This solicitation requests proposals for a construction project to renovate and expand a 47-bed domiciliary pod at a Department of Veterans Affairs medical center. The project includes complete renovation of an existing 17,600 square foot single story unit, replacement of the HVAC system, addition of 5,000 square feet of new construction, and upgrades to finishes and systems to current standards of care. Competition is restricted to verified Service Disabled Veteran Owned Small Businesses. Interested parties must attend the pre-bid site visit on the confirmed date and submit any questions in writing. The estimated construction cost ranges from $5-10 million. Proposals are due on October 13, 2021 and award will be made to the responsive, responsible bidder with the lowest price, subject to funding availability.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2016-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 12/28/21
ARP
OVERVIEW
The nLight Relay Panel family delivers cost-effective 0-10V dimming and switching for your building design needs. The panel communicates with an nLight network and supports up to 128 digital devices per nLight control zone. Offering a full range of panel sizes, the nLight Relay Panel is ideal for spaces that require full circuit control, with the optional flexibility of configuring single pole relays into a two or three-pole relays in the field.
Also included on each panel is a programmable input that can be connected to a photocell, for example, and a separate dry contact “alarm” input that overrides all relays until the contact is released.
nLIGHT OPERATION The nLight Relay Panel is nLight-enabled, meaning it has the ability to communicate over an nLight network. When daisy-chain wired with other nLight-enabled sensors, power packs, or WallPods™ using CAT-5e cabling, an nLight control zone is created. Connecting the panel to an nLight network backbone and nLight® ECLYPSE™ system controller enables time-based control, remote programming and monitoring from SensorView™ software, and BMS integration capabilities.
The digital time clock (DTC) option allows for on-screen configuration and control of connected devices, while introducing scheduling to standalone panel. When connected to nLight backbone and nLight ECLYPSE system controllers the panels relinquish all time clock functionality.
FEATURES
• Communicates with an nLight network
• Up to 128 digital devices per nLight control zone - each nLight Relay Panel utilizes 9 device addresses per 8 relays/dimming outputs:
• 1 address per relay/dimming output
• 1 address for the programmable input
• All relays include local manual override lever
• All relays are individually programmable
• One 0-10V dimming output per relay
• Create and control up to 32 schedules — Normal & Holiday (DTC version)
• Astronomical Timeclock feature enables +/- Sunset or Sunrise settings and programmable Latitude/
Longitude (DTC version)
• Programmable “dry contact/pull high” input (with provided 24VDC source)
• Input is programmable to preset/profile scene, photosensor signal, wallpod toggle (maintain or momentary)
• Contact input for “alarm” override (requires maintain contact signal)
• All relays communicate with switch/occupancy/photocell channel 1 out of the box (programmable through SensorView)
• FCR type relays capable of being field configured to 2 and 3-pole relay configurations with included hardware:
• 4/8 Relay Panel: 2x2-Pole and 1x3-Pole Hardware Included
• 12/16 Relay Panel: 4x2-Pole and 2x3-Pole Hardware Included
• 24/32/48 Relay Panel: 6x2-Pole and 3x3-Pole Hardware Included
• Supplies auxiliary 24VDC power and nLight network bus power (40mA per RJ45 port)
• Removable back plate for ease of installation
• UL 924 panel listing for Switching Emergency Circuits
• Optional field installed voltage barrier(s) for normal/emergency use, or mixed voltage use
• Remotely Configurable/Upgradeable
Relay Panel
Catalog Number: Date: Project:
Buy American This product is assembled in the USA and meets the Buy America(n) government procurement requirements under FARS, DFARS and DOT. Please refer to www.acuitybrands.com/resources/ buy-american for additional information.
Warranty Five-year limited warranty. Complete warranty terms located at:
www.acuitybrands.com/support/warranty/terms-and-conditions Note: Actual performance may differ as a result of end-user environment and application.
Specifications subject to change without notice.
