36C24419R0047-063.pdf

PDF 10 MB Posted

Attached to
503-314 Expand for Specialty Clinic on 3rd Floor
Solicitation number
36C24419R0047
Issued by

About this file

36C24419R0047 503-314 Expand for Specialty Care on 3rd Floor Drawings_Part5.pdf

View the file

Other files

File Type Posted
36C24419R0047-0003000.docx DOCX document
36C24419R0047-0002000.docx DOCX document
36C24419R0047-0001001.pdf PDF
36C24419R0047-0001000.docx DOCX document
36C24419R0047-047.pdf PDF
36C24419R0047-056.pdf PDF
36C24419R0047-051.pdf PDF
36C24419R0047-055.pdf PDF
36C24419R0047-066.docx DOCX document
36C24419R0047-059.pdf PDF
36C24419R0047-069.docx DOCX document
36C24419R0047-048.pdf PDF
36C24419R0047-049.pdf PDF
36C24419R0047-053.pdf PDF
36C24419R0047-067.docx DOCX document
36C24419R0047-064.pdf PDF
36C24419R0047-065.docx DOCX document
36C24419R0047-068.docx DOCX document
36C24419R0047-045.docx DOCX document
36C24419R0047-050.pdf PDF
36C24419R0047-058.pdf PDF
36C24419R0047-061.pdf PDF
36C24419R0047-062.pdf PDF
36C24419R0047-057.docx DOCX document
36C24419R0047-060.pdf PDF
36C24419R0047-070.docx DOCX document
36C24419R0047-046.pdf PDF
36C24419R0047-052.pdf PDF
36C24419R0047-054.pdf PDF
36C24419R0047-030.docx DOCX document
36C24419R0047-000.docx DOCX document
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

GFI

GFI

ELECTRICAL LEGEND

PANELBOARD RECESSED IN WALL.

PANELBOARD SURFACE MOUNTED ON WALL.

MOTOR SWITCH WITH THERMAL OVERLOAD

MAGNETIC MOTOR CONTROLLER/STARTER

JJJ

PULL BOXP

M

F

CONDUIT BELOW SLAB

DUPLEX RE CEPTACLE - 2P, 3W, 20A, 125V,

NEMA 5-20R IN SURFACE OUTLET BOX,

SURFACE MOUNTED, 18" A.F.F., U.O.N.

HOMERUN TO PANELBOARD -

ARROWS INDICATE NUMBER OF

CIRCUITS SLASHES INDICATE CIRCUIT

CONDUCTORS NO SLASH INDICATES

TWO CIRCUIT CONDUCTORS PROVIDE

GROUNDING CONDUCTOR, NOT

SHOWN. PROVIDE SEPARATE

NEUTRAL FOR EACH CIRCUIT.

PHASE

CONDUCTOR

DUPLEX RECEPTACLE, NEMA 5-20R,

20A HOSPITAL GRADE, WALL

MOUNTED 18" AFF. IN RECESSED

OUTLET BOX. U.O.N. (GFI = GROUND

FAULT, HOSPITAL GRADE

RECEPTACLE)

QUADRUPLEX RECEPTACLE, NEMA

5-20R, 20A, HOSPITAL GRADE, WALL

MOUNTED 18" AFF. IN RECESSED

OUTLET BOX. U.O.N. (GFI = GROUND

FAULT, HOSPITAL GRADE

DUPLEX RECEPTACLE, MOUNTED 6"

ABOVE COUNTERTOP BACK SPLASH

UNLESS OTHERWISE NOTED

QUADRUPLEX RECEPTACLE, MOUNTED

6" ABOVE COUNTERTOP BACK SPLASH

UNLESS OTHERWISE NOTED

SPECIAL USE RECEPTACLE. REFER TO

PANEL SCHEDULE FOR AMPERAGE AND

VOLTAGE.

JUNCTION BOX: CEILING, WALL OR

FLUSH-FLOOR MOUNTED

FUSED DISCONNECT SWITCH, UPPER

NUMERAL INDICATES SWITCH SIZE,

LOWER NUMERAL INDICATES FUSE SIZE

NONFUSED DISCONNECT SWITCH,

NUMERAL INDICATES SIZE

VFD

SPECIAL RECEPTACLE WALL MOUNTED

18" A.F.F. COORDINATE CORD PLUG

WITH MANUFACTURER

DUPLEX RECEPTACLE - 2P, 3W, 2OA, 125V,

NEMA 5-2OR IN FLUSH MOUNTED FLOOR

OUTLET BOX

ELECTRICAL MOTOR

COMBINATION MAGNETIC MOTOR

STARTER WITH MCP OR FUSIBLE

DISCONNECT SWITCH

NURSE CALL DOME LIGHT, CEILING OR

WALL MOUNTED

NURSE CALL SYSTEM WITH PULL CORD

VARIABLE FREQUENCY DRIVE

NURSE CALL CODE BLUEB

J

J

J

J J

J

J

J J

J

J

J

J J J J J J J J

J

JJ

J

J

J

J

J

J

J

J

J

J

J

J

J

J J

J

J J

J

J

JJ

J

JJJJ JJ J J J

J

J

J

J J

J

J

J

J

J

J

J J

J J

DA E F G H JH.1 KC

B

A346

A341

A344

A343A342

A339

A335

A334

A340

A332 A333

A331

A350

A327

A328

A319

A325

A324A323

A322

A301B

A320

A348

A349

A326

ST1

EL1

A308 A309

A313

A318

A311

A307

A300

A301

A300A

GFCI

GFCI

GFCI

GFCI

PANEL

EQP3B

PANEL

EQP3C

PANEL

MEPC

A314

A329

A303

A301A

A310

A317A

A336

A321

A330

A338

A304

ST2

GFCI GFCI

GFCI

GFCI

GFCI

GFCI

GFCI GFCI

GFCI

GFCI

GFCI GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI GFCI

GFCI GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI GFCI

GFCI

GFCI GFCI

GFCI

GFCI

6(EQP3C)

7(EQP3C)

8 9

WP

WP

WP

WP

1,3,5(EQP3B) 2,4,6(EQP3B)

7 77

9(EQP3B)

10(EQP3B)

10 10

12(EQP3B)

11(EQP3B)8(EQP3B)

8(EQP3B)

13(EQP3B)

15(EQP3B)

15 15

14(EQP3B)

14 14 14

16(EQP3B)

17(EQP3B)

17(EQP3B)

20(EQP3B)

19(EQP3B) 19(EQP3B)

19(EQP3B)

19(EQP3B)

21(EQP3B)

21(EQP3B)

21(EQP3B) 21(EQP3B)

21(EQP3B)

22(EQP3B)

22(EQP3B)

23(EQP3B)

25(EQP3B)

24(EQP3B)

26(EQP3B)

26 26

28(EQP3B)

27(EQP3B)

27(EQP3B)

29(EQP3B)

31(EQP3B)

33(EQP3B)

32(EQP3B)

34(EQP3B)

34(EQP3B) 34(EQP3B)

34(EQP3B)

34(EQP3B)

35(EQP3B)

35 35

36(EQP3B)

37(EQP3B)

41(EQP3B)

43(EQP3B)

45(EQP3B)

47(EQP3B)

51(EQP3B)

53(EQP3B)

10,12,14(EQP3C)

16(EQP3C)

17(EQP3C)

21(EQP3C)

21(EQP3C)

21(EQP3C)

16(EQP3C)

21(EQP3C)

23,25(EQP3C)

27(EQP3C)

28(EQP3C)

36(EQP3C)

41(EQP3C)

55(EQP3B)

57(EQP3B)

59(EQP3B)

42(EQP3C)

42(EQP3C) 42(EQP3C)

45(EQP3C)

44,46(EQP3C)

47,49(EQP3C)

48(EQP3C)

484848

51(EQP3C)

36(EQP3C)

36(EQP3C)

50(EQP3C)

50(EQP3C)

50(EQP3C)

50(EQP3C) 50(EQP3C)

53(EQP3C)

53(EQP3C)

53(EQP3C)

GFCI

WP

GFCI

WP

GFCI

WP52(EQP3C)

52(EQP3C)

53(EQP3C)

A337

A312

A315

A316

A317

A347

A301C

11,13,15(EQP3C)

A306

GFCI

73(EQP3C)

GFCI

40(EQP3C)

GFCI

30(EQP3C)

GFCI

32(EQP3C)

43(EQP3C)

GFCI

39(EQP3C)

43(EQP3C)

43 43

43(EQP3C)

36(EQP3C)

36(EQP3C)

GFCI

GFCI

54(EQP3C)56(EQP3C)

58(EQP3C)

GFCI

60(EQP3C)

61(EQP3C)

55,57,59(EQP3C)

63(EQP3C)

62(EQP3C)

GFCI

48(EQP3C)

GFCI

GFCI

26(EQP3C)

24(EQP3C)

18(EQP3C)

24(EQP3C)

GFCI

29(EQP3C)

7(EQP3B)

11(EQP3B)

58(EQP3B)

58 58

18(EQP3B)

30(EQP3B)

36(EQP3C)

17 60(EQP3B)

14 15 14 15 14 15 14 15

62(EQP3B)

64(EQP3B)

14 14

42(EQP3C)

42(EQP3C)

64,66(EQP3C)

FCU-1

67,69(EQP3C)

GFCI

70(EQP3C)

GFCI

70(EQP3C)

GFCI

GFCI

61(EQP3B)

GFCI GFCI

68(EQP3C) 68(EQP3C)

GFCI

68(EQP3C)

17 GFCI

68(EQP3C)

GFCI GFCI

68(EQP3C)

GFCI 17

68(EQP3C)

GFCI 68(EQP3C)

68(EQP3C)

GFCI

GFCI

GFCI GFCI

61(EQP3B)

61(EQP3B)

61(EQP3B)

70(EQP3C)

70(EQP3C)

19(EQP3C)

34(EQP3C)

68(EQP3B)

52(EQP3C)52(EQP3C) 15

68(EQP3B)

66(EQP3B)

70(EQP3B)

71(EQP3C)

16(EQP3C)

21(EQP3C)

20(EQP3C)

20 21

PT-ACC-2 5

49(EQP3B)

22(EQP3C)

72(EQP3C)

50(EQP3C)

38(EQP3C)

74(EQP3C)

63(EQP3B)

65(EQP3B)

67(EQP3B)

65(EQP3C)

AC-6 3

M

75(EQP3C)

PT-FPP-5

M

77(EQP3C)

PT-FPP-6

FCU-2

PT-ACC-1 11

AHU-13

AHU-14

AC-7

B

B

B

B B

B B

B B

B

BB

B

BB

B B

B

B

69(EQP3B)

69(EQP3B)

69(EQP3B)

69(EQP3B)

B

B

B

B

B B

B

B

A345

78(EQP3C)

78(EQP3C)

78(EQP3C)

71(EQP3B)

73(EQP3B)

39(EQP3B)

77(EQP3B)

2775(EQP3B)

79(EQP3C)

81(EQP3C)

83(EQP3C)

DRAWING NOTES:

PROVIDE WALL MOUNTED JUNCTION BOX FOR POWER CONNECTION TO SYSTEM

FURNITURE. COORDINATE EXACT LOCATION IN THE FIELD AND ALL REQUIRED

ACCESSORIES WITH SYSTEM FURNITURE MANUFACTURER FOR A COMPLETE

SYSTEM INSTALLATION.

