This document provides details for a federal contract opportunity to renovate the patient ward 4W step down unit at a Veterans Affairs Medical Center. The solicitation number is 36C24221B0001 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2. The opportunity type is a solicitation to renovate the 4W MED SURG 100 CD patient ward, as outlined in the drawings file 2021-0129_VAMC_4W MED SURG_100 CD_DRAWINGS_REVISED.pdf. No other details are provided regarding response dates, pricing terms, or set asides.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RESIDENT
SURG. SERV.
4184N
RESIDENTS
4137AN
STAFF LOUNGE
4135N
STAFF
LOCKERS
4136N
LOUNGE
4088S
EQUIP. STOR.
4127aC
SOIL. EQUIP.
4086AC
STOR.
4086C
STAFF LOUNGE
4085S
DISTRIBUTION
4127C
SERV. LOBBY
4128C
2 BEDROOM
4084S
TOILET
4054C
HAC
4053C
HAC
4052C
IT
4051C
DR. OFFICE
4046C
2 BED ROOM
4044W
TOILET
4043W
2 BED ROOM
4042W
PHYS. OFFICE
4041W
MEDS
4040W
NURSE
STATION
4039W
2 BED ROOM
4037W
ISOLATION
ROOM
4034W
2 BED ROOM
4032W
2 BED ROOM
4030W
4 BEDROOM
4028W
TOILET
4029W
TOILET
4031W
TOILET
4035W
ANTE
4033W
TOILET
4038W
HAC
4002W
TOILET
4003W
2 BED ROOM
4004W
DAY ROOM
4005W
STORAGE
4006W
TOILET
4006AW
SOIL. UTL.
4007W
TOILET
4008W
KITCHEN
4010W
FAMILY
COORD.
4011W
EXAM
4012W
STORAGE
4013W
CORRIDOR
4019W
2 BED ROOM
4014W
2 BED ROOM
4016W
TOILET
4015W
STOR.
4019aW
CLEAN LINEN
4018W
SUPPLY
4017W
ELEC. CLOS.
4013W
TOILET
4020W
TOILET
4021W
ANTE
4023W
ISOLATION
ROOM
4022W
4 STAIR W
4STW
HOSE
CLOSET
4015W
2 BED ROOM
4024W
2 BED ROOM
4027W
TOILET
4026W
VERNACARE
4024aW
ELEC.
4049C
FEC
4053C
ELEC. CLOS.
4025aW
ELEC. CLOS.
4025bW
STORAGE
4001aW
STORAGE
4001bW
4 STAIR C
4STC
CONNECTION TO OR'S
(BUILDING 6)
OPEN TO
BELOW
STAFF
LOCKERS
4138N
STAFF TOILET
4137N
WAITING
4132N
TOILET
4130N
TOILET
4131N
CORRIDOR
4180N
HOSPITAL
DIRECTOR
3022W
ADMIN
ASSISTANT
3029W
EXEC. CHIEF
OF STAFF
3021W
ASS. DIRECTOR
PATIENT SERV.
3020W
PERF. IMPROV
MGR
3019WSTAFF
ASSISTANT
3024W
HEALTH SYS.
SPEC. COS
3032W
STAFF
ASSISTANT
3033W
DATA
MANAGER
3034W
BUSINESS
OFFICER
3035W
CONFERENCE
A
3036W
ASSOCIATE
DIRECTOR
3023W
F.A.C.
3015W
EL. CLOS.
3011W
T. STAFF MALE
3009W
T. STAFF
FEMALE
3010W
CORRIDOR
3010AW
CONFERENCE
PM.
3011EW
WAITING
3011W
STORAGE
3011DW
ACNS OPC.
COORDINATOR
3011CW
INFO. MGR.
3011AW
ADMIN.
RESIDENT
3010W
LOCKERS-FAX-COPY
3008A-W
FILES
3008B-W
OFFICE
(F.FRASER)
3008W
PROGRAM
MNG. OFFICE
3007W
M.V.P.
CO-COORDINATOR
3005W
CLOSET
3006W
HOUSEKEEPING
3003C
CONFERENCE
B
3036BW
EEO
SPECIALIST
3036C
PATIENT REP.
PROG.
3037C
PATIENT REP.
PROG.
3038C
ELEC. CLOSET
3001C
3 STAIR C
3STC
ELEVATOR
LOBBY
3000C
CORRIDOR
3039C
F.E.C.
3045C
CORRIDOR
3040C
FILE STORAGE
3061AE
DISTR.
3077C
EQUIP. STOR
3078C
SERVICE
LOBBY
3076C
PAT. SERVICES
SUPERVISOR
3038C
SECRETARY
MEDICAL
3043S
DEPUTY PL
MANAGER
3043S
CORRIDOR
3041S
MED CARE LINE
MANAGEMENT
3075S
NURSE
EDUCATOR
3075AS
CONFERENCE
ROOM
3076S
DIET.
VOLUNTEER
3081E
SALAD PREP
3080C
CORRIDOR
3102E
J.C.
3103C
L.C.
3102C
STORAGE
ROOM
3101C
UTILITY
3100E
DISH WASHERS
3105C
KITCH. & DISH
WASHING
3107N
CORRIDOR
3109N
SEC. TO CHIEF
3123N
CHIEF
DIETETIC
SERVICE
3123N
PROGRAM
CLERK
3123BN
DIETECIAN
3123N
TOILET
3123EN
TOILET
3123EN
MECHANICAL
ROOM
3122N
3078C
3 STAIR W
3STW
NATIONAL
ETHICS CTR.
3011BW
ICRA & PHASING LEGEND
ICRA & PHASING KEYED NOTEX
PHASING IMPACT AREA - STAGE 1
PHASING IMPACT AREA - STAGE 2
GENERAL ICRA & PHASING NOTES
PHASING IMPACT AREA - STAGE 3
SPECIFIC ICRA & PHASING NOTES
TEMPORARY FULL HEIGHT ICRA BARRIER SEALED AIR-
TIGHT, REFER TO PARTITION TYPE 11b
A. TYPE OF CONSTRUCTION PROJECT ACTIVITY:
TYPE D - MAJOR DEMOLITION AND CONSTRUCTION
PROJECTS. INCLUDES, BUT IS NOT LIMITED TO ACTIVITIES
WHICH REQUIRE CONSECUTIVE WORK SHIFTS; REQUIRES
HEAVY DEMOLITION OR REMOVAL OF A COMPLETE
CABLING SYSTEM; NEW CONSTRUCTION; ASBESTOS
ABATEMENT WORK.
B. PATIENT RISK GROUPS THAT WILL BE AFFECTED:
HIGH RISK: CCU, EMERGENCY ROOM, LABORATORIES
(SPECIMEN), OUTPATIENT SURGERY, PHARMACY, POST
ANESTHESIA CARE UNIT, SURGICAL UNITS
C. DESCRIPTION OF REQUIRED INFECTION CONTROL
PRECAUTIONS BY CLASS (IV):
DURING CONSTRUCTION OF PROJECT:
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING
DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS I.E. SHEETROCK,
PLYWOOD, PLASTIC, TO SEAL AREA FROM NON-WORK
AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH
PLASTIC COVERING AND SEALED CONNECTION TO WORK
SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT)
BEFORE CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE
UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS.
4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES
APPROPRIATELY.
5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL
TO PASS THROUGH THIS ROOM SO THEY CAN BE
VACUUMED USING A HEPA VACUUM CLEANER BEFORE
LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER
COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE
THE WORK SITE.
6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED
TO WEAR SHOE COVERS. SHOE COVERS MUST BE
CHANGED EACH TIME THE WORKER EXITS THE WORK
AREA.
7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL
COMPLETED PROJECT IS INSPECTED BY THE OWNER’S
SAFETY DEPARTMENT AND INFECTION CONTROL
DEPARTMENT AND THOROUGHLY CLEANED BY THE
OWNER’S ENVIRONMENTAL
SERVICES DEPARTMENT.
8. NOTE: ALL ASBESTOS ABATEMENT WORK SHALL BE
PERFORMED AS CLASS IV WORK, AND IS FURTHER
SUBJECT TO ADDITIONAL PROVISIONS OF THE NY STATE
ASBESTOS REGULATIONS (NY DEPARTMENT OF LABOR
INDUSTRIAL CODE RULE 56).
UPON COMPLETION OF PROJECT:
1. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE
SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH
CONSTRUCTION.
2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT
IN TIGHTLY COVERED CONTAINERS.
3. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE
COVERING UNLESS SOLID LID.
4. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.
5. WET MOP AREA WITH DISINFECTANT.
6. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE
WORK IS BEING PERFORMED.
7. FOR ASBESTOS ABATEMENT WORK, CONFIRM THAT THE
LICENSED PROJECT MONITOR HAS PERFORMED A FINAL
VISUAL INSPECTION AND CONDUCTED CLEARANCE AIR
SAMPLING AS REQUIRED UNDER NY STATE ASBESTOS
REGULATIONS (NY DEPARTMENT OF LABOR INDUSTRIAL
CODE RULE 56).
D. CONSTRUCTION BARRIER MUST BE APPROVED BY COR &
SAFETY MANAGER PRIOR TO START OF CONSTRUCTION WORK.
E. SWING SPACE WILL BE REQUIRED TO FACILITATE NEW WORK.
EXACT LOCATION TBD PRIOR TO NOTICE TO PROCEED FOR
CONSTRUCTION. COORDINATE SCOPE AND LOCATION WITH VA
PROJECT MANAGER.
F. PROVIDE STICKY WALK-OFF MATS ON BOTH SIDES OF ALL ICRA
DOORS AND ACCESS POINTS.
G. CONTRACTOR TO COORDINATE TEMP PARTITION LOCATIONS
WITH THE OPERATIONAL AND SECURITY REQUIREMENTS OF THE
VETERANS ASSOCIATION (VA). TEMP BARRIER TO BE PARTITION
TYPE 11b. CONTRACTOR TO PROVIDE 45 MINUTE DOOR TYPE F (3'-0" X 7'-0") WITH HOLLOW METAL FRAME TYPE a. DOOR TO
INCLUDE HARDWARE TYPE HW-5 WHICH INCLUDES AN EXIT
DEVICE, CLOSER AND STORAGE ROOM LOCKSET WITH 6 SETS OF
KEYS CREATED FOR USE BY CONTRACTOR & VA.
H. CONSTRUCTION BARRIER MUST BE INSTALLED AND APPROVED
BY COR & SAFETY MANAGER PRIOR TO START OF ANY
CONSTRUCTION WORK.
I. GC SHALL PROVIDE ALL ICRA ELEMENTS FOR ALL AREAS OF
WORK. COORDINATE WITH WORK SHOWN BY ALL DISCIPLINES,
ESPECIALLY WITH EXISTING OCCUPIED SPACES.
