VA Medical Center - Canandaigua - Fire Alarm Upgrades.pdf
PDF 598 KB Posted
- Solicitation number
- 36C24225B0037
About this file
This document is a set of technical drawings for a Fire Alarm System Upgrade project at the VA Medical Center in Canandaigua, NY. The project involves upgrading the fire alarm systems across 11 buildings (Buildings 4, 5, 6, 7, 8, 10, 11, 16, 36, 37, and 118), with key objectives including establishing an addressable fire alarm system, replacing existing modems with network cards and audio controllers, upgrading fire alarm devices, replacing fiber optic connectors, connecting Automated External Defibrillators (AEDs) to the fire alarm system, and installing door contacts. The technical drawings provide detailed riser diagrams showing the interconnection of fire alarm control panels, terminal cabinets, repeaters, and other system components across multiple buildings, with specific attention to wiring configurations, device placements, and network connectivity.
The project requires comprehensive system upgrades that comply with the latest fire safety codes, including replacing speaker strobes, reusing existing conduit and cabling where possible, and ensuring proper communication between fire alarm panels and security systems. Additional scope includes asbestos abatement in Building 4's basement, installing a master fire alarm control panel connected to the fire department radio system, and implementing IDNAC repeaters in Buildings 10 and 11 to ensure adequate power distribution. The technical specifications provide detailed guidelines on acceptable cable types, circuit properties, conduit sizing, and installation requirements, with a focus on maintaining system reliability and meeting national fire protection standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Pre-Bid RFI_528A5-21-504 -Upgrade Fire Alarm System-7-16-2025.pdf | ||
| 36C24225B0037 0008.docx | DOCX document | |
| 36C24225B0037 0007.docx | DOCX document | |
| RFI QUESTIONS AND ANSWERS.pdf | ||
| 36C24225B0037 0006.docx | DOCX document | |
| Pre-Bid RFI answers and questions.pdf | ||
| Fire Alarm Spec-7-8-2025.pdf | ||
| 36C24225B0037 0005.docx | DOCX document | |
| UPDATED WAGE RATES.pdf | ||
| 36C24225B0037 0004.docx | DOCX document | |
| RFI ANSWERS.pdf | ||
| FA panel.jpg | JPG image | |
| 36C24225B0037 0003.docx | DOCX document | |
| FA Panel .jpg | JPG image | |
| Pre-Bid RFI_528A5-21-504 -Upgrade Fire Alarm System.pdf | ||
| SITE VISIT SIGN IN SHEET.pdf | ||
| 30x42 full size set.pdf | ||
| 36C24225B0037 0002.docx | DOCX document | |
| 36C24225B0037 0001.docx | DOCX document | |
| 36C24225B0037_1.docx | DOCX document | |
| S02-DRAWINGS.pdf | ||
| S02-SPECS_BID DOCS new.pdf |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET:
DRAWN BY:
CHECKED BY:
JOB #:
PROJECT #:
DE
SC
RI
PT
IO
N
CA
D
DA
TE
MA
RK
SYSTEM:
CH
K
ISSUE DATE:
" x
A rch
E 1 S ize
IS
SU
E
LO
G:
Re vis ion s s ho wn w ith s ym bo l
NOT FOR CONSTRUCTION
SYSTEM SEQUENCE OF OPERATIONS
PROJECT DIRECTORY
APPLICABLE CODES & STANDARDS
ABBREVIATIONS LEGEND
GENERAL NOTES
LEGENDSDRAWING INDEX
DEVICE TAG LEGEND
FIRE ALARM SYSTEM
FIRE ALARM UPGRADES
VA MEDICAL CENTER - CANANDAIGUA
· FA: = FACP (NON-NETWORK)
· #: = NODE NUMBER
· T#: = TRANSPONDER NUMBER
· #:T# = NODE:TRANSPONDER NUMBER
· N#: = NAC EXTENDER NUMBER
DEVICE NUMBER
BRANCH / ISOLATED LOOP DESIGNATOR:
CIRCUIT DESIGNATOR
PANEL DESIGNATOR
1:T2:A2-1(E1:1)
· A# = IDNAC1 CIRCUIT NUMBER
· D# = DOOR HOLDER CIRCUIT NUMBER
· F# = FIRE PHONE CIRCUIT
· H# = AUDIBLE (HORN) CIRCUIT NUMBER
· M# = IDNET LOOP NUMBER
· P# = POWER CIRCUIT NUMBER
· S# = SPEAKER CIRCUIT NUMBER
· V# = VISUAL CIRCUIT NUMBER
· Z# = ZONE NUMBER
· (L#) = IDNET ISOLATED LOOP NUMBER
· (#) = IDNAC BRANCH NUMBER
· (E#:#) = EPR2 NUMBER:BRANCH NUMBER
1. IDNAC = ADDRESSABLE NOTIFICATION CIRCUIT
2. EPR = ENHANCED POWER REPEATER
1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS IS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON
THE RECORD DRAWINGS.
2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT JOHNSON CONTROLS IN A TIMELY MANNER SO AS NOT TO IMPAIR THE
CONSTRUCTION SCHEDULE.
3. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE.
ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS.
4. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION.
5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT
BREAKER, AND SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL
UNIT.
6. UPDATE THE AS-BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS-BUILT DRAWING SET TO JOHNSON CONTROLS NO
LATER THAN 7 DAYS AFTER FINAL TEST.
7. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMANLIKE MANNER.
8. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED JOHNSON CONTROLS TECHNICAL REPRESENTATIVE.
9. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM
DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER.
10. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME
THAT WORK IS NOT ACTIVELY BEING PERFORMED.
11. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER
LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPLICABLE ELECTRICAL CODES. REFER TO 'APPLICABLE CODES & STANDARDS' FOR SPECIFIC CODE REFERENCES.
12. ALL WIRING SHALL BE INSTALLED ACCORDING TO APPLICABLE ELECTRICAL CODES.
13. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPLICABLE ELECTRICAL CODES. MARK ALL FIRE ALARM WIRES IN
ACCORDANCE WITH APPLICABLE ELECTRICAL CODE SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE.
14 FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP.
15. FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATING MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL
RUNS IN SHAFTS SHALL BE TYPE FPLR.
16. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED FOR WET LOCATIONS.
17. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOORS SHALL BE INSTALLED IN ACCORDANCE APPLICABLE
ELECTRICAL CODES, WHERE APPLICABLE.
18. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS.
19. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE.
20. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT.
21. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING.
22. MAINTAIN MAXIMUM CONDUIT FILL RATIO AS PER APPLICABLE ELECTRICAL CODES REQUIREMENTS.
23. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY; HOWEVER, ANY EXISTING CONDUIT
WILL BE USED ONLY IF CONDUITS MEET CURRENT STANDARDS AND CODES. JOHNSON CONTROLS MAKES NO STATEMENTS WRITTEN OR
VERBAL AS TO THE CONDITION OF EXISTING CONDUITS.
PHONE:
Sales Representative
JASON KIMMEL
JASON.KIMMEL@JCI.COM
585-509-0330 PHONE:
Drawings Prepared By
BRIAN SOUTH
BRIAN.SOUTH@JCI.COM
303-932-3733
Site
VA MEDICAL CENTER
400 FORT HILL AVE.
CANANDAIGUA, NY 14424
Johnson Controls District - 153
90 GOODWAY DRIVE
ROCHESTER, NY 14623
PHONE: 585-475-1060
FAX: 585-475-1898
SERVICE: 585-475-1710
OCCUPANCY TYPE(S):
SPRINKLER PROTECTION:
B BUSINESS GROUP
BUILDING IS FULLY SPRINKLERED
JURISDICTIONS WITHIN THE STATE MAY HAVE AMENDMENTS TO THE STATE ADOPTED CODE. CHECK
WITH THE LOCAL JURISDICTION AUTHORITY FOR MORE DETAILS.
F
F
FACP
AED�
RPT
IDNAC REPEATER (POWER AND DISTANCE EXTENDER)
F F
S S
FIRE ALARM MANUAL PULL STATION
FIRE ALARM SPEAKER HORN - WALL, CEILING
FIRE ALARM DETECTOR HEAT
F FIRE ALARM STROBE - WALL, CEILING
FATC
FIRE ALARM CONTROL PANEL
AUTOMATED EXTERNAL DEFIBRILLATOR
FIRE ALARM TERMINAL CABINET
FA ECP
FIRE ALARM ELEVATOR CONTROL PANEL
FOPP
FIBER OPTIC PATCH PANEL
MFACP
MASTER FIRE ALARM CONTROL PANEL
NDU / NVCC NETWORK DISPLAY UNIT /
ADDRESSABLE MONITOR MODULE
FA
S
FIRE ALARM SYMBOLS LEGEND
F F FIRE ALARM HORN STROBE - WALL, CEILING
FIRE ALARM DETECTOR SMOKE - CEILING
FIRE ALARM SPEAKER
DOOR HOLD OPEN
F S FIRE ALARM SPEAKER STROBE - WALL, CEILING
FIRE ALARM DETECTOR SMOKE DUCT
FIRE ALARM TAMPER SWITCH
FIRE ALARM FLOW SWITCH
F S
NETWORK VOICE COMMAND CENTER
MM
SS
S
SPEAKER CIRCUIT SURGE SUPPRESSOR SS
N
IDNAC CIRCUIT SURGE SUPPRESSORSS
D
IDNET CIRCUIT SURGE SUPPRESSOR
ACCEPTABLE
CABLE TYPES
FIRE ALARM WIRE LEGEND
FP
LR
FP
LP
TH
HN
TF
FN
OU
TD
OO
R
C.
I.CIRCUIT DESCRIPTION CONSTRUCTION GAUGE CIRCUIT PROPERTIES
A ADDRESSABLE
NOTIFICATION UTP SOLID 14 AWG 60pf/ft. MAX CAPACITANCE; 3 twists/ft. MINIMUM X X
Ab ADDRESSABLE
NOTIFICATION - OUTDOOR STP SOLID 14 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
B RUI + COMMUNICATION UTP SOLID 18 AWG 58pf/ft. MAX CAPACITANCE, 35.5
Ω TOTAL LINE RESISTANCE X X
M IDNET UTP SOLID 18 AWG 0.60µF MAX TOTAL LINE
CAPACITANCE X X
Mb IDNET - OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
P POWER 2 COND. SOLID 14 AWG X X X X
R RELAY 2 COND. SOLID 14 AWG X X X X
S AUDIO - SPEAKER UTP SOLID 18 AWG 30pf/ft. MAX CAPACITANCE
RECOMMENDED X X
Sb AUDIO - SPEAKER -
OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
Y FIBER OPTIC - MULTIMODE,
ES NETWORK OFNP W/ SC CONNECTOR 62.5/125 µm Max. Attenuation 1.5 dB/km
Min. bandwidth 160 MHz*km
Z ZONE CIRCUIT 2 COND. SOLID 14 AWG X X X X
CONDUIT SIZE MAX CONDUCTOR AREA CONDUIT SIZE MAX CONDUCTOR AREA
1/2" 0.122 SQ. INCH* 1-1/4" 0.598 SQ INCH*
3/4" 0.213 SQ INCH* 1-1/2" 0.814 SQ INCH*
1" 0.346 SQ INCH* 2" 1.342 SQ INCH*
* 40% CONDUIT FILL PER N.E.C.
