Revised DWGS.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24620R0001
About this file
This notice announces an upcoming solicitation for construction services to renovate and expand operating rooms at the Charles George VA Medical Center in Asheville, North Carolina. The work includes renovating approximately 5,000 square feet of existing operating rooms and constructing an 8,000 square foot expansion. The contractor will be responsible for construction services such as permitting, demolition, construction, submittals, fixtures and equipment installation, scheduling, inspection, and project closeout. A pre-proposal site visit will be held on January 23, 2020, with responses due February 27, 2020. The North American Industry Classification System code is 236220 and the project value is estimated between $10-20 million. The solicitation will be set aside 100% for Service-Disabled Veteran Owned Small Businesses and issued via the System for Award Management.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STORAGE
SKY
LIGHT
STORAGE
SKY
LIGHT
UPUP
UP UP
XXX SF
X
XXX XXX
OCCUPANT LOAD TAG
ROOM AREA
LOAD FACTOR/
OCCUPANT LOAD
USE GROUP
FIRE EXTINGUISHER CABINET
FE
C
EGRESS CAPACITY TAG
XX" DOOR
XX"
INCH/PERSON
XXX PEOPLE
X'-XX"
MAX TRAVEL DISTANCE
REQUIRED EXIT E
LIFE SAFETY LEGEND
E
HE
E
99'-4"184'-0"
HE
E E
FEC
FEC
FEC
FEC
OPEN TO BELOW
EXISTING
2 HR
WALL
EXISTING 2 HR WALL
EXTERIOR WALL
EXISTING 4" CMU WALL
NEW 2HR RATED PARTITION
ROOF ACCESS
CORRIDOR SMOKE PARTITION
1 HOUR FIRE PARTITION
SMOKE BARRIER
2 HOUR FIRE PARTITION
2 HOUR FIRE/SMOKE BARRIER
WALL LEGEND
1 HOUR/SMOKE BARRIER
LIFE SAFETY PLAN LEGEND
E
FEC
EXIT
FIRE EXTINGUISHER CABINET
114'-0" TRAVEL DISTANCE TO EXIT
88' - 11" TRAVEL DISTANCE TO SUITE EXIT
HE HORIZONTAL EXIT
PROJECT
LIMITS / PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
BUILDING REGULATION DATA
IBC 2012
USE GROUP
I2: INSTITUTIONAL
CONSTRUCTION TYPE TABLE 601
TYPE 1A FULLY SPRINKLERED
STRUCTURAL FRAME: 3 HOURS
BEARING WALLS: 3 HOURS
FLOOR CONSTRUCTION: 2 HOURS
ROOF CONSTRUCTION: 1 1/2 HOURS
BUILDING AREA AND HEIGHTS TABLE 503
UNLIMITED
HAZARDOUS AREAS TABLE 509
WASTE AND LINEN COLLECTION ROOMS IN USE
GROUP I-2 : 1 HOUR
SECTION 407 GROUP I-2
TRAVEL DISTANCE MAX 200'x0" TO BARRIER DOOR.
407.3 CORRIDOR WALL CONSTRUCTION
CORRIDOR WALLS SHALL BE CONSTRUCTED AS
SMOKE PARTITIONS
407.5 SMOKE BARRIERS
SMOKE BARRIERS SHALL BE PROVIDED TO
SUBDIVIDE EVERY STORY INTO NO FEWER THAN 2
AN AREA OF NO MORE THAN 22,500 SF.
SMOKE BARRIER DOOR TABLE 716.5
1/3 HOUR
MEANS OF EGRESS
EXIT ACCESS TRAVEL DISTANCE TABLE 1016.2
B: 200 FEET WITH SPRINKLER SYSTEM
SECTION 1015 : EXIT AND EXIT ACCESS
DOORWAYS
TWO EXITS ARE REQUIRED SEPARATION
DISTANCE 1/2 THE DIAGONAL WITH SPRINKLER
SYSTEM
EGRESS WIDTH
10053.1 STAIRWAYS CAPACITY IS OCCUPANT
LOAD x .2 INCHES
10053.2 CORRIDORS CAPACITY IS OCCUPANT
LOAD x .15 INCHES
MINIMUM CORRIDOR WIDTH TABLE 1018.2
44 INCHES
96 INCHES GROUP I-2 WHERE REQUIRED FOR
BED MOVEMENT
SHAFT ENCLOSURE 713.4
SHAFT SHALL HAVE FIRE-RESISTANT ROOFING
OF NOT LESS THAN 1 HOUR WHEN
CONNECTING LESS THAN 4 STORIES.
USE GROUP
CHAPTER 18/19 NEW AND EXISTING
HEALTHCARE OCCUPANCIES
CHAPTER 43 BUILDING REHABILITATION
CONSTRUCTION TYPE TABLE 19.1.6.1
TYPE 1 (332) NFPA 220 2015 EDITION
BEARING ALLS 3 HOURS
COLUMNS SUPPORTING MORE THAN ONE
FLOOR: 3 HOURS
BEAMS SUPPORTING MORE THAN ONE
FLOOR: 3 HOURS
BEAMS SUPPORTING ON FLOOR: 2 HOURS
FLOOR - CEILING ASSEMBLIES: 2 HOURS
ROOF CEILING ASSEMBLIES: 1 1/2 HOURS
NUMBER OF STORIES
UNLIMITED
HAZARDOUS AREA PROTECTION TABLE
18.3.2.1
ROOMS WITH SOILED LINEN IN VOLUME
GREATER THAN 64 GAL: 1 HOUR
STORAGE ROOMS GREATER THAN 50 SF
AND LESS THAN 100 SF STORING
COMBUSTIBLE MATERIAL PROVIDE
STORAGE ROOMS GREATER THAN 100 SF W/
COMBUSTIBLE MATERIAL: 1 HOUR
ROOMS WITH COLLECTING TRASH IN
VOLUME EXCEEDING 64 GAL: 1 HOUR
CONSTRUCTION OF CORRIDOR HALLS
18.3.6.2.3
CORRIDOR WALLS SHALL FORM A BARRIER
TO BLOCK THE TRANSFER OF SMOKE
SUB DIVISION OF BUILDING SPACE 18.3.7
EVERY STORY OF AMBULATORY
HEALTHCARE FACILITY SHALL DIVIDE INTO
NOT LESS THAN 2 SMOKE COMPARTMENTS
NOT EXCEEDING 22,500SF
TRAVEL DISTANCE FROM ANY POINT TO
REACH SMOKE BARRIER DOOR : 200'-0"
SMOKE BARRIER DOOR EXHIBIT 18/19.90
DOORS IN SMOKE BARRIERS SHALL BE NO
LESS THAN 1-3/4" SELF CLOSING.
LATCHING HARDWARE NOT REQUIRED
18.3.7.8
NFPA 101 2012
INTERNATIONAL BUILDING CODE (IBC 2012)
NFPA-101 LIFE SAFETY CODE (2012)
NFPA-220 STANDARD TYPE OF BUILDING CONSTRUCTION (2012)
NFPA-10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS (2012)
NFPA-70 NATIONAL ELECTRIC CODE (2008)
NFPA-101 LIFE SAFETY CODE (2012) CHAPTER 43.6 RECONSTRUCTION
APPLICABLE CODES AND STANDARDS:
MEANS OF EGRESS
TRAVEL DISTANCE TO EXIT 18.2.6.2.1
TRAVEL DISTANCE SHALL NOT EXCEED 200
FEET WITH SPRINKLER SYSTEM
NUMBER OF MEANS OF EGRESS 18.2.4.2
NOT LESS THAN 2
SEPARATION DISTANCE NOT LESS THAN 1/3 THE
DIAGONAL 7.5.1.3.3
EGRESS WIDTH TABLE 7.3.3.1
STAIRWAYS : OCCUPANCY LOAD x 3 INCHES CORRIDORS : OCCUPANCY LOAD x .2 INCHES
CAPACITY OF MEANS OF EGRESS 18.2.3.4
SHALL NOT BE LESS THAN 8' CLEAR
18.2.3.4 (1) MINIMUM WIDTH OF 44 INCHES IN
NON PATIENT AREAS
SHAFT 8.6.5 ITEM 2
SHAFTS LESS THAN 4 STORIES SHALL HAVE 1-
HOUR FIRE BARRIER.
