36C24419R0047-059.pdf
PDF 15 MB Posted
- Attached to
- 503-314 Expand for Specialty Clinic on 3rd Floor
- Solicitation number
- 36C24419R0047
About this file
36C24419R0047 503-314 Expand for Specialty Care on 3rd Floor Drawings_Part1.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24419R0047-0003000.docx | DOCX document | |
| 36C24419R0047-0002000.docx | DOCX document | |
| 36C24419R0047-0001001.pdf | ||
| 36C24419R0047-0001000.docx | DOCX document | |
| 36C24419R0047-047.pdf | ||
| 36C24419R0047-056.pdf | ||
| 36C24419R0047-051.pdf | ||
| 36C24419R0047-055.pdf | ||
| 36C24419R0047-066.docx | DOCX document | |
| 36C24419R0047-069.docx | DOCX document | |
| 36C24419R0047-048.pdf | ||
| 36C24419R0047-049.pdf | ||
| 36C24419R0047-053.pdf | ||
| 36C24419R0047-067.docx | DOCX document | |
| 36C24419R0047-063.pdf | ||
| 36C24419R0047-064.pdf | ||
| 36C24419R0047-065.docx | DOCX document | |
| 36C24419R0047-068.docx | DOCX document | |
| 36C24419R0047-045.docx | DOCX document | |
| 36C24419R0047-050.pdf | ||
| 36C24419R0047-058.pdf | ||
| 36C24419R0047-061.pdf | ||
| 36C24419R0047-062.pdf | ||
| 36C24419R0047-057.docx | DOCX document | |
| 36C24419R0047-060.pdf | ||
| 36C24419R0047-070.docx | DOCX document | |
| 36C24419R0047-046.pdf | ||
| 36C24419R0047-052.pdf | ||
| 36C24419R0047-054.pdf | ||
| 36C24419R0047-030.docx | DOCX document | |
| 36C24419R0047-000.docx | DOCX document |
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEDUCT ALTERNATE NOTE:
BID ITEMS:
BASE BID: ALL WORK SHOWN.
DEDUCT ALTERNATE-1: DELETE PHOTOVOLTAIC ARRAY,
ALL PANELS, SUPPORTS, WIRING, RELATED EQUIPMENT
AND LABOR.
DEDUCT ALTERNATE-2: DELETE ALL WORK TO BE DONE IN
ROOM E300A CLERICAL STAFF.
Project Title
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
Drawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
Additions:
Revisions:
1 5 6 7 8
21 3 4 5 6 7 8
A B
C D
E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot
DELLC
JOB No.
JAMES E. VAN ZANDT
VETERANS ADMINISTRATION
MEDICAL CENTER
2 3 4
Consultants:Date
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL CONSULTING
ENGINEERING
6300 BLAIR HILL LANE
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 500
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009
ARCHITECTURE
PLANNING
ENGINEERING
KEY PLAN
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
100% CONSTRUCTION
DOCUMENTS
WHITMAN, REQUARDT & ASSOCIATES, LLP
CIVIL ENGINEERING
801 South Caroline Street Baltimore, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR ASSOCIATES
AUTOMATIC TRANSPORT ENGINEERING
182 THOMOS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
160702D
FULLY SPRINKLERED
2907 PLEASANT VALLEY BLVD. ALTOONA, PA 16602-4377
COVER SHEET EXPAND FOR SPECIALTY
CLINIC ADDITION ON 3RD
FLOOR
CP/ CAJ JSK/ DGW/ WPH
11/20/2018
1-3-X1
503-314
SCALE: 12" = 1'-0"1-3-X1
1 VA Logo
JAMES E. VAN ZANDT VETERANS
ADMINISTRATION MEDICAL CENTER
ALTOONA, PA.
EXPAND FOR SPECIALTY CLINIC
ADDITION ON 3rd FLOOR 503-314
INDEX OF DRAWINGS
SHEET No. SHEET NAME
11 ELECTRICAL
1-B-3-R-E1 ELECTRICAL LEGEND ABBREVIATIONS AND GENERAL NOTES
1-B-3-R-E2 POWER RISER DIAGRAM - NEW WORK
1-B-3-R-E3 PANEL SCHEDULES
1-B-E1 BASEMENT FLOOR PLAN ELECTRICAL - DEMOLITION
1-B-E2 BASEMENT FLOOR PLAN POWER - NEW WORK
1-1-E1 FIRST FLOOR PLAN - ELECTRICAL - DEMOLITION & NEW WORK
1-3-E1 THIRD FLOOR PLAN LIGHTING - NEW WORK
1-3-E3 THIRD FLOOR PLAN POWER - NEW WORK
1-3-E5 EXIST THIRD FLOOR PLAN - ELECTRICAL DEMOLITION & NEW WORK
1-3-E6 CONTROL WIRING DIAGRAM
1-R-E1 ROOF PLAN ELECTRICAL - NEW WORK
12 FIRE PROTECTION
1-3-FA1 FIRE ALARM NOTES, SYMBOLS, ABBREVIATIONS, AND MATRIX
1-3-FA2 THIRD FLOOR PLAN - FIRE ALARM
1-3-FP1 FIRE SUPPRESSION NOTES, SYMBOLS, AND ABBREVIATIONS
1-3-FP2 THIRD FLOOR PLAN - FIRE SUPPRESSION
1-3-FP3 FIRE SUPPRESSION DETAILS
13 IT / TELCOM
1-3-IT1 LEGEND SYMBOLS AND ABBREVIATIONS
1-3-IT2 THIRD FLOOR PLAN - NEW WORK - TELECOM
1-3-IT3 TELECOM PART PLAN AND RISER
1-3-IT4 TELECOM DETAILS
1-3-IT5 TELECOM DETAILS
1-3-IT6 TELECOM DETAILS
1-3-IT7 TELECOM DETAILS
1-3-IT8 FIRST AND SECOND FLOOR PLANS - NEW WORK - TELECOM
1-3-IT9 THIRD FLOOR PLAN - NEW WORK - SECURITY
1-3-IT10 EXISTING THIRD FLOOR PLANS - TELECOM
INDEX OF DRAWINGS
SHEET No. SHEET NAME
06 STRUCTURAL
1-3-S1 FOUNDATION AND FIRST FLOOR PLAN
1-3-S2 SECOND FLOOR FRAMING PLAN
1-3-S3 THIRD FLOOR FRAMING PLAN
1-3-S4 ROOF FRAMING PLAN
1-3-S5 STRUCTURAL SECTIONS AND DETAILS
1-3-S6 STRUCTURAL SECTIONS AND DETAILS
1-3-S7 STRUCTURAL BRACING DETAILS
1-3-S8 STRUCTURAL BRIDGE SECTIONS AND DETAILS
1-3-S9 STRUCTURAL BRIDGE SECTIONS AND DETAILS
1-3-S10 COLUMN SCHEDULE
1-3-S11 GENERAL NOTES AND SCHEDULE
07 VERTICAL TRANSPORTATION
1-1-3-R1 ELEVATOR HOISTWAY AND MACHINE ROOM
09 MECHANICAL
1-B-1-2-3-R-H1 MECHANICAL LEGEND ABBREVIATIONS AND GENERAL NOTES
1-B-1-2-3-R-H2 MECHANICAL SCHEMATICS
1-B-1-2-3-R-H3 MECHANICAL DETAILS
1-B-1-2-3-R-H4 MECHANICAL DETAILS
1-B-1-2-3-R-H5 MECHANICAL DETAILS
1-B-1-2-3-R-H6 MECHANICAL DETAILS
1-B-1-2-3-R-H7 MECHANICAL DETAILS
1-B-1-2-3-R-H8 MECHANICAL CONTROLS SEQUENCES
1-B-1-2-3-R-H9 MECHANICAL SCHEDULES
1-B-1-2-3-R-H10 MECHANICAL SCHEDULES
1-B-1-2-3-R-H11 HEATED AND CHILLED WATER RISER DIAGRAM
1-B-H1 BASEMENT FLOOR PLAN - HVAC - NEW WORK
1-1-H1 FIRST FLOOR PLAN MECHANICAL - DEMOLITION & NEW WORK
1-2-H1 SECOND FLOOR PLAN - HVAC PIPING - NEW WORK
1-3-H1 THIRD FLOOR PLAN - DUCTWORK - NEW WORK
1-3-H2 THIRD FLOOR PLAN - REFLECTED CEILING PLAN - NEW WORK
1-3-H3 THIRD FLOOR PLAN - HVAC PIPING - NEW WORK
1-3-H4 EXISTING HOSPITAL THIRD FLOOR PLAN - HVAC DEMO AND NEW WORK
1-3-H5 MECHANICAL SECTIONS
1-R-H1 ROOF PLAN - HVAC - NEW WORK
10 PLUMBING
1-B-1-2-3-R-P1 PLUMBING LEGEND ABBREVIATIONS, SCHEDULES AND GENERAL NOTES
1-B-1-2-3-R-P2 PLUMBING DETAILS
1-B-1-2-3-P1 DOMESTIC WATER RISER DIAGRAM
1-2-3-R-P1 SANITARY RISER DIAGRAM
