Structural Drawing.pdf
PDF 680 KB Posted
- Solicitation number
- 36C24620R0119
About this file
This document package includes architectural drawings and specifications for the renovation of patient privacy spaces in Wing J at the Veterans Affairs Medical Center in Salem, Virginia. The project involves renovating existing spaces to provide increased privacy for patients, including new partitions, finishes, casework, equipment, and MEP systems. Key project details include demolishing existing non-load bearing walls and installing new walls, doors, ceilings, flooring, signs, and casework. Mechanical, electrical and plumbing systems will be upgraded as needed. Enlarged views and interior elevations are provided along with schedules for doors, finishes, and equipment. Structural drawings also include details for supporting a new patient lift system that will be provided by others.
The related federal contract opportunity is solicitation number 36C24620R0119 for the renovation work. The estimated contract value is between $5-10 million. Proposals are due by February 21, 2018 and award is expected in April 2018. The renovation work must be completed within 365 days of the notice to proceed. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses and proposals will be evaluated based on technical experience, past performance, and price. The work will be overseen by the Department of Veterans Affairs VISN 6 office.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4J-107
CJ4-4
4J-119
J -1
A
J -1
A
4J-112 4J-111
4J-110
J -1
A
4J-105
4J-103
4J-113
4J-142B
4J-114
J -1
4J-115A
4J-123A
4J-128
J -1
A
4J-126
4J-125
J -1
A
J -1
A
J -1
A
J -1
A
J -1
A
4J-134
J -1
A
4J-137
J -1
A
J -1
A
4J-139
4J-131 4J-130
J -1
B
4J-136
4J-129
J -1
A
4J-124
4J-135
CJ4-3B
CJ4-7
CJ4-6
CJ4-8B
4J-141
J -1
J -1
B
4J-120A 4J-120B
4J-158
J -1
J -1
J -1
J -1
74J-140
4J-104
4J-122
4J-106
C J -5
CJ4-10
CJ4-8C
CJ4-8A
CJ4-9
CJ4-10
J -1
A
4J-144
J -1
4J-142 4J-142A
4J-145
J -1
4J-133
4J-132
4J-127B
J -1
B
J -1
A
J -1
J -1
A
J -1
B
4J-159
S-1
4J-118
J -M
J -1
J -1
B
4J-127A
GYP-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0" GYP-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0" AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
8' - 6"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
A T
-0
A T
-0
AT-01
9' - 0"
GYP-01
9' - 0"
AT-02
8' - 0"
AT-01
8' - 6"
AT-01
8' - 6"
AT-01
8' - 6"
AT-01
8' - 6"
AT-01
8' - 0"
AT-01
8' - 0"
AT-01
9' - 0"
AT-02
8' - 0"
A T
-0
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
AT-01
9' - 0"
GYP-01
9' - 0"
AT-02
8' - 0"
GBH-01
7' - 10"
AT-02
8' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
A T
-0
AT-01
9' - 0" AT-01
9' - 0"
GYP-01
9' - 0"
GYP-01
9' - 0"
AT-02
8' - 0"
AT-02
8' - 0"
GBH-01
7' - 10"
AT-01
8' - 0"
GBH-01
7' - 10"
GBH-01
7' - 10"
GBH-01
7' - 10"
GBH-01
7' - 10"
AT-01
9' - 0"
E
G
H
I
J
F
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.A.F.F. A.F.F.A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.A.F.F.
A.F.F.
A.F.F.A.F.F.
A.F.F.
A.F.F.A.F.F.A.F.F.
A.F.F.A.F.F.
A .F
.F
A .F
.F
A.F.F.
A.F.F.
A.F.F.
A.F.F.A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A .F
.F
A.F.F.A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.A.F.F.A.F.F. A.F.F.
A.F.F.
A .F
.F
A.F.F.
A.F.F.
A.F.F.A.F.F.
A.F.F.
S S
S S
S S
S S
S S
S S
A.F.F.
