
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
J
KEY PLAN
TRUE
NORTH
H
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
1/8" = 1'-0"
1 EXISTING ROOF PLAN - ZONE J
9"
3' -6
1' -0
LOUVER SIZE AS
REQ'D
1' -9
"C" LABEL
9"9"
SOUND RATED
5' -0
UE PR PATIENT ROOM
ENTRY
7' -0
5'-0"
4'-0" 1'-0"
3' -6
DASHED LINES INDICATE
OPENING REQD BY
MODIFICATION IN
REMARKS
SINGLE PATIENT
ROOM ENTRY
9"
3' -6
1 3 11 19 50
9"
3' -6
7'
0"
9"
3' -6
9"
4'-0"
9" 9"
INTEGRATED DOOR
ASSEMBLY
4"
4"
HOLLOW METAL
DOUBLE EGRESS
DOOR FRAME
4"
4" 2"
2"
HOLLOW METAL -
PATIENT TOILET ROOM
2"
SPLIT HEAD
FOR LIFT
TRACK
SCH.
SCH.
2"
2"
HOLLOW METAL
2"
SCH.
J-AE501
J-AE501
J-AE501
J-AE501
J-AE501
J-AE501
J-AE501
DOOR AND FRAME NOTES:
1. ALL DOORS SHALL BE TYPE F-WD 1 3/4" THICK UNLESS NOTED OTHERWISE.
2. TOP AND SIDE RAILS SHALL BE 9" MIN. BOTTOM RAILS SHALL BE 12" MIN.
CLARIFICATION OF GLAZING TYPES:
FG-1: 1/4" CLEAR FLOAT GLASS
FG-3: 1/4" CLEAR TEMPERED FLOAT GLASS
LG-1: 3/4" TEMPERED LAMINATED GLAZING
DOOR SCHEDULE ABBREVIATIONS / MODIFICATIONS
A LAMINATED GLAZING
AG ALL-GLASS ENTRANCE DOOR - LG-1
CR CARD READER ACCESS
D DOUBLE GLAZED TEMPERED GLASS
H ELECTRIC HOLD
L LOUVER
LP LIGHT PROOF LOUVER
M MECHANICAL SEAL FOR LIGHT PROOF AND SOUND RETARDING DOOR
PB PUSH BUTTON ACCESS
SD SLIDING DOOR (3'-6" CLEAR OPENING)
T TEMPERED GLASS
TO TEMPERED OBSCURE
U UNDERCUT 3/4"
UE UNEQUAL
V1 VIEW PANEL 4" x 32" (1/4" TEMPERED GLASS, WIRE GLASS AT FIRE RATED DOORS)
V2 VIEW PANEL 24" x 36" (1/4" THICK TEMPERED GLASS)
V3 VIEW PANEL 10" x 10" (1/4" TEMPERED GLASS, WIRE GLASS AT FIRE RATED DOORS)
W1 VIEW PANEL 10" x 10" (1/4" WIRE GLASS)
DOOR RATINGS
"A" LABEL: 3 HOURS FIRE RATED DOOR
"B" LABEL: 1 1/2 HOURS FIRE RATED DOOR
"C" LABEL: 3/4 HOUR FIRE RATED DOOR
2"
2"
HOLLOW METAL
2"SCH.
3' -1
0" 3'
-4
J-AE501
J-AE501
3'
4"
2' - 0"
3'
4"
2' - 6"
W1 W2
LG-1 LG-1
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AE103
DOOR SCHEDULE & DOOR /
FRAME TYPES
RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
DOOR NO
DOOR FRAME
RATING HW
VA Door
Sign Type REMARKSPAIR WIDTH HEIGHT TYPE MAT'L MAT'L TYPE
4H-100.11 3' - 6" 8' - 6" 1 WD HM 10 2H U
4H-100.12 3' - 6" 8' - 6" 1 WD HM 10 2H U
4H-100.17 3' - 6" 8' - 6" 1 WD HM 10 2H U
4H-100.24 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-103 3' - 0" 7' - 0" 19 WD HM 2 4J V1
4J-105.1 4' - 0" 7' - 0" 3 WD HM 2 4P TO
4J-105.2 4' - 0" 7' - 0" 3 WD HM 2 1K TO
4J-106 3' - 0" 7' - 0" EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
4J-107.1 4' - 0" 7' - 0" 3 WD HM 2 4P TO
4J-107.2 4' - 0" 7' - 0" 3 WD HM 2 1K TO
4J-107.3 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-107.4 4' - 0" 7' - 0" 3 WD HM 2 1B TO
4J-108 3' - 0" 7' - 0" 19 WD HM 2 4J V1
4J-109 3' - 0" 7' - 0" 19 WD HM 2 4J V1
4J-110.1 4' - 0" 7' - 0" 3 WD HM 2 1B TO
4J-110.3 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-111.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-111.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-112.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-113.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-113.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-114 3' - 0" 7' - 0" 1 WD HM 2 4F W1, U
4J-115.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-115.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-116 3' - 0" 7' - 0" 1 WD HM 2 5D U
4J-117 3' - 0" 7' - 0" 19 WD HM 2 4J V1
4J-118 3' - 10" 7' - 0" 1 WD HM 2 4F W1
4J-119 3' - 0" 7' - 0" EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
4J-120 3' - 0" 7' - 0" 19 WD HM 2 4E V3
4J-120A 3' - 0" 7' - 0" 19 WD HM 2 4B W1
4J-120B 3' - 0" 7' - 0" 19 WD HM 2 4B W1
4J-121 3' - 0" 7' - 0" 19 WD HM 2 SH-4 V1
4J-122 3' - 6" 7' - 0" 11 WD HM 2 C LABEL 5B W1, U
4J-123.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-123.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-125.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-125.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-126.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-127A 3' - 0" 7' - 0" 1 WD HM 2 4G
4J-128.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-128.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-129.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-129.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-130.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-130.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-131.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-131.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-132 3' - 8" 7' - 0" 11 WD HM 2 C LABEL SH-3C PB, W1
4J-133 3' - 8" 7' - 0" 11 WD HM 2 C LABEL SH-3C PB, W1
4J-134.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-135.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-135.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-136.1 4' - 0" 7' - 0" 3 WD HM 2 1B TO
4J-136.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-137.1 4' - 0" 7' - 0" 3 WD HM 2 1B TO
4J-137.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-139.1 UE PR 5' - 0" 7' - 0" 50 WD HM 2 8Z TO
4J-139.2 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-141 3' - 8" 7' - 0" 11 WD HM 2 C LABEL 4F W1, U
4J-142.1 4' - 0" 7' - 0" 3 WD HM 2 4P TO
4J-142.2 4' - 0" 7' - 0" 3 WD HM 2 1K TO
4J-142.3 3' - 6" 8' - 6" 1 WD HM 10 2H U
4J-144 3' - 0" 7' - 0" 11 WD HM 2 C LABEL 4F W1
4J-145 3' - 0" 7' - 0" 1 WD HM 2 4G
4J-160 3' - 0" 7' - 0" 19 WD HM 2 4J V1
CJ4-6 PR 7' - 0" 7' - 0" 42 HM HM 50 SH-10A V1
E
G
H
I
J
8 9 10 11 138.2 12
A.F.F.
