Perry Point Lead Survey Summary Report_Medgas - Copy.pdf

PDF 172 KB Posted

Attached to
Y1DA--VISN 5 - MULTIPLE AWARD TASK ORDER CONTRACT CONSTRUCTION 2022 Federal contract opportunity
Solicitation number
36C24522R0056
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 5

About this file

This is a solicitation for a multiple award task order contract for construction services. The contract will be awarded to multiple vendors to provide general construction services including maintenance, repair, alteration, mechanical, electrical, and other construction categories on an as-needed basis. Task orders will vary in size and scope but may include work such as site preparation, roofing, drywall, plumbing, and renovations. Services are needed at Veterans Affairs medical centers in Veterans Integrated Service Network 5. The base period of performance is one year from date of award. Task orders will be fixed price and the contractor's overhead and profit rates will remain fixed for the life of the contract. Davis Bacon wage rates will apply to task orders as relevant. Fair opportunity to compete will be provided for each task order unless an exception applies such as urgency or logical follow-on to a previous order.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--VISN 5 - MULTIPLE AWARD TASK ORDER CONTRACT CONSTRUCTION 2022, newest first.
File Type Posted
Resized_20221013_065215.jpg JPG image
Resized_20221013_063747.jpg JPG image
Resized_20221013_065407.jpg JPG image
36C24522R0056 0003.pdf PDF
Resized_20221013_065220.jpg JPG image
Resized_20221013_063633.jpg JPG image
Resized_20221013_063615.jpg JPG image
Resized_20221013_063628.jpg JPG image
Resized_20221013_065235.jpg JPG image
Resized_20221013_065343.jpg JPG image
Resized_20221013_063752.jpg JPG image
Resized_20221013_063737.jpg JPG image
Resized_20221013_063621.jpg JPG image
Drawing 32-01-A12 Main Building Elevations C _ D - Copy.pdf PDF
Building 1 first floor-Layout1 - Copy.pdf PDF
Building 1 Second Floor-Layout1 - Copy.pdf PDF
15246 Perry Point ACM Summary Report_Medgas - Copy.pdf PDF
36C24522R0056 0002.pdf PDF
MATOC Site Visit Attendance_9-22-2022 - Copy.pdf PDF
Building 1 Basement-Layout1 - Copy.pdf PDF
Expansion Joint Spec - Copy.pdf PDF
Lab Waiting Sign In - Copy.pdf PDF
MATOC Site Visit Attendance_8-30-2022 - Copy.pdf PDF
36C24522R0056 0001.pdf PDF
Attachment 7_ RFI SHEET.pdf PDF
Attachment 6C_ Security_SelfCertificationContinuousService.pdf PDF
Attachment 6A_ Security_ServicesRequestForm.pdf PDF
Attachment 6_Security Requirements Cover Page.pdf PDF
Attachment 5_ Surety Information.pdf PDF
Attachment 2D_ WAGE DETERMINATIONS PERRY POINT.pdf PDF
Attachment 6E_ VA0710.pdf PDF
Attachment 6D_ OF306.pdf PDF
Attachment 6B_ Security_ServicesRequestForm_Supplemental.pdf PDF
Attachment_4 Construction Price Breakdown(R).xls XLS spreadsheet
Attachment 1C_ Combined Final Drawings Renovate Lab Waiting Area -Beckley.pdf PDF
Attachment 6F_ Security_PIVSponsorshipForm.pdf PDF
Attachment 3_ Past Performance Evaluation.docx DOCX document
Attachment 2C_ 512A5-16-303 Construction Drawings Package- Perry Point.pdf PDF
Attachment 1B_ Combined Specs Renovate Lab Waiting Area - Beckley.pdf PDF
Attachment 1A_ SOW - 517-17-123 Lab Waiting Area Beckley.docx DOCX document
Attachment 8_ GEOGRAPHIC AREA SELECTION FORM.pdf PDF
Attachment 2B_ 512A5-16-303 SOW Upgrade Medical Gas Systems -Perry Point .docx DOCX document
Attachment 2A_ 512A5-16-303 Construction Specifications Package - Perry Point.pdf PDF
Attachment 1D_ WAGE DETERMINATIONS BECKLEY VAMC - Copy.pdf PDF
36C24522R0056_1.docx DOCX document
Show all 45

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

United States Department of Veterans Affairs

Perry Point Campus

Lead Paint Screening

Environmental Consultants

1331 Ashton Road P.O. Box 646 Hanover, MD 21076 410-684-3327 FAX: 410-684-3384 www.amaconsulting.com

November 13, 2013

Mr. Robert Deinert Safety/Occupational Health Program Manager VA Maryland Healthcare System Perry Point VA Medical Center Bldg. 101, Room 31 Perryville, MD 21902

RE: United States Department of Veteran Affairs VISN 5 Contract No. GS-10F-

0386K Lead Paint Screening for the Veterans Affairs Perry Point Campus

Bldg: Perry Point Campus

AMA Project #: 13404

Mr. Deinert:

Between September 30 and October 31st, 2013 Aerosol Monitoring & Analysis, Inc. (AMA) representatives, Mr. Andrew Washington, Mr. Patrick Dincher, Mr.

Adam Truax, Mr. Rob Schoennagel, Mr. Kinte Thompson, and Mr. Ron Stallard conducted an onsite lead paint screening of the Perry Point VAMC campus facilities for the purpose of identifying lead containing materials within the buildings.

Background Information

Perry Point Campus Perry Point, MD 21902

1,103,000 square feet for inspection

Total Buildings: 50 (including connecting corridors)

Original Construction Dates: Various dates ranging from 1918 – Present (Mansion constructed in 1750)

Renovations Dates: Various dates on select buildings ranging from 1968 - Present

Existing Lead Documentation – None to be relied upon

Buildings inspected by AMA:

(24H) Mental Health (1H) Domiciliary (25H) Mental Health (2H) Domiciliary (26) Fire House (3H) Administration (27H) Biomedical Shop

(4) Research (41) Greenhouse

(4H) IRMS (59)

(5H) Director’s Office (80H) Mental Health Clinic

(5) Stock Storage (82) Education/Research (6H) Voluntary Service (97) Gatehouse

(8) Engineering Storage (101) Administration (9H) Nursing Home (102) Filter Plant

(11) Warehouse (314A) Theater (11H) Human Resources (314B) Recreation (13H) Psychiatric Units (314C) Chapel

(13) Public Health Service (315) Boiler Plant (14H) Psychiatric Units (321) Chiller Plant

(14) (360)

(15) Administration (361) (15H) Rehab (364) (17H) Dietetics Connecting Corridors (18H) Maintenance Shops Credit Union (19H) Medical Wards Mansion House (20H) Medical Media/IRMS Grist Mill

(20) Water Pumping Station REMRO

(22) Filter Plant (22H) Substance Abuse/Detox (23H) Geropsych Nursing

General Summary

AMA randomly tested surfaces for lead containing materials (LCM) throughout each above listed building at the Perry Point VAMC Campus.

Lead Inspector(s) – Andrew Washington (Maryland Risk Assessor 10057) Adam Truax (Maryland Lead Inspector 14117) Robert Schoennagel (Maryland Lead Inspector 4179) Kinte Thompson (Maryland Lead Inspector 13795) Patrick Dincher (Maryland Lead Inspector 7164) Ronald Stallard (Maryland Lead Inspector 4357)

The LCM testing was performed with a Radiation Monitoring Device (RMD) LPA-1 model x-ray fluorescence analyzer (XRF), Serial #1954. The XRF contains a small radioactive source (Cobalt 57), which emits radiation when pressed against a surface. If the paint contains lead, the radiation will stimulate the lead atoms to re-emit x-rays, which are sensed by a detector in the unit. The XRF then converts these signals to a final reading in milligrams of lead per square centimeter of surface area tested (mg/cm2). The LPA-1 XRF is capable of achieving a ninety-five percent confidence interval in readings to a depth of 3/8 inch.