S S
S S
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
E
G
H
I
J
8 9 10 11 138.2 12 1.6
F
(EX.)W14X22 (EX.)W14X22 (EX.)W14X22 (EX.)W24X84
(EX.)W16X26
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(EX.)W16X40
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(EX.)W33X130 (EX.)W33X130
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(EX.)W16X40
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(EX.)W27X114 (EX.)W14X30 (EX.)W33X118
(EX.)W14X34 (EX.)W27X114
(EX.)W33X118
(EX.)W21X44(EX.)W14X30(EX.)W27X114
(EX.)W27X114 (EX.)W14X34 (EX.)W27X114
(EX.)W24X55
(E X
W
X
(EX.)W16X40
(E X
W
X
(E X
W
X
(EX.)W16X40(EX.)W24X84
(EX.)W16X26 (E
X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(E X
W
X
(EX.)W24X84 (EX.)W14X22
(EX.)W16X26
(EX.)W16X26
(E X
W
X
(E X
W
X
(EX.)W16X26
(EX.)W16X26
HATCHED AREA NOT
IN SCOPE OF WORK
PATIENT LIFT SYSTEM TRACK.
SHOWN FOR REFERENCE
ONLY. REFER TO 2/SF101 FOR
ATTACHMENT.
EXISTING WIDE
FLANGE JOISTS, TYP.
INDICATES FLOOR DRAIN
PENETRATION THROUGH EXISTING
SLAB. COORDINATE FINAL LOCATIONS
W/ ARCHITECHURAL PLANS. DRAINS
SHOULD BE INSTALLED PARALELL TO
FLOOR DECK, TYP.
(1) 5/8" Ø BOLT
L3x3x1/4 VERTICAL
STEEL ANGLE
L3x3x1/4 x 0'-6" LONG. DRILL &
EPOXY INTO EXISTING CONCRETE
DECK W/ (2) 1/2" Ø ANCHORS W/
2-3/4" EFFECTIVE EMBEDMENT, TYP.
@ BRACE & VERTICAL SUPPORT
ATTACHMENTS. SEE NOTES BELOW
FOR ANCHOR & EPOXY TYPE.
(1) 5/8" Ø BOLT
PROVIDE L3x3x1/4 x 0'-6" LONG MIN.
FOR ATTACHMENT TO TRACK CLIP.
ADJUST ANGLE LENGTH AS NEEDED
FOR ATTACHMENT PER
MANUFACTURER REQUIREMENTS
LIFT SYSTEM TRACK CLAMP &
TRACK CONNECTION BY
OTHERS
L3x3x1/4 STEEL
BRACE ANGLE
LIFT SYSTEM CONTROL BOX
BY OTHERS
V .I
.F
/2
V
.I .F
EXISTING CONCRETE
TOPPING OVER METAL
ROOF DECK
CEILING FINISH
NOTE:
1. PLACE SUPPORTS SHOWN IN THIS DETAIL EVERY 3' - 0" OF TRACK
LENGTH & AT ALL TRACK BENDS & CORNERS.
2. EPOXY ANCHORS TO BE HILTI HAS-V-36 (ASTM F1554 Gr. 36)
3. EPOXY SHALL BE HILTI HY-200+, INSTALLED IN ACCORDANCE W/
MANUFACTURER'S RECCOMENDATIONS, U.N.O.
4. PROVIDE ANGLE BRACES ALTERNATING IN THE TWO ORTHOGANAL
DIRECTIONS @ EACH VERTICAL LEG.
EQ EQ
1/2"
E Q
E Q
/2
E Q
E Q
1/4
LEVEL 5
1160.91
9'-0" A.F.F.
1154.91
IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO VERIFY EMBEDDED
UTILITIES & REINFORCING LOCATIONS
PRIOR TO DRILLING TO AVOID DAMAGING
/4
PROVIDE BRACING @
TRACK ENDS & AT
EVERY 3' - 0" OF
TRACK LENGTH
LIFT SYSTEM TRACK
LAYOUT BY OTHERS
ALTERNATE BRACE
DIRECTION. PROVIDE @
MIN. (3) BRACES IN EACH
ORTHOGONAL DIRECTION
DIAGONAL BRACE
ANGLE, TYP.