J. COORDINATE ICRA PLAN WITH CONSTRUCTION PHASES. NOT ALL
ICRA PARTITIONS ARE SHOWN ON THESE PLANS. ALL PHASES
MUST BE COORDINATED WITH THE OWNER PRIOR TO ANY WORK.
K. COORDINATE ALL SHUT-DOWNS WITH OWNER AND
COSNTRUCTION MANAGER AS PART OF ICRA REQUIREMENTS.
L. PROTECTIVE COVERALLS AND SHOE COVERS ARE REQUIRED
FOR ALL WORK TO BE DONE IN EXISTING BUILDING.
M. FOR PHASE 3, DESCRIPTION OF REQUIRED INFECTION CONTROL
PRECAUTIONS BY CLASS (II):
DURING CONSTRUCTION OF PROJECT:
1. PROVIDE AVTICE MEANS TO PREVENT AIRBORNE DUST
FROM DISPERSING INTO ATMOSPHERE.
2. WATER MIST WORK SURFACES TO CONTROL DUST
WHILE CUTTING.
3. SEAL UNUSED DOORS WITH DUCT TAPE.
4. BLOCK OFF AND SEAL AIR VENTS.
5. PLACE DUCT MAT AT ENTRANCE AND EXIT OF WORK
AREA.
6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE
WORK IS BEING PERFORMED.
UPON COMPLETION OF PROJECT:
1. WIPE WORK SURFACES WITH DISINFECTANT.
2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT
IN TIGHTLY COVERED CONTAINERS.
3. WET MOP AND/OR VACUUM WITH HEPA FILTERED
VACUUM BEFORE LEAVING WORK AREA.
4. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE
WORK IS BEING PERFORMED.
PROJECT IMPACT AREA
EXISTING FULL HEIGHT PARTITION AS BARRIER
STAFF/PATIENT TRAFFIC FLOW
SECURE STAIR DURING CONSTRUCITON. PROVIDE
TEMPORARY LOCK TO RESTRICT RE-ENTRY INTO THE
UNIT, BUT PROVIDE FREE EGRESS INTO THE STAIRWELL,
COORDINATE WITH VA TO PROVIDE KEYS FOR SECURITY
AND FACILITIES..
PROVIDE TEMPORARY BARRIER, HM DOOR WITH CARD
READER ACCESS TO RESTRICT ACCESS INTO BUILDING 6
DURING CONSTRUCTION, COORDINATE WITH VA TO
PROVIDE KEYS FOR SECURITY AND FACILITIES..
CONTRACTOR TO COORDINATE SCHEDULED WORK NEAR
THE ENTRANCES TO 4N AND 4S WITH THE VA TO
FACILITATE NEW SCOPE OF 4 CENTRAL. CONCEPT
SHOWN IS TO SHUTDOWN ONLY ONE ENTRANCE AT A
TIME SO THAT TRAFFIC AND EGRESS FROM CENTRAL
ZONE IS ACCESSIBLE IN AT LEAST ONE DIRECTION. ICRA
PRECAUTIONS IN THIS ZONE IS LIMITED TO CLASS II (TYPE
C, LOW RISK).
4N AND 4S ONLY HAVE 1 MEANS OF EGRESS AVAILABLE IF
ENTRANCE IS SHUTDOWN. PROVIDE ABILITY TO EXIT
THROUGH AREA OF WORK IN CASE OF EMERGENCY.
PROVIDE TEMPORARY BARRIER, HM DOOR WITH CARD
READER ACCESS TO RESTRICT ACCESS INTO THE
CONSTRUCTION ZONE, COORDINATE WITH VA TO
PROVIDE KEYS FOR SECURITY AND FACILITIES.
EGRESS PATH
HEPA EXHAUST UNIT TO EXTERIOR
NEGATIVE AIR MONITOR (BALL-IN-WALL OR EQUAL)
UTILIZE EXISTING DOOR AS CONSTRUCTION ENTRANCE.
PROVIDE TEMPORARY HARDWARE TO ALLOW FOR
LOCKING, COORDINATE WITH VA TO PROVIDE KEYS FOR
SECURITY AND FACILITIES.
TEMPORARILY REMOVE RESTRICTED ACCESS
CAPABILITIES TO ALLOW ACCESS FROM ELEVATORS TO
4N, 4S AND 4 CENTRAL.
SECOND MEANS OF EGRESS FROM 4S, 4N AND 4CENTRAL
IS AVAILABLE IN BOTH 4S AND 4N WINGS.
TWO MEANS OF EGRESS IS AVAILABLE FROM
CONSTRUCTION PHASE 1 IN THE 4W WING WITHOUT
BEING REQUIRED TO EXIT THE ZONE.
MAINTAIN OPERATIONS OF 4 ELEVATOR BAYS DURING
CONSTRUCTION PHASE 1 AND 2. COORDINATE
SHUTDOWN AND ACCESS CONTROL OF ELEVATORS WITH
OWNER.
TEMPORARY ICRA POLY BARRIER WITH ZIPPER ACCESS
DOOR.
STAFF
LOCKERS
4136N
LOUNGE
4088S
EQUIP. STOR.
4127aC
SOIL. EQUIP.
4086AC
STOR.
4086C
STAFF LOUNGE
4085S
DISTRIBUTION
4127C
SERV. LOBBY
4128C
TOILET
4054C
HAC
4053C
HAC
4052C
IT
4051C
DR. OFFICE
4046C
2 BED ROOM
4044W
HAC
4002W
ELEC.
4049C
FEC
4053C
4 STAIR C
4STC
STAFF
LOCKERS
4138N
WAITING
4132N
CORRIDOR
4180N
5 7
STAFF
LOCKERS
4136N
LOUNGE
4088S
EQUIP. STOR.
4127aC
SOIL. EQUIP.
4086AC
STOR.
4086C
STAFF LOUNGE
4085S
DISTRIBUTION
4127C
SERV. LOBBY
4128C
TOILET
4054C
HAC
4053C
HAC
4052C
IT
4051C
DR. OFFICE
4046C
2 BED ROOM
4044W
HAC
4002W
ELEC.
4049C
FEC
4053C
4 STAIR C
4STC
STAFF
LOCKERS
4138N
WAITING
4132N
CORRIDOR
4180N
STOR.
4086C
SERV. LOBBY
4128C
HAC
4053C
FEC
4053C
CORRIDOR
4180N
4 3
WEST
SOUTH NORTH
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
NTS
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc. 423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Sheet Number 113of
1-G204W
ICRA & PHASING - 3RD & 4TH FLOOR
- WEST & CENTRAL
Checker Author
630-18-101
December 18, 2020 5
SCALE: 1/16" = 1'-0"
F4
ICRA & PHASING PLAN 4TH FLOOR
SCALE: 1/16" = 1'-0"
F6
ICRA & PHASING PLAN 3RD FLOOR
SCALE: 3/32" = 1'-0"
F1
ICRA & PHASING PLAN 4TH FLOOR - PHASE 1
SCALE: 3/32" = 1'-0"
C1
ICRA & PHASING PLAN 4TH FLOOR - PHASE 2
SCALE: 3/32" = 1'-0"
A4
ICRA & PHASING PLAN 4TH FLOOR - PHASE 3
0 16' 32'0 16' 32'0 21'-4"10'-8"
0 21'-4"10'-8"
0 21'-4"10'-8"
ADDENDUM #1 1 06/05/2013
PULL
PULL
PAPER
TOWEL
DISPENSER
SOAP
DISPENSER
FULL
LENGTH
MIRROR
ACCESSIBLE
COAT HOOK
COAT
HOOK
SOAP
DISPENSER
NOTE: ALL DIMENSIONS INCLUDE ALL OPERABLE LEVERS.
DIGITAL
CLOCK
SHARPS
RECEPTACLE
PAPER TOWEL
DISPENSER
GLOVE BOX
HOLDER
CLINICAL
SERVICE
SINK
DIAGNOSTIC
SET
HAND
SANITIZER
NOTE: LIGHT SWITCH ALWAYS LOCATED ON SIDE CLOSER TO ROOM ENTRY DOOR.
CL
1'-6" 2'-11" 1" FILLER
CL1'-6"
2' -6
2' -6
" 3' -8
4' -6
3'
-6
3' -8
9" 9"
FOOT WALL
5' -0
2' -5
1' -3
M
IN
DIAPER
CHANGING
TABLE
NAPKIN
DISPENSER
4' -0
NOTE: CONTRACTOR TO COORDINATE IN FIELD TO ASSURE THAT A 2'-0"
SPACING IS MAINTAINED BETWEEN RECEPTACLES THAT ARE BACK TO BACK
WITHIN THE SAME PARTITION AT THE SAME MOUNTING HEIGHT.
5' -6
CL
5' -0
1'
-6
TELEVISION
5' -6
CL
MIRROR
INSULATE DRAIN
AND WATER PIPES
DASHED AREA
INDICATES
ACCESSIBLE KNEE
AND TOE CLEARANCE
SPACE
WALL MOUNTED LAVATORY
8" MIN
M
IN
N O
N A
C C
E S
S
IB
L E
A C
C E
S S
IB
L E
M
A X
1'-3" MIN
TOP OF
SPOUT
EQUIPMENT
PERMITTED IN
AREA SHOWN
DASHED
ELECTRIC WATER COOLER
"4
A5145.2
18" WIDE STAINLESS
STEEL SHELF
MOP HOLDER
SERVICE
FAUCET AND
CONTROLS
MOP BASIN
HAC
5" MAX
1'-3" MIN
PAPER TOWEL DISPENSER
6" MAX
FLOOR MOUNTED TOILET WITH
RETRACTABLE GRAB BARS
GRAB BARS
(ACCESSIBLE
ONLY)
SIDE
VIEW
FRONT
VIEW
SIDE
VIEW
FRONT
VIEW
SIDE
VIEW
FRONT
VIEW
1'-6" MIN
1'-8" MAX
TOILET PAPER
DISPENSER
NOTE: ACCESSIBLE AND NON-ACCESSIBLE PLUMBING FIXTURES ARE INDICATED IN THE PLUMBING DRAWINGS.