The XRF was calibrated in accordance with the manufacturer's instructions. Prior to obtaining readings from suspect surfaces, three calibration readings were taken on a National Institute for Science and Technology (NIST) Calibration Test Block and recorded. The NIST Calibration Block contains a known concentration of lead (1.02 mg/cm2) and the XRF must indicate 1.02 mg/cm2 with a tolerance of + or - 0.3 mg/cm2 for the average of the three readings. If the average of three readings is within the established tolerance, the unit is working properly. Calibration checks were performed prior to and at the end of the investigation.

The LPA-1 XRF features two modes of operation when in use: Quick mode and Standard mode. When the Quick mode is engaged on the LPA-1, the unit seeks the shortest period of time to assure a positive, or a negative measurement with 95% confidence. As stated in the XRF Performance Characteristics Sheet (PCS) developed jointly by the U.S. EPA and the U.S. Department of Housing and Urban Development (HUD); no substrate correction is needed. The Quick mode was used during the course of the investigation.

Many types of components tested were found to contain greater than (>) 0.7 mg/cm2 of surface area tested, which is the amount defined as a lead-containing material according to the COMAR, Title 26, Department of the Environment, Subtitle 16, Lead, Chapter 01. Table I at the end of the report lists components that were found to have lead concentrations of >0.7 mg/cm2 within each building.

Table II lists all XRF readings that were found to be LCM.

There is no requirement to remove LCM prior to demolition activities for this type of building in the State of Maryland, only that components finished with LCM be tested, to determine the disposal requirements, following the requirements of the Resource Conservation and Recovery Act (RCRA) and any other applicable federal, state and local laws and regulations. In addition, contractors need to be made aware of the existence of LCM so their workers and the environment can be adequately protected. All lead-containing waste is to be handled and disposed of as hazardous waste unless toxic characteristic leaching procedure (TCLP) testing is performed and indicates otherwise. The waste shall be considered as hazardous when the concentration of lead exceeds 5 parts per million (ppm) by the TCLP.

The Occupational Safety and Health Administration (OSHA) Lead in Construction Standard (29 CFR 1926.62, with Maryland Amendments) must be adhered to during demolition to the LCM finished surfaces. This standard established the permissible exposure level (PEL) for lead at 50 micrograms per cubic meter (ug/m3) as an eight-hour time weighted average (TWA); the action level has been established at 30 ug/m3 as an eight hour TWA. This regulation also requires employers to use engineering controls and special work practices to reduce worker lead exposure to, at, or below the PEL. It also triggers several requirements regarding exposure monitoring, biological monitoring, and employee training when a worker is exposed to airborne lead levels at or above the action level.

Some painted surfaces may contain levels of lead at or below 0.7 mg/cm2, which are able to create lead dust or lead-contaminated soil hazards if the paint is turned into dust by abrasion, scraping, or sanding. Whenever renovation or demolition is performed on any painted components, an attempt should be made to control dust. If any surfaces with measurable amounts of lead are to be disturbed, it must be done so in accordance with the OSHA, and by trained personnel using appropriate techniques and respiratory protection. The OSHA does not honor threshold levels of lead in paint.

Below is the facility-wide damaged LCM assessment. Materials that were identified as having peeling, flaking, or chipping lead containing paint are listed. Some of the paint is deteriorated over large areas and these materials are listed as significantly damaged.

Facility Condition Summary for Lead Containing Material

(1H) Domiciliary

Significantly damaged lead paint in building includes: Plaster Ceilings

(2H) Domiciliary

Significantly damaged lead paint in building includes: Plaster Ceilings Isolated damaged lead paint in building includes: Plaster Walls

(3H) Administration

Significantly damaged lead paint in building includes: Plaster Ceilings, Wood Overhangs Isolated damaged lead paint in building includes: Plaster Walls, Metal Grates, Wood Door Jambs, & Wood Door Casings

(4) Research

No damaged lead paint identified

(4H) IRMS

Significantly damaged lead paint in building includes: Plaster Ceilings Isolated damaged lead paint in building includes: Metal Radiator Pipe, & Metal Fire Alarm Case

(5H) Director’s Office

Isolated damaged lead paint in building includes: Plaster Ceilings

(5) Stock Storage

Isolated damaged lead paint in building includes: Metal Stairwell, Concrete Floor, & Brick Window Sills

(6H) Voluntary Service

No damaged paint identified

(8) Engineering Storage

Isolated damaged lead paint in building includes: Metal Door Casings, Wood Door Casings, Metal Steps, & Metal Window Sash

(9H)

Significantly damaged lead paint in building includes: Concrete Walls Isolated damaged lead paint in building includes: Wood Door Frame, Metal Door Casings, Metal Pipe, Metal Window Sash, & Plaster Columns

(11) Warehouse

Significantly damaged lead paint in building includes: Metal Window Sash Isolated damaged lead paint in building includes: Brick Walls, Metal Door Casings, Metal I-beam, Metal Pipe, & Metal Cage

(11H) Human Resources

Isolated damaged lead paint in building includes: Plaster Ceilings

(13) Public Health Service

Isolated damaged lead paint in building includes: Terracotta Brick Ceilings

(13H) Psychiatric Units

Isolated damaged lead paint in building includes: Plaster Columns, Walls & Ceilings, Metal Sinks, Metal Door Casings, Ceramic Baseboard, Concrete Ceilings, Wood Door Train, Metal Hand rail, Concrete Door Trim Base, & Wood Door Trim Base

(14)

Isolated damaged lead paint in building includes: Terracotta Floors, & Metal Window Sash.

(14H) Psychiatric Units

Significantly damaged lead paint in building includes: Plaster Ceilings & Walls Isolated damaged lead paint in building includes: Metal Hand rail, Wood Window Casings, & Metal Grate

(15) Administration

Isolated damaged lead paint in building includes: Wood Window Sash, Metal Window Sash, Steel I-beam, Metal Structural Beam, Wood Door, Wood Door Frame, & Wood Window Frame

(15H) Rehab

No damaged paint identified

(17H) Dietetics

Isolated damaged lead paint in building includes: Metal Step, Metal Riser, Metal Hand rail, Concrete Ceiling, Metal Newel Post, & Metal Safety Rail

(18H) Maintenance Shops

Isolated damaged lead paint in building includes: Plaster Walls, Metal Fire Extinguisher Case, Metal Fan Casing, Metal Fire Protection Pipe, & Porcelain Sink

(19H) Medical Wards

No damaged paint identified

(20H) Medical Media/IRMS

No damaged paint identified

(20) Water Pumping Station

Isolated damaged lead paint in building includes: Wood Door Casings, & Concrete Base

(22) Filter Plant

Isolated damaged lead paint in building includes: Wood Column, Wood Stairs, & Wood Walls.

(22H) Substance Abuse/Detox

Isolated damaged lead paint in building includes: Porcelain Toilet, Porcelain Sink, Concrete Floor, & Metal Pipe

(23H) Geropsych Nursing

No damaged paint identified

(24H) Mental Health

Isolated damaged lead paint in building includes: Metal Hand rail

(25H) Mental Health

No damaged paint identified

(26) Fire House

(27H) Biomedical Shop

No damaged paint identified

(41) Greenhouse

Isolated damaged lead paint in building includes: Terracotta Walls, & Wood Soffit

(59)

No damaged paint identified.

(80H) Mental Health Clinic

Isolated damaged lead paint in building includes: Concrete Walls, CMU Wall, Wood Door, Wood Door Casings, Concrete Ceiling, Wood Soffit, & Wood Fascia

(82) Education/Research

Significantly damaged lead paint in building includes: Concrete Walls & Ceilings Isolated damaged lead paint in building includes: Wood Hatch Door, Wood Door Casings, Metal Pipe, Metal Door, Metal Door Casings, Wood Window Sash, Wood Window Casings, & Wood Window Sill

(97) Gatehouse

No damaged paint identified.

