REVISED DRAWING ME 502 dated 2021_10_26.pdf

PDF 2 MB Posted

Attached to
Z2DZ--Fire Department Renovation at Building 19 Montrose VAMC
Solicitation number
36C24221B0072
Issued by

About this file

This document package includes a federal solicitation for the renovation of a fire department at the Montrose Veterans Affairs Medical Center in New York, along with supporting technical specifications.

The solicitation seeks bids for the renovation of the fire department located in Building 19, including the provision of all labor, materials, tools, equipment and supervision. Key details include a 300-day period of performance, a pre-bid site visit scheduled for October 14, 2021, and a bid opening via teleconference on November 3, 2021. Bids are due by email only to the contracting officer. The estimated value is between $500,000 and $1 million, and the procurement is set aside for service-disabled veteran-owned small businesses. The technical specifications outline the project scope and mechanical, electrical and controls requirements for the renovation and integration with existing building management systems.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

19-AHU-01 - SEQUENCE OF OPERATION

1. GENERAL

a. 19-AHU-01 CONTROLLER SHALL OPERATE WITH BACNET CONTROLS . AHU CONTROLLER

SHALL BE MOUNTED ON THE WALL IN THE SAME ROOM WHERE THE AHU IS LOCATED.

COORDINATE THIS LOCATION WITH THE VA COR. AHU CONTROLLER SHALL BE CONNECTED

TO A SUPERVISORY BUILDING CONTROLLER LOCATED IN THE TELECOMMUNICATIONS ROOM.

AHU UNIT SHALL BE STARTED AND STOPPED BY THE DIRECT DIGITAL CONTROL PANEL (DCP)

ON THE AHU CONTROLLER .

b. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF COMPLETE HVAC CONTROLS SYSTEM TO

VA COR FOR APPROVAL.

c. INTERLOCK THE AIR HANDLING UNIT SYSTEM WITH THE EXISTING FIRE ALARM SYSTEM.

d. ALL DIRECT DIGITAL CONTROL PANELS (DCP) SHALL BE FED FROM AN EMERGENCY POWER

CIRCUIT.

2. RUN CONDITION

a. COOLING MODE: IF SPACE TEMPERATURE IS ABOVE THE COOLING SETPOINT, ENTER

COOLING MODE UNTIL TEMPERATURE FALLS BELOW SETPOINT MINUS A 2°F DEADBAND.

b. HEATING MODE: IF SPACE TEMPERATURE IS BELOW THE HEATING SETPOINT, ENTER

HEATING MODE UNTIL TEMPERATURE RISES ABOVE SETPOINT PLUS A 2°F DEADBAND.

3. AIR FLOW CONTROL

a. THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DCP AND MODULATE THE SUPPLY

FAN VARIABLE FREQUENCY DRIVE (VFD) SPEED TO MAINTAIN A SPACE TEMPERATURE

SETPOINT, AS MEASURED BY FREQUENCY DRIVE (VFD) SPEED TO MAINTAIN A SPACE

TEMPERATURE SETPOINT, AS MEASURED BY FREQUENCY DRIVE (VFD) SPEED TO MAINTAIN

A SPACE TEMPERATURE SETPOINT, AS MEASURED BY TEMPERATURE SENSORS LOCATED IN

THE SPACE. WHEN MULTIPLE SENSORS ARE INDICATED, POLL ALL SENSORS AND CONTROL

TO THE MOST DEMANDING READING.

4. TEMPERATURE CONTROL

a. SUPPLY AIR TEMPERATURE, SENSED BY TT-1, SHALL BE MAINTAINED AT SETPOINT (55 DEG

F.) VIA DIGITAL CONTROL PANEL WHILE MINIMIZING THE FAN SPEED.

b. A FIXED VOLUME OF OUTSIDE AIR FLOW SHALL BE MAINTAINED AT 20% (600 CFM) AT ALL

TIMES.

