This architectural drawing set and mechanical plans specify renovations for patient privacy in Zone J at the Veterans Affairs Medical Center in Salem, Virginia. The project involves demolishing existing HVAC, plumbing, and ductwork; installing new systems including air handlers, VAV boxes, exhaust fans, and related controls; modifying ceiling, wall, flooring, and casework finishes; and reconfiguring rooms for improved patient care and workflow. Renovations will update an existing 4th floor wing to provide positive and negative pressure isolation rooms along with associated support spaces.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MH001
NOTES AND ABBREVIATIONS
MECHANICAL LEGENDS,
PRIVACY - ZONE J
RENOVATE FOR PATIENT
VAMC SALEM VIRGINIA
658-18-101
143 RLD JAH
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
Revisions: Date:
"A" x "B"
T
LEGEND AND ABBREVIATIONSGENERAL NOTES
THE PIPING SYSTEMS SHALL BE FLUSHED CLEAN PRIOR TO CONNECTION TO EQUIPMENT.16.
AND/OR AS INDICATED.
INSULATE DUCTWORK AND PIPING IN ACCORDANCE WITH SPECIFICATION SECTION 23 07 11 15.
1" W.G. WITH SEAL CLASS A.
OR ROUND DUCTWORK, AS INDICATED ON THE PLANS. PROVIDE SMACNA PRESSURE CLASS
RETURN, EXHAUST AND TRANSFER AIR DUCTWORK SHALL BE SINGLE WALL RECTANGULAR 14.
PRESSURE CLASS 1" W.G. WITH SEAL CLASS A.
RECTANGULAR OR ROUND DUCTWORK, AS INDICATED ON THE PLANS. PROVIDE SMACNA
SUPPLY DUCTWORK DOWNSTREAM OF THE VAV BOXES SHALL BE SINGLE WALL 13.
STATIC PRESSURE WITH SEAL CLASS A.
PROVIDE SMACNA STATIC PRESSURE CLASS AS REQUIRED FOR SCHEDULED EXTERNAL
RECTANGULAR FOR INSTALLATION OF FIRE DAMPERS AT CHASE WALL PENETRATIONS.
FLAT OVAL EXCEPT DUCT ROUTED THROUGH MECHANICAL DUCT CHASE WHICH SHALL BE
SUPPLY DUCTWORK UPSTREAM OF THE VAV BOXES SHALL BE SINGLE WALLED ROUND OR 12.
MAINTENANCE OF UNIT AND CONTROLS.
VAV BOXES SHALL BE INSTALLED TO MAINTAIN ACCESS CLEARANCE AS REQUIRED FOR 11.
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
REQUIRED AIRFLOW. PROVIDE FINAL TEST AND BALANCE REPORT. SEE THE
LOCATIONS SHOWING FULL OPEN/CLOSED POSITIONS AND DAMPER SETTING FOR
AS SCHEDULED OR SHOWN ON THE DRAWINGS. PROVIDE MARKERS AT ALL DAMPER
BALANCE ALL AIR DISTRIBUTION DEVICES, EXHAUST FANS, AND OUTSIDE AIR QUANTITIES 10.
MATERIAL TO MAINTAIN FIRE RATING OF THE BARRIER.
WALLS/FLOORS/CEILINGS BY DUCTWORK, PIPING, ETC., WITH U.L. LISTED FIRE STOPPING
THE CONTRACTOR SHALL FIRESTOP ALL PENETRATIONS OF FIRE RATED 9.
MECHANICAL EQUIPMENT.
PROVIDE FLEXIBLE NEOPRENE DUCT CONNECTORS BETWEEN DUCTWORK AND ISOLATED
ALL ROTATING MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH VIBRATION ISOLATION. 8.
COORDINATE WITH DETAILS.
MAY BE USED FOR FINAL CONNECTION TO SUPPLY/RETURN GRILLES (MAX. LENGTH 5').
SHOWN PROVIDE DUCT SAME SIZE AS GRILLE NECK SIZE. PRE-INSULATED FLEXIBLE DUCT
MANUAL BALANCING DAMPER AT EVERY TAKE-OFF. WHERE DUCT RUN-OUT SIZE IS NOT
ALL DUCT TAKE-OFFS SHALL BE INSTALLED AS SHOWN BY DETAILS ON THE PLANS WITH A 7.
SELECTED.
INSTALLATION IF ACCESS WILL BE HINDERED SO AN ALTERNATE LOCATION CAN BE
SPECIALTIES IN EASILY ACCESSIBLE LOCATIONS. ADVISE THE COR IN ADVANCE OF
INSTALL ALL DUCT MOUNTED DEVICES (DAMPERS, ACCESS DOORS, ETC.) AND PIPING 6.
LOCATIONS SPECIFIED.
TRANSITIONS OR OFFSETS 'WILL NOT BE ALLOWED'. PROVIDE DUCT ACCESS DOORS AT
DUCT SYSTEMS SHALL BE INSTALLED PER SMACNA STANDARDS. SHARP ANGLED
RECTANGULAR SUPPLY/RETURN/EXHAUST DUCT SYSTEMS. ANY OFFSETS REQUIRED IN
UNITS. PROVIDE TURNING VANES IN ALL 90 DEGREE ELBOWS IN ALL LOW PRESSURE
PROVIDE CURVED RADIUS ELBOW AT FIRST SUPPLY & RETURN FITTING FOR ALL HVAC 5.
TIME WITH DRAWING OF PROPOSED CHANGES.
COST OR TIME, PROVIDE COR WITH PROPOSED ADDITIONAL COSTS AND/OR
DIRECTED BY COR. WHERE PROPOSED CHANGES REQUIRE ADDITIONAL
PROBLEM CONDITIONS UNTIL APPROVAL OF PROPOSED CHANGE UNTIL
PROCEED WITH CONSTRUCTION OF DUCT WORK OR PIPING IN AREA OF
RESIZING AND/OR REROUTING OF DUCT WORK AND/OR PIPING. DO NOT
PREPARE SUPPLEMENTAL DRAWING(S) AS NECESSARY SHOWING PROPOSED
ROUTING, OR PIPING SYSTEMS SIZING AND/OR ROUTING, NOTIFY COR AND
WHERE CONDITIONS REQUIRE A CHANGE IN DUCT WORK SIZES AND/OR4.
DUCT DIMENSIONS ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.3.
CODES, THE MOST STRINGENT SHALL ALWAYS GOVERN.
AND LOCAL CODE OFFICIAL REQUIREMENTS. IN THE EVENT OF A CONFLICT BETWEEN
2017 EDITION OF THE INTERNATIONAL MECHANICAL CODE, 2018 EDITION OF THE NFPA 90A,
THE HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS SHALL COMPLY WITH THE 2.
PROVIDE ADDITIONAL OFFSETS AND FITTINGS AS NECESSARY.
THE MECHANICAL INSTALLATION W/ THE STRUCTURE AND OTHER TRADES AND SHALL
DUCTWORK, PIPING, ETC. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING
THE DRAWINGS SHOW THE GENERAL ARRANGEMENT AND LOCATION OF EQUIPMENT, 1.
SD
CO
P
8"
S1
8"
R1
XXX
NO.
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Sheet of
Final Design-For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2
:2
A
M
DESIGN/BUILD
POINT OF DISCONNECTION
POINT OF CONNECTION NEW WORK TO EXISTING
SQUARE ELBOW WITH TURNING
VANES
DUCTWORK, SIZE SHOWN IN INCHES
MANUAL BALANCING DAMPER
THERMOSTAT
DUCT SMOKE DETECTOR
CARBON MONOXIDE SENSOR
DUCT STATIC PRESSURE SENSOR
EQUIPMENT LABEL
SUPPLY DIFFUSER DESIGNATION
(TYPE, CFM, NECK SIZE)
RETURN DIFFUSER DESIGNATION
(TYPE, CFM, NECK SIZE)
DIFFUSER, DIRECTION OF FLOW AS
INDICATED
RETURN OR TRANSFER AIR OUTLET
EXHAUST GRILLE
AC AIR CONDITIONER DESIGNATION
AHU AIR HANDLING UNIT DESIGNATION
AFF ABOVE FINISHED FLOOR
DDC DIRECT DIGITAL CONTROLS
OA OUTSIDE AIR
RA RETURN AIR
EA EXHAUST AIR
UNO UNLESS NOTED OTHERWISE
D CONDENSATE DRAIN
CHS CHILLED WATER SUPPLY
CHR CHILLED WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWR HEATING HOT WATER RETUN
BG BELOW GRADE
TYP. TYPICAL
VAV VARIABLE AIR VOLUME
W.G. WATER GAUGE
AFMS AIR FLOW MONITORING STATION
02/28/19
8X6
8X4
8X4
8X6
8X4
8X6
8X10
8X6 8X6
8X6
8X68X4
8X4 8X6
8X4
8X6
8X6
8X4
8X6
8X6
8X4
8X4
12X8
14X10
18X10
14X812X8
16X10
10X12
8X8
10X12 8X8
8X6
12X10
4X8
8X6
8X4
8X4
8X6
8X4
8X4
8X4
8X4
8X6 8X6 8X6
8X6
8X6
8X6
8X6
8X6
8X4
8X4
8X8 10X8
12X12
14X8
16X8 16X10
14X10
14X1216X12
X
X
X
X
X
X
X
X
X
X
10X6
10X10
8X6 10X8
10X6 8X4
8X12
10X6
8X4
8X6
8X6
6X8
10X8
12X8
8X8
8X8
10X12
20X
8X4
4X8
8X4
8X6
8X4
8X8
8X4
10X6
32X16
20X
8X4
8X4 12X8
24X12
8X4
8X6
10X8
8X4
X
8X10
14X10
8X8
18X10
16X10
14X8
8X8
8X8
8X6
8X4 10X6
8X4
8X4
8X4
8X6
8X6
20X10
10X6
8X8
10X6 10X8
X
24X16
EXHAUST AIR 48X12
RETURN AIR 24X16 (ABOVE)
SUPPLY AIR 28X12 (BELOW)
SUPPLY AIR 34X16
EXHAUST AIR 12X8
E
F
G
H
I
J
8 9 10 11 1312
H.6
DEMOLITION NOTES
REMOVE DUCT TO HERE. CUT, CAP AND INSULATE TO MATCH EXISTING.