GYP-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
GYP-01
9' - 0" A.F.F.
GYP-01
9' - 0"
1.6
4J-107
CJ4-4
4J-119
J -1
A
J -1
A
4J-112 4J-111
4J-110
J -1
A
4J-105
4J-103
4J-113
4J-142B
4J-114
J -1
4J-115A
4J-123A
4J-128
J -1
A
4J-126
4J-125
J -1
A
J -1
A
J -1
A
J -1
A
J -1
A
4J-134
J -1
A
4J-137
J -1
A
J -1
A
4J-139
4J-131 4J-130
J -1
B
4J-136
4J-129
J -1
A
4J-124
4J-135
CJ4-3B
CJ4-7
CJ4-6
CJ4-8B
4J-141
J -1
J -1
B
4J-120A 4J-120B
4J-158
J -1
J -1
J -1
J -1
74J-140
4J-104
4J-122
4J-106
C J -5
CJ4-10
CJ4-8C
CJ4-8A
A.F.F.
AT-01
9' - 0"A.F.F.
AT-01
9' - 0" A.F.F.
AT-01
9' - 0"A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0" A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
8' - 6"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0" A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0" A.F.F.
AT-01
9' - 0"
A .F
.F
A T
-0
A .F
.F
A T
-0
A.F.F.
AT-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
AT-02
8' - 0"
A.F.F.
AT-01
8' - 6"A.F.F.
AT-01
8' - 6"
A.F.F.
AT-01
8' - 6"
A.F.F.
AT-01
8' - 6"
A.F.F.
AT-01
8' - 0"
A.F.F.
AT-01
8' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-02
8' - 0"
A .F
.F
A T
-0
A.F.F.
AT-01
9' - 0"A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A.F.F.
AT-02
8' - 0"
A.F.F.
GBH-01
7' - 10"
CJ4-9
CJ4-10
A.F.F.
AT-02
8' - 0"
J -1
A
4J-144
J -1
4J-142 4J-142A
4J-145
J -1
4J-133
4J-132
4J-127B
F
A.F.F.
GYP-01
9' - 0"A.F.F.
GYP-01
9' - 0"A.F.F.
GYP-01
9' - 0" A.F.F.
GYP-01
9' - 0"
A.F.F.
GYP-01
9' - 0"
A .F
.F
A T
-0
J -1
B
A.F.F.
AT-01
9' - 0"
A.F.F.
AT-01
9' - 0"
A.F.F.
GYP-01
9' - 0"A.F.F.
GYP-01
9' - 0"
J -1
A
J -1
J -1
A
J -1
B
A.F.F.
AT-02
8' - 0"
4J-159
S-1
4J-118
J -M
J -1
S S
S S
S S
S S
S S
S S
A.F.F.
AT-02
8' - 0"
J -1
B
S S
S S
4J-127A
A.F.F.
GBH-01
7' - 10"
A.F.F.
AT-01
8' - 0"
A.F.F.
GBH-01
7' - 10"
A.F.F.
GBH-01
7' - 10"
A.F.F.
GBH-01
7' - 10"
A.F.F.
GBH-01
7' - 10"
A.F.F.
AT-01
9' - 0"
EXISTING WALLS. CONTRACTOR VERIFY
THAT WALL MEET REQUIREMENTS OF A
1 HOUR FIRE/SMOKE BARRIER. SEAL
WALL AT FLOOR AND ROOF DECK
ABOVE. FIRE SEAL ALL OPENINGS. TYP.
