This document contains details related to a federal contract opportunity for installing electrical infrastructure to support new laboratory equipment at the Washington, DC Veterans Affairs Medical Center (DC VAMC). The key details include:

The scope of work involves installing power distribution and interfacing to a 40 kVA uninterruptible power supply (UPS) to support new equipment in the Core Lab in Suite GB 200 at the DC VAMC. The new equipment requires specific power requirements which are detailed, including the number and types of power receptacles and cable connections needed. The electrical contractor will be responsible for installing the required power distribution and connections per the provided space plan and equipment specifications. This contract opportunity is solicitation number 36C24524Q0670, issued by the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 5.

View the file

Other files for this federal contract opportunity

Other files attached to J059--Posting Answers to Vendor Questions - Core Lab Electrical Upgrade Install - DC VAMC 688-24-3-459-0307, newest first.
File Type Posted
36C24524Q0670 0001.pdf PDF
3300 Series Footprint and Clearance Requirements.pdf PDF
UPS Specs.pdf PDF
36C24524Q0670 0001_1.docx DOCX document
Final plan.pdf PDF
PowerVar 3300 users manaul A01-00134 3300 REV F 4-5-21.pdf PDF
ANSWERS TO VENDOR QUESTIONS - 36C24524Q0670.pdf PDF
36C24524Q0670 -.pdf PDF
36C24524Q0670_1.docx DOCX document
Wage Determination Washington D.C.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOT TO SCALE SHEET 3 OF 3

ROCHE DIAGNOSTICS

9115 HAGUE ROAD

INDIANAPOLIS, IN 46256

POWERVAR 3300 SERIES UPS CIRCUIT DIAGRAM CLEARANCE SPECIFICATIONS

RECOMMENDED INSTALLATION OPTIONAL PCDU OPTIONAL PCDU INSTALLATION

KEY LEGEND

INSTALL

x mm.

x’-x”

REFERENCE

x’-x”

WATER/DRAIN

x’-x”

POWER

NEW FLOOR DRAIN

EXISTING FLOOR DRAIN

# UTILITY LOCATION

DATA

POWER

WATER LOOP

W/SHUT OFF

CCM PSU

AIR

ROCHE DIAGNOSTICS

9115 HAGUE ROAD

INDIANAPOLIS, IN 46256

WASHINGTON VA

MEDICAL CENTER

WASHINGTON, DC

VA Washington DC_Phased Concept Space Plan111422MS-1

LDA: MARK SIMPSON

SWC: HARRY LANZONI

GENERAL NOTES:

1.SIZE AND CONFIGURATION OF SYMBOLS

SHOWN ON THE DRAWING ARE USED TO

REPRESENT THE EXISTENCE OF, OR NEED FOR

ADDITIONAL UTILITIES.

2.CUSTOMER IS RESPONSIBLE FOR MEETING ALL

LOCAL CODES.

3.CUSTOMER IS RESPONSIBLE FOR CONTACTING

EACH 3

RD

PARTY VENDOR TO OBTAIN TECHNICAL

EQUIPMENT SPECIFICATIONS RELATED TO

INSTALLATION OF INSTRUMENTS AND REQUIRED

UTILITIES. ROCHE WILL PROVIDE TECHNICAL

SPECIFICATIONS AND GENERAL LOCATIONS FOR

UTILITIES OF ROCHE EQUIPMENT ONLY.

CONNECTION TO 3

RD

PARTY SYSTEMS TO BE

VERIFIED BY CUSTOMER.

4.THIS DRAWING IS SUBJECT TO CHANGE.

DATE: DESCRIPTION:

XX/XX/XX TEXT

PROJECT HISTORY:

CUSTOMER PROVIDED INTERFACE CONNECTIONS PROVIDED ON CONSTRUCTION PLAN

EQUIPMENT SPECIFICATIONS

NOT TO SCALE SHEET 2 OF 3

TOTAL SYSTEM HEAT LOAD

BTU/HR (VALUES ROUNDED)