1-2-3-R-P2 STORM WATER RISER DIAGRAM
1-B-1-P1 PART BASEMENT & FIRST FLOOR PLAN - DEMOLITION & NEW WORK
1-2-P1 SECOND FLOOR PLAN - PLUMBING - DEMOLITION
1-2-P2 SECOND FLOOR PLAN PLUMBING - NEW WORK
1-3-P1 THIRD FLOOR PLAN - PLUMBING - NEW WORK
1-3-P2 EXISTING HOSPITAL - THIRD FLOOR PLAN - PLUMBING DEMOLITION & NEW WORK
1-R-P1 ROOF PLAN PLUMBING - DEMOLITION
1-R-P2 ROOF PLAN PLUMBING - NEW WORK
INDEX OF DRAWINGS
SHEET No. SHEET NAME
00 GENERAL
1-3-X1 COVER SHEET
1-3-X2 SYMBOLS ABBREVIATIONS AND CODE DATA
1-3-X3 LIFE SAFETY PLANS – THIRD FLOOR
1-3-X4 2ND FLOOR DEMOLITION AND ICRA DRAWING
01 SITE
1-B-1-R-L1 EXISTING CONDITIONS - DEMOLITION PLAN
1-B-1-R-L2 SITE PLAN
1-B-1-R-L3 SITE DETAILS
04 ARCHITECTURE
1-1-1 FIRST FLOOR - DEMOLITION & NEW WORK FLOOR PLAN & ELEVATIONS
1-3-1 THIRD FLOOR - DEMOLITION PLAN
1-3-1.5 DEPARTMENTAL PLAN
1-3-2 THIRD FLOOR - NEW WORK - PLAN
1-3-3 THIRD FLOOR DIMENSIONED PLAN
1-3-4 THIRD FLOOR - FURNITURE AND EQUIPMENT - PLAN
1-3-5 EXISTING THIRD FLOOR HOSPITAL - DEMOLITION & NEW WORK PLANS
1-3-6 THIRD FLOOR - REFLECTED CEILING PLAN
1-3-7 THIRD FLOOR - ROOF PLAN
1-3-7.1 THIRD FLOOR - ROOF PLAN - DEDUCT ALT
1-B-3-R-8 THIRD FLOOR - EXTERIOR ELEVATIONS
1-B-3-R-9 THIRD FLOOR - EXTERIOR ELEVATIONS
1-2-3-R-10 THIRD FLOOR - BRIDGE ELEVATIONS AND SECTIONS
1-2-3-R-11 THIRD FLOOR - BRIDGE SECTIONS AND DETAILS
1-B-3-R-12 BUILDING SECTIONS
1-2-3-R-13 THIRD FLOOR - WALL SECTIONS
1-3-14 ENLARGED PLANS & RESTROOM ELEVATIONS
1-3-15 ENLARGED PLANS & RESTROOM ELEVATIONS
1-3-16 INTERIOR ELEVATIONS
1-3-17 INTERIOR ELEVATIONS
1-3-18 DETAILS
1-3-19 DOOR SCHEDULE & DETAILS
1-3-20 STOREFRONT ELEVATIONS
1-3-21 STOREFRONT ELEVATIONS, SCHEDULE AND DETAILS
05 INTERIORS
1-3-22 FINISH SCHEDULE & LEGENDS
1-3-23 NOT USED
SCALE: 12" = 1'-0"1-3-X1
5 3D VIEW 1
SCALE: 12" = 1'-0"1-3-X1
2 3D VIEW 2
SCALE: 12" = 1'-0"1-3-X1
3 3D VIEW 3
6bs1
BASE - SEE
FINISH
SCHEDULE
BASE - SEE
FINISH
SCHEDULE
FLOOR FINISH -
SEE FINISH
SCHEDULE
FLOOR FINISH -
SEE FINISH
SCHEDULE
STRUCTURAL
DECK ABOVE
STRUCTURAL
DECK ABOVE
NOT RATED
1 HR RATED - FIRE BARRIER
SHALL CONFORM TO UL
DESIGN: U415
4bs
BASE - SEE
FINISH
SCHEDULE
FLOOR FINISH -
SEE FINISH
SCHEDULE
STRUCTURAL
DECK ABOVE
1 HR RATED - FIRE BARRIER
SHALL CONFORM TO UL
DESIGN:U419
2 1/2" METAL
STUD FRAMING
@ 16" O.C.
5/8" GYPSUM
WALLBOARD
3 5/8" METAL
STUD FRAMING
@ 16" O.C.
5/8" TYPE "X"
GYPSUM
WALLBOARD
(BOTH SIDES)
1 LAYER 5/8" TYPE
"X" GYPSUM
WALLBOARD
CERAMIC TILE BASE
FLOOR FINISH - SEE
FINISH SCHEDULE
STRUCTURAL
DECK ABOVE
NOT RATED
2 1/2" METAL
STUDS @ 16" O.C.
1/2" CEMENT
BOARD (BOTH
SIDES)
CERAMIC TILE
(BOTH SIDES)
5/8" GYPSUM
WALLBOARD
BASE - SEE
FINISH
SCHEDULE
FLOOR FINISH -
SEE FINISH
SCHEDULE
STRUCTURAL
DECK ABOVE
NOT RATED
6" METAL STUD
FRAMING
@ 16" O.C.
5/8" GYPSUM
WALLBOARD
(BOTH SIDES)
1" GYPSUM
SHAFT LINER
4" CH STUD @
24" O.C.
3 1/8" 4 7/8"7 1/4"
BASE - SEE FINISH
SCHEDULE
FLOOR FINISH -
SEE FINISH
SCHEDULE
STRUCTURAL
DECK ABOVE
3 5/8" METAL
STUD FRAMING
@ 16" O.C.
5/8" GYPSUM
WALLBOARD
(BOTH SIDES)
4 7/8"
NOT RATED
TYPICAL FOR ALL INTERIOR WALLS
UNLESS OTHERWISE NOTED
BASE - SEE
FINISH
SCHEDULE
FLOOR FINISH -
SEE FINISH
SCHEDULE
STRUCTURAL
DECK ABOVE
3 5/8" METAL
STUD FRAMING
@ 16" O.C.
5/8" GYPSUM
WALLBOARD
NOT RATED
4 1/4"4 5/8"
9bs
BASE - SEE
FINISH
SCHEDULE
FLOOR FINISH -
SEE FINISH
SCHEDULE
STRUCTURAL
DECK ABOVE
CEILING SEE
FINISH SCHEDULE
ON 1-3-22
1 HR RATED - FIRE BARRIER
SHALL CONFORM TO UL
DESIGN: U415
1 LAYER 5/8" TYPE
"X" GYPSUM
WALLBOARD
1" GYPSUM
SHAFT LINER
CH STUD @ 24"
O.C.
3 1/8"
INSULATION
AT EXTERIOR
WALLS
PLAN VIEW PLAN VIEW
4" CH STUD @
24" O.C.
2 1/2"
CH STUD @ 24"
O.C.
8 1/4"
CEILING SEE
FINISH SCHEDULE
ON 1-3-22
CEILING SEE
FINISH
SCHEDULE ON
1-3-22
CEILING SEE
FINISH SCHEDULE
ON 1-3-22
CEILING SEE
FINISH
SCHEDULE ON
1-3-22
CEILING SEE
FINISH
SCHEDULE ON
1-3-22
CEILING SEE
FINISH SCHEDULE
ON 1-3-22
CEILING SEE
FINISH
SCHEDULE ON
1-3-22 a = SMOKE PARTITION (NOT USED) bs = 1 HOUR FIRE AND SMOKE BARRIER cs = 2 HOUR FIRE AND SMOKE BARRIER (NOT USED)
VA WALL TYPE DESIGNATION LEGEND
Project Title
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
Drawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
Additions:
Revisions:
1 5 6 7 8
21 3 4 5 6 7 8
A B
C D
E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot
DELLC
JOB No.
JAMES E. VAN ZANDT
VETERANS ADMINISTRATION
MEDICAL CENTER
2 3 4
Consultants:Date
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL CONSULTING
ENGINEERING
6300 BLAIR HILL LANE
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 500
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009
ARCHITECTURE
PLANNING
ENGINEERING
KEY PLAN
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
100% CONSTRUCTION
DOCUMENTS
WHITMAN, REQUARDT & ASSOCIATES, LLP
CIVIL ENGINEERING
801 South Caroline Street Baltimore, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR ASSOCIATES
AUTOMATIC TRANSPORT ENGINEERING
182 THOMOS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
160702D
FULLY SPRINKLERED
2907 PLEASANT VALLEY BLVD. ALTOONA, PA 16602-4377
SYMBOLS ABBREVIATIONS
AND CODE DATA
EXPAND FOR SPECIALTY
CLINIC ADDITION ON 3RD
FLOOR
CP/ CAJ JSK/ DGW/ WPH
11/20/2018
1-3-X2
503-314 concrete masonry unit demolish, demolition
CU cubic
DR
D
DS
DWG
DF
DIA
DTL
DL
DEM
DIM
door downspout drinking fountain drain drawing dead load diameter detail dimension
AUTO automatic cast iron column ceramic tile cement control joint construction concrete continuous, continue ceiling catch basin
COL
CJT
CONT
CONST
CONC
CMU
CI
CT
CEM
CLG
CB
basement below finish floor bearing plate both sides board block building bottom built up roof bench mark bituminous
BLK
BS
BD
BUR
BLDG
BOT
BFF
BPL
BSMT
BM
BIT
alternate air conditioning above finish floor asphalt anchor bolt architect (ural) approximate aluminum
ALT
AB
ARCH
APPROX.