FINISH REQUIREMENTS (NFPA 101 10.2.2):
EXIT ENCLOSURES/EXIT PASSAGEWAYS:
CLASS A OR B
EXIT ACCESS CORRIDORS & OTHER EXIT
WAYS: CLASS A OR B
ROOMS & ENCLOSED SPACES: CLASS A, B,
OR C
FLOORS IN EXIT ENCLOSURES, EXIT
PASSAGEWAYS AND CORRIDORS
(OTHER THAN WOOD, VINYL, LINOLEUM, AND
RESILIENT FLOORS
W/O FIBER MATERIALS): CLASS I OR II
FIRE PROTECTION:
AUTOMATIC SPRINKLER SYSTEMS: FULLY
SPRINKLERED
PORTABLE FIRE EXTINGUISHERS (NFPA 10):
CLASS ABC TYPE, MIN RATING 2-A
WHERE INDICATED ON LIFE SAFETY PLAN
MAXIMUM TRAVEL DISTANCE: 75'
A S e rv ic e
D is a b le d
Ve t e r an Owned S m a l l B u s iness
SDVOSB
CVE
R
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY
08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT / ENGINEERS:
X
Office of Construction and Facilities
Managemen t o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 www.pfa-architect.com
ARCHITECTURE, PLANNING,
INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD
21045
410-750-2246 (BALT) 410-750-2588 (FAX)
KA PROJECT NUMBER: M023-08
K O
F F
E L
ASSOCIATES
ENGINEERS
Fire Protection
RENOVATE AND
EXPAND
OPERATING ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
2019-03-22
Approved: Medical Center Director
Building Number
TTI ENVIRONMENTAL, INC.
1253 NORTH CHURCH
STREET
MOORESTOWN, NJ 08057
BID DOCUMENTS
FULLY SPRINKLERED
637-315
Life Safety Second Floor Plan jhtjht
LS102.110/18/12
1/16" = 1'-0"
SECOND FLOOR -LIFE SAFETY PLAN
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
NO. DESCRIPTION DATE
1 REVISION 5-29-2020
13 14 15 16 17 18
N
M
K
L
Ls
6 3/8"
A500
/2
/2
/4
/8
M6
M6
M6
M6
M3
M3
M6
M1BM1B
M3
M3
M1B
M1B
M3
M1B
M1BM1B
SW38_2
SW38_2
SW38_2
M3_1
M3_1
M3_1 M3_1
M1BM1B
M1B M1B
M1B
M1B M1B
M1B
M6
M1B
M1B
M3 L
M3B
M3
M3_C
M3 L
M3_C
M3B
M6
M3_1
M1B
M1B
M1B
M3_1
M6_1
GENERAL OR
GENERAL OR
2020 CARDIAC OR
SCRUB
SCRUB
SCRUB
HYBRID OR
CLEAN CORE
M1B
M3B
M1B
M3_1
M3B
M3
A510
A510
H
M3_1
8' - 0 5/8" 9' - 7 1/8" 12' - 6 5/8" 3 5/8" 18' - 4 5/8" 3' - 0 7/8"
6 1/2"
1' - 0"
21' - 0" 5' - 2 1/2" 2' - 0" 6' - 8 3/4" 8' - 0 3/4" 6' - 6 1/4" 4' - 7 1/8"
2' - 1 7/8"
8' - 4 7/8"
/2
/1
/4
/2
/1
SSC
ORT
SD1 SD1 SD1 SD1
SD1 SD1 M6_L
1:12
SLOPE
DOWN
A800
A800 6
S L O
P E
D O
W N
M3_C
/1
/4
/4
/4
/2
/8
M3L_1
M6_L
4' - 3 3/4"
M3_CL
BW
MS MS MS
A520
A520
A520
A520
N.4
12.6 8' - 9 5/8" 22' - 0" 22' - 0" 22' - 0" 22' - 0" 22' - 0"
12' - 9"
/8
11 3/8"
23' - 6 1/8" 4' - 3"
HYBRID
CONTROL
HEART/LUNG
MACHINE ROOM
SEMI-RESTRICTED
CORRIDOR
A801 2
A8018 6
/8
A8104
LC
LC
LC
EB
LB
LB
ORT
AC
EB
MB
MTR
MB
HLM
/2
M6_L
20202010 2030 2040A
2040B2011
2021 2050
2060B
2060C
ELEC
/1
2' - 0"
M1B
A810
A8103
A202.1A
TYP.
NCP
IM
WPH
MB
MTR
BW
ORT
AC
EB
LB
LB
LB
LB
LC
HLM
CPM
CPM
CPM
NCP
MB
MB
IM
BW
MB
MB
IM IM
NCP
MTR
MTR
M6_C
NCP
WPH
M3_CL
10' - 6 3/4" 10' - 7 1/8"
WPH
5 5
TYP TYP
M3_1
5 5
B1
C2
B2
C1
MB
M3_CL
M1B
WPH
6 5/8" 11' - 9" 4' - 10" 8' - 4 5/8" 4' - 10" 2' - 0" 4' - 10" 7' - 9" 4' - 10" 7' - 9" 4' - 10" 2' - 0" 4' - 10" 8' - 9" 4' - 10" 8' - 9" 4' - 10" 2' - 0" 4' - 10" 7' - 7 3/8" 4' - 10" 3' - 1 1/8"
B B
E
B C
F
A
A
A
A
A A A A A A A A A A
M3B
2' - 0"
1' - 0 1/8"
/8
4' - 6"
/4
1' - 0 1/8"
/8
/8
1' - 0 1/8"
A500
3 3
M1B
M1B
M3B
M1BM1B M3B
M3B
M1B
M1B M3B
M3B
M3BL
M3B
1 3
M3BL
M3B
M3
M1B
M1B
M3 L
M1B
M3 L
/2
1' - 3 5/8"
/2
1' - 0"
/4
M3B M3B M3BM3B
M3B
M3
M3_1
M6_1
M3_C
M6_C
M3_1
M3_1
M3_1
AC
M6M6
OC
OC
OC
135.00°
.0
.0
EQ EQ
/8
/4
/1
M1B
M3B
A520
A520
A520
PT
SD1
OC
SSC
SSC
SSC
SSC
SSC
SSC
FEC
CPM
PHASE 1
PHASE 2
M3_C
/1
/2
/1
8' - 1 1/4" 14' - 11 5/8" 1' - 4" 5' - 6 1/4" 1' - 3" 5' - 6 1/4" 13' - 9 9/16" 1' - 3 13/16"2' - 1" 20' - 0 3/4" 1' - 9 1/2" 10' - 11 1/4" 7' - 4 3/8" 10' - 9 3/4" 4' - 7 7/8" 8' - 4 7/8" 1' - 4 5/8"
2041A
2041B
M3_CL
M3_C
HYBRID EQUIP
2' - 6" 2' - 0"
NEW WORK NOTES
1. PROVIDE 1 1/2" FLOOR EXPANSION JOINT
2. PROVIDE 1 1/2" WALL EXPANSION JOINT TYPICAL
3. PROVIDE 1 1/2" FLOOR TO WALL EXPANSION JOINT TYPICAL
4. SEE HYBRID OR DRAWINGS FOR ADDITIONAL INFORMATION.
COORDINATE LEAD REQUIREMENTS WITH VA SUPPLIED
PHYSICIST'S REPORT
5. 4' HIGH STAINLESS STEEL CORNER GUARD.[CG#2]
6. FULL HEIGHT ACROVYN CORNER GUARD [CG#1]
7. FIRE EXTINGUISHER AND CABINET
8. NOT USED
9. PROVIDE SPRINKLER DRAIN LINE DISCHARGE ON TO ROOF.
6" MINIMUM ABOVE EXISTING ROOF.