5. SMOKE CONTROL AUTOMATIC SHUTDOWN/RESTART

a. WHEN SMOKE IS DETECTED BY ANY ASSOCIATED DUCT MOUNTED SMOKE DETECTOR, THE

SUPPLY FAN AND INTERLOCKED RETURN/EXHAUST FAN(S) SHALL SHUT "OFF", AN ALARM

SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM.

b. SUPPLY FAN(S) SHALL AUTOMATICALLY RESTART WHEN FIRE ALARM CIRCUIT IS RESET.

6. EMERGENCY CONSTANT SPEED OPERATION

a. UPON FAILURE OF SUPPLY FAN VFD(S), THE SUPPLY FAN(S) SHALL BE STARTED/STOPPED

MANUALLY AT THE DCP AND ECC THROUGH A BY-PASS STARTER. ACTIVATION OF

CONSTANT SPEED OPERATION SHALL CAUSE THE SUPPLY FAN(S) TO OPERATE AT

CONSTANT SPEED.

7. SAFETIES

a. HIGH PRESSURE LIMIT: THE DCP, USING HIGH PRESSURE LIMIT SWITCH PSH-1 LOCATED AT

THE SUPPLY FAN DISCHARGE, SHALL PREVENT THE SUPPLY FAN(S) FROM DEVELOPING

OVER 4 IN. W.G. OF POSITIVE STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE

AT PSH-1 DOES EXCEED 4 IN. W.G., THE SWITCH WILL OVERRIDE ALL CONTROLS AND SHUT

DOWN THE SUPPLY FAN(S), AND A "HIGH PRESSURE" ALARM SIGNAL SHALL BE INDICATED AT

THE DCP AND ECC. PSH-1 SHALL BE HARDWIRED TO THE SUPPLY FAN VFD(S) AND UNIT

SHALL BE SHUTDOWN IN HAND, AUTO, OR BYPASS MODE. PSH-1 WILL REQUIRE MANUAL

RESET AT THE DEVICE.

b. FILTER STATUS: THE DCP SHALL MONITOR AND INDICATE THE DIFFERENTIAL PRESSURE

ACROSS EACH AIR HANDLING UNIT FILTER SECTION. PROGRAM A HIGH LIMIT SETPOINT FOR

EACH FILTER SECTION IN ACCORDANCE WITH FILTER MANUFACTURER’S RECOMMENDATION.

IF THE DIFFERENTIAL PRESSURE ACROSS A FILTER SECTION IS GREATER THAN THE HIGH

LIMIT SETPOINT, THE DCP AND ECC SHALL REPORT A FILTER MAINTENANCE ALARM WITH

MESSAGE INDICATING THAT THE FILTER NEEDS TO BE CHANGED.