8" MULTI-SERVICE POKE-THRU DEVICES EQUAL TO LEGRAND 8AT SERIES FOR

CONNECTION TO MOTORIZED CHAIR. COORDINATE LOCATION IN THE FIELD.

PROVIDE 30A, 2P NFSS FOR CONNECTION TO EQUIPMENT. EXTEND 2 #12, 1 #12 GW

IN 3/4" CONDUIT TO OUTDOOR UNIT (ROOF).

FOR CONNECTION TO PROJECTION SCREEN. PROVIDE CONNECTION TO UP AND

DOWN CONTROL SWITCH IN CONDUIT AS REQUIRED. COORDINATE LOCATION OF

SWITCH IN THE FIELD WITH VA COR.

REFER TO POWER RISER DIAGRAM NEW WORK DRAWING FOR MECHANICAL

EQUIPMENT CONNECTION INFORMATION.

PROVIDE CONNECTION TO AHU RECEPTACLE CIRCUIT.

SEE DRAWING 1-3-E1 FOR CONNECTION TO AHU LIGHTING.

PROVIDE 30A, 3P NFSS IN NEMA 3R ENCLOSURE FOR CONNECTION TO RETURN FAN.

SEE GENERAL NOTE 3. REFER TO POWER RISER DIAGRAM NEW WORK DRAWING

FOR ADDITIONAL MECHANICAL EQUIPMENT CONNECTION INFORMATION.

PROVIDE 30A, 3P NFSS IN NEMA 3R ENCLOSURE FOR CONNECTION TO SUPPLY FAN.

SEE GENERAL NOTE 3. REFER TO POWER RISER DIAGRAM NEW WORK DRAWING

FOR ADDITIONAL MECHANICAL EQUIPMENT CONNECTION INFORMATION.

8" MULTI-SERVICE POKE-THRU DEVICES EQUAL TO LEGRAND 8AT SERIES.

EXISTING MECHANICAL EQUIPMENT.

FOR CONNECTION TO ELECTRONIC BOARD.

FOR CONNECTION TO DOOR POWER SUPPLY CONTROL PANEL AND WIRELESS CARD

READER CONTROLLER. COORDINATE FINAL LOCATION WITH EQUIPMENT IN THE

FIELD.

PROVIDE POWER CONNECTION TO MOTORIZED WINDOW SHADE. COORDINATE

LOCATION IN THE FIELD. WINDOW SHADE SHALL BE CONNECTED TO BAS SYSTEM

FOR CONTROLS. COORDINATE WITH MECHANICAL CONTRACTOR FOR CONNECTION.

IQ2 DUAL SPLITTER (FURNISHED BY SHADE MANUFACTURER & INSTALLED BY

CONTRACTOR) LOCATED ABOVE ACCESSIBLE FINSIHED CEILING. PROVIDE LOW

VOLTAGE WIRING IN CONDUIT FROM SPLITTER TO CONTROL SWITCH STATION AND

FROM SPLITTER TO SPLITTER. COORDINATE TYPE WITH MOTORIZED SHADE

MANUFACTURER.

MOTORIZED SHADE CONTROL SWITCH SINGLE STATION. COORDINATE EXACT

LOCATION WITH VA CONTRACTING OFFICERS REPRESENTATIVE (COR). PROVIDE

LOW VOLTAGE WIRING IN CONDUIT TO SPLITTER. COORDINATE TYPE WITH

MOTORIZED SHADE MANUFACTURER.

INSTALL GFCI RECEPTACLE IN RECESSED ENCLOSURE WITH HINGED COVER FOR

CONNECTION TO TOILET / FAUCET SENSOR POWER SUPPLY. PROVIDE ENCLOSURE

IN SIZE TO HOUSE RECEPTACLE & POWER SUPPLY WITHOUT OVERHEATING.

COORDINATE LOW VOLTAGE CONNECTION REQUIREMENTS WITH FAUCET SENSOR

MANUFACTURER. PAINT TO MATCH ADJACENT SURFACES.

NURSE CALL STAFF/DUTY STATION.

PROVIDE NEMA 6-20R TYPE RECEPTACLE FOR TREADMILL CONNECTION.

MOUNT TO SUIT REFRIGERATOR.

MOUNT TO SUIT TV.

FOR CONNECTION TO EXAM TABLE.

PROVIDE CONNECTION TO DOOR POWER SUPPLY AND CARD READER. COORDINATE

FINAL LOCATION WITH EQUIPMENT ON THE FIELD.

PROVIDE POWER CONNECTION TO FIRE ALARM EQUPMENT (TYPICAL OF 4).

COORDINATE LOCATION WITH FIRE ALARM CONTRACTOR. CONNECT TO EXISTING

PANEL ELS1 LOCATED ON THE FIRST FLOOR ELECTRICAL ROOM B124. REFER TO

DRAWING 1-1-E1 FOR EXACT PANEL LOCATION. SEE PANEL SCHEDULE DRAWING

1-B-3-R-E3 FOR CIRCUIT NUMBERS' INFORMATION.

MOUNT RECEPTACLE 6" BELOW CEILING FOR TEMP TRACK. COORDINATE EXACT

LOCATION WITH VA COR PRIOR TO ROUGH-IN.

FOR CONNECTION TO NURSE CALL EQUIPMENT. COORDINATE EXACT LOCATION IN

THE FIELD.

FOR CONNECTION TO PAGING AMP EQUIPMENT. COORDINATE EXACT LOCATION IN

THE FIELD.

FOR CONNECTION TO PATIENT LIFT. COORDINATE EXACT LOCATION IN THE FIELD.

GENERAL NOTES:

1.

2.

3.

4.

5.

REFER TO DRAWING 1-B-3-R-E1 FOR LEGEND, ABBREVIATIONS AND

ADDITIONAL GENERAL NOTES.

SYSTEM FURNITURE SHALL HAVE THREE RECEPTACLES PER CUBICLE. REFER

TO DETAIL ON DRAWING 1-B-3-R-E1 FOR MORE INFORMATION.

WHERE MOTORS ARE SERVED BY VARIABLE FREQUENCY DRIVES (VFD),

PROVIDE THE LOCAL SAFETY DISCONNECT SWITCH WITH ONE SET OF

NORMALLY OPEN CONTACTS THAT OPERATE SIMULTANEOUSLY WITH THE

MAIN SWITCH. WIRE CONTACTS TO OPEN THE START-STOP CIRCUIT OF THE

VFD WHEN THE DISCONNECT SWITCH AT THE MOTOR IS OPENED (TO

PREVENT THE VFD FROM DAMAGE BY HIGH INRUSH CURRENT WHEN THE

DISCONNECT SWITCH RECLOSES). PROVIDE 2#10 CONTROL WIRES IN THE

MOTOR FEEDER CONDUIT TO BE USED FOR THIS INTERLOCK.

NURSE CALL SYSTEM IS INTELLIGENT ELECTRONIC SYSTEM, INC. AND SHALL

BE FULLY COMPATIBLE WITH EXISTING NURSE CALL SYSTEM.

REFER TO DRAWING 1-1-E1 FOR PROPOSED ROUTING OF CONDUITS TO

EXISTING PANEL ELS1.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

27.

28.

Project Title

DE

PA

RT

M

EN

T

OF

VE

TE

RA

NS

A

FF

AI

RS

Drawing Title Date

Project No.

Drawing No.

Dwg. Of

Approved: Associate Director for Operations:

Approved: Director, Medical Center:

Drawn:Building No: Checked:

Location:

Additions:

Revisions:

1 5 6 7 8

21 3 4 5 6 7 8

A B

C D

E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot

JAMES E. VAN ZANDT

VETERANS ADMINISTRATION

MEDICAL CENTER

2 3 4

Consultants:Date

& ASSOCIATES, INC.

BURDETTE KOEHLER MURPHY

RICKERT ENGINEERING, INC.

BUILDING COST CONSULTANTS

COST ESTIMATING

12917 - 30TH AVENUE

PLATTSMOUTH, NEBRASKA 68048

402.298.8260 - FAX 402.298.8290

MECHANICAL / ELECTRICAL CONSULTING

ENGINEERING

6300 BLAIR HILL LANE, SUITE 400

BALTIMORE, MARYLAND 21209

410.323.0600 - FAX 410.377.2543

STRUCTURAL ENGINEERING

8813 WALTHAM WOODS ROAD, SUITE 500

BALTIMORE, MARYLAND 21234

410.663.5110 - FAX 410.663.5114

Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009

ARCHITECTURE

PLANNING

ENGINEERING

FIRE PROTECTION ENGINEERING

8815 CENTRE PARK DR., SUITE 200

COLUMBIA, MARYLAND 21045

410.750.2246 - FAX 410.750.2588

KOFFEL ASSOCIATES, INC.

WHITMAN, REQUARDT & ASSOCIATES, LLP

CIVIL ENGINEERING

801 South Caroline Street Baltimore, MD 21231

410.235.3450 - FAX: 410.243.5716

ROBERT L. SEYMOUR ASSOCIATES

AUTOMATIC TRANSPORT ENGINEERING

182 THOMOS JOHNSON DR. SUITE 200

FREDERICK, MARYLAND 21702

301.662.8112 - FAX 301.662.8117

BKM# 16106.01

DELLC

JOB No.

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

160702D

KEY PLAN

THIRD FLOOR PLAN

POWER - NEW WORK

EXPAND FOR SPECIALTY

CLINIC ADDITION ON 3RD

FLOOR

LSF RSB

VAMC Altoona, Pennsylvania

01/15/19

1-3-E3

503-314

PLAN NORTH

TRUE NORTH

THIRD FLR ROOM LIST

A300 LOBBY

A300A BRIDGE

A301 CORRIDOR

A301A CORRIDOR

A301B CORRIDOR

A301C STAFF CORRIDOR

A303 MEN'S

A304 WOMEN'S

A306 EXAM / CONSULT

A307 EXAM RESTROOM

A308 EXAM / CONSULT

A309 EXAM / CONSULT

A310 NUTRITION

A311 CARDIOVASCULAR

WORKSTATIONS/ COPY

A312 STORAGE

A313 ECHO/ CARDIO

A314 EXAM/ PATIENT EDUCATION

A315 EKG

A316 TOILET

A317 STRESS ECHO

A317A CRASH CART

A318 CORRIDOR

A319 TELECOM

A320 DIALATION

A321 WAITING

A322 PRETEST/ EYE / CHECK-IN

A323 PHOTO/ FUNDUS TEST

A324 EYE 1/ WHEELCHAIR STORAGE

A325 CONSULT/ VIEWING

A326 EYE 3

A327 OCT

A328 POLY TROMA

A329 LOW VISION

A330 WORK STATION AREA 2

A331 VISUAL FIELDS TESTING

A332 EYEGLASS FITTING & DISPLAY

A333 EQUIP.