M
IN
6" MAX8" MIN
A
C C
E S
S
IB
L E
S T
A N
D A
R D
M
IN
PERPENDICULAR WALL OR
PROJECTING ELEMENT 4" MAX PROJECTION
/4
/4
1'-8" MAX
1'-6" MIN
S
T A
N D
A R
D
A
C C
E S
S
IB
L E
GRAB BARS
TOILET PAPER
DISPENSER
WATER
CLOSET
LOW HEIGHT
FLUSH VALVE
FLOOR MOUNTED TOILET
1'-0" 6"2'-0"1'-0" 3'-6"
SIDE
VIEW
FRONT
VIEW
2' -1
0"
1'-1"
A L
IG
N
CL
4' -8
WALL MOUNTED
LIGHT FIXTURE
9" ±
M
IN
". 2' -1
0"
M
IN
1' -3
" 2' -1
0"
1' -5
7"-9". 7"-9"
1'-3"
SOAP DISPENSER
PAPER TOWEL
DISPENSER
NC
1'-8"
3' -8
NURSE CALL
SOAP DISPENSER
1'-8"EQ EQ
"5
HALL LANTERNS
RAISED
BRAILLE
CHARACTERS
ON HOISTWAY
ENTRANCES
HALL CALL
BUTTON
BULLETIN
BOARD
INTERACTIVE
WHITE BOARD
LENGTH VARIES 2
C
L E
A R
FIRE ALARM
PULL BOX
M A
X
IM
U M
FIRE
EXTINGUISHER
WALL HUNG
FIRE EXTINGUISHER
IN RECESSED
CABINET
PULL HANDLE
LINE MOUNTED AT
TOP OF BASE
FIRE ALARM
SPEAKER
7' -6
U
.O .N
ALIG
N
FIRE ALARM
COMBINATION
SPEAKER/STROBE
OR STROBE
VAV BOX
LOCATION
CABLE TRAY
VAV BOX
LOCATION
EQ EQ
ACCESS ZONE
2'-0"
ZONE
LIGHT FIXTURE
ACCESS ZONE
2'-0"
MECHANICAL
PIPING
FIRE PROTECTION
PIPING
ELECTRICAL
CONDUIT
SCHEDULED
CEILING FINISH
SMOKE AND ACOUSTIC
SEALANT AT ALL
PERIMTER AND
PENETRATIONS OF
CORRIDOR FACING
WALLS. (TYP)
SCHEDULED
FLOOR FINISH
SCHEDULED SMOKE
BARRIER PARTITION.
TYPICAL AT
CORRIDORS
MECHANICAL
DUCT TRUNK
TYPICAL
CORRIDOR
N O
T E
D O
T H
E R
W
IS
E
U
N L E
S S
AUDIO FIRE
ALARM ONLY
EXIT SIGN FIRE ALARM
PULL STATION
(GENERALLY
LOCATE UNDER
A/V ALARM)
W
IT
H O
W N
E R
C O
O R
D
IN
A T
E
8"
COMBINATION
POWER/SIGNAL/OUTLET
FOR WALL MOUNTED
TELEVISION OR
MONITOR
T.V./DATA/
PHONE
POWER
RECEPTACLES
LIGHT
SWITCHES
DOME
LIGHT
OCCUPANCY
SENSOR
CARD
READER
POWER
DISCONNECT
REMOTE DOOR
RELEASE
"5
M
A X
RECEPTACLES AT
TYPICAL CASEWORK
ASSEMBLY
TYPICAL
WORKSTATION
ASSEMBLY
".3
CLEAR
2'-6"
TV
D/V
TV E
E
ED/V
L L OS CR DR E
E
E
D/V
EM
T
EQ EQ
ALIGN
THERMOSTAT AT
PERIMETER CONVECTOR
POWER/DATA
RECEPTACLES AT WALL
MOUNTED COMPUTER
STATIONS
P D
AUDIO/VISUAL FIRE ALARM,
NURSE CALL, THERMOSTAT,
HAND SANITIZER, WALL
SWITCH
NOTE: DOME LIGHTS AT END OF CORRIDORS ARE CEILING MOUNTED. DOME LIGHTS OUTISDE OF PATIENT TOILETS ON 10TH FLOOR ARE WALL MOUNTED.
EQ EQ
ALIGN
1' -6
3' -6
6' -5
/2
4' -6
NC
ALIGN
6"
D O
O R
F R
A M
E 1"
A B
O V
E
EQ EQ
DOME LIGHT ABOVE
DOOR FRAME
NOTE: CONTRACTOR TO COORDINATE IN FIELD TO ASSURE THAT A 2'-0" SPACING IS MAINTAINED BETWEEN RECEPTACLES THAT ARE BACK TO BACK WITHIN THE SAME PARTITION AT THE SAME MOUNTING HEIGHT.
NEW METAL
CONVECTOR
COVER
WINDOW
NIGHT LIGHT, THERMOSTAT,
WALL SWITCH, AND FIRE
ALARM WHERE APPLICABLE
AT PATIENT BATHS, PUBLIC
TOILET, AND STAFF TOILET.
6"
1' -6
3' -6
" 4' -6
NIGHT
LIGHT
PANIC
BUTTON
NC
3' -8
NURSE CALL
PULL
STATION
NC
PULL
STATION AT
SHOWER
PULL
STATION AT
WATER
CLOSET
6' -0
1' -6
ALIGN
TT
CL
M
IN
LOCATE
SIGN ON
LATCH SIDE
OF DOOR
D
IM
E N
S
IO
N S
S E
E C
O D
E S
IG
N
A G
E
A D
A D
E T
A
IL
S F
O R
2"
WALL MOUNTED
EXIT SIGN
NOTE: REFER TO 1-AG DRAWING SERIES (WAYFINDING)
FOR ADDITIONAL INFORMATION.
TACTILE CHARACTERS
BASELINE ZONE: 48" - 60"
MIN.
9"
CL
SINGLE DOOR
POSITION ON LATCH SIDE OF DOOR OR NEAREST
ADJACENT WALL, AT A 9" MIN DISTANCE FROM THE
CNTER OF THE RAISED CHARACTERS ON THE SIGN.
EXCEPTION: PERMITTED ON THE PUSH SIDE OF DOORS
WITH CLOSERS BUT WITHOUT HOLD OPEN DEVICES.
CL
INACTIVE ACTIVE
MIN.
9"
CL
MIN.
9"
LOWEST TACTILE CHARACTER
BASELINE NOT PERMITTED BELOW
CHARACTER BASELINE ZONE
DOUBLE DOOR
POSITION ON INACTIVE DOOR LEAF. IF TWO
ACTIVE LEAFS, SIGN GOES TO RIGHT OF RIGHT
HAND DOOR. IF NO SPACE THERE, THEN ON
NEAREST ADJACENT WALL.
LOREM
IPSUM
HIGHEST TACTILE
CHARACTER BASELINE
LOWEST TACTILE
CHARACTER BASELINE
SIGN
HIGHEST TACTILE CHARACTER
BASELINE NOT PERMITTED ABOVE
CHARACTER BASELINE ZONE
VACUUM BREAKER
SHOWER SLIDE WITH
HAND HELD SHOWER
AND 60" HOSE
1'-6" 6"
RECESSED SST
SHELF
CONTROL WALL
THERMOSTATIC
MIXING VALVE
4" 1'
-6
6"
3'-0"
2' -1
0"
SIDE WALL
1'-6" 6"
2' -1
0" 5"
NOTE: SHOWER HOSE VACUUM BREAKER SHALL BE LOCATED A MINIMUM OF
6" ABOVE HAND SPRAY AT UPPERMOST POSITION ON SLIDE BAR.
NC
6"
9 1/2" 1'-5"
1'-6"
6"
9 1/2"
/4
/4
/4
" 6"
RED
WHITE TEXT
1/32" THK RAISED LASER CUT AND
APPLIED LETTERING
ROWMARK BLACK - ADA ALTERNATIVE
CLEAR RASTER BRAILLE
REDUNDANT, GRADE II
3/16" THK CLEAR NON-GLARE ACRYLIC LENS WITH
2ND SURFACE FLANGE AT TOP AND BOTTOM
1/4 W X 3/8" D FABRICATED ALUMINIUM OUTER
FRAME. SATIN ANODIZED FINISH
/4
/4
/4
2 3 4 1
1'-6"
ELEVATOR
3002.3 EMERGENY SIGNS
TOILET FACILITY
1111.1 ACCESSIBILITY SIGNAGE
BUILDING EXITING LOCATION MEANS OF EGRESS
1011 EXIT SIGNAGE
MEANS OF EGRESS
1023.9 STAIRWAY
IDENTIFICATION SIGNS
MEANS OF EGRESS
1007.9 SIGNAGE
CORRESPONDING GRADE II BRAILLE.
1/10" WITHIN CELL. 2/10" BETWEEN CELLS,
1/40" MIN. RAISE ABOVE THE
BACKGROUND. LOCATED 3/8" MIN. BELOW
TACTILE CHARACTERS
WALL MOUNTED SIGNAGE TO BE LOCATED ON LATCH SIDE
OF DOOR, CLEAR OF DOOR SWING. TACTILE CHARACTERS
SHALL BE CENTERED ON A MIN 18"X18" AREA LOCATED
OUTSIDE THE ARC SWING OF THE DOOR. BRAILLE SHALL
COMPLY WITH ADAAG 703.3.1, 703.3.2, FIGURE 703.31, AND
TABLE 703.3.1
AREA OF
RESCUE
ASSISTANCE
H
IG
H E
S T
L
IN
E O
F T
E X
T
M A
X T
O B
O T
T O
M O
F
O F
L O
W E
S T
L
IN
E O
F
M
IN
T O
B O
T T
O M
T A
C T
IL
E
C H
A R
A C
T E
R S
T A
C T
IL
E
C H
A R
A C
T E
R S
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc. 423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Sheet Number 113of
1-A002
TYPICAL MOUNTING HEIGHTS
GV LP
630-18-101
December 18, 2020 12
SCALE: 1/4" = 1'-0"
EQUIPMENT AND ACCESSORIES
SCALE: 1/4" = 1'-0"
ACCESSORIES AND PLUMBING FIXTURES
SCALE: 1/4" = 1'-0"
ELEVATOR CONTROLS
SCALE: 1/4" = 1'-0"
VISUAL DISPLAY BOARDS
SCALE: 1/4" = 1'-0"
FIRE PROTECTION EQUIPMENT
0 4' 8'
0 4' 8'
0 4' 8'
0 4' 8' 0 4' 8'
0 4' 8'
0 4' 8'
0 4' 8'
SCALE: 1/2" = 1'-0"
TYPICAL CORRIDOR SECTION
SCALE: 1/4" = 1'-0"
ELECTRICAL CONTROL DEVICES
SCALE: 1/4" = 1'-0"
SPACE SIGNAGE
SCALE: 1/4" = 1'-0"
ACCESSIBLE SHOWERS
SCALE: 1" = 1'-0"
1-A002_3_
0 2' 4'
0 2'1'
ADDENDUM #1 1 06/05/2013
R.O.
+/- 7'-1"
R .O
- 6
'-9
2' -3
- 6
2' -9
9' -6
RELOCATE STEEL CHANNELS AS REQUIRED
TO ACCOMMODATE NEW HEATING UNIT, MAINTAIN
CHANNELS FOR SILL SUPPORT
EXISTING ORIGINAL STEEL WINDOW FRAME/ STEEL
SURROUND AND STEEL CHANNEL
ASSEMBLY TO REMAIN
EXTENT OF WINDOW REMOVAL, SEE DEMO DETAIL FOR ADDITIONAL INFO.
NEW DEMO
NOTE: VIEW SHOWN IS TYPICAL FROM THE INTERIOR AND
NEGATES EXISTING FINISHES AND RADIATOR COVER TO BE
REMOVED FOR DIAGRAMMATIC PURPOSES. SEE FLOOR
PLANS AND SCHEDULES FOR ADDITIONAL INFORMATION.
