VA Medical Center - Canandaigua - Fire Alarm Upgrades.pdf

PDF 598 KB Posted

Attached to
Z1DA--NRM-CONST NO CONTRACT YET PROJ#528A5-21-504-Upgradde Fire Alarm System
Solicitation number
36C24225B0037
Issued by

About this file

This document is a set of technical drawings for a Fire Alarm System Upgrade project at the VA Medical Center in Canandaigua, NY. The project involves upgrading the fire alarm systems across 11 buildings (Buildings 4, 5, 6, 7, 8, 10, 11, 16, 36, 37, and 118), with key objectives including establishing an addressable fire alarm system, replacing existing modems with network cards and audio controllers, upgrading fire alarm devices, replacing fiber optic connectors, connecting Automated External Defibrillators (AEDs) to the fire alarm system, and installing door contacts. The technical drawings provide detailed riser diagrams showing the interconnection of fire alarm control panels, terminal cabinets, repeaters, and other system components across multiple buildings, with specific attention to wiring configurations, device placements, and network connectivity.

The project requires comprehensive system upgrades that comply with the latest fire safety codes, including replacing speaker strobes, reusing existing conduit and cabling where possible, and ensuring proper communication between fire alarm panels and security systems. Additional scope includes asbestos abatement in Building 4's basement, installing a master fire alarm control panel connected to the fire department radio system, and implementing IDNAC repeaters in Buildings 10 and 11 to ensure adequate power distribution. The technical specifications provide detailed guidelines on acceptable cable types, circuit properties, conduit sizing, and installation requirements, with a focus on maintaining system reliability and meeting national fire protection standards.

View the file

Other files

File Type Posted
Pre-Bid RFI_528A5-21-504 -Upgrade Fire Alarm System-7-16-2025.pdf PDF
36C24225B0037 0008.docx DOCX document
36C24225B0037 0007.docx DOCX document
RFI QUESTIONS AND ANSWERS.pdf PDF
36C24225B0037 0006.docx DOCX document
Pre-Bid RFI answers and questions.pdf PDF
Fire Alarm Spec-7-8-2025.pdf PDF
36C24225B0037 0005.docx DOCX document
UPDATED WAGE RATES.pdf PDF
36C24225B0037 0004.docx DOCX document
RFI ANSWERS.pdf PDF
FA panel.jpg JPG image
36C24225B0037 0003.docx DOCX document
FA Panel .jpg JPG image
Pre-Bid RFI_528A5-21-504 -Upgrade Fire Alarm System.pdf PDF
SITE VISIT SIGN IN SHEET.pdf PDF
30x42 full size set.pdf PDF
36C24225B0037 0002.docx DOCX document
36C24225B0037 0001.docx DOCX document
36C24225B0037_1.docx DOCX document
S02-DRAWINGS.pdf PDF
S02-SPECS_BID DOCS new.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET:

DRAWN BY:

CHECKED BY:

JOB #:

PROJECT #:

DE

SC

RI

PT

IO

N

CA

D

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

" x

A rch

E 1 S ize

IS

SU

E

LO

G:

Re vis ion s s ho wn w ith s ym bo l

NOT FOR CONSTRUCTION

SYSTEM SEQUENCE OF OPERATIONS

PROJECT DIRECTORY

APPLICABLE CODES & STANDARDS

ABBREVIATIONS LEGEND

GENERAL NOTES

LEGENDSDRAWING INDEX

DEVICE TAG LEGEND

FIRE ALARM SYSTEM

FIRE ALARM UPGRADES

VA MEDICAL CENTER - CANANDAIGUA

· FA: = FACP (NON-NETWORK)

· #: = NODE NUMBER

· T#: = TRANSPONDER NUMBER

· #:T# = NODE:TRANSPONDER NUMBER

· N#: = NAC EXTENDER NUMBER

DEVICE NUMBER

BRANCH / ISOLATED LOOP DESIGNATOR:

CIRCUIT DESIGNATOR

PANEL DESIGNATOR

1:T2:A2-1(E1:1)

· A# = IDNAC1 CIRCUIT NUMBER

· D# = DOOR HOLDER CIRCUIT NUMBER

· F# = FIRE PHONE CIRCUIT

· H# = AUDIBLE (HORN) CIRCUIT NUMBER

· M# = IDNET LOOP NUMBER

· P# = POWER CIRCUIT NUMBER

· S# = SPEAKER CIRCUIT NUMBER

· V# = VISUAL CIRCUIT NUMBER

· Z# = ZONE NUMBER

· (L#) = IDNET ISOLATED LOOP NUMBER

· (#) = IDNAC BRANCH NUMBER

· (E#:#) = EPR2 NUMBER:BRANCH NUMBER

1. IDNAC = ADDRESSABLE NOTIFICATION CIRCUIT

2. EPR = ENHANCED POWER REPEATER

1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS IS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON

THE RECORD DRAWINGS.

2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT JOHNSON CONTROLS IN A TIMELY MANNER SO AS NOT TO IMPAIR THE

CONSTRUCTION SCHEDULE.

3. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE.

ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS.

4. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION.

5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT

BREAKER, AND SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL

UNIT.

6. UPDATE THE AS-BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS-BUILT DRAWING SET TO JOHNSON CONTROLS NO

LATER THAN 7 DAYS AFTER FINAL TEST.

7. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMANLIKE MANNER.

8. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED JOHNSON CONTROLS TECHNICAL REPRESENTATIVE.

9. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM

DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER.

10. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME

THAT WORK IS NOT ACTIVELY BEING PERFORMED.

11. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER

LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPLICABLE ELECTRICAL CODES. REFER TO 'APPLICABLE CODES & STANDARDS' FOR SPECIFIC CODE REFERENCES.

12. ALL WIRING SHALL BE INSTALLED ACCORDING TO APPLICABLE ELECTRICAL CODES.

13. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPLICABLE ELECTRICAL CODES. MARK ALL FIRE ALARM WIRES IN

ACCORDANCE WITH APPLICABLE ELECTRICAL CODE SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE.

14 FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP.

15. FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATING MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL

RUNS IN SHAFTS SHALL BE TYPE FPLR.

16. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED FOR WET LOCATIONS.

17. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOORS SHALL BE INSTALLED IN ACCORDANCE APPLICABLE

ELECTRICAL CODES, WHERE APPLICABLE.

18. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS.

19. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE.

20. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT.

21. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING.

22. MAINTAIN MAXIMUM CONDUIT FILL RATIO AS PER APPLICABLE ELECTRICAL CODES REQUIREMENTS.

23. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY; HOWEVER, ANY EXISTING CONDUIT

WILL BE USED ONLY IF CONDUITS MEET CURRENT STANDARDS AND CODES. JOHNSON CONTROLS MAKES NO STATEMENTS WRITTEN OR

VERBAL AS TO THE CONDITION OF EXISTING CONDUITS.

PHONE:

Sales Representative

JASON KIMMEL

JASON.KIMMEL@JCI.COM

585-509-0330 PHONE:

Drawings Prepared By

BRIAN SOUTH

BRIAN.SOUTH@JCI.COM

303-932-3733

Site

VA MEDICAL CENTER

400 FORT HILL AVE.

CANANDAIGUA, NY 14424

Johnson Controls District - 153

90 GOODWAY DRIVE

ROCHESTER, NY 14623

PHONE: 585-475-1060

FAX: 585-475-1898

SERVICE: 585-475-1710

OCCUPANCY TYPE(S):

SPRINKLER PROTECTION:

B BUSINESS GROUP

BUILDING IS FULLY SPRINKLERED

JURISDICTIONS WITHIN THE STATE MAY HAVE AMENDMENTS TO THE STATE ADOPTED CODE. CHECK

WITH THE LOCAL JURISDICTION AUTHORITY FOR MORE DETAILS.

F

F

FACP

AED�

RPT

IDNAC REPEATER (POWER AND DISTANCE EXTENDER)

F F

S S

FIRE ALARM MANUAL PULL STATION

FIRE ALARM SPEAKER HORN - WALL, CEILING

FIRE ALARM DETECTOR HEAT

F FIRE ALARM STROBE - WALL, CEILING

FATC

FIRE ALARM CONTROL PANEL

AUTOMATED EXTERNAL DEFIBRILLATOR

FIRE ALARM TERMINAL CABINET

FA ECP

FIRE ALARM ELEVATOR CONTROL PANEL

FOPP

FIBER OPTIC PATCH PANEL

MFACP

MASTER FIRE ALARM CONTROL PANEL

NDU / NVCC NETWORK DISPLAY UNIT /

ADDRESSABLE MONITOR MODULE

FA

S

FIRE ALARM SYMBOLS LEGEND

F F FIRE ALARM HORN STROBE - WALL, CEILING

FIRE ALARM DETECTOR SMOKE - CEILING

FIRE ALARM SPEAKER

DOOR HOLD OPEN

F S FIRE ALARM SPEAKER STROBE - WALL, CEILING

FIRE ALARM DETECTOR SMOKE DUCT

FIRE ALARM TAMPER SWITCH

FIRE ALARM FLOW SWITCH

F S

NETWORK VOICE COMMAND CENTER

MM

SS

S

SPEAKER CIRCUIT SURGE SUPPRESSOR SS

N

IDNAC CIRCUIT SURGE SUPPRESSORSS

D

IDNET CIRCUIT SURGE SUPPRESSOR

ACCEPTABLE

CABLE TYPES

FIRE ALARM WIRE LEGEND

FP

LR

FP

LP

TH

HN

TF

FN

OU

TD

OO

R

C.

I.CIRCUIT DESCRIPTION CONSTRUCTION GAUGE CIRCUIT PROPERTIES

A ADDRESSABLE

NOTIFICATION UTP SOLID 14 AWG 60pf/ft. MAX CAPACITANCE; 3 twists/ft. MINIMUM X X

Ab ADDRESSABLE

NOTIFICATION - OUTDOOR STP SOLID 14 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

B RUI + COMMUNICATION UTP SOLID 18 AWG 58pf/ft. MAX CAPACITANCE, 35.5

Ω TOTAL LINE RESISTANCE X X

M IDNET UTP SOLID 18 AWG 0.60µF MAX TOTAL LINE

CAPACITANCE X X

Mb IDNET - OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

P POWER 2 COND. SOLID 14 AWG X X X X

R RELAY 2 COND. SOLID 14 AWG X X X X

S AUDIO - SPEAKER UTP SOLID 18 AWG 30pf/ft. MAX CAPACITANCE

RECOMMENDED X X

Sb AUDIO - SPEAKER -

OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

Y FIBER OPTIC - MULTIMODE,

ES NETWORK OFNP W/ SC CONNECTOR 62.5/125 µm Max. Attenuation 1.5 dB/km

Min. bandwidth 160 MHz*km

Z ZONE CIRCUIT 2 COND. SOLID 14 AWG X X X X

CONDUIT SIZE MAX CONDUCTOR AREA CONDUIT SIZE MAX CONDUCTOR AREA

1/2" 0.122 SQ. INCH* 1-1/4" 0.598 SQ INCH*

3/4" 0.213 SQ INCH* 1-1/2" 0.814 SQ INCH*

1" 0.346 SQ INCH* 2" 1.342 SQ INCH*

* 40% CONDUIT FILL PER N.E.C.

