06 VAMC_4W MED SURG_ELEC DWGS_ADD 01.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24221B0001
About this file
This solicitation is for renovating a patient ward at a Veterans Affairs medical center. Key requirements include renovating the 4W step down unit to modernize patient rooms, support spaces, and building systems. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2. An award date was not specified. Pricing terms and response dates were not provided in the document.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEC
F E
C
F E
C
JT
JT
P
P
P2
P2
P2
P
P
P
P
P2
P2
UP
DN
FEC
F E
C
P
P2
P2
P
P
P
P
P
P
P
P
P
P
P
P2
J
12.1 13 15.1 16
Q
18.716.916.8
N
L
J
G
17 19 21
J.2
H
F.5
F
E.9
E
D
C
B
A
LW1A
LW1B
LZ1
LD1A
LD1A LD1A
LZ1
LD1ALD1A
LD1A LD1A
LW1B
LD1C
LD1A LD1A
LD1ALD1A
LZ1
LW1A
LD1C
LW1B
LW1B
LZ1
LD1A
LW1A
LW1B
LD1C
LZ1
LD1A LD1A
LW1A
LD1A
LD1A
4WLNL6
4WLNL7
4WLNL8
4WLCL5
4WLCL6
W
L S
L
LN1
LD1A
LU1
LU1
LN1
LN1
LD1C
LN1
LN1 LU1
LN1
LN1
LS1A
LS1A
LS1A
LS1A
LD1A
LD1A
LD1A
LT1A LT1A
LT1A
LD1A
LD1A
LD1A
LT1A
LT1A
LT1A
LT1A
LT1A
LT1A
LD1A
LD1A LD1A
LD5
LD5
LT1A
LD1C
LU1
LD1A LD1A
LZ1
LD1ALD1A
LD1C
t t t t b c c b a a a d e
LU1
D c
D II
ab
D t d e
LU1
j k k k kj
D a c a b e c d
D a e M c d
D a e c c cc a b e M c d c c a b e c d
D a e M c d c s s r
D a
D e g a b g g g j j jj e f m
M j t t
XA1
XA1
XA3
XA3
LU1
a a a b b a
LD5
LD5
W
P G
L
/F5 1-EL104W
XA1
cc c c a b e
LU1
d d
D a e M c
LN1
D a
LD1A LD1A
LD1ALD1A
LZ1
cc c c a b
LW1A
e e M c
LU1
d d
LN1
LN1
LW1B
LD1C
LT1B LT1B
D
LW1A
e
LU1
d d
D a e M c
LD1A LD1A
LD1ALD1A
LZ1
cc c c a b
LW1B
LN1
LN1
LD1C
LD5
LD5 LD5
D a
LD1A LD1A
LD1ALD1A
LZ1
cc c c a b
LN1
LN1
LW1B
LD1C
LW1A
e e M c
D a
LZ1
LD1A LD1A
LD1A LD1A
c c cc a b
LW1A
e e M c
LN1
LN1
LW1B
LD1C
LU1
d d
LD5
D a
LZ1
LD1A LD1A
c c a b
LD1A LD1A
cc
LW1A
e e M c
LW1B
LD1C
LN1
LD1C
LN1
LN1
LW1B
LU1
d d
D a
LZ1
LD1A LD1A
c c a b
LD1A LD1A
cc
LW1A
e e M c
LW1B
LD1C
LN1LN1
D a
LW1A
e M ce
LU1
d d
LZ1
LD1A
LD1A
LD1A
LD1A
a b c c c c
LD1A
c
LD1A
c
LW1A
eM c e
LU1
d d D a
LN1
LN1
LW1B
LD1C
LD5 LD5
LT1B
LT1B
LT1B
LT1B
LT1A
LT1B
LW1B
LD1A
LD1A
LD1A
LW1A
e e M c
D a
LZ1
LD1A LD1A
c c a b
LD1A LD1A
cc
LW1B
LN1
LN1
LD1C
d
LT1B
EX. ELEC.
CLOS.
4049C
4 STAIR
WEST
4STW
4 STAIR
CENTER
4STC
EXIST.
ELEC.CL.
4013W
PCTC
4025W
STORAGE
4007W
STF. TLT.
4005W
MED/SURG 1
BED
4014W
DATA
4012W
NOUR.
4024W
BATH
4018aW
BATH
4017aW
MED/SURG 1
BED
4017W
MED/SURG 1
BED
4016W
BATH
4016aW
BATH
4014aW
MED/SURG 1
BED
4020W
MED/SURG 1
BED
4022W
BATH
4023aW
BATH
4022aW
MED/SURG 1
BED
4023W
MED/SURG
BARIATRIC 1
BED
4032W
MED/SURG 1
BED
4029W
BATH
4029aW
MEDS
4028W
ISO. BATH
4002bW
ISO. BATH
4001bW
MED/SURG
ISOLATION
BED
4001W
ANTE
4001aW
MED/SURG
ISOLATION
BARIATRIC
BED
4002W
BATH
4011aW
BATH
4009aW
MED/SURG 1
BED
4009W
MED/SURG
1 BED
4011W
CLEAN
LINEN
4008W
CLEAN
UTILITY
4006W
BATH
4033aW
BATH
4032aW
MED/SURG 1
BED
4033W
SOIL. UTL.
4003W
HAC
4004W
CORRIDOR
4200aW
ELEC.
CLOSET
4030W
FOOD CART
ALCOVE
4010W
EQUIPMENT
ALCOVE
4201kW
ALCOVE
4201bW
NURSE
STATION
4026W
EX. FEC
4015W
MACERATOR
ROOM
4021W
ALCOVE
4201cW
ANTE
4002aW
ELEC.
CLOSET
4031bW
ELEC.
CLOSET
4031aW
PATIENT
MONITORING
4026aW
LT1B
LD1A
LD1A
c c
LT1A LT1A LT1A LT1A LT1A
t t tt t
LZ1
a b
LD1A
c
LD1A
c
LI1A LI1A
LI1ALI1A
CORRIDOR
4202W
XA1
LT1A
LT1A
LT1A
LT1A
LT1A
LT1A
LT1A
LT1A
t t t t t t t t
C5
C5
C5
C5
C5
C5
C5C5
C7
C7
C7
C7
C7
C7
C7
S2
S2
S2
S2
S2
S2 S2
C1
C1
C1
C1
C1
C1
2 2
2 2
C1
C1
C1
C1 C1
C1
C3 5
C3
C3 C3
C3
2 2
C1 C1
C1
C1
5 5
C1
C1C1
C1
C3
C3C3
C3
S1
S1
2 2
C1
C1
C1
C1
C1
C15
C1
C1
C1
C1
C1 C1
C1
C1
C3
C3
5C1
C1
C1
C1
4 4
4 4
C1
C1
C1
C1
C1
C1
C1
C1
4 4
5 5
C3
C3
C3
C3
C3
C3C3
C3
C1
C1
C1
C1
4 4
C1
C1
C1 4
C1
C1
C1
C1
4 4
S1
S1
S1
1 1 1 1 1
S1
LN1
C1
M g
CORRIDOR
4201W
LT1A
S1
LU1
5f f
LT1A
t1
LW1B
C1
LN1
C1
LN1
C1 LU1
m4
LN1
C1
LU1
m2LN1
C1
LU1
d d
LD5
sC3
LD5
sC3
LD5
sC3
LD5
C3s
LW1A
e4 e
LW1A
e e
LD5
LT1A
t1
MED/SURG 1 BED
4018W
DAY LOUNGE
4201fW
MED/SURG 1 BED
4019W
BATH
4019aW
BATH
4020aW
LW1B
C1
LW1B
C1
LD5
sC3
XA1
S1
U.1
V
W.1
12.1
GG
U.6
12.8
15.1
15.2 15.3 16.2 17.1 18 18.1 20
S
T
S.1
R
Q
O
18.716.916.8
LT1B LT1B
LT1A LT1A LT1A LT1A LT1A
LT1A
LT1A
LT1A LT1A LT1A
LD1B LD1B
LD1BLD1B
LD1B LD1B
LD1BLD1BLD1B
LD1B LD1B LD1B
LD1B
LD1B
LD1B
LS1A LS1A LS1A LS1A LS1A
LD1B
c a a aa b b b bb bb b
D II
ab x x x x a b y y y y y yp p p p ppp
LD1A LD1A LD1A
LD1A
LD1ALD1ALD1A
D p p xLL1
XA1
XA1
XA1
XA1
XA1
C
P G
L x x x y y
/F1 1-EL104W
N R
P -4
C
LU1
c
LT1B
LT1B LT1B
LT1B LT1B
LT1B
LT1A
LT1A
LT1B
LW1B
LD1A
D
EX. ELEC.
CLOS.
4049C
EXIST. IT
CLOSET
4051C
DAY
RM./FAMILY
LOUNGE
4035C
STAFF
LOUNGE
4079aC
4S STORAGE
4075C
STORAGE
4036C
PUB. TLT.
4037C
SHARED
STOR.
4080C
TEAM ROOM
4034W
ELEVATOR
LOBBY
4000C
CORRIDOR
4204C
CORRIDOR
4208C
CENTRAL
COR. B
4203C
SERVICE
ELEVATOR
LOBBY
4076C
EXIST.
DISTRIBUTION
4127C
EXIST. IT
CLOSET
4052C
CORRIDOR
4200C
LD1B
5 55
5 5
C3
C3 C3 C3
C3C3
C3 C3
C3C3
C3 C3
3S23
3 S2 3 3 S2
S1
S2
S1
S2
S2
3 S2 3 S2 3
5 5 5
5 5 5
C3
C3
S1
S1
S1
XA1
S1
X.1
SURGEON IN
CHIEF
4188N
OFFICE
4135N
XA1
S1
XA1
S1
LD1B
LD1B
aC3
C3a
LW1B
C1
LT1A
LT1A
LT1A
LT1A
XA1
S1
DEDUCT LEGEND
DEDUCT ALT #1 - SERVICE CORE
SCOPE REMOVAL. REFER TO SPEC
SECTION 012300 ALTERNATES
DEDUCT ALT #2 - CENTRAL CORE
SCOPE REMOVAL. REFER TO SPEC
SECTION 012300 ALTERNATES
WEST
SOUTH NORTH
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
NTS
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc.
Scale: 1/8" = 1'-0"
PARTITION FIRE RATING LEGEND
1 HOUR FIRE
1 HOUR FIRE /
SMOKE BARRIER
423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Area Not in Scope =
45 MIN. RATED DOOR
ASSEMBLY, TYP.
20 MIN. RATED DOOR
ASSEMBLY, TYP.
2 HOUR FIRE
90 MIN. RATED DOOR
ASSEMBLY, TYP.
2 HOUR FIRE /
SMOKE
BARRIER
90 MIN. RATED DOOR
ASSEMBLY, TYP.
Sheet Number 113of
1-EL104W
ELECTRICAL LIGHTING PLAN - 4TH
FLOOR - WEST AND CENTRAL
BN BN
630-18-101
JANUARY 17, 2020 73
SCALE: 1/8" = 1'-0"
F1
ELECTRICAL LIGHTING PLAN - 4TH FLOOR - WEST
1. ALL NIGHTLIGHT FIXTURES (TYPE 'LN1') SHALL BE
CONTROLLED BY INTEGRAL PHOTOCELL CONTROL ONLY
(UNSWITCHED). CONNECT TO CIRCUIT INDICATED UPSTREAM
OF ANY SWITCHES. (TYPICAL).
2. ALL LIGHT FIXTURES 'LZ1' CONSIST OF (3) SEPARATE
SECTIONS, EACH TO BE CIRCUITED AND CONTROLLED
SEPARATELY. (TYP. FOR ALL). REFER TO DETAIL ON DWG. 1-
EL601 FOR FURTHER INFORMATION. (TYPICAL).
a. THE EXAM SECTION SHALL BE CONTROLLED FROM THE PATIENT SERVICE WALL (DIMMER 'a' OR 'c' OR 'e') AND
CONNECTED TO THE CRITICAL PANEL.
b. THE READING/AMBIENT SECTIONS SHALL BE
CONTROLLED FROM THE PILLOW SPEAKER (CONTROL
DESIGNATION 'b' OR 'd' OR 'f') AND CONNECTED TO THE
NORMAL PANEL.
3. PROVIDE UL924 LIGHTING BYPASS RELAY FOR LIFE
SAFETY LUMINAIRES CONTROLLED BY LOCAL SWITCH/DIMMER
AS INDICATED BY CONTROL SUBSCRIPT (TYPICAL). NORMAL
CIRCUIT TO LIGHTING BYPASS RELAY SHALL BE CIRCUIT THAT
SERVES ALL NORMAL LIGHTING FIXTURES WITH THE SAME
CONTROL SUBSCRIPT. REFER TO DETAIL D6/1-EL601 FOR
FURTHER INFORMATION.
4. REFER TO DWG 1-EP401 FOR ELECTRIC CLOSET
LIGHTING PLAN.
5. LUMINAIRES CONNECTED TO LIFE SAFETY SHALL BE
UNSWITCHED AND 'ALWAYS ON' IN ELEVATOR LOBBY 4000C,
CORRIDORS 4200C, 4203C AND SERVICE ELEVATOR LOBBY
4076C. CONNECT UPSTREAM OF SWITCHES AND CONTROLS.
6. 'LD1A' LIGHT FIXTURES WITH CONTROL DESIGNATION
MATCHING MOMENTARY CONTACT WALL SWITCH IN PATIENT
ROOM SHALL BE CONTROLLED BY SAME WALL SWITCH AND
PILLOW SPEAKER. PROVIDE LOW VOLTAGE CONTROLLER TO
INTERFACE LIGHT FIXTURES WITH PILLOW SPEAKER AND
WALL SWITCH . REFER TO DETAIL C6/1-EL601. TYP FOR ALL
PATIENT ROOMS.
7. EXTEND EMERGENCY (LIFE SAFETY) BRANCH CIRCUITS
SERVING EGRESS LIGHTING AND EXIT SIGNS IN THIS AREA.
TERMINATE IN JUNCTION BOX ABOVE CEILING AND LABEL
WITH PANEL AND CIRCUIT NUMBER FOR FUTURE
CONNECTION.
8. NOT USED.
9. DISCONNECT, REMOVE, REINSTALL AND REWIRE ALL
EXISTING CEILING MOUNTED LIGHTING FIXTURES AND CEILING
MOUNTED LOW VOLTAGE DEVICES TO ACCOMMODATE THE
FIRE PROTECTION WORK IN THIS ROOM.
KEYED NOTES :
0 8' 16'
SCALE: 1/8" = 1'-0"
F5
ELECTRICAL LIGHTING PLAN - 4TH FLOOR CENTRAL
0 8' 16'
BRANCH CIRCUIT NOTES :
1. UNLESS OTHERWISE NOTED, CONNECT ALL NORMAL
LIGHTING CIRCUITS IN THIS AREA TO PANELBOARD '4WLNL6'
WITH 2#12&1#12G.-3/4"C.
2. UNLESS OTHERWISE NOTED, CONNECT ALL
EMERGENCY (CRITICAL) LIGHTING CIRCUITS IN THIS AREA TO
PANELBOARD '4WLCL5' WITH 2#12&1#12G.-3/4"C.
3. UNLESS OTHERWISE NOTED, CONNECT ALL
EMERGENCY (LIFE SAFETY) LIGHTING CIRCUITS IN THIS ARE
TO PANELBOARD '4WLSL1' WITH 2#10&1#10G.-3/4"C.
1 2 3 1 2 3
ADDENDUM 01 1 02/12/2021
VOLTAGE
SENSING
CIRCUITRY
TO LUMINAIRE
DRIVER
GENERATOR
SUPPLIED
UNSWITCHED
EMERGENCY
LIGHTING
BRANCH
CIRCUIT
NORMAL
UNSWITCHED
LIGHTING
CIRCUIT
L
N
N
L
L N
EMERGENCY LIGHTING BYPASS DEVICE
(ELBD1 OR ELBD2)
(RE: SPECIFICATION SECTION 26 51 00)
KEYED NOTES :
1. SPECIFIC LOCAL LIGHTING CONTROL DEVICE MAY BE SINGLE POLE, 3-
WAY, OR 4-WAY SWITCH(ES), AUTOMATIC SENSING DEVICE(S), OR DIMMER(S).
2. (1) ONE EMERGENCY LIGHTING BYPASS DEVICE (ELBD1) SHALL SERVE
ONE LUMINAIRE MAXIMUM. ELBD1 SHALL BE FACTORY INSTALLED INTEGRAL TO
THE CONTROLLED LUMINAIRE'S DRIVER/WIRING COMPARTMENT. WHERE
INSTALLATION WITHIN THE LUMINAIRE IS NOT FACTORY INSTALLED, OR NOT
PHYSICALLY POSSIBLE, CONTRACTOR SHALL PROVIDE NEC COMPLIANT NEMA
RATED ENCLOSURE, SIZED PER MANUFACTURER'S DIRECTION, FOR
INSTALLATION OF (1) ONE ELBD1 REMOTE FROM LUMINAIRE, FOR EACH
LUMINAIRE.
LOCAL LIGHTING
CONTROL DEVICE
3/4" C. WIRING AS
REQUIRED
BY MANUFACTURER
NURSE CALL AUDIO STATION BED
CONNECTOR (SYMBOL "ASBC")
LOW VOLTAGE SEQUENTIAL
SWITCH SUPPLIED BY LIGHTING
FIXTURE MANUFACTURER, WIRED
BY THE ELECTRICAL CONTRACTOR.
J
J
120V CRITICAL CKT
(EXAM SECTION)
120V NORMAL CKT
(READING AND
AMBIENT SECTIONS)
FINISHED
CEILING
LUMINAIRE TYPE 'LZ1'
READING/AMBIENT/EXAM LIGHT
NOTES:
TYPICAL FOR ALL PATIENT BED LOCATIONS.
DIGITAL PILLOW SPEAKER SHALL:
A. BE EQUIPPED WITH (2) BUTTONS TO CONTROL THE FOLLOWING LIGHTING:
1. BUTTON #1: SEQUENTIALLY SWITCH READING/AMBIENT LAMPS (LTG. FIXTURE 'LZ1')
2. BUTTON #2: SWITCH DOWNLIGHTS (LTG. FIXTURE 'LD1A')
B. CONTROL NURSE CALL
C. CONTROL TELEVISION
CURBELL LC-060 LOW VOLTAGE
CONTROLLER
J
120V NORMAL CKT
(LTG. FIXTURE 'LD1A')
LEVITON 56081-2 SERIES LOW
VOLTAGE (3A, 24VDC), DOUBLE
THROW, CENTER OFF, NORMALLY
OPEN MOMENTARY DRY CONTACT
WALL SWITCH (SYMBOL 'S' WITH 'M'
SUPERSCRIPT AND LOWER CASE
LETTER IDENTIFYING CONTROL
DESIGNATION). COMMERICAL GRADE,
THERMOPLASTIC BODY AND
ACTUATOR, STEEL STRAP, SELF-
GROUNDING, BACK&SIDE WIRED.
LTG. FIXTURE 'LD1A' WITH
INTEGRAL DRIVER, CONNECT
TO HIGH VOLTAGE SIDE OF
LOW VOLTAGE CONTROLLER
(TYP FOR FIXTURES MATCHING
MOMENTARY DRY CONTACT
WALL SWITCH CONTROL
DESIGNATION)
3/4" C. WIRING PER
MANUFACTURER
REQUIREMENTS
CONNECT TO LOW
VOLTAGE SIDE OF LOW
VOLTAGE CONTROLLER
TELEVISION CONTROL WIRING IN
3/4" C. WIRING AS REQUIRED
PER MANUFACTURER SHOP
DRAWINGS
120V, 20A, 1PH
TIMECLOCK WALL STATION
MINIMUM (8) ZONE 'ON/OFF'
CONTROLS & 'ALL ON' & 'ALL
OFF' SCENE CONTROL
LIGHTING CONTROL MODULE
ZONE 'w'
ZONE 'x'
ZONE 'y'
ZONE 'z'
LAYOUT SYMBOL:
LAYOUT SYMBOL:
TO ADDITIONAL DEVICES
WIRELESS ROUTER MOBILE
DIGITAL
DEVICE
LIGHTING CONTROL SETUP
DOUBLE CATEGORY
DATA JACK
8-CONDUCTOR, RJ45
PROGRAMMING
INTERFACE WITH
INTEGRAL DATA JACK
LCM
PI
LAYOUT SYMBOL:
(REFER TO FLOOR
PLAN FOR
CIRCUITING)
120V, 20A, 1PH
120V LINE
VOLTAGE
120V LINE VOLTAGE
(MOUNT ABOVE
LIGHTING CONTROL
PANEL IN ELEC. RM.
10014W)
CAT6E OR BETTER
TERMINATED WITH
RJ45 CONNECTOR
WIRING PER
MANUFACTURER
REQUIREMENTS
TWS
PANEL 10WLNL1, CIRCUIT #3
WIRING PER
MANUFACTURER
REQUIREMENTS
PANEL 10WLNL1, CIRCUIT #4
PANEL 10WLNL1, CIRCUIT #3
DESCRIPTIONTYPE MOUNTING REFLECTOR / DIFFUSERLAMPS SPECIAL COMMENTS REFERENCED PRODUCT(S)VOLTAGE
LD1A RECESSED
4.75" DEPTH
USAI "BEVELED BASIC"
#1010-B1-S-10 + #LSDT4-9014-M2-35KS-80-NCSM-120-DIML2
4" SQUARE
DOWNLIGHT
1000 LM / 14W
3500 K / 80+ CRI
LED
0-10V DIMMING
DRIVER
1" REGRESSED LOW GLARE
LENS; WIDE BEAM
REFLECTOR
3.5" X 3.5" SQUARE APERTURE
WITH A WHITE 1" REGRESSED
FLANGE; WHITE FINISH; MAX. 6"
WIDE HOUSING
120V
LUMINAIRE SCHEDULE
NOTES
RECESSEDLD1B SAME AS TYPE
'LD1A' EXCEPT
1300 LUMENS
120V1300 LM / 20W
3500 K / 80+ CRI
LED
0-10V DIMMING
DRIVER
USAI "BEVELED BASIC"
#1010-W-B1-S-10 + #LSDT4-9020-M2-35KS-80-NCSM-120-DIML2
LD5 RECESSED2" SQUARE
LENSED
DOWNLIGHT
CLEAR SPECULAR ALUMINUM
REFLECTOR WITH POLISHED
SELF-FLANGE; PHOSPHOR
LENS; 50 DEGREE BEAM
SPREAD
HEAT SINK FOR THERMAL
MANAGEMENT
UNV600 LM / 9W
3500 K / 80CRI
LED
0-10V DIMMING
DRIVER
USAI "SLIVERLED SQUARE DOWNLIGHT"
#SS11-BL-X109-35KS-50-S-WH + #SV-X109-NC-UNV-D2
1" REGRESSED LOW GLARE
LENS; WIDE BEAM
REFLECTOR
3.5" X 3.5" SQUARE APERTURE
WITH A WHITE 1" REGRESSED
FLANGE; WET LOCATION LISTED;
WHITE FINISH; MAX. 6" WIDE
HOUSING
LT1A RECESSED
3.25" DEPTH
UNV DAY-BRITE "DUALED 2X2 LED"
#2-GL-D-34L-835-2-D-UNV-DIM
2' X 2'
DIRECT
3400 LM / 29W
3500 K / 80+ CRI
LED
0-10V DIMMING
DRIVER
LOW GLARE, SOFT OPAL,
EXTRA DIFFUSE ACRYLIC
DIFFUSERS
MATTE WHITE PAINTED COAT
FINISH; DUAL CHAMBER
CONFIGURATION WITH TWO
LARGE AREA DIFFUSERS
LS1A RECESSED;
CONTINUOUS
RUN LENGTH AS
REQUIRED
3.5" WIDE
LINEAR SLOT
695 LM/LF / 7.1W/LF
3500 K / 80+ CRI
LED
0-10V DIMMING
DRIVER
TRIM WITH FLUSH HIGH
IMPACT ACRYLIC EXTRA
DIFFUSE LENS; ALUMINUM
REFLECTOR PAINTED WHITE;
3.5" W, 3 11/16" D; LINEAR
EXTRUDED ALUMINUM T6061
GRADE HOUSING; WHITE
POWDER COAT FINISH
LT1B UNVSAME AS TYPE
'LT1A' EXCEPT
2700 LUMENS
2700 LM / 22W
3500K / 80+ CRI
LED
0-10V DIMMING
DRIVER
ALW "LIGHTPLANE 3.5R"
#LP3.5RT-TGRID-SXX-LOW-80-3500K-0/10V/S-EXT-N-N-N-N-WH-UNV
UNV
LU1 SURFACE;
CONTINUOUS
LENGTH AS
REQUIRED
UNDERCABINET
TASK LIGHT
145 LM/LF / 2W/LF
3500K / 85 CRI
LED
INTEGRAL
ROCKER SWITCH
LOW GLARE, REDUCED LAMP
IMAGE, ACRYLIC TEXTURED
LENS
0.60" EXTRUDED ALUMINUM
HOUSING WITH INJECTION
MOLDED POLYCARBONATE
ENDCAPS AND COVERS; GLOSSY
WHITE POLYESTER POWDER
COATED; 1-3/16"D 4-3/16"W
HOUSING
DAY-BRITE "LINCS LED UNDERCABINET"
#LICS100E-LENGTH-935-120-WHG-DIM-RSW
120V
DAY-BRITE "DUALED 2X2 LED"
#2-GL-D-27L-835-2-D-UNV-DIM
RECESSED
3/25" DEPTH
LN1 WALL MOUNTEDNIGHTLIGHT 2W
AMBER / 80+ CRI
LED
INTEGRAL
PHOTOCELL
MOLDED ACRYLIC LENS 3-15/16" H, 5-3/8" W, 15/16" D;
LINEARLY CURVED LED DIE CAST
ALUMINUM; GALV. STEEL BACK
PLATE AND BOX; SOFT WHITE
FINISH; WET LOCATION
CHLORIDE "WG2H NIGHLIGHT"
#WG2H-2-SHW-PCC
120V
LOW GLARE, SOFT OPAL,
EXTRA DIFFUSE ACRYLIC
DIFFUSERS
MATTE WHITE PAINTED COAT
FINISH; DUAL CHAMBER
CONFIGURATION WITH TWO
LARGE AREA DIFFUSERS
XA1 RECESSED
WALL MTD.
ENCORE "UNO LED EXIT SIGN"EXIT SIGN LED 6" RED LETTERS ON
MIRROR BACKGROUND,
SINGLE/DOUBLE FACE AND
DIRECTIONAL ARROWS AS
SHOWN ON DWGS.
EDGELIT FRAMELESS INJECTION
MOLDED ACRYLIC PANEL SIGN;
DIE CAST ALUMINUM HOUSING
AND TRIM; SEALED
MAINTENANCE-FREE NICKEL
CADMIUM BATTERY; BRUSHED
ALUMINUM FINISH; MAX. 10-3/8" H
WITH TRIM
UNV
LZ1 11000 LM / 126W
3500K / 83 CRI
LED
0-10V DIMMING
DRIVER
VISA LIGHTING "UNITY CM1900"
#CM1900-L35K-H-MVOLT-MWAC
UNVRECESSED
6.5" DEPTH
2X2 MULTI-
FUNCTION
PATIENT BED
LIGHT
CURVED LUMIEO MATTE
WHITE ACRYLIC DIFFUSER
WITH LUMINOUS SIDE
PANELS
PROVIDE LOW VOLTAGE
SEQUENTIAL SWITCH
CONTROLLED BY PILLOW
SPEAKER (AMBIENT/READING);
PROVIDE MANUFACTURER
RECOMMENDED ELEC. DIMMING
DRIVER (EXAM)
XA3 SAME AS TYPE
"XA1" EXCEPT
SURFACE
MOUNTED
ENCORE "UNO LED EXIT SIGN"EXIT SIGN LED 6" RED LETTERS ON
MIRROR BACKGROUND,
SINGLE/DOUBLE FACE AND
DIRECTIONAL ARROWS AS
SHOWN ON DWGS.
EDGELIT FRAMELESS INJECTION
MOLDED ACRYLIC PANEL SIGN;
DIE CAST ALUMINUM HOUSING
AND TRIM; SEALED
MAINTENANCE-FREE NICKEL
CADMIUM BATTERY; BRUSHED
ALUMINUM FINISH; MAX 10-3/8" H
WITH TRIM
UNV
LW1B ALW "TRIPLANE LED WALL"
#TRPSMB-SXX-LOW-80-3500K-0/10V/S-LENS-WH-UNV
120VWALL MOUNTEDSAME AS TYPE
'LW1A' EXCEPT 14
WATTS PER
FOOT
LW1A 1460 LM / 20.6W
3500K / 80+ CRI
LED
REMOTE DRIVER
ALW "TRIPLANE LED WALL"
#TRPSMB-SXX-LOW-80-3500K-0/10V/S-LENS-WH-UNV
UNVWALL MOUNTED2'-0" LONG
LENSED LINEAR
WRAP
ALUMINUM REFLECTOR
PAINTED WHITE;
WRAPAROUND HIGH IMPACT,
LOW GLARE, LOW LAMP
IMAGE, FROSTED ACRYLIC
LENS
2 11/16" HIGH X 2 7/8" DEPTH;
EXTRUDED ALUMINUM T6061
GRADE HOUSING; WHITE
POWDER COAT FINISH
1946 LM / 27.4W
3500K / 80+ CRI
LED
REMOTE DRIVER
ALUMINUM REFLECTOR
PAINTED WHITE;
WRAPAROUND HIGH IMPACT,
LOW GLARE, LOW LAMP
IMAGE, FROSTED ACRYLIC
LENS
2 11/16" HIGH X 2 7/8" DEPTH;
EXTRUDED ALUMINUM T6061
GRADE HOUSING; WHITE
POWDER COAT FINISH
LI1A SUSPENDED
AT 8'-0" AFF
4'-0" LONG
SUSPENDED
INDUSTRIAL
4511 LM / 38W
3500 K / 80+ CRI
LED
ROUND PROFILE LINEAR
WRAP AROUND FULL
FROSTED ACRYLIC LENS
AND WIRE GUARD
3" W, 3-7/8" H; DIE FORMED C.R.S
HOUSING; INTEGRAL DRIVER;
PROVIDE36" CHAIN HANGER AND
ASSOCIATED MOUNTING
HARDWARE; WIRE GUARD
COOPER METALUX "SNLED"
#4-SNLED-LD5-44SL-LW-UNV-L835-CD-1 + #AYC-CHAIN/SET + #WG/SNF-4FT
UNV
LU2 NOT USED
LL1 RECESSED;
CONTINUOUS
RUN LENGTH
AS REQUIRED
3"W
CONTINUOUS
LINEAR WALL
GRAZER
500 LM/LF / 10.3W/LF
3500K / 80+ CRI
LED
0-10V DIMMING
DRIVER
SINGLE-PIECE EXTRUDED
SATINE LENS WITH CONVEX
WINGS AND ARTICULATE
CENTER SPINE
EXTRUDED ALUMINUM TRIM;
PRE-PAINTED FORMED 20 GA.
CRS HOUSING; ELECTRONIC
LED DRIVER; ANTI-MICROBIAL
PAINT; POWDER COAT WHITE
FINISH ON EXPOSED TRIM
PINNACLE "EDGE EVOLUTION 3 LINEAR WALL GRAZER"
#EV3WG-835HO-LENGTH-GX-U-OL1-1-W
UNIV
LD1C RECESSED
4.75" DEPTH
USAI "BEVELED BASIC"
#1010-W-B1-S-10 + #LSDT4-9014-M2-35KS-80-NCSM-120-DIML2
SAME AS TYPE
'LD1A' EXCEPT
WET LOCATION
1000 LM / 14W
3500 K / 80+ CRI
LED
0-10V DIMMING
DRIVER
1" REGRESSED LOW GLARE
LENS; WIDE BEAM
REFLECTOR
3.5" X 3.5" SQUARE APERTURE
WITH A WHITE 1" REGRESSED
FLANGE; WHITE FINISH; MAX. 6"
WIDE HOUSING, WET LOCATION
LISTED
120V
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc. 423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Sheet Number 113of
1-EL601
LUMINAIRE SCHEDULE AND
DETAILS
BN MMC
630-18-101
JANUARY 17, 2020 74
NTSSCALE:
D6
EMERGENCY LIGHTING BYPASS DEVICE (ELBD) SCHEMATIC
A. FOR ALL LUMINAIRES, REFER TO ADDITIONAL
SPECIFICATION REQUIREMENTS IN SECTION 26 51 00.
B. ALL LUMINAIRES ARE 120V, UNLESS OTHERWISE
NOTED.
C. COORDINATE ALL GRID OR FLANGE MOUNTING
HARDWARE REQUIRED AS PER ARCHITECTURAL CEILING
TYPE. REFER TO ARCHITECTURAL DWGS. FOR FURTHER
INFORMATION.
D. REFER TO ARCHITECTURAL PLANS FOR EXACT
LOCATIONS, PLACEMENT AND MOUNTING HEIGHTS OF ALL
LIGHTING FIXTURES, UON.
E. ALL LUMINAIRES WITHIN SPACES AT BUILDING
CORNERS SHALL BE ORIENTED WITH LAMPS PARALLEL TO
LONG DIMENSION OF SPACE.
F. ALL LUMINAIRES WITHIN CORRIDORS SHALL BE
ORIENTED WITH LAMPS PARALLEL TO ADJACENT WALLS.
G. LUMINAIRES SHALL BE PAINTED AFTER
FABRICATION.
GENERAL NOTES:
1. REFER TO ARCHITECTURAL FLOOR PLANS FOR EXACT
LENGTHS OF CONTINUOUS LIGHT FIXTURES. PROVIDE ALL
MOUNTING HARDWARE FOR COMPLETE INSTALLATION BASED ON
ARCHITECTURAL CEILING TYPE. COORDINATE CEILING TYPE WITH
ARCHITECTURAL DWGS.
2. COORDINATE EXACT LENGTHS AND QUANTITIES OF ALL
UNDERCABINET LIGHTING FIXTURES WITH ARCHITECTURAL
DRAWINGS. PROVIDE PRICING ALLOWANCE FOR ALL
UNDERCABINET LIGHTING FIXTURES REQUIRED FOR A COMPLETE
INSTALLATION AS PER ARCHITECTURALENLARGED PLANS,
ELEVATIONS, AND MILLWORK SHOP DRAWINGS.
3. EXPOSED RACEWAY TO ALL UNDERCABINET LIGHTING
FIXTURES SHALL BE SURFACE WIREMOLD RACEWAY FROM
ADJACENT WALL TO FIXTURE, COMPLETE WITH TRANSITION
FITTINGS AND HARDWARE, PAINTED TO MATCH CABINET COLOR.
4. THE EXAM SECTION (DIMMABLE) SHALL BE CONTROLLED
FROM THE PATIENT SERVICE WALL AND CONNECTED TO THE
CRITICAL PANEL, CIRCUIT "A". THE READING AND AMBIENT
SECTIONS SHALL BE CONTROLLED FROM THE PILLOW SPEAKER
AND CONNECTED TO THE NORMAL PANEL, CIRCUIT "B". REFER TO
FLOOR PLANS FOR ACTUAL CONTROL, CIRCUITING AND
PANELBOARD DESIGNATIONS.
5. NOT USED.
6. LIGHTING FIXTURES OF THIS TYPE SHALL ALSO MEET THE
FOLLOWING REQUIREMENTS: ABILITY TO BE UPGRADED TO THE
LATEST LED TECHNOLOGY, 3-3/4" MAX. HOUSING DEPTH, 0-10V
DIMMING CONTROL AND 5-YEAR LIMITED WARRANTY FROM THE
SAME MANUFACTURER THAT COVERS LED, DRIVER AND LIGHT
FIXTURE.
7. REFERENCED PRODUCT MANUFACTURER INFORMATION
PROVIDED FOR DESIGN INTENT AND PRICING ONLY. EQUIVALENT
PRODUCTS ACCEPTABLE.
KEYED NOTES :
NTSSCALE:
C6
NURSE CALL PATIENT BED AND ROOM LIGHTING CONTROL
INTERFACE DETAIL
NTSSCALE:
C4
CORRIDOR LIGHTING CONTROL WIRING SCHEMATIC DETAIL
ADDENDUM 01 1 02/12/2021
C B
T C
T C
J
J
J
J
J
D
D
D
F
F
DN
DN
DN
STAIRS #3
9071S
CORRIDOR
5105S 818.24
PHYSICIAN
5036W 5038W
EXAM. RM.
5040W
STAIR #2
9015W N. COORDINATOR
5034W
PODIATRY EX. RM.
5035W
MEDI. PREP.
5012W
EXAM. RM.
5007W
EXAM. RM.
50010W
WH. CH. & STR.
5042W 62.31
RECEPTION RM.
5003W
RECEPTION RM.
5004W
EXAM.RM.
5005W
EXAM. RM.
5006W
EXAM. RM.
5008W
JANITOR
5033W
EL. CL.
5017W
EXAM. RM.
5009W
NURSE STATION
5011W
CORRIDOR
C5-3W
M.H. TOILET
5031W
S. UTILITY
5029W
CLEAN UTILITY
5030W 5032W
DRESSING
5091A 25.00
RECEP. & CHARTING
5090S
129.54CYSTOSCOPY
5089S 224.34
CONFERENCE RM.
5092S 242.67
WAITING
5091S 167.29
DRESSING
5091BS
15.00
EXAM. RM.
5094S 115.95
EXAM. RM.
5095S 121.93
STORAGE
5083S 318.98
STERILIZER
5087S
STORAGR
5086S 319.73
PATIENT T.
5085S 31.00
CORRIDOR
323.36
UROFLOW RM.
5084S 36.49
CHIEF OF POD.
5041W
CORRIDOR
C5-4W
PODIATRY EX. RM.
5037W
POD. EX. RM.
5039W
CLEAN UTIL.
5078S 38.96
EXAM. RM.
5080S 133.15
GEN.
5078S 31.87
OFFICE (RN )
5081S 141.03
H.K.CLO.
5093S 393.40
F.A.C.
5077S 3.61
EXAM. RM.
5079S 131.59
DU
C T
SH
AF
T
F. LOCKER RM.
55104N 64.34
SPECIAL PROCEDURE
5015W
DRESS
5027W
DRESS
5027W
SCRUB RM.
5020W
PAT. TOILET
5023W
F.A.C.
8016W
EXAM. RM.
5013AW
C
OR
RI
DO
R C 5-
1W
CAST RM.
5025W
P. TOILET
5026W PAT. TOILET
5022W
PROCEDURE
5014W
DUCT SHAFT
DRESS
5024W
M. LOCKER RM.
5017WTOILET
5028W
FEM. LOCKER RM.
5018W
PROCEDURE RM.
5016W
MECHANICAL SPACE
5025W 1504.08
TOILET
5102N 44.60
LOCKER RM.
5101N
CHIEF OF NEPHROLOGY
M.D. OFFICE
5107N
133.75F. TOILET
5103N 52.36
FEL. TRAINING RM.
5106N 133.15
OFFICE ( RN.)
5108N 131.45
CONFERENCE RM.
5109N
WH. CHAIR
5002N
COAT RM.
5105N
CORRIDOR
C5-3N 279.93
SECRETARY
5111N 151.34
ELEC. CLOSET
5047C
ELEV. SHAFT
OFFICE
5105C
OFFICE
5105S
OFFICE
5098S 132.77
EXAM. RM.
5097S 117.21
EXAM. RM.
5096S 117.41
EXAM. RM.
5099S 116.63
WAITING
5102S 300.24
RECEPTION
5103S
OFFICE
5104C
CLOS.
5062S 9.59
EL. CL.
5074S 19.96
PATIENT T.
5100S 23.61
J.C.
5100AS
23.61
CLOSET
5066S 7.5
WOMENS T.
5064S 50.17
WOMENS T.
5101S 24.17
MENS T.
5063S 190.57
MECHANICAL RM.
5066S 1913.26
CORRIDOR
5106S
LAB.
5059S
WAITING
5061S
393.40 RESIDENT
5058S
OFFICE(COORDNR)
5057S
CORRIDOR
5056C
J.C.
5051C
TOILET
5053C
5109C
OFFICE
5113C
F.A.C.
5045C
ELEV. SHAFT
SERVICE LOBBY
5112C
DISTR.
5107C
ELEV. SHAFT
ELEV. SHAFT
ELEV. SHAFT
ELEV. SHAFT
TELEPHONE
5042C
TOILET
5052C
ELEVATOR LOBBY
5000C
ELEV. SHAFT
CORRIDOR
5055C
ELEV. SHAFT
ELEV. SHAFT
ELEV. SHAFT
ELEV. SHAFT
PATIENT WAITING
50001W
ELEV. SHAFT
STAIR #1
5001W
DUCT SHAFT
EXAM. RM.
5002W
EXAM. RM.
5004W
OFFICE
5048C
NURSE STATION
5011W
EXAM.RM.
5013W
C
OR
RI
DO
R C 5-
2W
D.F.
15.1
G
F.5
ERP-4W
C
E R
P W
E
R P
W
15.1
G
F.5
4WPGL4
C50
CR
W
4WLEL123
N
4WLCL5
4WLCL6
C50 W
CR
4WLSL1
C3
W
LI2B
C50
CR
L
4WLNL8
4WLNL7
4WLNL6
LI2B
C3
W C50
CR
15.1
R
Q
ES4
ERP-4C
15.1
R
Q
C
P G
L 3 13
C50
CR
W
E S
P9
P10
P11P12
ERP5W2
ERP5W1
P10
P9
28 28
E1-5
E2-3
E1-2
E1-3
1-EP401
F5
MCC-5A
MCC-E5A
APPROXIMATE LOCATION
OF PPGC-2 IN RM DC-21
HOUSEKEEPING STORAGE
ON THE GROUND FLOOR.
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc. 423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Sheet Number 113of
1-EP401
ELECTRICAL ENLARGED PLANS -
ELECTRICAL POWER PLAN - 5TH
FLOOR
IHF MTK
630-18-101
JANUARY 17, 2020 76
0 4' 8'SCALE: 1/4" = 1'-0"
A1
EXISTING ELECTRIC CLOSET
4013W - DEMOLITION
1. FIRE ALARM PULL BOX - ETR.
2. PULLBOX/CONDUIT RISERS - ETR.
3. 225A ENCLOSED C/B - ETBR
4. TELEPHONE TERMINAL CABINET AND WIRING - ETBR.
5. FIRE ALARM DISCONNECT SWITCH - ETR.
6. PULL BOX - ETR.
7. EXISTING CONDUIT RISERS - ETR.
8. EXISTING PANEL 'ERP-4W' - ETBR. 'CRITICAL'. 225A-3P
MAIN C/B, 120/208V, 3PH, 4W, 42 POLE PANEL. SQUARE D
PANELBOARD WITH (13) CONDUITS EXITING BOTTOM OF
PANELBOARD AND INTO THE FLOOR SLAB.
9. ELECTRONIC TIME SWITCHES, CONDUIT AND WIRING -
ETBR.
10. SPEAKER AMPLIFIER, CONDUIT AND WIRING - ETBR.
11. EXISTING PANEL 'ERP4W3' - ETBR. 'EMERGENCY'. 200A-3P
MAIN C/B, 120/208V, 3PH, 4W, 42 POLE SQUARE D
PANELBOARD.
12. EXISTING PANEL 'ERP4W4' - ETBR. 'EMERGENCY'. 175A-3P
MAIN C/B, 120/208V, 3PH, 4W, 42 POLE SQUARE D
PANELBOARD.
13. NEW DISTRIBUTION PANEL (250AF/225AT, 120/208V, 3PH,
4W).
14. EXISTING PANEL 'ES4' - ETR. 225A-3P MAIN C/B, 120/208V,
3PH, 4W, 42 POLE PANEL. SQUARE D PANELBOARD WITH
(5) CONDUITS EXITING THE BOTTOM OF THE PANEL AND
INTO THE FLOOR SLAB.
15. EXISTING PANEL 'ERP-4C' - ETBR. 'CRITICAL'. 225A-3P MAIN
C/B, 120/208V, 3PH, 4W, 42 POLE PANEL. PANELBOARD
WITH (7) CONDUITS EXITING THE BOTTOM OF THE PANEL
AND INTO THE FLOOR SLAB.
16. EXISTING DISTRIBUTION PANEL 'RPGE'.
17. EXISTING PANEL 'ERP-10C' - ETBR. 'CRITICAL'. 225A-3P
MAIN C/B, 120/208V, 3PH, 4W, 42 POLE PANEL.
PANELBOARD WITH (6) CONDUITS EXITING THE BOTTOM
OF THE PANEL AND INTO THE FLOOR SLAB. PANEL
'ERP-10C' BRANCH CIRCUITS SERVING AREAS
DESIGNATED 'ETR' OR NOT IN SCOPE SHALL BE
MAINTAINED AND RECONNECTED: NORMAL POWER
BRANCH CIRCUITS SHALL BE CONNECTED TO PANEL
'10WLNL1'; EMERGENCY (CRITICAL) BRANCH CIRCUITS
SHALL BE CONNECTED TO PANEL '10WLCL1'; EMERGENCY
(EQUIPMENT) BRANCH CIRCUITS SHALL BE CONNECTED
TO PANEL '10WCLEL1'.
18. EXISTING PANEL 'ES10' - ETR. 100A-3P MAIN C/B, 120/208V,
3PH, 4W, 30 POLE PANEL. ITE PANELBOARD WITH (7)
CONDUITS EXITING THE BOTTOM OF THE PANEL AND INTO
THE FLOOR SLAB.
19. EXISTING PANEL 'ERP-10C2' - ETBR. 100A-3P MAIN C/B,
120/208V, 3PH, 4W, 30 POLE PANEL. SQUARE D
PANELBOARD MOUNTED ABOVE CONDUIT RISER PULL
BOX.
20. EXISTING PANEL 'ERP-10W SECTION 1' - ETBR. 225A MAIN
C/B, 120/208V, 3PH, 4W, 36 POLE PANEL. ITE PANELBOARD
WITH (7) CONDUITS EXITING THE BOTTOM OF THE PANEL
AND INTO THE FLOOR SLAB.
21. EXISTING PANEL 'ERP-10W SECTION 2' - ETBR. 225A MAIN
C/B, 120/208V, 3PH, 4W, 36 POLE PANEL. ITE PANELBOARD
WITH (7) CONDUITS EXITING THE BOTTOM OF THE PANEL
AND INTO THE FLOOR SLAB.
22. LIGHTING CONTROL MODULE AND PROGRAMMING
INTERFACE FOR CORRIDOR LIGHTING. REFER TO WIRING
DIAGRAM ON DETAIL C4/1-2EL601.
23. CARD READER DESIGNATED BY SUBSCRIPT (CR) (TYP.)
UON, CONNECT TO EMERGENCY (CRITICAL) POWER.
CIRCUIT AS INDICATED. (TYP. FOR ALL CARD READERS).
24. RECONNECT EXISTING BRANCH CIRCUIT FROM MCC-5A TO
REDUNDENT VFD AND EXTEND TO NEW AC-24
25. RECONNECT EXISTING BRANCH CIRCUIT FROM MCC-5A TO
REDUNDENT VFD AND EXTEND TO NEW RF-24
26. EXTEND NEW CONDUIT AND WIRE FROM EXISTING
DISCONNECT TO NEW PUMPS P11 AND P12. CIRCUITS
ORIGINATE IN MCC-E5A.
27. EXTEND NEW CONDUIT AND WIRE FROM EXISTING
DISCONNECT TO NEW PUMPS P9 AND P10. CIRCUITS
ORIGINATE IN MCC-E5A
28. EXISTING STARTER AND BRANCH CIRCUIT FROM MCC-E5A
TO REMAIN AND BE RECONNECTED.
29. REMOVE, STORE, AND REINSTALL LIGHT FIXTURES AS
NECESSARY FOR AHU AND DUCTWORK REPLACEMENT.
30. EXISTING FIRE ALARM DUCT DETECTOR TO REMAIN.
31. RECONNECT EXISTING FIRE ALARM ADDRESSABLE TO
BOTH REDUNDANT VFDS.
32. UPSIZE EXISTING FEEDER FROM 100A (3)#2, (1)#8G,
1-1/4"C TO 250A (3)#4/0, (1)#4G, 2-1/2"C THAT EXTENDS
FROM EXISTING 600A SUB-DISTRIBUTION PANEL PPGC-2
KEYED NOTES :
SCALE: 1/4" = 1'-0"
D1
EXISTING ELECTRIC CLOSETS
4025aW AND 4025bW -
DEMOLITION
0 4' 8'
0 4' 8'SCALE: 1/4" = 1'-0"
C1
EXISTING ELECTRIC CLOSET
4013W - POWER AND SYSTEMS
SCALE: 1/4" = 1'-0"
F1
ELECTRIC CLOSET 4031aW -
POWER AND SYSTEMS
0 4' 8'
SCALE: 1/4" = 1'-0"
A3
ELECTRIC CLOSET 4031bW -
POWER AND SYSTEMS
0 4' 8'
SCALE: 1/4" = 1'-0"
C3
ELECTRIC CLOSET 4030W -
POWER AND SYSTEMS
0 4' 8'
SCALE: 1/4" = 1'-0"
D3
EXISTING ELECTRIC CLOSET
4049C - DEMOLITION
0 4' 8'
0 4' 8'
SCALE: 1/4" = 1'-0"
F3
EXISTING ELECTRIC CLOSET
4049C - POWER AND SYSTEMS
1. UNLESS OTHERWISE NOTED, CONNECT ALL
EMERGENCY (CRITICAL) LIGHTING CIRCUITS IN THIS AREA TO
PANELBOARD '4WLCL5' WITH 2#12&1#12G.-3/4"C.
2. UNLESS OTHERWISE NOTED, CONNECT ALL
EMERGENCY (CRITICAL) POWER CIRCUITS IN THIS AREA TO
PANELBOARD '4WLCL6' WITH 2#12&1#12G.-3/4"C.
3. UNLESS OTHERWISE NOTED, CONNECT ALL
EMERGENCY (CRITICAL) LIGHTING CIRCUITS IN THIS AREA TO
PANELBOARD '10WLCL1' WITH 2#12&1#12G.-3/4"C.
4. UNLESS OTHERWISE NOTED, CONNECT ALL
EMERGENCY (CRITICAL) POWER CIRCUITS IN THIS AREA TO
PANELBOARD '10WLCL1' WITH 2#12&1#12G.-3/4"C.
5. UNLESS OTHERWISE NOTED, CONNECT ALL NORMAL
POWER CIRCUITS IN THIS AREA TO PANELBOARD '10WLNL1'
WITH 2#12&1#12G.-3/4"C.
BRANCH CIRCUIT NOTES :
1 2
1 2 1 2
1 2
1 2
ADDENDUM 01 1 02/12/2021
SCALE: 1/4" = 1'-0"
F5
5th FLOOR ELECTRICAL EQUIPMENT ROOM POWER PLAN
SCALE: 1/32" = 1'-0"
C5
5th FLOOR OVERALL POWER PLAN
ALT #E01
E1-1 NOT APPLICABLE
E1-2 DEDUCT ALL WORK ASSOCIATED WITH THE INSTALLATION
OF NEW GLYCOL HEAT EXCHANGER PUMPS AND UPM
VFD'S
E1-3 DEDUCT ALL WORK ASSOCIATED WITH THE INSTALLATION
OF NEW HOT WATER HEAT EXCHANGER PUMPS AND PUMP
VFD'S
E1-4 NOT APPLICABLE
E1-5 DEDUCT ALL WORK ASSOCIATED WITH THE INSTALLATION
OF NEW REDUNDANT VFD'S FOR RETURN FAN RF-24.
ALT#E02
E2-1 NOT APPLICABLE
E2-2 NOT APPLICABLE
E2-3 DEDUCT ALL WORK ASSOCIATED WITH THE INSTALLATION
OF NEW REDUNDANT VFD'S FOR NEW AHU AC-24.
E2-4 NOT APPLICABLE
DEDUCT ALTERNATE NOTES
00 32' 64'
0 4' 8'
4SLCL3 4SLCL4 4SLNL3 4SLNL4 4SLNL5
ELEC. CLOSET
RM. 4205eS
ELEC. CLOSET
RM. 4063S
4WLSL1
ELEC.
CLOSET
RM. 4031aW
ELEC. CLOSET
RM. 4030W
8NLCL2 8NLSL1 8NLNL28NLCL1
ELEC. CLOSET
RM. 8119N
ELEC. CLOSET
RM. 8138N
17SLCL2 17SLNL3 17SLNL4
ELEC. CLOSET
RM. 17057S
ELEC. CLOSET
RM. 17051S
17NLSL1
ELEC. CLOSET
RM. 17096N
ELEC. CLOSET
RM. 17102N
40A-3P
GROUND
FLOOR
THROUGH TO
3RD FLOOR
4TH FLOOR
5TH FLOOR
THROUGH TO
7TH FLOOR
8TH FLOOR
GROUND
FLOOR
THROUGH TO
3RD FLOOR
5TH FLOOR
THROUGH TO
7TH FLOOR
8TH FLOOR
9TH FLOOR 9TH FLOOR
17TH
FLOOR 17TH FLOOR
EXTERIORINTERIORCENTER WINGWEST WINGWEST WINGSOUTH WING NORTH WINGCENTER WING
18TH FLOOR
THROUGH TO
ROOF
18TH FLOOR
THROUGH TO
ROOF
7TH FLOOR:
ERP7S, EDR7S1
4TH FLOOR
225A/MCB
ERP-8C
4WPGL44SPGL2
100A/MCB
ES4
100A/MCB
NRP-4C
PULLBOX
(ETR)
120/208V
3PH, 4W
42 POLE
120/208V
3PH, 4W
42 POLE
120/208V
3PH, 4W
42 POLE
FROM LOAD SIDE
OF ATS 1-1 VIA
SWBD. 'SSB-1'
'ERPGS-2'
2000A MLO
120/208V, 3PH, 4W
GROUND FL.
RM. 0165S
600A
600A
FROM LOAD
SIDE OF ATS 4-1
VIA SWBD.
'SSA-2'
'EDP-GW'
2000A MLO
120/2058V, 3PH, 4W
GROUND FL.
RM. 0119W
600A
FROM LOAD
SIDE OF ATS
4-1 VIA SWBD.
'SSA-2'
'EDP-GC'
2000A MLO
120/208V, 3PH, 4W
GROUND FL. RM. G001W
600A
600A
600A
FROM LOAD
SIDE OF ATS
3-1 VIA SWBD.
'SSA-1'
'EDP-GN'
2000A MLO
120/208V, 3PH, 4W
GROUND FL.
RM. 0253N
600A
600A
600A MLO
'ESS'
120/208V, 3PH, 4W
GROUND FL.
RM. 0273N
FROM
LOAD
SIDE OF
ATS 5-1
150A-3P
FROM
SWBD.
'SSC-1',
'NORMAL'
'RPGE'
800A MLO
120/208V, 3PH, 4W
GROUND FL.
RM. 0242N
ELEC. CLOS.
RM. 4056S
ELEC. CLOS.
RM. 4049C
STAFF
LOUNGE
RM. 4079AC
ELEC. CLOS.
RM. 8001C
ELEC. CLOS.
RM. 8128N
ELEC. CLOS.
RM. 17001C
ELEC. CLOS.
RM. 17121N
ELEC. CLOS.
RM. 17154S
6TH FLOOR:
ERP6C
7TH FLOOR:
ERP7C
1ST FLOOR:
ERP1C, ERP1C1
5TH FLOOR:
ERP5C
1ST FLOOR:
ERP1N
ESGC
100A/MCB
ES10
ES18
ES1
2ND FLOOR:
ERP2C
3RD FLOOR:
ERP3C
11TH FLOOR:
ERP11C, ERP11C1
14TH FLOOR:
ERP14C
16TH FLOOR:
ERP16C
13TH FLOOR:
ERP13C
12TH FLOOR:
EDP12C
15TH FLOOR:
EDP15C
13TH FLOOR:
ERP13S, ERP13S1,
ERP13S2
16TH FLOOR:
ERP16S, ERP16S1
5TH FLOOR:
EDP5S3, EDP5S4
8TH FLOOR:
ERP8S, ERP8S1
11TH FLOOR:
ERP11S, ERP11S1,
ERP11S4,
ERP11S5
14TH FLOOR:
ERP14S, ERP14S1,
ERP14S2,
ERP14S3
7TH FLOOR:
ERP7W, ERP7W1
7TH FLOOR:
ERP7N, ERP7N1,
ERP7N2
13TH FLOOR:
ERP13N, ERP13N1,
ERP13N2
16TH FLOOR:
ERP16N, ERP16N1
2ND FLOOR:
ERP2N
5TH FLOOR:
ERP5N, ERP5N1,
ERP5N2, ERP5N3,
ERP5N4, ERP5N5
11TH FLOOR:
ERP11N, ERP11N1,
ERP11N2,
ERP11N3
14TH FLOOR:
ERP14N, ERP14N1
'GS RISER 2'
1-750kcmil
'GS RISER 1'
1-750kcmil
'RISER 1'
1-750kcmil
'RISER 2'
1-750kcmil
'RISER 1'
1-750kcmil
'RISER 3'
1-750kcmil
1-#3/0
'RISER 2'
1-750kcmil
'RISER 1'
1-750kcmil
INTERIOREXTERIOR
18TH FLOOR:
ERP18C2, P-18F,
18AC, ERP18W1,
ERP18C1,
MCCE19A
17TH FLOOR:
ERP17W1
FROM
SWBD.
'SSC-1',
'NORMAL'
'EMDPG'
800A MLO
120/208V, 3PH, 4W
GROUND FL.
RM. 0211E
200A
225A
11TH FLOOR:
EPP11C,
NRP11C,
NRP11W
100A/MCB
NRP-8C
120/208V
3PH, 4W
DAY RM./FAM. LOUNGE
RM. 8113C
80A-3P
80A-3P
ELEC.
CLOSET
RM. 4031bW
8 8 8
PB40/4 40/4
PB
(ETR)
60/4
60/4
PB 60/4
60/49 10
4CPGL3
40A-3P
40A-3P
8NPGL1
17CPGL3
100A-3P
17NPGL1
80A-3P
TO ELEC. SHOP 7291. MAIN FEED FOR A/C
UNITS IN 5025 WEST
1-#4/0
ELEC. CLOS.
RM. 18001C
17SPGL2
17NLNL117NLCL1 17NLNL2
8NLNL1 8NLNL3
4WLNL6 4WLNL7 4WLNL84WLCL64WLCL5
120/208V
3PH, 4W
42 POLE
120/208V
3PH, 4W
42 POLE
225A/MCB
ERP4N
225A/MCB
ERP4N1
ELEC. CLOSET
RM. 8204fN
400A MLO
10CPEL1
120/208V
3PH, 4W
42 POLE
100A MLO
10CLEL1
120/208V
3PH, 4W
42 POLE
10TH FLOOR 10TH FLOOR
11TH FLOOR
THROUGH TO
16TH FLOOR
11TH FLOOR
THROUGH TO
16TH FLOOR
9TH FLOOR:
EDP9C
10TH FLOOR:
ERP10S, ERP10S1,
10TH FLOOR:
ERP10N, ERP10N1,
ERP10N2
300A
13TH FLOOR:
ES13
16TH FLOOR:
ES16
7TH FLOOR:
ES7
ELEC. CLOS.
RM. 10001C
MECH
ROOM
RM. 10011C
80A-3P 60A-3P
17NLEL1
8NLEL1
4WLEL1
ELEC. CLOS.
RM. 4013W
PB74
PB
PB
PB
PB
PB
PB
PB
80A-3P
PB
PB
200AF/100AT
200AF/100AT
200AF/100AT
125/4
100/4
150/4
(2) 150/4 150/4
100/4 125/4
/4
100/4 100/4
125/4
100/4
(2) 100/4
100/
125/
60/4
100/
200AF/200AT
200AF/200AT
120/208V
3PH, 4W
30 POLE
10CPGL1
10WPGL2
ELEC. CLOS.
RM. 10014W
10WLNL2
10WLCL1
10WLNL1
200A/MCB
EPP-10C
100A/MCB
NRP-10C
EXIST. DIST.
RM. 10109C
80A-3P
TO NRP-10N PANELBOARD
(NORTH WING)
100A/MCB
EPP-8C
EXIST. DIST.
RM. 8111C
120/208V
3PH, 4W
120/208V
3PH, 4W
120/208V
3PH, 4W
EXIST. DIST.
RM. 4127C
175A/MCB
EPP-4C
120/208V
3PH, 4W
ELEC. CLOSET
RM. 10018W
ELEC. CLOSET
RM. 10202aW
40A-3P
100A/MLO
9LSL1
ELEC.
RM 9131C
120/208V
3PH, 4W
30 POLE
PB
600A
225A MCB
ERP-17W
120/208V
3PH, 4W
42 POLE
100A MLO
ERP-17W-2
100A-3P
120/208V
3PH, 4W
26 POLE
1-#4/0 1-#2
'RISER 2'
1-750kcmil
8TH FLOOR:
ERP8W, ERP8W1
11TH FLOOR:
ERP11W,
ERP11W4,
ERP11W5
14TH FLOOR:
ERP114W,
ERP14W1,
ERP14W2
18TH FLOOR:
CLPP4, CLPP5
5TH FLOOR:
ERP5W, ERP5W1
6TH FLOOR:
ERP6W, ERP6W1
ELEC. CLOS.
RM. 17006W
125/4
125/4
/4
60A-3P
60A-3P
AREA NOT IN SCOPE =
FEEDE
R ID
AMPS
PHASE
WIRES
(AWG)
NEUTRAL
WIRES
(AWG)
GND
(AWG)
MIN.
CONDUIT
SIZE
40/4 40 (3)#8 (1)#8 #10 3/4
60/4 60 (3)#4 (1)#4 #10 1-1/4
100/4 100 (3)#1 (1)#1 #8 1-1/2
125/4 125 (3)#1 (1)#1 #6 1-1/2
150/4 150 (3)#1/0 (1)#1/0 #6 2
FEEDER SCHEDULE COPPER CONDUCTORS
175/4
(3)#2/0 (1)#2/0 #6 2
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc. 423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Sheet Number 113of
1-EP601
NEW PARTIAL ONE-LINE DIAGRAM
IHF MMC
630-18-101
JANUARY 17, 2020 79
1. THE EXISTING CONDITIONS PARTIAL ELECTRICAL RISER
DIAGRAM DEPICTED ON THIS DWG. WAS TAKEN FROM A SQUARE D
SYSTEMS ONE-LINE DIAGRAM DATED 03/09/05 AND SEL SYSTEMS
ONE-LINE DIAGRAM DATED 7/8/2013, 60% REVIEW. THE SQUARE D
SERIES OF DWGS. CONSISTS OF (12) DWGS.: DWG. NOS. D-
ML-04-360-1 THROUGH D-ML-04-360-12. THE SEL DWGS. CONSIST OF
(13) DWGS.: DWG. NOS. D-ML-04-360-1 THROUGH D-ML-04-360-13.
2. PANELBOARD DESIGNATIONS ARE NOTED BASED ON THE
SQUARE D DWGS. WITH THE EXCEPTION OF THE 4TH, 8TH, 10TH, AND
17TH FLOOR. THOSE PANEL DESIGNATIONS ARE BASED ON SITE
OBSERVATIONS.
3. COORDINATE THE SHUTDOWN OF EACH EXISTING VERTICAL
RISER, EXISTING SWITCHBOARD OR PANELBOARD TO
ACCOMMODATE NOTED SCOPE OF WORK WITH VETERANS AFFAIRS
(VA).
4. SUBMIT SCHEDULE FOR SHUTDOWNS OF ALL EXISTING
ELECTRICAL RISERS AND ASSOCIATED DOWNSTREAM DISTRIBUTION
COMPONENTS.
5. THE LIFE SAFETY BRANCH, CRITICAL BRANCH AND
EQUIPMENT SYSTEM SHALL BE KEPT ENTIRELY INDEPENDENT OF
ALL WIRING AND EQUIPMENT AND SHALL NOT ENTER THE SAME
RACEWAYS, OR PASS THROUGH WIREWAYS, BOXES OR CABINETS
WITH EACH OTHER OR OTHER WIRING.
1. PER NEC 517-14, THE EQUIPMENT GROUNDING TERMINAL
BUSES OF THE NORMAL AND ESSENTIAL BRANCH CIRCUIT
PANELBOARDS SERVING THE SAME INDIVIDUAL PATIENT VICINITY
SHALL BE BONDED TOGETHER WITH AN INSULATED CONTINUOUS
COPPER CONDUCTOR NOT SMALLER THAN #10 AWG. WHERE
MORE THAN TWO PANELS SERVE SAME LOCATION, THIS
CONDUCTOR SHALL BE CONTINUOUS FROM PANEL TO PANEL,
BUT SHALL BE PERMITTED TO BE BROKEN IN ORDER TO
TERMINATE ON THE GROUND BUS IN EACH PANEL. PROVIDE
REQUIRED BONDING FOR NORMAL AND CRITICAL PANELS PER
NEC AS INDICATED.
2. COORDINATE THE INSTALLATION AND ROUTING OF THE
NEW ELECTRICAL FEEDER ORGINATING FROM THE 10TH FLOOR
EXISTING PANEL 'ES10' DOWN TO THE 8TH FLOOR EMERGENCY
ELECTRICAL CLOSET '8204fN'. PROVIDE CORE DRILLING, FIRE
STOPPING, CUTTING, PATCHING AND PAINTING. PREPARE
CONDUIT ROUTING SHOP DRAWING FOR REVIEW AND APPROVAL
BY ARCHITECT AND VETERANS AFFAIRS (VA) STAFF.
3. COORDINATE THE INSTALLATION AND ROUTING OF THE
NEW ELECTRICAL FEEDER ORGINATING FROM THE 18TH FLOOR
EXISTING PANEL 'ES18' DOWN TO THE 17TH FLOOR EMERGENCY
ELECTRICAL CLOSET '17096N'. PROVIDE CORE DRILLING, FIRE
STOPPING, CUTTING, PATCHING AND PAINTING. PREPARE
CONDUIT ROUTING SHOP DRAWING FOR REVIEW AND APPROVAL
BY ARCHITECT AND VETERANS AFFAIRS (VA) STAFF.
4. COORDINATE THE INSTALLATION AND ROUTING OF THE
NEW ELECTRICAL FEEDER ORGINATING FROM THE 10TH FLOOR
EXISTING PANEL '10CLEL1' DOWN TO THE 17TH FLOOR
EMERGENCY ELECTRICAL CLOSET '17096N'. PROVIDE CORE
DRILLING, FIRE STOPPING, CUTTING, PATCHING AND PAINTING.
PREPARE CONDUIT ROUTING SHOP DRAWING FOR REVIEW AND
APPROVAL BY ARCHITECT AND VETERANS AFFAIRS (VA) STAFF.
5. COORDINATE THE INSTALLATION AND ROUTING OF THE
NEW ELECTRICAL FEEDER ORGINATING FROM THE 10TH FLOOR
EXISTING PANEL '10CPEL1' DOWN TO THE 8TH FLOOR
ELECTRICAL CLOSET '8128N'. PROVIDE CORE DRILLING, FIRE
STOPPING, CUTTING, PATCHING AND PAINTING. PREPARE
CONDUIT ROUTING SHOP DRAWING FOR REVIEW AND APPROVAL
BY ARCHITECT AND VETERANS AFFAIRS (VA) STAFF.
6. NOT USED
7. TYPICAL. PULLBOX LOCATIONS AND QUANTITIES PER
NEC. PULLBOX SUPPORTED FROM WALL OR BUILDING
STRUCTURE WITH U-CHANNEL AND THREADED ROD.
8. EXISTING RISER PULL BOX.
9. INSTALL NEW CIRCUIT BREAKER TO MATCH
MANUFACTURER AND ELECTRICAL CHARACTERISTICS, 22 KAIC.
NEW CIRCUIT BREAKER SHALL INCLUDE MOUNTING HARDWARE
AND BUS EXTENSIONS FOR COMPLETE INSTALLATION. UPDATE
PANELBOARD DIRECTORY AND INCLUDE CIRCUIT
BREAKER/PANELBOARD TRIM.
10. DISCONNECT AND REMOVE (3) 20A-1P C/B'S TO
ACCOMMODATE INSTALLATION OF NEW 3-POLE C/B. REWIRE (3)
20A-1P C/B'S TO PANEL INDICATED WITH 2#12&1#12G.-3/4"C.
11. FLOOR-TO-FLOOR HEIGHTS ARE APPROXIMATE.
12. NEW PANELBOARD (400AF/250AT, 120/208V, 3PH, 4W)
INSTALLED IN EXISTING CLOSET.
13. REMOVE EXISTING 300 KCMIL CONDUCTORS BACK TO
EXISTING MECHANICAL CONNECTORS ATTACHED TO RISER
DISTRIBUTION CABLE.
14. PROVIDE NEW MATCHING CONDUCTORS (4#300KCMIL
COPPER & 1#2/0G.) AND MECHANICAL CONNECTORS AND ATTACH
TO EXISTING RISER DISTRIBUTION CABLE. EXTEND NEW
CONDUCTORS AND RACEWAY TO PANELBOARD.
15. INSTALL MATCHING 3-POLE C/B. RECONNECT EXISTING
FEEDER SERVING AC UNITS IN 5025W. REFER TO PANEL
SCHEDULE.
16. INSTALL NEW 100A-3P C/B. RECONNECT EXISTING FEEDER
SERVING ELEC. SHOP 7291. REFER TO PANEL SCHEDULE.
17. NEW PANELBOARD, (250AF/225AT, 120/208V, 3PH, 4W).
18. PROVIDE NEW MATCHING CONDUCTORS (4#4/0&1#4G.)
AND MECHANICAL CONNECTORS AND ATTACHTO EXISTING RISER
DISTRIBUTION CABLE. EXTEND NEW CONDUCTORS AND
RACEWAY TO PANELBOARD.
19. COORDINATE THE INSTALLATION AND ROUTING OF THE
NEW ELECTRICAL FEEDER ORGINATING FROM THE 10TH FLOOR
EXISTING PANEL '10CPEL1' DOWN TO THE 4TH FLOOR
ELECTRICAL CLOSET '4013W'. PROVIDE CORE DRILLING, FIRE
STOPPING, CUTTING, PATCHING AND PAINTING. PREPARE
CONDUIT ROUTING SHOP DRAWING FOR REVIEW AND APPROVAL
BY ARCHITECT AND VETERANS AFFAIRS (VA) STAFF.
20. COORDINATE THE INSTALLATION AND ROUTING OF THE
NEW ELECTRICAL FEEDER ORGINATING FROM THE GROUND
FLOOR EXISTING PANEL 'RPGE' UP TO THE 4TH FLOOR
ELECTRICAL CLOSET '4063S'. PROVIDE CORE DRILLING, FIRE
STOPPING, CUTTING, PATCHING AND PAINTING. PREPARE
CONDUIT ROUTING SHOP DRAWING FOR REVIEW AND APPROVAL
BY ARCHITECT AND VETERANS AFFAIRS (VA) STAFF.
21. EXISTING 800A MLO, 24 POLE, SQUARE D I-LINE
PANELBOARD. INSTALL (3) NEW CIRCUIT BREAKERS TO MATCH
MANUFACTURER AND ELECTRICAL CHARACTERISTICS, 65 KAIC.
NEW CIRCUIT BREAKERS SHALL INCLUDE MOUNTING HARDWARE
AND BUS EXTENSIONS FOR COMPLETE INSTALLATION. UPDATE
PANELBOARD DIRECTORY AND INCLUDE CIRCUIT
BREAKER/PANELBOARD TRIM.
22. PROVIDE NEW 4#300KCMIL COPPER & 1#2/0G.
CONDUCTORS AND MECHANICAL CONNECTORS AND ATTACH TO
EXISTING RISER DISTRIBUTION CABLE. EXTEND NEW
CONDUCTORS AND RACEWAY TO PANELBOARD.
GENERAL NOTES:
KEYED NOTES :
NTSSCALE:
F1
NEW PARTIAL ONE-LINE DIAGRAM
ADDENDUM 01 1 02/12/2021
| 1-EL104W - ELECTRICAL LIGHTING PLAN - 4TH FLOOR - WEST AND CENTRAL |
| 1-EL601 - LUMINAIRE SCHEDULE AND DETAILS |
| 1-EP401 - ELECTRICAL ENLARGED PLANS - ELECTRICAL POWER PLAN - 5TH FLOOR |
| 1-EP601 - NEW PARTIAL ONE-LINE DIAGRAM |
File details come from the government source that posted it. Updated .