LOCATION/ CONFIGURATION OF PROPOSED
METAL RADIATOR COVERCOORD WITH MECH
+/- 4'-0"
LOCATION/ OF PROPOSED RADIATOR
B6
1-A451
OPH
SCOPE OF WORK AT EXISTING ORIGINAL WINDOW FRAMES AND STEEL SURROUND TO REMAIN:
- PATCH, INFILL, AND REPAIR EXISTING MASONRY WALL CONSTRUCTION IN KIND - AS REQUIRED
TO MAKE READY FOR NEW WORK. SEE SECTION AND WINDOW DETAILS FOR ADDITIONAL INFO.
-REINFORCE, RE-ATTACH, OR REPLACE DETERIORATED STEEL TABS, CLIPS, ANGLES, AND
ANCHORS FOR STEEL WINDOW FRAMES IN KIND - AS REQUIRED TO MAKE READY FOR NEW
WORK.
+/- 8"
- 5
+/- 8"
F1
1-A451
F5
1-A451
SCOPE OF WORK FOR EXISTING ORIGINAL STEEL WINDOW MULLION/ SUPPORT MEMBER TO REMAIN:
-REINFORCE, RE-ATTACH, AND REPLACE DETERIORATED STEEL CLIPS, ANGLES, AND ANCHORS FOR STEEL MULLION IN KIND - AS REQUIRED TO MAKE READY FOR NEW WORK. SEE TYPICAL WINDOW CENTER MULLION DETAIL FOR ADDITIONAL INFO. INCLUDE (1) 2X6 INTERMEDIATE VERTICAL MULLION
(ALUMINUM TUBE, 6063-75 MATERIAL MIN.)
F8
1-A451
1'-4 3/4" +/-
CL
+/- 1'-3 1/2"
+/- 1'-3 1/2"
HEAD
JAMB
SILL
- 2
'-8
/4
- 6
- 5
- 1
/2
- 2
'-6
- 2
/4
3"
E X
IS
TI
N G
M .O
- 7
'-0
- 1
/2
REMOVE ALUMINUM WINDOW
SYSTEM AND ASSOCIATED
EXTERIOR AND INTERIOR TRIM,
INCLUDING ATTACHMENTS,
CAULKING, BACKER ROD, ETC.
EXISTING ORIGINAL STEEL
WINDOW FRAME/ STOOL
ASSEMBLY TO REMAIN
EXISTING MASONRY
WALL CONSTRUCTION
EXISTING ALCOA SILL
TO REMAIN, REMOVE
ALL CAULK, CLEAN
AND PREP FOR NEW
WORK
REMOVE CEILING SYSTEM,
SUPPORTS AND
ATTACHMENTS IN ITS
ENTIRETY
R .O
REMOVE EXISTING
RADIATOR COVER AND
ATTACHEMENTS AS
REQUIRED FOR NEW
WORK
SILL BELOW TO REMAIN
EXISTING ORIGINAL STEEL
WINDOW FRAME AND STEEL
CHANNEL FRAMING ASSEMBLY TO
REMAIN
EXISTING ORIGINAL STEEL
WINDOW FRAME AND STEEL
CHANNEL FRAMING ASSEMBLY TO
REMAIN
REMOVE ALUMINUM WINDOW
SYSTEM AND ASSOCIATED
EXTERIOR AND INTERIOR TRIM,
INCLUDING ATTACHMENTS,
CAULKING, BACKER ROD, ETC.
+/- 9 1/2"
1'-4 3/4" +/-
+/- 1'-3 1/2"
+/- 1'-3 1/2"
HEAD
- 5
WORK POINT
GWB AT JAMB BEYOND
REFER TO REFLECTED CEILING
PLANS AND DETAILS FOR
CEILING/ SOFFIT CONFIGURATION
2 1/2" METAL STUD FURRING AT
16" O.C., MECHANICALLY
FASTENED TO EXISTING STEEL
WINDOW SURROUND TO REMAIN
INFILL STUDS WITH 1 1/2" SPRAY FOAM
INSULATION, INSTALL CONTINUOUS 1" SPRAY
FOAM INSULATION BEHIND FURRING, TOTAL
= 2 1/2" SPRAY FOAM INSUALTION
4" SPRAY FOAM INSULATION
SCHEDULED BASE
GWB WITH 1 5/8" METAL STUD
FURRING, 16" O.C., INSTALL STUDS
1" MIN. FROM EXISTING MASONRY
EXTERIOR WALL
EXISTING
MASONRY WALL
CONSTRUCTION
EXISTING ORIGINAL GROUTED STEEL
WINDOW FRAME/ SURROUND ASSEMBLY AND
ATTACHMENTS TO REMAIN
NOTE:
CONTRACTOR IS RESPONSIBLE TO INFILL,
REPAIR, REPLACE, OR RE-ATTACH
MATERIALS AS REQUIRED FOR NEW WORK.
SEE DETAIL B1 THIS SHEET FOR ADDITIONAL
INFO.
FACE OF EXISTING WALL
1/ 2"
S E
E S
C H
E D
U
LE
W
IN
D O
W
- 3
S E
E S
C H
E D
U
LE
R O
U G
H O
P E
N
IN
G
1/
2" 2'
-6 " 2' -9
/2
5/8" GWB TO DECK ABOVE, SPACKLED AND SANDED
3/ 4"
1/ 4"
PAINT EXPOSED JOINT
CONT 'J' BEAD
EXISTING ORIGINAL GROUTED STEEL WINDOW
FRAME/ SURROUND ASSEMBLY AND
ATTACHMENTS TO REMAIN
NOTE:
CONTRACTOR IS RESPONSIBLE TO INFILL,
REPAIR, REPLACE, OR RE-ATTACH MATERIALS
AS REQUIRED FOR NEW WORK. SEE DETAIL
B1 THIS SHEET FOR ADDITIONAL INFO.
EXISTING ORIGINAL GROUTED STEEL WINDOW
FRAME/ SURROUND ASSEMBLY AND
ATTACHMENTS TO REMAIN
NOTE:
CONTRACTOR IS RESPONSIBLE TO LEVEL, INFILL,
REPAIR, REPLACE, OR RE-ATTACH MATERIALS
AS REQUIRED FOR NEW WORK. SEE DETAIL B1
THIS SHEET FOR ADDITIONAL INFO.
EXISTING CONCRETE
CURB
SILL
FIRESTOPPING
2 1/2" SPRAY FOAM INSULATION
WOOD BLOCKING
GWB, PTD.
5/8" GWB, SPACKLED
AND SANDED
1/ 2"
3 1/4" FROM FACE OF EXISTING STEEL SURROUND
FACE OF FURRED OUT WALL-VARIES,
REFER TO FLOOR PLANS
METAL STUD FURRING TO DECK ABOVE,
INFILL STUDS WITH 1 1/2" SPRAY FOAM
INSULATION
JAMB
SOLID SURFACE SILL WITH EASED EDGES
ON FIRE RETARDENT PLYWOOD
ALUMINUM WINDOW SYSTEM
ALUMINUM WINDOW SYSTEM
3 5/8" BATT INSULATION
3 1/4" FROM FACE OF EXIST STEEL SURROUND
3 1/4" FROM FACE OF
EXISTING STEEL SURROUND
COL
1" GAP, MIN.
1 5/8" METAL STUD FURRING AT
16" O.C., MECHANICALLY
FASTENED TO EXISTING STEEL
WINDOW SURROUND TO REMAIN
SEALANT
1" GAP
1-A453 B7
1-A453 F7
EXIST. STL CHANNEL BEYOND
EXIST.
EXTERIOR
MASONRY WALL
FACTORY PTD. MTL
RADIATOR REMOVABLE
COVER
FIN TUBE RADIATOR,
REFER TO MECH DWGS.
MTL TOE CLIP
EXIST. CONC.
OPEN BACK DESK WHERE OCCURS,
REFER TO FLOOR PLANS
SCHEDULED BASE
FIRE RETARDENT WD.
BLOCKING ON 1-5/8" MTL.
STUDS @ 16" O.C.
SEALANT
1 1/4" FLUID APPLIED THERMAL
BARRIER COATING OVER 4"
SPRAY FOAM INSULATION.
NEW WINDOW SYSTEM
NOTE: REFER TO SECTION DETAILS AND
WINDOW SCHEDULE FOR WINDOW
TYPES, DIMENSIONS, AND TYPICAL NOTES
BENT SHEET MTL SPACED
1" FROM FIN TUBE
1-5/8" MTL. STUDS
3/ 4"
1/ 4"
4" 6"
4" 6"
4"
TO FACE OF NEW WALL
1'-7 1/2"
6"
R A
D
IA
T O
R C
O V
E R
2' -0
1"
2 1/2" SPRAY FOAM INSULATION
1" 1"
B6
1-A451
/2
EXIST. STL CHANNEL TO REMAIN
EXIST. EXT MASONRY WALL
FACTORY PTD. METAL
RADIATOR REMOVABLE COVER
FIN TUBE RADIATOR,
REFER TO MECH DWGS.
PTD. FIRE RETARDANT WD.
BLOCKING AND SHIMS
5/8" GWB PTD.
1-5/8" MTL STUDS @ 16"
OC
A L
IG
N
J-BEAD
4" SPRAY FOAM INSULATION
OVER EXISTING MASONRY WALL
REFER TO SECTION VIEW, PROVIDE
SHEET METAL BETWEEN SPRAY
FOAM INSULATION AND FIN TUBE
LINE OF EXIST. CONCRETE CURB
BELOW
1. SPRAY FOAM INSULATION IS TO BE INSTALLED CONTINUOUSLY AS
INDICATED, NOT LESS THAN 2 1/2" THICK OR IN THICKNESS INDICATED
AT ALL EXTERIOR WALLS FROM FLOOR TO DECK ABOVE WITHIN
PROJECT SCOPE AREA U.N.O.
2. SPRAY FOAM INSUALTION AT ALL LOCATIONS INSTALLED IS TO BE
COMPLETELY ENCLOSED AND SEALED WITH 5/8" GYPSUM BOARD TYPE
"X", OR ALTERNATE THERMAL BARRIER APPROVED BY RE, FROM
FLOOR TO DECK ABOVE, AT AND AROUND MASONRY OPENINGS.
3. REFER TO 1-A453 FOR H/J/S DETAILS UNLESS OTHERWISE NOTED.
4. REFER TO SPECIFICATION SECTION 072129 FOR ADDITIONAL
INFORMATION ON FLUID APPLIED THERMAL BARRIERS.