STP = SHIELDED TWISTED PAIR

UTP = UNSHIELDED TWISTED PAIR

** OUTDOOR AERIAL CABLE REQUIRES MESSENGER

ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THE ABOVE REQUIREMENTS. RECOMMENDED CABLE MANUFACTURERS AND MODEL NUMBERS ARE AVAILABLE UPON REQUEST.

AC = ABOVE CEILING

AFF = ABOVE FINISHED FLOOR

AHJ = AUTHORITY HAVING JURISDICTION

ALM = ALARM

ANN = ANNUNCIATOR

BMS = BUILDING MANAGEMENT SYSTEM

C = CEILING MOUNTED

CD = CANDELA RATING

DET = DETECTOR

DGP = DATA GATHERING PANEL

E = EXISTING TO REMAIN

EOL = END OF LINE

EPO = EMERGENCY POWER OFF

ER = ELEVATOR RECALL

FAA = FIRE ALARM ANNUNCIATOR

FACP = FIRE ALARM CONTROL PANEL

FATC = FIRE ALARM TERMINAL CABINET

FBO = FURNISHED BY OTHERS

FCC = FIRE COMMAND CENTER

FSD = FIRE SMOKE DAMPER

FTR = FIRE ALARM TRANSPONDER

H = HIGH HUMIDITY

HT = HEIGHT

HVAC = HEATING VENTILATION & AIR CONDITIONING

IMS = INFORMATION MANAGEMENT SYSTEM

MAX = MAXIMUM

MIN = MINIMUM

N/A = NOT APPLICABLE

NAC = NOTIFICATION APPLIANCE CIRCUIT

NDU = NETWORK DISPLAY UNIT

NEC = NATIONAL ELECTRIC CODE

NFPA = NATIONAL FIRE PROTECTION ASSOCIATION

NIC = NOT IN CONTRACT

NPU = NETWORK PROCESSING UNIT

NTS = NOT TO SCALE

PAP = PRE-ACTION PANEL

RC = EXISTING TO REMOVE AND COVER

RD = EXISTING DEVICE TO BE RELOCATED

RL = RELOCATED DEVICE

RR = REMOVE EXISTING & REPLACE WITH NEW

SCC = STATUS COMMAND CENTER

SLC = SIGNALING LINE CIRCUIT

SMK = SMOKE

SUPV = SUPERVISORY

TAC = TRUEALERT ADDRESSABLE CONTROLLER

TOS = TOP OF SHAFT

TRBL = TROUBLE

TS = TAMPER SWITCH

TYP = TYPICAL

UON = UNLESS OTHERWISE NOTED

VCC = VOICE COMMAND CENTER

VT = VALVE TAMPER

W = WATTAGE

W/ = WITH

W/O = WITHOUT

WF = WATERFLOW

WG = WIRE GUARD

WP = WEATHERPROOF

XP = EXPLOSION PROOF

JOHNSON CONTROLS CONTACTS

LA

ST

P

RI

NT

ED

LA

ST

S

AV

ED

B Y:

FI

LE

P

AT

H:

C:

\U se rs\ jso uth br

\O ne

Dr ive

Jo hn so n C on tro ls\

Ne w

FE

D

CO

E

Pr oje cts \V

A Me dic al

Ce nte r - C an an da igu a\G

CO

E De liv er ab les

\V A

Me dic al Ce nte r C an an da igu a- S tan da rd \F

A-

1.d wg

6/2 3/2

5 8

:29 :52

A M

JS

OU

TH

BR

153:

B. SOUTH

FIRE ALARM SYSTEM

VA

M

ED

IC

AL

C

EN

TE

R

0 F

OR

T

HI

LL

A

VE

CA

NA

ND

AI

GU

A, N Y

G

OO

DW

AY

D

RI

VE

RO

CH

ES

TE

R, N Y

PH

ON

E:

5-

5-

SE

RV

IC

E:

5-

5-

FA

X:

-4

-1

DI

ST

RI

CT

FA-001

COVER SHEET

JOHNSON CONTROLS © 2025

BID PURPOSES

VA

M

ED

IC

AL

C

EN

TE

R

- C

AN

AN

DA

IG

UA

FI

RE

A

LA

RM

U

PG

RA

DE

S

© Johnson Controls 2025. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited.

IMPORTANT NOTICE TO USER: This information may not be sold or transferred to any third party, used on other projects or additions to the project for which it was prepared, or used for completion of this project by any third party. Johnson Controls disclaims all liability for the use or reuse of altered files by the user or any third party and such use will be a user's sole risk. User shall, to the fullest extent permitted by law, defend, indemnify, and hold Johnson Controls harmless from any and all claims for loss, damage or injury arising directly or indirectly from any such unauthorized use.