http://www.acuitycontrols.com http://www.acuitybrands.com/resources/ buy-american http://www.acuitybrands.com/support/warranty/terms-and-conditions
ARP
nLight RELAY PANEL Example: ARP INTENC08 NLT 8FCR MVOLT SC SM
Panel Size Relay Quantity
ARP INTENC08 NLT 8-Relay Enclosure ARP INTENC16 NLT 16-Relay Enclosure ARP INTENC32 NLT 32-Relay Enclosure ARP INTENC48 NLT 48-Relay Enclosure
4SPR1 4-Single Pole Relays 8SPR1 8-Single Pole Relays 12SPR2 12-Single Pole Relays 16SPR2 16-Single Pole Relays 24SPR3 24-Single Pole Relays
32SPR3 32-Single Pole Relays 48SPR4 48-Single Pole Relays 4FCR1 4-Field Configurable Relays 8FCR1 8-Field Configurable Relays 12FCR2 12-Field Configurable Relays
16FCR2 16-Field Configurable Relays 24FCR3 24-Field Configurable Relays 32FCR3 32-Field Configurable Relays 48FCR4 48-Field Configurable Relays
Operating Voltage Voltage Barrier Door Type Mounting Clock Option
MVOLT 120-277VAC
CNDV5 120-277, 347VAC
[blank] No barriers 1VB 1 Voltage Barrier 2VB 2 Voltage Barriers 3VB6 3 Voltage Barriers 4VB6 4 Voltage Barriers
SC Screw Cover HLK7 Hinge Locking
SM7 Surface Mount FM Flush Mount
[blank] No Clock DTC Digital Time Clock
Photosensor Accessories: Order as separate catalog number.
Series Description Recommended Application
ARPA PC Simple switching (at ~1-3fc) with mechanically adjustable slide Outdoor dusk to dawn, On/Off only ARPA APS OL Analog sensor (0-100FC) with switching/dimming thresholds remotely adjustable (via SensorView) Outdoor dusk to dawn lighting, On/Off or On/Off/Dimming (where necessary)
PCELL 3WI ZT Analog sensor (0-100FC) with switching/dimming thresholds remotely adjustable (via SensorView)
Indoor On/Off or On/Off/Dimming Applications
Additional Accessories: Order as separate catalog number.
Series Description
ARP FCR CONFIG HARDWARE BAG Extra set of hardware to create 2 and 3-pole relays in the field (2x 2-pole relays, 1x 3-pole relay) ARPA FCR40 Replacement FCR40 Relay ARP BARRIER REPLACEMENT KIT Additional voltage barrier for 4/8/12/16 relay panels ARP32-48 VOLTAGE BARRIER Additional voltage barrier for 24/32/48 relay panels
ORDERING INFORMATION
NOTE: If desired, panel enclosure and interior components can be ordered separately (typically for panel enclosure rough-in prior to final wiring and system programming).
Contact your Acuity representative for ordering tree information.
NOTE: For additional photosensor information, see spec sheet: PCELL Spec Sheet.
1. Only available in 8-Relay Enclosure.
2. Only available in 16-Relay Enclosure.
3. Only available in 32-Relay Enclosure.
4. Only available in 48-Relay Enclosure.
5. Only available with xFCR Relay Option.
6. Only available in 32 or 48-Relay Enclosure Options.
7. 32/48 Enclosures only available in hinge locking surface mount.
http://www.acuitycontrols.com http://www.acuitybrands.com/products/detail/336748/Lighting-Controls-and-Design/Indoor-Digital-Photosensor/Indoor-Digital-Photosensor/-/media/products/Lighting_Controls_and_Design/336748/document/GR2400-Indoor-Photosensor_pdf.pdf
ARP
A A
B B
C C
D D
E E
F F
G G
H H
SHEET 1 OF 1
DRAWN
CHECKED
QA
MFG
APPROVED
CNO01 1/3/2018
DWG NO
STR_1
TITLE
SIZE
E
SCALE
REV
A A
B B
C C
D D
E E
F F
G G
H H
SHEET 1 OF 1
DRAWN
CHECKED
QA
MFG
APPROVED
CNO01 1/3/2018
DWG NO
STR_1
TITLE
SIZE
E
SCALE
REV
A A
B B
C C
D D
E E
F F
G G
H H
SHEET 1 OF 1
DRAWN
CHECKED
QA
MFG
APPROVED
CNO01 1/3/2018
DWG NO
STR_2
TITLE
SIZE
E
SCALE
REV
A A
B B
C C
D D
E E
F F
G G
H H
SHEET 1 OF 1
DRAWN
CHECKED
QA
MFG
APPROVED
CNO01 1/3/2018
DWG NO
STR_2
TITLE
SIZE
E
SCALE
REV
WIRING - SINGLE-POLE
Dead-Front removed Shown with optional Circuit Separation Barrier
8-Relay Enclosure
16-Relay Enclosure
32-Relay Enclosure
48-Relay Enclosure
O N
LOAD
LINE
RE
LA
Y
O N
LOAD
LINE
RE
LA
Y
O N
LOAD
LINE
RE
LA
Y
O N
LOAD
LINE
RE
LA
Y
O N
LOAD
LINE
RE
LA
Y
O N
LOAD
LINE
RE
LA
Y
O N
LOAD
LINE
RE
LA
Y
O N
LOAD
LINE
RE
LA
Y
G R
O U
N D
L U
G
HOT
NEUT
GND
JU
M P
E R
S
F
O
F
IE
L D
-C O
N F
IG
U
R A
B L
E
E L
A Y
S
0-
V D
IM
M
IN
G
O U
TP
U
TS
1-
OUTPUT
TEST
STATUS
RELAY DRIVER CARD
nLight INTERFACE CARD
8-RELAY PANEL ENCLOSURE SHOWN
OVERRIDE
INPUT
SENSOR
INPUT
BREAKER PANEL
NEUTRAL BUS BAR
CIRCUIT BREAKERS
TO LOADS
LINE IN
TO LOAD
LINE IN
TO LOAD
HIGH VOLTAGE
SIDE
LOW VOLTAGE
SIDE
LOW/HIGH
VOLTAGE
BARRIER
OPTIONAL ADD-IN BARRIERS FOR
SEPARATION OF CIRCUITS WHEN
REQUIRED
WHEN MORE THAN ONE OPTIONAL BARRIER
IS USED, FIELD-PERFORMED PUNCHOUTS
CAN BE ADDED TO THE ENCLOSURE
TO ACCESS COMPARTMENT MIDWAY WITHIN
THE RELAY STACK.