24" x 24" RETURN AIR OUTLET
24" x 24" AIR SUPPLY DIFFUSER
EXHAUST GRIELLE
24" x 24" LIGHT FIXTURE
RECESSED DOWNLIGHT
S CEILING PATTERN ORIGIN
PATIENT LIFT MOTOR AND TRACK
24" x 48" LIGHT FIXTURE
AT-01 24" x 24" ACOUSTICAL CEILING TILE
AT-02 24" x 48" ACOUSTICAL CEILING TILE
GYP-01 SUSPENDED GYPSUM BORAD CEILING
GBH-01 GYPSUM BOARD BULKHEAD
WALL MOUNTED STRIP LIGHT FIXTURE
24" x 24" EXHAUST AIR OUTLET
24" x 24" LIGHT FIXTURE ON EMERGENCY CIRCUIT
24" x 48" LIGHT FIXTURE ON EMERGENCY CIRCUIT
SURFACE MOUNTED LIGHT FIXTURE
EXIT FIXTURE
DESIGN/BUILD
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2 :2
A
M
Sheet of
AE111
REFLECTED CEILING PLAN RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
1/8" = 1'-0"
NEW - RCP - ZONE J
J
KEY PLAN
TRUE
NORTH
H
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
RCP GRAPHIC LEGEND
RCP GRAPHIC LEGEND
REFER TO SHEET GI002 FOR FLOOR PLAN GENERAL NOTES, SHEET NOTES, SYMBOL
LEGENDS, AND ABBREVIATIONS.
REFER TO SHEET IN103 FOR CEILING FINISH SELECTIONS.
Fourth Floor 0' - 0"
Penthouse Floor 14' - 0"
8 9 10 11 138.2 12
PATIENT RM
4J-128
BATH RM
4J-126A
PATIENT RM
4J-126
PATIENT RM
4J-125
BATH RM
4J-134A
PATIENT RM
4J-134
PATIENT RM
4J-131
BARIATRIC
RM
4J-130
PATIENT RM
4J-129
PATIENT RM
4J-135
Fourth Floor 0' - 0"
Penthouse Floor 14' - 0"
E G H I J
NEGATIVE
BARIATRIC
RM
4J-105
PATIENT RM
4J-131
BATH RM
4J-105B
CORRIDOR
CJ4-9
CORRIDOR
CJ4-6
CORRIDOR
CJ4-10
F
Fourth Floor 0' - 0"
Penthouse Floor 14' - 0"
EGHIJ
EXIST ELECT
4J-119
PATIENT RM
4J-110
PATIENT RM
4J-129
BATH RM
4J-129A
CORRIDOR
CJ4-9
CORRIDOR
CJ4-6
LOCKERS
4J-121B
NURSE
MANAGER
4J-109
HALLWAY
CJ4-5
STORAGE 2
4J-127B
LINEN
4J-159
F
Fourth Floor 0' - 0"
9 10
NURSE
STATION
CJ4-4CORRIDOR
CJ4-10
TELEM
4J-158
J-AE502
SIM.
J-AE502
SIM.
SCH. AT
SCH. AT
J-AE505
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AE301
BUILDING SECTIONS RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
1/4" = 1'-0"
1 BUILDING SECTION 1 - ZONE J
1/4" = 1'-0"
2 BUILDING SECTION 2 - ZONE J
1/4" = 1'-0"
3 BUILDING SECTION 3 - ZONE J
SCALE: 1/4" = 1'-0"
0 2' 4' 8'
3/8" = 1'-0"
4 BUILDING SECTION 4 - ZONE J
B
C
A
DOUBLE EGRESS DOOR
FRAME
NOTE: SHOWING THE SWING
OF DOUBLE EGRESS
DOORS.
JAMBJAMB
SIDE
SECTIONS DOUBLE EGRESS
DOORS
A B
DOOR
STOP
(BEYOND)
HEAD
PLAN
C
DOOR
BA
DOOR
C
09.029
DECK
1/2" GAP MAX. FILL w/
FIRESTOP SEALANT
SCH. PTN - DO NOT SECURE
GWB AND VERTICAL STUDS TO
TOP TRACK. RE: DEFLECTION
TRACK DETAIL
Z CLIPS @ 24" O.C. MAX.
EXISTING SPRAY-APPLIED
FIREPROOFING ON BEAM
NEW SPRAY-APPLIED
FIREPROOFING ON BEAM
1/ 2"
VARIES
(3) #8 PAN HEAD
SCREWS @ EACH
STUD
6" x 18GA. UNPUNCHED TRACK w/ MIN. 1
1/4" LEGS NOTCHED AT EACH STUD.
ATTACH TO MIN. (3) STUDS AND
EXTEND TO (1) STUD BEYOND
EQUIPMENT ATTACHMENT POINT
09.002
WALL BACKING TYPE B
USE FOR:
- BULLETIN BOARDS
- BULLETIN BOARDS w/ GLASS
LOCKING DOORS
- BUMPER GUARDS
- DOOR STOPS
- DOOR HOLDERS
- MIRRORS
- LIQUID CHALK BOARDS
- SIGNAGE
- BATH AND TOILET ACCESSORIES
(EXCEPT GRAB BARS)
- TELEPHONES
- LITERATURE / MAGAZING RACKS
- HAND RAILS
- CRASH RAILS
- CHART RACKS
- DIRECTORIES
ALLOWABLE LOADS:
VERTICAL: 90 LBS
LATERAL: 45 LBS
FASTEN AT EACH END WITH
MIN. 4 TAPPING SCREWS
CUT HORIZONTAL MEMBER
FROM STUD AS ONE PIECE
WALL FINISH
NOTE: CONTRACTOR SHALL
COORDINATE LOCATIONS OF
HORIZONTAL FASTENERS
ISOMETRIC
09.002
WALL BACKING TYPE A
USE FOR:
- GRAB BARS (NOT SWING-UP
TYPE)
- CABINETS
- SHOWER SEATS
HOLLOW METAL FRAME
PROVIDE FRAME ANCHOR AT
OPENINGS > 6'-4" IN WIDTH
SCHED. DOOR
CAULK - ENTIRE PERIMETER
BOTH SIDES
08.003
SEE SEE DET. 8 FOR
HEADER FOR HEADER
SCHEDULED PARTITION
@ UNRATED AND 1 HOUR PARTITIONS
2"
1/2"
VARIES
M
IN
1/ 2"
LINE OF STOP AND GLASS @ WINDOW
ACOUST. INSUL. @ STC-RATED
PARTITIONS
HOLLOW METAL FRAME
PROVIDE FRAME ANCHOR AT
OPENINGS > 6'-4" IN WIDTH
SCHED. DOOR
CAULK - ENTIRE PERIMETER
BOTH SIDES
08.005
SEE DET. 8 FOR
HEADER
SCHEDULED PARTITION
4"
1/2"
VARIES
2"
HOLLOW METAL CASED
OPENING FRAME JOINED TO
JAMB MEMBERS TO CREATE
STRUCTURAL FRAME
LINE OF CEILING
PROVIDE 2" SLOT IN HEAD FOR
PATIENT LIFT TRACK PASSAGE
09.006
ATTACH TRACK TO
HEADER w/ #10 SMS @ 16" O.C.