(101) Administration

Significantly damaged lead paint in building includes: Attic Steel Structure, Wood Structure Isolated damaged lead paint in building includes: Concrete Column, Steel I-beam, Steel Plank, Steel Joist, & Brick Walls

(102) Filter Plant

Isolated damaged lead paint in building includes: Wood Door, Walls, & Door Casings, & Metal Pipe.

(314A) Theater

Isolated damaged lead paint in building includes: Metal Window Lintel

(314B) Recreation

Isolated damaged lead paint in building includes: Metal Baseboard

(314C) Chapel

No damaged paint identified.

(315) Boiler Plant

Isolated damaged lead paint in building includes: Metal Tank

(321) Chiller Plant

Isolated damaged lead paint in building includes: Metal Support Column

(360)

Isolated damaged lead paint in building includes: Metal Corners

(361)

Isolated damaged lead paint in building includes: Metal Hand Rail

(364)

No damaged paint identified

Connecting Corridors

No damaged paint identified

Credit Union

No damaged paint identified

Mansion House

Significantly damaged lead paint in building includes: Plaster Walls and Ceilings, Wood Window Sill, Wood Shutter, Wood Door & Walls, Wood Awning, & Wood Window Casings Isolated damaged lead paint in building includes: Wood Stair Carriage, Wood Window Sash, Wood Door Casings, Wood Crown Molding

Grist Mill

Significantly damaged lead paint in building includes: Wood Door, Door Casings, & Window Casings

REMRO

If you have any questions regarding this summary or the attached data spreadsheets, please contact me at our office.

Sincerely, Andrew Washington Project Manager

Attachments

TABLE I – LEAD BASED PAINT COMPONENT TABLE

TABLE I

LBP COMPONENT TABLE

VA PERRY POINT

NOVEMBER 2013

Building 1H

Plaster Walls & Ceilings

Porcelain Sinks Metal Door

Casings Wood Door

Casings Wood Porch

Ceiling Wood Roof

Truss Concrete

Ledge Building 2H

Plaster Walls & Ceilings

Metal Stairtread Wood Door

Casings Wood Porch

Ceiling Concrete Ledge

Wood Roof Truss

Building 3H

Wood soffit Metal Grate Wood Door

Casings Metal Hand rail Plaster Walls &

Ceilings Metal

Baseboard Metal Door

Lintel Metal Sink Wood Door Jamb

Building 4

Concrete Stair Metal I-beam Cinderblock Wall Metal Pipe Metal Door

Casings Metal

Radiator Porcelain Sink

Concrete Soffit Wood Soffit Metal Hand Rail

Building 4H

Plaster Walls, Ceilings, & Columns

Ceramic Wall Tile Metal Radiator

Pipe Metal Stair

Tread Wood Roof Truss Metal Pipe

Wood Door Casing

Metal Fire Alarm Case

Metal Hand Rail

Building 5

Metal Window Sash Metal Hand Rail Wood Window

Casing Metal

Stairwell Metal I-beam Metal Door Concrete Floor

Metal Support Beam Concrete Support

Beam Concrete Walls

Brick Wash Sink

Brick Walls Metal Pipe Metal

Structural Support Strip

Brick Window Sill Metal Shelf

Building 5H

Plaster Walls, Ceilings, & Columns

Porcelain Sinks Metal Pipe Metal

Stairtread Metal Kick Plate

Ceramic tile Baseboard

Plaster Door Casing

Building 6H

Porcelain Sink Metal Hand rail

Building 8

Metal Door Casing Wood Door Casing Brick Walls Concrete

Walls Metal Wall Bin

Flange Wood Door Metal Step

Metal Window Sash Dryvit Window Sill

Building 9H

Wood Door Frame Wood Column Metal Hand Rail Concrete

Walls Plaster Walls

Plaster Door Jamb

Plaster Columns

Metal Locker Porcelain Sinks Plaster Walls and Ceilings

Metal Door Casing

Metal Shelf Porcelain Tub Metal Pipe

Metal Window Sash Metal Cage Door Wood Door

Building 11

Brick Walls Metal Door Casing Metal I-beam Metal

Window Sash Wood Door

Casing Metal Pipe

Wood Window Sash

TBL I-1

VA PERRY POINT

NOVEMBER 2013

Metal Cage Metal I-beam crossbar Concrete Walls

Metal Horizantal Support Beam

Concrete Window Casing

Concrete Floor

Metal Ladder

Metal Shelf Metal Cabinet

Building 11H Plaster Walls &

Ceilings Metal Extinguisher

Case Metal Door

Casings Metal Hand

Rail Porcelain Sinks Metal Pipe

Porcelain Slop Sink

Metal Fire Box Metal Window Sash

Building 13 Terracotta Brick

Ceiling Concrete Ceiling

Deck Concrete Walls Metal Pipe

Building 13H

Plaster Walls, Ceilings, & Columns

Metal Door Casing Metal Sink Ceramic

Baseboard Ceramic Wall Tile Metal Stringer Metal Riser

Metal Radiator Metal Ballard Wood Door

Frame Metal Hand rail Concrete Door

Trim Base Metal Down Spout Drain

Porcelain Sinks

Concrete Ceiling Wood Door Trim

Base

Building 14

Metall Support Pole Metal I-beam Metal Door

Casings Concrete Ceiling

Metal Cage Terracotta

Floor Concrete Walls

Wood Door Metal Stair Railing Metal Window

Sash Cinder Block

Walls Metal Window Sill

Concrete Base

Metal Safety Rail

Concrete Window Sill

Building 14H Plaster Walls &

Ceilings Metal Door Casing

Metal Newel Post

Metal Hand Rail

Metal Stringer Metal Riser Wood Door

Casing Wood Window

Casing Metal Grate

Building 15 Plaster Walls &

Ceilings Brick Walls

Wood Window Frames

Wood Window Sill

Wood Window Sash

Porcelain Sinks

Metal Window Sash

CMU Walls Metal Support Pole Metal Hand Rail Steel I-beam Metal Support

Strip Metal Pipe Metal Wall

Metal Conduit Pipe Metal Structural

Beam Wood Door

Wood Door Frame

Building 15H

Metal Door Casing Plaster Walls &

Ceiling Wood Door

Transom Porcelain

Sinks Porcelain Urinals

Ceramic Walls

Metal Pipe

Metal Hand rail Concrete Cellar Door

Case Metal Cellar Door Cage

Concrete Window Sill

Metal Ballard

Building 17H

Metal Door Casing Concrete Walls Metal Step Metal Kick

Plate Metal Riser

Metal Hand Rail

Concrete Ceiling

Metal Rail Metal Newel Post Metal Safety Rail

Building 18H

TBL I-2

VA PERRY POINT

NOVEMBER 2013

Metal Fire Extinguisher Case

Metal Fan Casing Metal Fire

Protection Pipe Metal Door

Casing Ceramic tile

Walls Concrete

Walls Plaster Walls &

Ceilings

Wood Column Metal Window Porcelain Sinks Metal Rail Metal Down

Spout Fan Case

Building 19H

Plaster Walls & Ceilings

Metal Radiator Cover Concrete Walls Metal

Electical Box Door

Metal Radiator Metal Cage Metal Stair

Riser

Metal Spindle Metal Newel Post Metal Kick Plate Concrete Ceiling

Metal Door Casings

Wood Crawlspace

Case Metal Pipe

G tilo Wall Concrete Columns

Building 20

Metal Lintel Wood Door Casing Metal Door

Frame Concrete

Base Building 20H

Cinderblock Walls Cinderblock Window

Sill Metal Window

Mullion Metal Pipe

Building 22

Wood Column Metal I-beam Wood Stairs Wood Walls

Building 22H

Metal Radiator Cover Plaster Walls Porcelain Sinks Porcelain

Toilet Ceramic tile Baseboard

Metal Door Casing

Metal Trap Door

Wood Window Casing

Plaster Radiator Cover

Metal Hand rail Metal Riser Metal Newel Post Ceramic tile

Wall Plaster

Window Case

Metal I-beam Concrete Floor Metal Pipe Wood Mullion Metal Stringer Metal Step Wood Door

