Department of Veteran Affairs H.H. McGuire VA Medical Center Richmond, Virginia
VA Project #652-17-104 A/E Upgrade Pharmacy to USP 800
Bid Documents: 2/14/19
28 23 00 - 1
SECTION 28 23 00
VIDEO SURVEILLANCE
PART 1 - GENERAL
1.1 DESCRIPTION
A. Provide and install a complete Video Surveillance System as an extension of the existing system, which is identified as the Video
Assessment and Surveillance System hereinafter referred to as the VASS
System as specified in this section.
B. This Section includes video surveillance system consisting of cameras, and data transmission wiring.
1.2 RELATED WORK
A. Section 01 00 00 - GENERAL REQUIREMENTS. For General Requirements.
B. Section 26 05 11 - REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.
Requirements for connection of high voltage.
C. Section 26 05 19 - LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
(600 VOLTS AND BELOW). Requirements for power cables.
D. Section 28 05 00 – COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for general requirements that are common to more than one section in Division 28.
E. Section 28 05 13 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for conductors and cables.
F. Section 28 05 26 - GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for grounding of equipment.
G. Section 28 05 28.33 - CONDUITS AND BACKBOXES FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for infrastructure.
1.3 DEFINITIONS
A. AGC: Automatic gain control.
B. B/W: Black and white.
C. CCD: Charge-coupled device.
D. CIF: Common Intermediate Format. CIF images are 352 pixels wide and
88/240 (PAL/NTSC) pixels tall (352 x 288/240).
E. 4CIF: resolution is 704 pixels wide and 576/480 (PAL/NTSC) pixels tall
(704 x 576/480).
F. 264 (also known as MPEG4 Part 10): an encoding format that compresses video much more effectively than older (MPEG4) standards.
G. ips: Images per second.
H. MPEG: Moving picture experts group.
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 2
I. MPEG4: a video encoding and compression standard that uses inter-frame encoding to significantly reduce the size of the video stream being transmitted.
J. NTSC: National Television System Committee.
K. UPS: Uninterruptible power supply.
L. PTZ: refers to a movable camera that has the ability to pan left and right, tilt up and down, and zoom or magnify a scene.
1.4 QUALITY ASSURANCE
A. The Contractor shall be responsible for providing, installing, and the operation of the VASS System as shown. The Contractor shall also provide certification as required.
B. The security system shall be installed and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the security system is stand-alone or a part of a complete Information Technology (IT) computer network.
C. The Contractor or security sub-contractor shall be a licensed security
Contractor as required within the state or jurisdiction of where the installation work is being conducted.
D. Manufacturers Qualifications: The manufacturer shall regularly and presently produce, as one of the manufacturer's principal products, the equipment and material specified for this project, and shall have manufactured the item for at least three years.
E. Product Qualification:
1. Manufacturer's product shall have been in satisfactory operation, on three installations of similar size and type as this project, for approximately three years.
2. The Government reserves the right to require the Contractor to submit a list of installations where the products have been in operation before approval.
F. Contractor Qualification:
1. The Contractor or security sub-contractor shall be a licensed security Contractor with a minimum of five (5) years experience installing and servicing systems of similar scope and complexity.
The Contractor shall be an authorized regional representative of the
Video Assessment and Surveillance System’s (VASS) manufacturer. The
Contractor shall provide four (4) current references from clients
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 3 with systems of similar scope and complexity which became operational in the past three (3) years. At least three (3) of the references shall be utilizing the same system components, in a similar configuration as the proposed system. The references must include a current point of contact, company or agency name, address, telephone number, complete system description, date of completion, and approximate cost of the project. The owner reserves the option to visit the reference sites, with the site owner’s permission and representative, to verify the quality of installation and the references’ level of satisfaction with the system. The Contractor shall provide copies of system manufacturer certification for all technicians. The Contractor shall only utilize factory-trained technicians to install, program, and service the VASS. The
Contractor shall only utilize factory-trained technicians to install, terminate and service cameras, control, and recording equipment. The technicians shall have a minimum of five (5) continuous years of technical experience in electronic security systems. The Contractor shall have a local service facility. The facility shall be located within 60 miles of the project site. The local facility shall include sufficient spare parts inventory to support the service requirements associated with this contract. The facility shall also include appropriate diagnostic equipment to perform diagnostic procedures. The COR reserves the option of surveying the company’s facility to verify the service inventory and presence of a local service organization.