CONTROLS.
AFCV - DEMOLISH AIR FLOW CONTROL VALVE COMPLETELY INCLUDING ALL
DEMOLISH ALL INCLUDING AFCVS (AUTOMATIC FLOW CONTROL VALVES).
CHASE TO PENTHOUSE. SEE DWG MD201 FOR ADDITIONAL INFORMATION.
BACK TO POINT OF DISCONNECTION AT DUCT PENETRATION OF RATED
DEMOLISH EXISTING BRANCH DUCT FROM ISOLATION ROOMS COMPLETELY
DEMOLISH EXISTING BRANCH DUCT RUN-OUT COMPLETELY.
SUPPLY DUCTS.
OUTLETS, INSULATION, ALL FITTINGS AND ACCESSORIES. TYPICAL FOR ALL
DEMOLISH EXISTING DUCTWORK COMPLETELY INCLUDING SUPPORTS, AIR
MD101
PLAN - ZONE J
MECHANICAL HVAC DEMO
PRIVACY - ZONE J
RENOVATE FOR PATIENT
VAMC SALEM VIRGINIA
658-18-101
143 RLD JAH
1/8" = 1'-0"1
MECHANICAL HVAC DEMO PLAN - ZONE J
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
Revisions: Date: 61 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Sheet of
Final Design-For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2
:2
A
M
DESIGN/BUILD
J
KEY PLAN
PLAN
NORTH
C H
R
H W
R
C H
S
H W
S
F
G
H
I
J
8 9 10 11 1312
H.6
DEMOLITION NOTES
ADDITIONAL INFORMATION.
SEE LARGE SCALE DRAWING MD201 OF SERVICE BAY FOR
BE DEMOLISHED COMPLETELY.
TYPICAL DEMOLITION HASH LINES. INDICATING PIPE LINES TO
FITTINGS, VALVES, AND JACKETING.
CONTROLS, DRAIN PIPING, CHS/CHR PIPING RUNOUTS, ALL
COOLING ONLY PANELS COMPLETELY INCLUDING SUPPORTS,
DEMOLISH EXISTING CEILING MOUNTED HYDRONIC RADIANT
INSULATION AND JACKETING.
FITTINGS, VALVES, AND ACCESSORIES, PIPING SUPPORTS,
CONTROLS, DRAIN PIPING, CHS/CHR, HWS/HWR PIPING, ALL
HEATING/COOLING PANELS COMPLETELY INCLUDING SUPPORTS,
DEMOLISH EXISTING CEILING MOUNTED HYDRONIC RADIANT
PIPING, SUPPORTS, INSULATION AND JACKETING.
ADDITIONAL INFORMATION. DEMOLISH COMPLETELY INCLUDING
DISCONNECTION IN SERVICE BAY. SEE DWG MD201 FOR
DEMOLISH EXISTING PIPING BACK TO POINTS OF 1
MD102
PLAN - ZONE J
MECHANICAL PIPING DEMO
PRIVACY - ZONE J
RENOVATE FOR PATIENT
VAMC SALEM VIRGINIA
658-18-101
143 RLD JAH
1/8" = 1'-0"1
MECHANICAL PIPING DEMO PLAN - ZONE J
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
Revisions: Date: 62 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Sheet of
Final Design-For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2
:2
A
M
DESIGN/BUILD
J
KEY PLAN
PLAN
NORTH
GRR
GR
CH
CHR
HWH
HWHR
143-AHU-4J1
143-AHU-4J2
143-P-4J4
143-ERC-4J2E
143-P-4J3
143-PF-4J2E
143-P-4J1
143-P-4J2
28X12 (BELOW)24X16 (ABOVE)
34X16
26X16
X L
O U
V E
R
26X16
X
A B
O V
E
24X18 (UP) (TYP.)
24X16 (UP)
22X10 (UP)
14X10 (DN)
143-AHU-4J1
143-AHU-4J2
48X12
PNEUMATIC, EXISITNG DAMPER CONTROLS ARE PNEUMATIC.
REQUIRED. EXISTING STEAM, GLYCOL AND WATER COIL CONTROL VAVLES ARE
NEXT DETECTION DEVICE TO REMAIN OR BACK TO FIRE ALARM PANEL AS
POINT OF ORIGIN. SMOKE DETECTORS SHALL BE DEMOLISHED BACK TO
TIGHT. ELECTRONIC POWER AND CONTROL SHALL BE DEMOLISHED BACK TO
TO POINT OF CONNECTION TO MAIN LINES AND SHALL BE CAPPED AIR
PNEUMATIC TUBING, PIPING AND SUPPORTS SHALL BE DEMOLISHED BACK
AND ALL INTERCONNECTING CONTROLS, DEVICES AND CIRCUITING. ALL
AND CONTROL CIRCUITING; ELECTRONIC CONTROL DEVICES AND CIRCUITING;
FIRE DETECTION CONTROLS, DEVICES AND CIRCUITING; ELECTRICAL POWER
CONTROLS, DEVICES AND TUBING; DDC CONTROLS, DEVICES AND CIRCUITING;
EQUIPMENT INDICATED TO BE DEMOLISHED INCLUDING: PNEUMATIC
TO DEMOLISH THE EXISTING CONTROL SYSTEM PRESENTLY SERVING THE
WING J. IT IS THE DECLARED AND ACKNOWLEDGED INTENTION AND MEANING
EXISTING CONTROL CENTER FOR HVAC SYSTEMS SERVING THE 4TH FLOOR
DEMOLISH DUCT TO CENTER CORE AREA. SEE DWG MD101.
ADDITIONAL INFORMATION.
AND ANY ACCESSORIES. SEE SECTIONS, PLANS, AND DETAILS THIS DWG FOR
INCLUDING FILTERS, COILS, SUPPORTS, INSULATION, DAMPERS, CONTROLS,
DEMOLISH EXISTING OUTSIDE AIR DUCTWORK BACK TO AHU COMPLETELY
NEW SYSTEM/UNIT.
PROVIDE SIZE, LOCATION, AND CAPACITY ARE SUITABLE FOR SUPPORT ON
AND DUCTWORK. EXISTING CONCRETE PAD MAY BE REUSED FOR NEW UNIT
ELEC. POWER, CONTROLS, PIPING, SUPPORTS, VALVES, FITTINGS, DRAINS,
DEMOLISH EXISTING AHU-4J1 AND AHU-4J2 COMPLETELY INCLUDING ALL
AND INSULATION.
ERC-4J2E COMPLETELY INCLUDING CONTROLS, PIPING, VALVES, SUPPORTS,
DEMOLISH EXISTING EXHAUST DUCTWORK, FILTERS PF-4J2E AND COIL
DAMPER. FINISHED INSTALLATION SHALL PROVIDE RATED CHASE.
REMOVABLE STAINLESS STEEL ACCESS PANEL TO PROVIDE ACCESS TO FIRE
DECOMMISSION FIRE DAMPER TO CLOSED POSITION. COVER OPENING WITH
DAMPER TO REMAIN. SEAL OFF DUCT FROM 4TH FLOOR AT PENETRATION.