FIRE CODE OF NEW YORK STATE, LATEST EDITION

NATIONAL ELECTRIC CODE (NFPA 70), LATEST EDITION

ELEVATOR CODE ASME A17.1-LATEST EDITION

NATIONAL FIRE ALARM CODE (NFPA 72), LATEST EDITION

SCOPE OF WORK

DESIGN STATEMENT

THIS PROJECT'S DESIGN IS BASED ON THE ENGINEERED PLANS AND

SPECIFICATIONS PREPARED BY:

ARCHITECTURAL PLANS DATED:

MECHANICAL PLANS DATED:

ELECTRICAL PLANS DATED:

SPECIFICATIONS DATED:

ADDENDUM DATED:

ARCHITECT OR ENGINEER NAME

MODIFY EXISTING FIRE ALARM SYSTEM: PROVIDE NEW DEVICES, RELOCATE AND

DEMO EXISTING DEVICES AS SHOWN ON DRAWINGS.

ALL NEW WIRING TO BE CLASS B.

THE EXISTING FIRE ALARM SYSTEM SHALL NOT BE DISCONNECTED OR TAKEN

OUT OF SERVICE WITHOUT WRITTEN PERMISSION FROM THE OWNER. IT IS THE

CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH THE OWNER THE TIMING

OF ANY EXISTING FIRE ALARM SYSTEM DEMOLITION WORK.

PATHWAY SURVIVABILITY

PATHWAY SURVIVABILITY LEVEL 1

PATHWAY SURVIVABILITY LEVEL 1 SHALL CONSIST OF PATHWAYS IN BUILDINGS

THAT ARE FULLY PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM IN

ACCORDANCE WITH NFPA 13 WITH ANY INTERCONNECTING CONDUCTORS,

CABLES, OR OTHER PHYSICAL PATHWAYS PROTECTED BY METAL RACEWAYS

OR METAL ARMORED CABLES.

SHARED PATHWAY DESIGNATION

SHARED PATHWAY LEVEL 1

LEVEL 1 PATHWAYS SHALL NOT BE REQUIRED TO SEGREGATE LIFE SAFETY

DATA FROM NON-LIFE SAFETY DATA, BUT SHALL PRIORITIZE ALL LIFE SAFETY

DATA OVER NON-LIFE SAFETY DATA.

F-1 FACTORY INDUSTRIAL GROUP - MODERATE-HAZARD OCCUPANCY

I-1 INSTITUTIONAL GROUP

R-1 RESIDENTIAL GROUP

S-1 STORAGE GROUP

Sheet List Table

Sheet Number Sheet Title General Information (FA-000 Series)

FA-001 COVER SHEET

Risers (FA-200 Series)

FA-201 RISER DIAGRAM 1

FA-202 RISER DIAGRAM 2

FA-203 RISER DIAGRAM 3

BUILDING 8

BUILDING 36

BUILDING 118�

LEVEL 2

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

FACP

(ETR)

LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1

FATC

(ETR)

FATC

(ETR)

BUILDING 37

LEVEL 3

FACP

(ETR)

BASEMENT BASEMENT

FROM BUILDING 36

BASEMENT

PARTIAL FIRE ALARM RISER DIAGRAM

NTS1

TO BUILDING 4

TO NEXT

DEVICE

MM

LEVEL 2 LEVEL 2

TO BUILDING 118 FROM BUILDING 37 TO BUILDING 36 FROM BUILDING 8 TO BUILDING 37 FROM BUILDING 7

(ENCL)

(ENCL)

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

FATC

(ETR)

FATC

(ETR)

FACP

(ETR)

(ENCL)

FATC

(ETR)

FATC

(ETR)

FACP

(ETR)

(ENCL)

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

A,S

A,M,S

M

M

Y

Y

Y Y Y Y Y Y

A,S

M

M

A,S

M

A,S

M

A,M,S A,M,S

A,S

M

M

A,M,S A,M,S

A,S

M A,M,S

A,S

M

A,S

M

M

A,S

M

M

A,S

M

M

A,S

M

SHEET:

DRAWN BY:

CHECKED BY:

JOB #:

PROJECT #:

DE

SC

RI

PT

IO

N

CA

D

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

" x

A rch

E 1 S ize

IS

SU

E

LO

G:

Re vis ion s s ho wn w ith s ym bo l

NOT FOR CONSTRUCTIONSCALE:N.T.S.

RISER DIAGRAM 1

LA

ST

P

RI

NT

ED

LA

ST

S

AV

ED

B Y:

FI

LE

P

AT

H:

C:

\U se rs\ jso uth br

\O ne

Dr ive

Jo hn so n C on tro ls\

Ne w

FE

D

CO

E

Pr oje cts \V

A Me dic al

Ce nte r - C an an da igu a\G

CO

E De liv er ab les

\V A

Me dic al Ce nte r C an an da igu a- S tan da rd \F

A-

1.d wg

6/2 3/2

5 8

:29 :54

A M

JS

OU

TH

BR

153:

B. SOUTH

FIRE ALARM SYSTEM

VA

M

ED

IC

AL

C

EN

TE

R

0 F

OR

T

HI

LL

A

VE

CA

NA

ND

AI

GU

A, N Y

G

OO

DW

AY

D

RI

VE

RO

CH

ES

TE

R, N Y

PH

5-

SE

RV

IC

E:

5-

5-

-4

-1

DI

ST

RI

CT

FA-201

RISER DIAGRAM 1

JOHNSON CONTROLS © 2025

BID PURPOSES

VA

M

ED

IC

AL

C

EN

TE

R

- C

AN

AN

DA

IG

UA

FI

RE

A

LA

RM

U

PG

RA

DE

S

© Johnson Controls 2025. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited.