10. THIS ELEMENT OF THE PROJECT HAS BEEN IDENTIFIED AS
WORK TO BE INCLUDED IN DETAIL AS A BID ITEM. SEE
SECIFICATIONS AND INSTRUCTIONS TO BIDDERS FOR A
DETAILED LISTING OF THESE ITEMS AND THE ASSOCIATED
SCOPES OF WORK.
PROJECT
LIMITS / PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND
CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY
DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE COR FOR A RESOLUTION. ADJUSTMENTS
TO DIMENSIONS AND CONDITIONS SHOWN MAY BE REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT
NEW CONSTRUCTION UNLESS OTHERWISE NOTED.
DIMENSIONS ARE REFERENCED FROM FACE OF FINISH AT
EXISTING CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST
BE FIELD VERIFIED PRIOR TO THE START OF CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO
INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR
SERVICES TO BE READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES
WHICH WILL REMAIN EXPOSED, ALIGN NEW WORK FLUSH WITH
EXISTING ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN
A WATER TIGHT CONDITION THROUGHOUT THE ENTIRE
CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY
CONSTRUCTION OPERATIONS. TAKE ALL PRECAUTIONS
NECESSARY TO PROTECT THE BUILDING AND ITS OCCUPANTS
DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY
TO THE CONSTRUCTION AREA. BARRIERS SHALL NOT
INTERFERE WITH THE OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN
THE AREA OF RENOVATION TO PREVENT THE SPREAD OF
DUST TO OCCUPIED AREAS OF THE BUILDING.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET
ARE FOR THIS ONLY UNLESS OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
• ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE
IN ACCORDANCE WITH VAMC'S EXISTING ROOF WARRANTY.
COORDINATE ALL MODIFICATIONS TO THE ROOF WITH THE
COR.
• ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET
CAN BE REFERENCED FROM SHEET A000.
GENERAL NEW WORK NOTES
A S e rv ic e
D is a b le d
Ve t e r an Owned S m a l l B u s iness
SDVOSB
CVE
R
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY
08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT / ENGINEERS:
X
Office of Construction and Facilities
Managemen t o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 www.pfa-architect.com
ARCHITECTURE, PLANNING,
INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD
21045
410-750-2246 (BALT) 410-750-2588 (FAX)
KA PROJECT NUMBER: M023-08
K O
F F
E L
ASSOCIATES
ENGINEERS
Fire Protection
RENOVATE AND
EXPAND
OPERATING ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
2019-03-22
Approved: Medical Center Director
Building Number
TTI ENVIRONMENTAL, INC.
1253 NORTH CHURCH
STREET
MOORESTOWN, NJ 08057
BID DOCUMENTS
FULLY SPRINKLERED
637-315
New Work Plan - Second Floor - Phase 1 - Area A
A102.1A09/25/14
1/4" = 1'-0"
NEW WORK PLAN -SECOND FLOOR - PHASE 1 - AREA A
WALL TYPE SCHEDULE - PHASE 1
TYPE STC DESCRIPTION FIRE RATING UL REMARKS
M1B N/A 1 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND GWB
4" ABOVE CEILING. FASTEN STUD TO UNDERSIDE OF DECK.
M3 N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND
GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE
OF DECK OR STRUCTURE ABOVE AT 48" O.C. MAX
M3 L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE AND 5/8" LEAD
LINED GWB ROOM SIDE. EXTEND GWB TO 4" ABOVE FINISHED CEILING.
ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48"
O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3 L_l N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" FIRERATED FIRERATED GWB
ONE SIDE AND 5/8" LEAD LINED GWB ROOM SIDE. EXTEND PARTITION TO
DECK ABOVE.
1 HR - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3_1 N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES.
EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE RATED PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M3_1SB 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES.
EXTEND PARTITION TO UNDERSIDE OF DECK ABOVE.
1 HR SMOKE
BARRIER
PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE BARRIER"
M3_2 N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB
BOTH SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR FIRE RATED PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M3_2S N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB
BOTH SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR SMOKE
BARRIER
U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR SMOKE BARRIER" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M3_C N/A 3 5/8" METAL STUDSAT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND
WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
SMOKE PARTITION - PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE PARTITION" AS REQUIRED
BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK ABOVE
M3_C L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWBONE SIDE AND 5/8" LEAD
LINED GWB ROOM SIDE. EXTEND PARTITION TO UNDERSIDE OF DECK
ABOVE.
SMOKE PARTITION - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3_SB 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES.
EXTEND PARTITION TO UNDERSIDE OF DECK ABOVE.
SMOKE BARRIER PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE BARRIER"
M3B N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL
ASSEMBLY TO 4" ABOVE FINISHED CEILING.
M3B L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" LEAD LINED GWB ONE SIDE.
EXTEND GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO
UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48" O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M6 N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND GWB
TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF
DECK OR STRUCTURE ABOVE AT 48" O.C. MAX
M6_1 N/A 6" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES.
EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE RATED PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M6_C N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND WALL
ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
SMOKE PARTITION - PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE PARTITION" AS REQUIRED
BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK ABOVE
M6_L N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE AND 5/8" LEAD
LINED GWB ROOM SIDE. EXTEND GWB TO 4" ABOVE FINISHED CEILING.
ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48"
O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M6B N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL
ASSEMBLY TO 4" ABOVE FINISHED CEILING.
M349_2S 49 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB
BOTH SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR SMOKE
BARRIER
U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR SMOKE BARRIER" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
SW_1 38 2 1/2" CH STUDS AT 24" O.C. MAX. 1" GYPSUM LINER ONE SIDE AND 1
LAYERS 5/8" GWB OTHER SIDE SIDE. EXTEND WALL ASSEMBLY TO DECK
ABOVE.
1 HR U 415
SYSTEM
B
SW_2 38 2 1/2" CH STUDS AT 24" O.C. MAX. 1" GYPSUM LINER ONE SIDE AND 2
LAYERS 5/8" GWB OTHER SIDE SIDE. EXTEND WALL ASSEMBLY TO DECK
ABOVE.
2 HR U 415
SYSTEM
B
EQUIPMENT SCHEDULE - PHASE 1
NAMEMARK VAFCI VAFOI CFCI COMMENTS
AC ANESTHESIA COLUMN *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
B1 LIGHT BOOM 2 *** RELOCATED FROM EXISTING OR #7
B2 LIGHT BOOM 1 *** RELOCATED FROM EXISTING OR #7
BW BLANKET WARMER *** PROVIDE POWER
C1 EQUIPMENT BOOM 1 *** RELOCATED FROM EXISTING OR#7
C2 ANESTHESIA BOOM 1 *** RELOCATED FROM EXISTING OR#7
CRT CART *** EXISTING - RELOCATED THIS PHASE
EB EQUIPMENT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
HLM HEART LUNG MACHINE *** PROVIDE POWER
IM INTEGRATION MONITOR *** PROVIDE POWER AND DATA
LB SURGICAL LIGHT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
LC LIGHT CONTROL *** PROVIDE POWER
MB MARKER BOARD *** *** PROVIDE BLOCKING AS REQUIRED
MS STAINLESS STEEL
SHELVES
MTR MONITOR *** PROVIDE POWER AND DATA
NCP NITROGEN CONTROL
PANEL
*** PROVIDE POWER
OC MOBILE OMNI CELL *** PROVIDE POWER AND DATA
ORC OR CART *** EXISTING - RELOCATED THIS PHASE
ORT OR TABLE ***
SSC STAINLESS STEEL
CABINET
WPH WALL PHONE *** PROVIDE POWER AND DATA
TOILET ACCESSORY SCHEDULE - PHASE 1
MARK DESCRIPTION MOUNTING HEIGHT VAFCI VAFOI VAFCI REMARKS
PT PAPER TOWEL DISPENSER 48" ABOVE AFF TO BOTTOM OF OPENING OFCI
SD1 AUTOMATIC SOAP DISPENSER 38" A.F.F. TO BOTTOM ***
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
16 17 18
K
J
L
Ls
H.6
A500
EQUIPMENT
STORAGE
ORTHO OR
M3_1
M6_1
M3_1
M3B
M3
M3B
M6
M3B
M1B
M6_1
M6_1
M3_2
M1B
M3B
M3B
A501
6"
5' - 9 7/8" 1' - 0" 12' - 7 1/4" 2' - 0 7/8"
7"
12' - 8 1/4" 8' - 4 7/8"
3 7/8" 9 1/8"
13' - 11 1/4" 8' - 0 3/4" 13' - 3 1/4" 8' - 2 3/4" 6"
/8
/2
/8
/1
/1
/8
SD1 SD1
6" 7 1/8"
A802 2
LB
AC
LB
EB
LC
10' - 6 3/4" 2' - 0" 9' - 0 1/4"
MB
MB
ORT
WPH
NCP
10' - 6 1/8" 10' - 11 1/4"
8 10 10
6 6
10 10
M3_1
CPM
1' - 7 1/2"
11' - 9 3/4" 2060C
2060B
2070 2060A
EQ
M3B
M3B
M3B
M1B
M1B
M1B M3 M3_1 M3_1
M1B
M1B
B
4' - 6" 4' - 6"
/8
1' - 0 1/8"