STP = SHIELDED TWISTED PAIR
UTP = UNSHIELDED TWISTED PAIR
** OUTDOOR AERIAL CABLE REQUIRES MESSENGER
ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THE ABOVE REQUIREMENTS. RECOMMENDED CABLE MANUFACTURERS AND MODEL NUMBERS ARE AVAILABLE UPON REQUEST.
AC = ABOVE CEILING
AFF = ABOVE FINISHED FLOOR
AHJ = AUTHORITY HAVING JURISDICTION
ALM = ALARM
ANN = ANNUNCIATOR
BMS = BUILDING MANAGEMENT SYSTEM
C = CEILING MOUNTED
CD = CANDELA RATING
DET = DETECTOR
DGP = DATA GATHERING PANEL
E = EXISTING TO REMAIN
EOL = END OF LINE
EPO = EMERGENCY POWER OFF
ER = ELEVATOR RECALL
FAA = FIRE ALARM ANNUNCIATOR
FACP = FIRE ALARM CONTROL PANEL
FATC = FIRE ALARM TERMINAL CABINET
FBO = FURNISHED BY OTHERS
FCC = FIRE COMMAND CENTER
FSD = FIRE SMOKE DAMPER
FTR = FIRE ALARM TRANSPONDER
H = HIGH HUMIDITY
HT = HEIGHT
HVAC = HEATING VENTILATION & AIR CONDITIONING
IMS = INFORMATION MANAGEMENT SYSTEM
MAX = MAXIMUM
MIN = MINIMUM
N/A = NOT APPLICABLE
NAC = NOTIFICATION APPLIANCE CIRCUIT
NDU = NETWORK DISPLAY UNIT
NEC = NATIONAL ELECTRIC CODE
NFPA = NATIONAL FIRE PROTECTION ASSOCIATION
NIC = NOT IN CONTRACT
NPU = NETWORK PROCESSING UNIT
NTS = NOT TO SCALE
PAP = PRE-ACTION PANEL
RC = EXISTING TO REMOVE AND COVER
RD = EXISTING DEVICE TO BE RELOCATED
RL = RELOCATED DEVICE
RR = REMOVE EXISTING & REPLACE WITH NEW
SCC = STATUS COMMAND CENTER
SLC = SIGNALING LINE CIRCUIT
SMK = SMOKE
SUPV = SUPERVISORY
TAC = TRUEALERT ADDRESSABLE CONTROLLER
TOS = TOP OF SHAFT
TRBL = TROUBLE
TS = TAMPER SWITCH
TYP = TYPICAL
UON = UNLESS OTHERWISE NOTED
VCC = VOICE COMMAND CENTER
VT = VALVE TAMPER
W = WATTAGE
W/ = WITH
W/O = WITHOUT
WF = WATERFLOW
WG = WIRE GUARD
WP = WEATHERPROOF
XP = EXPLOSION PROOF
JOHNSON CONTROLS CONTACTS
LA
ST
P
RI
NT
ED
LA
ST
S
AV
ED
B Y:
FI
LE
P
AT
H:
C:
\U se rs\ jso uth br
\O ne
Dr ive
Jo hn so n C on tro ls\
Ne w
FE
D
CO
E
Pr oje cts \V
A Me dic al
Ce nte r - C an an da igu a\G
CO
E De liv er ab les
\V A
Me dic al Ce nte r C an an da igu a- S tan da rd \F
A-
1.d wg
6/2 3/2
5 8
:29 :52
A M
JS
OU
TH
BR
153:
B. SOUTH
FIRE ALARM SYSTEM
VA
M
ED
IC
AL
C
EN
TE
R
0 F
OR
T
HI
LL
A
VE
CA
NA
ND
AI
GU
A, N Y
G
OO
DW
AY
D
RI
VE
RO
CH
ES
TE
R, N Y
PH
ON
E:
5-
5-
SE
RV
IC
E:
5-
5-
FA
X:
-4
-1
DI
ST
RI
CT
FA-001
COVER SHEET
JOHNSON CONTROLS © 2025
BID PURPOSES
VA
M
ED
IC
AL
C
EN
TE
R
- C
AN
AN
DA
IG
UA
FI
RE
A
LA
RM
U
PG
RA
DE
S
© Johnson Controls 2025. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited.
IMPORTANT NOTICE TO USER: This information may not be sold or transferred to any third party, used on other projects or additions to the project for which it was prepared, or used for completion of this project by any third party. Johnson Controls disclaims all liability for the use or reuse of altered files by the user or any third party and such use will be a user's sole risk. User shall, to the fullest extent permitted by law, defend, indemnify, and hold Johnson Controls harmless from any and all claims for loss, damage or injury arising directly or indirectly from any such unauthorized use.