SEE HIGH VOLTAGE AREA PUNCH-OUT
DIAGRAM FOR NOTES ON PUNCH OUT
POSITIONING
CAT5 cable to digital nLight devices (e.g.
nPODM wallpods, NCM Sensors) - 40mA of bus power available per port.
ARP
LOAD (a)
FIXTURE TYPE A1
(see plans for qty)
PS50 POWER SUPPLY
RJ45 RJ45
R
EL
AY
D
R
IV
ER
C
AR
D nLIGHT INTERFACE CARD
D
IM
M
IN
G O
U
TP
U
TS
- 8 0-
V
PHOTOCELL
INPUT
UL 924
EMERGENCY
INPUT
STATUS
SCODE
NEUT
HOT
GND
NEUT TO BREAKER PANEL
ARP NLT 8FCR
w/ 2-POLE SCENARIO
8 RELAY ENCLOSURE SHOWN
0-10VDC OUTPUT TERMINAL
BLOCKS #1 - 8
LABEL CLIP
ONE JUMPER BINDS THE TWO
ADJOINING RELAYS AS A
TWO POLE UNIT
BRIDGING CLIP
REQUIRED TO INTERLOCK
SWITCH TOGGLE MECHANISM
HOT
2-
PO
LE
R
EL
AY
R
EL
AY
R
EL
AY
R
EL
AY LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
R
EL
AY
R
EL
AY
R
EL
AY
LOAD (b)
FIXTURE TYPE A1
(see plans for qty)
LOAD (c)
FIXTURE TYPE A1
(see plans for qty)
LOAD (d)
PARKING LOT
(see plans for qty)
HOT B TO BREAKER PANEL
HOT A
LOAD (a)
FIXTURE TYPE A1
(see plans for qty)
PS50 POWER SUPPLY
RJ45 RJ45
R
EL
AY
D
R
IV
ER
C
AR
D nLIGHT INTERFACE CARD
D
IM
M
IN
G O
U
TP
U
TS
- 8 0-
V
PHOTOCELL
INPUT
UL 924
EMERGENCY
INPUT
STATUS
SCODE
NEUT
HOT
GND
NEUT TO BREAKER PANEL
ARP NLT 8FCR
w/ 3-POLE SCENARIO
8 RELAY ENCLOSURE SHOWN
0-10VDC OUTPUT TERMINAL
BLOCKS #1 - 8
+TWO ADJACENT JUMPERS BIND
THE THREE ADJOINING RELAYS
AS A THREE POLE UNIT
BRIDGING CLIP
REQUIRED TO INTERLOCK
SWITCH TOGGLE MECHANISM
HOT
3-
PO
LE
R
EL
AY
R
EL
AY
R
EL
AY
R
EL
AY LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
R
EL
AY
R
EL
AY
LOAD (b)
FIXTURE TYPE A1
(see plans for qty)
LOAD (c)
FIXTURE TYPE A1
(see plans for qty)
LOAD (d)
PARKING LOT
(see plans for qty)
HOT C
TO BREAKER PANELHOT B
HOT A
LABEL CLIP
ARP
ENCLOSURE DIMENSIONS
Note: Enclosure is NEMA 1 rated 8-Relay Enclosure
• BACKBOX ONLY: 14.25”H x 14.25”W x 4.00”D
• SURFACE MOUNT SCREW COVER (standard offering): 14.41”H x 14.41”W x 4.05”D
• FLUSH MOUNT SCREW COVER: 15.65”H x
15.65”W x 4.05”D (IN-WALL DEPTH: 4.0”)
16 Relay Enclosure
• BACKBOX ONLY: 22.25”H x 14.25”W x 4.00”D
• SURFACE MOUNT SCREW COVER (standard offering): 22.45”H x 14.45”W x 4.06”D
• FLUSH MOUNT SCREW COVER: 23.65”H x
15.65”W x 4.06”D (IN-WALL DEPTH: 4.0”)
32 Relay Enclosure
• BACKBOX ONLY: 32.10”H x 20.13”W x 6.00”D
• SURFACE MOUNT HINGED DOOR w/ KEYLOCK:
32.10”H x 20.13”W x 6.68”D
48 Relay Enclosure
• BACKBOX ONLY: 40.10”H x 20.13”W x 6.00”D
• SURFACE MOUNT HINGED DOOR w/ KEYLOCK:
40.10”H x 20.13”W x 6.68”D
Patent
• 10,129,950
• 9,691,578
• 9,368,306