ADDITIONAL INFORMATION. DUCT PENETRATION INTO CHASE WITH FIRE
DEMOLISH EXISTING DUCTWORK COMPLETELY. SEE DWG MD101 FOR
FITTINGS, VALVES, AND ACCESSORIES.
COMPLETELY INCLUDING ELEC. POWER, CONTROLS, SUPPORTS, INSULATION,
DEMOLISH EXISTING PUMPS P-4J1, P-4J2, P-4J3 AND P-4J4
NOTES 1 AND 2 ABOVE.
INCLUDING CHS/CHR, LPS/LPR, HWS/HWR AS PREVIOUSLY PRESCRIBED IN
DEMOLISH BRANCH RUN-OUT PIPING TO AHU-4J1, AHU-4J2 COMPLETELY
FITTINGS AND JACKETING.
COMPLETELY INCLUDING SUPPORTS, CONTROLS, VALVES, INSULATION,
DEMOLISH ERC-4J2E, PF-4J2E AND GR/GRR PIPING TO AHU-4J2
INFORMATION.
DEMOLISH LOUVER. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL
DEMOLITION NOTES
SCALE: 1/4" = 1'-0"
SERVICE BAY 4J-118 PIPING DETAIL
SCALE: 1/4" = 1'-0"
SERVICE BAY 4J-118 DUCTWORK DETAIL
PRIVACY - ZONE J
RENOVATE FOR PATIENT
VAMC SALEM VIRGINIA
658-18-101
143 RLD JAH
Revisions: Date:
DEMO PLANS
MECHANICAL ROOM SECTION
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Sheet of
Final Design-For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2
:2
A
M
DESIGN/BUILD
J
KEY PLAN
PLAN
NORTH
02/28/19
MD201
3 4
20 21
24 25 26
E
G
H
I
J
8 9 10 11 138.2 12 1.6
F
VAV
VAV
2 VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
20 VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
8"ø S1
200 CFM
12"x12" E1
550 CFM
10"ø S1
305 CFM
6"x6" E2
105 CFM
6"ø S1
90 CFM
6"x6" E1
115 CFM
10"x12"8"ø
8"x8"
6"x6"
8"x8" R1
65 CFM
6"ø S1
100 CFM
"ø
"x
12"x12" E1
550 CFM
"x
10"ø ø10"
"ø
6"ø
12"x12"
"x
12"x12"
"x
6"x6"
8"ø S1
200 CFM
10"ø S1
300 CFM
6"ø S1
100 CFM
6"x6" E2
100 CFM
6"x6" E1
115 CFM
"x
8"ø
10"ø 10"x8"
"x
12"x12" R1
300 CFM
18"/12"
8"ø S1
200 CFM
10"ø S1
300 CFM
6"x6" R1
40 CFM
"x
"x
8"x8" 10"x8"
"x
"x
"12"x12"
"x
18"x14"
6"ø S1
100 CFM
10"x10" R1
205 CFM
"x
10"ø
10"ø S1
305 CFM
10"ø S1
305 CFM
"x
"x
6"x6" E2
100 CFM
6"x6" E2
100 CFM
10"ø S1
300 CFM
6"x6" E2
115 CFM
"x
"x
12"x10"
"x
" 6"x6"
54"/16"
"x
12"x8" 6 "ø
"ø
8"x12"
10"ø
"ø
8"x12"
"x
10"ø 8"ø
10"x10"
10"ø
8"x12"
"ø
10"ø
8"x12"
"ø
"x
10"ø
"x
10"ø
12"ø
"x
"x
10"ø10"ø
"ø 8"ø
6"ø
10"x10" 10"x8"
"ø
6"ø
"ø
24"/14"
12"x8"
8"ø
6"ø
8"x12"
8"x12"
"x
"ø
"x
"x
8"x12"
"ø
10"ø
10"ø
8"x12" ø10"
8"x8"
"ø
14"x12"
"ø
6"ø 8"ø
"ø
"ø
8"x8"
"x
8"x8"
12"x12"
6"ø
8"ø
6"ø
8"ø
8"x8"
"x
8"x8"
10"x8" 16"x14" 28"x16"
"x
12"x12"
"x
"x
16"x12"12"x12" 10"x10"
"x
8"x8"
"x
"x
"x
" 10"x8"
12"x10" 10"x10"
"x
8"x8"
"x
8"x8"
"x
"x
18"x24"
"x
"x
"6"x6"
"x
"x
"x
8"x8"
"x
6"x6"
"x
8"x8"
6"x6"
6"x6"
"x
12"x10"
6"x6"
"x
"x
"x
12"x10"
8"ø
8"ø
"x
"x
10"x10"
6"x6"
"x
8"x8"
"x
"x
"x
"x
8"ø S1
170 CFM
8"ø S1
170 CFM
6"ø S1
100 CFM
8"ø S1
250 CFM
8"ø S1
150 CFM
18"x18" R1
730 CFM
6"ø S1
100 CFM
6"ø S1
100 CFM
6"x6" R1
65 CFM
6"x6" R1
65 CFM
8"ø S1
200 CFM
6"ø S1
65 CFM
6"x6" E1
100 CFM
8"x8" R1
150 CFM
6"x6" E2
100 CFM
6"x6" E2
100 CFM
6"x6"
E2
100 CFM
10"ø S1
290 CFM
10"x10" R1
190 CFM
6"x6" E2
100 CFM
6"x6" E2
115 CFM
10"x10" R1
205 CFM
10"ø S1
320 CFM
12"ø S1
380 CFM
12"x12" R1
280 CFM
6"x6" E2
100 CFM
6"x6" E2
0 CFM
10"x10"
R1
205 CFM
10"ø S1
305 CFM
6"x6" E2
100 CFM
10"x10" R1
205 CFM
10"ø S1
305 CFM 10"ø S1
305 CFM
12"x12" R1
280 CFM
6"x6" E2
100 CFM
8"ø S1
170 CFM
18"x18" R1
730 CFM
6"ø S1
75 CFM
6"x6" R1
50 CFM
8"ø S1
170 CFM
6"ø S1
95 CFM
8"x8" R1
75 CFM
6"ø S1
100 CFM
8"ø S1
170 CFM6"x6" E2
100 CFM
10"x10" R1
160 CFM
10"ø S1
260 CFM
10"ø S1
260 CFM 10"x10" R1
160 CFM
6"x6" E2
100 CFM
6"x6" E2
100 CFM
10"x10" R1
200 CFM
10"ø S1
300 CFM
6"x6" R1
65 CFM
6"ø S1
100 CFM
6"ø S1
50 CFM
10"x10" E1
170 CFM
6"x6" R1
65 CFM
6"ø S1
100 CFM
6"ø S1
100 CFM
6"x6" E1
100 CFM
6"ø S1
75 CFM
6"ø S1
100 CFM
8"ø S1
170 CFM
6"ø S1
100 CFM
6"x6" R1
65 CFM
6"x6" R1
100 CFM
6"ø S1
135 CFM
8"ø S1
170 CFM
8"ø S1
170 CFM
6"ø S1
100 CFM
6"x6" E2
125 CFM
10"ø S1
300 CFM
10"x10" R1
175 CFM
12"x12" R1
250 CFM
6"x6" E2
100 CFM
10"x10"
R1
200 CFM
6"x6" E2
100 CFM 10"ø S1
300 CFM
10"x10" R1
185 CFM
10"x10" R1
200 CFM
10"ø S1
300 CFM
6"x6" E2
115 CFM
6"x6" E2
100 CFM 10"ø S1
300 CFM
10"x10" R2
185 CFM
10"ø S1
255 CFM
6"x6" E2
125 CFM
10"x10" R1
130 CFM
6"x6" E2
75 CFM
4 5
8 8
12"x10"
"x
38"x10"
38"x10"
"x
"8"x8"
"x
8"x6"
8"x8"
20"x10"
"x
" 10"x6"
6"x6"
8"x8"
DESIGN/BUILD
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Final Design - For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2 :2
A
M
Sheet of
MH101
MECHANICAL NEW WORK
HVAC PLAN - ZONE J
RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/19
RLD SMP
1/8" = 1'-0"
Fourth Floor HVAC Ductwork
NOTES:
1. THE DESIGN IS BASED ON BASIC FIELD INVESTIGATIONS AND EXISTING PLANS
WHERE AVAILABLE. AS SUCH, THE CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS. IF ANY DEVIATIONS ARE DISCOVERED BETWEEN THE
ACTUAL CONDITIONS AND THE CONDITIONS SHOWN ON THE DESIGN
DOCUMENTS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY
AS MODIFICATIONS MAY BE REQUIRED. CONTRACTOR SHALL ALSO VERIFY
SPACE ABOVE CEILINGS AND IN MECHANICAL ROOMS PRIOR TO FABRICATION
OF DUCTWORK.