FIRE CODE OF NEW YORK STATE, LATEST EDITION
NATIONAL ELECTRIC CODE (NFPA 70), LATEST EDITION
ELEVATOR CODE ASME A17.1-LATEST EDITION
NATIONAL FIRE ALARM CODE (NFPA 72), LATEST EDITION
SCOPE OF WORK
DESIGN STATEMENT
THIS PROJECT'S DESIGN IS BASED ON THE ENGINEERED PLANS AND
SPECIFICATIONS PREPARED BY:
ARCHITECTURAL PLANS DATED:
MECHANICAL PLANS DATED:
ELECTRICAL PLANS DATED:
SPECIFICATIONS DATED:
ADDENDUM DATED:
ARCHITECT OR ENGINEER NAME
MODIFY EXISTING FIRE ALARM SYSTEM: PROVIDE NEW DEVICES, RELOCATE AND
DEMO EXISTING DEVICES AS SHOWN ON DRAWINGS.
ALL NEW WIRING TO BE CLASS B.
THE EXISTING FIRE ALARM SYSTEM SHALL NOT BE DISCONNECTED OR TAKEN
OUT OF SERVICE WITHOUT WRITTEN PERMISSION FROM THE OWNER. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH THE OWNER THE TIMING
OF ANY EXISTING FIRE ALARM SYSTEM DEMOLITION WORK.
PATHWAY SURVIVABILITY
PATHWAY SURVIVABILITY LEVEL 1
PATHWAY SURVIVABILITY LEVEL 1 SHALL CONSIST OF PATHWAYS IN BUILDINGS
THAT ARE FULLY PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM IN
ACCORDANCE WITH NFPA 13 WITH ANY INTERCONNECTING CONDUCTORS,
CABLES, OR OTHER PHYSICAL PATHWAYS PROTECTED BY METAL RACEWAYS
OR METAL ARMORED CABLES.
SHARED PATHWAY DESIGNATION
SHARED PATHWAY LEVEL 1
LEVEL 1 PATHWAYS SHALL NOT BE REQUIRED TO SEGREGATE LIFE SAFETY
DATA FROM NON-LIFE SAFETY DATA, BUT SHALL PRIORITIZE ALL LIFE SAFETY
DATA OVER NON-LIFE SAFETY DATA.
F-1 FACTORY INDUSTRIAL GROUP - MODERATE-HAZARD OCCUPANCY
I-1 INSTITUTIONAL GROUP
R-1 RESIDENTIAL GROUP
S-1 STORAGE GROUP
Sheet List Table
Sheet Number Sheet Title General Information (FA-000 Series)
FA-001 COVER SHEET
Risers (FA-200 Series)
FA-201 RISER DIAGRAM 1
FA-202 RISER DIAGRAM 2
FA-203 RISER DIAGRAM 3
BUILDING 8
BUILDING 36
BUILDING 118�
LEVEL 2
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
FACP
(ETR)
LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1
FATC
(ETR)
FATC
(ETR)
BUILDING 37
LEVEL 3
FACP
(ETR)
BASEMENT BASEMENT
FROM BUILDING 36
BASEMENT
PARTIAL FIRE ALARM RISER DIAGRAM
NTS1
TO BUILDING 4
TO NEXT
DEVICE
MM
LEVEL 2 LEVEL 2
TO BUILDING 118 FROM BUILDING 37 TO BUILDING 36 FROM BUILDING 8 TO BUILDING 37 FROM BUILDING 7
(ENCL)
(ENCL)
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
FATC
(ETR)
FATC
(ETR)
FACP
(ETR)
(ENCL)
FATC
(ETR)
FATC
(ETR)
FACP
(ETR)
(ENCL)
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
A,S
A,M,S
M
M
Y
Y
Y Y Y Y Y Y
A,S
M
M
A,S
M
A,S
M
A,M,S A,M,S
A,S
M
M
A,M,S A,M,S
A,S
M A,M,S
A,S
M
A,S
M
M
A,S
M
M
A,S
M
M
A,S
M
SHEET:
DRAWN BY:
CHECKED BY:
JOB #:
PROJECT #:
DE
SC
RI
PT
IO
N
CA
D
DA
TE
MA
RK
SYSTEM:
CH
K
ISSUE DATE:
" x
A rch
E 1 S ize
IS
SU
E
LO
G:
Re vis ion s s ho wn w ith s ym bo l
NOT FOR CONSTRUCTIONSCALE:N.T.S.
RISER DIAGRAM 1
LA
ST
P
RI
NT
ED
LA
ST
S
AV
ED
B Y:
FI
LE
P
AT
H:
C:
\U se rs\ jso uth br
\O ne
Dr ive
Jo hn so n C on tro ls\
Ne w
FE
D
CO
E
Pr oje cts \V
A Me dic al
Ce nte r - C an an da igu a\G
CO
E De liv er ab les
\V A
Me dic al Ce nte r C an an da igu a- S tan da rd \F
A-
1.d wg
6/2 3/2
5 8
:29 :54
A M
JS
OU
TH
BR
153:
B. SOUTH
FIRE ALARM SYSTEM
VA
M
ED
IC
AL
C
EN
TE
R
0 F
OR
T
HI
LL
A
VE
CA
NA
ND
AI
GU
A, N Y
G
OO
DW
AY
D
RI
VE
RO
CH
ES
TE
R, N Y
PH
5-
SE
RV
IC
E:
5-
5-
-4
-1
DI
ST
RI
CT
FA-201
RISER DIAGRAM 1
JOHNSON CONTROLS © 2025
BID PURPOSES
VA
M
ED
IC
AL
C
EN
TE
R
- C
AN
AN
DA
IG
UA
FI
RE
A
LA
RM
U
PG
RA
DE
S
© Johnson Controls 2025. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited.