ASPH
ALUM
AC
AFF
WC water closet plaster air conditioning
PLAS
insulation insulated glass unit inside diameter include (d) (ing) hot water heater hose bib horizontal hollow metal hollow core interior
INCL
INSUL
IGU
ID
INT
HOR
HWH
HM
HB
HC
point plywood plate concrete plank-painted square inch pounds per square foot pounds per polyvinyl chloride
PSF
PSI
PL
PT
PVC
PWD
PLK
west, width, wide welded wire fabric waterproof (ing) wood base wired glass
WB
WG
WWF
WP
W/ W
WD
with wood manholeMH
EXP expansion, exposed galvanized hollow metal fire extinguisher cabinet
GA
galvanized gypsum wall board glazed masonry unit general contractor heating ventilating grade, grading hardware gypsum gauge
GWB
HVAC
HDW
GYP
GALV
GMU
GHM
GD
GC
fire extinguisher finish (ed) exterior finished floor line foundation footing floor drain floor (ing) flashingFLG
FLR
FND
FTG
FD
EXT
FFL
FEC
FE
FIN
nominalNOM north opening on center outside diameter perimeter panel polished float glass overhead overall not to scale not in contract
OD
PER
OH
OA
PNL
PFG
N
OC
OPG
NTS
NIC
marble masonry manufacture (er) maximum metal mechanical miscellaneous minimum medium medium density overlay masonry opening
MTL
MECH
MISC
MIN
MED
MAX
MBL
MAS
MFR
MDO
MO
emergency each way existing exhaust estimate electric water cooler elevation electric (al)
EST
EXH
EXIST
EMER
ELEV
EW
EWC
ELEC
knock out invert left hand lavatory
LBL
LH
LPL
LAV
label low presure laminate
JT
KO
INV
joint
RO rough opening
TBD to be determined tempered float glass tongue & groove thick (ness) vinyl covered drywall vinyl composition tile vertical
VCT
VCD
VERT
TYP typical
TFG
T&G
THK
schedule section specification (s) square straight structural storage south, switch (es) seamless floor
SPEC
ST
SQ
STR
STL
STO
steel
SIM
SEC
SCH
SF
S similar reference quarry tile property line right of way revision, revised return air
REF
ROW
REV
RM
R
RA
riser room
QT
PL
R radius RCP reflected ceiling plan plastic laminateP-LAM
SYS system high pressure laminateHPL
LT light
ABBREVIATIONS SYMBOLS APPLICABLE CODES
A301
A301
OT
GYM
10'-0" A.F.F.
DETAIL TAG
COLUMN LINE BUBBLE TAG
CEILING HEIGHT TAG
A-?
DWG NAME
SCALE:
SECTION TAG
ROOM TAG - NEW WORK
WINDOW TAG
WALL TYPE TAG
TITLE TAG
W05
BREAKLINE SYMBOL
PIPE BREAK
INTERIOR ELEVATION
EXTERIOR ELEVATION
ELEVATION MARK
DETAIL CALL OUT
TAG
REVISION TAG
FIRST FLOOR
DOOR TAG
CONSTRUCTION KEY
NOTE TAG
X
D1-202A
A201
A201
125 SF
STOREFRONT
WINDOW TAG
S05
INTERIOR
WINDOW TAG
i05
CODE REVIEW
• NFPA 101 LIFE SAFETY CODE 2015 EDITION
• INTERNATIONAL MECHANICAL CODE (IMC) 2015 EDITION
• INTERNATIONAL ELECTRICAL CODE (IEC) 2015 EDITION
• INTERNATIONAL PLUMBING CODE (IPC) 2015 EDITION
• VA BARRIER FREE DESIGN GUIDE
• VA FIRE PROTECTION DESIGN MANUAL, SEVENTH EDITION
- DECEMBER 2015
Use and Occupancy
The Third Floor Addition will be classified as “Health Care” as defined by the LSC. it is defined as use group I per the IBC. As this project does connect to existing second floor areas, a smoke barrier separation is required throughout the new space.
This project is located above the outpatient wing of Building 1. The First Floor of the outpatient wing is classified as “Ambulatory Health Care.” Second Floor Addition is classified as “Business” The existing means of egress will not be obstructed during construction.
Construction
This project is adding 12,505 sq ft of new floor space to Building 1, but will not increase the overall footprint of the building or the over all height of the building. It will be considered an addition to existing Building 1. Building 1 construction type is classified as Type IB as defined by the IBC, and Type II(222) as defined by NFPA 220, Standard on Types of Building Construction. As such, any new construction to Building 1 will need to match the existing construction type. This construction includes the roof of the Second Floor, which will meet 2-hrs.
All columns and beams are to have a 2 hour fire resistance rating. The roof assebly is to have a 1 hour fire resistance rating.
All stairs, elevators, and elevator machine rooms are enclosed in 2-hour fire-rated construction. A two-hour fire-rating is required as the floor is required to be 2-hour fire-rated.
Storage areas require 1hr fire rated construction as these rooms have a degree of hazard greater than that normal to the general occupancy of the building. Doors must be 3/4 hour rated, self-close and positive latch.
The design of this project is based on a fully sprinkler-protected, ambulatory healthcare occupancy. With the construction type and full sprinkler protection, the addition will meet the height and area requirements as outlined in Table 18.1.6.1 of the LSC.
Egress
As required by the VA, all egress components meet the requirements of the LSC. The Life Safety Plan illustrates that the exit arrangement requirements are met and exit capacity is adequate. Corridors to resist the passage of smoke as this area of work is in a healthcare occupancy. Corridor walls do not have to be considered a smoke barrier or a smoke partition per section A.18.3.6.2.3. The common path of travel is limited to 100 ft and the maximum path of travel is 200 ft.
The travel distance to smoke barrier must not exceed 100 ft. Dead end corridors are limited to 50 ft.
The “Ambulatory Health Care” Occupancy on the First Floor will have a common path of travel limit of 100 ft and maximum path of travel limit of 200 ft. These limits will be maintained during construction.
The stairs have 48-in min width with 48-in wide landings. The stairs have doors with a clear width of 32-in. The means of egress capacity is designed to 0.2 inches/person for level components and .3 inches/persons for stairs.
Exit signage and emergency lighting will be provided in accordance with Sections 7.9 and 7.10 of the LSC.
HVAC
HVAC systems will be designed in accordance with NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. Supply side duct detection will be provided for the two new roof mounted air handling units. Each unit has a nominal 8,500 CFM capacity.
Interior Finish
Interior finishes must meet the requirements of Chapter 10 of the LSC. With complete building sprinkler protection, interior wall and ceiling finishes within exits and exit access, corridors must have a Class A or B rating, and other rooms or spaces must have a minimum Class C rating. New floor coverings in exit access corridors and spaces open to them shall have at least a Class II rating.
exterior insulated finishing systemEIFS
SCALE: 1 1/2" = 1'-0"1-3-X2
1 PARTITION TYPES
SCALE:1 1/2"=1'-0"
4" 8"0 16"
CORRIDOR
A301A
CORRIDOR
A301A
SHARED CONFERENCE
A335 SHARED BREAK/ LKR
A334
CARDIOVASCULAR
WORKSTATIONS/ COPY
A311
TELECOM
A319ELEC.
A348
WORK STATION AREA 2
A330
EYE 3
A326
CONSULT/ VIEWING
A325
EYE 1/ WHEELCHAIR
STORAGE
A324
EYEGLASS FITTING &
DISPLAY
A332
VISUAL FIELDS TESTING
A331
OCT
A327
POLYTRAUMA
A328
LOW VISION
A329
STRESS ECHO
A317
EQUIP.
A333
PULMONARY REHAB
AREA/ EXTENDED PULM
FUNCTION/ CONSULT.
ROOM/ WAITING/
WHEELCHAIR
A340
ELEVATORS
EL1
STAIR 1
ST1
STAIR 2
ST2
Not Enclosed
BRIDGE
A300A
466 SF
LOBBY
A300
MEN'S
A349
WOMEN'S
A350
PRETEST/ EYE /
CHECK-IN
A322 PHOTO/ FUNDUS TEST
A323
8'- 0"
TRAVEL DISTANCE 92'
EX
IT
T
RA
VE
L
DI
ST
AN
CE
4'
TRAVEL DISTANCE 77'SUITE B
SUITE A
TRAVEL DISTANCE 97' TO EXIT
TRAVEL DISTANCE 92' TO EXIT
SUITE A SUITE B
SUITE A SUITE B
EXIT TRAVEL DISTANCE 101'
EXISTING STAIR WITH
2 HOUR FIRE RATED
ENCLOSURE
1 HOUR FIRE
RATING
LINEN
A305
CORRIDOR
A301B
DIALATION
A320
WAITING
A321
STORAGE & EQUIP
A336
NUTRITION
A310
TRAVEL DISTANCE 97'
1 HOUR FIRE
RATING
1 HOUR FIRE
RATING
EX
IT
T
RA
VE
L
DI
ST
AN
CE
3'
PODIATRY
E305
TOILET
E305A
PODIATRY
E307
CORRIDOR
E307A
TOILET
E308A
UROLOGY
E308
UROLOGY
E310
CORRIDOR
E310A
NURSE TRIAGE
E309
BREAK ROOM
E311
STAIR D
ES303
TOILET
E312A
NEUROLOGY
E312
EQUIPMENT ROOM
E313
PULMONOLOGY
E314H
GYNECOLOGY
E314G
TOILET/ CHANGING
ROOM
E314F
GYNECOLOGY
E314E
GENERAL SURGERY
E314D
GENERAL SURGERY
E314C
DIRTY ROOM
E314A EXAM ROOM
E302
NURSE TRIAGE
E306
CORRIDOR
E315A
PULMONARY WORK
STATION
A346
CORRIDOR
A301
F.E.C.
