36C24419R0037-011.pdf

PDF 6 MB Posted

Attached to
Pittsburgh, Erie, Butler Construction MATOC
Solicitation number
36C24419R0037
Issued by

About this file

This document outlines a Multiple Award Task Order Contract (MATOC) opportunity for construction projects at VA medical centers in Pittsburgh, Erie, and Butler, Pennsylvania. The scope of work includes furnishing labor and materials for health care construction, hospital renovations, and campus maintenance and expansion projects valued between $2,000 and $20,000,000. A seed project to renovate prosthetics at the Heinz campus is estimated between $1,000,000 and $2,000,000 with a 365-day period of performance. The solicitation releasing on August 30, 2019 seeks proposals from Service-Disabled Veteran-Owned Small Businesses for 5 to 10 MATOC awards. NAICS codes include 236 for construction of buildings and 238 for specialty trade contractors. The PSC is Z2DA for repairs or alterations of hospitals and infirmaries. A pre-proposal conference and site visit will be held after solicitation release. Offers must be registered in SAM and verified as eligible in VIP by the proposal due date.

36C24419R0037 S02 DRAWINGS 04.pdf

View the file

Other files

File Type Posted
36C24419R0037-0005000.docx DOCX document
36C24419R0037-0004000.docx DOCX document
36C24419R0037-0003006.pdf PDF
36C24419R0037-0003000.docx DOCX document
36C24419R0037-0003004.pdf PDF
36C24419R0037-0003002.pdf PDF
36C24419R0037-0003001.docx DOCX document
36C24419R0037-0003003.pdf PDF
36C24419R0037-0003005.pdf PDF
36C24419R0037-0002000.docx DOCX document
36C24419R0037-0001002.docx DOCX document
36C24419R0037-0001000.docx DOCX document
36C24419R0037-0001003.docx DOCX document
36C24419R0037-0001001.docx DOCX document
EXHIBIT_F_-_PPQ.docx DOCX document
36C24419R0037-008.pdf PDF
36C24419R0037-009.pdf PDF
36C24419R0037-006.pdf PDF
36C24419R0037-001.docx DOCX document
36C24419R0037-016.pdf PDF
36C24419R0037-014.pdf PDF
36C24419R0037-005.pdf PDF
36C24419R0037-010.pdf PDF
36C24419R0037-003.pdf PDF
36C24419R0037-015.pdf PDF
36C24419R0037-012.pdf PDF
36C24419R0037-013.pdf PDF
36C24419R0037-002.pdf PDF
36C24419R0037-017.pdf PDF
36C24419R0037-018.pdf PDF
36C24419R0037-004.pdf PDF
36C24419R0037-007.pdf PDF
36C24419R0037-000.docx DOCX document
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPS

M

DX

SC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

04-30-2019

EP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

1. ALL DIMENSIONS ARE CONSIDERED FROM FINISHED FLOOR AND, UNLESS NOTED OTHERWISE, SHALL NOT VARY.

RAISED FLOORS SHALL BE CONSIDERED FINISHED FLOOR.

2. ALL DIMENSIONS SHALL BE COORDINATED WITH ARCHITECTURAL DETAILS AND MAY BE ADJUSTED TO CONFORM

WITH ARCHITECTURAL REQUIREMENTS AS LONG AS NO CODE RESTRICTION IS VIOLATED.

3. OUTLETS INSTALLED LOWER THAN 15" AFF (FORWARD REACH) AND 9" AFF (SIDE REACH) ARE IN VIOLATION OF ADA.

48" TO HIGHEST OPERABLE PART (SIDE OR FORWARD

ACCESS).

48" TO CENTERLINE OF BOX MINIMUM (TOILETS).

66" TO CENTERLINE OF BOX MAXIMUM (SHOWERS -

LOCATED OUT OF SPRAY AREA).

80" TO CENTERLINE OF DEVICE OR 6" BELOW CEILING,

WHICHEVER IS LOWER.

80" TO BOTTOM OF DEVICE OR NOT MORE THAN 96" TO

TOP.

FIRE ALARM VISUAL ONLY DEVICE OR A COMBINATION

AUDIBLE AND VISUAL DEVICE

NOT LESS THAN 90" TO TOP OR 6" BELOW CEILING, WHICH

EVER IS HIGHER.

48" TO CENTERLINE OF BOX - NOT MORE THAN 5'-0"

FROM EXIT.

54" TO DIAL CENTER (NON-ACCESSIBLE).

48" TO HIGHEST OPERABLE PART (ACCESSIBLE).

12" CEILING TO CENTERLINE OR 7'-0" TO CENTERLINE IF

CEILING IS OVER 8'-0".

AS NOTED ON DRAWINGS.

EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS

WHICH ARE 20"-25"D.

16" TO BOTTOM OF BOX OR AS NOTED ON DRAWINGS.

EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS

WHICH ARE 20"-25"D.

16" TO BOTTOM OF BOX.

EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS

WHICH ARE 20"-25"D.

90" TO CENTERLINE OF SIGN OR CENTERED IN WALL AREA

BETWEEN TOP OF DOOR AND CEILING.

DISCONNECT SWITCHES, MOTOR STARTERS, MOTOR PUSH

BUTTON STATIONS

48" TO CENTERLINE OF BOX.

EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS

WHICH ARE 20"-25"D.

MOUNTING HEIGHTSDEVICE

NOTES:

1. TABLES ARE BASED ON EVENLY DISTRIBUTED LOAD ALLOWING A 3% VOLTAGE DROP AT LAST OUTLET.

2. 480V MOTOR BRANCH CIRCUIT CONDUCTORS SHALL BE #12 AWG IN 3/4" C UNLESS OTHERWISE NOTED.

3. SIZE OF CONDUCTORS ARE BASED UPON EACH MOTOR BEING FED WITH SEPARATE CONDUIT. IF CONDUCTORS FOR TWO MOTORS (MAX.) ARE TO BE COMBINED IN ONE CONDUIT, INCREASE THE SIZE OF CONDUCTORS AND CONDUITS PER NATIONAL ELECTRICAL CODE (NEC), TO COMPENSATE FOR CONDUCTOR DE-RATING.

4. PROVIDE DEDICATED NEUTRAL FOR EACH CIRCUIT.

1. CODES

THE WORK SHALL COMPLY WITH ALL APPLICABLE LOCAL,

MUNICIPAL, STATE, NATIONAL CODES, AND ALL VA APPLICABLE

DESIGN MANUALS STANDARDS REQUIREMENTS. WHERE THE

CONSTRUCTION DOCUMENTS INDICATE MORE RESTRICTIVE

REQUIREMENTS THE CONSTRUCTION DOCUMENTS SHALL

GOVERN. HOWEVER, THE CONSTRUCTION DOCUMENTS SHALL

NOT BE INTERPRETED AS AUTHORITY TO VIOLATE ANY CODE OR

REGULATION.

ALL WORK, MATERIAL, AND EQUIPMENT SHALL COMPLY WITH

ALL REQUIREMENTS OF THE LATEST EDITIONS AND INTERIM

AMENDMENTS OF THE NATIONAL ELECTRICAL CODE (N.E.C.),

NATIONAL ELECTRICAL SAFETY CODE, OSHA, AND ALL

APPLICABLE FEDERAL, STATE, AND LOCAL LAWS AND

ORDINANCES ALONG WITH ALL DESIGN CRITERIA STD AND

REQMTS. ALL ELECTRICAL EQUIPMENT PROVIDED UNDER THIS

CONTRACT SHALL BE NEW (EXCEPT WHERE OTHERWISE NOTED)

AND SHALL SHALL BEAR THE MARK OF NATIONALLY

RECOGNIZED TESTING LABORATORY, WHEN APPLICABLE. ALL

EQUIPMENT OF THE SAME TYPE AND CAPACITY SHALL BE BY

THE SAME MANUFACTURER.

2. DRAWINGS AND SPECIFICATIONS

THE CONTRACTOR SHALL BE RESPONSIBLE FOR READING AND

COMPLYING WITH BOTH THE DRAWINGS AND SPECIFICATIONS.

IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN

THE DRAWINGS, NOTES, SPECIFICATIONS, OR CODES, THE

REFERENCE WHICH PROVIDES THE MORE COMPLETE OR

HIGHER STANDARD SHALL PREVAIL.

CONTRACTOR SHALL REVIEW ENTIRE SET OF CONTRACT

DOCUMENTS: INCLUDING BUT NOT NECESSARILY LIMITED TO

ALL ARCHITECTURAL, ALL STRUCTURAL, ALL MECHANICAL, ALL

ELECTRICAL, ALL PLUMBING, AND ENTIRE SPECIFICATIONS.

CONTRACTOR SHALL ACKNOWLEDGE AND INCLUDE IN THE

SCOPE OF WORK (CONTRACT) ALL CONDITIONS PERTINENT TO

THE COMPLETION OF THE ELECTRICAL WORK. CONTRACTOR

SHALL FULLY COORDINATE ELECTRICAL WORK WITH THE

INSTALLATION OF WORK BY ALL OTHER TRADES AND MAKE

NECESSARY FIELD ADJUSTMENTS AS REQUIRED TO

ACCOMMODATE THE ELECTRICAL INSTALLATION. ALL OF THE

ABOVE SHALL BE INCLUDED IN THE BASE SCOPE OF WORK AT

NO ADDITIONAL COST TO THE VA.

3. INTERPRETATION OF THE DOCUMENTS

CAREFULLY COMPARE THE DRAWINGS AND SPECIFICATIONS,

CHECKING MEASUREMENTS AND CONDITIONS UNDER WHICH

THIS INSTALLATION IS TO BE MADE. FOR CLARIFICATION

BETWEEN VARIOUS DRAWINGS, BETWEEN DRAWINGS OR

SPECIFICATION, OR BETWEEN SECTIONS OF THE

SPECIFICATION, THE MATTER SHALL BE REFERRED TO THE COR

BEFORE ANY WORK IS EXECUTED. THE CONTRACTOR SHALL

STATE IN THEIR PROPOSAL ANY EXCEPTIONS NECESSARY TO

MAKE THIS A COMPLETE, READY TO USE INSTALLATION. IF NOT

STATED IN THE BID, IT WILL NOT BE CONSIDERED EXTRA.

ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE

CONTRACT DOCUMENTS, IN A NEAT AND WORKABLE MANNER

CONSISTENT WITH RECOGNIZED GOOD PRACTICE, AND SHALL

BE SUBJECT TO THE APPROVAL OF THE VA.

ANY CHANGES TO THE CONTRACT REQUIREMENTS MUST BE

APPROVED PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL

KEEP UP-TO-DATE DRAWINGS, ON-SITE, AVAILABLE, INCLUDING

ALLOWABLE DEVIATIONS FROM THE CONTRACT DRAWINGS.

4. ELECTRICAL DRAWINGS

THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHALL

NOT BE SCALED. THE CONTRACTOR SHALL DETERMINE THE

EXACT LOCATION OF ALL DOORS, WALLS, FURNITURE,

EQUIPMENT, ETC.. THE LOCATION OF RACEWAY SYSTEM

COMPONENTS IS SCHEMATIC. THE EXACT LOCATION OF

RACEWAY SYSTEM COMPONENTS SHALL BE DETERMINED BY

THE CONTRACTOR IN THE FIELD. THE CONTRACTOR SHALL

CONFIRM THE DIMENSIONS OF THE ACTUAL EQUIPMENT TO BE

SUPPLIED FOR THIS PROJECT, AND VERIFY CLEARANCES AND

ROUGH-INS PRIOR TO STARTING WORK.

5. SITE EXAMINATION

BEFORE SUBMITTING A BID, THE CONTRACTOR SHALL VISIT THE

SITE, EXAMINE THE PREMISES, AND MAKE A THOROUGH SURVEY

OF THE EXISTING CONDITIONS. THIS VISIT SHALL ONLY BE

ALLOWED AS PER THE VA SCHEDULED WALKTHROUGH AND THE

SUBMISSION OF A BID WILL BE CONSTRUED AS EVIDENCE THAT

SUCH A VISIT HAS BEEN MADE. NO CONSIDERATION OR

ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT THE SITE

OR FOR LATER CLAIMS FOR LABOR, EQUIPMENT, MATERIALS

REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD

HAVE BEEN FORESEEN HAD SUCH VISIT BEEN MADE.

CONTRACTOR SHALL CAREFULLY EXAMINE THE DRAWINGS AND

SPECIFICATIONS, VISIT THE SITE OF THE WORK, AND FULLY

INFORM HIM/HER SELF AS TO ALL CONDITIONS AND MATTERS

THAT CAN, IN ANY WAY, AFFECT THE WORK OR THE COST

THEREOF, SHOULD THIS CONTRACTOR FIND DISCREPANCIES IN,

OR OMISSIONS FROM, THE DRAWINGS, SPECIFICATIONS OR

OTHER DOCUMENTS OR BE IN DOUBT AS TO THEIR MEANING,

NOTIFY THE VA AT ONCE, IN WRITING, OF ANY DISCREPANCIES

BETWEEN EXISTING CONDITIONS AND NEW WORK, OR BETWEEN

ELECTRICAL WORK AND THE WORK OF OTHER TRADES AND

OBTAIN CLARIFICATION PRIOR TO SUBMITTING ANY BID. LACK

OF SUCH NOTIFICATION SHALL BE CONSTRUED TO INDICATE NO

DISCREPANCIES OR CONFLICTS EXIST. ADDITIONAL

COMPENSATION WILL NOT BE GRANTED AFTER AWARD OF

CONTRACT FOR ANY WORK REQUIRED TO COMPLY WITH THESE

REQUIREMENTS.

6. COORDINATION WITH OTHER TRADES

THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COMPLETE SET

OF ARCHITECTURAL AND ENGINEERING DOCUMENTS AND

COORDINATE WITH MECHANICAL, PLUMBING, ARCHITECTURAL,

AND OTHER TRADES FOR EXACT DIMENSIONS, CLEARANCES,

ROUGH-IN LOCATIONS, AND OTHER ADDITIONAL SCOPES OF

WORK THAT MAY NOT BE SHOWN ON THE ELECTRICAL PLANS.

THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

ALL 120 VOLT (AND HIGHER) AC POWER TO OTHER TRADES

EQUIPMENT AND HARDWARE. THIS SHALL INCLUDE, BUT NOT BE

LIMITED TO, CONTROLS, FIRE AND SECURITY SYSTEMS,

MOTORIZED DOORS, DAMPERS, LIFTS, AND OTHER SYSTEMS.

UNLESS SPECIFICALLY NOTED OTHERWISE ON THE ELECTRICAL

PLANS, THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL

SAFETY DISCONNECT SWITCHES TO MECHANICAL EQUIPMENT.

THE CONTRACTOR SHALL CHECK ALL ARCHITECTURAL,

STRUCTURAL, AND MECHANICAL TRADES WORK FOR POSSIBLE

INTERFERENCE CAUSED BY CONDITIONS IN THE FIELD, BEFORE

THE BID IS MADE. NO ALLOWANCE SHALL SUBSEQUENTLY BE

MADE TO THE CONTRACTOR BY REASON OF HIS FAILURE TO

HAVE MADE SUCH EXAMINATIONS OR OF ANY ERROR OF

HIS/HER PART.

7. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR

SCHEDULING DELIVERY, RECEIVING, UNLOADING, UNCRATING,

STORING SETTING IN PLACE, AND PROTECTING FROM DAMAGE,

VANDALISM, THEFT OR WEATHER DURING CONSTRUCTION FOR

ALL NEW EQUIPMENT FURNISHED BY THE ELECTRICAL

CONTRACTOR.

CONTRACTOR SHALL PAY ALL PERMIT FEES, PLAN REVIEW FEES,

LICENSE FEES, INSPECTIONS AND TAXES APPLICABLE TO THIS

DIVISION IF NECESSARY. (FEDERAL GOVERNMENT IS NOT

SUBJECT TO LOCAL PERMITS OR FEE FOR THE PROJECT).

8. FIRE STOPPING

ALL PENETRATIONS IN WALL, FLOOR OR CEILINGS SHALL BE

SUITABLY CLOSED UP AND SEALED WITH AN INTUMESCENT FIRE

STOPPING COMPOUND LISTED IN THE MOST RECENT FACTORY

MUTUAL RESEARCH CORPORATION (FMRC) APPROVAL GUIDE.

FIRE STOPPING PRODUCTS SHALL BE MANUFACTURED BY 3M

CO EQUIPMENT

9. PAINTING

ALL NEWLY INSTALLED EXPOSED PIPING SHALL BE PAINTED TO

MATCH THE EXISTING ADJACENT WALL OR CEILING SURFACE.

10. VA FURNISHED EQUIPMENT

EQUIPMENT THAT WILL BE FURNISHED BY THE VA WILL BE

INDICATED ON A SEPARATE SCHEDULE. THE CONTRACTOR

SHALL COORDINATE WITH THE VA FOR DELIVERY SCHEDULES.

THE CONTRACTOR IS TO ASSUME THAT ON SITE STORAGE MAY

NOT BE AVAILABLE WHEN COORDINATING DELIVERY OF

EQUIPMENT. THE CONTRACTOR, IN COORDINATION WITH THE

COR, WILL INSPECT THE DELIVERY FOR ACCURACY AND

SHIPMENT DAMAGE AND ACCEPTING THE EQUIPMENT. THE

CONTRACTOR SHALL BE RESPONSIBLE TO STORE, PROTECT,

AND ULTIMATELY INSTALL THE EQUIPMENT.

11. ELECTRICAL SERVICE DISRUPTIONS

ANY WORK INVOLVING A TASK WHICH EXPOSES ACTIVE BUS

SHALL BE PERFORMED AFTER HOURS (11:00PM TO 5:00AM). THIS

RESTRICTION INCLUDES REMOVING THE COVER FROM ANY

PANEL BOARD, SWITCHBOARD, M.C.C. ETC.. ALL WORK WHICH

EXPOSES ACTIVE BUS REQUIRES A WRITTEN NOTIFICATION TO

THE COR WHICH WILL OUTLINE THE METHOD OF PROCEDURE

FOR THE WORK. THE CONTRACTOR SHALL PROVIDE A MINIMUM

OF 2 WEEKS NOTICE TO THE COR BEFORE WORKING ON ANY

ENERGIZED ELECTRICAL SYSTEM. ALL POWER DISRUPTION

SHALL OCCUR AT TIMES AND OF DURATIONS ACCEPTABLE TO

THE COR.

12. EQUIPMENT

ALL MATERIALS AND EQUIPMENT USED IN THIS INSTALLATION

SHALL BE NEW, AND HAVE THE APPROPRIATE UL LISTING AND

LABEL.

THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL,

TOOLS, EQUIPMENT SERVICES, AND ACCESSORIES FOR

COMPLETE INSTALLATION OF ALL ELECTRICAL WORK AS NOTED.

ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE

DRAWINGS, BUT SHOWN OR DESCRIBED IN ONE OR THE OTHER,

AND ITEMS NECESSARY TO MAKE THE ELECTRICAL SYSTEM

COMPLETE AND WORKABLE SHALL FORM A PART OF THE WORK.

13. MISCELLANEOUS SUPPORTING MEMBERS

ALL ANGLES CHANNELS, AND OTHER MISCELLANEOUS STEEL,

BOLTS, RODS, ETC.. REQUIRED TO SUPPORT LIGHT FIXTURE,

CONDUIT, RACEWAY, LADDER TRAY, OR OTHER ELECTRICAL

EQUIPMENT OR DEVICES SHALL BE FURNISHED AND INSTALLED

BY THE CONTRACTOR.

ANY MENTION OF A SPECIFIC VOLTAGE ON THE ELECTRICAL

DRAWINGS SHALL NOT RELIEVE THE ELECTRICAL CONTRACTOR

OF THE RESPONSIBILITY TO VERIFY THE VOLTAGE PRIOR TO

PURCHASING OR ROUGH-IN WORK.

14. DISTRIBUTION PANELS AND PANELS BOARDS

ALL DISTRIBUTION PANELS AND PANEL BOARDS SHALL BE

PROVIDED WITH TYPEWRITTEN DIRECTORIES. SEE PANEL

SCHEDULES ON THE DRAWINGS AND SPECIFICATION FOR

COMPLETE IDENTIFICATION AND LABELING REQUIREMENTS. ALL

DISTRIBUTION PANELS AND PANEL BOARDS SHALL BE LABELED

ON THE PANEL CABINET WITH THE PANEL NAME AND THE

POWER SOURCE FEEDING THE PANEL AS PER THE ELECTRICAL

ONE LINE. ALL PANELS AND PANEL BOARDS SHALL BE PROVIDED

WITH HINGED DOOR WITH LOCK AND KEY.

15. SAFETY

THE CONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO

ENSURE THE SAFETY OF THE VA'S EMPLOYEES, BUILDING

EMPLOYEES AND GUESTS, AS WELL AS THEIR OWN FORCES, BY

ADEQUATELY PROTECTING ANY EXPOSED LIVE CONDUCTORS,

OR DEVICES THROUGHOUT THE COURSE OF THIS WORK

16. EQUIPMENT CONNECTIONS

PROVIDE FINAL CONNECTIONS FOR ALL EQUIPMENT FURNISHED

UNDER OTHER DIVISIONS AND FOR ALL VA FURNISHED

EQUIPMENT. PROVIDE A FLEXIBLE LIQUID TIGHT CONNECTION

TO ALL VIBRATION PRODUCING EQUIPMENT.

17. TEMPORARY LIGHTING, POWER, FIRE, AND SAFETY

PROVIDE TEMPORARY LIGHTING AND POWER AS REQUIRED IN

AREAS UNDERGOING WORK DURING CONSTRUCTION. FURNISH

AND INSTALL ONE OSHA APPROVED PIGTAIL SOCKET WITH

150-WATT LAMP FOR EVERY 500 SQUARE FEET OF FLOOR SPACE

AND A MINIMUM 1 PER ROOM. THE TEMPORARY LIGHTING SHALL

BE LEFT IN PLACE UNTIL PERMANENT LIGHTING IS COMPLETELY

OPERATIONAL.

FURNISH AND INSTALL POWER OUTLETS TO A TOTAL ONE FOR

EVERY 2000 SQUARE FEET OR PART THEREOF OF FLOOR AREA

AND THESE SHALL BE 15 AMP, SINGLE PHASE RECEPTACLES

FOR EITHER 110 OR 220 VOLTS AS DIRECTED BY THE GENERAL

CONTRACTOR. COORDINATE FOR ADDITIONAL TEMPORARY

POWER REQUIREMENTS WITH OTHER TRADES AND PROVIDE AN

ADEQUATE INSTALLATION.

COMPLY WITH NFPA 241 FOR SAFEGUARDING DURING

CONSTRUCTION AND ALTERATION OPERATIONS. IN ADDITION,

ANY OPENINGS IN FIRE RATED SEPARATIONS BETWEEN

OCCUPIED AND UNOCCUPIED (OR OPERATIONAL AND

NON-OPERATIONAL) AREAS SHALL BE SEALED AT THE END OF

EACH WORK DAY WITH AN APPROPRIATE FIRE RATED

ENCLOSURE OR SEALANT. DO NOT COMPROMISE EXISTING

SECURITY OR FIRE ALARM SYSTEMS SERVING THE OCCUPIED

OR OPERATIONAL AREAS.

DURING CONSTRUCTION THE CONTRACTOR SHALL AT ALL TIMES

MAINTAIN ELECTRICAL UTILITIES OF THE BUILDING WITHOUT

INTERRUPTION. SHOULD IT BE NECESSARY TO INTERRUPT ANY

ELECTRICAL SERVICE OR UTILITY, THE CONTRACTOR SHALL

SECURE PERMISSION IN WRITING FROM THE COR FOR SUCH

INTERRUPTION AT LEAST 2 WEEKS IN ADVANCE. ANY

INTERRUPTION SHALL BE MADE WITH MINIMUM AMOUNT OF

INCONVENIENCE TO THE VA AND ANY SHUT-DOWN TIME SHALL

HAVE TO BE ON A PREMIUM TIME BASIS AND SUCH TIME TO BE

INCLUDED IN THE CONTRACTOR'S BID.

CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY

LIGHTING AND POWER FOR ALL TRADES DURING

CONSTRUCTION AND REMOVE IT AT COMPLETION OF WORK.

CONTRACTOR SHALL ESTABLISH SAFE WORKING PROCEDURES

FOR THE PROTECTION OF THE WORKMEN IN ALL PHASES OF

WORK, COMPLYING WITH THE APPLICABLE PROVISIONS OF ALL

CITY, STATE, AND FEDERAL SAFETY LAWS (OSHA), AND AS

RECOMMENDED IN THE "MANUAL OF ACCIDENT PREVENTION IN

CONSTRUCTION" AS ISSUED BY THE ASSOCIATION OF GENERAL

CONTRACTORS OF AMERICA, INC., 20TH AND E. STREETS, N.W.

WASHINGTON, D.C.

18. POWER COORDINATION

THE CONTRACTOR SHALL PERFORM ALL COORDINATION AND

SCHEDULING OF LOCAL POWER OUTAGES REQUIRED WITH THE

COR. ALL NEEDED POWER OUTAGES TO BE SCHEDULED WITH

THE COR TWO WEEKS IN ADVANCE.

19. CABLING

BRANCH CIRCUITS TO RECEPTACLES, LIGHTING AND MISC.

SMALL LOADS (15 OR 20 AMP CIRCUITS), UNLESS SPECIFICALLY

NOTED OTHERWISE, SHALL BE 2 - #10, 1 - #10 GRD., 3/4" C. A

SEPARATE NEUTRAL SHALL BE RUN FOR EACH CIRCUIT. SEE

WIRE SIZING TABLE ON THIS SHEET.

ALL WIRE SIZE #10 AWG AND LARGER SHALL BE STRANDED AND

SOLID FOR #14 AND SMALLER.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN

THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL

HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING

CONDUCTOR. ALL CONDUCTORS SHALL BE COPPER TYPE THWN

/ XHHW.

20. CABLING SIZES

BRANCH CIRCUIT CABLE SIZING SHALL BE ADJUSTED BASED ON

THE VALUES INDICATED IN THE WIRE SIZING TABLE PER THIS

SHEET.

21. SPECIAL LUG REQUIREMENTS

ANY CABLE WHICH TERMINATES DIRECTLY ON TO A BUS BAR

SHALL BE 2 BOLT LONG BARREL TYPE WITH INSPECTION HOLES

PRODUCED WITH NON FLASHING TYPE DYES AS

MANUFACTURED BY THOMAS AND BETTS, OR EQUAL MINIMUM 10

TONS OF COMPRESSION, HEX CRIMP. THE USE OF HEAT SHRINK

TUBING IS EXPLICITLY FORBIDDEN. THERE SHALL BE NO

"SHINERS" AT THE LUGS.

22. RACEWAYS

ALL WIRE SHALL BE INSTALLED IN THIN WALL (E.M.T.) CONDUIT

UNLESS OTHERWISE NOTED. MINIMUM SIZE SHALL BE 3/4"

EXCEPT FOR DROPS FOR DEVICES, SWITCH LEGS,

TEMPERATURE CONTROL CONDUITS, WHERE INDICATED OR AS

CALLED FOR ON DRAWINGS. ALL THINWALL FITTINGS SHALL BE

OF THE STEEL COMPRESSION GLAND TYPE.

ALL UNDERFLOOR, UNDERGROUND OR EXPOSED-TO-WEATHER

CONDUIT SHALL BE HEAVYWALL GALVANIZED RIGID STEEL.

(G.R.S.), MINIMUM 3/4"..

ALL CONDUIT FASTENERS, STRAPS, SUPPORTS ETC. MUST BE

"BOLT-ON" GALVANIZED STEEL ON EXPOSED CONSTRUCTION

AND IN WET AREAS. SNAP-ON BLACK METAL "CADDY" CLIPS IN

METAL PARTITION WALLS AND ABOVE SUSPENDED CEILINGS

WILL BE PERMITTED. ALL FASTENERS, STRAPS, CLIPS, ETC.

SHALL BE UL LISTED FOR THEIR USE.

SUPPORT CONDUIT WITH P1000 UNISTRUT AND 3/8" THREADED

ROD 8'-0" O.C. MAX.

PROVIDE MYERS HUBS OR EQUAL FOR ALL CONDUIT TO

ENCLOSURE CONNECTIONS.

ALL CONDUIT RACEWAYS SHALL BE CONCEALED IN OR WITHIN:

WALLS, CEILING CAVITY, ROOF CONSTRUCTION (WHERE

APPROVED), SLAB, GRADE, ETC. UNLESS OTHERWISE NOTED.

ANY RACEWAY THAT IS TO BE ROUTED EXPOSED SHALL BE

APPROVED BY THE VA/COR AND SUCCESSFULLY REVIEWED BY

THE ARCHITECT/ENGR. PRIOR TO INSTALLATION. ALL CONDUIT

SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALLS

AND STRUCTURAL MEMBERS WITH 90° BENDS WHERE REQUIRED

AND SHALL BE RACKED. PULL AND JUNCTION BOXES SHALL BE

HELD TO A MINIMUM. CONTRACTOR SHALL INSTALL ALL WORK IN

NEAT & WORK LIKE MANNER.

GROUND ALL CONDUITS, MOTORS, AND EXPOSED

NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL

EQUIPMENT IN ACCORDANCE WITH ALL PROVISIONS WITH THE

LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. VA

SPECIFICATION SECTION 26 05 26 "GROUNDING AND BONDING

ELECTRICAL SYSTEM".

CONTRACTOR SHALL PROVIDE BOXES, JUNCTION BOXES,

SPLICE BOXES AND FITTINGS WHERE NECESSARY OR REQUIRED

BY THE NEC.

ALL ELECTRICAL CONDUITS TO A MINIMUM OF 3/4". MULTI-GANG

BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF

EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL

HAVE DIVIDERS BETWEEN DEVICES.

PROVIDE COLOR RED CONDUIT FOR FIRE ALARM.

WHERE CORE DRILLING AND CUTTING OF FLOORS OR WALLS IS

REQUIRED, X-RAY THE AREAS PRIOR TO DRILLING. AVOID

INTERFERENCE WITH EXISTING CONCEALED ELECTRICAL,

PLUMBING INSTALLATIONS REINFORCING STEEL. REFINISH

DAMAGED AND CUT SURFACES TO MATCH ADJACENT FINISHES.

CONTRACTOR SHALL FIREPROOF ALL CONDUIT OPENINGS

BETWEEN FLOORS AND ANY INTERSPACE FIRE SEPARATION

BLOCK WALLS WITH AN COR APPROVED U.L. LISTED FIRE

RETARDANT MATERIAL. AS SUCCESSFULLY REVIEWD BY

ARCHITECT/ENGINEER

23. LIGHTING

ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING

FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL

REFLECTED CEILING PLAN.

24. RECEPTACLES

CONTRACTOR SHALL VERIFY ALL OUTLET MOUNTING

ARRANGEMENTS, HEIGHTS AND LOCATIONS WITH THE

ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. ANY MENTION

OF A SPECIFIC MOUNTING ARRANGEMENT, HEIGHT OR

LOCATION SHALL NOT RELIEVE THE CONTRACTOR OF THE

RESPONSIBILITY TO VERIFY THE SPECIFIC REQUIREMENT WITH

THE EQUIPMENT FURNISHED OR THE OTHER TRADES WORKING

IN THE SAME AREA. NO ADDITIONS TO THE CONTRACT SUM WILL

BE PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN

CONFLICT WITH OTHER WORK ETC. THE VA RESERVES THE

RIGHT TO RELOCATE ANY DEVICE 10'-0" PRIOR TO ROUGH-IN

WITHOUT ANY ADDITIONAL CHARGES BY THE CONTRACTOR.

25. GUARANTEE

ALL EQUIPMENT FURNISHED AND WORK PERFORMED UNDER

THE CONTRACT DOCUMENTS SHALL BE GUARANTEED AGAINST

DEFECTS IN MATERIALS OR WORKMANSHIP FOR A PERIOD AS

PER VA SPECIFICATION, UNLESS OTHERWISE NOTED. ANY

FAILURE OF EQUIPMENT OR WORK DUE TO DEFECTS IN

MATERIALS OR WORKMANSHIP SHALL BE CORRECTED BY THE

CONTRACTOR AT NO COST TO THE VA.

26. FINAL INSPECTION

ALL THE ITEMS AND WORK SHALL BE TESTED FOR SAFE,

PROPER OPERATIONS.

UPON COMPLETION OF THE WORK, THE ELECTRICAL

CONTRACTOR SHALL REVIEW AND CHECK THE ENTIRE PORTION

OF WORK, CLEAN EQUIPMENT AND DEVICES, REMOVE SURPLUS

MATERIALS AND RUBBISH FROM THE VA'S PROPERTY, LEAVING

THE WORK IN NEAT AND CLEAN ORDER AND IN COMPLETE

WORKING CONDITION. THE ELECTRICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR REMOVAL OF ANY CARTON, DEBRIS, ETC.

FOR EQUIPMENT INSTALLED BY THIS CONTRACTOR INCLUDING

EQUIPMENT FURNISHED BY THE VA. THE ABOVE SHALL ALSO

APPLY TO ALL EQUIPMENT FURNISHED BY OTHERS AND

UNPACKED OR REMOVED FROM CARTON, BY THE CONTRACTOR.

MOUNTING HEIGHTS FOR ELECTRICAL DEVICES

WIRE SIZING TABLE

ELECTRICAL GENERAL NOTES

LIGHT SWITCHES, WALL MOUNTED OCCUPANCY SENSORS

WALL MOUNTED EXIT SIGNS

CEILING MOUNTED EXIT SIGNS

RECEPTACLES

SPECIAL OUTLETS OR

RECEPTACLES

PLUGMOLD OR WIREMOLD

CLOCK OUTLETS

DATA/COMMUNICATION OR TELEPHONE OUTLETS

TELEPHONE OUTLETS - WALL TYPE

PAY TYPE TELEPHONE OUTLETS

FIRE ALARM MANUAL PULL STATIONS

FIRE ALARM AUDIBLE ONLY DEVICE

WALL MOUNTED REMOTE INDICATOR LIGHT

AREA OF REFUGE TELEPHONE

CALL FOR AID SWITCH WITH PULL CHAIN TO FLOOR

CARD READER

INTERCOM STATION

SOUND SYSTEM VOLUME CONTROL

MICROPHONE OUTLETS

THERMOSTATS

TEMPERATURE/HUMIDITY SENSORS 60" TO CENTER LINE OF BOX.

54" TO HIGHEST OPERABLE PART (SIDE ACCESS).

48" HIGHEST OPERABLE PART (FORWARD ACCESS).

16" TO BOTTOM OF BOX.

54" TO HIGHEST OPERABLE PART (SIDE ACCESS).

48" HIGHEST OPERABLE PART (FORWARD ACCESS).

54" TO HIGHEST OPERABLE PART (SIDE ACCESS).

48" HIGHEST OPERABLE PART (FORWARD ACCESS).

SAME AS TELEPHONE - ACCESSIBLE.

16" TO BOTTOM OF BOX.

80" TO BOTTOM FIXTURE.

60" TO CENTERLINE.

48" MAXIMUM TO COIN SLOT.

IF DISTANCE (A+B) IN

FEET IS: (SEE DIAGRAM

AT RIGHT)

FOR 120V-20A BRANCH CIRCUITS ONLY (UNLESS NOTED OTHERWISE)

USE COPPER WIRE IN METALLIC

CONDUIT, AWG SIZE AS FOLLOWS ON

ENTIRE CIRCUIT AND SIZE CONDUIT

ACCORDINGLY.

#12 AWG (MIN.)

#10 AWG

#8 AWG

#6 AWG (MAX.)

LAST ON

CIRCUIT.

FIRST ON

CIRCUIT.

PANELBOARD

1/2 WIRE LENGTH FROM FIRST TO

LAST RECEPTACLE OR LIGHTING

FIXTURE ON CIRCUIT.

FOR 277V-20A BRANCH CIRCUITS ONLY (UNLESS NOTED OTHERWISE)

PANELBOARD

LAST ON

CIRCUIT.

1/2 WIRE LENGTH FROM FIRST TO

LAST LIGHTING FIXTURE ON

CIRCUIT.

0' TO 100'

100' TO 175'

175' TO 300'

300' TO 450'

FIRST ON

CIRCUIT.

"B" FT.

"B" FT.

"A" FT.

1. EXIT SIGNS SHALL NOT BE INSTALLED IN A MANNER THAT THE SIGN WILL BLOCK FIRE ALARM VISUAL DEVICES.

2. FOR LIGHTING FIXTURES MOUNTING HEIGHTS SEE SCHEDULE AND DRAWINGS.

SPECIAL NOTES:

NOTES:

IF DISTANCE (A+B) IN

FEET IS: (SEE DIAGRAM

AT RIGHT)

USE COPPER WIRE IN METALLIC

CONDUIT, AWG SIZE AS FOLLOWS ON

ENTIRE CIRCUIT AND SIZE CONDUIT

ACCORDINGLY.

#12 AWG (MIN.)

#10 AWG

#8 AWG

#6 AWG (MAX.)

0' TO 250'

250' TO 400'

400' TO 700'

700' TO 1000'

1. EXAMINATION

A. THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE AREAS

UNDERWHICH THE WORK IS TO BE PERFORMED AND NOTIFY THE

OWNER IN WRITING OF ANY CONDITIONS DETRIMENTAL TO THE

PROPER AND TIMELY COMPLETION OF THE WORK. CONTRACTOR

SHALL NOT PROCEED WITH WORK UNTIL SATISFACTORY

CONDITIONS HAVE BEEN CORRECTED.

B. VERIFY FIELD MEASUREMENTS AND CIRCUITING ARRANGEMENTS

FOR DEVICES SHOWN ON DRAWINGS.

C. DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD

OBSERVATION AND EXISTING RECORD DRAWINGS. REPORT

DISCREPANCIES TO OWNER BEFORE DISTURBING EXISTING

INSTALLATION.

D. COMMENCEMENT OF DEMOLITION MEANS ACCEPTANCE OF EXISTING

CONDITIONS.

E. REVIEW MECHANICAL AND ARCHITECTURAL DEMOLITION DRAWINGS

FOR FOR ANY OTHER ELECTRICAL REQUIREMENTS.

2. PREPARATION

A. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND

CEILINGS SCHEDULED FOR REMOVAL.

3. DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK.

A. REMOVE, RELOCATE, AND EXTEND EXISTING ELECTRICAL WORK AS

INDICATED ON THE DRAWINGS AND AS NOTED HEREIN.

B. REMOVE ABANDONED WIRING AND CONDUIT BACK TO SOURCE OF

SUPPLY, FOR ALL EQUIPMENT SHOWN TO BE REMOVED.

C. WHERE SOURCE OF SUPPLY IS A PANELBOARD, RE-LABEL

PROTECTIVE DEVICE AS "SPARE". AFTER DEMOLITION IS COMPLETE,

SUBMIT REVISED PANELBOARD SCHEDULES INDICATING "SPARES"

TO OWNER AND ENGINEER.

D. REMOVE EXPOSED ABANDONED CONDUIT ABOVE ACCESSIBLE

CEILING FINISHES. CUT CONDUIT FLUSH WITH WALLS AND FLOORS,

AND PATCH SURFACES. CONDUIT MAY BE ABANDONED IN WALLS TO

REMAIN BUT EXISTING WIRING WITHIN THESE CONDUITS TO BE

REMOVED COMPLETELY.

E. REMOVE AND DISCONNECT ABANDONED OUTLETS AND ASSOCIATED

DEVICES.

F. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND

DISTRIBUTION EQUIPMENT.

G. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT

THAT IS NO LONGER IN USE.

H. DISCONNECT AND REMOVE ABANDONED LUMINARIES. REMOVE

BRACKETS, STEMS, HANGERS, AND OTHER ACCESSORIES.

I. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES, OR

CAP AND LABEL IN JUNCTION BOX FOR RE-USE, IN COMPLIANCE

WITH THE NATIONAL ELECTRIC CODE.

J. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING

DEMOLITION AND EXTENSION OF WORK.

K. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTORS PASSING THROUGH RENOVATED AREAS AND

SERVICING UNDISTURBED AREAS.

4. CLEANING, REPAIR, AND REPLACEMENT

A. GENERAL: CLEAN AND REPAIR EXISTING MATERIALS AND

EQUIPMENT THAT WILL REMAIN OR ARE TO BE REUSED.

GENERAL NOTES - DEMOLITION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

1. THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS MAY APPEAR ON THIS

SHEET AND NOT ON THE PLANS.

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE FAULT

CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CB CODE BLUE

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMERGENCY MONITORING CONTROL

PANEL

EMER, EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST, EX EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLT FLOODLIGHT

FLUOR FLUORESCENT

FLUOR FIX FLUORESCENT FIXTURE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF

NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT MICROWAVE

NA NOT APPLICABLE

NAC NOTIFICATION APPLIANCE CIRCUIT PANEL

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

WQM WATER EQUALITY MONITOR

XFER TRANSFER

XFMR TRANSFORMER

ELECTRICAL SYMBOLS - DIAGRAM ELECTRICAL SYMBOLS - POWER / DATA PLAN ELECTRICAL SYMBOLS - LIGHTING PLAN

ELECTRONIC SAFETY AND SECURITY SYMBOLS

NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER

TOP UNLESS OTHERWISE NOTED.

NURSE CALL TERMINAL CABINET.

PANELBOARD

EQUIPMENT TAG

SEE EQUIPMENT SCHEDULE

CABLE AND CONDUIT TAG

SEE SCHEDULE

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

DELTA CONNECTION

TRANSFORMER

WYE CONNECTION

EARTH GROUND

JUNCTION BOX

PULL BOX

TIME CLOCK

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR

EXTENSION TO EQUIPMENT AS DIRECTED.

CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED

FLOOR) FOR EXTENSION TO EQUIPMENT AS DIRECTED.

POWER JUNCTION BOX

TRANSFORMER, PLAN

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

WYE CONNECTION

EARTH GROUND

LADDER CABLE TRAY

PULL BOX

WIREWAY

REGULAR POWER

PANELBOARD CABINET, FLUSH MOUNTED

PANELBOARD CABINET, SURFACE MOUNTED

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT

INTERRUPTER MOUNTED AT 44"

RECEPTACLE, QUADRAPLEX

LIFE SAFETY POWER

CRITICAL POWER

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS

OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR

AS INDICATED.

COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA &

RECEPTACLE.

VARIABLE FREQUENCY DRIVE

DOUBLE GANG DEEP AUDIO/VISUAL JUNCTION BOX

SWITCH

BLANK = SINGLE POLE 2 = DOUBLE POLE

3 = THREE-WAY 4 = FOUR-WAY

D = DOOR SWITCH

DM= DIMMER K = KEY OPERATED

LV= LOW VOLTAGE L = LOCK

LM= LOW VOLTAGE MASTER P = WITH PILOT LIGHT

PB= PUSH BUTTON STATION RC= REMOTE CONTROL

T = TIMER OPERATED WP= WEATHER PROOF

X = EXPLOSION PROOF OS= OCCUPANCY SENSOR

VS= VACANCY SENSOR WITH AUTOMATIC ON/OFF

SWITCH, LAMP HOLDER POLE

LIGHT FIXTURE RECESSED ROUND CEILING MOUNTED DOWNLIGHT

LIGHT FIXTURE, RECESSED LED, 2'x4'

LIGHT FIXTURE, RECESSED LED 1'x4'

LIGHT FIXTURE, SURFACE MOUNTED LED, 2'x4' LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED LED, 1'x4' LETTER INDICATES TYPE.

LIGHT FIXTURE, LED EMERGENCY

LIGHT FIXTURE, RECESSED LED, 2'x2'

LIGHT FIXTURE, SURFACE MOUNTED LED

LIGHT TRACK WITH HEADS AS SHOWN

LIGHT FIXTURE, STRIP/INDUSTRIAL LED; LETTER INDICATES TYPE.

LIGHT FIXTURE, WALL MOUNTED

LIGHT FIXTURE RECESSED SQUARE CEILING MOUNTED DOWNLIGHT

SWITCH, EXTERIOR PHOTO CELL FOR CONTROL OF EXTERIOR LIGHTING

LIGHTING, UNDERCABINET LIGHT/COVE LIGHT

SWITCH, OCCUPANCY SENSOR REFER TO FIXTURE SCHEDULE FOR TYPE

ALARM, FIRE, MANUAL PULL STATION

ALARM, HORN/LIGHT, ONE ASSEMBLY

ALARM, SPEAKER/LIGHT, ONE ASSEMBLY

ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE

SMOKE DETECTOR

DETECTOR, SMOKE, FOR DUCT

FIRE ALARM LINE = FA

ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET

ALARM, HORN, ONE ASSEMBLY

EMERGENCY BATTERY BACK-UP EGRESS LIGHT

CEILING MOUNTED RECEPTACLE FOR PROJECTOR

DOUBLE FACED CEILING OR WALL MOUNTED EXIT SIGN. ARROW INDICATES

DIRECTION

SINGLE FACED CEILING OR WALL MOUNTED EXIT SIGN.

ARROW INDICATES DIRECTION

HOMERUN TO PANELBOARDS. SLASHED LINES INDICATE NUMBER

OF #12 AWG WIRES IN 3/4"C UNLESS OTHERWISE NOTED. LONG

SLASH INDICATES NEUTRAL, LONG SLASH WITH DOT INDICATES

EQUIPMENT GROUND.

SECURITY / DURESS-ALARM BUTTON MOUNTED 3" ABOVE

COUNTER TOP / COUNTER TOP BACK SPLASH.

NURSE CALL DOME LIGHT-CEILING MOUNTED.

NURSE CALL DOME LIGHT-WALL MOUNTED 54" AFF UNLESS

OTHERWISE NOTED.

NURSE CALL DUTY STATION-MOUNTED 54" AFF UNLESS

OTHERWISE NOTED.

EMERGENCY NURSE CALL.

ALARM, LIGHT/STROBE, ONE ASSEMBLY (WALL MOUNTED)

SPECIAL PURPOSE RECEPTACLE ON EMERGENCY POWER

208V, 1PH, NEMA L-20R, UNLESS NOTED OTHERWISE ON PLANS

JUNCTION BOX WITH DISCONNECT SWITCH AND FLEXIBLE CONDUIT

CONNECTION

PP PUSH PLATE (AUTO OPENING DOOR)

DUAL COIL SPEAKER FOR PA AND FIRE ALARM.

CONDUIT UP

CONDUIT DOWN

ELECTRICAL SYMBOLS ELECTRICAL ABBREVIATIONS

GENERAL NOTES

DATA OUTLET- SINGLE PORT CAT 6 VIP OUTLET, 48" A.F.F.

HORIZONTAL MOUNTED, STUB CONDUIT 6" INTO ACCESSIBLE

CEILING SPACE TO CABLE TRAY UNLESS NOTED OTHERWISE

TELEVISION OUTLET- MOUNTING +84'' A.F.F. OTHERWISE NOTED

EXISTING CABLE TRAY

A

CR

PROVIDE JUNCTION BOX & CONDUIT FOR WALL MOUNTED

DURESS ALARM BUTTON

CARD READER - BACK BOX & CONDUIT

PROVIDE JUNCTION BOX & CONDUIT FOR FUTURE SECURITY

CAMERA

HDMI OUTLET - CEILING

COAXIAL OUTLET - WALL

HDMI OUTLET - WALL

A PROVIDE JUNCTION BOX & CONDUIT ABOVE DOOR FOR

DURESS LITE.

R RADIO CHANEL SELECTOR

DRP DOOR RELEASE PANEL

TVM MONITOR

CCTV CAMERA

F MANUL FIRE ALARM STATION (LOCKED) - DEMOLITION

F CHIME, AUDIBLE DEVICE - DEMOLITION

CH

F SMOKE DETECTOR - DEMOLITION

S

FATC FIRE ALARM TERMINAL CABINET

ECAP EMERGENCY CALL ANNUNCIATOR PANEL

R RADIO CHANEL SELECTOR

EXISTING CABLE TRAY

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT

INTERRUPTERGFI

GFI

FLEXIBLE CONNECTION

EML ELECTROMAGNETIC LOCK

K KEY SWITCH FOR EML

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

04-30-2019

LIGHT FIXTURE, EXTERIOR MOUNTED OVER STAIRWELL

SPECIAL PURPOSE RECEPTACLE, 208V, 1PH, NEMA L-20R,

UNLESS NOTED OTHERWISE ON PLANS

AREA NOT IN PROJECT SCOPE

DEMO RECEPTACLE

DEMO TELEPHONE OUTLET

DEMO TELEPHONE DATA OUTLET

ELECTRICAL SYMBOLS - DEMOLITION PLAN

DEMO LIGHT FIXTURE, 2'x2'

DEMO LIGHT FIXTURE, 2'x4'

DEMO LIGHT FIXTURE, 1'x4'

DEMO EMERGENCY BATTERY BACK-UP EGRESS LIGHT

DEMO WALL MOUNTED EXIT SIGN

ARROW INDICATES DIRECTION

DEMO SWITCH, OCCUPANCY SENSOR

DEMO LIGHTING SWITCH

DSD

FOUR PORT (3/1) 3 DATA W/ VOICE/IP MOUNTED 18"

AFF UNLESS OTHERWISE NOTED.

CABLE AND JACK COLOR AS FOLLOW

GREEN - VOICE / VOIP,

BLUE - DATA, ORANGE - DATA, WHITE - DATA

T

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

AL

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

SEAL

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71

Drawing Number

Project Title

Location

Issue Date Checked Drawn

BID DOCUMENTS

U.S. Department of Veterans Affairs

PhasePROFESSIONAL

SEAL HZ PROSTHETIC B71/49 (PHASED)

1010 DELAFIELD RD., ASPINWALL, PA 15215

646-18-101

49 & 71