2. DUCT UP. SEE MH103 FOR CONTINUATION. MODIFY EXISTING HOLE IN ROOF
FOR NEW DUCT SIZE.
3. INSTALL FIRE DAMPER IN RATED WALL AS SHOWN. PROVIDE AND INSTALL
ACCESS DOOR IN DUCT AS NEEDED.
4. MOTOR OPERATED DAMPER FOR MODULATING OUTSIDE AIR AND
CONTROLLING ECONOMIZER FUNCTION. BOTTOM OUTSIDE AIR DUCT IS
MINIMUM REQUIRED VENTILATION. TOP OUTSIDE AIR DUCT DAMPER TO OPEN
FOR ECONOMIZER MODE. BOTH OUTSIDE AIR DAMPERS 100% OPEN FOR
ECONOMIZER MODE. RELIEF DAMPER SHALL BE INTERLOCKED WITH MAXIMUM
OUTSIDE AIR DAMPER.
5. AIR MONITORING STATION IN DUCT TO PROVIDE REQUIRED OUTSIDE AIR.
6. OFFSET DUCTS AS REQUIRED FOR CROSSING EACH OTHER AND ROUTING
UNDER STRUCTURE.
7. SEE MH102 FOR PIPING AND THERMOSTAT LOCATIONS.
8. PROVIDE ROOM PRESSURE MONITOR ON WALL OUTSIDE ISOLATION ROOM.
MODULATE SUPPLY AIR AS REQUIRED TO MAINTAIN REQUIRED PRESSURES.
9. EXISITNG 5 FT X 6 FT LOUVER. INSTALL PLENUM BOX ON LOUVER AND ATTACH
DUCT ON SIDE OF PLENUM AS SHOWN.
10. PROVIDE AND INSTALL DUCT MOUNTED SMOKE DETECTOR IN SUPPLY DUCT.
11. NO FIRE DAMPER IS REQUIRED PER EXCEPTION IN THE INTERNATIONAL
MECHANICAL CODE PROVIDED THAT THE DUCT IS 26 GAUGE METAL OR
HEAVIER.
12. INSTALL SMOKE DAMPER IN RATED WALL AS SHOWN. PROVIDE AND INSTALL
ACCESS DOOR IN DUCT AS NEEDED.
13. COORDINATE LOCATIONS OF ALL CEILING ITEMS WITH ARCHITECTURAL.
LOCATIONS SHOWN ON THESE LAYOUTS ARE CONCEPTUAL AND MAY DIFFER
FROM LAYOUTS IN THE FIELD DUE TO EXISTING CONDITIONS. COORDINATE ALL
WORK WITH OTHER TRADES.
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
J
KEY PLAN
PLAN
NORTH
Revisions: Date:
3 4
20 21
24 25 26
E
G
H
I
J
8 9 10 11 138.2 12 1.6
F
VAV
SOCIAL
WORKERS
WORKSTATION
4J-103
NEGATIVE
BARIATRIC RM
4J-105
POSITIVE
ISOLATION RM
4J-107
PATIENT RM
4J-110
PATIENT RM
4J-111
PATIENT RM
4J-112
BATH RM
4J-113A
PATIENT RM
4J-113
BATH RM
4J-112A
BATH RM
4J-111A
BATH RM
4J-110B
BATH RM
4J-107BANTE RM
4J-107AANTE RM
4J-105A
BATH RM
4J-105B
CORRIDOR
CJ4-6
CORRIDOR
CJ4-3B
BATH RM
4J-142B
NEGATIVE
ISOLATION RM
4J-142 ANTE RM
4J-142A
PATIENT RM
4J-139
BATH RM
4J-139A
PATIENT RM
4J-137
BATH RM
4J-137A
PATIENT RM
4J-136
BATH RM
4J-136A
STORAGE 3
4J-144
PATIENT RM
4J-135
BATH RM
4J-134A
PATIENT RM
4J-134
BATH RM
4J-135A
PATIENT RM
4J-131
BARIATRIC RM
4J-130
PATIENT RM
4J-129
PATIENT RM
4J-128
BATH RM
4J-128ABATH RM
4J-129A
BATH RM
4J-130A
BATH RM
4J-131A
CORRIDOR
CJ4-9
CORRIDOR
CJ4-10
SUPPLY
STORAGE
4J-141
NURSE STATION
CJ4-4
BATH RM
4J-115A
STORAGE 1
4J-114
PATIENT RM
4J-115
CORRIDOR
CJ4-7
EXIST MECH
RM/SVC BAY
4J-118
PATIENT RM
4J-123
CART /
STRETCHER
ALCOVE
4J-124 BATH RM
4J-123A
PATIENT RM
4J-125
BATH RM
4J-126A
PATIENT RM
4J-126
BATH RM
4J-125A
TELEM
4J-158
HALLWAY
CJ4-5
NURSE STATION
CJ4-8B
NURSE STATION
CJ4-8A
NURSE STATION
CJ4-8C
NURSE MANAGER
4J-109
ASST NURSE
MANAGER
4J-108
TLT 1
4J-120A
TLT 2
4J-120B
LOUNGE
4J-121
LOCKERS
4J-121B
NUTRITIONIST
OFFICE
4J-117
NOURISH
4J-120
EXIST ELECT
4J-119
MED GAS
4J-122UTILITY SOILED
4J-133
UTILITY CLEAN
4J-132
PHARMACIST
OFFICE
4J-160
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T T
T
T
T
2" HWS/R
2 1/2" HWS/R
1-1/2" HWS/R
1-1/2" HWS/R
1-1/4" HWS/R
1-1/4" HWS/R
3/4" HWS/R
3/4" HWS/R
1" HWS/R
3/4" HWS/R
1" HWS/R
3/4" HWS/R
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
1-1/4" HWS/R
3" CHS/R
1 1/2" LPS/LPR
AHU
STORAGE 4
4J-145
EXIST HKPG
4J-116
OMNI
4J-114B
DESIGN/BUILD
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Final Design - For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2 :2
A
M
Sheet of
MH102
MECHANICAL NEW WORK
PIPING PLAN - ZONE J
RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/19
RLD SMP
1/8" = 1'-0"
Fourth Floor HVAC Piping
1. ALL PIPING RUNOUTS TO VAV BOXES SHALL BE 3/4" PIPE
2. ROUTE CONDENSATE DRAIN FROM UNIT TO NEAREST
FLOOR DRAIN IN MECHANICAL ROOM.
3. CONNECT HOT WATER, CHILLED WATER, STEAM AND
CONDENSATE PIPES TO EXISTING RISERS.
SHEET NOTES
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
J
KEY PLAN
PLAN
G
H
I
J
8 9 10 11 138.2 12 1.6
F
EF
EF
EF
RF
24"x24" 18"x24"
"x
24"x24"
"x
"x
"x
DUCT DOWN. SEE MH101
FOR CONTINUATION.
DUCT DOWN. SEE MH101
FOR CONTINUATION.
TIE DUCT INTO EXISTING
LOUVER WHERE EXISTING
DUCT WAS REMOVED.
BAG-IN/BAG-OUT FILTER RACK ON ROOF
FAN DISCHARGE SHALL BE UP. EXTEND
DUCT FROM DISCHARGE 10 FT ABOVE ROOF.
SUPPORT DUCT WITH GUY WIRES.
COORDINATE WITH EXISTING CONDITIONS.
MODIFY EXISTING STRUCTURAL FRAME FOR
SUPPORTING DUCT, FILTER AND FANS.
COORDINATE WITH STRUCTURAL.
DESIGN/BUILD
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Final Design - For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2 :2
A
M
Sheet of
MH103
MECHANICAL NEW WORK
HVAC PENTHOUSE
RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/19
RLD SMP
1/8" = 1'-0"
Penthouse Floor HVAC
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
J
KEY PLAN
PLAN
G
H
1312 1.6
MH-201
18"x30"
54"/16" 52"x14"
18"x24"
"x
6"x6"
"x
AHU
Fourth Floor 0' - 0"
Penthouse Floor 14' - 0"
H
Fourth Floor 0' - 0"
Penthouse Floor 14' - 0"
30"x18"
30"x18"
52"x14"
54"/16"
MINIMUM OUTSIDE
AIR DUCT
MAXIMUM OUTSIDE
AIR DUCT
RELIEF DUCT
"x
DESIGN/BUILD
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Final Design - For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2 :2
A
M
Sheet of
MH201
MECHANICAL ROOM SECTION
NEW WORK PLANS
RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/19
RLD SMP
1/4" = 1'-0"
Fourth Floor HVAC Mechanical Room
1/4" = 1'-0"
Mechanical Room Section
AIR HANDLING UNITS
SYMBOL
TYPE
MINIMUM CFM
TOTAL CFM
MAX. FAN MOTOR HP
CAPACITY, BTU/HR
ENT. AIR DB, F
ENT. AIR WB, F
LVG. AIR DB, F
LVG. AIR WB, F
LOCATION
REMARKS
C O
O
LI
N G
C O
IL
AHU-1
MINIMUM OUTSIDE
AIR CFM
ELECTRICAL
CHARACTERISTICS
MAX. FACE
VELOCITY, FPM
MAX AIR PRESSURE
DROP, IN. H20
P R
E -H
E A
TI
N
G C
O
IL
CAPACITY, BTU/HR
ENT. AIR DB, F
LVG. AIR DB, F
MAX AIR PRESSURE
DROP, IN. H20
MAX. FACE
VELOCITY, FPM
MAX WATER PRESS.