PROVIDE BRACING @
ALL TRACK BENDS,
TYP.
O .C
M
A X
CONFIRM BRACING MAXIMUM
SPACING REQUIREMENTS W/
FIELD CONDITIONS &
MANUFACTURER SPECIFICATIONS
NEW DRAIN PENETRATION IN
EXISTING FLOOR. ENSURE
DRAIN IS INSTALLED
PARALLEL TO DECK FRAMING
METAL DECK RIB
PLAN VIEW
ELEVATION VIEW
EXISTING CONCRETE DECK
NEW DRAIN PENETRATION IN
EXISTING FLOOR. ENSURE
DRAIN IS INSTALLED
PARALLEL TO DECK FRAMING
EXISTING CONCRETE DECK
METAL DECK RIB
DESIGN/BUILD
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
FINAL DESIGN - FOR CONSTRUCTION
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2 :2
A
M
Sheet of
SF101
PATIENT LIFT SYSTEM
SUPPORT PLAN
RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/21/2018
TJM TJM
1/8" = 1'-0"
PATIENT LIFT SYSTEM SUPPORT PLAN
3/4" = 1'-0"
PATIENT LIFT SYSTEM TRACK ATTACHMENT
DESIGN CRITERIA
1. REFERENCE CODE
a. UFC 3 301 01 "STRUCTURAL DESIGN"
b. 2015 INTERNATIONAL BUILDING CODE
2. BUILDING DESIGN LOADS
a. LIVE LOAD INFORMATION
1. FLOOR LOADS & FUTURER FLOORS: 100 PSF
2. MECHANICAL/ELECTRICAL: 150 PSF
3. FLOOR CONCENTRATED LOADS: 2000 lbs./2.5 SQ. FT.
4. ROOF LIVE LOAD: 20 PSF
b. DEAD LOAD INFORMATION
1. FLOOR DEAD LOAD: WEIGHT OF MATERIALS
2. ROOF DEAD LOAD: WEIGHT OF MATERIALS
c. EQUIPMENT & LIFT LOADS:
1. BASED ON THE MANUFACTURERS DATA OR AS INTERPRETED BY THE
IBC.
d. RISK CATEGORY: IV
e. SEISMIC DESIGN INFORMATION
1. SEISMIC IMPORTANCE FACTOR (Ie) = 1.5
2. SEISMIC DESIGN CATEGORY = C
3. 0.2 SECOND SPECTRAL RESPONSE ACCELERATION (SS) = 0.216
4. 1 SECOND SPECTRAL RESPONSE ACCELERATION (S1) = 0.124
5. 0.2 SECOND DESIGN SPECTRAL RESPONSE ACCELERATION (SDS) = 0.21
6. 1 SECOND DESIGN SPECTRAL RESPONSE ACCELERATION (SD1) = 0.103
7. SITE CLASS = C
8. SEISMIC FORCE RESISTING SYSTEM: NOT AFFECTED BY LIFT
EQUIPMENT
GENERAL
1. THE INTENT OF THESE DRAWINGS IS TO SHOW ALL ITEMS NECESSARY TO COMPLETE
THE STRUCTURE. FOR ITEMS, METHODS, AND/OR MATERIALS NOT SHOWN, THE
MINIMUM REQUIREMENTS OF THE REFERENCE CODE SHALL GOVERN. ALL WORK AND
CONSTRUCTION SHALL COMPLY WITH ALL OTHER APPLICABLE BUILDING CODES,
REGULATIONS, AND SAFETY REQUIREMENTS.
2. THROUGHOUT THESE DRAWINGS, THE TERM ENGINEER REFERS TO THE ENGINEER OF
RECORD FOR THIS PROJECT. OTHER ENGINEERING DISCIPLINES WILL BE EXPLICITLY
DESCRIBED. THE TERM ARCHITECT REFERS TO THE ARCHITECT OF RECORD FOR THIS
PROJECT.