Casing

Plaster Door Trim Concrete Door Stoop Metal Rail Metal Fire

Box Building 23H

Metal Vent Cover Metal Hand Rail Metal Stair

Stringer Metal Stair

Riser Metal Stairtread

Metal Newel Post

Plaster Walls

Building 24H

Metal Hand rail Wood Door Frame Wood Window

Sill Metal Door

Casing Ceramic Wall

Wood Window Casing

Building 25H

Metal Baseboard Metal Window Case Metal Stringer Metal Kick

Plate Wood Window

Casing

Metal Radiator Cover

Wood Window Sill

Metal Window Jamb Metal Window Sill Wood Door

Casings Metal Fire

Box Metal Pipe

Building 26

Metal Conduit Wood Window Wood Door

Casings Metal

Window Sill Building 27H

Ceiling

Building 41

Plaster Walls & Ceilings

Wood Window Sill Wood Window

Casing Wood

Window Sash Wood Door

Wood Door Casing

Metal Pipe

TBL I-3

VA PERRY POINT

NOVEMBER 2013

Drywall Walls Terracotta Wall Wood Soffit

Building 59

No LBP

Building 80H

Concrete Walls Plaster Walls, Columns, & Ceilings Wood Crown

Molding Wood

Window Sill Wood Window

Casing Metal

Radiator Metal Door

Casing

Wood Shelf Ceramic Glazed Tile Wood Door

Casings Plaster Door

Casing Metal Newel Post

Metal Sprinkler

CMU Wall

Concrete Ceiling Wood Door Wood Window Concrete Column

Wood Column Wood Soffit Wood Fascia

Building 82

Plaster Walls, Ceilings, & Columns

Wood Crown Molding Wood Window

Casing Wood

Window Sill Wood Fireplace

Mantle Wood Door

Wood Door Casing

Metal Door Casing Metal Door Jamb Plaster Door

Casing Porcelain

Sinks Metal Ladder

Metal Roof Hatch

Wood Shelf

Metal Radiator Concrete Walls Concrete Ceiling Wood Hatch

Door Metal Pipe Metal Door Wood Column

Wood Fascia Wood Soffit Wood Decorative

Trim Wood

Window Sash

Building 97

Wood Window Sash Plaster Walls &

Ceiling Wood Door

Wood Door Casings

Wood Window Sill

Wood Window Casing

Wood AC Casing

Wood Soffit Wood Fascial Board

Building 101

Stucco Walls Concrete Columns Metal Door

Casings Metal Bottom

Trim Steel Structure

Wood Structure

Steel I-beam

Steel Plank Steel Joist Brick Walls Concrete

Down Spout Building 102

Wood Door Wood Door Casing Wood Wall Metal Pipe

Building 314A

Metal I-beam Metal Door Lintel Ceramic Wall Metal Hand rail Metal Newel Post

Metal Stair Stringer

Metal Kick Plate Riser

Metal Stairtread Metal Window Lintel Metal Base Plate

Building 314B

Metal Baseboard Metal Hand rail Wood Alley Floor

Strip Metal Newel

Post Metal Stair

Stringer Metal Stair

Riser Metal Stair Carriage

Metal I-beam

Building 314C

Metal Window Lintel

Building 315

Metal Wall Metal I-beam Metal Pipe Metal Boiler Metal Tank Metal Trench

Cover Metal Door

TBL I-4

VA PERRY POINT

NOVEMBER 2013

Building 321

Metal Door Casing Metal I-beam Metal Pipe Metal Tension

Rods Metal Support

Column

Building 360

Ceramic tile Metal Stall Metal Corner Metal Ladder Metal Pipe Metal Loading

Plate

Building 361

Ceramic tile Wall Metal Hand rail

Building 364

No LBP Connecting Corridors

Metal Ballard Metal Corner

Protector Metal Door

Metal Door Casing

Metal Door Lintel Metal Window

Lintel

Credit Union

No LBP

Mansion House

Plaster Walls & Ceilings

Wood Crown Molding Wood

Baseboard Wood Door

Wood Window Panel

Wood Fire Mantle

Wood Fireplace Case

Wood Window Sill Wood Window

Casing Wood Window

Well Wood Door

Casings Wood Shelf

Wood Window Sash

Wood Stair Carriage

Ceramic tile Wall Wood Shutter Concrete Walls Wood Walls Wood Awning

Grist Mill

Wood Door Wood Door Casing Wood Window

Casing

REMRO

Porcelain Sink

TBL I-5

TABLE II – POSTIVE XRF TABLE

TABLE II

POSITIVE XRF TABLE

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

Building 1H

005 1H foyer Tan Wall Plaster Intact >9.9

035 SP 128 Conference room Tan Ceiling Plaster Not intact >9.9 041 SP 130 Tan Ceiling Plaster Not intact >9.9 047 Exam room Tan Ceiling Plaster Not intact >9.9 049 West stairwell Tan Wall Plaster Intact >9.9 050 West stairwell Tan Wall Plaster Intact >9.9 051 West stairwell Tan Wall Plaster Intact >9.9 052 West stairwell Tan Wall Plaster Intact >9.9 055 West stairwell Tan Ceiling Plaster Intact >9.9 062 SP 225 Bedroom Tan Wall Plaster Intact >9.9 090 SP 211 White Sink Porcelain Intact >9.9 091 SP 211 Brown Door casing Metal Intact 0.8 095 SP 206 Tan Wall Plaster Intact >9.9 097 SP 206 Tan Wall Plaster Intact >9.9 099 SP 206 Off-white Ceiling Plaster Not intact >9.9 112 Exterior Tan Door casing Wood Intact 2.9 114 Exterior Tan Porch ceiling Wood Intact 3.6 123 Exterior Tan Roof truss Wood Intact >9.9 124 Exterior Red Ledge Concrete Intact 0.8

Building 2H

005 2H foyer Tan Wall Plaster Intact 7.9 006 2H foyer Tan Wall Plaster Intact 7.3 012 1st floor hallway Tan Wall Plaster Intact 4.5 018 1st floor hallway Off-white Wall Plaster Not intact 9.0 031 South stairwell Blue Stairtread Metal Intact 0.8 044 113 TV lounge Off-white Ceiling Plaster Not intact >9.9 047 102 Electrical closet Tan Wall Plaster Not intact 0.8 049 102 Electrical closet Tan Wall Plaster Intact 1.7 063 S100 Stairway Tan Wall Plaster Intact 1.3 064 S100 Stairway Tan Wall Plaster Intact 9.3 065 S100 Stairway Tan Wall Plaster Intact >9.9 067 S100 Stairway Tan Ceiling Plaster Intact >9.9 075 212 Multi-purpose Off-white Ceiling Plaster Not intact >9.9 088 216 Crach cart room Tan Ceiling Plaster Not intact >9.9 105 118 Residence room Off-white Ceiling Plaster Not intact >9.9 106 Exterior Off-white Door casing White Intact 0.8 108 Exterior Off-white Porch ceiling Wood Intact 2.2 113 Exterior Brown Ledge Concrete Intact 0.8 115 Exterior Tan Roof truss Wood Intact 1.4

Building 3H

007 Exterior White Soffit Wood Not intact 3.9 008 Exterior White Soffit Wood Not intact 3.7 011 Exterior Black Grate Metal Not intact 2.4 012 Exterior Off-white Door casing Wood Intact 3.9 014 Exterior Black Hand rail Metal Intact 0.8 016 1st floor - main entrance White Wall Plaster Intact >9.9 021 1st floor - main entrance White Ceiling Plaster Not intact >9.9