RISER NOTES:
1. RISER IS A DIAGRAMMATICAL REPRESENTATION OF THE
SYSTEM ARCHITECTURE IN BUILDING CROSS SECTION. IT IS
NOT INTENDED TO REPRESENT ACTUAL WIRE RUNS, PANEL
CONFIGURATIONS OR PENETRATIONS. REFER TO FLOOR
PLANS AND PANEL DETAILS FOR CIRCUIT ROUTING AND
CONFIGURATION INFORMATION.
2. ALL WIRING SHALL COMPLY WITH APPLICABLE ELECTRICAL
CODES. REFER TO 'APPLICABLE CODES & STANDARDS' ON
SHEET FA-001 FOR SPECIFIC CODE REFERENCES.
KEYED NOTES:
120VAC PRIMARY POWER SOURCE SHALL BE A
MECHANICALLY PROTECTED BRANCH CIRCUIT. THE CIRCUIT
DISCONNECTING MEANS SHALL HAVE A RED MARKING, AND
BE IDENTIFIED AS "FIRE ALARM CIRCUIT"
F
F
FACP
AED�
RPT
IDNAC REPEATER (POWER AND DISTANCE EXTENDER)
F F
S S
FIRE ALARM MANUAL PULL STATION
FIRE ALARM SPEAKER HORN - WALL, CEILING
FIRE ALARM DETECTOR HEAT
F FIRE ALARM STROBE - WALL, CEILING
FATC
FIRE ALARM CONTROL PANEL
AUTOMATED EXTERNAL DEFIBRILLATOR
FIRE ALARM TERMINAL CABINET
FA ECP
FIRE ALARM ELEVATOR CONTROL PANEL
FOPP
FIBER OPTIC PATCH PANEL
MFACP
MASTER FIRE ALARM CONTROL PANEL
NDU / NVCC NETWORK DISPLAY UNIT /
ADDRESSABLE MONITOR MODULE
FA
S
FIRE ALARM SYMBOLS LEGEND
F F FIRE ALARM HORN STROBE - WALL, CEILING
FIRE ALARM DETECTOR SMOKE - CEILING
FIRE ALARM SPEAKER
DOOR HOLD OPEN
F S FIRE ALARM SPEAKER STROBE - WALL, CEILING
FIRE ALARM DETECTOR SMOKE DUCT
FIRE ALARM TAMPER SWITCH
FIRE ALARM FLOW SWITCH
F S
NETWORK VOICE COMMAND CENTER
MM
SS
S
SPEAKER CIRCUIT SURGE SUPPRESSOR SS
N
IDNAC CIRCUIT SURGE SUPPRESSORSS
D
IDNET CIRCUIT SURGE SUPPRESSOR
ACCEPTABLE
CABLE TYPES
FIRE ALARM WIRE LEGEND
FP
LR
FP
LP
TH
HN
TF
FN
OU
TD
OO
R
C.
I.CIRCUIT DESCRIPTION CONSTRUCTION GAUGE CIRCUIT PROPERTIES
A ADDRESSABLE
NOTIFICATION UTP SOLID 14 AWG 60pf/ft. MAX CAPACITANCE; 3 twists/ft. MINIMUM X X
Ab ADDRESSABLE
NOTIFICATION - OUTDOOR STP SOLID 14 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
B RUI + COMMUNICATION UTP SOLID 18 AWG 58pf/ft. MAX CAPACITANCE, 35.5
Ω TOTAL LINE RESISTANCE X X
M IDNET UTP SOLID 18 AWG 0.60µF MAX TOTAL LINE
CAPACITANCE X X
Mb IDNET - OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
P POWER 2 COND. SOLID 14 AWG X X X X
R RELAY 2 COND. SOLID 14 AWG X X X X
S AUDIO - SPEAKER UTP SOLID 18 AWG 30pf/ft. MAX CAPACITANCE
RECOMMENDED X X
Sb AUDIO - SPEAKER -
OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
Y FIBER OPTIC - MULTIMODE,
ES NETWORK OFNP W/ SC CONNECTOR 62.5/125 µm Max. Attenuation 1.5 dB/km
Min. bandwidth 160 MHz*km
Z ZONE CIRCUIT 2 COND. SOLID 14 AWG X X X X
CONDUIT SIZE MAX CONDUCTOR AREA CONDUIT SIZE MAX CONDUCTOR AREA
1/2" 0.122 SQ. INCH* 1-1/4" 0.598 SQ INCH*
3/4" 0.213 SQ INCH* 1-1/2" 0.814 SQ INCH*
1" 0.346 SQ INCH* 2" 1.342 SQ INCH*
* 40% CONDUIT FILL PER N.E.C.
STP = SHIELDED TWISTED PAIR
UTP = UNSHIELDED TWISTED PAIR
** OUTDOOR AERIAL CABLE REQUIRES MESSENGER
ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THE ABOVE REQUIREMENTS. RECOMMENDED CABLE MANUFACTURERS AND MODEL NUMBERS ARE AVAILABLE UPON REQUEST.