G. Service Qualifications: There shall be a permanent service organization maintained or trained by the manufacturer which will render satisfactory service to this installation within four hours of receipt of notification that service is needed. Submit name and address of service organizations.
1.5 SUBMITTALS
A. Submit below items in conjunction with Master Specification Sections 01
33 23, Shop Drawings, Product Data, and Samples, and Section 02 41 00, Demolition Drawings.
B. Provide certificates of compliance with Section 1.4, Quality Assurance.
C. Provide manufacturer security system product cut-sheets. Submit for approval at least 30 days prior to commencement of formal testing, a
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 4
Security System Operational Test Plan. Include procedures for operational testing of each component and security subsystem, to include performance of an integrated system test.
D. Submit manufacture’s certification of Underwriters Laboratories, Inc.
(UL) listing as specified. Provide all maintenance and operating manuals per the VA General Requirements, Section 01 00 00, GENERAL
REQUIREMENTS.
1.6 APPLICABLE PUBLICATIONS
A. The publications listed below (including amendments, addenda, revisions, supplement, and errata) form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American National Standards Institute (ANSI)/Electronic Industries
Alliance (EIA):
330-09..................Electrical Performance Standards for CCTV
Cameras
375A-76.................Electrical Performance Standards for CCTV
Monitors
C. Institute of Electrical and Electronics Engineers (IEEE):
C62.41-02...............IEEE Recommended Practice on Surge Voltages in
Low-Voltage AC Power Circuits
802.3af-08..............Power over Ethernet Standard
D. Federal Communications Commission (FCC):
(47 CFR 15) Part 15 Limitations on the Use of Wireless
Equipment/Systems
E. National Electrical Contractors Association (NECA):
303-2005................Installing Closed Circuit Television (CCTV)
Systems
F. National Fire Protection Association (NFPA):
70-17...................Article 780-National Electrical Code
G. Federal Information Processing Standard (FIPS):
140-2-02................Security Requirements for Cryptographic Modules
H. Underwriters Laboratories, Inc. (UL):
983-06..................Standard for Surveillance Camera Units
3044-01.................Standard for Surveillance Closed Circuit
Television Equipment
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 5
1.7 COORDINATION
A. Coordinate arrangement, mounting, and support of video surveillance equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other installations.
3. To allow right of way for piping and conduit installed at required slope.
4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.
B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.
C. Coordinate location of access panels and doors for video surveillance items that are behind finished surfaces or otherwise concealed.
1.8 WARRANTY OF CONSTRUCTION
A. Warrant VASS System work subject to the Article “Warranty of
Construction” of FAR clause 52.246-21.
B. Demonstration and training shall be performed prior to system acceptance.
PART 2 - PRODUCTS
2.1 GENERAL
A. Video signal format shall comply with the NTSC standard composite video, interlaced. Composite video signal termination shall be 75 ohms.
B. Surge Protection: Protect components from voltage surges originating external to equipment housing and entering through power, communication, signal, control, or sensing leads. Include surge protection for external wiring of each conductor entry connection to components.
C. Power Connections: Comply with requirements in Section 28 05 00 COMMON
WORK REQUIREMENTS FOR ELECTRONIC SAFETY AND SECURITY, Part 2, as recommended by manufacturer for type of line being protected.
D. Tamper Protection: Tamper switches on cameras and other system components shall initiate a tamper-alarm signal when unit is opened or
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 6 partially disassembled. Control-station, control-unit alarm display shall identify tamper alarms and indicate locations.
2.2 CAMERAS
A. All Cameras will be EIA 330 and UL 1.Minimum Protection for Power
Connections 120 V and more: Auxiliary panel suppressors shall comply with requirements in Section 28 05 00 COMMON WORK REQUIREMENTS FOR
ELECTRONIC SAFETY AND SECURITY, Part 2.
B. Minimum Protection for Communication, Signal, Control, and Low-Voltage
983 compliant as well as:
1. Will be charge coupled device (CCD cameras and shall conform to
National Television System Committee (NTSC) formatting.
2. Fixed cameras shall be color and the primary choice for monitoring following the activities described below. Pan/Tilt/Zoom (P/T/Z) cameras shall be color and are to be utilized to complement the fixed cameras.
3. Shall be powered by either 12 volts direct current (VDC) or 24 volts alternate current (VAC). Power supplies shall be Class 2 and UL compliant and have a back-up power source to ensure cameras are still operational in the event of loss of primary power to the VASS
System. Match existing system type
4. In the event that the cameras are not 12 or 24 VDC, cameras shall be powered over Ethernet. Network switches supporting PoE cameras shall have a back-up power source to ensure cameras are still operational in the event of loss of primary power to the VASS
System. Match existing system type.