3. METHODS, MEANS, AND MATERIALS ARE EXPLICITLY CALLED OUT IN THESE NOTES.
ANY DEVIATION OR PROPOSED CHANGE IS TO BE COMMUNICATED IMMEDIATELY TO
THE ENGINEER. NO DEVIATION OR CHANGE IS ACCEPTABLE WITHOUT WRITTEN
APPROVAL BY THE VETERANS AFFAIRS.
4. IT SHALL BE THE CONTRACTOR’S SOLE RESPONSIBILITY TO DESIGN AND PROVIDE
ADEQUATE SHORING, BRACING, AND FORMWORK, ETC. AS REQUIRED FOR THE
PROTECTION OF LIFE AND PROPERTY DURING THE CONSTRUCTION OF THE BUILDING.
MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES DURING
CONSTRUCTION SHALL BE MAINTAINED PER ASCE STANDARD NO. 37-02 "DESIGN
LOADS ON STRUCTURES DURING CONSTRUCTION".
5. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS WITH THE
ARCHITECTURAL, CIVIL, ELECTRICAL, AND MECHANICAL DRAWINGS BEFORE
PREPARING SHOP DRAWINGS, FABRICATION, OR CONSTRUCTION. SEE
ARCHITECTURAL, CIVIL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR SIZE AND
LOCATIONS OF PIPES, SLEEVES, PITS, VENTS, DUCTS, ROOF OPENINGS, TRENCHES,
EQUIPMENT PADS, MISCELLANEOUS IRON, AND/OR ANY DETAILS NOT SHOWN ON THE
STRUCTURAL DRAWINGS.
6. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL
DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION. ANY
DISCREPANCIES THAT OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE
VETERANS AFFAIRS PRIOR TO START OF CONSTRUCTION SO THAT A CLARIFICATION
CAN BE ISSUED. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT
DOCUMENT OR ANY CODE REQUIREMENTS SHALL BE CORRECTED BY THE
CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE OWNER,
ARCHITECT, OR ENGINEER
7. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL
NOTES, SPECIFICATIONS, AND TYPICAL DETAILS. WHERE NO NOTE OR DETAIL IS GIVEN,
CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
8. ALL CONTRACTOR DESIGNED ELEMENTS SHALL BE DESIGNED BY A LICENSED
PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE THE FACILITY IS
LOCATED. CONTRACTOR SHALL SUBMIT CALCULATIONS CERTIFYING THAT ELEMENTS
ARE DESIGNED FOR THE UNFACTORED LOADS STATED.
9. SHOP DRAWINGS PREPARED BY SUPPLIERS AND SUBCONTRACTORS SHALL BE
REVIEWED BY THE GENERAL CONTRACTOR PRIOR TO SUBMITTING TO THE ENGINEER.
10. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS SHOWING SIZE, METHOD OF
ANCHORAGE, AND WEIGHT OF ALL EQUIPMENT THAT IS TO BE SUPPORTED BY THE
STRUCTURE FOR REVIEW BY THE ENGINEER. THIS IS TO DETERMINE ADEQUACY OF
THE STRUCTURE PRIOR TO ORDERING.
11. SHOP DRAWINGS AND SUBMITTALS:
A. AT A MINIMUM, SUBMIT THE FOLLOWING ITEMS FOR REVIEW BY THE ENGINEER.
1. MATERIAL CERTIFICATES FOR STRUCTURAL STEEL
2. PRODUCT SUBMITTAL FOR EPOXY ANCHORS
3. STRUCTURAL PRODUCT DATA SUBMITTALS
4. ADDITIONAL SUBMITTALS MAY BE REQUIRED IN THE STATEMENT OF
SPECIAL INSPECTIONS AND SPECIFICATIONS.