BUILDING 7 BUILDING 6
FATC
(ETR)
BUILDING 5
ATTIC
FATC
(ETR)
FATC
(ETR)
BUILDING 4
LEVEL 2
FATC
(ETR)
LEVEL 1
TO / FROM
BUILDING 16 FOPP
(ETR)
FACP
(ETR)
FACP
(ETR)
FACP FACP
BASEMENT GROUND
TO BUILDING 8
PARTIAL FIRE ALARM RISER DIAGRAM
NTS
BASEMENT BASEMENT
LEVEL 2
LEVEL 1
LEVEL 2
LEVEL 1
LEVEL 2
LEVEL 1
ATTIC ATTIC
FROM BUILDING 6
(ENCL)
TO BUILDING 7 FROM BUILDING 5 TO BUILDING 6 FROM BUILDING 4 TO BUILDING 5
FROM BUILDING 118
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
A,S
M
FATC
(ETR)
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
A,S
M
M
FATC
(ETR)
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
A,S
M
M
A,S
M
Y YYY Y Y Y
Y
(ENCL)
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
A,S
M
M
TO NEXT
DEVICE
F S F A,S
TO NEXT
DEVICE
M
A,M,S A,M,S A,M,S A,M,S
DC
AED
(ETR)
MM
M
TO NEXT
DEVICE
M
TO NEXT
DEVICE
F S F
A,S
TO NEXT
DEVICE
M
TO NEXT
DEVICE
F S F A,S
2Y 2Y
(ETR)
(ENCL)
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
A,S
M
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
A,S
M
A,M,S A,M,S
FATC
(ETR)
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
A,S
M
(ETR)
(ENCL)
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
A,S
M
M
A,M,S A,M,S
FATC
(ETR)
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
A,S
M
TO NEXT
DEVICE
F S F A,S
TO NEXT
DEVICE
M
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
A,S
M
M
SHEET:
DRAWN BY:
CHECKED BY:
JOB #:
PROJECT #:
DE
SC
RI
PT
IO
N
CA
D
DA
TE
MA
RK
SYSTEM:
CH
K
ISSUE DATE:
" x
A rch
E 1 S ize
IS
SU
E
LO
G:
Re vis ion s s ho wn w ith s ym bo l
NOT FOR CONSTRUCTIONSCALE:N.T.S.
RISER DIAGRAM 2
LA
ST
P
RI
NT
ED
LA
ST
S
AV
ED
B Y:
FI
LE
P
AT
H:
C:
\U se rs\ jso uth br
\O ne
Dr ive
Jo hn so n C on tro ls\
Ne w
FE
D
CO
E
Pr oje cts \V
A Me dic al
Ce nte r - C an an da igu a\G
CO
E De liv er ab les
\V A
Me dic al Ce nte r C an an da igu a- S tan da rd \F
A-
2.d wg
6/2 3/2
5 8
:29 :56
A M
JS
OU
TH
BR
153:
B. SOUTH
FIRE ALARM SYSTEM
VA
M
ED
IC
AL
C
EN
TE
R
0 F
OR
T
HI
LL
A
VE
CA
NA
ND
AI
GU
A, N Y
G
OO
DW
AY
D
RI
VE
RO
CH
ES
TE
R, N Y
PH
5-
SE
RV
IC
E:
5-
5-
-4
-1
DI
ST
RI
CT
FA-202
RISER DIAGRAM 2
JOHNSON CONTROLS © 2025
BID PURPOSES
VA
M
ED
IC
AL
C
EN
TE
R
- C
AN
AN
DA
IG
UA
FI
RE
A
LA
RM
U
PG
RA
DE
S
© Johnson Controls 2025. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited.
RISER NOTES:
1. RISER IS A DIAGRAMMATICAL REPRESENTATION OF THE
SYSTEM ARCHITECTURE IN BUILDING CROSS SECTION. IT IS
NOT INTENDED TO REPRESENT ACTUAL WIRE RUNS, PANEL
CONFIGURATIONS OR PENETRATIONS. REFER TO FLOOR
PLANS AND PANEL DETAILS FOR CIRCUIT ROUTING AND
CONFIGURATION INFORMATION.
2. ALL WIRING SHALL COMPLY WITH APPLICABLE ELECTRICAL
CODES. REFER TO 'APPLICABLE CODES & STANDARDS' ON
SHEET FA-001 FOR SPECIFIC CODE REFERENCES.
KEYED NOTES:
120VAC PRIMARY POWER SOURCE SHALL BE A
MECHANICALLY PROTECTED BRANCH CIRCUIT. THE CIRCUIT
DISCONNECTING MEANS SHALL HAVE A RED MARKING, AND
BE IDENTIFIED AS "FIRE ALARM CIRCUIT"
F
F
FACP
AED�
RPT
IDNAC REPEATER (POWER AND DISTANCE EXTENDER)
F F
S S
FIRE ALARM MANUAL PULL STATION
FIRE ALARM SPEAKER HORN - WALL, CEILING
FIRE ALARM DETECTOR HEAT
F FIRE ALARM STROBE - WALL, CEILING
FATC
FIRE ALARM CONTROL PANEL
AUTOMATED EXTERNAL DEFIBRILLATOR
FIRE ALARM TERMINAL CABINET
FA ECP
FIRE ALARM ELEVATOR CONTROL PANEL
FOPP
FIBER OPTIC PATCH PANEL
MFACP
MASTER FIRE ALARM CONTROL PANEL
NDU / NVCC NETWORK DISPLAY UNIT /
ADDRESSABLE MONITOR MODULE
FA
S
FIRE ALARM SYMBOLS LEGEND
F F FIRE ALARM HORN STROBE - WALL, CEILING
FIRE ALARM DETECTOR SMOKE - CEILING
FIRE ALARM SPEAKER
DOOR HOLD OPEN
F S FIRE ALARM SPEAKER STROBE - WALL, CEILING
FIRE ALARM DETECTOR SMOKE DUCT
FIRE ALARM TAMPER SWITCH
FIRE ALARM FLOW SWITCH
F S
NETWORK VOICE COMMAND CENTER
MM
SS
S
SPEAKER CIRCUIT SURGE SUPPRESSOR SS
N
IDNAC CIRCUIT SURGE SUPPRESSORSS
D
IDNET CIRCUIT SURGE SUPPRESSOR
ACCEPTABLE
CABLE TYPES
FIRE ALARM WIRE LEGEND
FP
LR
FP
LP
TH
HN
TF
FN
OU
TD
OO
R
C.