5. Shall be rated for continuous operation under the environmental conditions listed in Part 1, Project Conditions.
6. Each function and activity shall be addressed within the system by a unique user defined name, with minimum of twenty (20) characters.
The use of codes or mnemonics identifying the VASS action shall not be accepted.
7. Dummy or fake cameras will not be utilized at any time.
8. Appropriate signage shall be designed, provided, and posted that notifies people that an area is under camera surveillance.
2.3 VIDEO CAMERAS
A. The cameras shall be high-resolution color video cameras with wide dynamic range capturing capability.
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 7
B. The camera shall meet or exceed the following specifications:
1. The image capturing device shall be a 1/4-inch image sensor designed for capturing wide dynamic images.
a. The image capturing device shall have a separate analog-to-digital converter for every pixel.
b. The image capturing device shall sample each pixel multiple times per second.
c. The dynamic range shall be 95 dB typical and 120 dB maximum.
2. The camera shall optimize each pixel independently.
3. The camera shall have onscreen display menus for programming of the camera’s settings.
4. The signal system shall be NTSC.
C. The camera shall have composite video output.
D. The camera shall come with a manual varifocal lens.
E. The video output shall be composite: 1.0 volts peak-to-peak at 75-ohm load.
F. Fixed Color Camera
1. The camera shall be a high-resolution color video camera with wide dynamic range capturing capability.
2. Comply with UL 639.
3. Pickup Device: 1/3 CCD interline transfer.
4. Signal-to-Noise Ratio: Not less than 50 dB, with the camera AGC off.
5. With AGC, manually selectable on or off.
6. Manually selectable modes for backlight compensation or normal lighting.
7. Scanning Synchronization: Determined by external synch over the coaxial cable. Camera shall revert to internally generated synchronization on loss of external synch signal.
8. White Balance: Auto-tracing white balance, with manually selectable fixed balance option.
9. Fixed Color Cameras Technical Characteristics:
Pickup device 1/3" interline transfer CCD
Total pixels NTSC: 811(H) x 508(V)
Effective pixels NTSC: 768(H) x 494(V)
Resolution 500 TV lines
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 8
Sync. System Internal Sync
Scanning system NTSC: 525 Lines/60 Fields
S/N ratio More than 48 dB
Electronic shutter Auto 1/60 (1/50) ~1/100,000 sec.
Min. illumination 0.2 lux F2.0
Video output Composite 1.0 Vp-p/75 ohm
White balance Auto
Automatic gain control ON
Frequency horizontal NTSC: 15.734 KHz
Frequency vertical NTSC: 59.94Hz
Lens type Board lens/DC varifocal lens
Focal length 3-12mm
Power source DC12V/500mA or AC24/500mA
Power consumption < 3W (Max)
10. Fixed color camera shall be enclosed in dome and have board mounted varifocal lens.
11. Camera accessories shall include:
a. Surface mount adapter
b. Wall mount adapter
c. Flush mount adapter
2.4 AUTOMATIC COLOR DOME CAMERA - ANALOG
A. The camera shall be a high-resolution color video camera with wide dynamic range capturing capability.
B. Comply with UL 639.
C. Pickup Device: 1/3 CCD interline transfer.
D. Horizontal Resolution: 480 lines.
E. Signal-to-Noise Ratio: Not less than 50 dB, with the camera AGC off.
F. With AGC, manually selectable on or off.
G. Sensitivity: Camera shall deliver 1-V peak-to-peak video signal at the minimum specified light level. The illumination for the test shall be with lamps rated at approximately 2200-K color temperature, and with the camera AGC off.
H. Manually selectable modes for backlight compensation or normal lighting.
I. Network Cameras
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 9
1. Shall be IEEE 802.3af compliant.
a. Shall be utilized for interior and exterior purposes.
b. A Category CAT6 cable will be the primary source for carrying signals up to 100 m(300 ft.) from a switch hub or network server. If any camera is installed greater than 300 ft. from the controlling device then the following will be required:
1) A local or remote 12 VDC or 24 VAC power source will be required from a Class 2, UL compliant power supply.
