Power Conditioning Distribution Unit.pdf
PDF 1 MB Posted
- Attached to
- J059--Posting Answers to Vendor Questions - Core Lab Electrical Upgrade Install - DC VAMC 688-24-3-459-0307 Federal contract opportunity
- Solicitation number
- 36C24524Q0670
About this file
This document contains details related to a federal contract opportunity for installing electrical infrastructure to support new laboratory equipment at the Washington, DC Veterans Affairs Medical Center (DC VAMC). The key details include:
The scope of work involves installing power distribution and interfacing to a 40 kVA uninterruptible power supply (UPS) to support new equipment in the Core Lab in Suite GB 200 at the DC VAMC. The new equipment requires specific power requirements which are detailed, including the number and types of power receptacles and cable connections needed. The electrical contractor will be responsible for installing the required power distribution and connections per the provided space plan and equipment specifications. This contract opportunity is solicitation number 36C24524Q0670, issued by the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 5.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24524Q0670 0001.pdf | ||
| 3300 Series Footprint and Clearance Requirements.pdf | ||
| UPS Specs.pdf | ||
| 36C24524Q0670 0001_1.docx | DOCX document | |
| Final plan.pdf | ||
| PowerVar 3300 users manaul A01-00134 3300 REV F 4-5-21.pdf | ||
| ANSWERS TO VENDOR QUESTIONS - 36C24524Q0670.pdf | ||
| 36C24524Q0670 -.pdf | ||
| 36C24524Q0670_1.docx | DOCX document | |
| Wage Determination Washington D.C.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT TO SCALE SHEET 3 OF 3
ROCHE DIAGNOSTICS
9115 HAGUE ROAD
INDIANAPOLIS, IN 46256
POWERVAR 3300 SERIES UPS CIRCUIT DIAGRAM CLEARANCE SPECIFICATIONS
RECOMMENDED INSTALLATION OPTIONAL PCDU OPTIONAL PCDU INSTALLATION
KEY LEGEND
INSTALL
x mm.
x’-x”
REFERENCE
x’-x”
WATER/DRAIN
x’-x”
POWER
NEW FLOOR DRAIN
EXISTING FLOOR DRAIN
# UTILITY LOCATION
DATA
POWER
WATER LOOP
W/SHUT OFF
CCM PSU
AIR
ROCHE DIAGNOSTICS
9115 HAGUE ROAD
INDIANAPOLIS, IN 46256
WASHINGTON VA
MEDICAL CENTER
WASHINGTON, DC
VA Washington DC_Phased Concept Space Plan111422MS-1
LDA: MARK SIMPSON
SWC: HARRY LANZONI
GENERAL NOTES:
1.SIZE AND CONFIGURATION OF SYMBOLS
SHOWN ON THE DRAWING ARE USED TO
REPRESENT THE EXISTENCE OF, OR NEED FOR
ADDITIONAL UTILITIES.
2.CUSTOMER IS RESPONSIBLE FOR MEETING ALL
LOCAL CODES.
3.CUSTOMER IS RESPONSIBLE FOR CONTACTING
EACH 3
RD
PARTY VENDOR TO OBTAIN TECHNICAL
EQUIPMENT SPECIFICATIONS RELATED TO
INSTALLATION OF INSTRUMENTS AND REQUIRED
UTILITIES. ROCHE WILL PROVIDE TECHNICAL
SPECIFICATIONS AND GENERAL LOCATIONS FOR
UTILITIES OF ROCHE EQUIPMENT ONLY.
CONNECTION TO 3
RD
PARTY SYSTEMS TO BE
VERIFIED BY CUSTOMER.
4.THIS DRAWING IS SUBJECT TO CHANGE.