20 GA. NESTED STUD.
ATTACH RUNNER TRACK TO
NESTED STUD w #10 SMS @
12" O.C. - TYP EACH FLANGE
LINE OF OPENING FRAME
@ OPENINGS TO 3'-4" WIDE @ OPENINGS FROM 3'-4" TO 12'-0" WIDE
ATTACH TRACK TO
HEADER w/ #10 SMS @ 16" O.C.
DBL STUD BOX HEADER:
4"x20 GA @ OPNGS TO 6'-4" WIDE 6"x20 GA @ OPNGS TO 8'-4" WIDE 8"x20 GA. @ OPNGS TO 12'-0" WIDE
EXTEND WEB & ATTACH TO JAMB
STUD BEYOND
HEADER ATTACHMENT
TO JAMB BEYOND
LINE OF OPENING FRAME
HEADER ATTACHMENT
TO JAMB BEYOND
20 GA. NESTED STUD
HEADER - FOLD BACK 90
DEG. & FASTEN TO JAMB
STUD w (3) #10 SMS @
EACH STUD FLANGE
CUT NESTED STUD
FLANGE SHORT OF JAMB
STUD
PAIRED 16 GA JAMB
STUDS
EXTEND WEB OF BOX
STUDS OVER JAMB
STUDS & ATTACH w/ (3) #
10 SMS @ 6" HEADERS
AND (2) #10 SMS @ 4"
HEADERS
PAIRED 16 GA JAMB
STUDS
TRACK
TRACK
09.007
LINE OF FINISHES
@ OPENINGS TO 3'-4" WIDE @ OPENINGS FROM 3'-4" TO 12'-0" WIDE
NESTED STUD. ATTACH TO
TRACK w/ #10 SMS @ 12"
O.C. EACH FACE
16 GA. TRACK - FOLD
BACK 90 DEG. & FASTEN
TO JAMB STUD w (3) #10
SMS @ EACH STUD
FLANGE
CRIPPLE STUD
PAIRED 16 GA JAMB
STUDS
NESTED STUD
TRACK
ATTACH RUNNER TO
CRIPPLE STUDS BELOW
w/ (1) #10 SMS EACH
FACE
CRIPPLE STUD
PAIRED 16 GA JAMB
STUDS
LINE OF FINISHES
ATTACH RUNNER TO
CRIPPLE STUDS BELOW
w/ (1) #10 SMS EACH
FACE
09.013
DOOR
OPENING
WINDOW
OPENING
DUCTEQ
EQ
M
AX
0'
6"
EQ
EQ
DEEP LEG SLOTTED
DEFLECTION TRACK
HORIZONTAL
BRACING
DBL 16GA STUDS
@ EACH OPENING
JAMB - TYP. BACKING PLATE
IN TYPE AND
LOCATION AS
REQ'D
CEILING LINE
HEADER
CONDITION VARIES
BY OPENING WIDTH
BEAM
J-AE501
J-AE501
J-AE501
J-AE501
J-AE501
J-AE501
J-AE501
J-AE501
J-AE501
09.005
C
LE
AR
3/ 4"
CONT. LATERAL BRACE: 1-1/2"
CR CHANNEL w/ 1-1/2"x2"x16
GA. CLIP ANGLE @ EACH
STUD - CLIP LENGTH = STUD
WIDTH LESS 1/4"
BTM OF DECK
ACOUSTIC CAULK @
NON-RATED PTNS;
FIRESTOP @ RATED
PTNS
M
AX
0'
6"
VARIES
PTN TYPE
BOARD NUMBERS AND
TYPE VARIES - SEE PTN
TYPE
PROVIDE SLIP-FIT PAN
HEAD SCREW AT EACH
STUD FLANGE IN SLOTS
C
LE
AR
3/ 4"
1. INSTALL GYPSUM BOARD ANCHORS TO
STUD CLEAR OF TRACK
2. WHERE TOP TRACK RUNS PARALLEL TO
DECK FLUTES, INSTALL CONT. 14 GA.
PLATE ACROSS 2 FLUTES MIN. ON DECK
BEFORE TRACK.
3. AT UNRATED PTNS, INSTALL
FIRESTOPPING IN FLUTES ABOVE
PLATE/TRACK. AT RATED PTNS, INSTALL
FIRESTOPPING IN ALL CONCEALED FLUTES
ABOVE PLATE/TRACK
SLOTTED DEFLECTION TRACK
09.011
SC
H
. P
TN
SCH. PTN.
SC
H
. R
AT
ED
P
TN
ATTACH @ 24" O.C. VERT.
SCH. UNRATED PTN.
RATED
UNRATED
09.010
30'-0" MAX.
0' - 0 1/2"
SC
H
P
TN
BOARD NUMBER AND
TYPE VARIES - SEE PTN
TYPE
CONTROL JOINT
09.014
MAX.