2) A signal converter will be required to convert from a CAT6 cable over to a fiber optic or standard signal cable. The signal will need to be converted back to a CAT6 cable at the controlling device using a signal converter card.
c. Shall be routed to a controlling device via a network switch.
d. Shall be of hybrid design with both an Internet Protocol (IP) output and a monitor video output which produces a picture equivalent to an analog camera, and allows simultaneous output of both.
e. Shall be a programmable IP address that allows for installation of multiple units in the same Local Area Network
(LAN) environment.
f. Incorporate a minimum of Transmission Control Protocol
(TCP)/IP, User Datagram Protocol (UDP), Hypertext Transfer
Protocol (HTTP), File Transfer Protocol (FTP), Internet
Control Message Protocol (ICMP0, Address Resolution Protocol
(ARP), Real-Time Transport Protocol (RTP), Dynamic Host
Configuration Protocol (DHCP), Network Time Protocol (NTP), Simple Mail Transfer Protocol (SMTP), Internet Group
Management Protocol (IGMP), and Differentiated Service Code
Point (DSCP) protocols for various network applications.
J. Fixed Network Camera
1. The fixed network camera shall have following technical characteristics:
Video Standards MPEG-4; M-JPEG
Video Data Rate 9.6 Kbps - 6 Mbps Constant & variable
Image Resolution 768x494 (NTSC)
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 10
Video Resolution 704 x 576/480 (4CIF: 25/30 IPS)
704 x 288/240 (2CIF: 25/30 IPS) 352 x 288/240 (CIF: 25/30 IPS) 176 x 144/120 (QCIF: 25/30 IPS)
Select Frame Rate 1-25/30 IPS (PAL/NTSC);Field/frame based coding
Network Protocols RTP, Telnet, UDP, TCP, IP, HTTP, IGMP, ICMP
Software Update Flash ROM, remote programmable
Configuration Via web browser, built-in web server interfaces
Video Out 1x Analog composite: NTSC or PAL;
BNC connector 75 Ohm
Sensitivity 1 0.65 lux (color) 0.26 lux (NightSense)
Minimum Illumination 0.30 lux (color)0.12 lux (NightSense)
Video Signal-to-Noise Ratio
50 dB
Video Signal Gain 21 dB, (max) Electronic Shutter Automatic, up to 1/150000 sec.
(NTSC)
Alarm In Automatic sensing (2500 - 9000 K)
Input Voltage +5 V nominal, +40 VDC max VDC: 11-36 V (700 mA) VAC: 12-28 V (700 mA) PoE: IEEE 802.3af compliant
2. Camera accessories shall include:
a. Surface mount adapter
b. Wall mount adapter
c. Flush mount adapter
K. Lenses
1. Camera Field of View shall be set by the Contractor to produce full view of door or window opening and anyone entering or leaving through it. Follow the project construction drawings for design intent.
2. Camera Lenses shall be of the type supplied with the camera from the manufacture. All cameras which are not supplied with lenses from the factory are specified in this specification. The lens shall be equipped with an auto-iris mechanism unless otherwise specified.
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 11
Lenses having auto-iris, DC iris, or motor zoom functions shall be supplied with connectors, wiring, receiver/drivers, and controls as needed to operate the lens functions. Lenses shall have sufficient circle of illumination to cover the image sensor evenly. Lenses shall not be used on a camera with an image format larger than the lens is designed to cover. Lenses shall be provided with pre-set capability.
3. Lenses shall have optical-quality coated optics, designed specifically for video surveillance applications, and matched to specified camera. Provide color-corrected lenses with color cameras, megapixel lenses for megapixel cameras, and lenses with day/night for color/b&w cameras.
4. Auto-Iris Lens: Electrically controlled iris with circuit set to maintain a constant video level in varying lighting conditions.
5. Zoom Lenses: Motorized, remote-controlled units, rated as "quiet operating." Features include the following:
a. Electrical Leads: Filtered to minimize video signal interference.
b. Motor Speed: Variable.
c. Lens shall be available with preset positioning capability to recall the position of specific scenes.
6. Lenses: Shall be utilized in a manner that provides maximum coverage of the area being monitored by the camera. The lenses shall:
a. Be 1/3” to fit CCD fixed camera.
b. Be all glass with coated optics.
c. Have mounts that are compatible with the camera selected.
d. Be packaged and supplied with the camera.
e. Have a maximum f-stop of f/1.3 for fixed lenses, and a maximum f-stop of f/1.6 for variable focus lenses.
f. Be equipped with an auto-iris mechanism.
g. Have sufficient circle of illumination to cover the image sensor evenly.
h. Not be used on a camera with an image format larger than the lens is designed to cover.
i. Be provided with pre-set capability.