TBL II-1

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

027 1st floor - main entrance Tan Ceiling Plaster Not intact >9.9 034 1st floor - medical library Tan Ceiling Plaster Not intact >9.9 041 1st floor - stairwell S-119 Black Baseboard Metal Intact 0.8 046 1st floor - Room 116 White Wall Plaster Intact >9.9 047 1st floor - Room 116 White Wall Plaster Intact >9.9 051 1st floor - Room 116 Green Ceiling Plaster Not intact >9.9 053 1st floor - stairwell S-102 White Wall Plaster Intact >9.9 054 1st floor - stairwell S-102 White Wall Plaster Intact 4.9 055 1st floor - stairwell S-102 White Wall Plaster Intact >9.9 056 1st floor - stairwell S-102 White Wall Plaster Intact >9.9 057 1st floor - stairwell S-102 White Ceiling Plaster Intact >9.9 058 1st floor - stairwell S-102 Gray Hand rail Metal Intact 0.8 067 1st floor - main corridor White Wall Plaster Intact >9.9 068 1st floor - main corridor White Wall Plaster Intact >9.9 070 1st floor - main corridor White Ceiling Plaster Not intact >9.9 077 1st floor - Room 111 Brown Door lentil Metal Intact 6.3 078 1st floor - Room 111 White Sink Metal Intact >9.9 085 2nd floor - Room 220 White Ceiling Plaster Not intact >9.9 090 2nd floor - Main corridor White Ceiling Plaster Not intact >9.9 093 2nd floor - Room 208 White Ceiling Plaster Not intact >9.9 099 2nd floor - Room 201A White Ceiling Plaster Not intact >9.9 104 2nd floor - Room 201F White Wall Plaster Intact >9.9 105 2nd floor - Room 201F White Ceiling Plaster Intact >9.9 111 2nd floor - Room 201D White Ceiling Plaster Intact 2.4 117 2nd floor - Room 201 Blue Wall Plaster Not intact >9.9 118 2nd floor - Room 201 White Ceiling Plaster Not intact >9.9 119 2nd floor - Room 201 White Door jamb Wood Not intact >9.9 120 2nd floor - Room 201 White Door casing Wood Not intact >9.9 123 2nd floor - Room 203 White Wall Plaster Intact >9.9 129 2nd floor - Room 203 White Ceiling Plaster Not intact >9.9

Building 4

009 Lobby Off-white Stair Concrete Intact 0.8 013 Lobby Off-white I-beam Metal Intact 2.8 018 Print shop Tan Wall Cinder block Intact 5.1 020 Print shop Tan Pipe Metal Intact 3.9 021 Print shop Tan Door casing Metal Intact 5.9 036 Main Corridor Off-white Door casing Metal Intact 3.2 063 Stairwell (west) Off-white Radiator Metal Intact 0.8 068 2nd floor foyer Off-white I-beam Metal Intact 0.8 070 2nd floor foyer Off-white Door casing Metal Intact 5.2 076 211 floor foyer White Sink Pocelain Intact 3.3 110 Exterior roof Off-white Soffit Concrete Intact 0.8 114 Exterior Off-white Soffit Wood Intact >9.9 121 Exterior Gray Hand rail Metal Intact 0.8

Building 4H

005 Lobby Off-white Wall Plaster Intact >9.9 007 Lobby Off-white Wall Plaster Intact 0.8 012 Hallway 1st floor Off-white Wall Plaster Intact >9.9 018 Hallway 1st floor Off-white Wall Ceramic tile Intact 3.5 021 Stairwell Off-white Wall Plaster Intact >9.9

TBL II-2

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

022 Stairwell Off-white Wall Plaster Intact >9.9 023 Stairwell Off-white Wall Plaster Intact >9.9 024 Stairwell Off-white Wall Plaster Intact >9.9 025 Stairwell Off-white Wall Plaster Intact >9.9 033 Supply closet Off-white Wall Plaster Intact >9.9 035 103 FCP Services Off-white Wall Plaster Intact >9.9 048 Room 103B Off-white Column Plaster Intact >9.9 049 Room 103B Tan Ceiling Plaster Not intact >9.9 056 Men's room Gray Wall Plaster Intact >9.9 065 Men's room Gray Radiator pipe Metal Not intact 0.8 083 2nd floor hall Off-white Wall Plaster Intact >9.9 085 2nd floor hall Off-white Wall Plaster Intact >9.9 090 2nd floor hall Tan Ceiling Plaster Not intact >9.9 094 202-205 Corridor Off-white Wall Plaster Intact >9.9 100 Kitchen/conference room Off-white Wall Plaster Intact >9.9 101 Kitchen/conference room Off-white Wall Plaster Intact >9.9 106 Mechanical room Red Stair tread Metal Intact 0.8 111 Exterior Tan Roof truss Wood Intact 1.3 114 Exterior Tan Pipe Metal Intact 0.8 115 Exterior Tan Door casing Wood Intact 1.6

118 Exterior Red Fire alarm case Metal Not intact 6.1 122 Exterior Black Hand rail Metal Intact 0.8 125 Exterior Tan Roof truss Wood Intact 2.0

Building 5

008 Exterior, west wall Tan Window sash Metal Intact 0.8 011 Exterior, north wall Yellow Handrail Metal Intact 0.8

022 Exterior, east wall Off-white Window casing Wood Intact 0.8 024 Exterior, south wall Black Stairwell Metal Not intact 5.4 036 Interior, electric room White I-beam Metal Intact 0.8

Interior, ground floor warehouse Red Door Metal Intact 1.4 070 Interior, Paint storage Gray Floor Concrete Not intact 0.8

076 Interior, warehouse storage Yellow Support Beam Metal Intact 0.8

077 Interior, warehouse storage Red Support Beam Concrete Intact 0.8

079 Interior, warehouse storage White I-beam Metal Intact 0.8

085 Interior, warehouse storage White Wall Concrete Intact 0.8

Interior, Refrigerator #3 room White Wash sink Brick Intact 0.8

Interior, Refrigerator #3 room White Wall Brick Intact 0.8

110 Interior, warehouse (east) White Wash sink Brick Intact 0.8

Warehouse interior, 2nd level White Wall Brick Intact 0.8

TBL II-3

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

Warehouse interior, 2nd level White Pipe Metal Intact 0.8

Warehouse interior, 2nd level White Structural

Support Strip Metal Intact 0.8

Warehouse interior, 2nd level White Window sash Metal Intact >9.9

Warehouse interior, 2nd level White Window sill Brick Not intact 0.8

Warehouse interior, 2nd level Gray Window sash Metal Intact 2.3

Warehouse interior, 2nd level Gray Window sill Brick Not intact 0.8

Warehouse interior, 2nd level Orange Shelf Metal Intact 0.8 Building 5H

005 Lobby Off-white Wall Plaster Intact >9.9 006 Lobby Off-white Wall Plaster Intact 9.1 012 1st floor corridor Off-white Wall Plaster Intact 8.8 013 1st floor corridor Off-white Wall Plaster Intact 9.6 014 1st floor corridor Off-white Wall Plaster Intact >9.9 015 1st floor corridor Off-white Wall Plaster Intact 6.3 021 1st floor corridor Off-white Ceiling Plaster Not intact >9.9 029 1st floor corridor White Sink Porcelain Intact >9.9 038 Room 103 Green Ceiling Plaster Not intact >9.9 043 Copy room 109 Off-white Wall Plaster Intact >9.9 046 Copy room 109 Off-white Sink Porcelain Intact 2.6 056 South stairwell Red Pipe Metal Intact 0.8 057 South stairwell Black Stair tread Metal Intact 0.8 059 South stairwell Black Kick plate Metal Intact 0.8 065 206B Off-white Wall Plaster Intact 8.1 066 206B Off-white Wall Plaster Intact 6.1 067 206B Off-white Ceiling Plaster Intact >9.9 081 2nd floor corridor Off-white Wall Plaster Intact >9.9 087 Bathroom (unisex) White Ceiling Plaster Intact >9.9 096 Kitchen Off-white Wall Plaster Intact >9.9