RISER NOTES:

1. RISER IS A DIAGRAMMATICAL REPRESENTATION OF THE

SYSTEM ARCHITECTURE IN BUILDING CROSS SECTION. IT IS

NOT INTENDED TO REPRESENT ACTUAL WIRE RUNS, PANEL

CONFIGURATIONS OR PENETRATIONS. REFER TO FLOOR

PLANS AND PANEL DETAILS FOR CIRCUIT ROUTING AND

CONFIGURATION INFORMATION.

2. ALL WIRING SHALL COMPLY WITH APPLICABLE ELECTRICAL

CODES. REFER TO 'APPLICABLE CODES & STANDARDS' ON

SHEET FA-001 FOR SPECIFIC CODE REFERENCES.

KEYED NOTES:

120VAC PRIMARY POWER SOURCE SHALL BE A

MECHANICALLY PROTECTED BRANCH CIRCUIT. THE CIRCUIT

DISCONNECTING MEANS SHALL HAVE A RED MARKING, AND

BE IDENTIFIED AS "FIRE ALARM CIRCUIT"

F

F

FACP

AED�

RPT

IDNAC REPEATER (POWER AND DISTANCE EXTENDER)

F F

S S

FIRE ALARM MANUAL PULL STATION

FIRE ALARM SPEAKER HORN - WALL, CEILING

FIRE ALARM DETECTOR HEAT

F FIRE ALARM STROBE - WALL, CEILING

FATC

FIRE ALARM CONTROL PANEL

AUTOMATED EXTERNAL DEFIBRILLATOR

FIRE ALARM TERMINAL CABINET

FA ECP

FIRE ALARM ELEVATOR CONTROL PANEL

FOPP

FIBER OPTIC PATCH PANEL

MFACP

MASTER FIRE ALARM CONTROL PANEL

NDU / NVCC NETWORK DISPLAY UNIT /

ADDRESSABLE MONITOR MODULE

FA

S

FIRE ALARM SYMBOLS LEGEND

F F FIRE ALARM HORN STROBE - WALL, CEILING

FIRE ALARM DETECTOR SMOKE - CEILING

FIRE ALARM SPEAKER

DOOR HOLD OPEN

F S FIRE ALARM SPEAKER STROBE - WALL, CEILING

FIRE ALARM DETECTOR SMOKE DUCT

FIRE ALARM TAMPER SWITCH

FIRE ALARM FLOW SWITCH

F S

NETWORK VOICE COMMAND CENTER

MM

SS

S

SPEAKER CIRCUIT SURGE SUPPRESSOR SS

N

IDNAC CIRCUIT SURGE SUPPRESSORSS

D

IDNET CIRCUIT SURGE SUPPRESSOR

ACCEPTABLE

CABLE TYPES

FIRE ALARM WIRE LEGEND

FP

LR

FP

LP

TH

HN

TF

FN

OU

TD

OO

R

C.

I.CIRCUIT DESCRIPTION CONSTRUCTION GAUGE CIRCUIT PROPERTIES

A ADDRESSABLE

NOTIFICATION UTP SOLID 14 AWG 60pf/ft. MAX CAPACITANCE; 3 twists/ft. MINIMUM X X

Ab ADDRESSABLE

NOTIFICATION - OUTDOOR STP SOLID 14 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

B RUI + COMMUNICATION UTP SOLID 18 AWG 58pf/ft. MAX CAPACITANCE, 35.5

Ω TOTAL LINE RESISTANCE X X

M IDNET UTP SOLID 18 AWG 0.60µF MAX TOTAL LINE

CAPACITANCE X X

Mb IDNET - OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

P POWER 2 COND. SOLID 14 AWG X X X X

R RELAY 2 COND. SOLID 14 AWG X X X X

S AUDIO - SPEAKER UTP SOLID 18 AWG 30pf/ft. MAX CAPACITANCE

RECOMMENDED X X

Sb AUDIO - SPEAKER -

OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

Y FIBER OPTIC - MULTIMODE,

ES NETWORK OFNP W/ SC CONNECTOR 62.5/125 µm Max. Attenuation 1.5 dB/km

Min. bandwidth 160 MHz*km

Z ZONE CIRCUIT 2 COND. SOLID 14 AWG X X X X

CONDUIT SIZE MAX CONDUCTOR AREA CONDUIT SIZE MAX CONDUCTOR AREA

1/2" 0.122 SQ. INCH* 1-1/4" 0.598 SQ INCH*

3/4" 0.213 SQ INCH* 1-1/2" 0.814 SQ INCH*

1" 0.346 SQ INCH* 2" 1.342 SQ INCH*

* 40% CONDUIT FILL PER N.E.C.

STP = SHIELDED TWISTED PAIR

UTP = UNSHIELDED TWISTED PAIR

** OUTDOOR AERIAL CABLE REQUIRES MESSENGER

ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THE ABOVE REQUIREMENTS. RECOMMENDED CABLE MANUFACTURERS AND MODEL NUMBERS ARE AVAILABLE UPON REQUEST.