0' - 6"
MAX.
0' - 6"
NOTE:
BOARD MUST SPAN 2 STUDS BEFORE
CANTILEVER - REF UL DESIGN
DECK
1/2" GAP MAX. FILL w/
FIRESTOP SEALANT
STUDS
RUNNER TRACK
FILL ENTIRE VOID AND GAPS w/
FORMING MAT'L
09.008
BOARD NUMBER AND
TYPE VARIES - SEE PTN
TYPE
SEALANT :
ACOUSTIC @ NON-RATED
PARTITIONS
FIRESTOP @ RATED
SCH. PTN
0'
1/ 2"
09.012
PLAN SECTION
HSS 3x3x1/4 w/ 1/4" BASE PLATE. ANCHOR TO SLAB w/
(4) 3/8" EXP. BOLTS
ATTACH STUDS TO TUBE
" M
AX
0'
6" M
IN
M
AX
0'
1/
2"
REFER TO DETAILS
FOR TOP OF WALL
CONFIGURATION
ANCHORAGE TO
SLAB TO PROVIDE
RESISTENCE TO 50#
CONCENTRATED
LOAD APPLIED TO
TOP OF PARTITION.
CAULK - ENTIRE PERIMETER
BOTH SIDES
08.004
MIN. (3) ANCHORS PER
JAMB WELDED TO DR.
FRAME -FASTEN
ANCHORS TO STUDS w/
MIN. (2) #10 SMS PER
ANCHOR - FLR. ANCHOR
WELDED TO FRAME
AND FASTENED TO
SLAB w/ (2) 0.14" PAF
20 GA. STUDS FULL HT
TO STRUCT ABOVE. RE:
SCHEDULED PARTITION
SCHED. DOOR
2"
MIN.
4"
1/ 2"
@ UNRATED AND 1 HOUR PARTITIONS
LINE OF STOP AND
GLASS @ WINDOW
ACOUST. INSUL. @ STC-
RATED PARTITIONS
PROVIDE HOSPITAL STOPS @ BOTTOM BOTH SIDES
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AE501
WALL - CEILING DETAILS RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
3" = 1'-0"
1 RATED PTN HEAD AT BEAM
1 1/2" = 1'-0"
2 WALL BACKING - TYPE B
1 1/2" = 1'-0"
3 WALL BACKING - TYPE A
3" = 1'-0"
4 TYPICAL DOOR HEAD DETAILS
3" = 1'-0"
5 PATIENT TOILET ROOM DOOR HEAD
3" = 1'-0"
8 HEADER FRAMING @ STUD PTN OPENINGS
3" = 1'-0"
9 SILL FRAMING
1/4" = 1'-0"
7 TYPICAL PARTITION FRAMING
3" = 1'-0"
13 DEFLECTION TRACK (TYP @ FULL HT PTNS)
3" = 1'-0"
10 INTERIOR PTN INTERSECTION
3" = 1'-0"
11 GWB CONTROL JOINT
1" = 1'-0"
14 RATED PTN AT INTERSECTING BEAM
3" = 1'-0"
12 BASE OF STUD PTN
3" = 1'-0"
15 STRUCTURE FOR PARTIAL HGT PTNS
3" = 1'-0"
6 TYPICAL DOOR JAMB DETAILS
3" = 1'-0"
16 DOUBLE EGRESS DOOR DETAILS
09.018
SCH. AT
SYSTEM
REF
RCP
REF
RCP
REF. RCP
CORNER BEAD
0'
4" 0'
2"
VA
R
IE
S
0'
4"
09.017
SCH. AT
SYSTEM
SHADOW MOLD
10.001
2'
SIDE ELEVATION
FRONT ELEVATION
UPSWING GRABBAR
(2) 5"x3"x1/4" ANGLES ANCHORED
TO STRUCTURAL FLOOR. ATTACH
VERT. TUBE w/ 1/2" THROUGH
BOLT IN SLOT
DECK
APPLIED FINISH
HSS 6"x2"x1/4" FROM FLR TO DECK w/ 1/4" x 12" BASE PLATE. ANCHOR TO
SLAB w/ 3/8" EXP. BOLTS
16 GA. METAL STUDS
(4) 1/4" THROUGHBOLTS
PER BAR: PREDRILL
HOLES IN TUBE
PLAN
ANCHORAGE TO PROVIDE
RESISTANCE FOR SUPPORT TUBE AND
PLATES TO A SINGLE 250#
CONCENTRATED LOAD WHEN APPLIED
AT ANY POINT IN ANY DIRECTION TO
GRABBAR.
10.004
SCH. HANDRAIL
WALL BACKING TYPE B
CONCEALED
ANCHOR PLATE
10.005
SCH. HANDRAIL
WALL BACKING TYPE B
CONCEALED
ANCHOR PLATE
1 1/2"
11.001
REF
RCP
SUPPORTS TO DECK PER
MFR'S RECOMMENDATIONS
DIAGONAL BRACING PER
MFR'S
RECOMMENDATIONS
PATIENT LIFT ENGINE
SCH. ACT SYSTEM w/
MOLD. CONT. ALONG RAIL
2.75" HIGH PATIENT LIFT
RAIL. HOLD TIGHT TO
CEILING LINE.
PATIENT LIFT HANDLE.
PROVIDE (1) DOCKING
STATION PER PATIENT LIFT
SYSTEM.
45°
3/
4"
DESIGN PATIENT LIFT SYSTEM TO
ACCOMMODATE PATIENT LOAD OF
550# EXCLUSIVE OF SYSTEM
DEAD LOAD WITH A SINGLE
MOTOR.
SUPPORT CONFIGURATION
SHOWN IS CONCEPTUAL. REFER
TO SPECIFICATIONS FOR
REQUIRED DELEGATED DESIGN.