I.CIRCUIT DESCRIPTION CONSTRUCTION GAUGE CIRCUIT PROPERTIES
A ADDRESSABLE
NOTIFICATION UTP SOLID 14 AWG 60pf/ft. MAX CAPACITANCE; 3 twists/ft. MINIMUM X X
Ab ADDRESSABLE
NOTIFICATION - OUTDOOR STP SOLID 14 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
B RUI + COMMUNICATION UTP SOLID 18 AWG 58pf/ft. MAX CAPACITANCE, 35.5
Ω TOTAL LINE RESISTANCE X X
M IDNET UTP SOLID 18 AWG 0.60µF MAX TOTAL LINE
CAPACITANCE X X
Mb IDNET - OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
P POWER 2 COND. SOLID 14 AWG X X X X
R RELAY 2 COND. SOLID 14 AWG X X X X
S AUDIO - SPEAKER UTP SOLID 18 AWG 30pf/ft. MAX CAPACITANCE
RECOMMENDED X X
Sb AUDIO - SPEAKER -
OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
Y FIBER OPTIC - MULTIMODE,
ES NETWORK OFNP W/ SC CONNECTOR 62.5/125 µm Max. Attenuation 1.5 dB/km
Min. bandwidth 160 MHz*km
Z ZONE CIRCUIT 2 COND. SOLID 14 AWG X X X X
CONDUIT SIZE MAX CONDUCTOR AREA CONDUIT SIZE MAX CONDUCTOR AREA
1/2" 0.122 SQ. INCH* 1-1/4" 0.598 SQ INCH*
3/4" 0.213 SQ INCH* 1-1/2" 0.814 SQ INCH*
1" 0.346 SQ INCH* 2" 1.342 SQ INCH*
* 40% CONDUIT FILL PER N.E.C.
STP = SHIELDED TWISTED PAIR
UTP = UNSHIELDED TWISTED PAIR
** OUTDOOR AERIAL CABLE REQUIRES MESSENGER
ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THE ABOVE
BUILDING 16
TO EXISTING
DEVICES
TO FIRE DEPARTMENT
RADIO COMMAND
CENTER
BUILDING 10 BUILDING 11
FACP
(ETR)
(ENCL)
MFACP
(ETR)
NDU /
NVCC
(ETR)
FATC
(ETR) REPEATER
LEVEL 1
TO EXISTING
DEVICES
BASEMENT
TO BUILDING 10
TO BUILDING 11
TO BUILDING 16 TO BUILDING 16
3 PARTIAL FIRE ALARM RISER DIAGRAM
NTS
LEVEL 1 LEVEL 1
FIRE ALARM RISER KEYNOTES
1.
2.
TIE FIRE DEPARTMENT RADIO SYSTEM INTO FIRE ALARM SYSTEM AT DISPATCH CONSOLE IN BUILDING 16.
COORDINATE EXACT ROOM WITH VA COR. RADIOS TO RECEIVE NOTIFICATIONS PER THE MATRIX ON SHEET FA001. NOTIFICATIONS SHALL INFORM USERS THE FLOOR AND BUILDINGS IN WHICH THE EVENT HAS OCCURED.
INSTALL A SECOND NDU / NVCC PANEL TO OPERATE WITH THE EXISTING PANEL FOR THE DURATION OF
CONSTRUCTION.
TO BUILDING 7
FROM BUILDING 7
NDU /
NVCC
FATC
(ETR) REPEATER
Y
Y
TO NEXT
DEVICE
F S F
DC
AED
(ETR)
TO NEXT
DEVICE
MM
A,S
M
M
TO NEXT
DEVICE
F S F
TO NEXT
DEVICE
A,S
M
A
S
A
TO BUILDING 10
A
TO BUILDING 11
A
S
SS
N
SS
N
SS
S
SS
S
TO BUILDING 16
S
A A
TO BUILDING 16
S
SS
N
SS
S
SS
N
SS
S
SHEET:
DRAWN BY:
CHECKED BY:
JOB #:
PROJECT #:
DE
SC
RI
PT
IO
N
CA
D
DA
TE
MA
RK
SYSTEM:
CH
K
ISSUE DATE:
" x
A rch
E 1 S ize
IS
SU
E
LO
G:
Re vis ion s s ho wn w ith s ym bo l
NOT FOR CONSTRUCTIONSCALE:N.T.S.
RISER DIAGRAM 3
LA
ST
P
RI
NT
ED
LA
ST
S
AV
ED
B Y:
FI
LE
P
AT
H:
C:
\U se rs\ jso uth br
\O ne
Dr ive
Jo hn so n C on tro ls\
Ne w
FE
D
CO
E
Pr oje cts \V
A Me dic al
Ce nte r - C an an da igu a\G
CO
E De liv er ab les
\V A
Me dic al Ce nte r C an an da igu a- S tan da rd \F
A-
3.d wg
6/2 3/2
5 8
:29 :58
A M
JS
OU
TH
BR
153:
B. SOUTH
FIRE ALARM SYSTEM
VA
M
ED
IC
AL
C
EN
TE
R
0 F
OR
T
HI
LL
A
VE
CA
NA
ND
AI
GU
A, N Y
G
OO
DW
AY
D
RI
VE
RO
CH
ES
TE
R, N Y
PH
5-
SE
RV
IC
E:
5-
5-
-4
-1
DI
ST
RI
CT
FA-203
RISER DIAGRAM 3
JOHNSON CONTROLS © 2025
BID PURPOSES
VA
M
ED
IC
AL
C
EN
TE
R
- C
AN
AN
DA
IG
UA
FI
RE
A
LA
RM
U
PG
RA
DE
S
© Johnson Controls 2025. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited.