099 Kitchen Brown Baseboard Ceramic tile Intact >9.9 101 Stair #2 Off-white Wall Plaster Intact 8.5 102 Stair #2 Off-white Wall Plaster Intact 8.4 103 Stair #2 Off-white Wall Plaster Intact >9.9 104 Stair #2 Off-white Wall Plaster Intact 6.2 105 Stair #2 Off-white Ceiling Plaster Intact 5.9 109 Executive suit White Wall Plaster Intact >9.9 111 Executive suit White Wall Plaster Intact 8.5 114 Executive suit White Column Plaster Intact 7.3 117 Exterior Tan Door casing Plaster Intact 1.3 126 Exterior Red Pipe Metal Intact 0.8

Building 6H

017 Room 9 Off-white Sink Porcelain Intact >9.9 033 Exterior Black Hand rail Metal Intact 1.9

TBL II-4

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

Building 8

004 Warehouse Brown Door casing Metal Not intact 6.2 014 Warehouse White Door casing Wood Not intact 6.6 018 Ice machine room White Wall Brick Intact 0.8 024 Break room Tan Wall Concrete Intact 1.3

039 Storage Black Wall bin flange Metal Intact 0.8 040 Storage White Door Wood Intact 4.7 041 Platform Gray Step Metal Not intact 0.8 051 Exterior Red Window sash Metal Not intact 1.9 052 Exterior Tan Window sill Dryvit Intact 0.8 053 Exterior Red Door casing Metal Not intact 3.2 060 Exterior Brown Door casing Metal Not intact 3.9

Building 9H

006 Exterior Tan Door frame Wood Not intact >9.9 007 Exterior Tan Column Wood Intact >9.9 008 Exterior Black Hand rail Metal Intact 4.2 013 Exterior Brown Wall Concrete Intact 0.8 015 Exterior Off-white Wall Concrete Intact 0.8 016 Exterior Black Hand rail Metal Intact 4.4 024 1st floor corridor White Wall Plaster Intact >9.9 029 Room 148 White Door jamb Plaster Intact >9.9 030 Room 148 White Door frame Metal Intact >9.9 038 Room 16 White Column Plaster Intact >9.9 039 Room 16 Orange Locker Metal Intact 1.5 042 Laundry room Blue Column Plaster Intact >9.9 044 Laundry room White Sink Porcelain Intact >9.9 074 East stairwell White Wall Plaster Intact >9.9 075 East stairwell White Wall Plaster Intact >9.9 076 East stairwell Tan Hand rail Metal Intact 8.0 087 Room 264 Pink Locker Metal Intact 0.8 091 Room 248 White Door casing Metal Intact >9.9 100 Room 258 White Door casing Metal Intact >9.9 101 Room 258 White Wall Plaster Intact >9.9 110 Room 249 Yellow Shelf Metal Intact 0.8 111 Room 249 White Sink Porcelain Intact >9.9 115 2nd floor lounge White Wall Plaster Intact >9.9 125 Room 209 Orange Locker Metal Intact 1.7 126 Room 209 White Wall Plaster Intact >9.9 129 Room 219 White Wall Plaster Intact >9.9 131 Room 219 White Wall Plaster Intact >9.9 132 Room 219 White Door casing Metal Intact >9.9 140 Room 215 White Tub Porcelain Intact >9.9 150 Basement corridor White Wall Concrete Not intact >9.9 151 Basement corridor White Wall Concrete Not intact >9.9 152 Basement corridor White Wall Concrete Not intact 9.4 153 Basement corridor White Wall Concrete Not intact >9.9 155 Basement corridor White Door casing Metal Not intact 8.0 156 Basement corridor Red Pipe Metal Not intact 0.8 160 Mechanical room White Window sash Metal Not intact >9.9

TBL II-5

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

162 Boiler room Tan Cage door Metal Intact >9.9 163 Boiler room Gray Door casing Metal Intact >9.9 169 Storage room White Sink Porcelain Intact >9.9 170 Storage room Tan Door frame Wood Intact >9.9 171 Storage room Tan Door Wood Intact >9.9 172 Storage room Tan Wall Concrete Intact >9.9 174 Basement bedroom Green Wall Concrete Not intact 9.5 175 Basement bedroom Green Wall Concrete Not intact 7.2 176 Basement bedroom Green Door casing Metal Not intact 9.6 177 Basement bedroom Green Wall Concrete Not intact >9.9 178 Basement bedroom Green Door casing Metal Not intact >9.9 179 Basement bedroom Green Column Plaster Not intact >9.9 190 1st floor - Room 104 Tan Locker Metal Intact 1.4 195 Exterior Black Hand rail Metal Intact 2.6

Building 11

005 Exterior, north wall White Wall Brick Not intact 1.9 006 Exterior, north wall Brown Door casing Metal Not intact 0.8 008 Exterior, north wall White I-beam Metal Intact >9.9 011 Exterior, north wall Brown I-beam Metal Not intact >9.9 013 Exterior, west wall White Window sash Metal Not intact 9.3 016 Exterior, west wall Brown Door casing Metal Intact 0.8 019 Exterior, south wall Brown Door casing Metal Intact 0.8 022 Exterior, south wall White Window sash Metal Not intact 0.8 024 Exterior, south wall White Door casing Wood Intact 3.0 030 Exterior, east wall Red Pipe Metal Not intact 1.5 031 Exterior, north wall White Window sash Wood Not intact 3.1

Interior, warehouse 1st level Green Cage Metal Not intact 1.7

Interior, warehouse 1st level White I-beam Metal Intact 8.6

Interior, warehouse 1st level White I-beam crossbar Metal Intact 0.8

Interior, warehouse 1st level White Wall Brick Intact 0.8

Interior, warehouse 1st level Yellow I-beam Metal Not intact 7.4

Interior, warehouse 1st level Red Wall Brick Intact 0.8

Interior, warehouse 1st level Yellow I-beam Metal Intact >9.9 064 Warehouse 2nd level White I-beam Metal Intact >9.9 065 Warehouse 2nd level Green Wall Brick Not intact 0.8 066 Warehouse 2nd level Gray Window sash Metal Intact >9.9 072 Warehouse 2nd level White Wall Concrete Intact 0.8 076 Warehouse 2nd level Green I-beam Metal Intact 2.5 077 Warehouse 2nd level Green Wall Brick Intact 0.8

080 Warehouse 2nd level Gray Horizantal support beam Metal Intact 0.8 093 Warehouse 3rd level Green I-beam Metal Intact 0.8 099 Warehouse 3rd level Red I-beam Metal Intact >9.9

TBL II-6

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

103 Warehouse 3rd level White Window casing Concrete Intact >9.9

105 Warehouse 3rd level White Window casing Concrete Intact >9.9 107 Warehouse 4th level Gray Floor Concrete Intact >9.9 112 Warehouse 4th level Yellow I-beam Metal Intact 7.8 113 Warehouse 4th level Black Ladder Metal Intact 1.7 114 Warehouse 4th level Black I-beam Metal Intact 2.8 116 Warehouse 4th level Black Pipe Metal Intact 3.9 121 Warehouse 4th level Yellow Shelf Metal Intact 1.6 122 Warehouse 4th level Yellow Shelf Metal Intact 1.5 132 Warehouse 4th level Yellow Shelf Metal Intact 1.7

Warehouse bathroom 1st level Blue Pipe Metal Intact 2.4

Warehouse bathroom 1st level Blue I-beam Metal Intact 8.9

150 Warehouse office 1st level Blue Cabinet Metal Intact 2.2 159 Warehouse 1st level West I-beam Metal Intact 5.5

Building 11H

009 1st floor hall Off-white Wall Plaster Intact 0.8 016 Human resource lobby Off-white Wall Plaster Intact 4.4