POINTS LIST: 19-AHU-01

POINT

TAG POINT DESCRIPTION UNITS

POINT TYPE SETPOINTS

ALARM CONDITION NOTESBINARY ANALOG

VIRTUAL ADJ. INITIAL HIGH LOW

IN OUT IN OUT

OCCUPIED MODE STATUS ON/OFF

UNOCCUPIED MODE STATUS ON/OFF

HUMIDIFICATION MODE STATUS ON/OFF

DEHUMIDIFICATION MODE STATUS ON/OFF

SUPPLY FAN START/STOP ON/OFF X

C-1 SUPPLY FAN STATUS ON/OFF X SUPPLY FAN PROOF

FAILED

SUPPLY FAN SPEED COMMAND % X

SUPPLY FAN MINIMUM SPEED SETPOINT % X X 50

SUPPLY FAN VFD ALARM ON/OFF X

PSH-1 SUPPLY DUCT PRESSURE SWITCH HIGH LIMIT SAFETY NORMAL/ALARM X X 5.0 ALARM

DD-1 SUPPLY AIR DUCT SMOKE DETECTOR NORMAL/ALARM X ALARM

FT-1 SUPPLY AIR FLOW CFM X

SUPPLY AIR FLOW SETPOINT CFM X

SPS-1 SUPPLY AIR STATIC PRESSURE IN. W.G. X

MORE THAN 20%

ABOVE OR BELOW

SETPOINT

SUPPLY AIR STATIC PRESSURE SETPOINT IN. W.G. X X 2.0 2.5 1.0

TT-1 SUPPLY AIR TEMPERATURE DEG. F X

MORE THAN 10 DEG F

ABOVE OR BELOW

SETPOINT

AVERAGING

SUPPLY AIR TEMPERATURE SETPOINT DEG. F X X 55 60 49

DD-2 SUPPLY AIR DUCT SMOKE DETECTOR NORMAL/ALARM X ALARM

FT-3 RETURN AIR FLOW CFM X

RETURN AIR FLOW SETPOINT CFM X

TT-4 RETURN AIR TEMPERATURE DEG. F X

D-2 RETURN AIR DAMPER COMMAND % OPEN X N.O.

ZC-2 RETURN AIR DAMPER POSITION % OPEN X

FT-2 OUTSIDE AIR FLOW CFM X OA FLOW LESS THAN

80% OF SETPOINT

OUTSIDE AIR FLOW SETPOINT CFM X X X PER SCHEDULE

TT-2 OUTSIDE AIR TEMPERATURE DEG. F X

PDS-1 PRE-FILTER 1 DIFFERENTIAL PRESSURE IN. W.G. X

PDS-2 PRE-FILTER 2 DIFFERENTIAL PRESSURE IN. W.G. X

TT-5 MIXED AIR TEMPERATURE DEG. F X AVERAGING

TT-6 COOLING COIL LEAVING AIR TEMPERATURE DEG. F X

MORE THAN 10 DEG F

ABOVE OR BELOW

SETPOINT

AVERAGING

HCV-1 PREHEAT STEAM CONTROL VALVE COMMAND % OPEN X N.O.

Drawing Title

Approved: Facility Director , VAHVHCS:

Project Title

Date

Location

Checked

Building(s) Number

Project Number

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS: NORTH:

Revisions: Date:

Approved: John Cliffe, Facility Chief of Engineering

Firehouse Enhancement at FDR

APPROVED:

APPROVED:

APPROVED:

Dwg 35 of 61

ME 502

AMI

Montrose, New York

08-30-2021

620-20-206

APPROVED:

APPROVED:

APPROVED:

APPROVED:

APPROVED:

LS

New Mechanical HVAC Controls Information Scale: As Noted

BID DOCUMENT REVISION #1 10/26/2021

HVAC CONTROL GENERAL NOTES

1. ALL VAV CONTROLLERS AND THE AHU CONTROLLER SHALL BE

CONNECTED TO A SUPERVISORY BUILDING CONTROLLER LOCATED IN THE

NEW TELECOMMUNICATIONS CLOSET 16A. THE BUILDING CONTROLLER

SHALL BE CONNECTED BY THE CONTRACTOR TO AN EXISTING NETWORK

SWITCH LOCATED IN THE NEW TELECOMMUNICATIONS CLOSET 16A VIA

ETHERNET CABLE.

2. CONTRACTOR SHALL PROVIDE A COMPLETE AND WORKING DIRECT

DIGITAL CONTROL SYSTEM. CONTRACTOR SHALL PROVIDE ALL

ENGINEERING, PROGRAMMING, CONTROLS AND INSTALLATION MANUALS,

INSTALLATION LABOR, COMMISSIONING AND START-UP, TRAINING, FINAL

PROJECT DOCUMENTATION, AND WARRANTY.

3. THE CONTRACTOR SHALL CONNECT THE NEW DDC SYSTEM TO THE EXISTING

BMS SYSTEM AND ENSURE THAT IT IS INTEGRATED FULLY WITH THAT SYSTEM.

THE EXISTING BMS SERVER WILL BE THE MAIN CONTRROL POINT AND INTERFACE

FOR THE INSTALLED SYSTEM.

4. THIS FACILITY'S EXISTING DIRECT-DIGITAL CONTROL (DDC) SYSTEM IS

MANUFACTURED BY VYKON (NIAGARA 4) AND ITS ECC IS LOCATEDAT CASTLE

POINT VAMC.

5. SEE SECTION 23 90 23 DIRECT DIGITAL CONTROLS IN THE SPECIFICATIONS

FOR MORE INFORMATION.