36C24619B0021-009.pdf

PDF 24 MB Posted

Attached to
LINAC Vaults 1 & 2 Modifications FY19 (VA-19-00023131) Project 652-16-107
Solicitation number
36C24619B0021
Issued by

About this file

36C24619B0021 S02 4 DWGS-Electrical.pdf

View the file

Other files

File Type Posted
36C24619B0021-0005000.docx DOCX document
36C24619B0021-0004006.pdf PDF
36C24619B0021-0004003.pdf PDF
36C24619B0021-0004004.pdf PDF
36C24619B0021-0004001.pdf PDF
36C24619B0021-0004007.pdf PDF
36C24619B0021-0004005.pdf PDF
36C24619B0021-0004000.docx DOCX document
36C24619B0021-0004002.pdf PDF
36C24619B0021-0003000.docx DOCX document
36C24619B0021-0002002.pdf PDF
36C24619B0021-0002001.pdf PDF
36C24619B0021-0002000.docx DOCX document
36C24619B0021-0001002.pdf PDF
36C24619B0021-0001005.pdf PDF
36C24619B0021-0001000.docx DOCX document
36C24619B0021-0001006.pdf PDF
36C24619B0021-0001007.pdf PDF
36C24619B0021-0001004.pdf PDF
36C24619B0021-0001001.pdf PDF
36C24619B0021-0001003.pdf PDF
36C24619B0021-0001009.pdf PDF
36C24619B0021-0001008.pdf PDF
36C24619B0021-002.docx DOCX document
36C24619B0021-007.pdf PDF
36C24619B0021-004.pdf PDF
36C24619B0021-011.pdf PDF
36C24619B0021-001.docx DOCX document
36C24619B0021-003.pdf PDF
36C24619B0021-010.pdf PDF
36C24619B0021-008.pdf PDF
36C24619B0021-005.pdf PDF
36C24619B0021-006.pdf PDF
36C24619B0021-000.docx DOCX document
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LINAC VAULTS 1 & 2

MODIFICATIONS

652-16-107

NO. DESCRIPTION DATE

BLDG. 500

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0014

B

A

C

D

E

F

ELECTRICAL

ABBREVIATIONS & SYMBOLS

E-001

MJRMJR

652-16-107

NO. DESCRIPTION DATE

BLDG. 500

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0014

B

A

C

D

E

F

ELECTRICAL

NOTES

E-002

E.J.

COVER

PLATE

BLK

W

V

U

T

S

R

LINAC VAULTS 1 & 2

MODIFICATIONS

652-16-107

NO. DESCRIPTION DATE

BLDG. 500

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

ACTUAL & PLAN

NORTH

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0014

B

A

C

D

E

F

KEYPLAN

NTS

AREA OF WORK

ELECTRICAL

DEMOLITION PLAN

LEVEL 1

ED111

U

T

24 25 25A 24 25 25A

V

24 25

1Z-133

1Z-134

1Z-132

1Z-135

1Z-133A

1Z-133

1Z-134

1Z-132

1Z-135

1Z-133A

W

V

LINAC VAULTS 1 & 2

MODIFICATIONS

652-16-107

NO. DESCRIPTION DATE

BLDG. 500

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

ACTUAL & PLAN

NORTH

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0014

B

A

C

D

E

F

KEYPLAN

NTS

AREA OF WORK

ELECTRICAL

POWER, SYSTEMS, & LIGHTING PLANS

LEVEL 1 & ROOF

E-111

652-16-107

NO. DESCRIPTION DATE

BLDG. 500

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

ACTUAL & PLAN

NORTH

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0014

B

A

C

D

E

F

KEYPLAN

NTS

AREA OF WORK

ELECTRICAL

CONDUIT ROUTING PLAN

E-401

Computer Cabinet

E x a c T ra c

B e a m

O n

C u s to m e r w a rn in g l ig h ts

X

-R a y G e n e ra to r e n e rg iz e d from emergency-off circuit door interlock

F 50A/50Hz indolent

Fi

0.03A

F 16A/50Hz

Fi

0.03A

Overvoltage protection Typ 2 / Class II

TN Star Network

24V DC 24V DC

230V AC

C u s to m e r w a rn in g l ig h ts

E x a c T ra c X

-R a y in u s e w ir e c ro s s s e c ti o n m a x m m

² w ir e c ro s s s e c ti o n

,5 m a x m m ²

OnOff OnOff

230V AC

L, N & G

400V AC

L1, L2, L3, N & G

F le x ib le c a b le

F le x ib le c a b le w ir e c ro s s s e c ti o n m m ² w ir e c ro s s s e c ti o n m m ²

X-Ray Generator

Customer supplied including cabling to connection point at Computer- and Generator cabinet x-ray plus 3 m

230V AC

E x a c T ra c

X -R a y i n u s e

24V DC

w ir e c ro s s s e c ti o n m m ²

12V DC

(*) The power shut down is not an ExacTrac installation requirement.

Please check if your local regulations require it.

(**) ExacTrac can also provide a 12 Volts DC signal.

Option to use the bunker warning lights instead of the ones provided with ExacTrac.

(***) Option to connect the X-Ray generators to the bunker warning lights.

(****) Optional Beam On signal. The minimum signal time can be adjusted.

1.0 2.0a

Door interlock

24V DC

Computer Cabinet

LINAC

Distribution Box

LINAC

Door interlock

24V DC

24V DC

12V DC

1.0

E x a c T ra c

X -R a y G e n e ra to r e n e rg iz e d

24V DC

230V AC

w ir e c ro s s s e c ti o n m m ²

Customer warning lights.

Beam On

Generator Cabinet

Computer

Cabinet m m ²

Floor Box 1Floor Box 2

,5 m m

²

Grounding reference bar.

Maximum at 3 meters from Computer Cabinet.

LINAC

Bunker Grounding reference bar.

Door Interlock

OnOff OnOff

L

N

G m in

,5 m m

² m a x m m ²

L

L

L

N

G m a x m m ²

Customer supplied incl. cabling to connection point at Computer- and Generator Cabinet X-ray plus 3 m

Bunker Warning

Lights m m ² m m ²

In-Room Power Distribution Box

Control Room Power Distribution Box

L N

G

,5 m m ²

L N

G

,5 m m ²

F le x ib le

F le x ib le

12volts m m ²

Bunker Warning

Lights

12volts

,5 m m

² m m ² m m ² m m ²

M u lt ip le x

X m m

²

M u lt ip le x

X m m

²

1.3 2.1a 2.1b

1.0

2.0a

1.5

Generator Cabinet

2.0b m m ² m m ²

G ro u n d in g r e fe re n c e b a r in s id e t h e r o o m w h e re th e

E T

C o m u te r

C a b in e t

(1 .0 is lo c a te d

A c c e s s ib e l fo r s e rv ic e

ExacTrac X-Ray in use

ExacTrac Beam On

ExacTrac X-Ray

Generator energized m m ²

Bunker Warning

Lights

12volts

M u lt ip le x

X m m

²

3.2

In-Room

Distribution Box

External

Bluetooth Module

Stand & Gantry

0.0

1.3

L

LL

A 3" C.

G2 2" C.

J 3/4" C.

T 2" C.

M (2) 3" C.

O 1" C.

R 2" C.

I 1" c.

(optional)

H2 1" C.

P 1" C.

B1 3" C.

Control Room

Distribution Box

1.5

G1 2" C.

(optional)

2.4ExacTrac Console

Control-Room Workspace 1.6

H1 2" C.

D2 3" C.

E 2" C.

K 1" C.

M (2) 3" C.

Floorbox with x-ray Tube 2

2.2a 2.2b

1.0 Computer Cabinet

U 1" C.

Hospital

Network 4.0

Grounding

Spot

X-Ray

Dual Generator

2.0a 2.0b

2.3b 2.3a

1.2 1.2

1.1

2.5a

2.5bX-ray Warning Light

Warning Light

Flat panel

Detector

IR and Video

Camera System

Water Cooling System

ExacTrac Dynamic

X 4" C.

Power Plug

(for Robotics

Charger)

Emergency Off

(typ. of 3)

Flat panel

Detector

Laser (typ of 3)

Floorbox with x-ray Tube 2

Wall Mounted Monitor

Ceiling

Mounted

Monitor

O 1" C.

B2 3" C.

C 2" C.

S 3" C.

D1 3" C.

X-Ray

System Barrier

Control Room

Treatment Room m e te rs m e te rs m e te rs m e te rs m e te rs

20 meters m e te rs m e te rs m e te rs m e te rs m e te rs m e te rs m e te rs

3 meters m e te rs

(2)

(3)

(1) 30cm cable used at this point.

(2) 1m cable used at this point.

(3) 2m cable used at this point.

(2) (2)

(1)

(1)

(1)

(1)

(1) (1)

(2) (2)

(3)

(3) (3)

(1)

(3) m e te rs

External

Bluetooth

Module

LINAC

(3) m e te rs m e te rs

3.2

2.0b

2.2a 2.2b

Network Plug

(provided by

Hospital)

1.2 2.3b

0.1

1.2

1.5

2.5a

2.4

1.0

0.0

1.3

Control-Room

Workplace

O R B2H1 C T

G1

JG2

M

A

E

D2

2.0a

2.5b

2.1b2.1a

2.3a

4.0

1.6

H2 optional

D1

B1

1.1

U

Treatment

Room

W a te r C o o li n g S y s te m

E x a c

T ra c D y n a m ic

X

S

LINAC VAULTS 1 & 2

MODIFICATIONS

652-16-107

NO. DESCRIPTION DATE

BLDG. 500

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0014

B

A

C

D

E

F

ELECTRICAL

DETAILS

E-501

652-16-107

NO. DESCRIPTION DATE

BLDG. 500

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0014

B

A

C

D

E

F

ELECTRICAL

DETAILS

E-502

652-16-107

NO. DESCRIPTION DATE

BLDG. 500

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0014

B

A

C

D

E

F

ELECTRICAL

PANEL SCHEDULES

& SINGLE LINE DIAGRAMS

E-701

File details come from the government source that posted it.