7. Two types of lenses shall be utilized for both interior and exterior fixed cameras:
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 12
a. Manual Variable Focus
b. Auto Iris Fixed
8. Manual Variable Focus:
a. Shall be utilized in large areas that are being monitored by the camera. Examples of this are perimeter fence lines, vehicle entry points, parking areas, etc.
b. Shall allow for setting virtually any angle of field, which maximizes surveillance effects.
c. Technical Characteristics:
Image format 1/3 inch
Focal length 5–50mm
Iris range F1.4 to close
Focus range 1m (3.3 ft)
Back focus distance 10.05 mm (0.4 in)
Angle view Wide (1/3 in) 53.4 x 40.1
Angle view Tele (1/3 in) 5.3 x 4.1
Iris control manual
Focus ctrl manual
Zoom ctrl manual
L. Camera Housings and Mounts
1. This section pertains to all interior and exterior housings, domes, and applicable wall, ceiling, corner, pole, and rooftop mounts associated with the housing. Housings and mounts shall be specified in accordance to the type of cameras used.
2. All cameras and lenses shall be enclosed in a tamper resistant housing. Any additional mounting hardware required to install the camera housing at its specified location shall be provided along with the housing.
3. The camera and lens contained inside the housing shall be installed on a camera mount. All additional mounting hardware required to install the camera housing at its specified location shall be provided along with the housing.
4. Shall be manufactured in a manner that are capable of supporting a maximum of three (3) cameras with housings, and meet environmental requirements for the geographical area the camera support equipment is being installed on or within.
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 13
5. Environmentally Sealed
a. Shall be designed in manner that it provides a condensation free environment for correct camera operation.
b. Shall be operated in a 100 percent condensing humidity atmosphere.
c. Shall be constructed in a manner that:
1) Has a fill valve to allow for the introduction of nitrogen into the housing to eliminate existing atmospheric air and pressurize the housing to create moisture free conditions.
2) Has an overpressure valve to prevent damage to the housing in the event of over pressurization.
3) Is equipped with a humidity indicator that is visible to the eye to ensure correct atmospheric conditions at all times.
4) The leak rate of the housing is not to be greater than 13.8kPa or 2 pounds per square inch at sea level within a 90 day period.
5) It shall contain camera mounts or supports as needed to allow for correct positioning of the camera and lens.
6) The housing and sunshield are to be white in color.
6. All electrical and signal cables required for correct operations shall be supplied in a hardened carrier system from the controller to the camera.
7. The mounting bracket shall be adjustable to allow for the housing weight of the camera and the housing unit it is placed in.
8. Accessibility to the camera and mounts shall be taken into consideration for maintenance and service purposes.
M. Indoor Mounts
1. Ceiling Mounts:
a. This enclosure and mount shall be installed in a finished or suspended ceiling.
b. The enclosure and mount shall be fastened to the finished ceiling, and shall not depend on the ceiling tile grid for complete support.
c. Suspended ceiling mounts shall be low profile, and shall be suitable for replacement of 610mm x 610mm (2 foot by 2 foot) ceiling tiles.
2. Wall Mounts:
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 14
a. The enclosure shall be installed in manner that it matches the existing décor and placed at a height that it will be unobtrusive, unable to cause personal harm, and prevents tampering and vandalism.
b. The mount shall contain a manual pan/tilt head that will provide 360 degrees of horizontal and vertical positioning from a horizontal position, and has a locking bar or screw to maintain its fixed position once it has been adjusted.
N. Interior Domes
1. The interior dome shall be a pendant mount, pole mount, ceiling mount, surface mount, or corner mounted equipment.
2. The lower portion of the dome that provides camera viewing shall be made of black opaque acrylic and shall have a light attenuation factor of no more that 1 f-stop.
3. The housing shall be equipped with integral pan/tilt capabilities complete with wiring, wiring harness, connectors, receiver/driver, pan/tilt control system, pre-position cards, or any other hardware and equipment as needed to fully provide a fully functional pan/tilt dome.
4. The pan/tilt mechanism shall be:
a. Constructed of heavy duty bearings and hardened steel gears.
b. Permanently lubricated to ensure smooth and consistent movement of all parts throughout the life of the product.
c. Equipped with motors that are thermally or impedance protected against overload damage.
d. Pan movements shall be 360 degrees and tilt movement shall no be less than +/- 90 degrees.
e. Pan speed shall be a minimum of 10 degrees per second.
