This document is a space plan and equipment specifications related to a federal contract opportunity for the Core Lab electrical upgrade at the Washington DC Veterans Affairs Medical Center (DC VAMC).
The key details are:
- The Core Lab is installing new processing equipment on the basement floor in Suite GB 200.
- A 40 KVA Uninterruptable Power Supply (UPS) will be used to provide emergency power to the new equipment.
- The electrical contractor is required to install the power distribution and interface the equipment to the 40 KVA UPS located in room GB 220.
- Detailed power and utility requirements are provided for each piece of Roche Diagnostics equipment, including power voltage, amperage, phases, receptacle types, UPS ratings, and heat dissipation.
- The solicitation number is 36C24524Q0670 and the agency is the Department of Veterans Affairs Veterans Health Administration.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| PowerVar 3300 users manaul A01-00134 3300 REV F 4-5-21.pdf | ||
| ANSWERS TO VENDOR QUESTIONS - 36C24524Q0670.pdf | ||
| 3300 Series Footprint and Clearance Requirements.pdf | ||
| UPS Specs.pdf | ||
| 36C24524Q0670 0001_1.docx | DOCX document | |
| Power Conditioning Distribution Unit.pdf | ||
| 36C24524Q0670 0001.pdf | ||
| Wage Determination Washington D.C.pdf | ||
| 36C24524Q0670 -.pdf | ||
| 36C24524Q0670_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT FOR CONSTRUCTION
KEY LEGEND
INSTALL
x mm.
x’-x”
REFERENCE
x’-x”
WATER/DRAIN
x’-x”
POWER
NEW FLOOR DRAIN
EXISTING FLOOR DRAIN
# UTILITY LOCATION
DATA
POWER
WATER LOOP
W/SHUT OFF
CCM PSU
AIR
ROCHE DIAGNOSTICS
9115 HAGUE ROAD
INDIANAPOLIS, IN 46256
SCALE: ¼” = 1'-0" SHEET 1 OF 3
WASHINGTON VA
MEDICAL CENTER
WASHINGTON, DC
VA Washington DC_8100 Space Plan111422MS-1
LDA: MARK SIMPSON
SWC: HARRY LANZONI
GENERAL NOTES:
1.SIZE AND CONFIGURATION OF SYMBOLS
SHOWN ON THE DRAWING ARE USED TO
REPRESENT THE EXISTENCE OF, OR NEED FOR
ADDITIONAL UTILITIES.
2.CUSTOMER IS RESPONSIBLE FOR MEETING ALL
LOCAL CODES.
3.CUSTOMER IS RESPONSIBLE FOR CONTACTING
EACH 3
RD
PARTY VENDOR TO OBTAIN TECHNICAL
EQUIPMENT SPECIFICATIONS RELATED TO
INSTALLATION OF INSTRUMENTS AND REQUIRED
UTILITIES. ROCHE WILL PROVIDE TECHNICAL
SPECIFICATIONS AND GENERAL LOCATIONS FOR
UTILITIES OF ROCHE EQUIPMENT ONLY.
CONNECTION TO 3
RD
PARTY SYSTEMS TO BE
VERIFIED BY CUSTOMER.
4.THIS DRAWING IS SUBJECT TO CHANGE.
DATE: DESCRIPTION:
XX/XX/XX TEXT
PROJECT HISTORY:
UTILITIES – SPACE PLAN
Lo ck e rs
Lo ck e rs
Fr zr
-2 c
Refrig Fisher Refrig
S a fe ty s h o w e r
H2O system
Shred
Box
H2O system
S ta in e r
R e fr ig e ra to rs a n d S u p p li e s
Exist ing drain
Exist ing drain
Exist ing drain
Fr ig
Exist ing drain
R ef ri g
Refrig
-8 c Fr ee ze r
RefrigRefrig
D xH
D xH
M anuals
S T
A -C o m p a c t
Fi le
Fi le
Fi le
Shelf
Sh el f
Shelf S hred
Box
S T
A -C o m p a c t
PTS
H20
S ta in e r
L
IS
Heme Archive Table Heme Input Table
New +4c
N ew
4c
D I C o n tro lle r
8100 Control Unit & Report Printer
R S
F A
O B
O B
S c o b a s o u tp u t s ta tio n
DSPACU with ACBIPB
HS
cobas 8100 input station
ACU with ACB BCL AQM cobas 8100 aliquot station
CRW
c o b a s
TLJ
T L J
TLJ
TLJ
S L L cobas 8100
B R
F c o b a s p ro c o b a s p ro
B R
F c o b a s p ro c o b a s p ro c o b a s p ro c o b a s L in k
R e p o rt
P ri n te r c o b a s p ro c o b a s L in k
R e p o rt
P ri n te r c o b a s
A
T L
SUGGESTED AREA FOR NEW DRAINS.