GENERAL NOTES
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc. 423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Sheet Number 113of
1-A451
EXTERIOR SECTION DETAILS
AH/GV GP
630-18-101
December 18, 2020 14
SCALE: 1/2" = 1'-0"
B1
WALL ELEVATION AT WINDOW DEMOLITION
SCALE: 1 1/2" = 1'-0"
F1
SECTION DETAIL AT TYPICAL WINDOW DEMOLITION
SCALE: 1 1/2" = 1'-0"
F5
SECTION DETAIL: AT TYPICAL WINDOW REPLACEMENT
SCALE: 1 1/2" = 1'-0"
F8
RADIATOR DETAIL - TYPICAL
SCALE: 1 1/2" = 1'-0"
B6
RADIATOR PLAN DETAIL - TYPICAL
0 2' 4'
0 8" 16" 0 8" 16" 0 8" 16"
0 8" 16"
ADDENDUM 1-17N, 17S, 17W 1 11/03/2014
3-5/8" MTL. STUD @ 16"
O.C. TO DECK ABOVE
5/8" GWB
CORNER BEAD, TYP.
AT ALL CORNERS
ACT, REFER TO RCP
CONT. ANGLE (1" x 1" x 16GA.)
METAL STUD DIAGONAL
BRACING TO DECK
ABOVE @ 4'-0" O.C.
REFER TO RCP
REFER TO RCP
3-5/8" MTL. STUD @ 16"
O.C. TO DECK ABOVE
5/8" GWB
CORNER BEAD, TYP.
AT ALL CORNERS
ACT, REFER TO RCP
CONT. ANGLE (1" x 1" x 16GA.)
METAL STUD DIAGONAL
BRACING TO DECK
ABOVE @ 4'-0" O.C.
REFER TO RCP
LED RECESSED LINEAR WALL
GRAZER (SEE ELEC. DWGS)
SCHEDULED CEILING
METAL CEILING EDGE TRIM
LATERAL BRACING, REFER
TO STRUCTURE DRAWINGS
3 5/8" .
EXISTING WALL
HANGER WIRE
PROVIDE WOOD BLOCKING
ATTACHED TO SUSPENSION
SYSTEM WHERE EXPOSED 'T'S
ARE NOT AVAILABLE. ATTACH
CUBICLE CURTAIN TRACK
THROUGH TILE TO BLOCKING
ACT, REFER TO RCP
EXTRUDED ALUMINUM
TRACK
REFER TO RCP
MAIN 'T' SPACED AT 2'-0" O.C.
CUBICLE CURTAIN
SHEET METAL SCREWS
ALTERNATIVELY
SPACED
3-5/8" MTL. STUD
5/8" GWB
CORNER BEAD, TYP.
AT ALL CORNERS
ACT-3, TYP.
CONT. ANGLE (1" x 1" x
16GA.)
TO DECK ABOVE
REFER TO RCP
REFER TO RCP
3-5/8" MTL. STUD DIAGONAL
BRACING TO DECK ABOVE
@ 4'-0" O.C.
PENCIL ROD
1-5/8" MTL STUD MAIN RUNNER
7/8" HAT FURRING CHANNEL
MOISTURE RESISTANT GYP.BD.-
FRAMING CHANNEL @ 12" O.C.
GWB BOARD CEILING
SCHEDULED PARTITION
CONT. ANGLE (1" x 1" x 16GA.)
PERPENDICULAR TO MAIN RUNNER
PENCIL ROD
GWB BOARD CEILING
SCHEDULED PARTITION
CONT. ANGLE (1" x 1" x 16GA.)
1-5/8" MTL STUD MAIN RUNNER
7/8" HAT FURRING CHANNEL,
MOISTURE RESISTANT GYP.BD.-
FRAMING CHANNEL @ 12" O.C.
PARALLEL TO MAIN RUNNER
3-5/8" METAL STUD @ 16" O.C.
5/8" GWB
CORNER BEAD, TYP.
AT ALL OUTSIDE
CORNERS
ACT, REFER TO RCP
CONT. ANGLE (1" x 1" x 16GA.)
TYP.
TO DECK ABOVE
SEE RCP
METAL STUD DIAGONAL
BRACING TO DECK ABOVE
@ 4'-0" O.C.
6"
3-5/8" METAL STUD
5/8" GWB, TYP.
CONT. ANGLE (2" x 2" x
16GA.)
TO DECK ABOVE
REFER TO RCP
METAL DOOR
CONCEALED PIANO
HINGE
METAL FRAME
10"SEE RCP
METAL STUD DIAGONAL
BRACING TO DECK ABOVE @
4'-0" O.C.
3-5/8" METAL STUD @ 16" O.C.
5/8" GWB
CORNER BEAD, TYP. AT
ALL OUTSIDE CORNERS
ACT, REFER TO RCP
CONT. ANGLE (1" x 1" x 16GA.) TYP.
TO DECK ABOVE
REFER TO RCP
SEE RCP
CONTINUE GWB TO DECK WHERE
REQUIRED, REFER TO PARTITION TYPE
METAL STUD DIAGONAL BRACING
TO DECK ABOVE @ 4'-0" O.C.
MAIN TEE @ SPACING
INDICATED ON GRID PLAN
TORSION SPRING
CROSS TEE @ SPACING
INDICATED ON GRID PLAN
ACT-3, TYP.
TORSION SPRING
HINGE
LIGHT FIXTURE AS SCHEDULED.
REFER TO ELECTRICAL DWGS
FIELD FASTEN AS REQ'D. TYP.
PERIMETER TRIM TO MATCH PANELS. FIELD FASTEN
TO TEE. FIELD CUT & MITER AS REQUIRED, TYP.
LIGHT FIXTURE
INDEPENDENTLY HUNG
FROM CEILING SYSTEM
PENCIL ROD, TYP.
1-5/8" CHANNEL
3-5/8" MTL. STUD @ 16"
O.C. TO DECK ABOVE
5/8" PAINTED GWB
FASCIA AND SOFFIT
CORNER BEAD, TYP.
AT ALL CORNERS
5/8" PAINTED GWB SOFFIT
METAL STUD DIAGONAL
BRACING TO DECK
ABOVE @ 4'-0" O.C.
REFER TO RCP
REFER TO RCP
ACOUSTIC CEILING TILE
PAINTED GWB SOFFIT
HVAC LINEAR DIFFUSER
(SEE MECH. DRAWINGS)
PAINTED GWB CEILING
CORNER BEAD
CONT. ANGLE 1x1 (16 GA)
TO DECK ABOVE
3-5/8" METAL STUDS
4 1/2"
4"
ACOUSTIC CEILING
REFER TO RCP
GWB CEILING
REFER TO RCP
6"
PAINTED GWB CEILING
2 1/2" METAL STUDS @ 16" O.C.
ALUMINUM WINDOW SYSTEM, REFER
TO WINDOW SCHEDULE AND DETAILS
FOR ADDITIONAL INFORMATION
ACOUSTICAL CEILING TILE
FACE OF THE WALL BEYOND
WHERE APPLIES (SEE PLAN)
COL
SEE PLAN
10" U.O.N.
1-5/8" METAL STUDS WITH GWB
AND INSULATION. REFER TO
SECTION DETAILS FOR
ADDITIONAL INFO.
1/4"
CONT. ANGLE
(1" x 1" x 16GA)
WINDOW
RECEIVER
TRACK
BEYOND
CONT ALUM TUBE
INFILL AT JAMB
RECEIVER
1/ 4"
EXTEND DOWN 1-5/8" METAL
STUDS @ 16" O.C.
ACOUSTICAL CEILING TILE
FACE OF THE WALL BEYOND
WHERE APPLIES (SEE PLAN)
COL
SEE PLAN
ALUMINUM WINDOW SYSTEM, REFER
TO WINDOW SCHEDULE AND DETAILS
FOR ADDITIONAL INFORMATION
METAL STUDS WITH GWB, AND
INSULATION. REFER TO SECTION
DETAILS FOR ADDITIONAL INFO.
PREFINISHED METAL CEILING EDGE TRIM
CONTINUOUS ALUM TUBE INFILL AT JAMB RECEIVER
1/ 4"
HVAC LINEAR DIFFUSER (SEE MECH. DWGS)
PAINTED GWB SOFFIT
ALUMINUM WINDOW SYSTEM, REFER
TO WINDOW SCHEDULE AND DETAILS
FOR ADDITIONAL INFORMATION
COL
METAL STUDS WITH GWB AND
INSULATION. REFER TO SECTION
DETAILS FOR ADDITIONAL INFO.
CORNER BEAD
2 1/2" METAL STUDS @ 16" O.C.
9'-3 1/2"
SEE RCP
FACE OF THE WALL BEYOND WHERE APPLIES
(SEE PLAN)
TO LINEAR DIFFUSER
1'-0 1/2".
ROLL DOWN SHADES, WHERE SCHEDULED
11 1/4"
HVAC LINEAR DIFFUSER (SEE MECH. DWGS)
PAINTED GWB SOFFIT
2 1/2" METAL STUDS @ 16" O.C.
ALUMINUM WINDOW SYSTEM, REFER
TO WINDOW SCHEDULE AND DETAILS
FOR ADDITIONAL INFORMATION
ACOUSTICAL CEILING TILE
FACE OF THE WALL BEYOND WHERE
APPLIES (SEE PLAN)
COL
1-5/8" METAL STUDS WITH GWB
AND INSULATION. REFER TO
SECTION DETAILS FOR
ADDITIONAL INFO.
1/4"
CONTINUOUS ANGLE
(1x1x16GA)
WINDOW RECEIVER TRACK
BEYOND
CONT ALUM TUBE INFILL AT JAMB
RECEIVER
1/ 4"
CORNER BEAD, TYP. AT ALL CORNERS
1" X 1" 12 GA. ALUMINUM ANGLE
EXTEND DOWN 1-5/8" METAL
STUDS @ 16" O.C.
U.O.N.
5"
TELEVISION BY VA
ADJUSTABLE
EXTENSION
FINISHED CEILING
AS SCHEDULED
COVER PLATE
WELD
ANGLE TO
PLATE
3/8"? PLATE TO
MATCH TOP OF
PLATE OF TV
SUPPORT
3" X 3" X 3/8" ANGLE
BRACING, FIELD WELD
TO PLATE (ADJUST
BRACING TO
ACCOMODATE MECH.
DUCT WORK)
1 1/2" MIN.1 1/2" MIN.
DRILL & TAP TO
MATCH HOLES IN TV
SUPPORT
CEILING
DECOUPLER
ATTACHMENT
CL
NOTE:
CEILING MOUNTED TELEVISION
SUPPORT VERIFIED WITH TV MFR.
PROVIDE ALL
ATTACHMENTS AND
FASTENERS REQUIRED
TO SECURE ASSEMBLY
TO STRUCTURE ABOVE.