/8
/8
/2
CLEAN CORE
OC
/8
M1B
M6
M6
M3B
M1B
M1B
M6B
M1B
M3B
E Q
E Q
E Q
E Q
R A
M P
D O
W N
/3
P E
R F
O O
T
S O
L
ID
C
O N
C R
E T
E S
E E
S E
C T
IO
N
/A
TYP
R A
M P
D O
W N
/3
P E
R F
O O
T
E L E
V A
T E
D R
A M
P S
E E
S E
C T
IO
N
/A
M6_1 M6B
SSC
SSC
M3_2
M3_2
/8
NEW WORK NOTES
1. PROVIDE 1 1/2" FLOOR EXPANSION JOINT & JOINT COVER.
2. PROVIDE 1 1/2" WALL EXPANSION JOINT & JOINT COVER.
3. FIRE EXTINGUISHER CABINET.
4. 5"X5"X1/2" STEEL ANGLE. FASTEN TO METAL STUDS.
5. EDGE OF RAMP.
6. FULL HEIGHT ACROVYN CORNER GUARD (CG#1).
7. 4' HIGH STAINLESS STEEL CORNER GUARD (CG#2).
8. 5/8" GWB GLUED TO FACE OF CONCRETE COLUMN.
9. ALIGN EDGE OF STUD TO FACE OF CONCRETE BEAM. GLUE 5/8" GWB TO FACE OF BEAM BELOW.
10. PROVIDE BUMPER GUARD (BG#1) AT 34" TO CENTERLINE AFF. BELOW BUMPER RAIL. PROVIDE
WAINSCOT (WS#1). TOP OF WAINSCOT TO TERMINATE AT CENTERLINE OF BUMPER GUARD.
PROJECT LIMITS /
PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
COR FOR A RESOLUTION. ADJUSTMENTS TO DIMENSIONS AND CONDITIONS SHOWN MAY BE
REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT NEW CONSTRUCTION UNLESS
OTHERWISE NOTED. DIMENSIONS ARE REFERENCED FROM FACE OF FINISH AT EXISTING
CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST BE FIELD VERIFIED PRIOR TO THE
START OF CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL
ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES WHICH WILL REMAIN EXPOSED, ALIGN NEW
WORK FLUSH WITH EXISTING ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN A WATER TIGHT CONDITION
THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY CONSTRUCTION
OPERATIONS. TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE BUILDING AND ITS
OCCUPANTS DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE CONSTRUCTION AREA.
BARRIERS SHALL NOT INTERFERE WITH THE OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO
PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF THE BUILDING.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS ONLY UNLESS
OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
• ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN ACCORDANCE WITH VAMC'S
EXISTING ROOF WARRANTY. COORDINATE ALL MODIFICATIONS TO THE ROOF WITH THE COR.
• ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET CAN BE REFERENCED FROM SHEET A000.
GENERAL NEW WORK NOTES
A S e rv ic e
D is a b le d
Ve t e r an Owned S m a l l B u s iness
SDVOSB
CVE
R
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY
08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT / ENGINEERS:
X
Office of Construction and Facilities
Managemen t o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 www.pfa-architect.com
ARCHITECTURE, PLANNING,
INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD
21045
410-750-2246 (BALT) 410-750-2588 (FAX)
KA PROJECT NUMBER: M023-08
K O
F F
E L
ASSOCIATES
ENGINEERS
Fire Protection
RENOVATE AND
EXPAND
OPERATING ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
2019-03-22
Approved: Medical Center Director
Building Number
TTI ENVIRONMENTAL, INC.
1253 NORTH CHURCH
STREET
MOORESTOWN, NJ 08057
BID DOCUMENTS
FULLY SPRINKLERED
637-315
New Work Plan - Second Floor - Phase 1 - Area B jasjht A102.1B01/15/15
1/4" = 1'-0"
NEW WORK PLAN -SECOND FLOOR - PHASE 1 AREA B
WALL TYPE SCHEDULE - PHASE 1
TYPE STC DESCRIPTION FIRE RATING UL REMARKS
M1B N/A 1 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND GWB
4" ABOVE CEILING. FASTEN STUD TO UNDERSIDE OF DECK.
M3 N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND
GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE
OF DECK OR STRUCTURE ABOVE AT 48" O.C. MAX
M3 L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE AND 5/8" LEAD
LINED GWB ROOM SIDE. EXTEND GWB TO 4" ABOVE FINISHED CEILING.
ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48"
O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3 L_l N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" FIRERATED FIRERATED GWB
ONE SIDE AND 5/8" LEAD LINED GWB ROOM SIDE. EXTEND PARTITION TO
DECK ABOVE.
1 HR - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3_1 N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES.
EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE RATED PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M3_1SB 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES.
EXTEND PARTITION TO UNDERSIDE OF DECK ABOVE.
1 HR SMOKE
BARRIER
PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE BARRIER"
M3_2 N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB
BOTH SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR FIRE RATED PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M3_2S N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB
BOTH SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR SMOKE
BARRIER
U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR SMOKE BARRIER" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M3_C N/A 3 5/8" METAL STUDSAT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND
WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
SMOKE PARTITION - PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE PARTITION" AS REQUIRED
BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK ABOVE
M3_C L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWBONE SIDE AND 5/8" LEAD
LINED GWB ROOM SIDE. EXTEND PARTITION TO UNDERSIDE OF DECK
ABOVE.
SMOKE PARTITION - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3_SB 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES.
EXTEND PARTITION TO UNDERSIDE OF DECK ABOVE.
SMOKE BARRIER PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE BARRIER"
M3B N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL
ASSEMBLY TO 4" ABOVE FINISHED CEILING.
M3B L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" LEAD LINED GWB ONE SIDE.
EXTEND GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO
UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48" O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M6 N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND GWB
TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF
DECK OR STRUCTURE ABOVE AT 48" O.C. MAX
M6_1 N/A 6" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES.
EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE RATED PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M6_C N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND WALL
ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
SMOKE PARTITION - PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE PARTITION" AS REQUIRED
BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK ABOVE
M6_L N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE AND 5/8" LEAD
LINED GWB ROOM SIDE. EXTEND GWB TO 4" ABOVE FINISHED CEILING.
ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48"
O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M6B N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL
ASSEMBLY TO 4" ABOVE FINISHED CEILING.
M349_2S 49 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB
BOTH SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR SMOKE
BARRIER
U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR SMOKE BARRIER" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
SW_1 38 2 1/2" CH STUDS AT 24" O.C. MAX. 1" GYPSUM LINER ONE SIDE AND 1
LAYERS 5/8" GWB OTHER SIDE SIDE. EXTEND WALL ASSEMBLY TO DECK
ABOVE.