10.003
SCH. PTN
ALUM. RETAINER
BUMPER GUARD COVER
FINISH EXPOSED EDGES OF GYP. BD. @
BTM OF GUARD w/ J MOLD . SKIM AND
PAINT TO MATCH ADJ. PARTITION
LINE OF BASE BELOW
SCH. PTN
ALUM. RETAINER
BUMPER GUARD COVER
LINE OF BASE BELOW
WALL END CAP
WALL OUTSIDE CORNER
10.002
REF
RCP
8 GA. SUSPENSION WIRE @
24" O.C. IN ADDITION TO TYP.
CLG GRID SUSPENSION
WIRE
20 GA. MTL STUD ATTACHED
TO CLG. GRID
CUBICLE CURTAIN TRACK
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AE502
ARCHITECTURAL DETAILS RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
3" = 1'-0"
6 GYP. BD. BULKHEAD
3" = 1'-0"
7 ACOUST. CLG @ WALL - TYP.
1 1/2" = 1'-0"
1 UP-SWING GRAB BAR
3" = 1'-0"
2 CRASH RAIL
3" = 1'-0"
3 HAND RAIL
1 1/2" = 1'-0"
4 PATIENT LIFT TRACK SUPPORT
3" = 1'-0"
5 CORNER GUARD
3" = 1'-0"
8 CUBICLE CURTAIN TRACK SUPPORT
10.005
WP-1 WP-2 WP-3
2' -1
0"
/2
/2
4' -0
HNDRL-01
CR-01 CR-01
FR PLYWD
2" DOOR WIDTH 2"
DOOR IN
FULLY
OPENED
POSITION
SCH WP SCH WP
WALL PROTECTION
EXTENTS FOR DOORS
OPENING 180 DEGREES
C G
-0
8' -0
CORNER GUARD
RE: AE501 FOR WALL BACKING TYPES FOR WALL PROTECTION ELEMENTS
2" 2"
FE CAB
FOR AN UNOBSTRUCTED APPROACH, THE
MAXIMUM FORWARD REACH TO THIS
EQUIPMENT (FOR EXAMPLE, THE FIRE
EXTINGUISHER HANDLE) IS 48" ABOVE THE
FLOOR. THE MAXIMUM SIDE REACH FOR
SUCH AN APPROACH IS 54'. THE ACTUAL
MOUNTING HEIGHTS FOR CABINETS
HOUSING THIS EQUIPMENT CAN BE
DETERMINED BY REVIEWING THE EXACT
DIMENSIONS OF THE SPECIFIED CABINET
AND THE POSITIONING OF THE FIRE
EQUIPMENT WITHIN THAT CABINET
09.030
CL
DOOR WHERE OCCURS
CERAMIC /
PORCELAIN TILE
SST TRANSITION
STRIP
RESILIANT FLOORING
(TILE, SHEET, OR LINOLEUM)
CRACK ISOLATION OR
WATERPROOFING
MEMBRANE - EXTEND 2"
UNDER RESILIANT
SLAB
1/2"
AS
S
C H
DOOR WHERE OCCURS
CERAMIC /
PORCELAIN TILE
RESILIANT
TRANSITION STRIP
RESILIANT FLOORING
(TILE, SHEET, OR LINOLEUM)
SLAB
CL
CERAMIC / PORCELAIN TO RESILIANT
CARPET TO RESILIANT
DOOR WHERE OCCURS
RESILIANT
FLOORING
HEAT-WELDED SEAM
BETWEEN RESILIANT
SHEET FLOORING
ADHERED SEAM BETWEEN
RESILIANT SHEET AND
OTHER RESILIANT
RESILIANT FLOORING
(TILE OR SHEET)
SLAB
CL
RESILIANT TO RESILIANT
RESILIANT EDGE STRIP -
CENTER UNDER DOOR
WHERE OCCURSRESILIANT
FLOORING SLAB
CL
RESILIANT TO CONCRETE
DOOR WHERE OCCURS
DOOR WHERE OCCURS
RESINOUS
FLOORING -
SLOPE TO DRAIN
ACCESSIBLE SST
TRANSITION STRIP
RESILIANT FLOORING
(TILE, SHEET, OR LINOLEUM)
SLAB
CL
RESINOUS TO RESILIANT
1/ 8"
1/ 2"
1 1/8" SLAB
SLOPED
RESIONOUS
THINSET BED
RESINOUS FLOOR /
INTEGRAL BASE
SST TRIM PROFILE
SCH. WALL TILE
2" 1/
2"
INTEGRAL RESINOUS BASE 09.032
DRAIN STRAINER SET FLUSH
WITH FINISHED FLOOR
SURFACE
1/ 8"
RESINOUS FLOORING - 1/8"
MAX. HT. @ DRAIN
LINEAR DRAIN BODY -
RECESS INTO EXISTING
SLAB
PORCELAIN TILE SIMILAR
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AE503
ARCHITECTURAL DETAILS RENOVATE FOR PATIENT
PRIVACY -
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
1/2" = 1'-0"
1 WALL PROTECTION TYPES
12" = 1'-0"
2 FLOOR TRANSITIONS
6" = 1'-0"
3 RESINOUS FLOORING @ DRAIN
06.005E2013-CAB_BASE_4DRWR-001
SE
E
EL
EV
0'
6"
2' - 1"
CONT. LADDER BASE
SCH. TOP
SOLID FACE STILE
SEAL
SCH. BASE
4 SIDED FRAME UNDER
TOP;FACE FRAME
UNDER DRAWERS
WALL BACKING
EQ
EQ
DC
0' - 3"
1/
4"
DRAWER
E2013-CNTR_SDSF_SKRT
CFSEAL
SE
E
EL
EV
SE
E
EL
EV
CONCEAL MOUNT
SUPPORT
SCH. TOP
1'
8"
SPEC. SUBSTRATE
E2013-BASE_SHLF
SE
E
EL
EV
0'
6"
2' - 1"
CONT. LADDER BASE
OVERLAY DOOR
ADJ. SHELF
SCH. TOP
SOLID FACE STILE