EXIST CONCRETE SLAB
1/2"Ø THREADED ROD @
36"OC W/ ANCHOR (2" MIN
EMBED)
CONTINUOUS J-BEAD
ACT, REFER TO RCP
PATIENT LIFT TRACK SYSTEM
1/2"Ø ROD W/ 45° ANGLE CONNECTIONS,
ALTERNATE SIDES OF HANGER. PROVIDE
ADDITIONAL BRACE IN LINE W/ TRACK @ 6'-0"OC
MAX
1/2"Ø ANCHOR
(3" EMBED)
LIFT TRACK AT GWB CEILING LIFT TRACK AT ACT CEILING
CONT. ANGLE (1"
X 1" X 16 GA)
LATERAL BRACING,
REFER TO
STRUCTURAL
DRAWINGS
3 5/8" METAL STUDS @16" O.C.
GWB CEILING
MIN., TYP.
1/4" OVERLAP
MIN., TYP.
1/4" OVERLAP
M A
X
1/
2"
M A
X
/2
EXIST CONCRETE SLAB
SCHEDULED CEILING
PATIENT LIFT TRACK SYSTEM
1/2"Ø ROD W/ 45° ANGLE
CONNECTIONS. PROVIDE
ADDITIONAL BRACE IN LINE W/
TRACK @ 6'-0"OC MAX AT
EACH HANGER
1/2"Ø ANCHOR (3" EMBED)
STRUT TYPE METAL
FRAMING SYSTEM
3'-0" MAX
1/2"Ø THREADED ROD @ 36"OC
W/ ANCHOR (2" MIN EMBED) MECHANICAL
DUCT
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc. 423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Sheet Number 113of
1-A711
CEILING DETAILS
AH JKC
630-18-101
December 18, 2020 25
0 8" 16"
0 8" 16"
0 8" 16"
0 8" 16"
0 8"4"
0 8" 16"
0 8"4"
0 8" 16"
0 8" 16"
0 8" 16"
SCALE: 1 1/2" = 1'-0"
D9
CEILING DETAIL - ACT TO GWB
SCALE: 1 1/2" = 1'-0"
C9
CEILING DETAIL - ACT TO GWB
SCALE: 3" = 1'-0"
F7
CEILING DETAIL - COVE LIGHT
SCALE: 1 1/2" = 1'-0"
B9
CEILING DETAIL - CURTAIN TRACK
SCALE: 1 1/2" = 1'-0"
E7
CEILING DETAIL - METAL CEILING TO GWB
SCALE: 1 1/2" = 1'-0"
F9
CEILING DETAIL
SCALE: 1 1/2" = 1'-0"
B7
CEILING DETAIL - ACT WITH GWB SOFFIT
SCALE: 1 1/2" = 1'-0"
C7
TYPICAL CEILING DETAIL - ACCESS DOOR
SCALE: 1 1/2" = 1'-0"
D7
CEILING DETAIL - ACT WITH GWB SOFFIT
SCALE: 3" = 1'-0"
F5
CEILING DETAIL - LIGHT AT METAL PANEL
SCALE: 1 1/2" = 1'-0"
A9
CEILING DETAIL - GWB TO GWB
0 8" 16"SCALE: 1 1/2" = 1'-0"
A7
CEILING DETAIL - LINEAR DIFFUSER & RAISED CEILING
0 8" 16"
SCALE: 1 1/2" = 1'-0"
B5
CEILING DETAIL OF PERIMETER WINDOW
SCALE: 1 1/2" = 1'-0"
D5
CEILING DETAIL OF PERIMETER WINDOW
0 8" 16"
SCALE: 1 1/2" = 1'-0"
F3
CEILING DETAIL - PERIMETER WINDOW AT PAT. ROOM
0 8" 16"
SCALE: 1 1/2" = 1'-0"
D3
CEILING DETAIL - PERIMETER WINDOW AT PAT. ROOM
0 8" 16"SCALE:N.T.S.
D1
TYPICAL CEILING MOUNTED TV BRACKET AT 4TH WEST
SCALE: 1 1/2" = 1'-0"
B2
TYPICAL OVERHEAD TRACK SUPPORT
SCALE: 1 1/2" = 1'-0"
F1
OVERHEAD TRACK SUPPORT AT DUCT WORK
0 8" 16"
0 8" 16"
ADDENDUM #1 1 06/05/2013
0 8" 16"
COL
COL
S E
E P
L A
N
NEW SPRAY-ON
CEMENTITIOUS
FIREPROOFING OVER
EXISTING COLUMN
(2-HR RATED)
EXIST. STL. COLUMN
MTL. STUD, REFER TO
SCHEDULED
PARTITION
PTD. 5/8" GWB, REFER
TO SCHEDULED
PARTITION
CORNER GUARD, REFER
TO FINISH LEGEND
COL
COL
S E
E P
L A
N
SEE PLAN 10" .
S E
E P
L A
N
SCHEDULED PARTITION
EXIST. STL. COLUMN
NEW SPRAY-ON CEMENTITIOUS
FIREPROOFING OVER EXIST.
COLUMN (2-HR RATED)
SCHEDULED PARTITION
FIRE RETARDANT WD. BLOCKING
3/16" BREAKFORM ALUM.
CORNER GUARD, CG-3
COUNTERSUNK SCREW IN 1/2"
SPACER FOR ALUM. CORNER
GUARD
4"
WD. SHIM
NEW SPRAY-ON
CEMENTITIOUS
FIREPROOFING OVER
EXISTING COLUMN
(2-HR RATED)
EXIST. STL. COLUMN
MTL. STUD, REFER TO
SCHEDULED
PARTITION
PTD. 5/8" GWB, REFER
TO SCHEDULED
PARTITION
SEE PLAN
VARIES
SEE PLAN
VARIES
SCHEDULED
DOOR
COL
COL
S E
E P
L A
N
V A
R
IE
S
S E
E P
L A
N
V A
R
IE
S
EXIST. MASONRY
FIRE RETARDENT
SEALANT AND
BACKER ROD, EACH
SIDE
SCHEDULED
PARTITION
GYPSUM BOARD TO BE
SECURED TO VERTICAL
STUDS NOT RUNNER TRACK
VERTICAL RUNNER TRACK
CHANNEL SECURED TO
MASONRY PARTITION @ 12" 0C
SCHEDULED
PARTITION
RECESSED COMPONENT
(EX. TOILET PAPER
DISPENSER RECEPTACLE,
LIGHT SWITCH, ETC.)
SOUND INSULATION
AROUND SIDES AND BACK
OF COMPONENT,
THICKNESS OF SOUND
INSULATION DEPENDENT ON
STC REQUIRED FOR
SCHEDULED PARTITION
FURNISH AND INSTALL NEW
RECESSED FIRE
EXTINGUISHER CABINET.
INSTALL AS PER MFR'S
RECOMMENDATION.
PROVIDE WD.
SHIM AS REQ'D
DETAIL AT CHASE WALL CONDITION
PROVIDE MTL STUD
FRAMING ALONG SIDES,
FULL HT. AND PROVIDE
HORIZONTAL STUD AT
TOP AND BOTTOM OF
RECESSED F.E.C.
PROVIDE SOUND
ATTENUATION BLANKET IN
OPPOSITE CHASE PARTITION
FOR ROOMS SCHEDULED TO
BE STC RATED.
8"X8"X27" MIN. INSIDE
DIMENSIONS
CL
A L
IG
N
EXTERIOR WINDOW
SYSTEM
CENTERLINE OF MULLION & PARTITION
SCHEDULED PARTITION
LINE OF SILL COVER BELOW
ALUMINUM CLOSURE/ SNAP TRIM
EACH SIDE
FILL WITH ACOUSTICAL BATTS
BACKER ROD AND SEALANT,
ALL SIDES, 1/4" MAX THICKNESS
BACKER ROD AND SEALANT,
ALL SIDES, 1/4" MAX THICKNESS
NEOPRENE SHIM
WOOD BLOCKING
PARTITION TYPE E4/1-A1001
EXISTING CONCRETE BEAM ENCASING
EXISTING BEAM WITH BOTTOM
FLANGE EXPOSED
(2) LAYERS OF 5/8" TYPE 'X'
GWB (ALL SIDES), PAINTED
EXISTING PIPING
PROVIDE FIRESTOPPING
FIRE RESISTIVE SEALANT
FIRE RETARDANT WD SHIM
NOTE:
REFER TO
DRAWING 1-A1001
FOR ADDITIONAL
FIRESTOP
INFORMATION
QUANTITY OF
LOCATIONS
CANNOT BE
CONFIRMED UNTIL
FOLLOWING
DEMOLITION,
CONTRACTOR TO
INCLUDE THIS
REMEDIATION IN 10
LOCATIONS FOR
EACH WING. 3 5/8" MTL STUD @ 16" O.C., TYP.
CORNER BEAD, TYP.
NEW SPRAY PROOFING TO ACHIEVE
FULLY ENCAPSULATED BEAM
2 1/2" MTL STUD @ 16" O.C., TYP.
EXISTING ACCESS DOOR
SCHEDULED
PARTITION
ALUMINUM FACING ON
3/4" PLYWOOD
SUBSTRATE (ALL
SIDES)
EXISTING MASONRY WALL
V
.I .F
SCHEDULED
PARTITION
ALUMINUM FACING ON
3/4" PLYWOOD
SUBSTRATE (ALL SIDES)
1"
C4
1-A801
V.I.F.
6 3/4"
V.I.F.
2'-1"
V.I.F.
2'-3 3/4" R.O.
EXIST. ACCESS DOOR
EXIST. MASONRY WALL FOLLOWING ADJACENT
DEMOLITION CONTRACTOR TO PATCH ANY
DAMAGE OR PENETRATIONS
SCHEDULED
PARTITION
SCHEDULED
PARTITION
ALUM. TRIM FRAME
ALUM. FACING ON 3/4"
PLYWOOD SUBSTRATE
(ALL SIDES)
SCHEDULED PARTITION
J-BEAD
F4
1-A801
EXIST. EXT. WALL
CONSTRUCTION
EXIST. MASONRY
COLUMN ENCLOSURE
EXIST. STL. COLUMN
NEW GLAZED ALUM. WINDOW
WITH INSECT SCREEN. REFER
TO SHEET A451 FOR
ADDITIONAL INFORMATION
RELATING TO WINDOW.
PTD. 5/8" GWB, REFER TO
SCHEDULED PARTITION
SEE PLAN
S E
E P
L A
N
SOLID SURFACE S-1
SILL, BELOW
AT LOCATIONS WITH EXISTING PLUMBING
RISERS, THE CONTRACTOR IS TO PROVIDE
CONTINUOUS SPRAY FOAM INSULATION
BETWEEN PIPING AND THE EXTERIOR WALL
AT A MINIMUM THICKNESS OF 1”. IN ADDITION
TO THE 1” OF SPRAY FOAM INSULATION,
PROVIDE 3 ½” BATT INSULATION ALONG THE
INTERIOR METAL FRAME PARTITIONS
COL
COL
1 5/8" METAL STUDS
ADJACENT TO EXISTING
STEEL WINDOW /
SURROUND TO REMAIN
1 5/8" METAL STUD ADJACENT
TO EXISTING STEEL WINDOW
SURROUND
2 1/2" SPRAY FOAM
INSULATION, TYP.