1 HR U 415
SYSTEM
B
SW_2 38 2 1/2" CH STUDS AT 24" O.C. MAX. 1" GYPSUM LINER ONE SIDE AND 2
LAYERS 5/8" GWB OTHER SIDE SIDE. EXTEND WALL ASSEMBLY TO DECK
ABOVE.
2 HR U 415
SYSTEM
B
ROOM LEGEND - PHASE 1
NUMBER NAME
2000 RAMP
2001 SEMI-RESTRICTED CORRIDOR
2002 SEMI-RESTRICTED CORRIDOR
2003 SCRUB
2004 SCRUB
2005 SCRUB
2006 CORRIDOR
2007 RAMP
2009 SEMI-RESTRICTED CORRIDOR
2010 GENERAL OR
2016 SCRUB
2020 GENERAL OR
2030 CARDIAC OR
2031 HEART/LUNG MACHINE ROOM
2040 HYBRID OR
2041 HYBRID EQUIP
2050 HYBRID CONTROL
2060 EQUIPMENT STORAGE
2070 ORTHO OR
2080 CLEAN CORE
2090 ELEC
DB221B Room
TOILET ACCESSORY SCHEDULE - PHASE 1
MARK DESCRIPTION MOUNTING HEIGHT VAFCI VAFOI VAFCI REMARKS
PT PAPER TOWEL DISPENSER 48" ABOVE AFF TO BOTTOM OF OPENING OFCI
SD1 AUTOMATIC SOAP DISPENSER 38" A.F.F. TO BOTTOM ***
EQUIPMENT SCHEDULE - PHASE 1
NAMEMARK VAFCI VAFOI CFCI COMMENTS
AC ANESTHESIA COLUMN *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
B1 LIGHT BOOM 2 *** RELOCATED FROM EXISTING OR #7
B2 LIGHT BOOM 1 *** RELOCATED FROM EXISTING OR #7
BW BLANKET WARMER *** PROVIDE POWER
C1 EQUIPMENT BOOM 1 *** RELOCATED FROM EXISTING OR#7
C2 ANESTHESIA BOOM 1 *** RELOCATED FROM EXISTING OR#7
CRT CART *** EXISTING - RELOCATED THIS PHASE
EB EQUIPMENT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
HLM HEART LUNG MACHINE *** PROVIDE POWER
IM INTEGRATION MONITOR *** PROVIDE POWER AND DATA
LB SURGICAL LIGHT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
LC LIGHT CONTROL *** PROVIDE POWER
MB MARKER BOARD *** *** PROVIDE BLOCKING AS REQUIRED
MS STAINLESS STEEL
SHELVES
MTR MONITOR *** PROVIDE POWER AND DATA
NCP NITROGEN CONTROL
PANEL
*** PROVIDE POWER
OC MOBILE OMNI CELL *** PROVIDE POWER AND DATA
ORC OR CART *** EXISTING - RELOCATED THIS PHASE
ORT OR TABLE ***
SSC STAINLESS STEEL
CABINET
WPH WALL PHONE *** PROVIDE POWER AND DATA
*SEE ALL NEW WORK SHEETS FOR EXTENT OF EQUIPMENT*
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
UP UP
13 14 15 16
K
J
H
L
Ls
H.6
G.4
G.6
GENERAL OR
STER. DIRTY
2130A
ANESTHESIA
WORK RM
SEMI-RESTRICTED
CORRIDOR
STORAGE
S - 3
GENERAL OR
HAC
CLEAN CORE
2081M3_1
M3_1
M3_1
M3B
M1B
M6_C
M3_1
M6_C
M3_1
M3_1
M1B
M1B
M1B
M6_C
M6
M3
M3_C
M3_C
M6_C
M3_C
M1B
M1BM6_C
M3_C
M3_SB
M3_C
M3_C
M6_C
M1B
M1B
M1B
M3_C
M3_1
M1BM1BM1B M1B
RAMP
1:12
M3_1
M6_C
A8028
A8034
M1B
12.6
M1B
SD1
SD1 SD1
CPM
MALE LOCKER
ROOM
B217A
SHOWER
B217
PHASE 1
PHASE 2
SOILED
GAS STORAGE
SEMI-RESTRICTED
CORRIDOR
A900
A8105
A803 5
A810 8
LB
EB
LB
AC
BW
BW
CPM
LC
LB
AC
LB
EB
IM
NCP
MB
MB
LC
WPH
MTR
MB
MB
NCP
IM
M3_1
WPH
1 1
M3_1
ORT
M1B
SD1
2 2
2180 2120 2140 2150
2130A
M1B
M6_C
M3B
M3B
M1B
M1B M1B
M3B
M1B
4 4
B B
RAMP
A510
M1B
M1B
M6_C
M6_1
OC
OC
SEMI-RESTRICTED
CORRIDOR
CORRIDOR
SEMI-RESTRICTED
CORRIDOR
CORRIDOR
M1B
ALIGN
D
.0
SD1
PT
PT
LB
ORT
SSC
SSC
AM
1 1
SSC
SSC
A202.2
STER. CLEAN
2130B A803
M6_C
ST
A8038
M3_C
2130B
2130C
PT SD1
SD1
PT
SD1
NEW WORK NOTES
1. PROVIDE FULL HEIGHT ACROVYN CORNER GUARD (CG#1).
2. PROVIDE 4' HIGH STAINLESS STEEL CORNER GUARD (CG#2).
3. PROVIDE SEMI-RECESSED FIRE EXTINGUISHER CABINET.
4. SECURE DOORS CLOSED PRIOR TO START OF NEW WORK.
5. EXTEND WALLS TO DECK ABOVE W/ 5/8" FIRERATED GWB BOTH SIDES TO CREATE SMOKE
BARRIER.
PROJECT LIMITS
/ PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
COR FOR A RESOLUTION. ADJUSTMENTS TO DIMENSIONS AND CONDITIONS SHOWN MAY BE
REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT NEW CONSTRUCTION UNLESS
OTHERWISE NOTED. DIMENSIONS ARE REFERENCED FROM FACE OF FINISH AT EXISTING
CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST BE FIELD VERIFIED PRIOR TO THE
START OF CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL
ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES WHICH WILL REMAIN EXPOSED, ALIGN NEW
WORK FLUSH WITH EXISTING ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN A WATER TIGHT CONDITION
THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY CONSTRUCTION
OPERATIONS. TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE BUILDING AND ITS
OCCUPANTS DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE CONSTRUCTION AREA.
BARRIERS SHALL NOT INTERFERE WITH THE OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO
PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF THE BUILDING.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS ONLY UNLESS
OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
• ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN ACCORDANCE WITH VAMC'S
EXISTING ROOF WARRANTY. COORDINATE ALL MODIFICATIONS TO THE ROOF WITH THE COR.
• ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET CAN BE REFERENCED FROM SHEET A000.
GENERAL NEW WORK NOTES
A S e rv ic e
D is a b le d
Ve t e r an Owned S m a l l B u s iness
SDVOSB
CVE
R
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY
08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT / ENGINEERS:
X
Office of Construction and Facilities
Managemen t o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 www.pfa-architect.com
ARCHITECTURE, PLANNING,
INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD
21045
410-750-2246 (BALT) 410-750-2588 (FAX)
KA PROJECT NUMBER: M023-08
K O
F F
E L
ASSOCIATES
ENGINEERS
Fire Protection
RENOVATE AND
EXPAND
OPERATING ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
2019-03-22
Approved: Medical Center Director
Building Number
TTI ENVIRONMENTAL, INC.
1253 NORTH CHURCH
STREET
MOORESTOWN, NJ 08057
BID DOCUMENTS
FULLY SPRINKLERED
637-315
New Work Plan - Second Floor - Phase 2 jasjht A102.207/26/2017
1/4" = 1'-0"
NEW WORK PLAN- SECOND FLOOR - PHASE 2
WALL TYPE SCHEDULE - PHASE 2
TYPE STC DESCRIPTION FIRE RATING UL REMARKS
M1B N/A 1 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE.
EXTEND GWB 4" ABOVE CEILING. FASTEN STUD TO UNDERSIDE
OF DECK.