A334 SHARED BREAK/ LKR

A335 SHARED CONFERENCE

A336 STORAGE & EQUIP

A337 WOMEN'S

A338 MEN'S

A339 HAC

A340 PULMONARY REHAB AREA/

EXTENDED PULM FUNCTION/

CONSULT. ROOM/ WAITING/

WHEELCHAIR

A341 RESPIRATORY THERAPY/ CPAP

A342 PFT

A343 TREATMENT ROOM

A344 MED

A345 O2 STOR.

A346 PULMONARY WORK STATION

A347 CRASH CART

A348 ELEC.

A349 MEN'S

A350 WOMEN'S

EL1 ELEVATORS

ST1 STAIR 1

ST2 STAIR 2

SCALE: 1/8" = 1'-0"

1 THIRD FLOOR PLAN - POWER - NEW WORK

GFI

ELECTRICAL LEGEND

LIGHTING FIXTURE: DOWNLIGHT, 2' x 4' & 2' x 2' A

LIGHTING FIXTURE ON EMERGENCY CIRCUIT

NL - NIGHT LIGHT

NL

SINGLE POLE TOGGLE SWITCH ,

MOUNTED 46" TO THE TOP OF THE

SWITCH A.F.F., U.O.N.

UPPER CASE - FIXTURE TYPE (TYPICAL

FOR ALL LIGHTING FIXTURES) - SEE

LIGHTING FIXTURE SCHEDULE

CEILING MOUNTED OCCUPANCY SENSOROS

JJJ

DUPLEX RECEPTACLE, NEMA 5-20R,

20A HOSPITAL GRADE, WALL

MOUNTED 18" AFF. IN RECESSED

OUTLET BOX. U.O.N. (GFI = GROUND

FAULT, HOSPITAL GRADE

RECEPTACLE)

QUADRUPLEX RECEPTACLE, NEMA

5-20R, 20A, HOSPITAL GRADE, WALL

MOUNTED 18" AFF. IN RECESSED

OUTLET BOX. U.O.N. (GFI = GROUND

FAULT, HOSPITAL GRADE

JUNCTION BOX: CEILING, WALL OR

FLUSH-FLOOR MOUNTED

J

EXISTING 2' x 4' LIGHTING FIXTURE TO BE

REMOVED

EXISTING NURSE CALL DOME LIGHT TO

BE REMOVED

EXISTING NURSE CALL DOME LIGHT TO

REMAIN

EXISTING JUNCTION BOX TO BE

REMOVED

EXISTING DUPLEX RECEPTACLE TO

REMAIN

EXISTING RECEPTACLE TO BE REMOVED

EXISTING QUAD RECEPTACLE TO REMAIN

J

J

J

J

B6

B7

B8

B9

B10

B12

B14

TT B-K L B-MB-H

2 2

6 6

ETRETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETRETR

ETR

ETR

ETR

TELECLOSET

335G

ELEC. CLOSET

PANEL

CBP-3E

PANEL

LP-3D (LS &

RS)

B6

B7

B8

B9

B10

B12

B14

TT B-K L B-MB-H

4 5

17 17

PANEL

CBP-3E

PANEL

LP-3D (LS &

RS) GENERAL NOTES:

DRAWING NOTES:

REMOVE EXISTING ELECTRICAL CONNECTION TO EXISTING HEADWALL.

REMOVE EXISTING ASSOCIATED WIRING AND CONDUIT BACK TO SOURCE.

ALL ELECTRICAL DEVICES IN THIS AREA ARE EXISTING TO REMAIN,

UNLESS OTHERWISE INDICATED.

CONNECT TO NEAREST EXISTING EMERGENCY LIGHTING BRANCH CIRCUIT.

ALL LIGHTING FIXTURES SHOWN IN THIS AREA ARE EXISTING RELOCATED.

CONTRACTOR SHALL REWIRE ALL NORMAL LIGHTING FIXTURES AND

CONNECT TO EXISTING NORMAL LIGHTING BRANCH CIRCUIT SERVING THIS

AREA PRIOR TO DEMOLITION. CONTROL OF THESE FIXTURES SHALL BE

TIED TO EXISTING LIGHTING IN ADJACENT CORRIDOR.

REMOVE AND RELOCATE EXISTING LIGHTING FIXTURE. EXISTING BRANCH

CIRCUIT WIRING SHALL REMAIN FOR REUSE UNDER NEW WORK PHASE.

EXISTING PREWIRED FURNITURE POWER FEED TO BE REMOVED

INCLUSIVE OF BRANCH CIRCUIT BACK TO SOURCE.

EXISTING HEADWALL (NURSE CALL DEVICES, NORMAL & EMERGENCY

RECEPTACLES, LIGHTING AND CONTROL SWITCHES, ETC.) TO BE

REMOVED & RELOCATED. DISCONNECT FROM EXISTING CONNECTIONS

AND REFER TO NEW WORK PLAN FOR NEW LOCATION AND

RECONNECTIONS.

EXISTING SWITCH TO BE REMOVED & RELOCATED. REFER TO NEW WORK

PLAN FOR NEW LOCATION.

RELOCATED EXISTING HEADWALL (SEE NOTE 8). RECONNECT TO EXISTING

BRANCH CIRCUITS, NURSE CALL, GROUNDING AND MEDICAL GASES (SEE

MECHANICAL DRAWINGS) SERVING HEADWALL PRIOR TO DEMOLITION.

RELOCATED EXISTING SWITCH.

EXISTING INDICATOR LIGHT TO BE REMOVED AND RETURNED TO VA.

PROVIDE NEW OUTLET AS INDICATED. CONNECT TO EXISTING BRANCH

CIRCUIT PREVIOUSLY SERVING THE AREA PRIOR TO DEMOLITION.

CONNECT TO EXISTING NORMAL LIGHTING BRANCH CIRCUIT PREVIOUSLY

SERVING THIS AREA PRIOR TO DEMOLITION.

PROVIDE NEW EXIT LIGHT.

ALL WORK NDICATED IN THIS AREA SHALL BE UNDER ADD ALTERNATE.

CONNECT TO EXISTING PANEL LP3D (RS) 20A, 1P SPARE BRANCH CIRCUIT

BREAKER (TYPICAL OF 6 CIRCUITS).

GENERAL NOTES:

1. REFER TO DRAWING 1-B-3-R-E1 FOR LEGEND, ABBREVIATIONS AND

ADDITIONAL GENERAL NOTES.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

Project Title

DE

PA

RT

M

EN

T

OF

VE

TE

RA

NS

A

FF

AI

RS

Drawing Title Date

Project No.

Drawing No.

Dwg. Of

Approved: Associate Director for Operations:

Approved: Director, Medical Center:

Drawn:Building No: Checked:

Location:

Additions:

Revisions:

1 5 6 7 8

21 3 4 5 6 7 8

A B

C D

E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot

JAMES E. VAN ZANDT

VETERANS ADMINISTRATION

MEDICAL CENTER

2 3 4

Consultants:Date

& ASSOCIATES, INC.

BURDETTE KOEHLER MURPHY

RICKERT ENGINEERING, INC.

BUILDING COST CONSULTANTS

COST ESTIMATING

12917 - 30TH AVENUE

PLATTSMOUTH, NEBRASKA 68048

402.298.8260 - FAX 402.298.8290

MECHANICAL / ELECTRICAL CONSULTING

ENGINEERING

6300 BLAIR HILL LANE, SUITE 400

BALTIMORE, MARYLAND 21209

410.323.0600 - FAX 410.377.2543

STRUCTURAL ENGINEERING

8813 WALTHAM WOODS ROAD, SUITE 500

BALTIMORE, MARYLAND 21234

410.663.5110 - FAX 410.663.5114

Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009

ARCHITECTURE

PLANNING

ENGINEERING

FIRE PROTECTION ENGINEERING

8815 CENTRE PARK DR., SUITE 200

COLUMBIA, MARYLAND 21045

410.750.2246 - FAX 410.750.2588

KOFFEL ASSOCIATES, INC.

WHITMAN, REQUARDT & ASSOCIATES, LLP

CIVIL ENGINEERING

801 South Caroline Street Baltimore, MD 21231

410.235.3450 - FAX: 410.243.5716

ROBERT L. SEYMOUR ASSOCIATES

AUTOMATIC TRANSPORT ENGINEERING

182 THOMOS JOHNSON DR. SUITE 200

FREDERICK, MARYLAND 21702

301.662.8112 - FAX 301.662.8117

BKM# 16106.01

DELLC

JOB No.

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

160702D

KEY PLAN

EXISTING - THIRD

FLOOR PLAN - ELECTRICAL

DEMOLITION & NEW WORK

EXPAND FOR SPECIALTY

CLINIC ADDITION ON 3RD

FLOOR

LSF RSB

VAMC Altoona, Pennsylvania

01/15/19

1-3-E5

503-314

SCALE: 1/8" = 1'-0"

1 EXISTING HOSPITAL - THIRD FLOOR PLAN - ELECTRICAL - DEMOLITION

SCALE: 1/8" = 1'-0"

2 EXISTING HOSPITAL - THIRD FLOOR PLAN - ELECTRICAL - NEW WORK

PLAN NORTH

TRUE NORTH

WP

ELECTRICAL LEGEND

MOTOR SWITCH WITH THERMAL OVERLOAD

MAGNETIC MOTOR CONTROLLER/STARTER

JJJ

M

F

CONDUIT BELOW SLAB

HOMERUN TO PANELBOARD -

ARROWS INDICATE NUMBER OF

CIRCUITS SLASHES INDICATE CIRCUIT

CONDUCTORS NO SLASH INDICATES

TWO CIRCUIT CONDUCTORS PROVIDE

GROUNDING CONDUCTOR, NOT

SHOWN. PROVIDE SEPARATE

NEUTRAL FOR EACH CIRCUIT.

PHASE

CONDUCTOR

DUPLEX RECEPTACLE, NEMA 5-20R, 20A

HOSPITAL GRADE, WALL MOUNTED 18"

AFF. IN RECESSED OUTLET BOX. U.O.N.

(GFI = GROUND FAULT, HOSPITAL

GRADE RECEPTACLE), WP =

WEATHERPROOF

SPECIAL USE RECEPTACLE. REFER TO

PANEL SCHEDULE FOR AMPERAGE AND

VOLTAGE.

JUNCTION BOX: CEILING, WALL OR

FLUSH-FLOOR MOUNTED

FUSED DISCONNECT SWITCH, UPPER

NUMERAL INDICATES SWITCH SIZE,

LOWER NUMERAL INDICATES FUSE SIZE

NONFUSED DISCONNECT SWITCH,

NUMERAL INDICATES SIZE

ELECTRICAL MOTOR

COMBINATION MAGNETIC MOTOR

STARTER WITH MCP OR FUSIBLE

DISCONNECT SWITCH

DA E F G H JH.1 KC

B

M

EF-25

M

EF-28

M M

M

EF-26

EF-27

EF-29

1(EQP3C)

2(EQP3C)

3(EQP3C)

4(EQP3C)5(EQP3C)

WP

GFCI

WP

GFCI

WP

GFCI

WP

GFCI

33333333

CU-6

31,33(EQP3C)

35,37(EQP3C)

14,16,18(MEPC)

EF-30

CU-75

6 6 6

WP

GFCI

76(EQP3C)

76(EQP3C)

76(EQP3C)

76(EQP3C)

76(EQP3C)

WP

WP

WP

WP

WP

DRAWING NOTES:

GENERAL NOTES:

1.