F.E.C.F.E.C.
F.
E.
C
F.
E.
C
F.
E.
C
F.
E.
C
F.
E.
C
F.E.C.
F.E.C.
EXAM / CONSULT
A306
EXAM / CONSULT
A308
EXAM / CONSULT
A309
EXAM RESTROOM
A307
EXAM/ PATIENT
EDUCATION
A314
EKG
A315ECHO/ CARDIO
A313
STORAGE
A312
CRASH CART
A317A
TOILET
A316
CORRIDOR
A318
STAFF CORRIDOR
A301C
HAC
A339
WAITING
A302
CRASH CART
A347
CO
M
M O
N
PA
TH
O
F
TR
AV
EL
5'
CO
M
M O
N
PA
TH
O
F
TR
AV
EL
8'
RESPIRATORY THERAPY/
CPAP
A341
PFT
A342
TREATMENT ROOM
A343
MED
A344
O2 STOR.
A345
EXISTING
STAIR WITH 2
HOUR RATED
ENCLOSURE
1 HR FIRE RATED WALL & SMOKE
BARRIER
2 HR FIRE RATED WALL & SMOKE
BARRIER
EXIT
EXIT SIGN
LIFE SAFETY LEGEND
FIRE EXTINGUISHER CABINETF.E.C.
TRAVEL PATH & DISTANCE
1/2 " M
AX
5/8" MIN. THICKNESS OF
FIRE STOP FILL
MATERIAL - BOTH
SIDES, SAND SMOOTH
NON - INSULATED
DUCT
1/2 " M
AX
5/8" MIN. THICKNESS OF
FIRE STOP FILL
MATERIAL - BOTH
SIDES, SAND SMOOTH
INSULATED DUCT
ONE LAYER OF MIN. 1/8" THICK
INTUMESCENT MATERIAL, SUPPLIED IN
2" WIDE STRIPS TIGHTLY WRAPPED
AROUND DUCT INSULATION AND HELD IN
PLACE WITH 2" WIDE MIN. 3 MIL FOIL
TAPE. WRAP STRIP SLID INTO ANNULUS
ON BOTH SIDES OF WALL SUCH THAT
WRAP STRIPS EXTEND APPROX. 1/2"
BEYOND BOTH SURFACES OF WALL.
EXPOSED PORTION OF WRAP STRIP TO
BE COMPLETELY COVERED WITH 3 MIL
FOIL TAPE.
1/2 " M
AX
5/8" MIN. THICKNESS OF
FIRE STOP FILL
MATERIAL - BOTH
SIDES, SAND SMOOTH
PIPE/ CONDUIT
1/2 " M
AX
5/8" MIN. THICKNESS OF
FIRE STOP FILL
MATERIAL - BOTH
SIDES, SAND SMOOTH
INSULATED PIPE
ONE LAYER OF MIN. 1/8" THICK
INTUMESCENT MATERIAL, SUPPLIED IN
2" WIDE STRIPS TIGHTLY WRAPPED
AROUND DUCT INSULATION AND HELD IN
PLACE WITH 2" WIDE MIN. 3 MIL FOIL
TAPE. WRAP STRIP SLID INTO ANNULUS
ON BOTH SIDES OF WALL SUCH THAT
WRAP STRIPS EXTEND APPROX. 1/2"
BEYOND BOTH SURFACES OF WALL.
EXPOSED PORTION OF WRAP STRIP TO
BE COMPLETELY COVERED WITH 3 MIL
FOIL TAPE.
FIRE - PROOFING TO BE
SPRAYED AROUND AND
COMPLETELY COAT ALL
STRUCTURAL MEMBERS,
MINIMUM THICKNESS OF
1 1/16"
CEILING/ FLOOR STRUCTURE -
SEE STRUCTURAL DRAWINGS
STRUCTURAL BEAM -
SEE STRUCTURAL
DRAWINGS
NOTES:
DETAIL BASED ON UL DESIGN D916
FIRE PROOFING TO BE A CONTINUOUS COATING WITH
OUT GAPS OR HOLES.
CONTRACTOR TO PROPERLY COVER AND PROTECT
ALL SURFACES NOT GETTING COATED WITH FIRE
PROOFING.
A301
A301
OT
GYM
10'-0" A.F.F.
DETAIL TAG
COLUMN LINE
BUBBLE TAG
CEILING
HEIGHT TAG
A-?
DWG NAME
SCALE:
SECTION TAG
ROOM TAG -
NEW WORK
WALL TYPE TAG
TITLE TAG
BREAKLINE
SYMBOL
INTERIOR ELEVATION
EXTERIOR
ELEVATION
ELEVATION MARK
FIRST FLOOR
DOOR TAG
CONSTRUCTION KEY
NOTE TAG
X
311.1
A201
125 SF
STOREFRONT
WINDOW TAG
S05
DETAIL
CALL-
OUT
TAG
A201
BASIC ARCHITECTURAL SYMBOLS
FIRE - PROOFING TO BE
SPRAYED AROUND AND
COMPLETELY COAT ALL
STRUCTURAL WIDE FLANGE
COLUMNS, MAINTAIN A
MINIMUM THICKNESS OF 1 3/8"BASED ON UL DESIGN
X795
NOTES:
DETAIL BASED ON UL DESIGN X796
FIRE PROOFING TO BE A CONTINUOUS COATING WITH
OUT GAPS OR HOLES.
CONTRACTOR TO PROPERLY COVER AND PROTECT
ALL SURFACES NOT GETTING COATED WITH FIRE
PROOFING.
NEW WALLS
EXISTING WALLS
TO REMAIN
NEW DOORS
EXISTING DOORS
TO REMAIN
GENERAL LEGEND
Project Title
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
Drawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
Additions:
Revisions:
1 5 6 7 8
21 3 4 5 6 7 8
A B
C D
E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot
DELLC
JOB No.
JAMES E. VAN ZANDT
VETERANS ADMINISTRATION
MEDICAL CENTER
2 3 4
Consultants:Date
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL CONSULTING
ENGINEERING
6300 BLAIR HILL LANE
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 500
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009
ARCHITECTURE
PLANNING
ENGINEERING
KEY PLAN
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
100% CONSTRUCTION
DOCUMENTS
WHITMAN, REQUARDT & ASSOCIATES, LLP
CIVIL ENGINEERING
801 South Caroline Street Baltimore, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR ASSOCIATES
AUTOMATIC TRANSPORT ENGINEERING
182 THOMOS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
160702D
FULLY SPRINKLERED
2907 PLEASANT VALLEY BLVD. ALTOONA, PA 16602-4377
LIFE SAFETY PLANS – THIRD
FLOOR
EXPAND FOR SPECIALTY
CLINIC ADDITION ON 3RD
FLOOR
CP/ CAJ JSK/ DGW/ WPH
11/20/2018
1-3-X3
503-314
SCALE: 1/8" = 1'-0"1-3-X3
1 LIFE SAFETY PLAN
NOTES:
1. OCCUPANCY IS HEALTHCARE
2. SUITE A = 4,967 sf
3. SUITE B = 6,280 sf
4. ALL NEW AND EXISTING CONSTRUCTION IS FULLY SPRINKLED
PLAN NORTH
TRUE NORTH
OCCUPANT LOAD
ALLOWED : 100 GSF / OCCUPANT
SUITE A : 50 OCCUPANTS
SUITE B : 63 OCCUPANTS
EGRESS CAPACITY
ALLOWED - LEVEL : .2 INCHES / OCCUPANT
ALLOWED - STAIRS : .3 INCHES / OCCUPANT
SUITE A :
50 OCCUPANTS X .2" = 10" REQUIRED EGRESS WIDTH
TOTAL EXITS : 3
TOTAL EXIT WIDTH : 192"
SUITE B :
63 OCCUPANTS X .2" = 13" REQUIRED EGRESS WIDTH
TOTAL EXITS : 3
TOTAL EXIT WIDTH : 240"
SCALE: 1 1/2" = 1'-0"1-3-X3
4 WALL PENTRATION DETAILS
SCALE: 1 1/2" = 1'-0"1-3-X3
TYPICAL FLOOR/CEILING FIRE
PROOFING
SCALE: 1/8" = 1'-0"
4'-0" 8'-0"0 16'-0"
SCALE:1 1/2"=1'-0"
4" 8"0 16"
SCALE: 1 1/2" = 1'-0"1-3-X3
TYPICAL COLUMN FIRE RATING
DETAILS
T
T
T
T
APPROXIMATE LOCATION OF
LIMITS OF WORK AND PLASTIC
TENTING
ENTRANCE TO WORK AREA
FAN UNITS TO CREATE
NEGATIVE PRESSURE
ADHESIVE WALK OFF MATT
1 HR. TEMPORARY
CONSTRUCTION BARRIER
ICRA LEGEND
OO1
B6
B7
B8
TT B-K L B-MB-H
AA
BB
A.7
A.8
GENERAL SURGERY
E314C
TOILET
E314B DIRTY ROOM
E314A
WAITING ROOM
E314
TOILET
E315
SUPPLY CLOSET
E316
CLERICAL STAFF
E300A
NURSE TRIAGE
E301
EXAM ROOM
E302
CORRIDOR
E304
NEW NURSE TRIAGE
E303
E303 E302
2'-1"
6'-0"
T-
T-
SEAL BOTTOM
OF THE WALL
FLOOR FINISH -
SEE FINISH
SCHEDULE
STRUCTURAL
DECK ABOVE
CEILING
3 5/8" METAL
STUD FRAMING
@ 16" O.C.