M3 N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES.
EXTEND GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS
TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48" O.C.
MAX
M3_1 N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH
SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK
ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR
FIRE RATED PARTITION" AS REQUIRED BY BUILDING CODE.
PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M3_1S B
3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH
SIDES. EXTEND PARTITION TO UNDERSIDE OF DECK ABOVE.
1 HR SMOKE
BARRIER
PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE
BARRIER"
M3_C N/A 3 5/8" METAL STUDSAT 16" O.C. MAX. 5/8" GWB BOTH SIDES.
EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
SMOKE PARTITION - PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE
PARTITION" AS REQUIRED BY BUILDING CODE. PROVIDE
INSULATION WHERE COMPONENTS MEET DECK ABOVE
M3_SB 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH
SIDES. EXTEND PARTITION TO UNDERSIDE OF DECK ABOVE.
SMOKE BARRIER PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE
BARRIER"
M3B N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE.
EXTEND WALL ASSEMBLY TO 4" ABOVE FINISHED CEILING.
M6 N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES.
EXTEND GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS
TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48" O.C.
MAX
M6_1 N/A 6" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH
SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK
ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR
FIRE RATED PARTITION" AS REQUIRED BY BUILDING CODE.
PROVIDE INSULATION WHERE COMPONENTS MEET DECK
ABOVE.
M6_C N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES.
EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
SMOKE PARTITION - PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE
PARTITION" AS REQUIRED BY BUILDING CODE. PROVIDE
INSULATION WHERE COMPONENTS MEET DECK ABOVE
EQUPIMENT SCHEDULE - PHASE 2
MARK NAME VAFCI VAFOI VAFCI TYPE COMMENTS
AC ANESTHESIA COLUMN *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
AM ANESTHESIA MACHINE * PROVIDE POWER
ANC ANESTHESIA CART *
BW BLANKET WARMER *** PROVIDE POWER
CC CONTROL CONSOLE *
CPM COMPUTER MONITOR *** PROVIDE POWER AND DATA
EB EQUIPMENT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
IM INTEGRATION MONITOR *** PROVIDE POWER AND DATA
LB SURGICAL LIGHT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
LC LIGHT CONTROL *** PROVIDE POWER
MB MARKER BOARD *** *** PROVIDE BLOCKING AS REQUIRED
MTR WALL MONITOR *** PROVIDE POWER AND DATA
NCP NITROGEN CONTROL PANEL *** PROVIDE POWER
OC MOBILE OMNI CELL *** PROVIDE POWER AND DATA
ORT OR TABLE ***
RBT SURGICAL DI VINCI ROBOT *
SSC STAINLESS STEEL CART ***
ST STERILIZER *** PROVIDE POWER AND STEAM
VMT VIDEO MONITOR *
WPH WALL PHONE *** PROVIDE POWER AND DATA
TOILET ACCESSORY SCHEDULE - PHASE 2
MARK DESCRIPTION MOUNTING HEIGHT VAFCI VAFOI VAFCI REMARKS
PT PAPER TOWEL DISPENSER 48" ABOVE AFF TO BOTTOM OF OPENING OFCI
SD1 AUTOMATIC SOAP DISPENSER 38" A.F.F. TO BOTTOM ***
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
F
FLUSH SOLID CORE WOOD
FNV
FLUSH NARROW VISION
SOLID CORE WOOD
6" 7"
S C
H E
D U
L E
D H
E
IG
H T
SCHEDULED WIDTH
S C
H E
D U
L E
D H
E
IG
H T
SCHEDULED WIDTH
FDU
FLUSH DOUBLE UNEVEN
SOLID CORE WOOD
S C
H E
D U
L E
D H
E
IG
H T
1 1/2 HR
RATED
DOOR
1/4" TEMPERED
GLASS
1/4" FIRE
RATED
GLASS @
RATED
DOOR
4' - 0" 2' - 0"
FDE
FLUSH DOUBLE EGRESS
SOLID CORE WOOD
6" 7"
S C
H E
D U
L E
D H
E
IG
H T
SCHEDULED WIDTH
SCHEDULED WIDTH
FV
FLUSH VISION
SOLID CORE WOOD
1/4"
TEMPERED
GLASS
1/4"
FIRE RATED GLASS
@ RATED DOORS
3" WIDTH AT 1 1/2
HOUR RATED DOORS
3" WIDTH AT 1 1/2
HOUR RATED DOORS
2" 2"VARIES
V A
R
IE
S
2" 2"VARIES
V A
R
IE
S
1 2
2" 2"VARIES
V A
R
IE
S
2" 4' - 6" 2"
2" 3' - 8"
2"
2" 7' - 4"
2"
2" 3' - 8"
2"
A B C DALUMINUM HOLLOW METAL HOLLOW METAL
LEAD EQUIVALENT
ALUMINUM
1" INSULATED
GLAZING SEU
1/4"
INSULATED
GLAZING SEU
LEAD
EQUIVALENT
GLASS
1/4"
TEMPERED
GLASS
2" 3' - 8" 2"
1/4" TEMPERED
GLASS
E HOLLOW METAL
2" 6' - 6" 2" 3' - 0"
2"
LEAD
EQUIVALENT
GLASS
WIDTH TO MATCH EXISTING
1"
INSULATED
GLASS SEU
G ALUMINUMF HOLLOW METAL
LEAD LINED
A600
A600
A600
FINISHED FLOOR
FINISHED FLOOR
4' - 10"
7' - 8"
4' - 0" 4' - 0"
10' - 0"
A600
A600
A600
SIM
SIM
A600
A600
A600
SIM
SIM 9
A600
A600
A600
A600
A600
A600
A600
SIM
SIM
SIM
A600
A600
A600
SIM
SIM
SIM
2" 2"
N.4
3" EIFS WITH BACK WRAP
FLUID APPLIED AIR AND VAPOR BARRIER
6" MTL STUD @ 16" OC WITH 5.5" UNFACED
MINERAL WOOL INSULATION
5/8" GWB SHEATHING
2X TREATED WOOD BLOCKING
CONT BACKER ROD AND SEALANT, BOTH SIDES
ALUM FRAMED STOREFRONT W/ THERMALLY
BROKEN FRAME. SEE WINDOW ELEVATIONS FOR
GLAZING TYPE
4 5/8"
5/8" GWB, PAINTED
CONT CAULK N.4
3' - 8" AFF
/1
3/4" SOLID SURFACE WINDOW SILL
3/4"
4 5/8"
ALUM FRAMED STOREFRONT WITH
THERMALLY BROKEN FRAME, COLOR
TO MATCH EXISTING
CONT CAULK
2X WOOD BLOCKING
CONT BACKER ROD AND SEALANT,
BOTH SIDES
BACK-WRAP TERMINATION
WRAP ROUGH WINDOW OPENING
WITH VAPOR BARRIER, COMPATIBLE
WITH EIFS SYSTEM
EIFS WALL SYSTEM, INSTALL PER
MANUFACTURER'S REQUIREMENTS
ALUM FRAMED STOREFRONT WITH THERMALLY
BROKEN FRAME, COLOR TO MATCH EXISTING
CONT CAULK
2X WOOD BLOCKING
CONT BACKER ROD AND SEALANT,
BOTH SIDES
3" INSULATED ALUM METAL WALL PANEL,
DETAIL PER MANUFACTURER'S REQUIREMENTS
VAPOR BARRIER
5/8" GWB, TYP
CONT CAULK
HOLLOW METAL FRAME
2X WOOD BLOCKING
FOR PARTITION TYPE SEE
FLOOR PLAN
CONT CAULK
2"
P A
R T
IT
IO
N W
ID
T
H
A D
JU
S
T F
O R
FOR GLASS TYPE SEE
WINDOW ELEVATIONS
5/8" GWB, TYP
CONT CAULK
HOLLOW METAL FRAME
2X WOOD BLOCKING
FOR PARTITION TYPE SEE
FLOOR PLAN
CONT CAULK
2"
P A
R T
IT
IO
N W
ID
T
H
A D
JU
S
T F
O R
LEAD EQUIVALENT GLASS
LEAD LINING IN FRAME
LEAD LINING BEHIND