2.

3.

REFER TO DRAWING 1-B-3-R-E1 FOR LEGEND, ABBREVIATIONS AND ADDITIONAL

GENERAL NOTES.

REFER TO PV SINGLE LINE DIAGRAM ON DRAWING 1-B-3-R-E1 FOR ADDITIONAL

INFORMATION.

COORDINATE PV PANELS WITH SKYLIGHTS AND MECHANICAL EQUIPMENT.

1.

2.

3.

4.

5.

6.

7.

INDICATED ROOF AREA AVAILABLE FOR SOLAR ARRAYS IS APPROXIMATELY

6,000 SQUARE FEET. THIS AREA MUST ACCOMMODATE STRUCTURE, SOLAR

PANEL ARRAYS, DISCONNECT SWITCHES & INVERTERS / DC COLLECTION

UNITS. IN ADDITION, ACCESS AISLES MUST BE MAINTAINED WHICH COULD

SLIGHTLY DECREASE CALCULATED AVAILABLE SQUARE FOOTAGE. INVERTERS /

DC COLLECTION UNITS WILL ALSO BE ON ROOF AND WILL BE CONNECTED TO

NORMAL POWER SWITCHBOARD THROUGH A FEEDER BREAKER INSTALLED

WITHIN THE SWITCHBOARD. METERING WILL BE PROVIDED TO MONITOR

POWER PRODUCED FROM SOLAR ARRAYS.

PROVIDE COMBINATION STARTER NEMA SIZE 0 AND MOTOR CIRCUIT

PROTECTOR IN NEMA 3R ENCLOSURE FOR CONNECTION TO UNIT AS INDICATED.

EXTEND 3 #12 + 1 #12 GW IN 3/4" CONDUIT TO EQUIPMENT AND CIRCUIT

INDICATED.

SUB-ARRAY: 13 MODULES IN SERIES, TO DC COLLECTION UNIT. INTERCONNECT

WITH #10 AWG WIRING.

TO INDOOR UNIT AC-6 / AC-7. PROVIDE INTERCONNECTION BETWEEN INDOOR &

OUTDOOR UNIT PER EQUIPMENT MANUFACTURERS RECOMMENDATION.

PROVIDE 100A, 480/277V, 3 PHASE, 4W COMBINER BOX IN NEMA 3R ENCLOSURE

FOR CONNECTION TO INVERTERS / DC COLLECTION UNITS. PROVIDE

STRUCTURAL SUPPORTS TO RIGIDLY MOUNT ON ROOF.

INVERTER / DC COLLECTION UNIT.

PROVIDE 30A, 2P NFSS IN NEMA 3R ENCLOSURE FOR CONNECTION TO UNIT AS

INDICATED. PROVIDE STRUCTURAL SUPPORTS TO RIGIDLY MOUNT ON ROOF.

Project Title

DE

PA

RT

M

EN

T

OF

VE

TE

RA

NS

A

FF

AI

RS

Drawing Title Date

Project No.

Drawing No.

Dwg. Of

Approved: Associate Director for Operations:

Approved: Director, Medical Center:

Drawn:Building No: Checked:

Location:

Additions:

Revisions:

1 5 6 7 8

21 3 4 5 6 7 8

A B

C D

E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot

JAMES E. VAN ZANDT

VETERANS ADMINISTRATION

MEDICAL CENTER

2 3 4

Consultants:Date

& ASSOCIATES, INC.

BURDETTE KOEHLER MURPHY

RICKERT ENGINEERING, INC.

BUILDING COST CONSULTANTS

COST ESTIMATING

12917 - 30TH AVENUE

PLATTSMOUTH, NEBRASKA 68048

402.298.8260 - FAX 402.298.8290

MECHANICAL / ELECTRICAL CONSULTING

ENGINEERING

6300 BLAIR HILL LANE, SUITE 400

BALTIMORE, MARYLAND 21209

410.323.0600 - FAX 410.377.2543

STRUCTURAL ENGINEERING

8813 WALTHAM WOODS ROAD, SUITE 500

BALTIMORE, MARYLAND 21234

410.663.5110 - FAX 410.663.5114

Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009

ARCHITECTURE

PLANNING

ENGINEERING

FIRE PROTECTION ENGINEERING

8815 CENTRE PARK DR., SUITE 200

COLUMBIA, MARYLAND 21045

410.750.2246 - FAX 410.750.2588

KOFFEL ASSOCIATES, INC.

WHITMAN, REQUARDT & ASSOCIATES, LLP

CIVIL ENGINEERING

801 South Caroline Street Baltimore, MD 21231

410.235.3450 - FAX: 410.243.5716

ROBERT L. SEYMOUR ASSOCIATES

AUTOMATIC TRANSPORT ENGINEERING

182 THOMOS JOHNSON DR. SUITE 200

FREDERICK, MARYLAND 21702

301.662.8112 - FAX 301.662.8117

BKM# 16106.01

DELLC

JOB No.

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

160702D

KEY PLAN

ROOF PLAN

ELECTRICAL - NEW WORK

EXPAND FOR SPECIALTY

CLINIC ADDITION ON 3RD

FLOOR

LSF RSB

VAMC Altoona, Pennsylvania

01/15/19

1-R-E1

503-314

PLAN NORTH

TRUE NORTH

SCALE: 1/8" = 1'-0"

1 ROOF PLAN - ELECTRCIAL - NEW WORK

FIRE ALARM PROJECT NOTES:

1. MODIFY THE EXISTING ADDRESSABLE NOTIFIER 3030 DIGITAL VOICE FIRE ALARM SYSTEM TO

ACCOMMODATE THE NEW THIRD FLOOR ADDITION ABOVE THE OUTPATIENT WING OF BUILDING 1 AT THE JAMES E. VAN ZANDT VA MEDICAL CENTER IN ALTOONA, PA. ALL NEW DEVICES SHALL BE CONNECTED TO AND

COMPATIBLE WITH THE EXISTING NOTIFIER 3030 FIRE ALARM SYSTEM.

2. PROVIDE ALL NECESSARY MATERIALS AND LABOR TO DESIGN AND INSTALL A COMPLETE AND OPERATIONAL SYSTEM

AS DESCRIBED IN THE PROJECT SPECIFICATIONS AND CONTRACT DRAWINGS.

3. ALL REFERENCE TO THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL MEAN THE DEPARTMENT OF VETERAN AFFAIRS (VA) REGIONAL FIRE PROTECTION ENGINEER. ALL REFERENCE TO THE ENGINEER SHALL MEAN KOFFEL

ASSOCIATES, INC. ALL REFERENCE TO THE OWNER SHALL MEAN THE VA.

4. BETTWY SYSTEMS SHALL BE THE SOLE SOURCE CONTRACTOR FOR THE FIRE ALARM INSTALLATION.

5. COORDINATE WORK WITH PROJECT PHASING PLAN.

6. FIRE ALARM AND DETECTION SYSTEM AND ASSOCIATED COMPONENTS SHALL BE IN ACCORDANCE WITH:

• NFPA 70, NATIONAL ELECTRICAL CODE, 2017 EDITION

• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2016 EDITION

• NFPA 101®, LIFE SAFETY CODE®, 2015 EDITION

• VA FIRE PROTECTION DESIGN MANUAL (VAFPDM) 7TH EDITION, DECEMBER 2015

• THE MANUFACTURER'S REQUIREMENTS

• APPLICABLE LOCAL CODES AND REGULATIONS

7. ALL AREAS PROVIDED WITH AUTOMATIC DETECTION SHALL BE ASSUMED TO BE PROVIDED WITH A MINIMUM AMBIENT TEMPERATURE OF 40 DEGREES AND BE FREE OF EXCESSIVE DUST PARTICLES OR HUMIDITY LEVELS, UNLESS NOTED

OTHERWISE.

8. ALL NEW FIRE ALARM SYSTEM WIRING SHALL BE IN CONDUIT. SIZE OF CONDUIT AND PERCENT FILL SHALL BE DETERMINED BY THE CONTRACTOR AND SHALL BE IN ACCORDANCE WITH NFPA 70. SYSTEM CIRCUITS SHALL CONFORM

TO THE FOLLOWING:

• SIGNALING LINE CIRCUITS (SLC): CLASS B

• NOTIFICATION APPLIANCE CIRCUITS (NAC): CLASS B

9. PROVIDE TWISTED-PAIR, SHIELD WIRE FOR ALL AUDIO CIRCUITS. PROVIDE A MINIMUM OF 12-18 AWG WIRE.

10. ALL NEW ADDRESSABLE MODULES SHALL BE LOCATED WITHIN 3 FEET OF THE ASSOCIATED NON-INTELLIGENT

DEVICE MONITORED OR CONTROLLED.

11. ALL DETECTION AND CONTROL CONDUIT AND JUNCTION BOXES SHALL BE INSTALLED AS HIGH AS POSSIBLE. IN NO CASE SHALL ANY PORTION OF THE SYSTEM WIRING BE INSTALLED BELOW THE BOTTOM HORIZONTAL PLANE OF LIGHTING FIXTURES, WITH THE EXCEPTION OF DROPS TO INDIVIDUAL DEVICES AND PANELS. IN AREAS WITH SUSPENDED CEILINGS ALL CONDUIT SHALL BE CONCEALED. PROVIDE ACCESS PANELS FOR CONCEALED DEVICES

AND JUNCTION BOXES, WHERE REQUIRED.

12. ALL WALL MOUNTED AUDIBLE AND VISUAL NOTIFICATION DEVICES SHALL BE MOUNTED A MINIMUM OF 80 INCHES AND

A MAXIMUM OF 96 INCHES ABOVE THE FINISHED FLOOR, PER NFPA 72.

13. A FULL ACCEPTANCE TEST OF ALL NEW FIRE ALARM DETECTION AND CONTROL SYSTEM COMPONENTS IS REQUIRED AS PART OF THIS PROJECT. THIS SHALL INCLUDE A FUNCTIONAL TEST OF 100% OF NEW INITIATING DEVICES.

CONTRACTOR SHALL PROVIDE ALL MATERIALS AND TECHNICAL SUPPORT TO PERFORM ACCEPTANCE TEST IN ACCORDANCE WITH NFPA 72. THE ACCEPTANCE TESTING PERFORMED BY THE CONTRACTOR SHALL BE WITNESSED BY

THE DEPARTMENT OF VETERANS AFFAIRS, OR THEIR CHOSEN REPRESENTATIVE.

14. ALL EQUIPMENT SHALL BE LISTED BY UL LISTED AND FM APPROVED FOR USE ON COMMERCIAL FIRE ALARM

SYSTEMS.