BUILDING 7 BUILDING 6

FATC

(ETR)

BUILDING 5

ATTIC

FATC

(ETR)

FATC

(ETR)

BUILDING 4

LEVEL 2

FATC

(ETR)

LEVEL 1

TO / FROM

BUILDING 16 FOPP

(ETR)

FACP

(ETR)

FACP

(ETR)

FACP FACP

BASEMENT GROUND

TO BUILDING 8

PARTIAL FIRE ALARM RISER DIAGRAM

NTS

BASEMENT BASEMENT

LEVEL 2

LEVEL 1

LEVEL 2

LEVEL 1

LEVEL 2

LEVEL 1

ATTIC ATTIC

FROM BUILDING 6

(ENCL)

TO BUILDING 7 FROM BUILDING 5 TO BUILDING 6 FROM BUILDING 4 TO BUILDING 5

FROM BUILDING 118

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

A,S

M

FATC

(ETR)

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

A,S

M

M

FATC

(ETR)

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

A,S

M

M

A,S

M

Y YYY Y Y Y

Y

(ENCL)

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

A,S

M

M

TO NEXT

DEVICE

F S F A,S

TO NEXT

DEVICE

M

A,M,S A,M,S A,M,S A,M,S

DC

AED

(ETR)

MM

M

TO NEXT

DEVICE

M

TO NEXT

DEVICE

F S F

A,S

TO NEXT

DEVICE

M

TO NEXT

DEVICE

F S F A,S

2Y 2Y

(ETR)

(ENCL)

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

A,S

M

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

A,S

M

A,M,S A,M,S

FATC

(ETR)

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

A,S

M

(ETR)

(ENCL)

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

A,S

M

M

A,M,S A,M,S

FATC

(ETR)

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

A,S

M

TO NEXT

DEVICE

F S F A,S

TO NEXT

DEVICE

M

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

A,S

M

M

SHEET:

DRAWN BY:

CHECKED BY:

JOB #:

PROJECT #:

DE

SC

RI

PT

IO

N

CA

D

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

" x

A rch

E 1 S ize

IS

SU

E

LO

G:

Re vis ion s s ho wn w ith s ym bo l

NOT FOR CONSTRUCTIONSCALE:N.T.S.

RISER DIAGRAM 2

LA

ST

P

RI

NT

ED

LA

ST

S

AV

ED

B Y:

FI

LE

P

AT

H:

C:

\U se rs\ jso uth br

\O ne

Dr ive

Jo hn so n C on tro ls\

Ne w

FE

D

CO

E

Pr oje cts \V

A Me dic al

Ce nte r - C an an da igu a\G

CO

E De liv er ab les

\V A

Me dic al Ce nte r C an an da igu a- S tan da rd \F

A-

2.d wg

6/2 3/2

5 8

:29 :56

A M

JS

OU

TH

BR

153:

B. SOUTH

FIRE ALARM SYSTEM

VA

M

ED

IC

AL

C

EN

TE

R

0 F

OR

T

HI

LL

A

VE

CA

NA

ND

AI

GU

A, N Y

G

OO

DW

AY

D

RI

VE

RO

CH

ES

TE

R, N Y

PH

5-

SE

RV

IC

E:

5-

5-

-4

-1

DI

ST

RI

CT

FA-202

RISER DIAGRAM 2

JOHNSON CONTROLS © 2025

BID PURPOSES

VA

M

ED

IC

AL

C

EN

TE

R

- C

AN

AN

DA

IG

UA

FI

RE

A

LA

RM

U

PG

RA

DE

S

© Johnson Controls 2025. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited.

RISER NOTES:

1. RISER IS A DIAGRAMMATICAL REPRESENTATION OF THE

SYSTEM ARCHITECTURE IN BUILDING CROSS SECTION. IT IS

NOT INTENDED TO REPRESENT ACTUAL WIRE RUNS, PANEL

CONFIGURATIONS OR PENETRATIONS. REFER TO FLOOR

PLANS AND PANEL DETAILS FOR CIRCUIT ROUTING AND

CONFIGURATION INFORMATION.

2. ALL WIRING SHALL COMPLY WITH APPLICABLE ELECTRICAL

CODES. REFER TO 'APPLICABLE CODES & STANDARDS' ON

SHEET FA-001 FOR SPECIFIC CODE REFERENCES.

KEYED NOTES:

120VAC PRIMARY POWER SOURCE SHALL BE A

MECHANICALLY PROTECTED BRANCH CIRCUIT. THE CIRCUIT

DISCONNECTING MEANS SHALL HAVE A RED MARKING, AND

BE IDENTIFIED AS "FIRE ALARM CIRCUIT"

F

F

FACP

AED�

RPT

IDNAC REPEATER (POWER AND DISTANCE EXTENDER)

F F

S S

FIRE ALARM MANUAL PULL STATION

FIRE ALARM SPEAKER HORN - WALL, CEILING

FIRE ALARM DETECTOR HEAT

F FIRE ALARM STROBE - WALL, CEILING

FATC

FIRE ALARM CONTROL PANEL

AUTOMATED EXTERNAL DEFIBRILLATOR

FIRE ALARM TERMINAL CABINET

FA ECP

FIRE ALARM ELEVATOR CONTROL PANEL

FOPP

FIBER OPTIC PATCH PANEL

MFACP

MASTER FIRE ALARM CONTROL PANEL

NDU / NVCC NETWORK DISPLAY UNIT /

ADDRESSABLE MONITOR MODULE

FA

S

FIRE ALARM SYMBOLS LEGEND

F F FIRE ALARM HORN STROBE - WALL, CEILING

FIRE ALARM DETECTOR SMOKE - CEILING

FIRE ALARM SPEAKER

DOOR HOLD OPEN

F S FIRE ALARM SPEAKER STROBE - WALL, CEILING

FIRE ALARM DETECTOR SMOKE DUCT

FIRE ALARM TAMPER SWITCH

FIRE ALARM FLOW SWITCH

F S

NETWORK VOICE COMMAND CENTER

MM

SS

S

SPEAKER CIRCUIT SURGE SUPPRESSOR SS

N

IDNAC CIRCUIT SURGE SUPPRESSORSS

D

IDNET CIRCUIT SURGE SUPPRESSOR

ACCEPTABLE

CABLE TYPES

FIRE ALARM WIRE LEGEND

FP

LR

FP

LP

TH

HN

TF

FN

OU

TD

OO

R

C.