SEAL
SCH. BASE
4 SIDED FRAME
WALL BACKING
BA
0' - 3"
1/
4"
RE: SECTION BC
FOR TRASH
RECEPTICLE
RE: SECTION BB
FOR SINK
SCHED. HW
1. VERIFY DIMENSIONS OF TV
RECESS w/ VA
2. PLAM-01 ON SHROUD
3. PLAM-04 ON WARDROBE
OVERLAY DOOR
SCH. BASE
1' - 7 3/4" 4 1/4"
SCHED. HW
M0500 PLASMA TV &
MOUNT - VV
1/
4" 5'
1/ 4"
1'
/2
TV / DATA JUNCTION
BOX - RE: ELEC
1-1/2" FACE STILE
PLAM SOFFIT
ADJ. SHELF (2)
DRAWER
3/4" PLYWOOD
2' - 0"
3"
8'
0"
PWC
E2013-BASE_SINK-001
SE
E
EL
EV
0'
6"
2' - 1"
CONT. LADDER BASE
OVERLAY DOOR
SCH. TOP
SOLID FACE STILE
SEAL
SCH. BASE
WALL BACKING
HOLD PLUMBING ROUGH-
IN AS HIGH AS POSSIBLE
BB
SCHED. HW
SCHED. FIXTURE
0' - 3"
1/
4"
CONT. LADDER BASE
WALL BACKING
SCHED. HW
PLAM SOFFIT 1. VERIFY DIMENSIONS OF TV
RECESS w/ VA
2. PLAM-01 ON SHROUD
3. PLAM-04 ON WARDROBE
1' - 7 3/4" 4 1/4"
2' - 0"
1/
4" 5'
1/ 4"
1'
/2
8'
0"
3"
OVERLAY DOOR
M0500 PLASMA TV &
MOUNT - VV
TV / DATA JUNCTION
BOX - RE: ELEC
1-1/2" FACE STILE
3/4" PLYWOOD
PWH
06.007
BC
SE
E
EL
EV
0'
6"
2' - 1"
CONT. LADDER BASE
OVERLAY DOOR
SCH. TOP
SOLID FACE STILE
SEAL
SCH. BASE
4 SIDED FRAME
WALL BACKING
8" SSTL TRASH
GROMMET
0' - 3"
JSN F2017
WASTEBASKET
1/
4"
SCHED. HW
1' - 3" 1' - 9"
2'
0"
1' - 3" 1' - 9"
WARDROBE STORAGE
PLAM CABINET BODY:
1" SIDE PANELS
1/4" BACK
3/4" ALL OTHERS
BACK PANEL GLUED AND
DADO'D INTO SIDE
PANELS
SCH. HW
2 1/2"2 1/2"
1. VERIFY DIMENSIONS OF TV RECESS w/ VA
2. PLAM-01 ON SHROUD
3. PLAM-04 ON WARDROBE
SCRIBE
PW
SS COUNTERTOP
& SKIRT
1/
2"
1"
SE
E
EL
EV
CONCEALED COUNTER
SUPPORTS
PRD
E2013-BASE_DRWR_SHLF
BD
SE
E
EL
EV
0'
6"
2' - 1"
CONT. LADDER BASE
OVERLAY DOOR
ADJ. SHELF
SCH. TOP
SOLID FACE STILE
SEAL
SCH. BASE
4 SIDED FRAME
WALL BACKING
0'
5" 0'
1/ 8"
0' - 3"
SCHED. HW
DRAWER
1/
4"
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AE504
CASEWORK DETAILS RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
1 1/2" = 1'-0"
DC SECTION AT DRAWER BANK - 4 DRAWERS
1 1/2" = 1'-0" CF SECTION AT COUNTERTOP w/ SKIRT
1 1/2" = 1'-0"
BA SECTION AT SINK BASE CABINET
1 1/2" = 1'-0"
PWC SECTION AT PATIENT ROOM WARDROBE
1 1/2" = 1'-0"
BB SECTION AT SINK BASE CABINET
1 1/2" = 1'-0"
PWH SECTION AT WARDROBE
1 1/2" = 1'-0"
BC
SECTION AT BASE CABINET - TRASH
RECEPTICLE
1 1/2" = 1'-0"
PW PLAN AT PATIENT WARDROBE
1 1/2" = 1'-0"
PRD SECTION AT PATIENT ROOM DESK
1 1/2" = 1'-0" BD SECTION AT BASE CABINET w/ DRAWER
E2013-WALL_OPEN_SHLF
WB
SOLID FACE STILE
FIN. CLG. - ELEVATION VARIES
WALL BACKING
UNDER CABINET
TASK LIGHT - REFER
TO ELEVATION FOR
LOCATIONS
ADJ. SHELF
SHELF CLIP HOLES
SE
E
EL
EV
0'
3/
4"
1' - 1"
0' - 0 3/4"
E2013-WALL_DOOR_SHLF
WA
OVERLAY DOOR
SOLID FACE STILE
FIN. CLG. - ELEVATION VARIES
WALL BACKING
SE
E
EL
EV
AT
IO
N 0'
2"
ADJ. SHELF
SHELF CLIP HOLES
1' - 1"
SCHED. HW
UNDER CABINET TASK
LIGHT - REFER TO
ELEVATION FOR
LOCATIONS
PLAM SOFFIT
E2013-CNTR-SUPT
END
1-1/2" END PANEL
1/4" EXPANSION BOLT
WOOD BLOCK
E2013-WALL_DOOR_MCRW
WCFIN. CLG. - ELEVATION VARIES
WALL BACKING
0'
1/
2" 1'
4"
VA
R
IE
S
SE
E
EL
EV
2' - 1"
PLAM SOFFIT
1" SHELF
K4460 MICROWAVE
SCHED. HW
1" SHELF
ATTACH TO ADJACENT
CABINETS w/ CONNECTOR
BOLTS
E2013-CNTR_SDSF_SINK_SEMI
CD
1'
7" 1'
2"
2'
9" 0'
5"
1' - 2"
LINE OF WALL
MOUNTED MIRROR
SOLID SURFACE TOP,
FRONT AND SIDE
SKIRTS AND SPLASH ON
SPECIFIED SUBSTRATE
2x4 AND ANGLE FRAME PER
LAV. MANUFACTURER'S
REQUIREMENTS
SCH. WALL, BASE,
FLOOR FINISHES
ABA REQ'D KNEE AND
TOE CLEARANCES
SCH. FIXTURE & TRIM
EASE EDGE PER LAV.