15. PRIOR TO START OF WORK, CONTRACTOR SHALL PERFORM A FULL FUNCTION TEST OF THE EXISTING FIRE ALARM SYSTEM, INCLUDING ANY WORK THAT IS OCCURING DURING THE SECOND FLOOR ADDITION, PER CHAPTER 14 OF NFPA 72. ANY DEFECTS FOUND IN THE EXISTING SYSTEM, NOT RELATED TO ANY ITEMS INDENTIFIED IN THE NEW WORK PLANS, SHALL BE DOCUMENTED AND REPORTED TO THE CONTRACTING OFFICER FOR CORRECTION. OTHERWISE, ANY DEFECTS FOUND AT THE FINAL INSPECTION FOR THE MODIFIED SYSTEM INSPECTION WILL BE PRESUMED TO BE

THE RESPONSIBILIITY OF THE CONTRACTOR, AT NO COST TO THE OWNER.

16. SLC CIRCUITS SHALL NOT SERVE MORE THAN 25,000 SQ. FT.

FIRE ALARM SYMBOLS

ADDRESSABLE INPUT MODULE

(MONITOR MODULE)

FLOW SWITCH

VALVE SUPERVISORY SWITCH

MANUAL PULL STATION

FIRE ALARM SPEAKER

(SUBSCRIPT "C" DENOTES CEILING-MOUNTED)

COMBINATION FIRE ALARM SPEAKER/STROBE

(SUPERSCRIPT DENOTES CANDELA RATING;

SUBSCRIPT "C" DENOTES CEILING-MOUNTED)

VISUAL NOTIFICATION DEVICE

(SUPERSCRIPT DENOTES CANDELA RATING;

SUBSCRIPT "C" DENOTES CEILING-MOUNTED)

NAC POWER EXTENDER PANEL

FIRE ALARM CONTROL PANEL

FIRE ALARM SPEAKER AMPLIFIER PANEL

ADDRESSABLE OUTPUT MODULE

(CONTROL MODULE)

DUCT SMOKE DETECTOR - RETURN

(SUBSCRIPT DENOTES AIR HANDLING UNIT NUMBER)

DUCT SMOKE DETECTOR - SUPPLY

(SUBSCRIPT DENOTES AIR HANDLING UNIT NUMBER)

PHOTOELECTRIC SMOKE DETECTOR (CEILING-MOUNTED)

(SUBSCRIPT 'RB' DENOTES DETECTOR EQUIPPED WITH

INTEGRAL RELAY BASE)

ELECTROMAGNETIC DOOR HOLDER

REMOTE TEST STATION FOR DUCT SMOKE DETECTOR

SPRINKLER/FIRE ALARM ZONE BOUNDARY

NAC

FACP

AOM

F

C

XX

S C

XX

R,AHU-X

S, AHU-X

AMP

M

RB

AIM

RTS

FIRE ALARM ABBREVIATIONS

ACT ACOUSTICAL CEILING TILE

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

CONC CONCRETE

DACT DIGITAL ALARM COMMUNICATOR

TRANSMITTER

EOL END OF LINE DEVICE

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

HVAC HEATING, VENTILATION AND AIR

CONDITIONING

MAX MAXIMUM

MIN MINIMUM

MT METAL TILE

N.C. NORMALLY CLOSED (CONTACT)

N.O. NORMALLY OPEN (CONTACT)

NAC NOTIFICATION APPLIANCE CIRCUIT

NIC NOT IN CONTRACT

NTS NOT TO SCALE

PL PLASTER

POC POINT OF CONNECTION

RA RETURN AIR (HVAC)

RTU ROOF TOP UNIT

RX REMOVE EXISTING DEVICE

SA SUPPLY AIR (HVAC)

SLC SIGNALING LINE CIRCUIT

SPL HIDDEN SPLINE (CEILING)

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

WP WEATHER PROOF

FIRE ALARM RISER GENERAL NOTES:

BUILDING 1 -

3RD FLOOR

NEW ADDITION

BLDG 1 - 2ND FLOOR

BLDG 1 - 1ST FLOOR

EXISTING

NOTIFIER

FACP

EXISTING

AMPLIFIER

PANELS

NEW

AMPLIFIER

PANEL

NEW

NAC

PANEL

(A106B -

MAIN LOBBY)

(A106B -

MAIN LOBBY)

(ELEC A348)

S, AHU-XR, AHU-X

120 VAC

EXISTING

NAC

PANELS

(ELEC B124-1)

C

XXXX

C

XXXX

C

XX

1. RISER IS INTENDED TO SHOW GENERAL SYSTEM

ARCHITECTURE AS IT RELATES TO NEW THIRD FLOOR

ADDITION. SOME DEVICE SYMBOLS SHOWN ON THIS

DIAGRAM REPRESENT MULTIPLE TYPICAL DEVICES,

APPLIANCES, AND CIRCUITS. CONTRACTOR IS RESPONSIBLE

FOR VERIFYING QUANTITY AND LOCATION OF ALL NEW

FIRE ALARM DEVICES.

2. PROVIDE NEW SLC AND CONDUIT FROM EXISTING NOTIFIER 3030 FACP

TO 3RD FLOOR ADDITION. PROVIDE ONE NOTIFICATION CIRCUIT PER

SPRINKLER/SMOKE ZONE.

3. PROVIDE NEW FIRE ALARM SPEAKER PANELS AND NEW NAC

PANELS AND CONDUIT. COORDINATE 120 V CONNECTION WITH

ELECTRICAL. PROVIDE A DEDICATED NOTIFICATION APPLIANCE

CIRCUIT(S) AND PANEL PERSPRINKLER/ SMOKE ZONE SO THAT

EACH ZONE CAN ANNUNCIATE INDEPENDENTLY. THE LINK BRIDGE

ZONE CAN BE INCLUDED IN SPRINKLER ZONE 3-2.

4. DEVICES ON 2ND FLOOR ADDITION DETAILED IN DIFFERENT

DESIGN PACKAGE.

5. COORDINATE CONDUIT ROUTING TO THIRD FLOOR WITH OTHER TRADES.

REFER TO DRAWING 1-1-E1, SPECIFICALLY NOTE 14 IN DETAIL AND THE APPLICABLE

SECTION FOR ROUTING LOCATIONS AND METHOD.

6. AS A CONTRACTOR ALTERNATE, NAC RISERS CAN BE PULLED FROM SECOND FLOOR.

F FAIM

RB

AIM AOM

ROOF

(ELEC A348)

120 VAC

EXISTING

AMPLIFIER

PANELS

EXISTING

AMPLIFIER

PANELS

Project Title

DE

PA

RT

M

EN

T

OF

VE

TE

RA

NS

A

FF

AI

RS

Drawing Title Date

Project No.

Drawing No.

Dwg. Of

Approved: Associate Director for Operations:

Approved: Director, Medical Center:

Drawn:Building No: Checked:

Location:

Additions:

Revisions:

1 5 6 7 8

21 3 4 5 6 7 8

A B

C D

E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot

DELLC

JOB No.

JAMES E. VAN ZANDT

VETERANS ADMINISTRATION

MEDICAL CENTER

2 3 4

Consultants:Date

& ASSOCIATES, INC.

BURDETTE KOEHLER MURPHY

RICKERT ENGINEERING, INC.

BUILDING COST CONSULTANTS

COST ESTIMATING

12917 - 30TH AVENUE

PLATTSMOUTH, NEBRASKA 68048

402.298.8260 - FAX 402.298.8290

MECHANICAL / ELECTRICAL CONSULTING

ENGINEERING

1416 CLARKVIEW ROAD

BALTIMORE, MARYLAND 21209

410.323.0600 - FAX 410.377.2543

STRUCTURAL ENGINEERING

8813 WALTHAM WOODS ROAD, SUITE 500

BALTIMORE, MARYLAND 21234

410.663.5110 - FAX 410.663.5114

Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009

ARCHITECTURE

PLANNING

ENGINEERING

FIRE PROTECTION ENGINEERING

8815 CENTRE PARK DR., SUITE 200

COLUMBIA, MARYLAND 21045

410.750.2246 - FAX 410.750.2588

KOFFEL ASSOCIATES, INC.

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

WHITMAN, REQUARDT & ASSOCIATES, LLP

CIVIL ENGINEERING

801 South Caroline Street Baltimore, MD 21231

410.235.3450 - FAX: 410.243.5716

ROBERT L. SEYMOUR ASSOCIATES

AUTOMATIC TRANSPORT ENGINEERING

182 THOMOS JOHNSON DR. SUITE 200

FREDERICK, MARYLAND 21702

301.662.8112 - FAX 301.662.8117

160702D

FIRE ALARM NOTES,

SYMBOLS, ABBREVIATIONS,

AND MATRIX

EXPAND FOR SPECIALTY

CLINIC ADDITION ON 3RD

FLOOR

MJA KLC

2907 PLEASANT VALLEY BLVD ALTOONA, PA 16602-4377

01/18/2019

1-3-FA1

503-314

NTS

FIRE ALARM MATRIX

NTS

FIRE ALARM RISER DIAGRAM1

1-3-FA1

1-3-FA1

89 103

SHEET KEY NOTES:

PROVIDE ADDRESSABLE MODULES AT WATERFLOW

SWITCH AND TAMPER SWITCH FOR NEW SPRINKLER

ZONE 3-2.

PROVIDE ADDRESSABLE MODULES AT WATERFLOW INDICATOR

AND TAMPER SWITCH FOR NEW SPRINKLER ZONE 3-1.

DUCT DETECTOR FOR AHU ON ROOF. INSTALL ON

SUPPLY SIDE. INSTALL INSIDE BUILDING DOWNSTREAM

OF AIR FILTERS AND AHEAD OF ANY BRANCH CONNECTIONS.

PROVIDE SMOKE DETECTOR TO INITIATE PHASE 1 ELEVATOR RECALL.

PROVIDE SMOKE DETECTOR WITHIN 5 FEET OF SMOKE BARRIER

CROSS CORRIDOR DOOR.

RELEASE FOR SMOKE BARRIER DOORS ON HOLD-OPEN DEVICES.

POWER FROM FIRE ALARM SYSTEM.

THE ZONE SPLITS AT THIS COLUMN LINE ALONG SMOKE BARRIER

BOUNDARY.

PROVIDE SHUTDOWN FOR AHU.

DUCT DETECTOR FOR AHU 15 AND 16 ON ROOF ON RETURN

SIDE PER VA REQUEST. INSTALL INSIDE BUILDING UPSTREAM

OF AIR FILTERS AND CONNECTIONS.

EXTEND SLC FROM EXISTING CIRCUIT ON THIRD FLOOR TO NEW DEVICE.

DEMOLISH EXISTING MANUAL PULL STATION AT DOOR TO BE

REMOVED (BY OTHERS). PROVIDE NEW MANUAL PULL STATION AT

NEW DOOR ON FIRST FLOOR. EXTEND SLC FROM EXISTING

CIRCUIT ON FIRST FLOOR.

PROVIDE NEW NOTIFICATION APPLIANCE IN CORRIDOR CREATED BY LINK

BRIDGE. POWER DEVICE FROM EXISTING CIRCUIT IN MAIN BUILDING FROM

NAC PANEL #5, LOCATED IN ROOM 337. CONTRACTOR TO FIELD VERIFY

EXISTING CONDITIONS.