I.CIRCUIT DESCRIPTION CONSTRUCTION GAUGE CIRCUIT PROPERTIES

A ADDRESSABLE

NOTIFICATION UTP SOLID 14 AWG 60pf/ft. MAX CAPACITANCE; 3 twists/ft. MINIMUM X X

Ab ADDRESSABLE

NOTIFICATION - OUTDOOR STP SOLID 14 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

B RUI + COMMUNICATION UTP SOLID 18 AWG 58pf/ft. MAX CAPACITANCE, 35.5

Ω TOTAL LINE RESISTANCE X X

M IDNET UTP SOLID 18 AWG 0.60µF MAX TOTAL LINE

CAPACITANCE X X

Mb IDNET - OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

P POWER 2 COND. SOLID 14 AWG X X X X

R RELAY 2 COND. SOLID 14 AWG X X X X

S AUDIO - SPEAKER UTP SOLID 18 AWG 30pf/ft. MAX CAPACITANCE

RECOMMENDED X X

Sb AUDIO - SPEAKER -

OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

Y FIBER OPTIC - MULTIMODE,

ES NETWORK OFNP W/ SC CONNECTOR 62.5/125 µm Max. Attenuation 1.5 dB/km

Min. bandwidth 160 MHz*km

Z ZONE CIRCUIT 2 COND. SOLID 14 AWG X X X X

CONDUIT SIZE MAX CONDUCTOR AREA CONDUIT SIZE MAX CONDUCTOR AREA

1/2" 0.122 SQ. INCH* 1-1/4" 0.598 SQ INCH*

3/4" 0.213 SQ INCH* 1-1/2" 0.814 SQ INCH*

1" 0.346 SQ INCH* 2" 1.342 SQ INCH*

* 40% CONDUIT FILL PER N.E.C.

STP = SHIELDED TWISTED PAIR

UTP = UNSHIELDED TWISTED PAIR

** OUTDOOR AERIAL CABLE REQUIRES MESSENGER

ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THE ABOVE

BUILDING 16

TO EXISTING

DEVICES

TO FIRE DEPARTMENT

RADIO COMMAND

CENTER

BUILDING 10 BUILDING 11

FACP

(ETR)

(ENCL)

MFACP

(ETR)

NDU /

NVCC

(ETR)

FATC

(ETR) REPEATER

LEVEL 1

TO EXISTING

DEVICES

BASEMENT

TO BUILDING 10

TO BUILDING 11

TO BUILDING 16 TO BUILDING 16

3 PARTIAL FIRE ALARM RISER DIAGRAM

NTS

LEVEL 1 LEVEL 1

FIRE ALARM RISER KEYNOTES

1.

2.

TIE FIRE DEPARTMENT RADIO SYSTEM INTO FIRE ALARM SYSTEM AT DISPATCH CONSOLE IN BUILDING 16.

COORDINATE EXACT ROOM WITH VA COR. RADIOS TO RECEIVE NOTIFICATIONS PER THE MATRIX ON SHEET FA001. NOTIFICATIONS SHALL INFORM USERS THE FLOOR AND BUILDINGS IN WHICH THE EVENT HAS OCCURED.

INSTALL A SECOND NDU / NVCC PANEL TO OPERATE WITH THE EXISTING PANEL FOR THE DURATION OF

CONSTRUCTION.

TO BUILDING 7

FROM BUILDING 7

NDU /

NVCC

FATC

(ETR) REPEATER

Y

Y

TO NEXT

DEVICE

F S F

DC

AED

(ETR)

TO NEXT

DEVICE

MM

A,S

M

M

TO NEXT

DEVICE

F S F

TO NEXT

DEVICE

A,S

M

A

S

A

TO BUILDING 10

A

TO BUILDING 11

A

S

SS

N

SS

N

SS

S

SS

S

TO BUILDING 16

S

A A

TO BUILDING 16

S

SS

N

SS

S

SS

N

SS

S

SHEET:

DRAWN BY:

CHECKED BY:

JOB #:

PROJECT #:

DE

SC

RI

PT

IO

N

CA

D

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

" x

A rch

E 1 S ize

IS

SU

E

LO

G:

Re vis ion s s ho wn w ith s ym bo l

NOT FOR CONSTRUCTIONSCALE:N.T.S.

RISER DIAGRAM 3

LA

ST

P

RI

NT

ED

LA

ST

S

AV

ED

B Y:

FI

LE

P

AT

H:

C:

\U se rs\ jso uth br

\O ne

Dr ive

Jo hn so n C on tro ls\

Ne w

FE

D

CO

E

Pr oje cts \V

A Me dic al

Ce nte r - C an an da igu a\G

CO

E De liv er ab les

\V A

Me dic al Ce nte r C an an da igu a- S tan da rd \F

A-

3.d wg

6/2 3/2

5 8

:29 :58

A M

JS

OU

TH

BR

153:

B. SOUTH

FIRE ALARM SYSTEM

VA

M

ED

IC

AL

C

EN

TE

R

0 F

OR

T

HI

LL

A

VE

CA

NA

ND

AI

GU

A, N Y

G

OO

DW

AY

D

RI

VE

RO

CH

ES

TE

R, N Y

PH

5-

SE

RV

IC

E:

5-

5-

-4

-1

DI

ST

RI

CT

FA-203

RISER DIAGRAM 3

JOHNSON CONTROLS © 2025

BID PURPOSES

VA

M

ED

IC

AL

C

EN

TE

R

- C

AN

AN

DA

IG

UA

FI

RE

A

LA

RM

U

PG

RA

DE

S

© Johnson Controls 2025. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited.