RISER NOTES:
1. RISER IS A DIAGRAMMATICAL REPRESENTATION OF THE
SYSTEM ARCHITECTURE IN BUILDING CROSS SECTION. IT IS
NOT INTENDED TO REPRESENT ACTUAL WIRE RUNS, PANEL
CONFIGURATIONS OR PENETRATIONS. REFER TO FLOOR
PLANS AND PANEL DETAILS FOR CIRCUIT ROUTING AND
CONFIGURATION INFORMATION.
2. ALL WIRING SHALL COMPLY WITH APPLICABLE ELECTRICAL
CODES. REFER TO 'APPLICABLE CODES & STANDARDS' ON
SHEET FA-001 FOR SPECIFIC CODE REFERENCES.
KEYED NOTES:
120VAC PRIMARY POWER SOURCE SHALL BE A
MECHANICALLY PROTECTED BRANCH CIRCUIT. THE CIRCUIT
DISCONNECTING MEANS SHALL HAVE A RED MARKING, AND
BE IDENTIFIED AS "FIRE ALARM CIRCUIT"
F
F
FACP
AED�
RPT
IDNAC REPEATER (POWER AND DISTANCE EXTENDER)
F F
S S
FIRE ALARM MANUAL PULL STATION
FIRE ALARM SPEAKER HORN - WALL, CEILING
FIRE ALARM DETECTOR HEAT
F FIRE ALARM STROBE - WALL, CEILING
FATC
FIRE ALARM CONTROL PANEL
AUTOMATED EXTERNAL DEFIBRILLATOR
FIRE ALARM TERMINAL CABINET
FA ECP
FIRE ALARM ELEVATOR CONTROL PANEL
FOPP
FIBER OPTIC PATCH PANEL
MFACP
MASTER FIRE ALARM CONTROL PANEL
NDU / NVCC NETWORK DISPLAY UNIT /
ADDRESSABLE MONITOR MODULE
FA
S
FIRE ALARM SYMBOLS LEGEND
F F FIRE ALARM HORN STROBE - WALL, CEILING
FIRE ALARM DETECTOR SMOKE - CEILING
FIRE ALARM SPEAKER
DOOR HOLD OPEN
F S FIRE ALARM SPEAKER STROBE - WALL, CEILING
FIRE ALARM DETECTOR SMOKE DUCT
FIRE ALARM TAMPER SWITCH
FIRE ALARM FLOW SWITCH
F S
NETWORK VOICE COMMAND CENTER
MM
SS
S
SPEAKER CIRCUIT SURGE SUPPRESSOR SS
N
IDNAC CIRCUIT SURGE SUPPRESSORSS
D
IDNET CIRCUIT SURGE SUPPRESSOR
ACCEPTABLE
CABLE TYPES
FIRE ALARM WIRE LEGEND
FP
LR
FP
LP
TH
HN
TF
FN
OU
TD
OO
R
C.
I.CIRCUIT DESCRIPTION CONSTRUCTION GAUGE CIRCUIT PROPERTIES
A ADDRESSABLE
NOTIFICATION UTP SOLID 14 AWG 60pf/ft. MAX CAPACITANCE; 3 twists/ft. MINIMUM X X
Ab ADDRESSABLE
NOTIFICATION - OUTDOOR STP SOLID 14 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
B RUI + COMMUNICATION UTP SOLID 18 AWG 58pf/ft. MAX CAPACITANCE, 35.5
Ω TOTAL LINE RESISTANCE X X
M IDNET UTP SOLID 18 AWG 0.60µF MAX TOTAL LINE
CAPACITANCE X X
Mb IDNET - OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
P POWER 2 COND. SOLID 14 AWG X X X X
R RELAY 2 COND. SOLID 14 AWG X X X X
S AUDIO - SPEAKER UTP SOLID 18 AWG 30pf/ft. MAX CAPACITANCE
RECOMMENDED X X
Sb AUDIO - SPEAKER -
OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND
IN CONDUIT/AERIAL** X
Y FIBER OPTIC - MULTIMODE,
ES NETWORK OFNP W/ SC CONNECTOR 62.5/125 µm Max. Attenuation 1.5 dB/km
Min. bandwidth 160 MHz*km
Z ZONE CIRCUIT 2 COND. SOLID 14 AWG X X X X
CONDUIT SIZE MAX CONDUCTOR AREA CONDUIT SIZE MAX CONDUCTOR AREA
1/2" 0.122 SQ. INCH* 1-1/4" 0.598 SQ INCH*
3/4" 0.213 SQ INCH* 1-1/2" 0.814 SQ INCH*
1" 0.346 SQ INCH* 2" 1.342 SQ INCH*
* 40% CONDUIT FILL PER N.E.C.
STP = SHIELDED TWISTED PAIR
UTP = UNSHIELDED TWISTED PAIR
** OUTDOOR AERIAL CABLE REQUIRES MESSENGER
ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THE ABOVE
| Sheets and Views |
| FA-001 COVER SHEET |
| FA-201 RISER DIAGRAM 1 |
| FA-202 RISER DIAGRAM 2 |
| FA-203 RISER DIAGRAM 3 |
File details come from the government source that posted it. Updated .