IF REUSING EXISTING DRAINS, THEY SHOULD BE WITHIN 16
FT OF THE INSTRUMENT. IF NOT, SEE ROCHE INSTALLATION
SITE REQUIREMENTS FOR ADDITIONAL SPECIFICATIONS.
SUGGESTED AREA
FOR UTILITY DROPS.
TYPICAL OF 4
Data Power Water Loop
Power
#1
U P
S
.0 k V
A
S e ri e s
B a tt e ry C a b in e t
See UPS/Battery Cabinet Specs.
Power
Off-site location TBD. Max distance is 250ft.
#0
Firewall c o b a s p ro
IS
E -5
-I S
E -5
-8 c o b a s p ro
IS
E -5
-8
Virtual Server Primary
Virtual Server Shadow
Off-site location TBD.
#0
Data
Water Loop
FirewallFirewall
#2
#4
Data
#3
KEY LEGEND
INSTALL
x mm.
x’-x”
REFERENCE
x’-x”
WATER/DRAIN
x’-x”
POWER
NEW FLOOR DRAIN
EXISTING FLOOR DRAIN
# UTILITY LOCATION
DATA
POWER
WATER LOOP
W/SHUT OFF
CCM PSU
AIR
ROCHE DIAGNOSTICS
9115 HAGUE ROAD
INDIANAPOLIS, IN 46256
WASHINGTON VA
MEDICAL CENTER
WASHINGTON, DC
LDA: MARK SIMPSON
SWC: HARRY LANZONI
GENERAL NOTES:
1.SIZE AND CONFIGURATION OF SYMBOLS
SHOWN ON THE DRAWING ARE USED TO
REPRESENT THE EXISTENCE OF, OR NEED FOR
ADDITIONAL UTILITIES.
2.CUSTOMER IS RESPONSIBLE FOR MEETING ALL
LOCAL CODES.
3.CUSTOMER IS RESPONSIBLE FOR CONTACTING
EACH 3
RD
PARTY VENDOR TO OBTAIN TECHNICAL
EQUIPMENT SPECIFICATIONS RELATED TO
INSTALLATION OF INSTRUMENTS AND REQUIRED
UTILITIES. ROCHE WILL PROVIDE TECHNICAL
SPECIFICATIONS AND GENERAL LOCATIONS FOR
UTILITIES OF ROCHE EQUIPMENT ONLY.
CONNECTION TO 3
RD
PARTY SYSTEMS TO BE
VERIFIED BY CUSTOMER.
4.THIS DRAWING IS SUBJECT TO CHANGE.