DROP, FT. H20
HOT WATER GPM
ENTERING WATER
TEMP., F
LEAVING WATER
TEMP., F
EXTERNAL STATIC
PRESSURE, IN. H20
CHILLED WATER,
GPM
ENTERING WATER
TEMP., F
LEAVING WATER
TEMP., F
MAX WATER PRESS.
DROP, FT. H20
10,765
401,600
82.6
67.1
55.0
54.8
90,700
47.2
55.0
460 V / 3 PH
1.0
80.3
1.0
9.1
2.0
STACKED
4J-118
9,625
15 HP
1. MOTOR HORSEPOWER IS TOTAL. UNIT HAS 2 FANS.
EACH 7.5 HP.
2. UNIT SHALL CONSIST OF THE FOLLOWING
SECTIONS: INTAKE, PREFILTER 1 AND 2, HOT WATER
HEATING COIL, HUMIDIFIER SECTION WITH
HUMIDIFIER SIZED FOR 15 PSIG STEAM AT 261
LB/HR, TURNING CHILLED WATER COIL, DUAL
PLENUM SUPPLY FANS DIRECT DRIVE WITH VFD,
AFTER FILTER, AND DISCHARGE.
SYMBOL
TYPE
LOCATION
ELECTRICAL
VAV- 17VAV- 16 VAV- 18
MAXIMUM CFM
MINIMUM CFM
MAXIMUM BOX PRESSURE
DROP, IN. H20
VARIABLE AIR VOLUME BOXES
HEATING CFM
MAXIMUM N.C. LEVEL
CAPACITY, BTU/HR
ENT. AIR DB, F
LVG. AIR DB, F
H E
A
TI
N G
ENTERING WATER
TEMP., F
LEAVING WATER
TEMP., F
HOT WATER, GPM
VAV- 19 VAV- 20 VAV- 21 VAV- 22 VAV- 23 VAV- 24 VAV- 25 VAV- 26 VAV- 27 VAV- 28 VAV- 29
SYMBOL
TYPE
LOCATION
ELECTRICAL
VAV- 2VAV- 1 VAV- 3
MAXIMUM CFM
MINIMUM CFM
MAXIMUM BOX PRESSURE
DROP, IN. H20
VARIABLE AIR VOLUME BOXES
HEATING CFM
MAXIMUM N.C. LEVEL
CAPACITY, BTU/HR
ENT. AIR DB, F
LVG. AIR DB, F
H E
A
TI
N G
ENTERING WATER
TEMP., F
LEAVING WATER
TEMP., F
HOT WATER, GPM
VAV- 4 VAV- 5 VAV- 6 VAV- 7 VAV- 8 VAV- 9 VAV- 10 VAV- 11 VAV- 12 VAV- 13 VAV- 14 VAV- 15
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
PRESSURE
INDEPENDENT
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
0.3
SEE PLANS
22,500
2.2
10,600
1.1
0.3
6,600
0.7
24,600
2.5
13,600
1.4
22,700
2.3
25,300
2.5
11,600
1.2
4,800
0.5
7,600
0.8
11,000
1.1
12,100
1.2
12,100
1.2
21,400
2.1
10,000
1.0
260 300
11,400
1.1
9,700
1.0
11,400
1.1
10,000
1.0
11,400
1.1
11,400
1.1
11,400
1.1
11,400
1.1
11,400
1.1
11,600
1.2
11,600
1.2
11,600
1.2
11,600
1.2
120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH
120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH
120 V / 1 PH 120 V / 1 PH 120 V / 1 PH 120 V / 1 PH
SYMBOL
TYPE
REMARKS
LOCATION
ELECTRICAL
CHARACTERISTICS
CFM
MAXIMUM dBA
EXTERNAL STATIC
PRESSURE, IN. H20
MAXIMUM MOTOR HP
DRIVE
MAXIMUM TIP SPEED, FPM
MAXIMUM FAN SPEED, RPM
MAXIMUM OUTLET
VELOCITY, FPM
EXHAUST FANS
EF- 1 RF- 1 EF- 2
INLINE INLINE UTILITY SET
1.0
11,297
DIRECT
PENTHOUSE
1.0
3/4
DIRECT
PENTHOUSE
460V / 3 PH
1.25
BELT
ROOF
EF- 3
UTILITY SET
1.25
BELT
ROOF
460V / 3 PH 460V / 3 PH 460V / 3 PH
REGISTER, LOUVER & GRILLE SCHEDULE
REMARKS/NOTESBLOWTYPE SERVICEMARK
S1
R1
LAY-IN
TYPE
PERFORATED FACE
CEILING
REGISTER
RETURN REGISTER AS
INDICATED WITH OBD-
2-WAY;
SUPPLY
DIFFUSER
PERFORATED FACE
CEILING
SQUARE
DIRECTIONAL
-LAY-IN CEILINGS PROVIDE
24"X24"
ALUMINUM T-BAR
TITUS
PAR-AA
4-WAY
3-WAY;
RETURN
WITH OBD.
-LAY-IN CEILINGS PROVIDE 24"X24" ALUMINUM T-
BAR
LAY-IN FRAME
TITUS PCS-AA
EXHAUST
LAY-IN
TYPE
PERFORATED FACE
CEILING
REGISTER
-LAY-IN CEILINGS PROVIDE
24"X24"
ALUMINUM T-BAR
TITUS
PAR-AA
RETURN
EXHAUST
EXHAUST REGISTER AS
INDICATED WITH OBD-
E1
REGISTER
2-WAY;
SUPPLYSQUARE
DIRECTIONAL
4-WAY
3-WAY;
RETURN
EXHAUST
REGISTER
RETURN
EXHAUST
E2
S2
R2
LOUVERED FACE
CEILING
WITH OBD.
-GYP BOARD CEILING PROVIDE FLUSH MOUNTED
FRAME
TITUS 300FS
SURFACE
MOUNT
LOUVERED FACE
CEILING
SURFACE
MOUNT
LOUVERED FACE
CEILING
SURFACE
MOUNT
WITH OBD.
-GYP BOARD CEILING PROVIDE FLUSH MOUNTED
FRAME
TITUS 350FL
WITH OBD.
-GYP BOARD CEILING PROVIDE FLUSH MOUNTED
FRAME
TITUS 350FL
DESIGN/BUILD
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Final Design - For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2 :2
A
M
Sheet of
MH401
MECHANICAL NEW WORK
SCHEDULES - ZONE J
RENOVATE FOR PATIENT
PRIVACY - ZONE J
VAMC SALEM, VIRGINIA
658-18-101
02/28/19
RLD SMP
9068Revisions: Date:
SUPPORT SPACING
5'-0" MAXIUM
1" BAND CLAMPWIRE HANGER
1" MIN
MAX SAG 1/2"
PER FOOT OF
SUPPORT SPACING
SEE
NOTE 2
SEE
NOTE 2
SUPPORT SYSTEM MUST
NOT DAMAGE DUCT OR
CAUSE OUT OF ROUND SHAPE
DUCTS ARE FLEXIBLE WITH
EXTERNAL INSULATION AND
VAPOR BARRIER JACKETING
MIN CENTER LINE BEND RADIUS IS ONE
DIA, (OR INSIDE RADIUS OF D/2)
NOTES:
1" MIN
STRAIGHT SECTION FLEXIBLE DUCT (TYPICAL)
MAX. LENGTH 6 FT.
TIGHT AGAINST DUCT AND MEMBERS.
TO ANCHOR STRAPS TO DUCT AND JOISTS. ALL STRAPS SHALL BE
NO. 10x3/4" SELF TAPPING CADMIUM PLATED SHEET METAL SCREWS
INSULATION
8'-0"NONE REQUIREDUP TO 34" 1" X 18 GAUGE STRAP
SCALE: NTS
DUCT STRAP HANGER DETAIL
RECTANGULAR DUCT
HANGER SIZES FOR
SIDE
MAX. HANGER
SUPPORT ANGLE
HORIZONTAL
SPACING
MAXIMUM
NO POP RIVETS ALLOWED
HANGER STRAPS
1"
34" TO 40" 1" X 18 GAUGE STRAP NONE REQUIRED 6'-0"
DIFFUSER CONNECTION
ROUND RIGID DUCT
12" WIDE 24 GA SHIELD
TO STRUCTURE
2"x24" GA STRAP
CHANNELS BOTH
DIRECTIONS, FOR
LAY-IN CEILING
DIFFUSER SUPPORT
PROVIDE
(TYP)
OPERATED BAND
SCREW DRIVER
STAINLESS STEEL
WIRE HANGER
EXCEPT AT DIFFUSER CONNECTION.