PROVIDE NEW NOTIFICATION APPLIANCE IN MODIFIED OFFICE. POWER

DEVICE FROM EXISTING CIRCUIT IN MAIN BUILDING FROM NAC PANEL #5,

LOCATED IN ROOM 337, CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS.

PROVIDE NEW FIRE ALARM SPEAKER AMPLIFIER(S) AND NAC PANEL(S).

LOCATE SMOKE DETECTOR ABOVE PANELS.COORDINATE 120V POWER

WITH ELECTRICAL. COORDINATE LOCATIONS WITH ELECTRICAL AND

SECURITY PLANS.

THIS WORK SHALL OCCUR IN PHASE 1.

GENERAL NOTES:

1. EXTEND FIRE ALARM SYSTEM TO THE NEW THIRD FLOOR.

2. EXTEND NEW SLC AND NAC AS NECESSARY TO ACCOMMODATE

NEW WORK. SEE SHEET 1-3-FA1 FOR MORE DETAILS.

3. PROVIDE A DEDICATED NOTIFICATION APPLIANCE CIRCUIT PER

SPRINKLER / FIRE ALARM ZONE.

4. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN ACTIVE

DURING CONSTRUCTION, INCLUDING WITHIN ANY AREA OF

WORK. MINIMIZE OR AVOID DISRUPTIONS TO THE EXISTING

SYSTEMS. FIRE ALARM SYSTEM SHALL BE RETURNED TO

SERVICE EACH DAY AND WHEN NOT UNDERGOING

MODIFICATION. THE VA CONTRACTING OFFICER SHALL

APPROVE ALL SHUTDOWNS.

5. REFER TO ARCHITECTURAL DRAWINGS FOR EXTENT

OF DEMOLITION.

6. ALL NEW FIRE ALARM SPEAKERS SHALL BE TAPPED

AT 1/2 WATT AND BE FIELD-ADJUSTABLE TO SUIT

ACTUAL FIELD CONDITIONS.

D

A

E

F

G H JH.1 K

1.8

7.7

8.9 9.1

B

C

1.3

9.4

9.2

YX

7.1

B9

B10

B12

B14

A.11

A.10

A.7

A.9

A.16

A.3

AIMAIM

AIM AIM

STAIR 1

ST1

ELEVATORS

EL1

STAIR 2

ST2

CORRIDOR

A301A

SHARED CONFERENCE

A335

SHARED BREAK/ LKR

A334

CARDIOVASCULAR

WORKSTATIONS/ COPY

A311

TELECOM

A319

ELEC.

A348

WORK STATION AREA 2

A330

EYE 3

A326

CONSULT/ VIEWING

A325

EYE 1/ WHEELCHAIR

STORAGE

A324

EYEGLASS FITTING &

DISPLAY

A332 VISUAL FIELDS TESTING

A331

OCT

A327

POLYTRAUMA

A328

LOW VISION

A329

STRESS ECHO

A317

EQUIP.

A333

PULMONARY REHAB

AREA/ EXTENDED PULM

FUNCTION/ CONSULT.

ROOM/ WAITING/

WHEELCHAIR

A340

BRIDGE

A300A

LOBBY

A300

MEN'S

A349

WOMEN'S

A350

PRETEST/ EYE /

CHECK-IN

A322 PHOTO/ FUNDUS TEST

A323

CORRIDOR

A301

PULMONARY WORK

STATION

A346

CORRIDOR

A301B

LINEN

A305 NUTRITION

A310

WAITING

A321

DIALATION

A320

STORAGE

A312

STORAGE & EQUIP

A336

CORRIDOR

A318

EKG

A315

CRASH CART

A317A

EXAM/ PATIENT

EDUCATION

A314

ECHO/ CARDIO

A313

TOILET

A316

EXAM / CONSULT

A309

EXAM / CONSULT

A308EXAM / CONSULT

A306

CRASH CART

A347

EXAM RESTROOM

A307

STAFF CORRIDOR

A301C

WAITING

A302

HAC

A339

WOMEN'S

A337

MEN'S

A338

RESPIRATORY

THERAPY/ CPAP

A341

MED

A344

O2 STOR.

A345

TREATMENT ROOM

A343

PFT

A342

MEN'S

A303

WOMEN'S

A304

RS

S, AHU-16

R, AHU-16

, AHU-15 , AHU-15

M

AT

C H

LI

N

E

SE

E

D

ET

AI

L

M

AT

C H

LI

N

E

SE

E

D

ET

AI

L

AOM

NEW SPRINKLER / FIRE ALARM ZONE 3-2

NEW SPRINKLER / FIRE ALARM ZONE 3-1

AM

P

N

AC

x2 x2

RB

RB

RBRB

RBRB

FIRE ALARM SYMBOLS

ADDRESSABLE INPUT MODULE

(MONITOR MODULE)

FLOW SWITCH

VALVE SUPERVISORY SWITCH

MANUAL PULL STATION

FIRE ALARM SPEAKER

(SUBSCRIPT "C" DENOTES CEILING-MOUNTED)

COMBINATION FIRE ALARM SPEAKER/STROBE

(SUPERSCRIPT DENOTES CANDELA RATING;

SUBSCRIPT "C" DENOTES CEILING-MOUNTED)

VISUAL NOTIFICATION DEVICE

(SUPERSCRIPT DENOTES CANDELA RATING;

SUBSCRIPT "C" DENOTES CEILING-MOUNTED)

NAC POWER EXTENDER PANEL

FIRE ALARM CONTROL PANEL

FIRE ALARM SPEAKER AMPLIFIER PANEL

ADDRESSABLE OUTPUT MODULE

(CONTROL MODULE)

DUCT SMOKE DETECTOR - RETURN

(SUBSCRIPT DENOTES AIR HANDLING UNIT NUMBER)

DUCT SMOKE DETECTOR - SUPPLY

(SUBSCRIPT DENOTES AIR HANDLING UNIT NUMBER)

PHOTOELECTRIC SMOKE DETECTOR (CEILING-MOUNTED)

(SUBSCRIPT 'RB' DENOTES DETECTOR EQUIPPED WITH

INTEGRAL RELAY BASE)

ELECTROMAGNETIC DOOR HOLDER

REMOTE TEST STATION FOR DUCT SMOKE DETECTOR

SPRINKLER/FIRE ALARM ZONE BOUNDARY

NAC

FACP

AOM

F

C

XX

S C

XX

R,AHU-X

S, AHU-X

AMP

M

RB

AIM

RTS

B8

A.7

A.9

A.16

BRIDGE

A300A

CORRIDOR

E304

EXAM ROOM

E302

NEW NURSE TRIAGE

E303

NURSE TRIAGE

E301

CLERICAL STAFF

E300A

CLERICAL STAFF

E300A

CORRIDOR

E315A

M

AT

C H

LI

N

E

- S

EE

D

ET

AI

L

M

AT

C H

LI

N

E

- S

EE

D

ET

AI

L

AOM

A

Y

B8

A.3

Project Title

DE

PA

RT

M

EN

T

OF

VE

TE

RA

NS

A

FF

AI

RS

Drawing Title Date

Project No.

Drawing No.

Dwg. Of

Approved: Associate Director for Operations:

Approved: Director, Medical Center:

Drawn:Building No: Checked:

Location:

Additions:

Revisions:

1 5 6 7 8

21 3 4 5 6 7 8

A B

C D

E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot

DELLC

JOB No.

JAMES E. VAN ZANDT

VETERANS ADMINISTRATION

MEDICAL CENTER

2 3 4

Consultants:Date

& ASSOCIATES, INC.

BURDETTE KOEHLER MURPHY

RICKERT ENGINEERING, INC.

BUILDING COST CONSULTANTS

COST ESTIMATING

12917 - 30TH AVENUE

PLATTSMOUTH, NEBRASKA 68048

402.298.8260 - FAX 402.298.8290

MECHANICAL / ELECTRICAL CONSULTING

ENGINEERING

1416 CLARKVIEW ROAD

BALTIMORE, MARYLAND 21209

410.323.0600 - FAX 410.377.2543

STRUCTURAL ENGINEERING

8813 WALTHAM WOODS ROAD, SUITE 500

BALTIMORE, MARYLAND 21234

410.663.5110 - FAX 410.663.5114

Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009

ARCHITECTURE

PLANNING

ENGINEERING

KEY PLAN

FIRE PROTECTION ENGINEERING

8815 CENTRE PARK DR., SUITE 200

COLUMBIA, MARYLAND 21045

410.750.2246 - FAX 410.750.2588

KOFFEL ASSOCIATES, INC.

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

WHITMAN, REQUARDT & ASSOCIATES, LLP

CIVIL ENGINEERING

801 South Caroline Street Baltimore, MD 21231

410.235.3450 - FAX: 410.243.5716

ROBERT L. SEYMOUR ASSOCIATES

AUTOMATIC TRANSPORT ENGINEERING

182 THOMOS JOHNSON DR. SUITE 200

FREDERICK, MARYLAND 21702

301.662.8112 - FAX 301.662.8117

160702D

THIRD FLOOR - NEW WORK -

FIRE ALARM PLAN

EXPAND FOR SPECIALTY

CLINIC ADDITION ON 3RD

FLOOR

MJA KLC

2907 PLEASANT VALLEY BLVD ALTOONA, PA 16602-4377

01/18/2019

1-3-FA2

503-314

1/8" = 1'-0"1-3-FA2

THIRD FLOOR - NEW WORK - FIRE ALARM1

PLAN NORTH

TRUE NORTH

1/8" = 1'-0"1-3-FA2

THIRD FLOOR PART PLAN - CORRIDOR E3042

1/8" = 1'-0"1-3-FA2

FIRST FLOOR PART PLAN - NEW DOOR3

90 103

FIRE SUPPRESSION PROJECT NOTES:

1. PROVIDE WET-PIPE SPRINKLER PROTECTION THROUGHOUT THE NEW THIRD FLOOR ADDITION ABOVE THE OUTPATIENT WING

OF BUILDING 1 AT THE JAMES E. ZANDT VA MEDICAL CENTER IN ALTOONA, PA. PROVIDE ALL NECESSARY MATERIALS AND LABOR TO

FURNISH AND INSTALL THE SYSTEM AS DESCRIBED IN THE CONTRACT DOCUMENTS.

2. REFER TO DETAILS 1, 2, 3, AND 4/1-3-FP1 FOR EXISTING SPRINKLER INFRASTRUCTURE INFORMATION ON HOW THE SPRINKLER SYSTEM

THROUGHOUT AREA OF WORK IS SUPPLIED FROM THE CAMPUS FIRE PUMP.

3. ALL REFERENCE TO THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL MEAN THE DEPARTMENT OF VETERAN AFFAIRS (VA) REGIONAL FIRE PROTECTION ENGINEER. ALL REFERENCE TO THE ENGINEER SHALL MEAN KOFFEL

ASSOCIATES, INC. ALL REFERENCE TO THE OWNER SHALL MEAN THE VA.