12. SHOP DRAWINGS AND OTHER ITEMS SHALL BE SUBMITTED TO THE ENGINEER FOR
REVIEW PRIOR TO FABRICATION. ALL CONTRACTOR SHOP DRAWINGS SHALL BE
REVIEWED BY THE GENERAL CONTRACTOR BEFORE SUBMITTAL AND STAMPED
"APPROVED BY CONTRACTOR". THE ENGINEER'S REVIEW IS INTENDED TO REVIEW FOR
CONFORMANCE WITH THE DESIGN CONCEPT AND GENERAL COMPLIANCE WITH THE
RELEVANT CONTRACT DOCUMENTS. THE ENGINEER'S REVIEW DOES NOT RELIEVE THE
CONTRACTOR OF THE SOLE RESPONSIBILITY TO REVIEW, CHECK, AND COORDINATE
THE SHOP DRAWINGS PRIOR TO SUBMISSION. THE CONTRACTOR REMAINS SOLELY
RESPONSIBLE FOR ERRORS AND OMISSIONS ASSOCIATED WITH THE PREPARATION OF
SHOP DRAWINGS AS THEY PERTAIN TO MEMBER SIZES, DETAILS, DIMENSIONS, ETC.
REPRODUCTIONS OF CONTRACT DOCUMENTS SHALL NOT BE USED TO PREPARE
SHOP DRAWINGS. SHOP DRAWINGS AND SUBMITTALS SHALL BE SUBMITTED
"CONTRACTOR APPROVED".
13. WHERE A PROPRIETARY MANUFACTURER IS STATED, A PRODUCT THAT PROVIDES THE
EQUIVELANT OR BETTER PERFORMANCE MAY BE USED PROVIDED IT MEETS
NECESSARY APPROVAL CODES.
STRUCTURAL STEEL
1. ALL DESIGN, FABRICATION AND ERECTION SHALL CONFORM TO THE AISC STEEL
CONSTRUCTION MANUAL. WELDING SHALL CONFORM TO THE LATEST AWS AND AISC
SPECIFICATIONS.
2. WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE BEST PRACTICE AND WITHIN THE
TOLERANCES SPECIFIED IN THE AISC SPECIFICATION FOR STRUCTURAL STEEL.
3. IT IS SPECIFICALLY NOTED THAT BURNED HOLES ARE NOT ACCEPTABLE UNLESS
SPECIAL PERMISSION IS GIVEN BY ENGINEER.
4. ALL SHOP FABRICATED WORK SHALL BE DONE IN A SHOP APPROVED BY THE
GOVERNING AGENCY. FABRICATOR SHALL SUBMIT PROGRAM OF WELDING
INSPECTION TO ENGINEER FOR APPROVAL.
5. ALL STRUCTURAL STEEL SHALL BE AS FOLLOWS UNLESS NOTED OTHERWISE:
a. CONNECTION PL AND MISC STEEL ASTM A36
b. ANGLE ASTM A36
c. THREADED ROD ASTM A36
6. ALL HIGH STRENGTH BOLTS SHALL BE ASTM A325-N TYPE UNLESS OTHERWISE NOTED.
7. ALL BOLTS USED FOR ERECTION SHALL BE ASTM A325 TYPE WITH THREADS
EXCLUDED FROM SHEAR PLANES.
8. ALL PLAIN ANCHORS SHALL BE A36. ALL ANCHOR BOLTS SHALL COMPLY WITH ASTM
F1554. 3" MINIMUM CONCRETE COVER WILL BE PLACED AROUND ALL ANCHOR BOLTS
EXPOSED TO WEATHER, UNLESS OTHERWISE NOTED.
9. SUBMIT CONTRACTOR SHOP DRAWINGS STAMPED "APPROVED BY CONTRACTOR" FOR
THE FABRICATION AND ERECTION OF ALL ASSEMBLIES OF STRUCTURAL STEEL WORK.
INCLUDE PLANS AND ELEVATIONS AT NOT LESS THAN 1/8" TO 1'-0" SCALE AND INCLUDE
DETAILS OF SECTIONS AT NOT LESS THAN 1" TO 1'-0" SCALE.
10. NO FINISH FABRICATION SHALL BE COMMENCED, OR MATERIAL DELIVERED TO THE
JOB UNTIL THE VETERANS AFFAIRS HAS REVIEWED AND APPROVED THE SHOP
DRAWINGS.