GWB
FLUID APPLIED AIR AND VAPOR BARRIER
6" MTL STUD BOX HEADER
2X TREATED WOOD BLOCKING
CONT BACKER ROD AND SEALANT, BOTH SIDES
ALUM FRAMED STOREFRONT W/ THERMALLY
BROKEN FRAME. SEE WINDOW ELEVATIONS FOR
GLAZING TYPE
5/8" GWB, PAINTED
CONT CAULK
EXISTING 9" CONCRETE BEAM
1" RIGID INSULATION
WEEP HOLES AT 16" OC
EXISTING BRICK
3x3x1/4 ANGLE MOUNTED TO EXISTING CONCRETE BEAM
THRU WALL FLASHING WITH METAL DRIP EDGE
6" METAL STUD AT 16" OC WITH 6" UNFACED MINERAL WOOL INSULATION
THRU WALL FLASHING WITH METAL DRIP EDGE
WEEP HOLE AT 16" OC
4x3x1/4" STEEL ANGLE
CEILING AS SCHEDULED. SEE FINISH SCHEDULE
2 1/8"
PATCH PLASTER
AS REQUIRED
SOLID SURFACE
THRU WALL FLASHING
WITH METAL DRIP EDGE
CONT BACKER ROD AND
SEALANT, BOTH SIDES
ALUMINUM STOREFRONT
WITH 1" INSULATED
GLAZING TO MATCH
EXISTING
EXISTING ROOFING SYSTEM
2X TREATED WOOD BLOCKING
CONT CAULK
EXISTING CONCRETE BEAM
SHIM
7 1/8"
/8
1 1/8"
6 1/16"
H.6
1 1/8"
CONT CAULK
SHIM
2X TREATED BLOCKING
CONT BACKER ROD
AND SEALANT, BOTH
SIDES
ALUMINUM STOREFRONT
WITH 1" INSULATED GLAZING
TO MATCH EXISTING
EXISTING BRICK
EXISTING CMU WALL
SYSTEM
5/8" GWB
J
SHIM
1 1/2" METAL STUD WITH
1 1/2" UNFACED MINERAL
WOOL INSULATION
DEMOLISH PORTION OF
EXISTING PRECAST
CONCRETE WRAP AS NEEDED
TO FIT WINDOW TYPE G
ALUMINUM
STOREFRONT WITH 1"
INSULATED GLAZING
TO MATCH EXISTING
CONT CAULK
1X TREATED WOOD BLOCKING
CONT BACKER ROD AND
SEALANT, BOTH SIDES
1 1/8"
EXISTING COLUMN
EIFS SHAPE
GWB
MTL STUDS
CAULK
HOLLOW METAL FRAME
1/2"
PROVIDE MINIMUM OF
3 JAMB ANCHORS PER
JAMB
SEE WALL TYPE
PERPINDICULAR WALL
-SEE PLAN IF APPLICABLE
A S e rv ic e
D is a b le d
Ve t e r an Owned S m a l l B u s iness
SDVOSB
CVE
R
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY
08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT / ENGINEERS:
X
Office of Construction and Facilities
Managemen t o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 www.pfa-architect.com
ARCHITECTURE, PLANNING,
INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD
21045
410-750-2246 (BALT) 410-750-2588 (FAX)
KA PROJECT NUMBER: M023-08
K O
F F
E L
ASSOCIATES
ENGINEERS
Fire Protection
RENOVATE AND
EXPAND
OPERATING ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
2019-03-22
Approved: Medical Center Director
Building Number
TTI ENVIRONMENTAL, INC.
1253 NORTH CHURCH
STREET
MOORESTOWN, NJ 08057
BID DOCUMENTS
FULLY SPRINKLERED
637-315
Door and Window Elevations, Schedule, Notes, and Details jhtjht A6003/2/15
3/8" = 1'-0"
DOOR TYPES
3/8" = 1'-0"
FRAME TYPES HOLLOW METAL
3/8" = 1'-0"
WINDOW TYPES
DOOR SCHEDULE - PHASE 1
NUMBER
DOOR FRAME FIRE
RATING HARDWARE REMARKSTYPE WIDTH HEIGHT THICKNESS TYPE HEAD JAMB SILL
2001 FDE 7' - 4" 7' - 0" 0' - 1 3/4" 2 4 SIM 4 1/3 HR HW-6B
2006 FDE 7' - 4" 7' - 0" 0' - 1 3/4" 2 4 SIM 4 1/3 HR HW-6B
2009 FDE 7' - 4" 7' - 0" 0' - 1 3/4" 2 4 SIM 4 1 1/2 HR HW-SH-4B
2010 FVDU 6' - 0" 7' - 0" 0' - 1 3/4" 3 4 SIM 4 - HW-10F
2011 FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2020 FVDU 6' - 0" 7' - 0" 0' - 1 3/4" 3 4 SIM 4 - HW-10F
2021 FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2030 FVDU 6' - 0" 7' - 0" 0' - 1 3/4" 3 4 SIM 4 - HW-10F
2031 FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 HW-4P
2032 FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 HW-4P
2033 FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2040A FVDU 6' - 0" 7' - 0" 0' - 1 3/4" 3 4 SIM 4 - HW-10H
2040B FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P LEAD LINED
2041A FD 7' - 4" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 HW-11A
2041B F 4' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 HW-5F
2050 FNV 3' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 - HW-4P LEAD LINED
2052 FNV 3' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 - HW-4P
2060A FD 6' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-10C
2060B FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2060C F 4' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2070 FVDU 6' - 0" 7' - 0" 0' - 1 3/4" 3 4 SIM 4 - HW-10F
2071 FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2080 FNV 4' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2090 F 3' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 HW-4G
DOOR SCHEDULE - PHASE 2
NUMBER
DOOR FRAME FIRE
RATING
HARDWAR
E REMARKSTYPE WIDTH HEIGHT THICKNESS TYPE HEAD JAMB SILL
2012 FDE 7' - 4" 7' - 0" 0' - 1 3/4" 2 4 SIM 4 1/3 HR HW-6B
2081 FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2100 FD 7' - 4" 7' - 0" 0' - 1 3/4" 3 4 SIM 4 3/4 HR HW-10C
2102 FNV 3' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4G
2120 FVDU 6' - 0" 7' - 0" 0' - 1 3/4" 3 4 SIM 4 - HW-10F
2121 FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2130A FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4C
2130B FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4C
2130C FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4C
2140 F 4' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-SH-3D
2150 FVDU 6' - 0" 7' - 0" 0' - 1 3/4" 3 4 SIM 4 - HW-10F
2170 F 3' - 0" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
2180 FD 7' - 4" 7' - 0" 0' - 1 3/4" 2 4 SIM 4 HW-10C
2181 FNV 3' - 8" 7' - 0" 0' - 1 3/4" 1 4 SIM 4 3/4 HR HW-4P
A600 1 1/2" = 1'-0"
1 HEAD DETAIL
A600 1 1/2" = 1'-0"
2 SILL DETAIL
A600 1 1/2" = 1'-0"
3 JAMB DETAIL
A600 3" = 1'-0"
5 JAMB DETAIL - HEAD AND SILL SIMILAR
A600 3" = 1'-0"
JAMB LEAD LINED DETAIL -
HEAD AND SILL SIMILAR
A600 1 1/2" = 1'-0"
7 HEAD DETAIL
A600 1 1/2" = 1'-0"
8 SILL DETAIL
A600 1 1/2" = 1'-0"
9 JAMB DETAIL
A600 1 1/2" = 1'-0"
10 JAMB DETAIL
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
A600 1 1/2" = 1'-0"
4 HOLLOW MTL STANDARD JAMB DTL
FINISH REMARKS
GENERAL FINISH NOTES
• PROVIDE ONE-PIECE VINYL TRANSITION STRIP AT ALL FLOOR FINISH TRANSITIONS. COLOR
SHALL MATCH ADJAENT RUBBER BASE.
• ALL FLOOR FINISH TRANSITIONS SHALL BE CONCEALED BY A CLOSED DOOR.
• ALL FINISHES LISTED ARE NEW UNLESS SPECIFIALLY NOTED AS EXISTING.
• WALL BASE SHALL BE RUBBER ROLL GOODS.
• WHERE PAINTED GWB ARE INDICATED, PAINTING INCLUDES ALL PREVIOUSLY PAINTED
SURFACES AND TRIM.
• HATCH PATTERNS ON FINISH PLANS ARE REPRESENTATIONAL ONLY TO DISTINGUISH
COLOR CHANGES, UNLESS OTHERWISE NOTED.
• ALL WALLS TO BE PAINTED PNT #1, EGGSHELL, UNLESS OTHERWISE NOTED. SEE FINISH
COLORS FOR INFORMATION.
• ALL TRIM TO BE PAINTED PNT#2, SEMI-GLOSS, UNLESS OTHERWISE NOTED. SEE FINISH
COLORS FOR INFORMATION.
• ALL VINYL COMPOSITION TILE TO BE INSTALLED MONOLITHIC.
• ALL EPOXY BASE TO BE 6" HIGH UNLESS OTHERWISE NOTED
FINISH COLORS
FLOOR
CONC#1 SEALED CONCRETE
SV#1 GRAY
SV#2 GRAY
EPXY#1 WHITE WITH BLUE SPECKS
EPXY#2 DARK BLUE WITH VARIOUS SHADES OF BLUE
WALL AND CEILING
PNT#1 (FIELD) EXTRA WHITE
PNT#2 (TRIM) EIDER WHITE
PNT#3 (ACCENT) LIGHT BLUE
PNT#4 (EPOXY) WHITE
ACT#1 (WHITE) 24" X 24" TILE
CG#1 (GRAY) DRIFTWOOD
CG#2 (METAL) BRUSHED SILVER
RB#1 (GREY) METALLIC FINISH
WS#1 (GRAY) DRIFTWOOD
BG#1 (METAL) BRUSHED SILVER
CASEWORK
SS#1 (WHITE) WHITE WITH SPECS
SS#2 (GRAY) PLATINUM
PLAM#1 GREY WOOD GRAIN
PLAM#2 (HORIZONTAL) OFF WHITE LINEN
1. PROVIDE WAINSCOT (WS#1) ALL WALLS TO 48"
2. PROVIDE BUMPER GUARD (BG#1) AT 34" AFF PROVIDE WAINSCOT (WS#1) TO TERMINATE
AT CENTER OF BUMPER GUARD. SEE FINISH COLORS FOR MORE INFORMATION.
3. PROVIDE ACCENT WALL PAINT PNT#3. SEE NEW WORK NOTE - ON A102.
4. PROVIDE 4" COVE BASE AND HEAT WELDED SEAMS. SEE DETAIL 1/610.
5. PROVIDE FLOOR PATTERN PLAN THIS ROOM. SEE SHEET A620 FLOOR FINISH PLAN FOR
MORE INFORMATION.
6. CEILING HT. FOR THIS ROOM IN ITS ENTIRETY IS TAKEN FROM THE SURGERY FLOOR.
7. SEE SECTION 2/A500.
8. PHASE 1 - RIGHT OF COLUMN 16. PHASE 2 - LEFT OF COLUMN 16.
9. ALL TRIM AND WINDOWS FRAMES TO BE PAINTED WITH EPOXY PNT#4.
10. NO FINISH WORK ANTICIPATED THIS ROOM.
VINYL COVE CAP
WALL AS SCHEDULED
SHEET VINYL RESILIENT
FLOORING TURNED UP
TO FORM BASE
RUBBER FILLET STRIP
SHEET VINYL
RESILIENT FLOORING
FINISH
FLOOR
CAULK
A S e rv ic e
D is a b le d
Ve t e r an Owned S m a l l B u s iness
SDVOSB
CVE
R
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY
08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT / ENGINEERS:
X
Office of Construction and Facilities
Managemen t o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 www.pfa-architect.com
ARCHITECTURE, PLANNING,
INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD
21045
410-750-2246 (BALT) 410-750-2588 (FAX)
KA PROJECT NUMBER: M023-08
K O
F F
E L
ASSOCIATES
ENGINEERS
Fire Protection
RENOVATE AND
EXPAND
OPERATING ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
2019-03-22
Approved: Medical Center Director
Building Number
TTI ENVIRONMENTAL, INC.
1253 NORTH CHURCH
STREET
MOORESTOWN, NJ 08057
BID DOCUMENTS
FULLY SPRINKLERED
637-315
Finish Schedule, Notes, and Details jasjht A61002/23/15
FINISH SCHEDULE - PHASE 1
NUMBER ROOM NAME
FLOOR BASE WALL CEILING
REMARKSMTL COLOR MTL COLOR MTL COLOR MTL COLOR HEIGHT
2000 RAMP SV SV#2 SV SV#2 PTD GWB /WS PNT#1, PNT#3 / WS#1 ACT / PTD GWB ACT#1 / PNT#1 VARIES 1,2,3,4,7
2001 SEMI-RESTRICTED CORRIDOR SV SV#2 SV SV#2 PTD GWB /WS PNT#1, PNT#3 / WS#1 ACT ACT#1 8' - 0" 1,2,3,4
2002 SEMI-RESTRICTED CORRIDOR SV SV#2 SV SV#2 PTD GWB /WS PNT#1, PNT#3 / WS#1 ACT ACT#1 8' - 0" 1,2,3,4
2003 SCRUB SV SV#2 SV SV#2 PTD GWB /WS PNT#1 / WS#1 ACT ACT#1 7' - 10" 1,2,4
2004 SCRUB SV SV#2 SV SV#2 PTD GWB /WS PNT#1 / WS#1 ACT ACT#1 7' - 10" 1,2,4
2005 SCRUB SV SV#2 SV SV#2 PTD GWB /WS PNT#1 / WS#1 ACT ACT#1 7' - 10" 1,2,4
2006 CORRIDOR SV SV#2 SV SV#2 PTD GWB /WS PNT#1, PNT#3 / WS#1 ACT ACT#1 8' - 0" 1,2,3,4
2007 RAMP SV SV#2 SV SV#2 PTD GWB /WS PNT#1, PNT#3 / WS#1 ACT / PTD GWB ACT#1 / PNT#1 VARIES 1,2,3,4
2009 SEMI-RESTRICTED CORRIDOR SV SV#2 SV SV#2 PTD GWB /WS PNT#1 / WS#1 ACT ACT#1 9' - 0" 1,2,4,8
2010 GENERAL OR EPXY/RES-3 EPXY#1,EPXY#2 EPXY EPXY#1 GWB W/RSC RES-W2 PNT#4 EPOXY PTD GWB PNT#1 10' - 0" 5,9
2016 SCRUB SV SV#2 SV SV#2 PTD GWB /WS PNT#1 / WS#1 ACT ACT#1 7' - 10" 1,4
2020 GENERAL OR EPXY/RES-3 EPXY#1,EPXY#2 EPXY/RES-3 EPXY#1 GWB W/RSC RES-W2 PNT#4 EPOXY PTD GWB PNT#1 10' - 0" 5,9
2030 CARDIAC OR EPXY/RES-3 EPXY#1,EPXY#2 EPXY/RES-3 EPXY#1 GWB W/RSC RES-W2 PNT#4 EPOXY PTD GWB PNT#1 10' - 0" 5,9
2031 HEART/LUNG MACHINE ROOM EPXY/RES-3 EPXY#1 EPXY/RES-3 EPXY#1 GWB W/RSC RES-W2 PNT#4 EPOXY PTD GWB PNT#1 9' - 0" 1,2,4,9
2040 HYBRID OR EPXY/RES-3 EPXY#1,EPXY#2 EPXY/RES-3 EPXY#1 GWB W/RSC RES-W2 PNT#4 ACT ACT#1 10' - 0" 5,9
2041 HYBRID EQUIP SV SV#2 SV…