2.5 POWER SUPPLIES
Power supplies shall be a low-voltage power supplies matched for voltage and current requirements of cameras and accessories, type as recommended by camera and lens manufacturer.
2.6 WIRES AND CABLES
A. Shall meet or exceed the manufactures recommendation for power and signal.
B. Will be carried in an enclosed conduit system, utilizing electromagnetic tubing (EMT) to include the equivalent in flexible
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 15 metal, rigid galvanized steel (RGS) to include the equivalent of liquid tight, polyvinylchloride (PVC) schedule 40 or 80.
C. All conduits will be sized and installed per the NEC. All security system signal and power cables that traverse or originate in a high security office space will contained in either EMT or RGS conduit.
D. All conduit, pull boxes, and junction boxes shall be clearly marked with colored permanent tape or paint that will allow it to be distinguished from all other conduit and infrastructure.
E. Conduit fills shall not exceed 50 percent unless otherwise documented.
F. A pull string shall be pulled along and provided with signal and power cables to assist in future installations.
G. At all locations where there is a wall penetration or core drilling is conducted to allow for conduit to be installed, fire stopping materials shall be applied to that area
H. High voltage and signal cables shall not share the same conduit and shall be kept separate up to the point of connection. High voltage for the security system shall be defined as any cable or sets of cables carrying 30 VDC/VAC or higher.
I. Coaxial Cables
1. All video signal cables for the VASS System, with exception to the
PoE cameras, shall be a coaxial cable and have a characteristic impedance of 75 ohms plus or minus 3 ohms.
2. For runs up to 750 feet use of an RG-59/U is required. The RG-59/U shall be shielded which provides a minimum of 95 percent coverage, with a stranded copper center conductor of a minimum 23 AWG, polyethylene insulation, and black non-conductive polyvinylchloride
(PVC) jacket.
3. For runs between 750 feet and 1250 feet, RG-6/U is required. RG-6/U shall be shielded which provides a minimum of 95 percent coverage, with a stranded copper center conductor of a minimum 18 AWG, polyethylene insulation, and black non-conductive polyvinylchloride
(PVC) jacket.
4. RG-59/U Technical Characteristics
AWG 22
Stranding 7x29
Conductor Diameter .031 in.
Conductor Material BCC
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 16
Insulation Material Gas-injected FHDPE
Insulation Diameter .145 in.
Outer Shield Type Braid/Braid
Outer Jacket Material PVC
Overall Nominal Diameter .242 in.
UL Temperature Rating 75°C
Nom. Characteristic Impedance 75 Ohms
Nom. Inductance 0.094 μH/ft
Nom. Capacitance Conductor to Shield 17.0 pF/ft
Nom. Velocity of Propagation 80 %
Nom. Delay 1.3 ns/ft
Nom. Conductor DC Resistance @ 20°C
12.2 Ohms/1000 ft
Nom. Outer Shield DC Resistance @ 20°C
2.4 Ohms/1000 ft
Max. Operating Voltage UL 300 V RMS
5. RG-6/U Technical Characteristics:
AWG 18
Stranding 7x27
Conductor Diameter .040 in.
Conductor Material BC
Insulation Material Gas-injected FHDPE
Insulation Diameter .180 in.
Outer Shield Material Trade Name Duofoil
Outer Shield Type Tape/Braid
Outer Shield %Coverage 100 %
Outer Jacket Material PVC
Overall Nominal Diameter .274 in.
Nom. Characteristic Impedance
75 Ohms
Nom. Inductance 0.106 μH/ft
Nom. Capacitance Conductor to Shield 16.2 pF/ft
Nom. Velocity of Propagation
82 %
Nom. Delay 1.24 ns/ft
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 17
Nom. Conductor DC
Resistance
6.4 Ohms/1000 ft
Nominal Outer Shield DC Resistance @ 20°C
2.8 Ohms/1000 ft
6. Signal Cables:
a. Signal wiring for PoE cameras depends on the distance the camera is being installed from either a hub or the server.
b. If the camera is up to 300 ft from a hub or the server, then use a shielded UTP category 6 cable a with standard RJ-45 connector at each end. The cable with comply with the Power over Ethernet, IEEE802.3af, Standard.
c. Provide a separate cable for power.
d. CAT-6 Technical Characteristics:
Number of Pairs 4
Total Number of Conductors 8
AWG 24
Stranding Solid
Conductor Material BC - Bare Copper
Insulation Material PO – Polyolefin (plenum rated)
Overall Nominal Diameter .230 in.