11. ALL STRUCTURAL STEEL SHALL BE PAINTED WITH ONE SHOP COAT OF ZINC
CHROMATE PRIMER OR EQUAL. AFTER ERECTION, FIELD CONNECTIONS SHALL BE
TOUCHED UP. DO NOT PAINT PORTION OF STEEL TO BE EMBEDDED IN CONCRETE,
HEADED ANCHOR STUDS, FRAYING SURFACES, OR AREAS TO RECEIVE FIRE
PROOFING. EXPOSED STEEL MEMBERS ARE SPECIFIED TO BE HOT-DIPPED
GALVANIZED OR STAINLESS STEEL.
1/2" = 1'-0"
TYPICAL TRACK ATTACHMENT PLAN VIEW
Revisions: Date:
3/4" = 1'-0"
FLOOR DRAIN PENETRATION
| 1-GI sheets |
| J-GI001 - TITLE SHEET |
| Sheets |
| J-GI001 - TITLE SHEET |
| J-GI002 - PROJECT INFORMATION SHEET |
| Sheets |
| J-GI002 - PROJECT INFORMATION SHEET |
| J-GI003 - PARTITION TYPES - TYPICAL MOUNTING HEIGHTS |
| Sheets |
| J-GI003 - PARTITION TYPES / TYPICAL MOUNTING HEIGHTS |
| J-GI004 - STANDARD ABBREVIATION |
| Sheets |
| J-GI004 - STANDARD ABBREVIATION |
| J-GI005 - EXISTING CONDITIONS - SCOPE OF WORK |
| Sheets |
| J-GI005 - EXISTING CONDITIONS - SCOPE OF WORK |
| J-GI111 - DEPARTAMENTAL USE PLAN - ZONE J |
| Sheets |
| J-GI111 - DEPARTAMENTAL USE PLAN - ZONE J |
| J-GI112 - DEDUCTIVE ALTERNATE #1 |
| Sheets |
| J-GI112 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #1 |
| J-GI113 - DEDUCTIVE ALTERNATE #2 |
| Sheets |
| J-GI113 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #2 |
| J-GI114 - DEDUCTIVE ALTERNATE #3 |
| Sheets |
| J-GI114 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #3 |
| J-GI115- DEDUCTIVE ALTERNATE #4 |
| Sheets |
| J-GI115 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #4 |
| 2-AD sheet |
| Sheets |
| J-AD101 - DEMOLITION FLOOR PLAN - ZONE J |
| J-GI111 - DEPARTAMENTAL USE PLAN - ZONE J |
| 3-AE sheets |
| J-AE101 - NEW FLOOR PLAN - ZONE J |
| Sheets |
| J-AE101 - NEW FLOOR PLAN - ZONE J |
| J-AE102 - NEW WORK ROOF PLAN - ZONE J |
| Sheets |
| J-AE102 - NEW WORK ROOF PLAN - ZONE J |
| J-AE103 - DOOR SCHEDULE & DOOR - FRAME TYPES |
| Sheets |
| J-AE103 - DOOR SCHEDULE & DOOR / FRAME TYPES |
| J-AE111 - REFLECTED CEILING PLAN |
| J-AE111 - REFLECTED CEILING PLAN |
| Sheets |
| J-AE103 - DOOR SCHEDULE & DOOR / FRAME TYPES |
| J-AE111 - REFLECTED CEILING PLAN |
| J-AE301 - BUILDING SECTIONS |
| Sheets |
| J-AE301 - BUILDING SECTIONS |
| J-AE501 - WALL - CEILING DETAILS |
| Sheets |
| J-AE501 - WALL - CEILING DETAILS |
| J-AE502 - ARCHITECTURAL DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE503 - ARCHITECTURAL DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE504 - CASEWORK DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE505 - CASEWORK DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| 4- IN sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN102 - FINISHES SCHEDULES |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN103 - FINISH SELECTIONS |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN202 - SIGNAGE TYPES |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN301 - INTERIOR VIEWS |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| 5- QH sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH101 - EQUIPMENT PLAN - ZONE J |
| J-QH401 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH402 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH403 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH404 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH405 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
| Sheets |
| J-QH406 - ENLARGED VIEWS AND INTERIOR ELEVATIONS |
File details come from the government source that posted it. Updated .