5/8" GYPSUM
WALLBOARD
(BOTH SIDES)
4 7/8"
1 HR TEMPORARY
CONSTRUCTION/ ICRA BARRIERS
BASED ON UL DESIGN U419
SEAL TOP OF
THE WALL
D
A
E F G
H
JH.1 KJ.7
1.8
7.7
8.9
9.1
B
C
2.5
1.3
9.4
5.8
YXX.1
7.1
AA
BB
C2
A.4
Project Title
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
Drawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
Additions:
Revisions:
1 5 6 7 8
21 3 4 5 6 7 8
A B
C D
E on e-qu ar te r i nc h on e fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot th re e in ch es o ne fo ot
DELLC
JOB No.
JAMES E. VAN ZANDT
VETERANS ADMINISTRATION
MEDICAL CENTER
2 3 4
Consultants:Date
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL CONSULTING
ENGINEERING
6300 BLAIR HILL LANE
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 500
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
Bel Air, Maryland 21015-1436 2215 Conowingo Rd, Suite 100 fax 410.836.6611 410.803.0009
ARCHITECTURE
PLANNING
ENGINEERING
KEY PLAN
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
100% CONSTRUCTION
DOCUMENTS
WHITMAN, REQUARDT & ASSOCIATES, LLP
CIVIL ENGINEERING
801 South Caroline Street Baltimore, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR ASSOCIATES
AUTOMATIC TRANSPORT ENGINEERING
182 THOMOS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
160702D
FULLY SPRINKLERED
2907 PLEASANT VALLEY BLVD. ALTOONA, PA 16602-4377
2ND FLOOR DEMOLITION
AND ICRA DRAWING
EXPAND FOR SPECIALTY
CLINIC ADDITION ON 3RD
FLOOR
CP/ CAJ JSK/ DGW/ WPH
11/20/2018
1-3-X4
503-314
SCALE: 1/8" = 1'-0"1-3-X4
EXISTING HOSPITAL THIRD FLOOR -
NEW WORK - ICRA PLAN
SCALE: 1 1/2" = 1'-0"1-3-X4
3 CONSTRUCTION PARTITION
SCALE: 1/8" = 1'-0"1-3-X4
1 SECOND FLOOR - ICRA PLAN
NOTES:
1. PLASTIC TENTING TO EXTEND FROM FLOOR TO DECKING
ABOVE.
2. CONTRACTOR TO COORDINATE THE MOVING AND STORING
OF ANY FURNITURE TO BE TEMPORARILY RELOCATED.
3. ALL EXISTING FURNITURE TO REMAIN IS TO BE COVERED
AND PROTECTED DURING WORK.
4. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
REPLACE ALL WALLS, MILLWORK FINISHES, ELECTRICAL, I.T.,
PLUMBING AND FIXTURES AS THEY WERE PRIOR TO
DEMOLITION.
5. CONTRACTOR TO PROTECT ALL EXISTING FINISHES DURING
DEMOLITION AND CONSTRUCTION. CONTRACTOR TO REPAIR
ANY DAMAGE TO EXISTING FINISHES. ALL NEW AND
REPLACED FINISHES ARE TO MATCH EXISTING.
6. CONTRACTOR MAY TEMPORARILY REMOVE ANY HANDRAILS
OR OTHER FINISHES WITH VA APPROVAL. ALL REMOVED
HANDRAILS AND FINISHES ARE TO BE PUT BACK IN THEIR
ORIGINAL POSITION, CLEANED & RESTORED TO THEIR PRE-
CONSTRUCTION CONDITION.
7. CONTRACTOR TO NOTIFY AND RECEIVE PERMISSION FROM
COR BEFORE DEMOLISHING ANY PART OF THE EXISTING
BUILDING THAT IS NOT COVERED IN THE DEMOLITION
DRAWINGS.
8. CONTRACTOR TO FIX ANY DAMAGE TO EXISTING FINISHES
CAUSED BY CREWS DURING DEMOLITION OR CONSTRUCTION
9. CONTRACTOR TO PAINT ALL NEW WORK AND VARIOUS
PATCHES TO MATCH THE EXISTING CONDITIONS, OR AS
DIRECTED BY THE VA. IF AN EXACT PAINT MATCH CAN NOT BE
MADE, THE CONTRACTOR MUST PAINT THE ENTIRE WALL
CORNER TO CORNER, FLOOR TO CEILING WITH NEW PAINT
THAT IS A CLOSE MATCH OR A COMPLIMENTARY COLOR. ALL
SURFACES NOT BEING PAINTED ARE TO BE PROTECTED. SEE
FINISH SCHEDULE FOR MORE PAINT INFORMATION.
10. CONTRACTOR TO COORDINATE NOISE GENERATING
ACTIVITIES WITH COR PRIOR TO CONSTRUCTION START; ALL
EXCESSIVELY LOUD OPERATIONS WILL NEED TO BE
ACCOMPLISHED AFTER NORMAL WORKING HOURS.
11. TRASH REMOVAL AND MATERIAL DELIVERIES SHALL BE
LIMITED TO SPECIFIC HOURS AS DIRECTED AND
COORDINATED WITH THE COR.
12. ALL TEMPORARY CONSTRUCTION BARRIERS, DOORS AND
FRAMES SHALL HAVE A 1 HOUR FIRE RATING.
PLAN NORTH
TRUE NORTH
FIRST FLOOR
EL. 1135.60
3'
HEDGE
3'
HB
HEDGE
1134.11
WALL
2'
4'
HEDGE
4'
HEDGE
2'
5'
HEDGE
1127.33
WALL
EMH(1274)
TOP:1127.26
E
6'
1126.39
WALL
3"
5'
WALL
SWL
3"
2'
2"
CEDAR
2'
2"
CEDAR
4'
2"
CEDAR
3'
T
1127.30
C
O
N
C
W
A
L
L
P
V
C
I
N
V
P
V
C
P
V
C
P
V C
I
P
SSMH
TOP=1134.06
b a c
SSMH
TOP=1134.01
METAL FENCE
SMOKE SHELTER
I
N
L
E
T
T
O
P
I
N
V
U
**NOTE**
FIRST FLOOR ELEVATION FOR
INFORMATIONAL PURPOSES ONLY.
THE SURVEYED AND VERIFIED FIRST
FLOOR ELEVATION = 1135.60. ALL
DRAWINGS, HOWEVER, ARE SHOWN
AT 1136.00 AND SHALL BE USED FOR
CONSTRUCTION PURPOSES.
BUILDING #01
TEMPORARY CONSTRUCTION
FENCE AND LIMITS OF
CONTRACTOR ACCESS (SEE
DETAIL SHEET L3)
3'
UGUNKUTIL
3'
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
2'
8" PVC
2'
UGUNKUTIL
8" PVC
I
N
L
E
T
T
I
N
BUILDING #01
5.2500
5.0000
E
X
S
D
E
W
A
L
K
Project TitleDrawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
1 5 6 7 8
21 3 4 5 6 7 8
A B
C D
E
DELLC
JOB No.
2 3 4
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL CONSULTING
ENGINEERING
1416 CLARKVIEW ROAD
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 500
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
KEY PLAN
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
WHITMAN, REQUARDT & ASSOCIATES,
LLP
CIVIL ENGINEERING
801 South Caroline Street
Baltimore, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR ASSOCIATES
AUTOMATIC TRANSPORT ENGINEERING
182 THOMOS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
160702D
ARCHITECTURE
PLANNING
ENGINEERING
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
01/15/2019
503-314
EXPAND FOR SPECIALTY
CLINIC ADDITION
100% CONSTRUCTION DOCUMENTS
FULLY SPRINKLED
LEGEND
EXISTING PROPOSEDDESCRIPTION
BUILDING
TREE
INLET
SANITARY
MANHOLE
LIGHT POLE
CONCRETE
SIDEWALK
STORM DRAIN
MANHOLE
SANITARY SEWER
GENERAL NOTES
1. UNLESS OTHERWISE NOTED, ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST VETERAN'S ADMINISTRATION SPECIFICATIONS AND DETAILS.
2. NOTIFY OWNER FORTY EIGHT (48) HOURS PRIOR TO COMMENCING WORK.
3. EXISTING SITE AND UTILITY FEATURES, INCLUDING HORIZONTAL AND VERTICAL LOCATIONS, ARE BASED ON PREVIOUS DESIGN PLANS FROM PROJECT NO. 503-308
AND WERE NOT FIELD LOCATED. THE CORRECTNESS OR COMPLETENESS OF THE INFORMATION SHOWN IS NOT GUARANTEED. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING EXISTING FEATURES TO HIS OWN SATISFACTION PRIOR TO ORDERING MATERIALS. CONTRACTOR SHALL REPORT ANY
DISCREPANCIES TO THE ENGINEER. THE CONTRACTOR SHALL PROVIDE A THIRD PARTY LOCATOR TO VERIFY EXISTING UTILITIES.
4. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY ALL UTILITY COMPANIES, ALL PIPELINE OWNERS, OR OTHER PARTIES AFFECTED WITHIN THE
CONSTRUCTION AREA AT LEAST 48 HOURS PRIOR TO COMMENCING WORK.
5. CONTRACTOR SHALL PROTECT ALL EXISTING UTILITIES DURING CONSTRUCTION. EXISTING UTILITIES WHICH ARE NOT TO BE REMOVED OR ABANDONED SHALL
REMAIN OPERATIONAL AT ALL TIMES.
6. SHOULD EXISTING CONDITIONS IN THE FIELD NECESSITATE CONSTRUCTION METHODS OR MEANS OTHER THAN THOSE SHOWN OR SPECIFIED ON THESE PLANS, THE CONTRACTOR SHALL NOTIFY THE OWNER TO OBTAIN APPROVAL PRIOR TO PROCEEDING WITH CONSTRUCTION.
7. EROSION AND SEDIMENT CONTROL MEASURES SHALL BE UTILIZED, IN ACCORDANCE WITH THE LATEST EDITION OF THE PENNSYLVANIA DEPARTMENT OF
ENVIRONMENTAL PROTECTION EROSION AND SEDIMENT POLLUTION CONTROL PROGRAM MANUAL.
8. ALL EROSION AND SEDIMENT CONTROL MEASURES SHALL BE MAINTAINED THROUGHOUT THE CONSTRUCTION PHASE. ANY DAMAGED DEVICES SHALL BE
REPAIRED OR REPLACED AT THE END OF EACH WORK DAY BEFORE LEAVING THE SITE.
9. ALL DISTURBED AREAS SHALL BE RESTORED TO THE ORIGINAL CONDITION OR BETTER.
10. THE CONTRACTOR SHALL FOLLOW SAME-DAY STABILIZATION PRACTICES FOR ALL UTILITY INSTALLATION. ONLY THE AMOUNT OF TRENCH THAT CAN BE OPENED, WORKED IN, AND THEN STABILIZED IN A WORK DAY SHALL BE PERFORMED. IF STABILIZATION DOES NOT OCCUR AT THE END OF THE WORK DAY, THEN
APPROPRIATE EROSION CONTROLS, SEDIMENT CONTROLS, AND SAFETY CONTROLS SHALL BE INSTALLED.
11. POSITIVE DRAINAGE SHALL BE MAINTAINED AT ALL TIMES. PONDING OF WATER SHALL NOT BE PERMITTED.
12. ANY DAMAGE OUTSIDE OF THE LIMITS OF DISTURBANCE INCLUDING THE CONSTRUCTION ACCESS SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. METAL
PLATES MAY BE UTILIZED TO PROTECT EXISTING FEATURES.
13. SURROUNDING FACILITIES ARE TO REMAIN IN OPERATION DURING CONSTRUCTION. ALL WORK SHALL BE CONDUCTED SO AS TO MINIMIZE DISRUPTION TO THOSE
FACILITIES.
14. THE CONTRACTOR SHALL MAINTAIN TRAFFIC AT ALL TIMES. PEDESTRIAN THRUWAY TRAFFIC AND ACCESS TO ALL BUILDINGS IS TO BE MAINTAINED AT ALL TIMES.
THE CONTRACTOR SHALL PROVIDE THE APPROPRIATE PROTECTIONS INCLUDING PEDESTRIAN SAFETY AND DIRECTIONAL SIGNS DURING ALL PHASES OF
DEMOLITION AND CONSTRUCTION. PLAN MUST BE APPROVED BY COR BEFORE CONSTRUCTION.
15. SURFACED STREETS AND PARKING AREAS SHALL BE MAINTAINED IN A CLEAN CONDITION, MUD AND DUST FREE AT ALL TIMES. ADEQUATE MEANS SHALL BE
PROVIDED TO CLEAN TRUCKS AND EQUIPMENT. ALL TOOLS AND EQUIPMENT SHALL BE STORED WITHIN THE CONTRACTOR'S STAGING AREA.
16. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE AND RECYCLE WHERE POSSIBLE OR LEGALLY DISPOSE OF ANY AND ALL
DEMOLISHED/DELETERIOUS MATERIALS.
17. EXISTING CONCRETE SIDEWALK SHALL BE SAWCUT PRIOR TO REMOVAL. ALL SAWCUTS SHALL BE STRAIGHT, EVEN CUTS. JAGGED EDGES SHALL NOT BE
PERMITTED.
18. NUMERICALLY WRITTEN DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS.
19. REFER TO ARCHITECTURAL DRAWINGS FOR BUILDING DIMENSIONS.
20. THE CONTRACTOR SHALL MAINTAIN 2.0 FEET MINIMUM COVER OVER ALL UTILITIES DURING CONSTRUCTION.
21. UNLESS OTHERWISE NOTED, ALL FRAMES AND COVERS ARE TO BE SET TO FINISHED GRADE.
22. PRIOR TO CONNECTING TO ANY EXISTING PIPE, THE CONTRACTOR SHALL VERIFY THE TYPE OF PIPE, JOINT TYPE, AND HORIZONTAL AND VERTICAL LOCATIONS HE
IS TO CONNECT TO AT THE LOCATIONS INDICATED. THE CONTRACTOR SHALL PROVIDE THE REQUIRED ADAPTERS, SLEEVES, AND/OR COUPLINGS NECESSARY TO
CONNECT TO THE EXISTING PIPE.
23. ALL PIPES SHALL BE CLEANED BEFORE THEY ARE LAID AND SHALL BE KEPT CLEAN UNTIL ACCEPTANCE OF THE COMPLETED WORK BY THE OWNER. OPEN ENDS OF
PIPES SHALL BE FITTED WITH WATERTIGHT STOPPERS TO PREVENT ENTRANCE OF FOREIGN MATTER WHEN PIPE-LAYING OPERATIONS ARE INTERRUPTED.
24. IT IS DISTINCTLY UNDERSTOOD THAT FAILURE TO MENTION SPECIFICALLY ANY WORK THAT WOULD NORMALLY BE REQUIRED TO COMPLETE THIS PROJECT SHALL
NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITY TO PERFORM SUCH WORK.
25. CONTRACTOR SHALL PROVIDE THIRD PARTY UTILITY LOCATOR TO TEST PIT AND VERIFY LOCATIONS OF ALL UTILITIES PRIOR TO CONSTURCTION. IMMEDIATELY
NOTIFY THE ENGINEER OF RECORD OF ANY DISCREPENCIES.
26. ALL WORK SHALL BE PERFORMED TO THE SATISFACTION OF THE OWNER.
27. ANY CRANE LIFT TO BE COMPLETED OFF HOURS AND COORDINATED WITH COR.
28. ALL AREAS OUTSIDE OF THE LOD AND CONTRACTOR ACCESS/STAGING AREAS WILL NOT BE MADE AVAILABLE FOR CONTRACTOR USE UNLESS OTHERWISE
APPROVED BY THE COR. SIDEWALKS OUTSIDE THE LOD AND CONTRACTOR ACCESS/STAGING AREA WILL REMAIN IN OPERATION DURING CONSTRUCTION.
29. THE FOLLOWING PLANS MUST BE REVIEWED AND APPROVED THE COR PRIOR TO CONSTRUCTION, REFER TO THE GENERAL CONDITIONS:
A. CONSTRUCTION VEHICLE AND CRANE ACCESS PLAN
B. UTILITY PROTECTION PLAN
C. CONCRETE WASH BOX LOCATION AND METHOD PLAN
D. CONSTRUCTION FENCING AND PEDESTRIAN ACCESS/SIGNAGE PLAN
30. CONTRACTOR TO KEEP CONSTRUCTION AREA LOCKED AT ALL TIMES. FENCE AREAS ENCOMPASSING CONSTRUCTION AREA SHALL BE PROVIDED WITH A MEANS OF
ENTRY AND SECURED BY A LOCK. ALL LOCKS KEYED ALIKE WITH (2) TWO COPIES OF KEY PROVIDED TO THE COR. OR ALL LOCKS PROVIDED WITH SAME
COMBINATION.
31. THE CONTRACTOR IS RESPONSIBLE TO REPAIR/REPLACE AND AND ALL EXISTING FEATURES (INCLUDING BUT NOT LIMITED TO CONCRETE, ASPHALT, CURB AND
GUTTER, AND PAVEMENT MARKINGS) DAMAGED DURING CONSTRUCTION TO THE PRE-CONSTRUCTION CONDITION AND TO THE SATISFACTION OF THE COR.
SIDEWALK
DEMOLITION
LIMIT OF DISTURBANCE
STORM DRAIN
WATER LINE
ELECTRIC LINE
FIBER OPTIC LINE
ELECTRICAL DUCTBANK
REMOVE EXISTING
SIDEWALK
REMOVE EXISTING
LANDSCAPING
REMOVE
EXISTING DOOR
ACCESS BUTTON AND
ASSOCIATED
EQUIPMENT
PLAN NORTH
TRUE NORTH
EXISTING CONDITIONS/
DEMOLITION PLAN
THIS PROJECT IS UNDER 5,000SF OF DISTURBANCE AND DOES NOT REQUIRE A STORMWATER
MANAGEMENT PERMIT BY THE PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION . THE
CONTRACTOR IS TO MAINTAIN THESE A LIMITS AND NOTIFY THE ENGINEER OF RECORD SHOULD ANY
DISTURBANCE OUTSIDE THE SHOWN LIMITS BECOME NECESSARY DUE TO UNFORESEEN CONDITIONS.