4. SPRINKLER SYSTEM AND ASSOCIATED COMPONENTS SHALL BE IN ACCORDANCE WITH:

• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION

• NFPA 14, STANDARD OF STANDPIPE AND HOSE SYSTEMS, 2016 EDITION

• NFPA 101®, LIFE SAFETY CODE®, 2015 EDITION

• VA FIRE PROTECTION DESIGN MANUAL (VAFPDM) 7TH EDITION, DECEMBER 2015

• THE MANUFACTURER'S REQUIREMENTS

• APPLICABLE LOCAL CODES AND REGULATIONS

5. THE FOLLOWING DESIGN CRITERIA APPLIES:

• UNLESS NOTED OTHERWISE - LIGHT HAZARD: 0.10 GPM/SQ.FT OVER 1,500 SQ.FT

• MECHANICAL AND ELECTRICAL ROOMS – ORDINARY HAZARD GROUP I: 0.15 GPM/SQ.FT OVER 1,500 SQ.FT

• STORAGE, LINEN, EQUIPMENT, AND FILE ROOMS – ORDINARY HAZARD GROUP II: 0.20 GPM/SQ.FT OVER 1,500 SQ.FT

PER SECTION 11.2.3.2.3.1 OF NFPA 13, A REDUCTION IN THE DESIGN AREA UP TO 40% IS PERMITTED WHERE LISTED

QUICK-RESPONSE SPRINKLERS ARE UTILIZED.

6. MUNICIPAL WATER SUPPLY TO THE BUILDING 1 SPRINKLER SYSTEM IS SUPPLEMENTED BY AN ELECTRIC-DRIVE HORIZONTAL SPLIT CASE FIRE PUMP LOCATED IN BUILDING 3 WITH A BACKUP DIESEL FIRE PUMP. RESULTS FROM THE MOST RECENT FIRE PUMP TEST

ARE:

STATIC (CHURN): - 125 PSI

100%: - 95 PSI @ 1,018 GPM

150% - 70 PSI @ 1,661 GPM

LOCATION: - FIRE PUMP DISCHARGE FLANGE IN BLDG 3

DATE OF TEST: - SEPTEMBER 16, 2014

SOURCE: - LIBERTY FIRE SOLUTIONS

CONTRACTOR SHALL PROVIDE PUMP TEST DATA NO MORE THAN ONE YEAR OLD FOR ALL HYDRAULIC CALCULATIONS, AS REQUIRED BY NFPA 13. IF TEST RESULTS SHOW DEGRADATION IN EXCESS OF FIVE PERCENT OF MANUFACTURER’S PUMP CURVE, NOTIFY THE OWNER IMMEDIATELY. NOTE THAT THE 2016 ANNUAL FIRE PUMP TEST PRODUCED RESULTS BELOW MANUFACTURER'S PUMP CURVE AND

PER THE VA, THE FIRE PUMPS WERE TO BE INVESTIGATED AND REPAIRED, AS NECESSARY.

7. ALL HYDRAULIC CALCULATIONS SHALL YIELD AT LEAST A 10 PERCENT SAFETY FACTOR FOR EACH SPRINKLER DESIGN

AREA, INCLUDING REQUIRED HOSE STREAMS, PER VAFPDM: 6.1D.

8. SPRINKLER TYPES SHALL BE AS DESCRIBED IN THE PROJECT SPECIFICATIONS. ALL NEW SPRINKLERS SHALL BE U.L. LISTED AND FM APPROVED. SPRINKLERS SHALL ALSO BE QUICK RESPONSE, UNLESS PROHIBITED BY THEIR LISTING. ALL NEW SPRINKLERS

SHALL BE MANUFACTURED BY VIKING.

9. SPRINKLERS SHALL BE LOCATED IN SUSPENDED CEILING TILES, AS INDICATED ON DETAIL 2/1-3-FP3. ARMOVERS AND DROPS TO INDIVIDUAL SPRINKLERS SHALL BE FIELD CUT TO ENSURE PROPER SPRINKLER PLACEMENT.

10. SPRINKLER PIPE AND FITTINGS SHALL MEET THE FOLLOWING CRITERIA:

• PIPE SIZES 2" AND SMALLER: SCHEDULE 40, BLACK STEEL, MEETING ASTM A53 (TYPE E GRADE B) OR A795

(TYPE E GRADE A) SPECIFICATIONS, CONNECTED WITH THREADED FITTINGS.

• PIPE SIZES 2-1/2" AND LARGER: SCHEDULE 10, BLACK STEEL, MEETING ASTM A135 OR A795 TYPE E GRADE A

SPECIFICATIONS, CONNECTED WITH LISTED GROOVED COUPLINGS.

11. PIPE FITTINGS SHALL INCLUDE:

• THREADED FITTINGS FOR SCHEDULE 40 PIPE SHALL CONFORM TO SECTION 6.4 OF NFPA 13.

• ROLL GROOVED FITTINGS FOR SCHEDULE 10 PIPE SHALL BE UL LISTED. COUPLINGS SHALL COMPLY WITH ASTM A536, AND A183 SPECIFICATIONS WITH GRADE E, TYPE A GASKETS. ALL COMPONENTS SHALL BE FROM A

SINGLE MANUFACTURER.

12. ALL NECESSARY CONNECTIONS TO THE FIRE ALARM SYSTEM SHALL BE MADE BY AND COORDINATED WITH THE FIRE ALARM CONTRACTOR. SYSTEM ACCEPTANCE TESTS SHALL BE CONDUCTED BY THE FIRE ALARM CONTRACTOR AND

WITNESSED BY THE VA.

13. ALL HANGERS SHALL BE U.L. LISTED FOR USE WITH SPRINKLER SYSTEMS. HANGER INSTALLATION AND SPACING SHALL BE IN ACCORDANCE WITH NFPA 13. TYPICAL HANGER ARRANGEMENTS ARE INDICATED IN DETAIL 3/1-3-FP3.

14. ALL SPRINKLER SYSTEM PIPING AND HANGERS SHALL BE CONCEALED WHEREVER POSSIBLE. PROVIDE ACCESS

PANELS FOR ALL VALVES, WHERE REQUIRED.

15. PENETRATION OF FIRE-RATED ASSEMBLIES SHALL BE SEALED WITH A U.L. CERTIFIED THROUGH-PENETRATION

SYSTEM APPROPRIATE FOR THE RATING OF THE WALL PENETRATED.

16. COORDINATE THE LOCATION OF SPRINKLER PIPING SHOWN WITH MECHANICAL, STRUCTURAL, AND CEILING SYSTEMS. COORDINATE FINAL LOCATIONS OF ALL SPRINKLERS, PIPING, PIPE SIZES, HANGER LOCATIONS, ETC.

17. CONTRACTOR SHALL BE RESPONSIBLE FOR DEVELOPMENT OF SHOP DRAWINGS, HYDRAULIC CALCULATIONS, PERMIT FEES, APPROVAL OF SHOP DRAWINGS, AND ACCEPTANCE OF THE SYSTEM BY THE AHJ.

18. PRIOR TO SUBMITTING AN APPLICATION FOR SPRINKLER PERMIT TO THE AHJ, PROVIDE TWO COPIES OF ALL SHOP DRAWINGS, HYDRAULIC CALCULATIONS, AND PRODUCT DATA SHEETS TO THE ENGINEER FOR REVIEW AND COMMENT. PERMIT APPLICATION SHALL NOT BE MADE UNTIL SUCH TIME THAT THE OWNER AND ENGINEER HAS COMPLETED A REVIEW OF THE SHOP

DRAWING PACKAGE.

19. PAINT ALL EXPOSED SPRINKLER PIPE PER PROJECT SPECIFICATION SECTION 21 13 13 (WET-PIPE SPRINKLER SYSTEMS).

FIRE SUPPRESSION ABBREVIATIONS

ABD AUTOMATIC BALL DRIP

ACT ACOUSTICAL CEILING TILE

AFF ABOVE FINISHED FLOOR

AS AUTOMATIC SPRINKLER

ATR ALL THREAD ROD

BFP BACKFLOW PREVENTER

BOB BOTTOM OF BEAM

CB CONCRETE BEAM

COL COLUMN

CONC CONCRETE

DI DUCTILE IRON

DN DOWN

DP DRY PENDENT (SPRINKLER)

DS DRY SIDEWALL (SPRINKLER)

EC EXTENDED COVERAGE (SPRINKLER)

EXP EXPOSED (NO CEILING)

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FHV FIRE HOSE VALVE

FS FLOW SWITCH

GALV GALVANIZED

GYP GYPSUM WALL BOARD (SHEETROCK)

HT HIGH TEMPERATURE (SPRINKLER)

ITC INSPECTORS TEST CONNECTION

MAX MAXIMUM

MIN MINIMUM

MT METAL TILE

NIC NOT IN CONTRACT

NS NON-SPRINKLERED

NTS NOT TO SCALE

OSJ OPEN STEEL JOIST

PL PLASTER (CEILING)

POC POINT OF CONNECTION

PRV PRESSURE RELIEF VALVE

QR QUICK RESPONSE (SPRINKLER)

SCH SCHEDULE

SPL HIDDEN SPLINE (CEILING)

STL STEEL

TYP TYPICAL

TS TAMPER SWITCH

UNO UNLESS NOTED OTHERWISE

NFPA 13 SPRINKLER HAZARD CLASSIFICATIONS

NONE LIGHT HAZARD

OH1 ORDINARY HAZARD GROUP I

OH2 ORDINARY HAZARD GROUP II

BUILDING 1

BUILDING 3

VALVE PIT

2 X 45 EL

8"

8"

45 EL

45 EL

~500'

FP

8" APOLLO DOUBLE

CHECK ASSEMBLY (MODEL

4SG-1C0) AND 8" MUELLER

STRAINER (MODEL 911)

KJE G HB C

A

9.4

9.2

6-INCH FEED MAIN UP

FROM BASEMENT

FDCUP TO SECOND FLOOR

6" CONTROL VALVE,

FLOW SWITCH AND

CHECK VALVE

6" UP TO FIRST FLOOR

6" UP TO FIRST

FLOOR AND FDC

Project Title

DE

PA

RT

M

EN

T

OF

VE

TE

RA

NS

A

FF

AI

RS

Drawing Title Date

Project No.

Drawing No.

Dwg. Of

Approved: Associate Director for Operations:

Approved: Director, Medical Center:

Drawn:Building No: Checked:

Location:

Additions:

Revisions:

1 5 6 7 8

21 3 4 5 6 7 8

A B

C D

E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot

DELLC

JOB No.

JAMES E. VAN ZANDT

VETERANS ADMINISTRATION

MEDICAL CENTER

2 3 4

Consultants:Date

& ASSOCIATES, INC.

BURDETTE KOEHLER MURPHY

RICKERT ENGINEERING, INC.

BUILDING COST CONSULTANTS

COST ESTIMATING

12917 - 30TH AVENUE

PLATTSMOUTH, NEBRASKA 68048

402.298.8260 - FAX 402.298.8290

MECHANICAL / ELECTRICAL CONSULTING

ENGINEERING

1416 CLARKVIEW ROAD

BALTIMORE, MARYLAND 21209

410.323.0600 - FAX 410.377.2543

STRUCTURAL ENGINEERING

8813 WALTHAM WOODS ROAD, SUITE 500

BALTIMORE, MARYLAND 21234

410.663.5110 - FAX 410.663.5114

Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009

ARCHITECTURE

PLANNING

ENGINEERING

FIRE PROTECTION ENGINEERING

8815 CENTRE PARK DR., SUITE 200

COLUMBIA, MARYLAND 21045

410.750.2246 - FAX 410.750.2588

KOFFEL ASSOCIATES, INC.