018 Human resource lobby Off-white Extinguisher case Metal Intact 4.9 019 Human resource lobby Off-white Door casing Metal Intact >9.9 021 Central stairwell Off-white Wall Plaster Intact 6.5 022 Central stairwell Off-white Wall Plaster Intact 3.5 024 Central stairwell Off-white Wall Plaster Intact 3.7 025 Central stairwell Black Hand rail Metal Intact 0.8 028 Central stairwell Off-white Ceiling Plaster Intact >9.9 031 2nd floor lobby Off-white Wall Plaster Intact 3.0 032 2nd floor lobby Off-white Wall Plaster Intact 5.7 033 2nd floor lobby Off-white Wall Plaster Intact 7.8 034 2nd floor lobby Off-white Door casing Metal Intact >9.9 036 2nd floor lobby Off-white Door casing Metal Intact >9.9 038 2nd floor hallway Off-white Wall Plaster Intact 7.3 039 2nd floor hallway Off-white Wall Plaster Intact 5.7 043 2nd floor hallway Off-white Door casing Metal Intact >9.9 045 2nd floor hallway Off-white Door casing Metal Intact >9.9 048 Copy room 201 Off-white Wall Plaster Intact 8.1 054 Men's room Off-white Wall Plaster Intact >9.9 055 Men's room Off-white Wall Plaster Intact >9.9 057 Men's room Off-white Wall Plaster Intact >9.9 060 Men's room White Sink Porcelain Intact >9.9 063 Men's room White Door casing Metal Intact >9.9 068 Men's room Off-white Ceiling Plaster Not intact >9.9 072 North lobby Off-white Wall Plaster Intact 7.2 074 North lobby Off-white Door casing Metal Intact >9.9

076 North lobby Off-white Extinguisher case Metal Intact 5.6 084 Room 211 Off-white Door casing Metal Intact >9.9

TBL II-7

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

090 House keeping closet Off-white Sink Porcelain Intact >9.9 091 House keeping closet Off-white Door casing Metal Intact 9.0 095 House keeping closet White Pipe Metal Intact 0.8 103 Vending room Off-white Wall Plaster Intact 6.2 107 Vending room Off-white Door casing Metal Intact >9.9 112 Janitor closet Off-white Slop sink Porcelain Intact >9.9 113 Janitor closet Off-white Door casing Metal Intact >9.9 117 Exterior Red Fire box Metal Intact 0.8 125 Exterior White Window sash Metal Intact 0.8

Building 13

029 2nd floor - CIMS Office Gray Ceiling Terracotta brick Not intact >9.9 066 1st floor - corridor White Ceiling deck Concrete Intact >9.9 071 Exterior - south wall Tan Wall Concrete Intact 0.8 075 Exterior - east wall Tan Pipe Metal Intact 0.8

Building 13H

1st floor, main entrance, vestibule Off-white Wall Plaster Intact 6.0

1st floor, main entrance, vestibule Beige Door casing Metal Intact 2.5

1st floor, main entrance, vestibule Beige Door casing Metal Intact 5.2

1st floor, main hall

(east/west) Off-white Wall Plaster Intact 6.1

1st floor, main hall

(east/west) Off-white Wall Plaster Intact 5.3 018 1st floor, Room 125 Off-white Door casing Metal Intact 0.8 025 1st floor, Room 129 Blue Wall Plaster Not intact >9.9 026 1st floor, Room 129 White Sink Metal Not intact 0.8 028 1st floor, Room 129 Blue Wall Plaster Not intact >9.9 029 1st floor, Room 129 Blue Wall Plaster Not intact >9.9 031 1st floor, Room 129 Blue Door casing Metal Not intact 4.7 032 1st floor, Room 128 White Wall Plaster Not intact >9.9 033 1st floor, Room 128 White Wall Plaster Not intact >9.9 034 1st floor, Room 128 Gray Door casing Metal Not intact 3.9 035 1st floor, Room 128 White Column Plaster Not intact >9.9 036 1st floor, Room 128 White Wall Plaster Not intact >9.9 037 1st floor, Room 128 Brown Baseboard Ceramic Not intact >9.9 039 1st floor, Room 128 White Wall Plaster Not intact >9.9 041 1st floor, Room 128 Gray Door casing Metal Intact 3.4

1st floor, Room 128, Shower area Yellow Wall Ceramic tile Intact >9.9

1st floor, Room 128, Shower area Gray Wall Plaster Intact >9.9

1st floor, Room 128, Shower area Gray Door casing Metal Intact 3.1

1st floor, Room 131, Women's room Tan Wall Ceramic tile Intact 3.6

TBL II-8

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

1st floor, Room 131, Women's room Off-white Wall Plaster Intact 9.5

1st floor, Room 131, Women's room Off-white Wall Plaster Intact >9.9

1st floor, Room 131, Women's room Beige Door casing Metal Intact 6.0

1st floor, Room 131, Women's room Off-white Ceiling Plaster Intact 6.0

1st floor, Room 140, Break room Beige Door casing Metal Intact 4.8 079 1st floor, Room 133 Green Wall Plaster Intact 9.1 080 1st floor, Room 133 Green Wall Column Plaster Intact 9.1 086 1st floor, Room 137 White Wall Plaster Intact 9.3 094 Stair No. 4 Black Stringer Metal Intact 0.8 099 1st floor, Room 122 White Wall Plaster Intact 8.8 100 1st floor, Room 122 Gray Door casing Metal Intact 3.9 101 1st floor, Room 122 White Wall Plaster Intact 7.9 102 1st floor, Room 120 Tan Wall Plaster Intact 7.8 104 1st floor, Room 120 Tan Wall Plaster Intact 6.3 106 1st floor, Room 120 Beige Door casing Metal Intact 4.2 107 1st floor, Room 120 White Ceiling Plaster Intact 4.9 114 1st floor, Room 107 White Wall Plaster Intact 7.0 115 1st floor, Room 107 White Wall Plaster Intact 7.6 119 Stair No. 1 Green Stair riser Metal Intact 0.8

2nd floor, east-west corridor Off-white Wall Plaster Intact >9.9

2nd floor, east-west corridor Off-white Wall Plaster Intact >9.9 134 2nd floor, Room 237 Pink Wall Plaster Intact >9.9 142 2nd floor, Room 225 Off-white Wall Plaster Intact >9.9 143 2nd floor, Room 225 Off-white Wall Plaster Intact >9.9 144 2nd floor, Room 225 Off-white Wall Plaster Intact >9.9 147 2nd floor, Room 217 Green Wall Plaster Intact 9.3 148 2nd floor, Room 217 Green Wall Plaster Intact 7.8 149 2nd floor, Room 217 Green Column Plaster Intact 9.2

2nd floor, Room 207, Men's room Off-white Wall Plaster Intact >9.9

2nd floor, Room 207, Men's room Off-white Wall Plaster Intact >9.9

2nd floor, Room 207, Men's room Off-white Wall Plaster Intact >9.9

2nd floor, Room 207, Men's room Beige Wall Ceramic tile Intact 4.4

2nd floor, Room 207, Men's room White Ceiling Plaster Intact >9.9

2nd floor, Room 210, Kitchenette Green Wall Plaster Intact >9.9

2nd floor, Room 210, Kitchenette Green Wall Plaster Intact >9.9

2nd floor, Room 210, Kitchenette Green Wall Plaster Intact >9.9 178 2nd floor, Room 212 Green Wall Plaster Intact 9.5

TBL II-9

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

183 Basement, Hall Off-white Wall Plaster Intact 4.3 184 Basement , Room 20 Beige Wall Plaster Intact 0.8 188 Basement, Room 20 White Sink Porcelain Intact 0.8 191 Basement, Room 20 Beige Door casing Metal Intact >9.9 192 Basement, Room 20 Beige Ceiling Concrete Not intact 0.8

Basement, Room 13, Men's Locker Blue Wall Plaster Intact 2.0

Basement, Room 13, Men's Locker Blue Wall Plaster Intact 0.8

Basement, Room 13, Men's Locker Blue Wall Plaster Intact 1.8

Basement, Room 13, Men's Locker Blue Radiator Metal Intact 0.8 202 Basement, Hall Yellow Ballard Metal Intact 1.5 203 Exterior White Door Frame Wood Not intact 3.4 205 Exterior Black Hand rail Metal Not intact 0.8