TEMPORARY CONSTRUCTION FENCE
AND LIMITS OF CONTRACTOR ACCESS
PHASE 1 - SEE
PHASING PLAN
ADDITIONAL
CONTRACTOR
ACCESS/STAGING
AREA
FIRST FLOOR
EL. 1135.60
3'
HEDGE
3'
HB
HEDGE
1134.11
WALL
2'
4'
HEDGE
4'
HEDGE
2'
5'
HEDGE
1127.33
WALL
EMH(1274)
TOP:1127.26
E
6'
1126.39
WALL
3"
5'
WALL
SWL
3"
2'
2"
CEDAR
2'
2"
CEDAR
4'
2"
CEDAR
3'
T
1127.30
C
O
L
L
P
V
C
I
N
V
P
V
C
P
V
C
P
V C
P
SSMH
TOP=1134.06
b a c
SSMH
TOP=1134.01
METAL FENCE
SMOKE SHELTER
L
C
P
P
C
P
P
D
R
R
I
C
P
P
I
N
L
E
T
T
I
N
**NOTE**
FIRST FLOOR ELEVATION FOR
INFORMATIONAL PURPOSES ONLY.
THE SURVEYED AND VERIFIED FIRST
FLOOR ELEVATION = 1135.60. ALL
DRAWINGS, HOWEVER, ARE SHOWN
AT 1136.00 AND SHALL BE USED FOR
CONSTRUCTION PURPOSES.
BUILDING #01
TEMPORARY CONSTRUCTION
FENCE AND LIMITS OF
CONTRACTOR ACCESS (SEE
DETAIL SHEET L3)
3'
UGUNKUTIL
3'
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
2'
8" PVC
2'
UGUNKUTIL
8" PVC
I
N
L
E
T
T
I
N
BUILDING #01
Project TitleDrawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
1 5 6 7 8
21 3 4 5 6 7 8
A B
C D
E
DELLC
JOB No.
2 3 4
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL CONSULTING
ENGINEERING
1416 CLARKVIEW ROAD
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 500
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
KEY PLAN
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
WHITMAN, REQUARDT & ASSOCIATES,
LLP
CIVIL ENGINEERING
801 South Caroline Street
Baltimore, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR ASSOCIATES
AUTOMATIC TRANSPORT ENGINEERING
182 THOMOS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
160702D
ARCHITECTURE
PLANNING
ENGINEERING
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
11/22/2017
503-314
EXPAND FOR SPECIALTY
CLINIC ADDITION
100% CONSTRUCTION DOCUMENTS
FULLY SPRINKLED
LEGEND
EXISTING PROPOSEDDESCRIPTION
BUILDING
TREE
INLET
SANITARY
MANHOLE
LIGHT POLE
CONCRETE
SIDEWALK
STORM DRAIN
MANHOLE
SANITARY SEWER
GENERAL NOTES
1. UNLESS OTHERWISE NOTED, ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST VETERAN'S ADMINISTRATION SPECIFICATIONS AND DETAILS.
2. NOTIFY OWNER FORTY EIGHT (48) HOURS PRIOR TO COMMENCING WORK.
3. EXISTING SITE AND UTILITY FEATURES, INCLUDING HORIZONTAL AND VERTICAL LOCATIONS, ARE BASED ON PREVIOUS DESIGN PLANS FROM PROJECT NO. 503-308
AND WERE NOT FIELD LOCATED. THE CORRECTNESS OR COMPLETENESS OF THE INFORMATION SHOWN IS NOT GUARANTEED. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING EXISTING FEATURES TO HIS OWN SATISFACTION PRIOR TO ORDERING MATERIALS. CONTRACTOR SHALL REPORT ANY
DISCREPANCIES TO THE ENGINEER. THE CONTRACTOR SHALL PROVIDE A THIRD PARTY LOCATOR TO VERIFY EXISTING UTILITIES.
4. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY ALL UTILITY COMPANIES, ALL PIPELINE OWNERS, OR OTHER PARTIES AFFECTED WITHIN THE
CONSTRUCTION AREA AT LEAST 48 HOURS PRIOR TO COMMENCING WORK.
5. CONTRACTOR SHALL PROTECT ALL EXISTING UTILITIES DURING CONSTRUCTION. EXISTING UTILITIES WHICH ARE NOT TO BE REMOVED OR ABANDONED SHALL
REMAIN OPERATIONAL AT ALL TIMES.
6. SHOULD EXISTING CONDITIONS IN THE FIELD NECESSITATE CONSTRUCTION METHODS OR MEANS OTHER THAN THOSE SHOWN OR SPECIFIED ON THESE PLANS, THE CONTRACTOR SHALL NOTIFY THE OWNER TO OBTAIN APPROVAL PRIOR TO PROCEEDING WITH CONSTRUCTION.
7. EROSION AND SEDIMENT CONTROL MEASURES SHALL BE UTILIZED, IN ACCORDANCE WITH THE LATEST EDITION OF THE PENNSYLVANIA DEPARTMENT OF
ENVIRONMENTAL PROTECTION EROSION AND SEDIMENT POLLUTION CONTROL PROGRAM MANUAL.
8. ALL EROSION AND SEDIMENT CONTROL MEASURES SHALL BE MAINTAINED THROUGHOUT THE CONSTRUCTION PHASE. ANY DAMAGED DEVICES SHALL BE
REPAIRED OR REPLACED AT THE END OF EACH WORK DAY BEFORE LEAVING THE SITE.
9. ALL DISTURBED AREAS SHALL BE RESTORED TO THE ORIGINAL CONDITION OR BETTER.
10. THE CONTRACTOR SHALL FOLLOW SAME-DAY STABILIZATION PRACTICES FOR ALL UTILITY INSTALLATION. ONLY THE AMOUNT OF TRENCH THAT CAN BE OPENED, WORKED IN, AND THEN STABILIZED IN A WORK DAY SHALL BE PERFORMED. IF STABILIZATION DOES NOT OCCUR AT THE END OF THE WORK DAY, THEN
APPROPRIATE EROSION CONTROLS, SEDIMENT CONTROLS, AND SAFETY CONTROLS SHALL BE INSTALLED.
11. POSITIVE DRAINAGE SHALL BE MAINTAINED AT ALL TIMES. PONDING OF WATER SHALL NOT BE PERMITTED.
12. ANY DAMAGE OUTSIDE OF THE LIMITS OF DISTURBANCE INCLUDING THE CONSTRUCTION ACCESS SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. METAL
PLATES MAY BE UTILIZED TO PROTECT EXISTING FEATURES.
13. SURROUNDING FACILITIES ARE TO REMAIN IN OPERATION DURING CONSTRUCTION. ALL WORK SHALL BE CONDUCTED SO AS TO MINIMIZE DISRUPTION TO THOSE
FACILITIES.
14. THE CONTRACTOR SHALL MAINTAIN TRAFFIC AT ALL TIMES. PEDESTRIAN THRUWAY TRAFFIC AND ACCESS TO ALL BUILDINGS IS TO BE MAINTAINED AT ALL TIMES.
THE CONTRACTOR SHALL PROVIDE THE APPROPRIATE PROTECTIONS INCLUDING PEDESTRIAN SAFETY AND DIRECTIONAL SIGNS DURING ALL PHASES OF
DEMOLITION AND CONSTRUCTION. PLAN MUST BE APPROVED BY COR BEFORE CONSTRUCTION.
15. SURFACED STREETS AND PARKING AREAS SHALL BE MAINTAINED IN A CLEAN CONDITION, MUD AND DUST FREE AT ALL TIMES. ADEQUATE MEANS SHALL BE
PROVIDED TO CLEAN TRUCKS AND EQUIPMENT. ALL TOOLS AND EQUIPMENT SHALL BE STORED WITHIN THE CONTRACTOR'S STAGING AREA.
16. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE AND RECYCLE WHERE POSSIBLE OR LEGALLY DISPOSE OF ANY AND ALL
DEMOLISHED/DELETERIOUS MATERIALS.
17. EXISTING CONCRETE SIDEWALK SHALL BE SAWCUT PRIOR TO REMOVAL. ALL SAWCUTS SHALL BE STRAIGHT, EVEN CUTS. JAGGED EDGES SHALL NOT BE
PERMITTED.
18. NUMERICALLY WRITTEN DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS.
19. REFER TO ARCHITECTURAL DRAWINGS FOR BUILDING DIMENSIONS.
20. THE CONTRACTOR SHALL MAINTAIN 2.0 FEET MINIMUM COVER OVER ALL UTILITIES DURING CONSTRUCTION.
21. UNLESS OTHERWISE NOTED, ALL FRAMES AND COVERS ARE TO BE SET TO FINISHED GRADE.
22. PRIOR TO CONNECTING TO ANY EXISTING PIPE, THE CONTRACTOR SHALL VERIFY THE TYPE OF PIPE, JOINT TYPE, AND HORIZONTAL AND VERTICAL LOCATIONS HE
IS TO CONNECT TO AT THE LOCATIONS INDICATED. THE CONTRACTOR SHALL PROVIDE THE REQUIRED ADAPTERS, SLEEVES, AND/OR COUPLINGS NECESSARY TO
CONNECT TO THE EXISTING PIPE.