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

WHITMAN, REQUARDT & ASSOCIATES, LLP

CIVIL ENGINEERING

801 South Caroline Street Baltimore, MD 21231

410.235.3450 - FAX: 410.243.5716

ROBERT L. SEYMOUR ASSOCIATES

AUTOMATIC TRANSPORT ENGINEERING

182 THOMOS JOHNSON DR. SUITE 200

FREDERICK, MARYLAND 21702

301.662.8112 - FAX 301.662.8117

160702D

FIRE SUPPRESSION NOTES

AND ABBREVIATIONS

EXPAND FOR SPECIALTY

CLINIC ADDITION ON 3RD

FLOOR

MJA KLC

2907 PLEASANT VALLEY BLVD ALTOONA, PA 16602-4377

01/18/2019

1-3-FP1

503-314

FS0.0

1/8" = 1'-0"

EXISTING SITE INFRASTRUCTURE PLAN

1/32" = 1'-0"1-3-FP1

EXISTING FIRST FLOOR INFRASTRUCTURE PLAN4

1-3-FP1

91 103

ZCA

GENERAL NOTES:

1. PROVIDE A CLASS I MANUAL WET STANDPIPE

SYSTEM THROUGHOUT BUILDING ADDITION. EACH

STAIRWAY SHALL BE PROVIDED WITH A 4" STANDPIPE

AND 2-1/2" HOSE CONNECTION LOCATED ON THE

PRIMARY LANDING. REFER TO DETAIL 5 AND 6 /1-3-FP3.

2. WHERE INDICATED, UPRIGHT SPRINKLERS SHALL

BE PROVIDED WITH A PROTECTIVE CAGE. CAGE

SHALL BE AN APPROVED ACCESSORY FROM THE

SPRINKLER MANUFACTURER.

SHEET KEY NOTES:

EXTEND STANDPIPE FROM SECOND FLOOR. PROVIDE

2-1/2" HOSE VALVE CONNECTION AT MAIN STAIR

LANDING.

SPRINKLER ZONE CONTROL ASSEMBLY. REFER TO

DETAILS/1-3-FP3.

EXTEND 2" DRAIN FROM SECOND FLOOR.

PROVIDE TEMPORARY PROTECTION OF HOSE VALVE

THREADS DURING CONSTRUCTION. PROVIDE PLASTIC

CAPS OR EQUIVALENT.

RELOCATE EXISTING SPRINKLERS IN CORRIDOR TO

SUPPORT CONNECTION OF NEW LINK BRIDGE.

DEMOLISH EXISTING SECOND FLOOR STAIR SPRINKLERS WHEN

STAIR TOWER IS EXTENDED. PROVIDE NEW SPRINKLERS

ON THIRD FLOOR.

INSTALL SPRINKLERS AROUND SKYLIGHT.

EXTEND SPRINKLER PROTECTION TO NEW ROOM.

RELOCATE EXISTING SPRINKLERS IN THIS ROOM AS NECESSARY

TO SUPPORT NEW WORK.

DEMOLISH EXISTING SPRINKLERS IN STAIR AND CONNECTION TO

2ND FLOOR SYSTEM.

DEMOLISH EXISTING SPRINKLERS AND PIPING IN STAIR BEFORE

RISER UP TO THIRD FLOOR IS INSTALLED. THE EXISTING BRANCH

LINE PIPING CONFLICTS WITH NEW RISER LOCATION.

THE EXISTING RISER ON THE SECOND FLOOR DOES NOT ALIGN

WITH THE THIRD FLOOR STAIR LANDING BEFORE THE RISER IS

EXTENDED TO THE THE THIRD FLOOR, THE PIPING MUST BE

RE-ALIGNED. DO NOT CUT OR CORE DRILL ANY STEEL

SUPPORTING THIRD FLOOR LANDING.

3. THE SPRINKLER LOCATIONS ARE PRELIMINARY TO

INDICATE GENERAL DESIGN INTENT, SCOPE OF

WORK, AND AREA OF COVERAGE. SPRINKLER

CONTRACTOR IS RESPONSIBLE FOR FINAL

SPRINKLER LAYOUT.

4. THE EXISTING SPRINKLER SYSTEM SHALL REMAIN

ACTIVE DURING CONSTRUCTION, INCLUDING WITHIN

ANY AREA OF WORK. MINIMIZE OR AVOID DISRUPTIONS

TO THE EXISTING SYSTEMS. SPRINKLER SYSTEM SHALL

BE RETURNED TO SERVICE EACH DAY AND WHEN NOT

UNDERGOING MODIFICATION. THE CONTRACTING OFFICER

SHALL APPROVE ALL SHUTDOWNS.

5. REFER TO ARCHITECTURAL DRAWINGS FOR EXTENT

OF DEMOLITION.

6. CONTRACTOR TO VERIFY LOCATION OF EXISTING ZONE

CONTROL ASSEMBLY IN MAIN BUILDING.

7. PROVIDE AN AUTOMATIC AIR VENT FOR EACH SYSTEM

PER NFPA 13: 8.16.6. THE VENT MUST BE LOCATED NEAR

THE HIGH POINT. PROVIDE AUTOMATIC VENT THAT DOES

NOT REQUIRE DRAIN.

KJH.1D E G HB C

A

1.8

2.5

1.3

9.4

9.2

YX

7.1

A.11

A.10

A.7

A.8

A.14

A.4

1-3-FP3

1-3-FP3

ZCA

ZCA

NEW SPRINKLER ZONE 3-2

6,475 SQ FT

NEW SPRINKLER ZONE 3-1

6,550 SQ FT

STAIR 1

ST1

ELEVATORS

EL1

STAIR 2

ST2

CORRIDOR

A301A

SHARED CONFERENCE

A335 SHARED BREAK/ LKR

A334

CARDIOVASCULAR

WORKSTATIONS/ COPY

A311

TELECOM

A319

ELEC.

A348

WORK STATION AREA 2

A330

EYE 3

A326

CONSULT/ VIEWING

A325

EYE 1/ WHEELCHAIR

STORAGE

A324

EYEGLASS FITTING &

DISPLAY

A332 VISUAL FIELDS TESTING

A331

OCT

A327

POLYTRAUMA

A328

LOW VISION

A329

STRESS ECHO

A317

EQUIP.

A333

PULMONARY REHAB

AREA/ EXTENDED PULM

FUNCTION/ CONSULT.

ROOM/ WAITING/

WHEELCHAIR

A340

BRIDGE

A300A

LOBBY

A300

MEN'S

A349

WOMEN'S

A350

PRETEST/ EYE /

CHECK-IN

A322

PHOTO/ FUNDUS TEST

A323

CORRIDOR

A301

PULMONARY WORK

STATION

A346

CORRIDOR

A301B

LINEN

A305

NUTRITION

A310

WAITING

A321

DIALATION

A320

STORAGE

A312

STORAGE & EQUIP

A336

CORRIDOR

A318

EKG

A315

CRASH CART

A317A

EXAM/ PATIENT

EDUCATION

A314

ECHO/ CARDIO

A313

TOILET

A316

EXAM / CONSULT

A309

EXAM / CONSULT

A308

EXAM / CONSULT

A306

CRASH CART

A347

EXAM RESTROOM

A307

STAFF CORRIDOR

A301C

WAITING

A302

HAC

A339 WOMEN'S

A337

MEN'S

A338

RESPIRATORY

THERAPY/ CPAP

A341

MED

A344

O2 STOR.

A345TREATMENT ROOM

A343

PFT

A342

MEN'S

A303 WOMEN'S

A304

NS

11 12

11 12

OH 2

OH 2

OH 1

OH 2

OH 2

OH 2

OH 2

OH 2

OH 1

NS

NEW SYSTEM PIPING

SYSTEM RISER

HOSE VALVE

FLUSHING CONNECTION OR CAP

UPRIGHT SPRINKLER WITH PROTECTIVE CAGE

UPRIGHT SPRINKLER ON SPRIG

PENDENT SPRINKLER;

ON DROP NIPPLE

ZONE CONTROL VALVE ASSEMBLY

SPRINKLER ZONE BOUNDARY

NON-SPRINKLERED AREA

FIRE SUPPRESSION LEGEND:

A.7

A.8

A.14

CORRIDOR

E304

EXAM ROOM

E302

CLERICAL STAFF

E300A

NURSE TRIAGE

E301

EXAM ROOM

E302

NEW NURSE TRIAGE

E303

CORRIDOR

E315A

CORRIDOR

E315A

BRIDGE

A300A

CLERICAL STAFF

E300A

Project Title

DE

PA

RT

M

EN

T

OF

VE

TE

RA

NS

A

FF

AI

RS

Drawing Title Date

Project No.

Drawing No.

Dwg. Of

Approved: Associate Director for Operations:

Approved: Director, Medical Center:

Drawn:Building No: Checked:

Location:

Additions:

Revisions:

1 5 6 7 8

21 3 4 5 6 7 8

A B

C D

E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot

DELLC

JOB No.

JAMES E. VAN ZANDT

VETERANS ADMINISTRATION

MEDICAL CENTER

2 3 4

Consultants:Date

& ASSOCIATES, INC.

BURDETTE KOEHLER MURPHY

RICKERT ENGINEERING, INC.

BUILDING COST CONSULTANTS

COST ESTIMATING

12917 - 30TH AVENUE

PLATTSMOUTH, NEBRASKA 68048

402.298.8260 - FAX 402.298.8290

MECHANICAL / ELECTRICAL CONSULTING

ENGINEERING

1416 CLARKVIEW ROAD

BALTIMORE, MARYLAND 21209

410.323.0600 - FAX 410.377.2543

STRUCTURAL ENGINEERING

8813 WALTHAM WOODS ROAD, SUITE 500

BALTIMORE, MARYLAND 21234

410.663.5110 - FAX 410.663.5114

Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009

ARCHITECTURE

PLANNING

ENGINEERING

KEY PLAN

FIRE PROTECTION ENGINEERING

8815 CENTRE PARK DR., SUITE 200

COLUMBIA, MARYLAND 21045

410.750.2246 - FAX 410.750.2588

KOFFEL ASSOCIATES, INC.

100% CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

WHITMAN, REQUARDT & ASSOCIATES, LLP

CIVIL ENGINEERING

801 South Caroline Street Baltimore, MD 21231

410.235.3450 - FAX: 410.243.5716

ROBERT L. SEYMOUR ASSOCIATES

AUTOMATIC TRANSPORT ENGINEERING

182 THOMOS JOHNSON DR. SUITE 200

FREDERICK, MARYLAND 21702

301.662.8112 - FAX 301.662.8117

160702D

THIRD FLOOR PLAN - FIRE

SUPPRESSION -…