DATE: DESCRIPTION:
XX/XX/XX TEXT
PROJECT HISTORY:
CUSTOMER PROVIDED INTERFACE CONNECTIONS PROVIDED ON CONSTRUCTION PLAN
EQUIPMENT SPECIFICATIONS
NOT TO SCALE SHEET 2 OF 3
VA Washington DC_8100 Space Plan111422MS-1
TOTAL SYSTEM HEAT LOAD
BTU/HR (VALUES ROUNDED)
103,808
AT UTILITY
LOCATION ROCHE SUPPLIED EQUIPMENT POWERED FROM
NUMBER OF DEVICE
POWER CABLES
PRIMARY POWER,
VOLTS
POWER PROTECTION,
AMPS PHASE RECEPTACLE TYPE
DEVICE'S UPS
RATING, KVA
HEAT
DISSIPATION,
BTU/HR
0 UPS 40.0 kVA WITH BATTERY CABINET FACILITY 0 208 150 3 PHASE 4 CONDUCTOR WITH GROUND HARDWIRED FROM CUSTOMER'S FACILITIES DEPARTMENT 40.0 12,270
0 DI - SHADOW CONTROL UNIT (PC & MONITOR) UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 120 20 SINGLE PHASE NEMA 5-20R 0.6 1,025
0 DI - PRIMARY CONTROL UNIT (PC & MONITOR) UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 120 20 SINGLE PHASE NEMA 5-20R 1.4 1,655
1 REPORT PRINTER (from COBAS PRO) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877
1 COBAS LINK 2 UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 0
1 FORTIGATE FIREWALL UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 61
1 COBAS_PRO <ISE/503/ISE/503/801> UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 208 50 SINGLE PHASE HUBBELL 3762C (CORD) OR 3771 (WALL MOUNT) 10.0 28,661
2 REPORT PRINTER (from COBAS PRO) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 1,877
2 COBAS LINK 2 UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 0
2 FORTIGATE FIREWALL UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 61
2 COBAS_PRO <ISE/503/801> UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 208 50 SINGLE PHASE HUBBELL 3762C (CORD) OR 3771 (WALL MOUNT) 10.0 19,107
3 REPORT PRINTER (from COBAS 8100) FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 2,048
3 COBAS 8100 CONTROL UNIT (PC & MONITOR) UPS 40.0 kVA MAIN LUG PANEL (MLP) 2 120 20 SINGLE PHASE NEMA 5-20R 0.8 1,550
3 FORTIGATE FIREWALL UPS 40.0 kVA MAIN LUG PANEL (MLP) 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 61
3 COBAS 8100 SYSTEM UPS 40.0 kVA MAIN LUG PANEL (MLP) 5 208 30 SINGLE PHASE NEMA L6-30R 5.2 33,385
4 AUTOMATED TIP LOADER FACILITY 1 120 20 SINGLE PHASE NEMA 5-20R 0.0 170
AT UTILITY
LOCATION CUSTOMER SUPPLIED DATA CONNECTION CONNECTION TYPE
1 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS
2 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS
3 DATA UTILITY SEE CUSTOMER PROVIDED INTERFACE CONNECTIONS
AT UTILITY
LOCATION CUSTOMER SUPPLIED WATER CONNECTION CONNECTION SIZE
DEIONIZED WATER
SUPPLY RATE,
LITERS/HR
MINIMUM FLOOR DRAIN
INSIDE DIAMETER,
INCHES
1 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 98 2
2 WATER UTILITY 5/8" BARBED HOSE FITTING W 1/2" ID 64 2
CUSTOMER'S WATER/WASTE RESPONSIBILITY
NOTE: TYPE 1 CLRW, UTILIZING A CONTINUOUS RECIRCULATION /POLISHING LOOP, WITH A MINIMAL VELOCITY OF 5 FT/SEC. AND A 0.2 MICRON OUTPUT FILTER. PLEASE REFER TO THE SPECIFIC INSTALLATION SITE REQUIREMENTS DOCUMENTATION.
CUSTOMER'S POWER RESPONSIBILITY
CUSTOMER'S DATA RESPONSIBILITY
NOT TO SCALE SHEET 3 OF 3
ROCHE DIAGNOSTICS
9115 HAGUE ROAD
INDIANAPOLIS, IN 46256
POWERVAR 3300 SERIES UPS CIRCUIT DIAGRAM CLEARANCE SPECIFICATIONS
RECOMMENDED INSTALLATION OPTIONAL PCDU OPTIONAL PCDU INSTALLATION
| VA Washington DC_8100 Space Plan111422MS-1.vsdx |
| 1/4" - SPACE PLAN |
| 1/4" - SPECS |
| 1/4" - UPS/PCDU SPECS |
File details come from the government source that posted it. Updated .