DATE: DESCRIPTION:
XX/XX/XX TEXT
PROJECT HISTORY:
CUSTOMER PROVIDED INTERFACE CONNECTIONS PROVIDED ON CONSTRUCTION PLAN
EQUIPMENT SPECIFICATIONS
NOT TO SCALE SHEET 2 OF 3
TOTAL SYSTEM HEAT LOAD
BTU/HR (VALUES ROUNDED)
105,368
AT UTILITY
LOCATION ROCHE SUPPLIED EQUIPMENT POWERED FROM
NUMBER OF
DEVICE POWER
CABLES PRIMARY POWER, VOLTS POWER PROTECTION, AMPS PHASE RECEPTACLE TYPE
DEVICE'S UPS
RATING, KVA
HEAT DISSIPATION,
BTU/HR
0 UPS 40.0 kVA WITH BATTERY CABINET FACILITY 0 208 150 3 PHASE 4 CONDUCTOR WITH GROUND HARDWIRED FROM CUSTOMER'S FACILITIES DEPARTMENT 40.0 12,270
0 DI - SHADOW CONTROL UNIT (PC & MONITOR) UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 120 20 SINGLE PHASE NEMA 5-20R 0.6 1,025
0 DI - PRIMARY CONTROL UNIT (PC & MONITOR) UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 120 20 SINGLE PHASE NEMA 5-20R 1.4 1,655
1 REPORT PRINTER (from COBAS PRO) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877
2 REPORT PRINTER (from COBAS PRO) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877
3 REPORT PRINTER (from COBAS 6000) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877
3 UPS 5.2 kVA FACILITY 1 208 30 SINGLE PHASE NEMA L6-30R 5.2 1,970
4 REPORT PRINTER (from COBAS 6000) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877
4 UPS 5.2 kVA FACILITY 1 208 30 SINGLE PHASE NEMA L6-30R 5.2 1,970
AT UTILITY
LOCATION CUSTOMER SUPPLIED DATA CONNECTION CONNECTION TYPE
1 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS
2 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS
3 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS
4 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS
AT UTILITY
LOCATION CUSTOMER SUPPLIED WATER CONNECTION CONNECTION SIZE
DEIONIZED WATER
SUPPLY RATE,
LITERS/HR
MINIMUM FLOOR DRAIN INSIDE
DIAMETER, INCHES
1 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 98 2
2 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 64 2
3 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 110 2
4 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 70 2
AT UTILITY
LOCATION ROCHE SUPPLIED EQUIPMENT POWERED FROM
NUMBER OF
DEVICE POWER
CABLES PRIMARY POWER, VOLTS POWER PROTECTION, AMPS PHASE RECEPTACLE TYPE
DEVICE'S UPS
RATING, KVA
HEAT DISSIPATION,
BTU/HR
1 COBAS LINK 2 UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 0
1 FORTIGATE FIREWALL UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 61
1 COBAS_PRO <ISE/503/ISE/503/801> UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 208 50 SINGLE PHASE HUBBELL 3762C (CORD) OR 3771 (WALL MOUNT) 10.0 28,661
2 COBAS LINK 2 UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 0
2 FORTIGATE FIREWALL UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 61
2 COBAS_PRO <ISE/503/801> UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 208 50 SINGLE PHASE HUBBELL 3762C (CORD) OR 3771 (WALL MOUNT) 10.0 19,107
3 COBAS 6000 CONTROL UNIT (PC & MONITOR) UPS 5.20 kVA 2 120 20 SINGLE PHASE NEMA 5-20R 1.4 1,550
3 COBAS CCE UPS 5.20 kVA 1 208 30 SINGLE PHASE NEMA L6-30R 5.2 17,061
4 COBAS 6000 CONTROL UNIT (PC & MONITOR) UPS 5.20 kVA 2 120 20 SINGLE PHASE NEMA 5-20R 1.4 1,550
4 COBAS CE UPS 5.20 kVA 1 208 30 SINGLE PHASE NEMA L6-30R 5.2 10,919
CUSTOMER'S POWER RESPONSIBILITY
CUSTOMER'S DATA RESPONSIBILITY
CUSTOMER'S WATER/WASTE RESPONSIBILITY
NOTE: TYPE 1 CLRW, UTILIZING A CONTINUOUS RECIRCULATION /POLISHING LOOP, WITH A MINIMAL VELOCITY OF 5 FT/SEC. AND A 0.2 MICRON OUTPUT FILTER. PLEASE REFER TO THE SPECIFIC INSTALLATION SITE REQUIREMENTS DOCUMENTATION.
POWER DISTRIBUTED BY ROCHE SUPPLIED EQUIPMENT
| VA Washington DC_Phased Concept Space Plan111422MS-1.vsdx |
| 1/4" - SPACE PLAN |
| 1/4" - SPECS |
| 1/4" - UPS/PCDU SPECS |