23. ALL PIPES SHALL BE CLEANED BEFORE THEY ARE LAID AND SHALL BE KEPT CLEAN UNTIL ACCEPTANCE OF THE COMPLETED WORK BY THE OWNER. OPEN ENDS OF
PIPES SHALL BE FITTED WITH WATERTIGHT STOPPERS TO PREVENT ENTRANCE OF FOREIGN MATTER WHEN PIPE-LAYING OPERATIONS ARE INTERRUPTED.
24. IT IS DISTINCTLY UNDERSTOOD THAT FAILURE TO MENTION SPECIFICALLY ANY WORK THAT WOULD NORMALLY BE REQUIRED TO COMPLETE THIS PROJECT SHALL
NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITY TO PERFORM SUCH WORK.
25. CONTRACTOR SHALL PROVIDE THIRD PARTY UTILITY LOCATOR TO TEST PIT AND VERIFY LOCATIONS OF ALL UTILITIES PRIOR TO CONSTURCTION. IMMEDIATELY
NOTIFY THE ENGINEER OF RECORD OF ANY DISCREPENCIES.
26. ALL WORK SHALL BE PERFORMED TO THE SATISFACTION OF THE OWNER.
27. ANY CRANE LIFT TO BE COMPLETED OFF HOURS AND COORDINATED WITH COR.
28. ALL AREAS OUTSIDE OF THE LOD AND CONTRACTOR ACCESS/STAGING AREAS WILL NOT BE MADE AVAILABLE FOR CONTRACTOR USE UNLESS OTHERWISE
APPROVED BY THE COR. SIDEWALKS OUTSIDE THE LOD AND CONTRACTOR ACCESS/STAGING AREA WILL REMAIN IN OPERATION DURING CONSTRUCTION.
29. THE FOLLOWING PLANS MUST BE REVIEWED AND APPROVED THE COR PRIOR TO CONSTRUCTION, REFER TO THE GENERAL CONDITIONS:
A. CONSTRUCTION VEHICLE AND CRANE ACCESS PLAN
B. UTILITY PROTECTION PLAN
C. CONCRETE WASH BOX LOCATION AND METHOD PLAN
D. CONSTRUCTION FENCING AND PEDESTRIAN ACCESS/SIGNAGE PLAN
30. CONTRACTOR TO KEEP CONSTRUCTION AREA LOCKED AT ALL TIMES. FENCE AREAS ENCOMPASSING CONSTRUCTION AREA SHALL BE PROVIDED WITH A MEANS OF
ENTRY AND SECURED BY A LOCK. ALL LOCKS KEYED ALIKE WITH (2) TWO COPIES OF KEY PROVIDED TO THE COR. OR ALL LOCKS PROVIDED WITH SAME
COMBINATION.
31. THE CONTRACTOR IS RESPONSIBLE TO REPAIR/REPLACE AND AND ALL EXISTING FEATURES (INCLUDING BUT NOT LIMITED TO CONCRETE, ASPHALT, CURB AND
GUTTER, AND PAVEMENT MARKINGS) DAMAGED DURING CONSTRUCTION TO THE PRE-CONSTRUCTION CONDITION AND TO THE SATISFACTION OF THE COR.
SIDEWALK
DEMOLITION
LIMIT OF DISTURBANCE
STORM DRAIN
WATER LINE
ELECTRIC LINE
FIBER OPTIC LINE
ELECTRICAL DUCTBANK
REMOVE EXISTING
SIDEWALK
REMOVE EXISTING
LANDSCAPING
REMOVE
EXISTING DOOR
ACCESS BUTTON AND
ASSOCIATED
EQUIPMENT
PLAN NORTH
TRUE NORTH
EXISTING CONDITIONS/
DEMOLITION PLAN
THIS PROJECT IS UNDER 5,000SF OF DISTURBANCE AND DOES NOT REQUIRE A STORMWATER
MANAGEMENT PERMIT BY THE PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION . THE
CONTRACTOR IS TO MAINTAIN THESE A LIMITS AND NOTIFY THE ENGINEER OF RECORD SHOULD ANY
DISTURBANCE OUTSIDE THE SHOWN LIMITS BECOME NECESSARY DUE TO UNFORESEEN CONDITIONS.
TEMPORARY CONSTRUCTION FENCE
AND LIMITS OF CONTRACTOR ACCESS
PHASE 1 - SEE
PHASING PLAN
ADDITIONAL
CONTRACTOR
ACCESS/STAGING
AREA
V
C
T
V
C
T
V
C
T
V
C
T
V
C
T
V
C
T
V
F
O
F
O
F
O
F
O
FIRST FLOOR
EL. 1135.60
W
W
W
HB
EMH(1274)
TOP:1127.26
E
T
P
V
C
I
N
V
P
V
C
P
V
C
P
V C
P
SSMH
TOP=1134.06
b a c
SSMH
TOP=1134.01
METAL FENCE
SMOKE SHELTER
BUILDING #01
TEMPORARY CONSTRUCTION FENCE AND
LIMITS OF CONTRACTOR ACCESS (SEE
DETAIL SHEET L3)
APPROXIMATE LOCATION FOR
CONTRACTOR'S CONCRETE WASH BOX,
CONFIRM LOCATION AND METHODS WITH
COR PRIOR TO CONSTRUCTION
1135.60
1135.60
1135.55
1135.55
1135.51
1135.46
EX INLET
TOP 1134.82
INV OUT 1131.82
10'-8" WALKWAY
SEE ARCHITECTURAL DWGS
6" HDPE
STORMDRAIN
INV. 1131.92
6" HDPE
STORMDRAIN
REFER TO PLUMBING DWGS
FOR DOWNSPOUT DETAIL
DOOR ACCESS PEDESTAL
(SEE ELECTRICAL DWGS)
ADJUST CONSTRUCTION FENCE
AS NEEDED TO CONSTRUCT
PROPOSED SIDEWALK.
L-3
6' WIDE CONCRETE
SIDEWALK
L-3
5' WIDE CONCRETE
SIDEWALK
Project TitleDrawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
1 5 6 7 8
21 3 4 5 6 7 8
A B
C D
E
DELLC
JOB No.
2 3 4
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL CONSULTING
ENGINEERING
1416 CLARKVIEW ROAD
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 500
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
KEY PLAN
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
WHITMAN, REQUARDT & ASSOCIATES,
LLP
CIVIL ENGINEERING
801 South Caroline Street
Baltimore, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR ASSOCIATES
AUTOMATIC TRANSPORT ENGINEERING
182 THOMOS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
160702D
ARCHITECTURE
PLANNING
ENGINEERING
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
01/15/2019
503-314
EXPAND FOR SPECIALTY
CLINIC ADDITION
100% CONSTRUCTION DOCUMENTS
FULLY SPRINKLED
10' 20'
SCALE: 1" = 10'
5'
PLAN NORTH
TRUE NORTH
LEGEND
EXISTING PROPOSED DESCRIPTION
BUILDING
TREE
INLET
SANITARY MANHOLE
LIGHT POLE
CONCRETE SIDEWALK
s
STORM DRAIN MANHOLE
S S S S
D D
SANITARY SEWER
SIDEWALK DEMOLITION
LIMITS OF CONSTRUCTION ACCESS
LOD
LIMIT OF DISTURBANCE
STORM DRAIN
D D
WATER LINE
W W
ELECTRIC LINE
E E
FIBER OPTIC LINE
FO
ELECTRICAL DUCTBANK
STORM DRAIN
X
TEMPORARY CONSTRUCTION FENCE AND
LIMITS OF CONTRACTOR ACCESS
PHASE 1 - SEE PHASING
PLAN
1135.60
PROPOSED SPOT ELEVATION
FIRST FLOOR
EL. 1135.60
3'
HEDGE
3'
HB
HEDGE
1134.11
WALL
2'
4'
HEDGE
4'
HEDGE
2'
5'
HEDGE
1127.33
WALL
EMH(1274)
TOP:1127.26
E
6'
1126.39
WALL
3"
5'
WALL
SWL
3"
2'
2"
CEDAR
2'
2"
CEDAR
4'
2"
CEDAR
3'
T
1127.30
C
O
L
L
P
V
C
I
N
V
P
V
C
P
V
C
P
V C
P
SSMH
TOP=1134.06
b a c
SSMH
TOP=1134.01
METAL FENCE
SMOKE SHELTER
C
P
P
C
P
P
R
R
I
C
P
P
I
N
L
E
T
T
I
N
**NOTE**
FIRST FLOOR ELEVATION FOR
INFORMATIONAL PURPOSES ONLY.
THE SURVEYED AND VERIFIED FIRST
FLOOR ELEVATION = 1135.60. ALL
DRAWINGS, HOWEVER, ARE SHOWN
AT 1136.00 AND SHALL BE USED FOR
CONSTRUCTION PURPOSES.
BUILDING #01
TEMPORARY CONSTRUCTION
FENCE AND LIMITS OF
CONTRACTOR ACCESS (SEE
DETAIL SHEET L3)
3'
UGUNKUTIL
3'
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
UGUNKUTIL
2'
8" PVC
2'
UGUNKUTIL
8" PVC
I
N
L
E
T
T
I
N
BUILDING #01
Project TitleDrawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
1 5 6 7 8
21 3 4 5 6 7 8
A B
C D
E
DELLC
JOB No.
2 3 4
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL CONSULTING
ENGINEERING
1416 CLARKVIEW ROAD
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 500
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
KEY PLAN
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
WHITMAN, REQUARDT &…