CONTRACTOR TO
PROVIDE SPRAY FOAM
INSULATION ALONG THE
EXTERIOR MASONRY AT
A DEPTH OF 4", TYPICAL
U .O
.N
1' -0
/4
1"
EXIST.
ELEVATOR
SHAFT
EXIST. MASONRY WALL
SCHEDULED DOOR, P-13
EXIST. CONDUIT RACEWAY, VIF
SCHEDULED GWB
CEILING, REFER TO RCP
SCHEDULED DOOR FRAME, P-13
5" MIN.
1" X 1" 12 GA. ALUMINUM ANGLE
EXIST.
ELEVATOR
SHAFT
EXIST. PTD. MTL. FRAME, P-13
EXIST. MASONRY WALL
5/8" GWB ON 3-5/8"" MTL
STUDS @ 16" O.C.
MTL-1 ADHERED TO
GWB
3/8" SEALANT AT JOINT
ALUM. TRIM, P-13, ADHERED
TO WD. BLOCKING
EXIST. ELEVATOR DOOR, P-13
9 5/8"
/2
FACE OF PARTITION
9 3/4"
SCHEDULED GWB CEILING,
REFER TO RCP
1" X 1" 12 GA. ALUMINUM ANGLE
EXIST.
ELEVATOR
SHAFT
EXIST. MASONRY
WALL
5/8" GWB ON 3-5/8" MTL
STUDS @ 16" O.C.
PORCELAIN MOSAIC TILE
F A
C E
O F
P A
R T
IT
IO
N
/4
MTL-1
3/8" ALUM. BAR TRIM
PORCELAIN MOSAIC TILE
OVER 5/8" GWB ON 3-5/8"
STUDS @ 16" O.C.
EXIST. MASONRY
WALL
EXIST. STRUCT.
EXIST. WALL
MOUNTED PANEL,
VIF
3'-0" V.I.F.
SCHEDULED DOOR
FRAME, P-13
SCHEDULED DOOR,
P-13
M
IN
F A
C E
O F
P A
R T
IT
IO
N
/4
SCHEDULED
PARTITION
1/8"
ALUMINUM TRIM ANGLE
EXIST.
ELEVATOR
SHAFT
EXIST. PTD. MTL. FRAME, P-13
EXIST. MASONRY
WALL
5/8" GWB ON 3 5/8" MTL
STUDS @ 16" O.C.
PORCELAIN MOSAIC TILE
1/2" SEALANT AT JOINT
ALUM. TRIM, P-13, ON FIRE
RETARDANT WD. BLOCKING
/8
1 1/2"
EXIST. ELEVATOR DOOR, P-13
EXIST. WALL MOUNTED
PANEL, VIF
SCHEDULED DOOR
FRAME
F A
C E
O F
P A
R T
IT
IO
N
/4 " 5
M
IN
SCHEDULED DOOR
1/2" PAINTED MDF
3 5/8" MTL STUDS, TYP.
EXIST.
ELEVATOR
SHAFT
EXIST. MASONRY WALL
5/8" GWB ON 3-5/8"" MTL
STUDS @ 16" O.C.
PORCELAIN MOSAIC TILE
1/8" ALUM. BASE AS
SCHEDULED
FACE OF PARTITION
9 3/4"
O F
G W
B
/8
T
O B
T M
FLOOR FINISH AS
SCHEDULED
CONTINUOUS ALUMINUM
SUPPORT PLATEEXPANSION OPENING
EXISTING
/8
FLAT HEAD CONCRETE
SCREW
(7 PER FRAME @ 18" O.C.)
CONTINUOUS
ALUMINUM SURFACE
MOUNT FRAMEFLOOR FINISH AS SCHEDULED
CONTINUOUS SEAL
EXISTING SLAB.
PATCH AND REPAIR AS
REQUIRED TO RECIEVE NEW
EXPANSION JOINT ASSEMBLY.
EXISTING RATED EXP. JOINT
TO REMAIN
NOTE: CONTRATOR TO INSPECT EXISTING TO REMAIN EXPANSION JOINT. REPLACE
IN FULL IF DAMAGED TO MATCH EXISTING FIRE RATING OF FLOOR ASSEMBLY.
CONTINUOUS ALUMINUM
WALL PLATE
SELF-TAPPING SHEET
METAL SCREW
(7 PER FRAME @ 18" O.C.)
CONTINUOUS SEAL
EXISTING CONSTRUCTION.
PATCH AND REPAIR AS
REQUIRED TO RECIEVE NEW
EXPANSION JOINT ASSEMBLY.
E X
P O
P E
N
IN
G
E X
IS
T
IN
G
C U
T B
A C
K T
O A
D J S
T U
D
P R
O V
ID
E
N E
W F
IN
IS
H
PATCH AND REPAIR FINISH
TO RECIEVE NEW EXPASION
WALL/CEILING JOINT AS
REQUIRED. ALL RATINGS
MUST BE MAINTAINED. (TYP.)
EXISTING RATED EXP. JOINT
TO REMAIN
NOTE: CONTRATOR TO INSPECT EXISTING TO REMAIN EXPANSION JOINT. REPLACE IN
FULL IF DAMAGED TO MATCH EXISTING FIRE RATING OF BUILDING SEPARATION.
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc. 423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Sheet Number 113of
1-A801
INTERIOR DETAILS
AH JKC
630-18-101
December 18, 2020 26
SCALE: 1 1/2" = 1'-0"
B6
PLAN DETAIL @ COLUMN ENCLOSURE
SCALE: 1 1/2" = 1'-0"
E4
PLAN DETAIL OF COLUMN
ENCLOSURE
SCALE: 1 1/2" = 1'-0"
D6
PLAN DETAIL OF COLUMN ENCLOSURE
SCALE: 1 1/2" = 1'-0"
D8
PLAN DETAIL - TYP. RATED
ISOLATION JOINT AT
GWB/MASONRY
SCALE: 1 1/2" = 1'-0"
C8
TYP. RECESSED
COMPONENT OF STC
RATED WALL
SCALE: 1 1/2" = 1'-0"
F8
TYP. PLAN DETAILS OF F.E.C. ENCLOSURE
0 8" 16"
0 8" 16"
0 8" 16"
0 8" 16"
0 8" 16"
0 8" 16"
0 8" 16"
0 8" 16"
0 8" 16"
SCALE: 1 1/2" = 1'-0"
B8
TYP. CENTERED PARTITION DETAIL AT EXTERIOR WALL
SCALE: 1 1/2" = 1'-0"
B4
FIRE PROTECTION REPAIR
AND ENCLOSURE AT
EXISTING BEAM
0 8" 16"
SCALE: 1 1/2" = 1'-0"
F4
SECTION DETAIL OF LAUNDRY CHUTE
SCALE: 1 1/2" = 1'-0"
C4
PLAN DETAIL OF LAUNDRY CHUTE
SCALE: 1 1/2" = 1'-0"
F6
PLAN DETAIL OF EXTERIOR WALL COLUMN ENCLOSURE
0 8" 16"
SCALE: 1 1/2" = 1'-0"
F1
DETAIL OF ELEVATOR LOBBY DOOR HEAD (H6)
SCALE: 1 1/2" = 1'-0"
E1
METAL PANEL OF ELEVATOR HEAD
SCALE: 1 1/2" = 1'-0"
C1
TRANSITION DETAIL,
PORCELAIN TILE
WALL/METAL PANEL OF
ELEVATOR LOBBY
SCALE: 1 1/2" = 1'-0"
B1
PORCELAIN TILE WALL OF CORNER JAMB
SCALE: 1 1/2" = 1'-0"
F2
PORCELAIN TILE WALL OF ELEVATOR JAMB
SCALE: 1 1/2" = 1'-0"
E2
BASE DETAIL OF PORCELAIN TILE WALL
0 8" 16"
0 8" 16"0 8" 16"
0 8" 16"
0 8" 16"
0 8" 16"
ADDENDUM #1 1 06/05/2013
SCALE: 6" = 1'-0"
C2
EXPANSION JOINT DETAIL AT FLOOR SLAB
SCALE: 6" = 1'-0"
B2
EXPANSION JOINT DETAIL AT WALL/CEILING
0 2" 4"
0 2" 4"
WOOD BLOCKING
ADJUSTABLE SHELF (3/4"
PLYWOOD WITH PLAM FINISH ON
ALL SIDES) WITH ALUMINUM EDGES
RECESSED SHELF SUPPORT STRIPS
1/4" TEMPERED HARDBOARD
SCHEDULED BASE
2" X WOOD BASE
3/4" S-1 ON 3/4" PLYWOOD
3/4" PLYWOOD WITH
PLAM FINISH DOOR
1/2" THICK BACKSPLASH REFER TO
INTERIOR ELEVATIONS FOR OCCURANCE
3/4" PLYWOOD WITH
PLAM FINISH FASCIA
S E
E E
L E
V A
T
IO
N
U .O
.N
/2
1 1/2"
SEE PLAN
2'-1" U.O.N.
3"
3 1/2" 3 1/2"
FULL EXTENSION DRAWER
SLIDE HARDWARE
WD. BLOCKING WITH
PLAM FINISH EDGE
3/4" PLYWOOD DRAWER
CONSTRUCTION
3/4" X 4" BOX FRAME TYP.
CABINET LOCK
WHERE REQ'D,
DOUBLE LOCKS
REQ'D AT ALL
MEDS ROOMS
WOOD BLOCKING
1/4" TEMPERED HARDBOARD
SCHEDULED BASE
2" X WOOD BASE
3/4" S-1 ON 3/4" PLYWOOD
3/4" PLYWOOD WITH
PLAM-1 FINISH DOOR
1/2" THICK BACKSPLASH REFER
TO INTERIOR ELEVATIONS FOR
OCCURANCE
3/4" PLYWOOD WITH
PLAM FINISH FASCIA
S E
E E
L E
V A
T
IO
N
U .O
.N
/2
1 1/2"
SEE PLAN
2'-1" U.O.N.
FULL HEAVY DUTY
EXTENSION DRAWER SLIDE
HARDWARE
WD. BLOCKING WITH
P.LAM FINISH EDGE
3/4" PLYWOOD DRAWER
6"
3/4" X 4" BOX FRAME
CABINET LOCK
WHERE REQ'D,
DOUBLE LOCKS
REQ'D AT ALL
MEDS ROOMS
WOOD BLOCKING
ADJUSTABLE SHELF (3/4"
PLYWOOD WITH PLASTIC
LAMINATE FINISH ON ALL
SIDES) WITH PLAM EDGES
RECESSED SHELF
SUPPORT STRIPS
1/4" TEMPERED HARDBOARD
SCHEDULED BASE
2" X WOOD BASE
3/4" S-1 ON 3/4" PLYWOOD
3/4" PLYWOOD WITH
PLAM FINISH DOOR
SCRIBE EDGE TO WALL (TYP.)