IEC Specification 11801 Category 6
TIA/EIA Specification 568-C.2 Category 6
Max. Capacitance Unbalance (pF/100 m) 150 pF/100 m
Nom. Velocity of Propagation 70 %
Max. Delay (ns/100 m) 538 @ 100MHz
Max. Delay Skew (ns/100m) 45 ns/100 m
Max. Conductor DC Resistance 9.38 Ohms/100
Max. DCR Unbalance@ 20°C 3 %
PART 3 - EXECUTION
3.1 GENERAL
A. Installation: The Contractor shall install all system components including Owner furnished equipment, and appurtenances in accordance with the manufacturer’s instructions, ANSI C2 and as shown, and shall
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 18 furnish all necessary connectors, terminators, interconnections, services, and adjustments required for a complete and operable data transmission system.
B. Identification and Labeling: The Contractor shall supply permanent identification labels for each cable at each end that will appear on the as-built drawings. The labeling format shall be identified and a complete record shall be provided to the Owner with the final documentation. Each cable shall be identified by type or signal being carried and termination points. The labels shall be printed on letter size label sheets that are self laminated vinyl that can be printed from a computer data base or spread sheet. The labels shall be E-Z code WES12112 or equivalent.
1. The Contractor shall provide all personnel, equipment, instrumentation, and supplies necessary to perform all testing.
C. Contractor’s Field Test: The Contractor shall verify the complete operation of the data transmission system during the Contractor’s Field
Testing. Field test shall include a bit error rate test. The
Contractor shall perform the test by sending a minimum of 1,000,000 bits of data on each DTM circuit and measuring the bit error rate. The bit error rate shall not be greater than one (1) bit out of each
100,000 bits sent for each dial-up DTM circuit, and one (1) bit out of
1,000,000 bits sent for each leased or private DTM circuit. The
Contractor shall submit a report containing results of the field test.
D. Acceptance Test and Endurance Test: The wire line data transmission system shall be tested as a part of the completed IDS and EECS during the Acceptance test and Endurance Test as specified.
E. Identification and Labeling: The Contractor shall supply identification tags or labels for each cable. Cable shall be labeled at both end points and at intermediate hand holes, manholes, and junction boxes. The labeling format shall be identified and a complete record shall be provided to the Owner with the final documentation.
Each cable shall be identified with type of signal being carried and termination points.
3.2 INSTALLATION
A. System installation shall be in accordance with NECA 303, manufacturer and related documents and references, for each type of security subsystem designed, engineered and installed.
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 19
B. Components shall be configured with appropriate “service points” to pinpoint system trouble in less than 30 minutes.
C. The Contractor shall install all system components including Government furnished equipment, and appurtenances in accordance with the manufacturer's instructions, documentation listed in Sections 1.5 of this document, and shall furnish all necessary connectors, terminators, interconnections, services, and adjustments required for a complete and operable system.
D. The VASS System will be designed, engineered, installed, and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the system is a stand alone or a complete network.
E. For programming purposes refer to the manufacturers requirements for correct system operations. Ensure computers being utilized for system integration meet or exceed the minimum system requirements outlined on the systems software packages.
F. The extension of the complete VASS System shall be comprised of, but not limited to, the following components:
1. Cameras
2. Lenses
3. Camera Housings and Mounts
4. Wiring and Cables
G. The Contractor shall visit the site and verify that site conditions are in agreement/compliance with the design package. The Contractor shall report all changes to the site or conditions that will affect performance of the system to the Contracting Officer in the form of a report. The Contractor shall not take any corrective action without written permission received from the Contracting Officer.
H. Existing Equipment
1. The Contractor shall connect to and utilize existing video equipment, video and control signal transmission lines, and devices as outlined in the design package. Video equipment and signal lines that are usable in their original configuration without modification may be reused with Contracting Officer approval.
2. The Contractor shall perform a field survey, including testing and inspection of all existing video equipment and signal lines intended to be incorporated into the VASS System, and furnish a report to the
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 20
Contracting Officer as part of the site survey report. For those items considered nonfunctioning, provide (with the report) specification sheets, or written functional requirements to support the findings and the estimated cost to correct the deficiency. As part of the report, the Contractor shall include a schedule for connection to all existing equipment.
