DEMOLITION REMARKS
1. DASHED LINES INDICATE EXTENT OF DEMOLITION WORK.
2. REMOVE CONCRETE SLAB COMPLETELY.
17 1617
PHASE 1PHASE 2
PHASE 1PHASE 2
IREMOVE PASE 1 ICRA BARRIER
UPON ERECTING PHASE 2 ICRA BARRIER.
6 6
23 24 25 25A
T
U
± 77' - 9"
PHASE 1PHASE 2
PHASE 1PHASE 2
± 44' - 2 1/2" ± 33' - 6 1/2"
1Z-133 1Z-134
1Z-133A
1Z-132
1Z-135
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
www.pfa-architect.com - Project No: 2412.17B
ARCHITECTURE, PLANNING, INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510
Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
BID DOCUMENTS
ACTUAL & PLAN
NORTH
NTS
LINAC VAULTS 1 & 2
MODIFICATIONS
HUNTER HOLMES MCGUIRE
VAMC RICHMOND, VA
652-16-107
BLDG. 500
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
/1
/2
:4 :5
P
M M a c \H o m e \D o c u m e n ts
\L o c a l R e v it F ile s \2
B
L
IN
A C
V a u lt s
M o d if ic a ti o n s
C e n tr a l_ d p e ro n n e t.
rv t
AD101
DEMOLITION PLANS
JCHDJP5-13-2019
5-13-2019
1/4" = 1'-0"
DEMOLITION PLAN - FIRST LEVEL
1 DEMOLISH CONCRETE SLAB, SEE STRUCTURAL DRAWINGS FOR EXTENT OF DEMOLITION.
2 NOT USED
3 REMOVE AND RETAIN EXISTING CASEWORK FOR REUSE.
4 REMOVE TURNTABLE AND FRAME COMPONENTS COMPLETE.
5 REMOVE AND DISCARD DECORATIVE LIGHT FIXTURE.
6 COORDINATE REMOVAL AND RELOCATION OF ALL REUSED POSITIONING EQUIPMENT WITH COR AND INDEPENDENT CONTRACTOR.
7 REMOVE ALL CEILING MOUNTED EQUIPMENT AND STRUCTURAL SUPPORT. TURN EQUIPMENT OVER TO COR.
8 REMOVE AND DISCARD EXISTING ROOF SYSTEM TO EXTENTS NOTED. COORDINATE AREAS OF PHASED REMOVAL WITH NEW WORK.
MAINTAIN WATERTIGHT / WATER RESISTANT TEMPORARY ROOF WHERE REQUIRED BETWEEN PHASES.
9 REMOVE AND DISCARD EXISTING GRAVEL STOP TO MATCH LENGTH OF ROOF REMOVED.
10 REMOVE FENCE SYSTEM AND TURN OVER MATERIAL TO COR. COORDINATE REQUIRED TEMPORARY FENCING TO REMAIN DURING
CONSTRUCTION WITH PHASING AND COR.
11 REMOVE EXISTING TOILET ACCESSORIES AND SALVAGE FOR REUSE.
12 REMOVE EXISTING WALL AS ILLUSTRATED.
13 REMOVE DOOR, FRAME, AND HARDWARE. TURN OVER TO COR.
14 REMOVE CASEWORK IN IT'S ENTIRETY INCLUDING BUT NOT LIMITED TO: BASE CABINETS, WALL CABINETS, BRACING, AND HARDWARE.
15 REMOVE PLUMBING FIXTURE. SEE PLUMBING DRAWINGS.
16 ICRA TEMPORARY FULL HEIGHT 1 HR PARTITION. DEMOLISH AFTER THE COMPLETION OF NEW WORK OR END OF PHASE. ERECT ICRA
BARRIER UPON COMPLETION OF PILE INTALLATION AND BEFORE PHASE 1 BEGINS
17 PROVIDE TEMPORARY 1/3 HOUR RATED DOOR, FRAME, AND HARDWARE. PROVIDE HINGES, CLOSER, AND CLASSROOM LOCKSET, AUTOMATIC DOOR BOTTOMS AND RUBBER SEALS.
18 REMOVE SHELVING UNITS COMPLETELY, THIS ROOM.
19 REMOVE OPERATOR / ACTIVATOR FROM VAULT DOOR AND DISCARD. FRAME TO REMAIN IN PLACE.
1/8" = 1'-0"
PARTIAL DEMOLITION PLAN - ROOF LEVEL
DEMOLITION SCHEDULE
*** ALL FINISHES LISTED IN SCHEDULE ARE TO BE REMOVED
COMPLETELY UNLESS OTHERWISE NOTED ***
NUMBER FLOOR BASE WALL CEILING REMARKS
1Z-132 ETR ETR ETR ETR -
1Z-133 LVT RB PTD GWB ACT 1
1Z-133A LVT RB PTD GWB ACT -
1Z-134 LVT RB PTD GWB ACT 1, 2
1Z-135 ETR ETR ETR ETR -
• DEMOLITION DRAWINGS INDICATE IN GENERAL, THE EXTENT OF DEMOLITION. REMOVE ALL ASSOCIATED APPURTENANCES NOT REQUIRED IN THE NEW WORK, ALL ABANDONED ITEMS, AND ALL ITEMS REQUIRED FOR THE INSTALLATION OF NEW WORK, TO PROVIDE FOR A COMPLETE PROJECT. ITEMS NOT SPECIFICALLY INDICATED THAT ARE QUESTIONABLE FOR REMOVAL SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT FOR A DECISION.
• THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION.
• THE CONTRACTOR SHALL PATCH ALL EXISTING SURFACES TO MATCH EXISTING WHERE AFFECTED BY CONSTRUCTION OPERATIONS, INCLUDING BUT NOT LIMITED TO PLUMBING, MECHANICAL AND ELECTRICAL WORK.
• THE CONTRACTOR SHALL PATCH NAIL HOLES, ETC, AND REMOVE MISCELLANEOUS APPURTENANCES ON EXISTING WALLS TO BE PAINTED
OR COVERED WITH WALL COVERING.
• ALL EXISTING FLOORING MATERIALS WHICH ARE TO REMAIN IN PLACE SHALL BE COMPLETELY CLEANED AND STRIPPED OF WAX IN ORDER
TO RECEIVE NEW FINISHES.
• ALL NEW WORK SHALL ALIGN WITH EXISTING WHERE THEY INTERSECT UNLESS OTHERWISE NOTED.
• THE CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING SURFACES WHICH WERE PREVIOUSLY DAMAGED PRIOR TO CONSTRUCTION OPERATIONS IF VISIBLE AFTER NEW WORK IS COMPLETE, REGARDLESS IF THE ITEM WAS SPECIFICALLY NOTED OR NOT.
• THE CONTRACTOR SHALL REMOVE AND PATCH ANY AREAS UNCOVERED WHERE WOOD NAILERS OR GROUNDS ARE FOUND TO EXIST BEHIND ANY TRIM ITEMS OR EQUIPMENT REMOVED. WALLS SHALL BE MADE FLUSH WITH EXISTING ADJACENT SURFACES AND READY TO
RECEIVE NEW FINISHES.
• IF ANY ASBESTOS CONTAINING MATERIAL IS ENCOUNTERED DURING THE COURSE OF CONSTRUCTION OPERATIONS WHICH IS NOT INDICATED ON THE CONTRACT DOCUMENTS THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY.
• WHERE EXISTING VINYL WALL COVERING IS REMOVED ON EXISTING WALLS TO REMAIN, THE CONTRACTOR SHALL PATCH AND REPAIR WALL AS REQUIRED TO PROVIDE A LEVEL AND TRUE SURFACES ON WHICH TO INSTALL NEW FINISHES.
• ALL SIGNAGE WHICH OCCURS ON WALL OR ON DOORS TO BE REMOVED SHALL BE REMOVED BY THE CONTRACTOR AND TURNED OVER TO
THE OWNER.
• ALL FINISHES LISTED IN THE DEMOLITION SCHEDULE SHALL BE REMOVED COMPLETELY UNLESS INDICATED OTHERWISE. DEMOLITION SHALL INCLUDE BACKINGS, MASTIC AND GLUES, SETTING BEDS, AND SUBSTRATE AS REQUIRED TO PREPARE THE MATERIAL FOR NEW
WORK AND/OR FINISHES.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE NOTED.
• EXISTING HAND RAIL AND BUMPER GUARD SHALL BE REMOVED AND TURNED OVER TO THE OWNER.
• ALL EXISTING NURSE CALL, SMOKE DETECTORS, AND SPEAKERS TO REMAIN AND REWORKED WITH NEW CEILING SYSTEM.
• EXISTING WALL FINISHES TO BE VERIFIED AND PREPPED ACCORDINGLY FOR NEW FINISHES SCHEDULES - BY CONTRACTOR.
• THESE DEMOLITION NOTES ARE FOR ARCHITECTURAL WORK ONLY. SEE ALL OTHER DRAWINGS FOR DEMOLITION INFORMATION
PERTAINING TO OTHER DISCIPLINES.
• FOR ICRA RESTRICTIONS AND INFORMATION SEE SHEET AG001.
GENERAL DEMOLITION NOTES
DEMOLITION NOTES
1/8" = 1'-0"
DEMOLITION - REFLECTED CEILING PLAN
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
Addendum 11 6/19/19
AE401
1Z-133
1Z-134
1Z-132
1Z-135
M3B
1Z-133A
9' - 6" 12' - 0"
5 6
M3B
M3B M3B
M1B
M3B
PHASE 1PHASE 2
PHASE 1PHASE 2
/8
2' - 0 7/8"
1' - 7 5/8"
M1B
M1B
/8
/4
/8
/2
M1B
AE300
AE300
1Z-133
1Z-134
1Z-132
1Z-135
2' - 1" 7' - 0 3/4" 9' - 9 1/2" 2' - 1"
19' - 8"
/4
/8
/8
C L O
F L
IN
A
C
E Q
' - 0
E
Q
EQ
16' - 0"
EQ
1Z-133A
+ 9' - 6"
+ 10' - 2"
PHASE 1PHASE 2
PHASE 1PHASE 2
TYP.