RISER NOTES:

1. RISER IS A DIAGRAMMATICAL REPRESENTATION OF THE

SYSTEM ARCHITECTURE IN BUILDING CROSS SECTION. IT IS

NOT INTENDED TO REPRESENT ACTUAL WIRE RUNS, PANEL

CONFIGURATIONS OR PENETRATIONS. REFER TO FLOOR

PLANS AND PANEL DETAILS FOR CIRCUIT ROUTING AND

CONFIGURATION INFORMATION.

2. ALL WIRING SHALL COMPLY WITH APPLICABLE ELECTRICAL

CODES. REFER TO 'APPLICABLE CODES & STANDARDS' ON

SHEET FA-001 FOR SPECIFIC CODE REFERENCES.

KEYED NOTES:

120VAC PRIMARY POWER SOURCE SHALL BE A

MECHANICALLY PROTECTED BRANCH CIRCUIT. THE CIRCUIT

DISCONNECTING MEANS SHALL HAVE A RED MARKING, AND

BE IDENTIFIED AS "FIRE ALARM CIRCUIT"

F

F

FACP

AED�

RPT

IDNAC REPEATER (POWER AND DISTANCE EXTENDER)

F F

S S

FIRE ALARM MANUAL PULL STATION

FIRE ALARM SPEAKER HORN - WALL, CEILING

FIRE ALARM DETECTOR HEAT

F FIRE ALARM STROBE - WALL, CEILING

FATC

FIRE ALARM CONTROL PANEL

AUTOMATED EXTERNAL DEFIBRILLATOR

FIRE ALARM TERMINAL CABINET

FA ECP

FIRE ALARM ELEVATOR CONTROL PANEL

FOPP

FIBER OPTIC PATCH PANEL

MFACP

MASTER FIRE ALARM CONTROL PANEL

NDU / NVCC NETWORK DISPLAY UNIT /

ADDRESSABLE MONITOR MODULE

FA

S

FIRE ALARM SYMBOLS LEGEND

F F FIRE ALARM HORN STROBE - WALL, CEILING

FIRE ALARM DETECTOR SMOKE - CEILING

FIRE ALARM SPEAKER

DOOR HOLD OPEN

F S FIRE ALARM SPEAKER STROBE - WALL, CEILING

FIRE ALARM DETECTOR SMOKE DUCT

FIRE ALARM TAMPER SWITCH

FIRE ALARM FLOW SWITCH

F S

NETWORK VOICE COMMAND CENTER

MM

SS

S

SPEAKER CIRCUIT SURGE SUPPRESSOR SS

N

IDNAC CIRCUIT SURGE SUPPRESSORSS

D

IDNET CIRCUIT SURGE SUPPRESSOR

ACCEPTABLE

CABLE TYPES

FIRE ALARM WIRE LEGEND

FP

LR

FP

LP

TH

HN

TF

FN

OU

TD

OO

R

C.

I.CIRCUIT DESCRIPTION CONSTRUCTION GAUGE CIRCUIT PROPERTIES

A ADDRESSABLE

NOTIFICATION UTP SOLID 14 AWG 60pf/ft. MAX CAPACITANCE; 3 twists/ft. MINIMUM X X

Ab ADDRESSABLE

NOTIFICATION - OUTDOOR STP SOLID 14 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

B RUI + COMMUNICATION UTP SOLID 18 AWG 58pf/ft. MAX CAPACITANCE, 35.5

Ω TOTAL LINE RESISTANCE X X

M IDNET UTP SOLID 18 AWG 0.60µF MAX TOTAL LINE

CAPACITANCE X X

Mb IDNET - OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

P POWER 2 COND. SOLID 14 AWG X X X X

R RELAY 2 COND. SOLID 14 AWG X X X X

S AUDIO - SPEAKER UTP SOLID 18 AWG 30pf/ft. MAX CAPACITANCE

RECOMMENDED X X

Sb AUDIO - SPEAKER -

OUTDOOR STP SOLID 18 AWG DIRECT BURIAL/UNDERGROUND

IN CONDUIT/AERIAL** X

Y FIBER OPTIC - MULTIMODE,

ES NETWORK OFNP W/ SC CONNECTOR 62.5/125 µm Max. Attenuation 1.5 dB/km

Min. bandwidth 160 MHz*km

Z ZONE CIRCUIT 2 COND. SOLID 14 AWG X X X X

CONDUIT SIZE MAX CONDUCTOR AREA CONDUIT SIZE MAX CONDUCTOR AREA

1/2" 0.122 SQ. INCH* 1-1/4" 0.598 SQ INCH*

3/4" 0.213 SQ INCH* 1-1/2" 0.814 SQ INCH*

1" 0.346 SQ INCH* 2" 1.342 SQ INCH*

* 40% CONDUIT FILL PER N.E.C.

STP = SHIELDED TWISTED PAIR

UTP = UNSHIELDED TWISTED PAIR

** OUTDOOR AERIAL CABLE REQUIRES MESSENGER

ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THE ABOVE

Sheets and Views
FA-001 COVER SHEET
FA-201 RISER DIAGRAM 1
FA-202 RISER DIAGRAM 2
FA-203 RISER DIAGRAM 3

File details come from the government source that posted it. Updated .