DUCT. SEE SPECS. NO SAGS OR
UL 181 LABELED INSULATED FLEX
OR SQUARE ADAPTER
ROUND TO RECTANGULAR
MAXIMUM LENGTH 5 FT.
DIFFUSER
INSULATED
SHALL BE
BACK OF DIFFUSER
DIFFUSER
2" X 24" GA STRAP
GYP. CEILING
SQUARE ADAPTER
RECTANGULAR OR
ROUND TO
CONNECTION. MAXIMUM LENGTH 5 FT.
TURNS ALLOWED EXCEPT AT DIFFUSER
UL 181 LABELED INSULATED FLEX DUCT.
SPECIFICATIONS.
DUCT WRAP. SEE
COVER CONNECTIONS WITH
WRAP ALL BRANCH DUCTS AND
TO STRUCTURE
WIRE HANGER
OPERATED BAND (TYP)
SCREW DRIVER
STAINLESS STEEL
TAKE-OFFS)
(TYPICAL ALL
QUADRANT.
LOCKING
DAMPER WITH
BALANCING
SCREWS
SHEET METAL
FASTEN RIGID DUCT W/
RIGID DUCT
ROUND
GA SHIELD
12" WIDE 24
SUPPORT
DIFFUSER
DIRECTIONS, FOR
CHANNELS, BOTH
PROVIDE 3/4" HAT
LENGTH.
DUCTS OVER 6'-0" IN
SUPPORTS ON BRANCH
MINIMUM OF TWO
BRANCH DUCT RUNOUTS.
PROVIDE SUPPORT ON ALL
NOTE:
SURFACE MOUNTED
INSULATED
SHALL BE
BACK OF DIFFUSER
D1 + 2"
D1 "B"
45 DEGREE BRANCH TAKEOFF
"A"
6" (TYP)
DO NOT USE CONNECTIONS WITH SCOOPS
2"
PROVIDE BALANCING
DAMPER WITH 2"
STAND-OFF
2"
PROVIDE BALANCING
DAMPER WITH 2"
STAND-OFF
LOW PRESSURE DUCTWORK
BALANCING DAMPERS
PROVIDE FLUORESCENT FLAGGING ON ALL
NOTE:
2. ALL MATERIAL SHALL BE TYPE "L" COPPER.
INSULATE FOR CONDENSATE CONTROL AS REQD
(DRAWTHRU) AHU TOTAL PRESSURE IN INCHES-WC
(BLOWTHRU) AHU TOTAL PRESSURE IN INCHES-WC
NECK AND CAP FOR CLEANING TRAP
THREADED TEE, WITH EXTENDED
AIR HANDLING UNIT
B = GREATER OF 2" OR 1/2" PLUS
A = GREATER OF 4" OR 1/2" PLUS
NOTES:
A
B
CONDENSATE DRAIN TRAP
SUPPORT
W/ OR W/OUT
W/ OR W/OUT TYPE
OR SHIELD AS REQD
HANGER RODS
48 SPRING CUSHION
AS REQD
PROTECTIVE SADDLE
ANGLE IRON OR
UNISTRUT TYPE
REQUIREMENT W/SAFETY FACTOR OF 5
MEMBER APPROVED TO SATISFY LOAD
SIZE RODS, SPRING CUSHION, AND HORIZONTAL
AS REQD
NON-INSULATED
INSULATE PIPE
NOTES:
PIPE
PIPE; 1/4" MIN SIZE
COUPLING WELDED TO
3000# FULL STRENGTH
BARRIER AS REQD
INSULATION AND VAPOR
BLACK NIPPLE
3" LONG SCH 80
INSULATE GAUGE COCK
STRATION PURPOSES ONLY
TOP OF PIPE FOR ILLU-
INSTALLATION SHOWN ON
INSTALL GAUGE COCK ON
COCK W/PIPE THREADSEITHER SIDE OF PIPE
LEVER HANDLE GAUGE
TRAPEZE TYPE PIPE SUPPORT
GAUGE COCK INSTALLATION
HOT WATER UNIT HEATER
TYPICAL CONNECTIONS TO HORIZONTAL
UNIT HEATER
HOT WATER
SUPPLY
HOT WATER
RETURN
MV
CONTROL VALVE
AUTOMATIC FLOW
CYCLING
TEMPERATURE BY
MAINTAIN SPACE
THERMOSTAT SHALL
NOTE: UNIT MOUNTED
AIR VENT
MANUAL
STRAINER
BALL VALVE
VALVE
DRAIN LINE WITH
3-WAY COILS AUTOMATIC BALANCED
COIL
MANUAL AIR VENT
WITH P/T PORT AND
UNION
COMBINATION BALL VALVE,
& "O" RING UNION WITH PORT SECTION
END DRAIN WITH CAP & RETAINER STRAP
P/T PORT, BY-PASS ADAPTER & HOSE
`Y'-STRAINER & "O" RING UNION WITH
COMBINATION BALL VALVE,
SUPPLY
UNION WITH P/T PORTS
VENTURI REGULATOR & `O'-RING
COMBINATION BALL VALVE,
RETURN
VAV BOX 2-WAY COILS AUTOMATIC BALANCED
MANUAL AIR VENT
WITH P/T PORT AND
UNION
COIL
CAP & RETAINER STRAP
P/T PORT & HOSE END DRAIN WITH
`Y'-STRAINER & "O" RING UNION WITH
COMBINATION BALL VALVE,
SUPPLY
UNION WITH DUAL P/T PORTS
AUTOFLOW REGULATOR & "O"-RING
COMBINATION BALL VALVE,
RETURN
HW
SCALE: NTS
SCALE: NTS
SCALE: NTSSCALE: NTS
SCALE: NTS
SCALE: NTS
SCALE: NTS
SCALE: NTS
SCALE: NTS
1.
2.
3.
4.
AIR FLOW
UNION
UNION
MH501
MECHANICAL HVAC - DETAILS
PRIVACY
RENOVATE FOR PATIENT
VAMC SALEM VIRGINIA
143 RLD JAH
658-18-101 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Sheet of
Final Design-For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2
:2
A
M
DESIGN/BUILD
VARIABLE AIR VOLUME SINGLE DUCT SHUT-OFF BOX (VAV BOX)
SCALE: NTS
PLANS
SHOWN ON
SIZE AS
TAKEOFF
LOWLOSS
PRESSURE
PROVIDE HIGH
MASTIC
WITH DRAWBAND AND
PRESSURE FLEX. SEAL
MAXIMUM OF 24" HIGH
BOX
INSULATED VAV
DOUBLE
CFM MEASUREMENT DEVICE
STRAIGHT HARD DUCT UPSTREAM OF VAV
PROVIDE MINIMUM 4X INLET DIAMETER OF
PANEL.
ACCESS TO VAV CONTROL
PROVIDE MINIMUM 36"CLEAN
FLOW
AIR
MIN OF 1"
JACKETING OVER PIPE INSULATION
FIELD APPLIED METAL
SCALE: NTS
LONGITUDINAL JACKETING SEAMS POSITIONED
LAP FACING DOWN FOR WEATHER PROOFING
AT 3 OR 9 O'CLOCK ONLY W/TOP
OVERLAP JACKETING A MIN OF 1-1/2"
LAPING JOINT
BAND AND OVER
BETWEEN FIRST
NOTES:
BANDS TO SECURE
INSULATION
PIPE
PLACE
INSULATION IN
INSTRUCTIONS
PER MFGS
BELT INSTALLED
METAL BAND OR
SEE NOTE 2
METAL JACKET W/TOP
LAP FACING DOWN
SEAMS
SCREWS AT
RIVETS OR
SCH 40 PVC OR
FLATHEAD SCREWS
FASTEN TO WALL W/
ADJACENT WALL AREAS
FINISH PAINT TO MATCH
SIZED AS REQD; SEAL W/
CUT TO TIGHTLY FIT
ESCUTCHEON PLATE
PIPE PENETRATION THRU WALLS
MOUNT SLEEVE AND PROVIDE ESCUTCHEON PLATE.