+ 9' - 6"
+ 9' - 8"
AE112
TYP.
EQ EQ
E Q
E Q
E Q
E Q
E Q
5' - 0" 1' - 8"
EQ EQ
EQ EQ
E Q
E Q
2' - 0" EQ EQ EQ EQ 2' - 0"
/8
/8
EQ EQ
2 X 2 INDIRECT
LED LIGHT FIXTURE
CEILING LEGEND
RETURN AIR DIFFUSER
SUPPLY AIR DIFFUSER
RECESSED CEILING LIGHT
EXIT SIGN
LOUVERED SUPPLY DIFFUSER
STRUCTURAL SUPPORT
FOR CEILING EQUIPMENT
COORDINATE AND CONFIRM ALL FIXED EQUIPMENT AND DEVICE LOCATIONS WITH MANUFACTURER
INSTALLATION DOCUMENTS. INSTALL MOUNTING HARDWARE FOR WALL MOUNTED DEVICES AS
DIRECTED BY MANUFACTURER.
CONTRACTOR'S NOTE
FOR DIMENSION
SEE RCP
3 5/8" METAL STUDS FASTENED
TO STRUCTURE ABOVE, TYP
CEILING AS SCHEDULED
5/8" PTD GWB, TYP
T Y
P
T Y
P
FOR DIMENSION
SEE RCP
CEILING AS SCHEDULED
5/8" PTD
GWB, TYP
3 5/8" MTL STUDS,
FASTENED TO
STRUCTURE ABOVE,
TYP
SEE WALL TYPE
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
www.pfa-architect.com - Project No: 2412.17B
ARCHITECTURE, PLANNING, INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510
Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
BID DOCUMENTS
ACTUAL & PLAN
NORTH
NTS
LINAC VAULTS 1 & 2
MODIFICATIONS
HUNTER HOLMES MCGUIRE
VAMC RICHMOND, VA
652-16-107
BLDG. 500
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
/1
/2
:4 :5
P
M M a c \H o m e \D o c u m e n ts
\L o c a l R e v it F ile s \2
B
L
IN
A C
V a u lt s
M o d if ic a ti o n s
C e n tr a l_ d p e ro n n e t.
rv t
AE112
NEW WORK PLANS
JCHDJP5-13-2019
5-13-2019
ROOM LEGEND
NUMBER NAME Comments
1Z-132 CONTROL SEE MEP DRAWINGS FOR WORK IN THIS AREA
1Z-133 VAULT 1 -
1Z-133A EQUIPMENT CLOSET -
1Z-134 VAULT 2 -
1Z-135 CONTROL SEE MEP DRAWINGS FOR WORK IN THIS AREA
1/4" = 1'-0"
NEW WORK PLAN - FIRST LEVEL
1/4" = 1'-0"
REFLECTED CEILING PLAN - FIRST LEVEL
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A RESOLUTION. ADJUSTMENTS TO DIMENSIONS AND CONDITIONS
SHOWN MAY BE REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT NEW CONSTRUCTION UNLESS OTHERWISE NOTED. DIMENSIONS ARE
REFERENCED FROM FACE OF FINISH AT EXISTING CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST BE FIELD VERIFIED PRIOR TO THE START OF CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE
READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES WHICH WILL REMAIN EXPOSED, ALIGN NEW WORK FLUSH WITH EXISTING
ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN A WATER TIGHT CONDITION THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY CONSTRUCTION OPERATIONS. TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE BUILDING
AND ITS OCCUPANTS DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE CONSTRUCTION AREA. BARRIERS SHALL NOT INTERFERE WITH THE
OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO PREVENT THE SPREAD OF DUST TO OCCUPIED
AREAS OF THE BUILDING.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS ONLY UNLESS OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
WALL TYPE SCHEDULE
TYPE STC DESCRIPTION
FIRE
RATING UL REMARKS
C 12 N/A 12" CONCRETE TO 17' - 9" AFF. SEAL CONCRETE FACES EXPOSED TO
EXTERIOR.
N/A N/A COORDINATE WITH
STRUCTURAL DRAWINGS
M1B N/A 1 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL
ASSEMBLY TO 4" ABOVE FINISHED CEILING.
N/A N/A
M3 N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND
WALL ASSEMBLY TO 4" ABOVE FINISHED CEILING.
N/A N/A
M3B N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL
ASSEMBLY TO 4" ABOVE FINISHED CEILING.