3. The Contractor shall make written requests and obtain approval prior to disconnecting any signal lines and equipment, and creating equipment downtime. Such work shall proceed only after receiving
Contracting Officer approval of these requests. If any device fails after the Contractor has commenced work on that device, signal or control line, the Contractor shall diagnose the failure and perform any necessary corrections to the equipment.
4. The Contractor shall be held responsible for repair costs due to
Contractor negligence, abuse, or incorrect installation of equipment.
5. The Contracting Officer shall be provided a full list of all equipment that is to be removed or replaced by the Contractor, to include description and serial/manufacturer numbers where possible.
The Contractor shall dispose of all equipment that has been removed or replaced based upon approval of the Contracting Officer after reviewing the equipment removal list. In all areas where equipment is removed or replaced the Contractor shall repair those areas to match the current existing conditions.
I. Enclosure Penetrations: All enclosure penetrations shall be from the bottom of the enclosure unless the system design requires penetrations from other directions. Penetrations of interior enclosures involving transitions of conduit from interior to exterior, and all penetrations on exterior enclosures shall be sealed with rubber silicone sealant to preclude the entry of water and will comply with VA Master
Specification 07 84 00, Firestopping. The conduit riser shall terminate in a hot-dipped galvanized metal cable terminator. The terminator shall be filled with an approved sealant as recommended by the cable manufacturer and in such a manner that the cable is not damaged.
J. Cold Galvanizing: All field welds and brazing on factory galvanized boxes, enclosures, and conduits shall be coated with a cold galvanized paint containing at least 95 percent zinc by weight.
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 21
K. Cameras:
1. Install the cameras with the focal length lens as indicated for each zone.
2. Connect power and signal lines to the camera.
3. Aim camera to give field of view as needed to cover the alarm zone.
4. Focus the lens to give a sharp picture (to include checking for day and night focus and image quality) over the entire field of view
5. Synchronize all cameras so the picture does not roll on the monitor when cameras are selected.
L. Camera Housings, Mounts, and Poles:
1. Install the camera housings and mounts as specified by the manufacturer and as shown, provide mounting hardware sized appropriately to secure each camera.
2. Provide electrical and signal transmission cabling to the mount location via a hardened carrier system from the Physical Access
Control System and Database Management to the device.
3. Connect signal lines and AC power to the housing interfaces.
3.3 SYSTEM START-UP
A. The Contractor shall not apply power to the VASS System until the following items have been completed:
1. VASS System equipment items and have been set up in accordance with manufacturer's instructions.
2. A visual inspection of the VASS System has been conducted to ensure that defective equipment items have not been installed and that there are no loose connections.
3. System wiring has been tested and verified as correctly connected as indicated.
4. All system grounding and transient protection systems have been verified as installed and connected as indicated.
5. Power supplies to be connected to the VASS System have been verified as the correct voltage, phasing, and frequency as indicated.
B. Satisfaction of the above requirements shall not relieve the Contractor of responsibility for incorrect installation, defective equipment items, or collateral damage as a result of Contractor work efforts.
Richmond, Virginia
VA Project #652-17-104
28 23 00 - 22
3.4 SUPLEMENTAL CONTRACTOR QUIALITY CONTROL
A. The Contractor shall provide the services of technical representatives who are familiar with all components and installation procedures of the installed VASS System; and are approved by the Contracting Officer.
B. The Contractor will be present on the job site during the preparatory and initial phases of quality control to provide technical assistance.
C. The Contractor shall also be available on an as needed basis to provide assistance with follow-up phases of quality control.
D. The Contractor shall participate in the testing and validation of the system and shall provide certification that the system installed is fully operational as all construction document requirements have been fulfilled.
- - - E N D - - -
| SECTION 28 23 00 VIDEO SURVEILLANCE |
| 1.2 RELATED WORK |
| 1.3 DEFINITIONS |
| 1.4 QUALITY ASSURANCE |
| 1.5 SUBMITTALS |
| 1.6 APPLICABLE PUBLICATIONS |
| 1.7 COORDINATION |
| 1.8 WARRANTY OF CONSTRUCTION |
| PART 2 - PRODUCTS |
| 2.2 CAMERAS |
| 2.3 VIDEO CAMERAS |
| 2.4 AUTOMATIC COLOR DOME CAMERA - ANALOG |
| 2.5 POWER SUPPLIES |
| 2.6 WIRES AND CABLES |
| PART 3 - EXECUTION |
| 3.2 INSTALLATION |
| 3.3 SYSTEM START-UP |
| 3.4 SUPLEMENTAL CONTRACTOR QUIALITY CONTROL |