PROFILE
E2013-SOFFIT_PLAM
1/ 2"
AL
IG
N
SOFFIT FINISH TO MATCH CAB. DOORS
3/4" PART. BD. BRACE @ 24" O.C. MAX.
LINE OF SCH. CEILING
7'-0" U.N.O.
PS
E2013-CTOP_SDSF
CA
CAULK
1/2" SPLASH SOLID SURFACE
1/2" SPECIFICED SUBSTRATE: PROVIDE
ADDITIONAL 3/4" LAYER AT BRACKET
SUPPORTED TOPS
U.N.O.
2' - 1"
0'
1/
8"
0'
1"
1"4"
E2013-WALL_DOOR_SHLF_DEEP
WD
OVERLAY DOOR
SOLID FACE STILE
PLAM SOFFIT
WALL BACKING
SE
E
EL
EV
0'
2"UNDER CABINET
TASK LIGHT - REFER
TO ELECTRICAL FOR
LOCATIONS
ADJ. SHELF
SHELF CLIP HOLES
2' - 1"
FIN. CLG. - ELEVATION VARIES
SCHED. HW
E2013-CTOP_SPRT-002
ZB
2'
0'
6"SCH. TOP ON
SPECIFIED SUBSTRATE
SOLID FACE STILE
SCRIBE
1/4" BOLTS - (3) PER
FRAME
1-1/2"x1-1/2" x3/16"
STEEL ANGLE
BRACKET
CONT. 2X2 WALL
LEDGER W/ #10X3
SELF-TAPPING
SCREWS 16" O.C.
1. LOCATE SUPPORT FRAMES @ 32" O.C. U.N.O.
2. AT PARTIAL HEIGHT WALLS, PROVIDE
SUPPORT TUBES @ EACH FRAME. RE: D/AE515
SS DIVIDER WALL
SS HIGH SHROUD
GROMMET
LINE OF SPLASH
BELOW
1/
2"
3/ 8"
4 3/8"
2 1/2" 6 1/8" 1 3/8"
1" 2' - 10"
5"
1/ 2"
1'
/2
1/
2"1/ 4"
1/
4"
2'
6"
3'
4"
1 1/2" 3/4" 5/8"
2' - 0" 10"
SST. BASE
SS
3/4" PLAM PANEL
CONCEALED MOUNT
SUPPORT
SS TOPS, FACES, RETURNS,
SPLASH
1/2" REMOVABLE PLAM PANEL
1/
2"
TASK LIGHT ENTIRE LENGTH
OF WORKSURFACE
3" GROMMETS : (3) PER
WORKSTATION
PARTIAL HGT. WALL TUBE
SUPPORT @ EACH COUNTER
SUPPORT ANGLE
KEYBOARD TRAY - VV
1/
2"
7"
4 5/8" 2 3/8"
(1) 1/2" AND (1) 3/4"
SUBSTRATES
NURSE STATION SS ASSIGNMENTS:
SS-01: COUNTERTOPS AND SPLASHES
SS-03: DIVIDER WALLS & END WALLS
SS-04: PASS-THROUGH, HIGH SHROUD, AND CAPS
2 1/2"
SS ON SPECIFIED
SUBSTRATE
1"
LINE OF COUNTERTOP
BELOW
END PANEL PLAN
SST. BASE
SECTION
SE
E
EL
EV
1/ 4"
1/
4"
2 1/2" 5 3/8"
DIVIDER PANEL PLAN
SS ON SPECIFIED
SUBSTRATE
3/4" PLAM PANEL
1"x1" SST ANGLE:
CONCEALED FASTERNERS
LINE OF SS BELOW
PALM TO WOOD OUTSIDE CORNER
PALM TO SS OUTSIDE CORNER
SS END PANEL / DIVIDER
WALL
3/4" PLAM PANEL
1/2" PLAM PANEL
1"x1" SST ANGLE
DESIGN/BUILD
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
Ve te ra ns
Af fa irsApproved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
1/
/2
9:
:2
AM
Sheet of
AE505
CASEWORK DETAILS RENOVATE FOR PATIENT
PRIVACY -
VAMC SALEM, VIRGINIA
658-18-101
02/28/2019
TJM TJM
1 1/2" = 1'-0"
WB SECTION AT WALL CABINET - OPEN
1 1/2" = 1'-0"
WA SECTION AT WALL CABINET - 1DR/2DRS
3" = 1'-0"
EN…
This is the start of the file's text. The full file is on GovTribe.