206 Exterior White Door trim base Concrete Not intact 0.8

207 Exterior White Door trim base Wood Not intact 1.9

211 Exterior Orange Down spout drain Metal Intact 0.8 Building 14

053 Hallway Off-white Support pole Metal Intact 3.4 054 Hallway Off-white Support pole Metal Intact 2.6 064 Chair quality P.B. Office Off-white Support pole Metal Intact 5.9 070 Hallway outside Lin PL6 White I-beam Metal Intact 3.4 072 Hallway outside Lin PL6 White Door casing Metal Intact 3.6 073 Hallway outside Lin PL6 Black Door casing Metal Intact 5.6 080 Vault drug storage White Ceiling Concrete Intact 3.2 082 Vault White Cage Metal Intact >9.9 083 Vault White Cage Metal Intact 9.6 085 Vault White Support pole Metal Intact 4.9 087 Vault Gray Floor Terracotta Not intact 0.8 088 Vault Gray I-beam Metal Intact 8.1 091 Label production control White Wall Concrete Intact 3.8 092 Label production control Off-white Door Wood Intact 5.8 093 Label production control Tan Door casing Metal Intact 5.5 096 Finished lable storage White Wall Concrete Intact 0.8 098 Lable production hall Blue I-beam Metal Intact 0.8 104 Lable production room Tan Wall Concrete Intact 6.5 191 Clinical trials & assembly Yellow Stair railing Metal Intact 1.3

194 Clinical trials & assembly Gray Window sash Metal Not intact 6.2

196 Clinical trials & assembly White Ceiling Concrete Intact 3.3

198 Mechanical room White Wall Cinder block Intact 5.6 200 Mechanical room White Wall Concrete Intact 5.4 205 Exterior Brown Window sill Metal Intact 0.8 213 Exterior Tan Wall Concrete Intact 5.2

TBL II-10

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

215 Exterior Tan Base Concrete Intact 0.8 217 Exterior Yellow Safety rail Metal Intact 2.7 226 Exterior Tan Wall Concrete Intact 5.8 227 Exterior Tan Window sill Concrete Intact 0.8 228 Exterior Tan Window sash Metal Intact 0.8

Building 14H

010 1st floor - Room 144 Off-white Ceiling Plaster Not intact >9.9

1st floor - Northeast corridor Off-white Ceiling Plaster Not intact 8.1

1st floor - Northeast corridor Off-white Wall Plaster Not intact >9.9 057 1st floor - Dining room Off-white Ceiling Plaster Not intact >9.9 073 1st floor - Room 160 Off-white Ceiling Plaster Not intact >9.9

2nd floor - corridor outside

252 Red Door casing Metal Intact 5.5 124 2nd floor - Room 244 Off-white Ceiling Plaster Not intact >9.9 141 2nd floor - Room 231 Tan Ceiling Plaster Not intact >9.9

2nd floor - Corridor outside

Room 23 Tan Ceiling Plaster Not intact >9.9 169 2nd floor, Dining room Off-white Ceiling Plaster Not intact >9.9 170 2nd floor, Dining room Off-white Wall Plaster Not intact >9.9 190 Stairwell #3 - 1st floor Yellow Wall Plaster Intact >9.9 191 Stairwell #3 - 1st floor Yellow Wall Plaster Intact >9.9 193 Stairwell #3 - 1st floor Yellow Wall Plaster Intact >9.9 194 Stairwell #3 - 1st floor Black Newel post Metal Intact 7.7 195 Stairwell #3 - 1st floor Black Hand rail Metal Intact 2.2 196 Stairwell #3 - 1st floor Black Stringer Metal Intact 0.8 197 Stairwell #3 - 1st floor Black Stair riser Metal Intact 0.8 200 Stairwell #3 - 1st floor Red Door casing Metal Intact 1.3 201 Exterior White Door casing Wood Intact 6.4 205 Exterior Black Hand rail Metal Not intact 0.8 209 Exterior White Window casing Wood Not intact >9.9 211 Exterior White Grate Metal Not intact 4.6

Building 15

005 Entrance lobby White Wall Plaster Intact >9.9 016 Main corridor White Wall Brick Intact 3.4 019 Copy room White Wall Brick Intact 3.9 026 Women's room White Window casing Wood Intact >9.9 027 Women's room White Window sill Wood Intact 5.1 028 Women's room White Window sash Wood Intact 6.4 029 Women's room White Wall Brick Intact 0.8 031 Women's room White Sink Porcelain Intact >9.9 041 NY meeting room 8 Brown Window sash Wood Not intact >9.9

Community relations department 9 Tan Wall Brick Intact 1.7

Community relations department 9 Tan Wall Brick Intact 2.0

Community relations department 9 Off-whtie Window sash Wood Intact 3.1 051 Resource room White Wall Brick Intact 0.8

TBL II-11

VA PERRY POINT

NOVEMBER 2013

Sample # Location Color Component Substrate Condition Result

(mg/cm2)

055 Courtney & Ben's offices White Wall Brick Intact 0.8 057 Courtney & Ben's offices White Window sash Metal Intact 4.8 061 Chesapeake room II White Window sash Metal Intact >9.9 069 Room 15 storage Green Wall Brick Intact 0.8 078 Room 26 White Sink Porcelain Intact 3.1 093 Room 23 White Wall CMU Intact 0.8 120 Room 38 White Wall Brick Intact 0.8 126 Exterior Tan Support pole Metal Intact 0.8 130 Exterior Tan Window sash Metal Not intact 0.8 132 Exterior Black Hand rail Metal Intact 0.8 133 Exterior Tan I-beam Steel Not intact 4.6 135 Exterior Tan Support strip Metal Intact 5.8 138 Exterior White Pipe Metal Intact 0.8 139 Exterior Tan Window sash Metal Intact 2.1 141 Exterior White Wall Metal Intact >9.9 143 Exterior White Conduit pipe Metal Intact 0.8

146 Exterior Tan Structural beam Metal Not intact 3.9 150 Exterior Tan Door Wood Not intact >9.9 151 Exterior Tan Door frame Wood Not intact 5.6 154 Exterior Tan Window sash Metal Intact 1.1 156 Exterior Black Hand rail Metal Intact 0.8 158 Exterior Tan Window frame Wood Not intact >9.9 159 Exterior Tan Window sash Metal Not intact >9.9

Building 15H

009 1st floor - main entrance Tan Door casing Metal Intact >9.9 010 1st floor - main entrance Off-white Ceiling Plaster Intact >9.9

1st floor - corridor outside

Room 102 Tan Door casing Metal Intact >9.9

1st floor - hall outside

Room 104 White Wall Plaster Intact 8.3

1st floor - hall outside

Room 104 White Ceiling Plaster Intact >9.9 031 1st floor - Room 102 Yellow Wall Plaster Intact >9.9 032 1st floor - Room 102 White Ceiling Plaster Intact >9.9 034 1st floor - Room 102 Tan Door transom Wood Intact >9.9 037 1st floor - Room 102 White Sink Porcelain Intact 1.4 038 1st floor - Room 102 White Wall Ceramic Intact 6.0 046 Stairwell #1 White Wall Plaster Intact >9.9 048 Stairwell #1 Tan Door casing Metal Intact >9.9

1st floor - Room south of

103A Black Door casing Metal Intact 0.8 069 1st floor - Room 106 White Wall Plaster Intact >9.9 070 1st floor - Room 106 White Wall Plaster Intact >9.9 073 1st floor - Room 106 White Sink Porcelain Intact 0.8 074 1st floor - Room 106 White Urinal Porcelain Intact 6.1 079 1st floor - Room 106 Tan Door casing Metal Intact >9.9 095 2nd floor - Room 202 Yellow Door casing Metal Intact >9.9 096 2nd floor - Room 202 White Ceiling Plaster Intact >9.9 101 2nd floor - Room 215 White Sink Porcelain…

This is the start of the file's text. The full file is on GovTribe.