105,368

AT UTILITY

LOCATION ROCHE SUPPLIED EQUIPMENT POWERED FROM

NUMBER OF

DEVICE POWER

CABLES PRIMARY POWER, VOLTS POWER PROTECTION, AMPS PHASE RECEPTACLE TYPE

DEVICE'S UPS

RATING, KVA

HEAT DISSIPATION,

BTU/HR

0 UPS 40.0 kVA WITH BATTERY CABINET FACILITY 0 208 150 3 PHASE 4 CONDUCTOR WITH GROUND HARDWIRED FROM CUSTOMER'S FACILITIES DEPARTMENT 40.0 12,270

0 DI - SHADOW CONTROL UNIT (PC & MONITOR) UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 120 20 SINGLE PHASE NEMA 5-20R 0.6 1,025

0 DI - PRIMARY CONTROL UNIT (PC & MONITOR) UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 120 20 SINGLE PHASE NEMA 5-20R 1.4 1,655

1 REPORT PRINTER (from COBAS PRO) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877

2 REPORT PRINTER (from COBAS PRO) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877

3 REPORT PRINTER (from COBAS 6000) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877

3 UPS 5.2 kVA FACILITY 1 208 30 SINGLE PHASE NEMA L6-30R 5.2 1,970

4 REPORT PRINTER (from COBAS 6000) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877

4 UPS 5.2 kVA FACILITY 1 208 30 SINGLE PHASE NEMA L6-30R 5.2 1,970

AT UTILITY

LOCATION CUSTOMER SUPPLIED DATA CONNECTION CONNECTION TYPE

1 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS

2 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS

3 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS

4 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS

AT UTILITY

LOCATION CUSTOMER SUPPLIED WATER CONNECTION CONNECTION SIZE

DEIONIZED WATER

SUPPLY RATE,

LITERS/HR

MINIMUM FLOOR DRAIN INSIDE

DIAMETER, INCHES

1 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 98 2

2 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 64 2

3 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 110 2

4 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 70 2

AT UTILITY

LOCATION ROCHE SUPPLIED EQUIPMENT POWERED FROM

NUMBER OF

DEVICE POWER

CABLES PRIMARY POWER, VOLTS POWER PROTECTION, AMPS PHASE RECEPTACLE TYPE

DEVICE'S UPS

RATING, KVA

HEAT DISSIPATION,

BTU/HR

1 COBAS LINK 2 UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 0

1 FORTIGATE FIREWALL UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 61

1 COBAS_PRO <ISE/503/ISE/503/801> UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 208 50 SINGLE PHASE HUBBELL 3762C (CORD) OR 3771 (WALL MOUNT) 10.0 28,661

2 COBAS LINK 2 UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 0

2 FORTIGATE FIREWALL UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 61

2 COBAS_PRO <ISE/503/801> UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 208 50 SINGLE PHASE HUBBELL 3762C (CORD) OR 3771 (WALL MOUNT) 10.0 19,107

3 COBAS 6000 CONTROL UNIT (PC & MONITOR) UPS 5.20 kVA 2 120 20 SINGLE PHASE NEMA 5-20R 1.4 1,550

3 COBAS CCE UPS 5.20 kVA 1 208 30 SINGLE PHASE NEMA L6-30R 5.2 17,061

4 COBAS 6000 CONTROL UNIT (PC & MONITOR) UPS 5.20 kVA 2 120 20 SINGLE PHASE NEMA 5-20R 1.4 1,550

4 COBAS CE UPS 5.20 kVA 1 208 30 SINGLE PHASE NEMA L6-30R 5.2 10,919

CUSTOMER'S POWER RESPONSIBILITY

CUSTOMER'S DATA RESPONSIBILITY

CUSTOMER'S WATER/WASTE RESPONSIBILITY

NOTE: TYPE 1 CLRW, UTILIZING A CONTINUOUS RECIRCULATION /POLISHING LOOP, WITH A MINIMAL VELOCITY OF 5 FT/SEC. AND A 0.2 MICRON OUTPUT FILTER. PLEASE REFER TO THE SPECIFIC INSTALLATION SITE REQUIREMENTS DOCUMENTATION.

POWER DISTRIBUTED BY ROCHE SUPPLIED EQUIPMENT

VA Washington DC_Phased Concept Space Plan111422MS-1.vsdx
1/4" - SPACE PLAN
1/4" - SPECS
1/4" - UPS/PCDU SPECS