RELAYS
“FCR” Type Relays - Field Configurable for 2-Pole and 3-Pole Relays
• Magnetic/Standard Ballast:
• 40A @ 120-347VAC (Single-pole)
• 40A @ 480VAC (Multi-pole)
• Electronic Ballast:
• 16A @ 120-347VAC
• Tungsten:
• 20A @ 120-277VAC
• Horsepower Ratings:
• 2HP @ 120VAC
• 3HP @ 240-277VAC
• DC:
• 20A @ 48VDC
• SCCR:
• 65kA @ 277/480VAC with:
Screw Cover (SC) option for 8 & 16 relay enclosure Hinge Locking (HLK) option for 32 & 48 relay enclosure
• 14kA @ 277/480VAC with:
Hinge Locking (HLK) option for 8 & 16 relay enclosure
“SPR” Type Relays
• Magnetic/Standard Ballast:
• 20A @ 120-277VAC
• Electronic Ballast:
• 16A @ 120-277VAC
• Tungsten:
• 5000W @ 250VAC
• Horsepower Ratings:
• 2HP @ 120VAC
• DC:
• 20A @ 48VDC
• SCCR:
• 5kA @ 277VAC
NLIGHT ADDRESSES PER PANEL
• (9) ARP04/08
• (8) Relays/Dimming Outputs
• (1) Programmable Input
• (18) ARP12/16
• (16) Relays/Dimming Outputs
• (2) Programmable Inputs
• (36) ARP24/32
• (32) Relays/Dimming Outputs
• (4) Programmable Inputs
• (54) ARP48
• (48) Relays/Dimming Outputs
• (6) Programmable Inputs
INPUTS (1 PER 8 RELAYS)
• (1) Programmable Input for contact closure or photosensor signal (see photosensor accessories above)
• (1) Override input (requires maintained signal)
• 24VDC/200mA auxiliary power available (per 8 relays)
• Connectors accept 16 to 24 AWG wire
OUTPUTS
• 0-10V Capable of Class 1 or Class 2 Wiring
• 100mA Sink Per Dimming Output
• Note:
• Low trim default 1V, adjustable down to 0.7V
• High trim default 10V, 10V max
• Off mode: < 0.7V
• Connectors accept 16 to 24 AWG wire
POWER SUPPLY INPUTS
• 120-277VAC
• 347VAC Option
• 50/60 Hz
• Max 0.5 Amps for 8/16 relay enclosure
• Max 1.0 Amp for 32/48 relay enclosure
PROGRAMMING
• Via SensorView Software
ENVIRONMENT
• Ambient, 8 & 16 relay enclosure: 32-122F
(0-50C)
• Ambient, 32 & 48 relay enclosure: 32-113F
(0-45C)
• Relative Humidity: 90% non-condensing
STANDARDS
• UL and cUL 916 listed
• UL 924 listed (for emergency circuit use)
• UL 2043 (Plenum) Rated for Surface Mount Screw cover “SC SM” option (8 & 16 relay enclosure only)
BUS CONNECTOR
• (2) RJ45 connectors
• 40mA Bus Power per RJ45 (80mA total)
SPECIFICATIONS
http://www.acuitycontrols.com
| Text Field 2: |
| Text Field 3: |
| Text Field 6: |
| Text Field 8: |
| Text Field 9: |
| Text Field 10: |
| Text Field 16: |
| Text Field 17: |
| Text Field 18: |
| Text Field 19: |
| Text Field 20: |
| Text Field 21: |
File details come from the government source that posted it. Updated .