N/A N/A
GENERAL NOTES
1 ISOCENTER
2 SKY FACTORY REVELATION SKYCEILINGS W/ IMAGE #8FE. MODIFY IMAGE AS NECESSARY TO FIT SIZE. SEE FINISH PLAN SHEET.
3 SEE STRUCTURAL DRAWINGS FOR NEW CONCRETE LOCATIONS.
4 INFILL FORMER EQUIPMENT RECESS TO MATCH EXISTING SLAB. SEE STRUCTURAL DRAWINGS.
5 COOLING WATER SUPPLY AND RETURN CONTROL VALVES. SEE PLUMBING DRAWINGS.
6 RELAY JUNCTION BOX BY "VARIAN"
7 EXACTRAC COMPUTER CABINET BY "BRAINLAB".
8 PROVIDE 2x4 ACT TILE (ACT#2) IN THIS LOCATION ONLY.
9 COORDINATE CONCRETE SLAB VOIDS WITH EQUIPMENT INSTALLATION DOCUMENTS. SEE STRUCTURAL DRAWINGS FOR DIMENSIONS.
10 NEW CONCRETE SLAB, ENTIRE ROOM. SEE STRUCTURAL DRAWINGS.
11 PROVIDE NEW SINGLE BOWL SCRUB SINK WITH FOOT PEDAL CONTROLS. SEE PLUMBING DRAWINGS.
12 PROVIDE NEW DOOR, DOOR CONTROLLER, AND HARDWARE. COORDINATE SECURITY REQUIREMENTS WITH COR.
13 PAINT GWB CEILING PNT#4. SEE FINISH COLORS FOR MORE INFORMATION.
14 STRUCTURAL SUPPORT FOR CEILING MOUNTED EQUIPMENT. COORDINATE LOCATION WITH STRUCTURAL, EQUIPMENT MANUFACTURER
INSTALLATION INSTRUCTIONS, AND COR.
15 WORK COUNTER BY OTHERS
NEW WORK NOTES
1 1/2" = 1'-0"
3 SOFFIT DETAIL - CEILING TO CEILING
AE112 1 1/2" = 1'-0"
4 SOFFIT DETAIL - CEILING TO WALL
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
Addendum 11 6/19/19
AE401
1Z-133
1Z-134
1Z-132
1Z-135
1Z-133A
9' - 6" 12' - 0"
8 9
PT
SD
HSD
PHASE 1PHASE 2
PHASE 1PHASE 2
AE300
AE300
1Z-133
1Z-134
1Z-132
1Z-135
2' - 1" 7' - 0 3/4" 9' - 9 1/2" 2' - 1"
/4
/8
/8
C L O
F L
IN
A
C
E Q
' - 0
E
Q
EQ
16' - 0"
EQ
1Z-133A
+ 9' - 6"
14 14
PHASE 1PHASE 2
PHASE 1PHASE 2
+ 10' - 2"
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
www.pfa-architect.com - Project No: 2412.17B
ARCHITECTURE, PLANNING, INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510
Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
BID DOCUMENTS
ACTUAL & PLAN
NORTH
NTS
LINAC VAULTS 1 & 2
MODIFICATIONS
HUNTER HOLMES MCGUIRE
VAMC RICHMOND, VA
652-16-107
BLDG. 500
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
/1
/2
:4 :0
P
M M a c \H o m e \D o c u m e n ts
\L o c a l R e v it F ile s \2
B
L
IN
A C
V a u lt s
M o d if ic a ti o n s
C e n tr a l_ d p e ro n n e t.
rv t
AE113
EQUIPMENT PLANS
JCHDJP5-13-2019
5-13-2019
TOILET ACCESSORY SCHEDULE
MARK DESCRIPTION MOUNTING HEIGHT OFCI OFOI CFCI REMARKS Comments
HSD HAND SANITIZING DISPENSER 48" A.F.F. TO BOTTOM OF CONTROLS *** SALVAGED FROM EXISTING
SD VERTICAL MOUNT SOAP DISPENSER 48" TO BOTTOM OF CONTROLS *** SALVAGED FROM EXISTING
PT AUTOMATIC PAPER TOWEL DISPENSER 48" A.F.F. TO BOTTOM OF OPENING *** SALVAGED FROM EXISTING
ROOM LEGEND
NUMBER NAME Comments
1Z-132 CONTROL SEE MEP DRAWINGS FOR WORK IN THIS AREA
1Z-133 VAULT 1 -
1Z-133A EQUIPMENT CLOSET -
1Z-134 VAULT 2 -
1Z-135 CONTROL SEE MEP DRAWINGS FOR WORK IN THIS AREA
1/4" = 1'-0"
EQUIPMENT PLAN - FIRST LEVEL
1/4" = 1'-0"
EQUIPMENT PLAN - REFLECTED CEILING PLAN - FIRST LEVEL
1 ISOCENTER
2 SKY FACTORY REVELATION SKYCEILINGS W/ IMAGE #8FE. MODIFY IMAGE AS NECESSARY TO FIT SIZE. SEE 3 / AE112
3 NOT USED.
4 EQUIPMENT BY OTHERS. COORDINATE WITH COR.
5 INFILL FORMER EQUIPMENT RECESS TO MATCH EXISTING SLAB. SEE STRUCTURAL DRAWINGS.
7 X-RAY FLOOR BOX BY "BRAINLAB"
8 COOLING WATER SUPPLY AND RETURN CONTROL VALVES. SEE PLUMBING DRAWINGS.
9 RELAY JUNCTION BOX BY "VARIAN"
10 DUAL X-RAY GENERATOR CABINETS BY "BRAINLAB"
11 EXACTRAC COMPUTER CABINET BY "BRAINLAB".
12 CONTROL STATION FOR "VARIAN" AND "BRAINLAB" EQUIPMENT.
13 "TRUEBEAM 2-1 CABINET" BY "VARIAN".