4" HIGH BACKSPLASH REFER
TO INTERIOR ELEVATIONS
FOR OCCURANCE
S E
E E
L E
V A
T
IO
N
U .O
.N
/2
/4
1 1/2"
SEE PLAN
2'-1" U.O.N.
3"
3 1/2" 3 1/2"
3/4" X 4" BOX FRAME TYP.
CABINET LOCK WHERE
REQ'D, DOUBLE LOCKS
REQ'D AT ALL MEDS ROOMS
NOTE:
100 x 400 x 350 GAUGE STEEL
STRIPS ACCEPTABLE AS
ALTERNATIVE TO WOOD. MUST
WELD STRIPS TO STUDS.
SCREW ATTACH 2 X 4'S
TO STUDS AT MOUNTING
HEIGHTS REQUIRED
5/8" TYPE 'X' GWB
5/8" TYPE 'X' GWB
DOUBLE SCREW STUDS AS SHOWN
BEHIND ALL H.C.U. TACK WELD OR
SCREW ATTACH STUDS TOGETHER
(EXTRA STUDS 7" IN LENGTH)
HORIZONTAL 2 X 4
WOOD BLOCKING
BETWEEN STUDS
FIRE RETARDANT WOOD
BLOCKING
3/4" PLYWOOD
S-1 COUNTERTOP W/ DRIP
EDGE
/4
"7/8"
1. UNLESS OTHERWISE NOTED ON DETAILS, TYPICAL CONSTRUCTION IS TO BE AS FOLLOWS:
3/4" PLYWOOD FRONT
1/2" PLYWOOD SIDES AND BACK
1/4" PLYWOOD BOTTOM
1/4" TEMPERED HARDBOARD BACK PANEL
2. UNLESS OTHERWISE NOTED ON DETAILS, ALL DOOR FRONTS ARE TO BE 3/4" PLYWOOD CONSTRUCTION WITH PLASTIC
LAMINATE FINISH.
3. UNLESS OTHERWISE NOTED ON DETAILS, ALL MILLWORK TO BE 3/4" PLYWOOD CONSTRUCTION.
4. WHERE ELECTRICAL RECEPTACLES OCCUR UNDER COUNTERTOPS PROVIDE CORD SLOTS WITH GROMMETS IN COUNTERTOP.
5. ALL EXPOSED SURFACE TO RECEIVE PLASTIC LAMINATE FINISH, UNLESS OTHERWISE NOTED.
6. ALL CABINETRY AND MILLWORK TO COMPLY WITH AWI CATEGORY C STANDARDS. REFER TO SPECIFICATIONS.
7. ALL CABINETRY WITHIN PATIENT SPACES, OTHER THAN THE PATIENT WARDROBE, SHALL BE LOCKABLE WITH STAINLESS
STEEL CAM LOCK.
GENERAL NOTES
WOOD BLOCKING
1/2" S-1 COUNTERTOP
WOOD BLOCKING
1/2" S-1 BACKSPLASH
1'-2 1/2"
18" X 18" X 2" STL COUNTER
SUPPORT. REFER TO INTERIOR
ELEVATIONS FOR LOCATIONS
OR SPACE 48" O.C. MAX
SCHEDULED
BASE
2'-1"
/2
/2
C
L E
A R
M
IN
7"
M
IN
3/4" PLYWOOD WITH PLAM-1
FINISH WITH ANGLE
ATTACHMENTS
BASE CABINET BEYOND
WHERE OCCURS
UNDERMOUNT STAINLESS
STEEL SINK
/2
3/4" PLYWOOD WITH PLAM-1
FINISH
6"
CUT OUT TO ALLOW FOR
BASE TO BE CONTINUOUS
1-A901 A6
WOOD BLOCKING
WOOD BLOCKING
3" 2"
/2
S E
E E
L E
V A
T
IO
N S
/4
" 1'-3" U.O.N.
1/4" 1/2"
RECESSED SHELF
SUPPORT STRIPS
1/4" TEMPERED HARDBOARD
ADJUSTABLE SHELF (3/4"
PLYWOOD WITH PLAM FINISH
ON ALL SIDES) WITH PLAM
EDGES
3/4" PLYWOOD WITH
PLAM FINISH DOOR
CAB. DOOR
WIRE PULL
HEAVY DUTY
EUROPEAN
SYTLE HINGES
CABINET LOCK
WHERE REQ'D,
DOUBLE LOCKS
REQ'D AT ALL
MEDS ROOMS
TASK LIGHT WHERE
OCCURS, REFER TO ELEC
DWGS FOR LOCATIONS
SCHEDULED PARTITION
GWB CEILING, REFER TO RCP
PLAN EDGES (TYP.)
WOOD BLOCKING
WOOD BLOCKING
2"
/2
1/4" 1/2"
RECESSED SHELF
SUPPORT STRIPS
1/4" HARDBOARD
ADJUSTABLE SHELF (3/4"
PLYWOOD WITH PLAM FINISH
ON ALL SIDES) WITH PLAM
EDGES
TASK LIGHT WHERE
OCCURS, REFER TO ELEC
DWGS FOR LOCATIONS
SCHEDULED PARTITION
GWB CEILING, REFER TO RCP
/4
S
E E
E L
E V
A T
IO
N
S
1'-3" U.O.N
HIGH BACKSPLASH REFER TO
INTERIOR ELEVATIONS FOR
OCCURENCE
SCHEDULED BASE
3/4" X 4" BOX FRAME
CORE SLOTS W/ 2" SST GROMMETS,
3'-0" O.C, TO BE CONFIRMED WITH VA
WOOD BLOCKING
WOOD BLOCKING
18"X18" COUNTER SUPPORT.
REFER TO INTERIOR ELEVATIONS
FOR LOCATIONS OR SPACE 48"
O.C. MAX.
1.5" X 1.5" X 1/8" CONT.
ALUMINUM ANGLE AT ALL SIDES
3/4" S-1 ON 3/4" PLYWOOD
/2
1"
R E
F E
R T
O E
L E
V A
T
IO
N
O R
2'-1" U.O.N.
UNDER COUNTER EQUIPMENT,
WHERE OCCURS. REFER TO PLANS.
5 1/2"
CL
4"
FIRE RETARDANT WOOD
BLOCKING
SCRIBE EDGE TO WALL (TYP.)
S-1 COUNTERTOP
FIRE RETARDANT WOOD
BLOCKING
1/2" S-1 BACKSPLASH
/2
/2
C
L E
A R
M
IN
COUNTER SUPPORT. REFER TO
INTERIOR ELEVATIONS FOR
LOCATIONS OR SPACE 48" O.C. MAX
SCHEDULE
D BASE
2'-1"
M
IN
8 3/4"
3/4" PLYWOOD WITH PLAM-1
FINISH
PLYWOOD WTIH P.LAM
FINISH END PANEL BEYOND
3/4" PLYWOOD WITH PLAM-1
FINISH WITH ANGLE
ATTACHMENTS
INTEGRAL SOLID SURFACE
SINK
1-A901 A6
FIRE RETARDANT WOOD
BLOCKING
SCRIBE EDGE TO WALL (TYP.)
S-1 COUNTERTOP
FIRE RETARDANT WOOD
BLOCKING
1/2" S-1 BACKSPLASH
/2
/2
C
L E
A R
M
IN
COUNTER SUPPORT. REFER TO
INTERIOR ELEVATIONS FOR
LOCATIONS OR SPACE 48" O.C. MAX
SCHEDULE
D BASE
1'-9"
M
IN
8 3/4"
3/4" PLYWOOD WITH PLAM-1
FINISH
PLYWOOD WTIH P.LAM
FINISH END PANEL BEYOND
3/4" PLYWOOD WITH PLAM-1 FINISH
WITH ANGLE ATTACHMENTS
INTEGRAL SOLID SURFACE
SINK
1-A901 A6
WOOD BLOCKING
1/4" TEMPERED HARDBOARD
SCHEDULED BASE
2" X WOOD BASE
3/4" S-1 ON
3/4" PLYWOOD
3/4" PLYWOOD WITH
PLAM-1 FINISH DOOR
1/2" THICK BACKSPLASH REFER
TO INTERIOR ELEVATIONS FOR
OCCURANCE
3/4" PLYWOOD WITH
PLAM FINISH FASCIA
S E
E E
LE
V
A T
IO
N
2' -1
0" U
.O .N
1/
2" 1/
4"
1 1/2"
SEE PLAN
2'-1" U.O.N.
FULL HEAVY DUTY
EXTENSION DRAWER SLIDE
HARDWARE
WD. BLOCKING WITH
P.LAM FINISH EDGE
3/4" PLYWOOD DRAWER
6"
3/4" X 4" BOX FRAME
E Q
E Q
E Q
E Q
CABINET LOCK
WHERE REQ'D,
DOUBLE LOCKS
REQ'D AT ALL
MEDS ROOMS
SCHEDULED BASE
3/4" X 4" BOX FRAME
WOOD BLOCKING
WOOD BLOCKING
18"X18" COUNTER SUPPORT.
REFER TO INTERIOR
ELEVATIONS FOR LOCATIONS
OR SPACE 48" O.C. MAX.
3/4" S-1 ON 3/4" PLYWOOD
/2
1"
2'-0" U.O.N.
1'-0"
CL
18"X18" ANGLE
9"
4 SIDES
1/2" TYP REVEAL
2"
4"
1" PLYWOOD
WITH PLAM-1
1/2" 2"
1" PLYWOOD
WITH PLAM-1
PTD. 5/8" GWB ON MTL. STUDS
@ 16" O.C., REFER TO PLANS
FOR SCHEDULED PARTITIONS
SCHEDULED WALL
COVERING TO EXTEND OVER
EDGE OF PLAM PANEL
3/4" BRUSHED
ALUMINUM CORNER
GUARD
FIRE RETARDANT WD.
BLOCKING AS REQ'D
PLAM-5 PANEL MOUNTED
WITH 1/4" Z CLIP ZONE
METAL BACK-UP PLATE IS
REQUIRED AT ALL
LOCATIONS REQUIRING
BLOCKING EXCEPT BASE CABINETS.
NON STRUCTURAL METAL
FRAMING
PARTITION
3/4" X 12" PLYWOOD
BLOCKING (RE: 2/A0901)
3/4" PLYWOOD
WITH P.LAM. FINISH
NON-SECURE CLOSET ROD
ELEVATION
SECTION "A"
VARIES - SEE PLANS
SECTION "A"
PARTITION
3/4" PLYWOOD WITH
PLASTIC LAMINATE FINISH
HANGER ROD
(CENTERED ON
SHELF @ 3A)
1'-0"
CL OF ROD
1 1/2"
3/4" X 12" PLYWOOD
BLOCKING (RE: 2/A0901)
PLYWOOD
BLOCKING
NOTE: PROVIDE CENTER BRACE
FOR UNITS OVER 48"
A F
F
A F
F
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT: