Additional RFI responses.docx
DOCX document 14 KB Posted
- Attached to
- F108--620-26-206 Asbestos Abatement
- Solicitation number
- 36C24227R0010
About this file
This file contains Additional RFI Responses documenting clarifications regarding an asbestos abatement project at Montrose VAMC. The responses reference two provided drawings: a T-shaped left wing survey plan marking VAT (Vinyl Asbestos Tile) locations and all radiator positions along perimeter walls, accompanied by a 2nd floor ACM (Asbestos-Containing Material) survey plan with a legend and tables identifying rooms containing ACM, quantities, and specific material locations. A second demonstration plan uses yellow lines to indicate the flooring system to be abated, covering approximately 3,000 square feet (confirmed as the actual abatement scope). The responses clarify that all partition walls shown with hatching on the plans are designated for demolition as part of the project scope.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI3.docx | DOCX document | |
| 36C24227R0010 0005.docx | DOCX document | |
| bldg3-2nd fl-ACM table.pdf | ||
| 36C24227R0010 0004.docx | DOCX document | |
| 2nd fl plan-survey.pdf | ||
| CASTLE POINT 2025.pdf | ||
| 36C24227R0010 0003.docx | DOCX document | |
| RFI Responses Asbestos 3PT.docx | DOCX document | |
| 2nd fl plan-ACM survey.pdf | ||
| MR-003-02-PTR-6-10-26 HA101-rev1.pdf | ||
| bldg3-2nd fl-ACM survey.pdf | ||
| 36C24227R0010 0002.docx | DOCX document | |
| 36C24227R0010 0001.docx | DOCX document | |
| FAR 52.225-2 BUY AMERICAN CERTIFICATE.docx | DOCX document | |
| Drawing MR-003-02-PTR-HA101.pdf | ||
| WAGE DETERMINATIONS.pdf | ||
| Specs _ Traditional Asbestos Abatement.pdf | ||
| VAAR 852.219-75 LIMITATIONS ON SUBCONTRACTING CERTIFICATE.docx | DOCX document | |
| 36C24227R0010_1.docx | DOCX document | |
| Specs _ Project 620-26-206 _ General Requirements.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
There are two drawings provided where one marks T-shape left wing of the bldg. with VAT plus all the radiator locations throughout the perimeter walls. It's called survey but no test results have been attached.
See attached 2nd floor ACM survey plan, the Legend and the tables that show the room that contain ACM with the number, quantity and where ACM material exists in the room
The other demo plan has some yellow lines which I would assume show the flooring system to be abated. Is this the actual 3,000 SF?
Yes, this is the actual 3000 SF
Are all partition walls in these rooms to be demolished?
The Highlighted walls (hatched) to be demolished
File details come from the government source that posted it. Updated .