14 PROVIDE 2x4 ACT TILE (ACT#2) IN THIS LOCATION TO ACCOMMODATE VARIAN EQUIPMENT.
15 COORDINATE CONCRETE SLAB VOIDS WITH EQUIPMENT. SEE STRUCTURAL DRAWINGS.
16 NEW CONCRETE SLAB, ENTIRE ROOM. SEE STRUCTURAL DRAWINGS.
17 PROVIDE NEW SINGLE BOWL SCRUB SINK WITH FOOT PEDAL CONTROLS. SEE PLUMBING DRAWINGS.
18 VA FURNISHED, CONTRACTOR INSTALLED DOUBLE DIAGNOSTIC LIGHT. CELING MOUNTED. SEE STRUCTURAL DRAWINGS.
19 PAINT GWB CEILING PNT#4. SEE FINISH COLORS FOR MORE INFORMATION.
20 MANUFACTURED STAINLESS STEEL CASEWORK. VAMC FURNISHED CONTRACTOR INSTALLED.
GENERAL NOTES
EQUIPMENT NOTES
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A RESOLUTION. ADJUSTMENTS TO DIMENSIONS AND CONDITIONS
SHOWN MAY BE REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT NEW CONSTRUCTION UNLESS OTHERWISE NOTED. DIMENSIONS ARE
REFERENCED FROM FACE OF FINISH AT EXISTING CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST BE FIELD VERIFIED PRIOR TO THE START OF CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE
READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES WHICH WILL REMAIN EXPOSED, ALIGN NEW WORK FLUSH WITH EXISTING
ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN A WATER TIGHT CONDITION THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY CONSTRUCTION OPERATIONS. TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE BUILDING
AND ITS OCCUPANTS DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE CONSTRUCTION AREA. BARRIERS SHALL NOT INTERFERE WITH THE
OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO PREVENT THE SPREAD OF DUST TO OCCUPIED
AREAS OF THE BUILDING.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS ONLY UNLESS OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
1 3/15/19Addendum 11 6/19/19
AE300
AE300
TYP.
AE300
16' - 10" 29' - 4 1/16" ± 25' - 4 1/4"
/4
80' - 9 11/16"
57' - 11 5/8"
LEVEL 1 - INT
10' - 2 1/2"
23242525A
CONCRETE SHIELDING BEYOND
PROVIDE NEW GRAVEL STOP TO MATCH EXISITING
NEW CONCRETE
WALL. PAINT TO
MATCH EXISTING
BRICK.
PVC ROOF MEMBRANE
AE300
17' - 9"T.O. DECK
R-15 RIGID INSULATION
PVC ROOF MEMBRANE
PVC ROOF FLASHING
8" MIN LEG VERTICAL AND HORIZONTAL
TAPERED
INSULATION R-15
MIN.
LEVEL 1 - INT
10' - 2 1/2"
TOS
17' - 7 1/2"
AE300
PHASE 1PHASE 2
PHASE 1PHASE 2
NEW PVC ROOF
ON TAPERED INSULATION
AE300
,OH
NEW CONCRETE SLAB
EQUIPMENT SUPPORTS, TYP.
SEE STRUCTURAL DRAWINGS
NEW PVC ROOF
ON TAPERED INSULATION
PRECAST CONCRETE PLANKS.
SEE STRUCTURAL DRAWINGS.
NEW PVC ROOF
ON TAPERED INSULATION
1/4" / 1'-0"
AE300
SIM
BASE SHEET AS REQUIRED
FOR DESIRED WARRANTY
INTERPLY SHEET
CANT STRIP
TAPERED INSULATION
EXISTING METAL DECK
R-15 RIGID INSULATION
CONTINUE PVC MEMBRANE
DOWN SIDES OF CONCRETE
ADDITION
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
www.pfa-architect.com - Project No: 2412.17B
ARCHITECTURE, PLANNING, INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510
Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
NO. DESCRIPTION DATE
BID DOCUMENTS
LINAC VAULTS 1 & 2
MODIFICATIONS
HUNTER HOLMES MCGUIRE
VAMC RICHMOND, VA
652-16-107
BLDG. 500
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
/1
/2
:4 :0
P
M M a c \H o m e \D o c u m e n ts
\L o c a l R e v it F ile s \2
B
L
IN
A C
V a u lt s
M o d if ic a ti o n s
C e n tr a l_ d p e ro n n e t.
rv t
AE300
ROOF PLAN, BUILDING AND WALL
SECTIONS
JCHDJP5-13-2019
5-13-2019
1/8" = 1'-0"
PARTIAL ROOF PLAN - NEW WORK
1 EDGE OF CONCRETE PLANKS
2 PVC ROOF MEMBRANE ON TAPERED INSULATION.
3 PROVIDE NEW GRAVEL STOP AT EDGE OF ROOF.
4 EXTENTS OF NEW ROOFING.
AE300 1/8" = 1'-0"
6 NORTH ELEVATION
GENERAL NOTES
NEW WORK ROOF NOTES
AE300 1 1/2" = 1'-0"
3 WALL SECTION - END WALL
1/4" = 1'-0"AE300
1 LONGITUDINAL SECTION
1/4" = 1'-0"AE300
2 TRANSVERSE SECTION
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A RESOLUTION. ADJUSTMENTS TO DIMENSIONS AND CONDITIONS
SHOWN MAY BE REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT NEW CONSTRUCTION UNLESS OTHERWISE NOTED. DIMENSIONS ARE
REFERENCED FROM FACE OF FINISH AT EXISTING CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST BE FIELD VERIFIED PRIOR TO THE START OF CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE
READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES WHICH WILL REMAIN EXPOSED, ALIGN NEW WORK FLUSH WITH EXISTING
ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN A WATER TIGHT CONDITION THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY CONSTRUCTION OPERATIONS. TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE BUILDING
AND ITS OCCUPANTS DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE CONSTRUCTION AREA. BARRIERS SHALL NOT INTERFERE WITH THE
OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO PREVENT THE SPREAD OF DUST TO OCCUPIED
AREAS OF THE BUILDING.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS ONLY UNLESS OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
• ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN ACCORDANCE WITH VAMC'S EXISTING ROOF WARRANTY. COORDINATE
ALL MODIFICATIONS TO THE ROOF WITH THE COR.
AE300 3" = 1'-0"
7 TYPICAL WALL TO ROOF DETAIL
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
Addendum 11 6/19/19
RESIN PANEL (RP#1) WITH
IMAGE AND LIGHT BOX,
SEE SPECIFICATIONS.
T Y
P
IC
A L
T Y
P
TYP.
10 1/2"
PATIENT POSITIONING LASER
BY OTHERS. TYPICAL
WALL OPENINING TO
CONCRETE BEYOND.
COORDINATE SIZE AND
POSITION WITH EQUPMENT
MANUFACTURER,TYPICAL
z
X-RAY GENERATOR CABINET
BY BRAINLAB, CONTRACTOR
INSTALLED.
X-RAY WARNING
LIGHT BY VAMC,
CONTRACTOR
INSTALLED.
C
AE610
PLAM#1
SS#1
SEE ELECTRICAL DRAWINGS, VARIAN
AND BRAINLAB PROVIDED
INSTALATION DRAWINGS FOR ALL
WALL MOUNTED DEVICE TYPES
TYPICAL
A
AE610
BASE AS SCHEDULED, TYP.
RELAY JUNCTION BOX BY VARIAN
CASEWORK, SEE 5 / AE401
VARIAN GENERATOR
CABINET BEYOND
CASEWORK, SEE 8 / AE401
SEE ELECTRICAL DRAWINGS, VARIAN
AND BRAINLAB PROVIDED INSTALATION
DRAWINGS FOR ALL WALL MOUNTED
DEVICE TYPES TYPICAL
OPEN TO
PASSAGEWAY
F 2' - 6" 3' - 6"
SS#1
PLAM#1
B
AE610
A
AE610
V
IF
LINE OF WALL
z
CCTV BY VARIAN,
CONTRACTOR
INSTALLED, TYPICAL
SPEAKER BY VARIAN,
CONTRACTOR
INSTALLED, TYPICAL
LIVE VIEW CAMERA
AND MICROPHONE BY
VAMC, CONTRACTOR
INSTALLED.
SEE ELECTRICAL DRAWINGS, VARIAN
AND BRAINLAB PROVIDED INSTALATION
DRAWINGS FOR ALL WALL MOUNTED
DEVICE TYPES TYPICAL
PLAM#1
TYP.
WEDGE TRAY TYPE
CASEWORK SEE VARIAN
DESIGNERS DESKTOP
REFERENCE FOR DETAILS.
WOOD RAILS AND STOPS
ONLY.
ELECTRON APPLICATOR
TYPE CASEWORK SEE
VARIAN DESIGNERS
DESKTOP REFERENCE
FOR DETAILS.
MED GAS
OUTLET
MODULATOR CABINET BY
VARIAN, CONTRACTOR
INSTALLED
LINE OF WALL LINE OF WALL
z
PLAM#1 D
AE610
2' - 10"
PLAM#1
3' - 0"
C
AE610SEE ELECTRICAL
DRAWINGS, VARIAN AND
BRAINLAB PROVIDED
INSTALATION DRAWINGS
FOR ALL WALL MOUNTED
DEVICE TYPES TYPICAL.
COORDINATE AND CONFIRM ALL FIXED EQUIPMENT AND DEVICE LOCATIONS WITH MANUFACTURER
INSTALLATION DOCUMENTS. INSTALL MOUNTING HARDWARE FOR WALL MOUNTED DEVICES AS
DIRECTED BY MANUFACTURER.
CONTRACTOR'S NOTE
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
www.pfa-architect.com - Project No: 2412.17B
ARCHITECTURE, PLANNING, INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510
Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
BID DOCUMENTS
ACTUAL & PLAN
NORTH
NTS
LINAC VAULTS 1 & 2
MODIFICATIONS
HUNTER HOLMES MCGUIRE
VAMC RICHMOND, VA
652-16-107
BLDG. 500
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
/1
/2
:4 :0
P
M M a c \H o m e \D o c u m e n ts
\L o c a l R e v it F ile s \2
B
L
IN
A C
V a u lt s
M o d if ic a ti o n s
C e n tr a l_ d p e ro n n e t.
rv t
AE401
VAULT 1 AND 2 ELEVATIONS
JCHDJP5-13-2019
5-13-2019
3/8" = 1'-0"AE112
5 VAULT 2 EAST
3/8" = 1'-0"AE112
6 VAULT 2 NORTH
3/8" = 1'-0"AE112
7 VAULT 2 SOUTH
3/8" = 1'-0"AE112
8 VAULT 2 WEST
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
Addendum 11 6/19/19
1Z-133
1Z-133A
1Z-134
1Z-135
1Z-132
6' - 2 1/4"
GENERAL FINISH NOTES
• PROVIDE ONE-PIECE VINYL TRANSITION STRIP AT ALL FLOOR FINISH TRANSITIONS. COLOR
SHALL MATCH ADJACENT RUBBER BASE.
• ALL FLOOR FINISH TRANSITIONS SHALL BE CONCEALED BY A CLOSED DOOR.
• ALL FINISHES LISTED ARE NEW UNLESS SPECIFIALLY NOTED AS EXISTING.
• WALL BASE SHALL BE RUBBER ROLL GOODS UNLESS OTHERWISE NOTED.
• WHERE PAINTED GWB ARE INDICATED, PAINTING INCLUDES ALL PREVIOUSLY PAINTED
SURFACES AND TRIM.
• ALL WALLS TO BE PAINTED PNT #1, EGGSHELL, UNLESS OTHERWISE NOTED. SEE FINISH
COLORS FOR INFORMATION.
• ALL TRIM TO BE PAINTED PNT#2, SEMI-GLOSS, UNLESS OTHERWISE NOTED. SEE FINISH
COLORS FOR INFORMATION.
FINISH COLORS
FLOOR
SV#1 GRAY
WALL AND CEILING
ACT#1 (WHITE) 24" X 24" TILE
ACT#2 (WHITE) 24" X 48" TILE
CG#1 CREAM
CG#2 CREAM
PNT#1 (FIELD) OFF WHITE
PNT#2 (TRIM) TAN
PNT#3 (ACCENT) LIGHT BLUE
PNT#4 (CEILING) WHITE
RB#1 TAN
RCP#1 SKYLIGHT
WS#1 CREAM
CASEWORK
SS#1 (TAN) TAN WITH SPECS
PLAM#1 WOOD GRAIN
RP#1 RESIN PANEL WITH IMAGE
FINISH NOTES#
1. PROVIDE CORNER GUARD (CG#1) THIS LOCATION. SEE FINISH COLORS FOR MORE
INFORMATION.
2. PROVIDE CORNER GUARD (CG#2) THIS LOCATION. SEE FINISH COLORS FOR MORE
INFORMATION.
3. PROVIDE ACCENT PAINT (PNT#3) THIS WALL, CORNER TO CORNER. SEE FINISH COLORS
FOR MORE INFORMATION.
4. PROVIDE WAINSCOT (WS#1) THIS WALL, FROM TOP OF COVE BASE TO 52" A.F.F. SEE
FINISH COLORS FOR MORE INFORMATION.
6. PROVIDE RP#1 THIS LOCATION. SEE ELEVATIONS FOR MORE INFORMATION.
7. PROVIDE 6" INTEGRAL BASE, THIS LOCATION. SEE COVE BASE DETAIL, THIS SHEET.
WALL PROTECTION
WHERE APPLICABLE
FLOORING
TURNED UP TO FORM BASE
COVE STRIP
FLOORING
COUNTERTOP SEE ELEVATION FOR
MATERIAL CAULK AT BACKSPLASH
DRAWER PULL - TYPICAL
BACKSPLASH SEE ELEVATION
FOR MATERIAL CAULK AT WALL
DRAWER CONSTRUCTION:
DOVETAIL OR DOWELED CORNERS.
1/4" PLYWOOD DRAWER DADO
BOTTOM AT ALL 4 SIDES
BODY EGDES
1/4" PLYWOOD BACK PANEL (DADO
INTO CABINET BOTTOM AND SIDES)
BASE AS SCHEDULED
FINISH FLOOR
2' - 1"
F O
R C
A S
E W
O R
K H
E
IG
H T
S E
E C
A S
E W
O R
K E
L E
V A
T
IO
N S
/4
/4
" 1
/4
/2
DOOR PULL
RECESSED SHELF
STANDARDS (ATTACH
TO CABINET SIDES)
3/4" PLYWOOD SHELVES
(MELAMINE WITH MATCHING
3MM EDGE BANDING)
SOLID SURFACE COUNTER TOP WITH
MARINE GRADE PLYWOOD PROVIDE
CONTINUOUS BED OF SEALANT UNDER
PERIMETER OF DROP IN SINK FOR
WATERTIGHT SEAL
BACKSPLASH SEE ELEVATION FOR
MATERIAL CAULK AT WALL
UNDERMOUNT SINK (SEE PLUMBING
DRAWINGS)
FACE OF WALL
F O
R C
A S
E W
O R
K H
E
IG
H T
S
S E
E C
A S
E W
O R
K E
L E
V A
T
IO
N S
BASE AS SCHEDULED
FINISH FLOOR
DOOR PULL
/4
/4
/2
TOE KICK ATTACHED
2' - 1"
RECESSED SHELF STANDARDS
(ATTACH TO CABINET SIDES)
3/4" PLYWOOD SHELVES (MELAMINE
W/ 3MM EDGE BAND)
COUNTERTOP SEE ELEVATION FOR
MATERIAL CAULK AT BACKSPLASH
3/4" PLYWOOD SHELVES
(MELAMINE WITH MATCHING
3MM EDGE BANDING)
1/4" PLYWOOD BACK PANEL
(DADO INTO CABINET SIDES)
RECESSED SHELF
STANDARDS (SCREW
ATTACH TO CABINET SIDES)
WOOD FRAME (TYPICAL)
BASE AS SCHEDULED
FINISH FLOOR
DOOR PULL
2' - 1"
F O
R C
A S
E W
O R
K H
E
IG
H T
S E
E C
A S
E W
O R
K E
L E
V A
T
IO
N S
/2
/4
C L E
A R
DOOR PULL
FACE OF WALL
3/4" PLYWOOD SHELVES
(GP-28 ALL SURFACES)
1/4" PLYWOOD BACK PANEL
(DADO INTO CABINET
SIDES)
RECESSED SHELF
STANDARDS (SCREW
ATTACH TO CABINET
SIDES)
WOOD FRAME (TYPICAL)
BASE AS SCHEDULED
FINISHED FLOOR
1' - 1"
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
www.pfa-architect.com - Project No: 2412.17B
ARCHITECTURE, PLANNING, INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510
Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
BID DOCUMENTS
ACTUAL & PLAN
NORTH
NTS
LINAC VAULTS 1 & 2
MODIFICATIONS
HUNTER HOLMES MCGUIRE
VAMC RICHMOND, VA
652-16-107
BLDG. 500
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
/1
/2
:4 :0
P
M M a c \H o m e \D o c u m e n ts
\L o c a l R e v it F ile s \2
B
L
IN
A C
V a u lt s
M o d if ic a ti o n s
C e n tr a l_ d p e ro n n e t.
rv t
AE610
FINISH PLAN - FIRST FLOOR
SMCDJP5-13-2019
5-13-2019
1/4" = 1'-0"
FINISH PLAN - FIRST FLOOR
FINISH SCHEDULE
NUMBER ROOM NAME
FLOOR BASE WALL CEILING
MTL / COLOR MTL / COLOR MTL COLOR MTL / COLOR HEIGHT
1Z-133 VAULT 1 ETR MATCH EXISTING PTD GWB MATCH EXISTING ETR VARIES, SEE RCP.
1Z-133A EQUIPMENT CLOSET ETR ETR ETR ETR ETR -
1Z-134 VAULT 2 SV#1 SV#1 (6" INTEGRAL) PTD GWB / WS / RP PNT#1, 3 / WS#1 / RP#1 ACT#1, 2 / PNT#4 / RCP#1 VARIES, SEE RCP
3" = 1'-0"
1 COVE BASE DETAIL
AE401 1" = 1'-0"
A BASE CABINET - DRAWER/CABINET
AE401 1" = 1'-0"
B SINK - SWINGING DOORS
12" = 1'-0"
2 SKY CEILING IMAGE
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
AE401 1" = 1'-0"
C WARDROBE - 2 DOORS
AE401 1" = 1'-0"
D WARDROBE - OPEN SHELVING - FULL HT
Addendum 11 6/19/19
| Sheets |
| AG001 - PHASING, ABBREVIATIONS, LEGENDS |
| AD101 - DEMOLITION PLANS |
| AE112 - NEW WORK PLANS |
| AE113 - EQUIPMENT PLANS |
| AE300 - ROOF PLAN, BUILDING AND WALL SECTIONS |
| AE401 - VAULT 1 AND 2 ELEVATIONS |
| AE610 - FINISH PLAN - FIRST FLOOR |