NOTE: WHERE PIPING IS EXPOSED AT FINISH WALLS, FLUSH
2 TYP FOR MASONRY
(TYP. NON FIRE-RATED WALLS)
SCALE: NTS
OR CONCRETE WALL
TYP FOR NON-INSULATED
PIPE
PIPE AND CONDUIT
NOTES:
WHERE EXPOSED
AND JACKET
INSULATION
ESCUTCHEON PLATE:
3/4" PLYWOOD
EACH PIPE
PAINT ALL SIDES
SPACE BETWEEN PIPE
CAULK AND SEAL ANNULAR
AND SLEEVE
SPACE BETWEEN PIPE
CAULK AND SEAL ANNULAR
AND SLEEVE
INTERIOR
SCH 40 PVC OR
GALV STEEL SLEEVE
SECURE TO PARTITION
INSULATION
PIPE W/OR W/OUT
EXTERIOR
SECURE TO PARTITION
GALV STEEL SLEEVE
INSULATED DUCT
FIRE DAMPER IN
UNINSULATED DUCT
FIRE DAMPER IN
WITH FIRE CAULKING
SEAL ANGLE AND HOUSING
SCALE: NTS
FIRE DAMPER INSTALLATION (TYPICAL)
PARTITION
DUCT
DAMPER & HOUSING.
FACTORY FABRICATED FIRE
ALL AROUND, INCLUDING
INSULATE EXTERNALLY
ON THE PARTITION.
SO THAT THERE WILL BE A MINIMUM OF 1" OF OVERLAP
ANGLES SHALL INCREASE IN SIZE PROPORTIONATELY,
A CLEARANCE OF 1/8"/FT. ON HT. & WIDTH &
BOLTS OR WELDING 8" O.C. DAMPERS SHALL HAVE
TO FIRE DAMPER HOUSING W/ 1/4" DIA. NUTS &
1-1/2" X 1-1/2" X 1/8" MIN. ANGLES FASTENED
TO FIRE DAMPER HOUSING
MAKE AIRTIGHT CONNECTION
"S" JOINT (TYPICAL)
ANGLES. SEAL INSULATION
TO WALL WITH MASTIC
VAPOR BARRIER
DUCT ACCESS DOOR
EXHAUST STACK DETAIL
SCALE: NTS
ROOF
FAN
EXHAUST
REQUIRED)
TRANSITION (AS
DRIP LIP
GUY WIRE (4 REQUIRED)
EXHAUST STACK
STEEL STRAP SECURED TO
1" [25mm] GALVANIZED
EXHAUST STACK
WELDED STAINLESS STEEL
JOINT
WELDED
(TYP.)
WIRE TO ROOF
SECURE GUY
COUPLING
WELDED
1/2" [15mm]
DRAIN,
M
IN
m m
A S
R
Q U
IR
E D
F.C.
ROOF (TYP.)
STACK TO
SECURE
M/S] OUTLET VELOCITY
SIZE TO MAINTAIN 3500 FPM [17.8
BLANK PLATE
MH502
MECHANICAL HVAC - DETAILS
PRIVACY
RENOVATE FOR PATIENT
VAMC SALEM VIRGINIA
143 RLD JAH
658-18-101 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Sheet of
Final Design-For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2
:2
A
M
DESIGN/BUILD
DP-1
DP-2
TS-3
TS-6
C O
O L
TS-8
SA
RA
TS-4
MOTOR (ON/OFF) - STARTER AUXILIARY CONTACT
DIFFERENTIAL PRESSURE SENSOR/SWITCH
DIFFERENTIAL PRESSURE SENSOR/SWITCH
ACROSS FAN
MS-1
DP-2
ACROSS FILTER
DP-1
CONTROL DIAGRAM LEGEND:
INSTRUCTIONS AND NFPA REQUIREMENTS.
INTO THE ALARM SYSTEM BY THE CONTRACTOR PER FIRE DEPARTMENT
DETECTORS FIRE/SMOKE DAMPERS AND/OR SMOKE DAMPERS SHALL BE TIED
8. FIRE ALARM SYSTEMS SHALL BE WIRED BY CONTRACTOR. DUCT SMOKE
CAMPUS WIDE ENERGY CONTROL MANAGEMENT SYSTEM (ECMS).
10. THE BUILDING WEB BASED DDC SYSTEM SHALL BE INTEGRATED WITH THE
9. LOCATE TEMPERATURE AND HUMIDITY SENSORS ON WALL 56" AFF.
ALL DEVICES NEW UNLESS NOTED OTHERWISE.
3. PROVIDE ALL SENSORS, ACTUATORS, DETECTORS SHOWN IN DIAGRAMS.
CONTROLS.
5. CONTRACTOR SHALL PROGRAM THE SEQUENCE OF OPERATIONS FOR
7. ALL CONTROL AND ELECTRICAL WIRING SHALL BE FIRE AND PLENUM RATED.
INDICATED. CONTROLS ARE TO BE FURNISHED BY THE CONTRACTOR.
4. WIRE CONTROLS TO DIRECT DIGITAL CONTROL (DDC) PANELS AS
6. REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
2. REFER TO SHEET MH601 FOR MECHANICAL SCHEDULES.
1. REFER TO SHEET MI001 FOR MECHANICAL LEGEND.
GENERAL NOTES:
OUTSIDE AMBIENT AIR TEMPERATURE SENSOR
SUPPLY AIR TEMPERATURE SENSOR
SPACE TEMPERATURE SENSOR
LOW LIMIT AIR TEMPERATURE SENSOR
TEMPERATURE SENSOR
TS-6
TS-7
TS-8
TS-3
TS-2
OUTSIDE AIR TEMPERATURE SENSOR
MOTORIZED DAMPER
TS-1
MD-1
VARIABLE FREQUENCY DRIVEVFD
SMOKE DETECTORSD
ANALOG OUTPUTS:
ANALOG INPUTS:
CONTROL WIRING SIGNALS
MINIMUM.
A/D CONVERSION RESOLUTION
4-20 mA OR 1-5 VDC WITH 12-BIT
MINIMUM.
CONVERSION RESOLUTION
0-10 VDC WITH 8-BIT D/A
AIR HUMIDITY SENSORHS-1
RETURN AIR TEMPERATURE SENSORTS-4
HS-1
SD
CV-1
CHILLED WATER CONTROL VALVE (2-WAY)CV-1
SA
AV-1
H W C
O
IL
CV-2
VAV TERMINAL UNIT
TS-7
UH
MS-1
H W C
O
IL
CV-2
TS-7
VFD
AHU-4J
NTS
P R
E F
IL
T E
R
F
IL
T E
R
MD-1
SUPPLY AIRSA
EXHAUST AIREA
RETURN AIRRA
DS-1
DUCT STATIC PRESSURE SENSORDS-1
AIR VALVE ACTUATORAV-1
NTSNTS
TS-7
MIN OA
DSP DUCT STATIC PRESSURE
HOT WATER CONTROL VALVE (2-WAY)CV-2
WATER CONTROL VALVE (3-WAY)CV-3
AND RELIEF FANS. SUPPLY FANS SHALL MODULATE AS REQUIRED TO MAINTAIN SET PRESSURE IN THE SUPPLY DUCT.
DETECTOR IN THE SUPPLY DUCT IS ENERGIZED, IT SHALL SEND A SIGNAL TO THE FIRE ALARM AND DE-ENERGIZE THE SUPPLY
STEAM HUMIDIFIER SHALL BE ENERGIZED AS NEEDED TO MAINTAIN HUMIDITY SENSED IN THE RETURN DUCT. IF THE SMOKE
TEMPERATURE SENSOR FAILS THE CHILLED WATER VALVE SHALL CLOSE AND AN ALARM SHALL BE ANNUNCIATED AT THE BAS.
AND THE RETURN DAMPER CLOSE AND THE RELIEF DAMPER OPEN ENERGIZING THE RELIEF FAN. IF THE DISCHARGE AIR
DISCHARGE AIR TEMPERATURE SETPOINT. IF ECONOMIZING IS ENABLED THE MAXIMUM OUTSIDE AIR DAMPER SHALL ALSO OPEN
VENTILATION REQUIREMENT. THE PREHEAT HOT WATER AND CHILLED WATER VALVES SHALL MODULATE TO MAINTAIN THE
THE SUPPLY FAN SHALL RUN CONTINUOUSLY AND THE MINIMUM OUTSIDE AIR DAMPER SHALL OPEN TO MAINTAIN MINIMUM
OCCUPIED:
WITH THE BAS THE CONTROLLER SHALL OPERATE USING DEFAULT MODES AND SETPOINTS.
HEAT/COOL MODES, THE BAS SHALL ALSO SEND THE DISCHARGE AIR TEMPERATURE SETPOINT. IF COMMUNICATION IS LOST
THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE MORNING WARM-UP/PRE-COOL, OCCUPIED/UNOCCUPIED AND
BUILDING AUTOMATION SYSTEM INTERFACE:
SEQUENCE OF OPERATIONS FOR VARIABLE VOLUME AIR HANDLING UNIT AH-4J
DUCT TEMPERATURE SENSOR
SYMBOL
ITEM
DESCRIPTION
SMOKE DAMPER
VOLUME DAMPER
VARIABLE FREQUENCY DRIVE
S
C
STEAM COIL
C
C
COOLING COIL
FAN
T
FZ
FREEZESTAT
2-WAY CONTROL VALVE
DA
DAMPER ACTUATOR
T-5
AIIR FILTER
3-WAY CONTROL VALVE
DPS
STATIC PRESSURE SWITCH
SPT
STATIC PRESSURE TRANSMITTER
CO2 SENSOR
SMOKE DETECTOR
TS
SD
CONTROLS SYMBOL LEGEND
SPACE TEMPERATURE SENSOR
SYMBOL
ITEM
DESCRIPTION
VFD
CO2
SD
MOTOR STARTERMS
SEQUENCE OF OPERATION FOR ISOLATION ROOMS
THE CORRIDOR.
ROOM TO A POSITIVE, NEGATIVE OR NEUTRAL PRESSURE COMPARED TO
THE RPM CONTAINS A 3-POSITION KEY SWITCH THAT ALLOWS SETTING THE
WILL BE INITIATED, AS WELL AS A SOFTWARE ALARM TO THE DDC SYSTEM.
PRESSURE IS OUTSIDE OF THE PRESET ALARM LIMITS, A LOCAL ALARM
CORRIDOR AND REPORT THAT VALUE TO THE DDC SYSTEM. IF THE ROOM
WILL MONITOR THE ROOM PRESSURIZATION LEVEL AS COMPARED TO THE
A HALLWAY MOUNTED ROOM PRESSURIZATION MONITOR PANEL (RPM)
ROOM PRESSURIZATION MONITORING
OWNER.
FANS FOR EQUAL RUN TIME. COORDINATE DESIRED RUNTIME WITH
REDUNDANCY. THE DDC SYSTEM SHALL SET A SCHEDULE TO ALTERNATE
SIGNAL WILL BE SENT TO THE DDC SYSTEM. THE SYSTEM HAS 2 FANS FOR
LIGHT WILL BE ENERGIZED AT THE AIR FILTER SENSOR AND AN ALARM
IF THE HEPA FILTER PRESSURE DROP EXCEEDS THE SETPOINT, AN ALARM
MONITOR THE EXHAUST FAN STATUS AND HEPA FILTER PRESSURE DROP.
THE EXHAUST FANS SHALL RUN CONTINUOUSLY. THE DDC SYSTEM SHALL
ISOLATION ROOM EXHAUST FANS
WILL SOUND ROOM PRESSURIZATION MONITOR PANEL.
SETPOINT. IF THE ROOM PRESSURIZATION IS OUT OF RANGE, AN ALARM
FAN WILL MODULATE TO MAINTAIN THE FIXED EXHAUST AIR FLOW
TO MAINTAIN ROOM TEMPERATURE SETPOINT. THE BATHROOM EXHAUST
MONITOR PANEL. THE SUPPLY AIR TERMINAL UNIT REHEAT WILL MODULATE
NEGATIVE OR NEUTRAL PRESSURIZATION AT THE ROOM PRESSURIZATION
THE AIRFLOW DIFFERENTIAL, BASED ON WHETHER THE ROOM IS SET FOR
SUPPLY AIR TERMINAL AND THE PATIENT ROOM EXHAUST FAN TO MAINTAIN
THE ROOM PRESSURE CONTROLLER MODULATES THE CONSTANT VOLUME
OCCUPIED MODE
THE HVAC SYSTEMS OPERATE CONTINUOUSLY.
THE ISOLATION ROOMS ARE CONSIDERED CONTINUOUSLY OCCUPIED AND
GENERAL
EXHAUST FAN
EF-ISOLATION ROOMS
MS
(TYP.) (TYP.)
(TYP.)NTS
HF
EF TYPICAL
(TYP.)NTS
HF
TS-3
TS-6
P R
E H
E A
T
CV-2
S T
E A
M
DP-1
F
IL
T E
R
CV-3
AFMS-1
MD-2
MAX OA
AFMS-2
RELIEF AIR
MD-3 MD-4
MS
MH601
SEQUENCE OF OPERATIONS
HVAC CONTROL SCHEMATICS
PRIVACY
RENOVATE FOR PATIENT
VAMC SALEM VIRGINIA
143 RLD JAH
658-18-101 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
CheckedBuilding Number Drawn
Corporate Office:
766 Middle St, Fairhope, AL 36532
Phone: 251.990.5778
Fax: 251.990.3716
Date
Project No.
Drawing No.
Location
Sheet of
Final Design-For Construction
V e te ra n s
A ff a ir s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
/3
/2
:2
:2
A
M
DESIGN/BUILD
| 1-GI sheets |
| J-GI001 - TITLE SHEET |
| Sheets |
| J-GI001 - TITLE SHEET |
| J-GI002 - PROJECT INFORMATION SHEET |
| Sheets |
| J-GI002 - PROJECT INFORMATION SHEET |
| J-GI003 - PARTITION TYPES - TYPICAL MOUNTING HEIGHTS |
| Sheets |
| J-GI003 - PARTITION TYPES / TYPICAL MOUNTING HEIGHTS |
| J-GI004 - STANDARD ABBREVIATION |
| Sheets |
| J-GI004 - STANDARD ABBREVIATION |
| J-GI005 - EXISTING CONDITIONS - SCOPE OF WORK |
| Sheets |
| J-GI005 - EXISTING CONDITIONS - SCOPE OF WORK |
| J-GI111 - DEPARTAMENTAL USE PLAN - ZONE J |
| Sheets |
| J-GI111 - DEPARTAMENTAL USE PLAN - ZONE J |
| J-GI112 - DEDUCTIVE ALTERNATE #1 |
| Sheets |
| J-GI112 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #1 |
| J-GI113 - DEDUCTIVE ALTERNATE #2 |
| Sheets |
| J-GI113 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #2 |
| J-GI114 - DEDUCTIVE ALTERNATE #3 |
| Sheets |
| J-GI114 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #3 |
| J-GI115- DEDUCTIVE ALTERNATE #4 |
| Sheets |
| J-GI115 - NEW FLOOR PLAN - ZONE J - DEDUCTIVE ALTERNATE #4 |
| 2-AD sheet |
| Sheets |
| J-AD101 - DEMOLITION FLOOR PLAN - ZONE J |
| J-GI111 - DEPARTAMENTAL USE PLAN - ZONE J |
| 3-AE sheets |
| J-AE101 - NEW FLOOR PLAN - ZONE J |
| Sheets |
| J-AE101 - NEW FLOOR PLAN - ZONE J |
| J-AE102 - NEW WORK ROOF PLAN - ZONE J |
| Sheets |
| J-AE102 - NEW WORK ROOF PLAN - ZONE J |
| J-AE103 - DOOR SCHEDULE & DOOR - FRAME TYPES |
| Sheets |
| J-AE103 - DOOR SCHEDULE & DOOR / FRAME TYPES |
| J-AE111 - REFLECTED CEILING PLAN |
| J-AE111 - REFLECTED CEILING PLAN |
| Sheets |
| J-AE103 - DOOR SCHEDULE & DOOR / FRAME TYPES |
| J-AE111 - REFLECTED CEILING PLAN |
| J-AE301 - BUILDING SECTIONS |
| Sheets |
| J-AE301 - BUILDING SECTIONS |
| J-AE501 - WALL - CEILING DETAILS |
| Sheets |
| J-AE501 - WALL - CEILING DETAILS |
| J-AE502 - ARCHITECTURAL DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE503 - ARCHITECTURAL DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE504 - CASEWORK DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE505 - CASEWORK DETAILS |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| Sheets |
| J-AE502 - ARCHITECTURAL DETAILS |
| J-AE503 - ARCHITECTURAL DETAILS |
| J-AE504 - CASEWORK DETAILS |
| J-AE505 - CASEWORK DETAILS |
| J-AE601 - ARCHITECTURAL 3D VIEW |
| 4- IN sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN102 - FINISHES SCHEDULES |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN103 - FINISH SELECTIONS |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN202 - SIGNAGE TYPES |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
| J-IN103 - FINISH SELECTIONS |
| J-IN201 - SIGNAGE PLAN - ZONE J |
| J-IN202 - SIGNAGE TYPES |
| J-IN301 - INTERIOR VIEWS |
| J-IN301 - INTERIOR VIEWS |
| Sheets |
| J-IN101 - FLOOR FINISH PLAN - ZONE J |
| J-IN102 - FINISHES SCHEDULES |
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .