03 VAMC_4W MED SURG_ARCH DWGS_ADD 01.pdf

PDF 4 MB Posted

Attached to
Y1DA--630-18-101 RENOVATE PATIENT WARD 4W STEP DOWN UNIT
Solicitation number
36C24221B0001
Issued by

About this file

This solicitation is for renovations to patient ward 4W at the Manhattan VA Medical Center in New York. The scope of work includes renovations to the step-down unit, including architectural, mechanical, electrical, and infrastructure upgrades. Specific requirements include renovating patient rooms, nurse stations, bathrooms, and common areas; replacing windows; upgrading mechanical, electrical, and plumbing systems; and installing new finishes. The solicitation includes construction drawings and specifications outlining the renovation work. The estimated award date is listed as February 2022.

View the file

Other files

File Type Posted
36C24221B0001 0009.docx DOCX document
06 VAMC_4W MED SURG_ELEC DWGS_ADD 01.pdf PDF
28 31 00 - FIRE DETECTION AND ALARM - ADDN 02.pdf PDF
VAMC_4W MED SURG_ADD 02 Narrative.pdf PDF
07 VAMC_4W MED SURG_TELECOMM DWGS_ADD 01.pdf PDF
2020-0228_VAMC_4W MED SURG_EQUIP CUT BOOK VOL 1 02.pdf PDF
02 VAMC_4W MED SURG_STRUCT DWGS_ADD 01.pdf PDF
36C24221B0001 0008.docx DOCX document
2020-0228_VAMC_4W MED SURG_EQUIP CUT BOOK VOL 1.pdf PDF
Manhattan VA 4 W-Pre-Bid RFIs-201219.xlsx XLSX spreadsheet
10 51 13 - METAL LOCKERS - ADDN 02.pdf PDF
36C24221B0001 0007.docx DOCX document
36C24221B0001 0006.docx DOCX document
Wage Determination NY 2021 0003.pdf PDF
VA 4W Follow Up RFI Comments 210211.pdf PDF
2021-0129_VAMC_4W MED SURG_100 CD_DRAWINGS_REVISED.pdf PDF
36C24221B0001 0005.docx DOCX document
Manhattan VA 4 W-Pre-Bid RFIs-Responses.xlsx XLSX spreadsheet
36C24221B0001 0004.docx DOCX document
36C24221B0001 0003.docx DOCX document
36C24221B0001 0002.docx DOCX document
36C24221B0001 0001.docx DOCX document
Drawings Renovate Patient Ward 4W Part 3.pdf PDF
Drawings Renovate Patient Ward 4W Part 1 -.pdf PDF
Specifications Renovate Patient Ward 4W Part 4.pdf PDF
Specifications Renovate Patient Ward 4W Part 1.pdf PDF
Specifications Renovate Patient Ward 4W Part 2.pdf PDF
Drawings Renovate Patient Ward 4W Part 4.pdf PDF
36C24221B0001_1.docx DOCX document
Specifications Renovate Patient Ward 4W Part 3.pdf PDF
Drawings Renovate Patient Ward 4W Part 2.pdf PDF
Specifications Renovate Patient Ward 4W Part 5.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Revisions:

Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

Building Number

Approved:

Drawing Title Project Title

Date

Office of Construction &

Facilities Management

F

E

D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

C

B

A

Location

Checked Drawn

Drawing Number

Project Number

CONSULTANTS: ARCHITECT/ENGINEERS:

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

KEY PLAN:

VA FORM 08-6231

Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered

ASBESTOS ABATEMENT CONSULTANT:

14 HIGH STREET

MAHWAH, NEW JERSEY 07430

Tel: (914) 320-7924

Egan Environmental Consulting, Inc. 423 EAST 23RD STREET

NEW YORK, NY 10010

VA NY HARBOR HEALTHCARE SYSTEM

MANHATTAN VAMC -

BUILDING 1 WARD RENOVATIONS

Sheet Number 113of

1-G001

DRAWING INDEX - 4TH FLOOR WEST

& CENTRAL

AH GV

630-18-101

February 12, 2021 2

DRAWING INDEX - 4TH FLOOR WEST

SHEET NUMBER SHEET NAME 0

/0

/2

S c h e m a ti c D e s ig n S u b m is s io n

/2

/2

C o n s tr u c ti o n

D o c u m e n t S u b m is s io n

/1

/2

C o n s tr u c ti o n

D o c u m e n t S u b m is s io n

/1

/2

A D

D E

N D

U M

1-Q104W EQUIPMENT PLAN AND INDEX - 4TH FLOOR - WEST & CENTRAL • •

MECHANICAL DEMOLITION

1-MD001 MECHANICAL DEMOLITION GENERAL NOTES, SYMBOLS, & ABBREVIATIONS • •

1-MD104W MECHANICAL DEMOLITION PLAN 4TH FLOOR - WEST & CENTRAL • • •

1-MD105W MECHANICAL DEMOLITION PLAN 5TH FLOOR WEST MER • •

MECHANICAL

1-M001 GENERAL NOTES, SYMBOLS & ABBREVIATIONS • • •

1-M002 MECHANICAL AHU ZONING PLAN • • • •

1-M104W DUCTWORK PLAN 4TH FLOOR - WEST & CENTRAL • • •

1-M204W MECHANICAL PIPING PLAN 4TH FLOOR - WEST & CENTRAL • • •

1-M301 ENLARGED PLANS AND SECTIONS • • •

1-M302 ENLARGED PLANS AND SECTIONS • •

1-M401 ENLARGED MECHANICAL PLANS - TYPICAL ROOMS • • •

1-M501 MECHANICAL DETAILS • • •

1-M502 MECHANICAL DETAILS • •

1-M503 MECHANICAL DETAILS • •

1-M504 MECHANICAL DETAILS • •

1-M505 MECHANICAL DETAILS •

1-M601 MECHANICAL SCHEDULES • •

1-M701 MECHANICAL DUCT RISER DIAGRAM • •

1-M801 MECHANICAL FLOW AND CONTROL DIAGRAMS • •

1-M802 MECHANICAL FLOW AND CONTROL DIAGRAMS •

1-M803 MECHANICAL FLOW AND CONTROL DIAGRAMS • •

FIRE ALARM

1-FA001 FIRE ALARM SYMBOLS, NOTES, ABBREVIATIONS AND SMOKE ZONE

DIAGRAMS

1-FA104W FIRE ALARM PLAN - 4TH FLOOR - WEST AND CENTRAL • • •

1-FA601 PARTIAL FIRE ALARM RISER DIAGRAM • • •

ELECTRICAL DEMOLITION

1-ED103W ELECTRICAL DEMOLITION PLAN - 3RD FLOOR - WEST AND CENTRAL - 5TH

FLOOR - CENTRAL

1-ED104W ELECTRICAL DEMOLITION PLAN - 4TH FLOOR - WEST AND CENTRAL • • •

1-ED601 EXISTING PARTIAL ONE-LINE DIAGRAM - ELECTRICAL DEMOLITION • • •

ELECTRICAL

1-E0001 ELECTRICAL SYMBOLS, NOTES AND ABBREVIATIONS • • •

1-EL104W ELECTRICAL LIGHTING PLAN - 4TH FLOOR - WEST AND CENTRAL • • • •

1-EL601 LUMINAIRE SCHEDULE AND DETAILS • • • •

1-EP104W ELECTRICAL POWER PLAN - 4TH FLOOR - WEST AND CENTRAL • • •

1-EP401 ELECTRICAL ENLARGED PLANS - ELECTRICAL POWER PLAN - 5TH FLOOR • • •

1-EP501 ELECTRICAL DETAILS • •

1-EP502 ELECTRICAL PATIENT SERVICE WALL DETAILS • •

1-EP601 NEW PARTIAL ONE-LINE DIAGRAM • • • •

1-EP602 ELECTRICAL SCHEDULES - 4 WEST NORMAL • •

1-EP603 ELECTRICAL SCHEDULES - 4 WEST EMERGENCY • •

TELECOMMUNICATION

1-T001 TELECOMMUNICATIONS LEGENDS, SYMBOLS & ABBREVIATIONS • • •

1-T101 TELECOMMUNICATIONS PLAN - 2ND FLOOR - WEST • • •

1-T102 TELECOMMUNICATIONS PLAN - 4TH FLOOR - WEST AND CENTRAL • • • •

1-T201 AUDIO VISUAL PLAN - 4TH FLOOR - WEST AND CENTRAL • • •

1-T301 NURSE CALL PLAN - 4TH FLOOR - WEST AND CENTRAL • • •

1-T401 SECURITY PLAN - 4TH FLOOR - WEST AND CENTRAL • • •

1-T611 OPTICAL FIBER BACKBONE DISTRIBUTION RISER • • •

1-T612 COPPER BACKBONE DISTRIBUTION RISER • • •

1-T711 TELECOMMUNICATIONS DETAILS • •

1-T712 TELECOMMUNICATIONS DETAILS • •

1-T721 AUDIO VISUAL DETAILS • •

1-T731 NURSE CALL DETAILS • • •

1-T741 SECURITY DETAILS • •

1-T742 SECURITY DETAILS • •

PLUMBING DEMOLITION

1-PD103W PLUMBING DEMOLITION PLAN 3RD FLOOR - WEST AND CENTRAL • • •

1-PD104W PLUMBING DEMOLITION PLAN 4TH FLOOR - WEST AND CENTRAL • • •

PLUMBING

1-P001 PLUMBING - ABBREVIATIONS AND SYMBOLS • • •

1-P103W PLUMBING SANITARY PLAN 3RD FLOOR - WEST AND CENTRAL • • •

1-P104W PLUMBING SANITARY PLAN 4TH FLOOR - WEST AND CENTRAL • • •

1-P203W PLUMBING SUPPLY PLAN 3RD FLOOR - WEST AND CENTRAL • • •

1-P204W PLUMBING SUPPLY PLAN 4TH FLOOR - WEST AND CENTRAL • • •

1-P304W PLUMBING MEDICAL GAS PLAN 4TH FLOOR - WEST AND CENTRAL • • •

1-P601 SANITARY RISER DIAGRAMS - 4TH FLOOR • • •

1-P602 SANITARY RISER DIAGRAMS - 4TH FLOOR • • •

1-P603 SANITARY RISER DIAGRAMS - 4TH FLOOR • • •

1-P604 WATER RISER DIAGRAMS - 4TH FLOOR • • •

1-P605 WATER RISER DIAGRAMS - 4TH FLOOR • • •

1-P606 WATER RISER DIAGRAMS - 4TH FLOOR • • •

1-P607 MEDICAL GAS RISER DIAGRAMS •

FIRE PROTECTION - DEMOLITION

1-FD104W FIRE PROTECTION DEMOLITION PLAN 4TH FLOOR - WEST AND CENTRAL • • •

FIRE PROTECTION

1-F001 FIRE PROTECTION GENERAL NOTES, ABBREVIATIONS AND SYMBOLS • • •

1-F104W FIRE PROTECTION PLAN 4TH FLOOR - WEST AND CENTRAL • • •

DRAWING INDEX - 4TH FLOOR WEST

SHEET NUMBER SHEET NAME 0

/0

/2

S c h e m a ti c D e s ig n S u b m is s io n

/2

/2

C o n s tr u c ti o n

D o c u m e n t S u b m is s io n

/1

/2

C o n s tr u c ti o n

D o c u m e n t S u b m is s io n

/1

/2

A D

D E

N D

U M

GENERAL PROJECT

1-G000 COVER SHEET - 4TH FLOOR WEST & CENTRAL • • •

1-G001 DRAWING INDEX - 4TH FLOOR WEST & CENTRAL • • • •

LIFE SAFETY

1-G104 LIFE SAFETY PLAN 4TH FLOOR - OVERALL • • •

1-G104W LIFE SAFETY PLAN 4TH FLOOR - WEST & CENTRAL • • •

1-G204W ICRA & PHASING - 3RD & 4TH FLOOR - WEST & CENTRAL • •

ARCHITECTURAL DEMOLITION

1-AD103W DEMOLITION PLANS 3RD FLOOR - WEST & CENTRAL • • •

1-AD104W DEMOLITION PLANS 4TH FLOOR - WEST & CENTRAL • • •

HAZARDOUS MATERIALS

1-H001 ASBESTOS ABATEMENT NOTES AND ACM QUANTITY TABLE • • •

1-H104W ASBESTOS ABATEMENT PLAN 4TH FLOOR - WEST & CENTRAL • • •

STRUCTURAL

1-S001 STRUCTURAL DETAILS AND GENERAL NOTES • • • •

ARCHITECTURAL

1-A001 SYMBOLS & ABBREVIATIONS • • •

1-A002 TYPICAL MOUNTING HEIGHTS • • • •

1-A104W ARCHITECTURAL PLAN 4TH FLOOR - WEST & CENTRAL • • • •

1-A451 EXTERIOR SECTION DETAILS • • •

1-A452 EXTERIOR SECTION DETAILS • •

1-A453 EXTERIOR WINDOW DETAILS • •

1-A601 PATIENT BED SERVICE WALL ELEVATIONS 4TH FLOOR - WEST • • •

1-A602 ENLARGED PLANS & INTERIOR ELEVATIONS 4TH FLOOR - WEST • •

1-A603 ENLARGED PLANS & INTERIOR ELEVATIONS 4TH FLOOR - WEST • • •

1-A604 ENLARGED PLANS & INTERIOR ELEVATIONS 4TH FLOOR - WEST • •

1-A605 ENLARGED PLANS & INTERIOR ELEVATIONS 4TH FLOOR - WEST • •

1-A606 ENLARGED PLANS & INTERIOR ELEVATIONS 4TH FLOOR - WEST • •

1-A607 INTERIOR ELEVATIONS 4TH FLOOR - WEST • •

1-A704W REFLECTED CEILING PLAN 4TH FLOOR - WEST & CENTRAL • • •

1-A711 CEILING DETAILS • • •

1-A801 INTERIOR DETAILS • • •

1-A802 INTERIOR DETAILS • • •

1-A901 MILLWORK DETAILS • • •

1-A902 MILLWORK DETAILS • • •

1-A903 MILLWORK DETAILS •

1-A1001 PARTITION SCHEDULE AND DETAILS • • •

1-A1002 PARTITION DETAILS • • •

1-A1005 DOOR SCHEDULE, WINDOW SCHEDULE, FRAME ELEVATIONS AND DETAILS

4TH FLOOR - WEST

1-A1006 DOOR FRAMES, ELEVATIONS AND DETAILS • •

1-A1201 FINISH LEGEND • • • •

1-A1202 FINISH SCHEDULE 4TH FLOOR - WEST & CENTRAL • • •

1-A1204W FINISH PLAN 4TH FLOOR - WEST & CENTRAL • • •

1-A1251 ENLARGED FINISH PLAN VIEWS 4TH FLOOR - WEST & CENTRAL • •

1-A1301 SIGNAGE ABBREVIATIONS SYMBOLS AND GENERAL NOTES • •

1-A1302 MESSAGE SCHEDULE 4TH FLOOR - WEST • •

1-A1304W WAYFINDING PLAN 4TH FLOOR - WEST & CENTRAL • •

1-A1311 INTERIOR SIGNAGE ELEVATIONS AND DETAILS • •

1-A1312 INTERIOR SIGNAGE ELEVATIONS AND DETAILS • •

1-A1313 INTERIOR SIGNAGE ELEVATIONS AND DETAILS • •

1-A1404W FURNITURE PLAN 4TH FLOOR - WEST & CENTRAL • •

EQUIPMENT

ADDENDUM 01 1 02/12/2021

1 1

DN

UP

UP

UP

UP

DN

UP

DN

UP

17 19 21

20 2212.8 15.2

18.716.8

17.1

16.9

16.2

A

B

C

D

E

G

F

J.2

H

J

L

N

O

Q

R

S S.1

T

U.6

15.3

E.9

U.1

W.1

F.5

12.1 13 15.1 16

V

X.1

RESIDENT

SURG. SERV.

4184N

RESIDENTS

4137AN

STAFF LOUNGE

4135N

STAFF

LOCKERS

4136N

LOUNGE

4088S

EQUIP. STOR.

4127aC

SOIL. EQUIP.

4086AC

STOR.

4086C

STAFF LOUNGE

4085S

DISTRIBUTION

4127C

SERV. LOBBY

4128C

2 BEDROOM

4084S

TOILET

4054C

HAC

4053C

HAC

4052C

IT

4051C

DR. OFFICE

4046C

2 BED ROOM

4044W

TOILET

4043W

2 BED ROOM

4042W

PHYS. OFFICE

4041W

MEDS

4040W

NURSE

STATION

4039W

2 BED ROOM

4037W

ISOLATION

ROOM

4034W

2 BED ROOM

4032W

2 BED ROOM

4030W

4 BEDROOM

4028W

TOILET

4029W

TOILET

4031W

TOILET

4035W

ANTE

4033W

TOILET

4038W

HAC

4002W

TOILET

4003W

2 BED ROOM

4004W

DAY ROOM

4005W

STORAGE

4006W

TOILET

4006AW

SOIL. UTL.

4007W

TOILET

4008W

KITCHEN

4010W

FAMILY

COORD.

4011W

EXAM

4012W

STORAGE

4013W

CORRIDOR

4019W

2 BED ROOM

4014W

2 BED ROOM

4016W

TOILET

4015W

STOR.

4019aW

CLEAN LINEN

4018W

SUPPLY

4017W

ELEC. CLOS.

4013W

TOILET

4020W

TOILET

4021W

ANTE

4023W

ISOLATION

ROOM

4022W

4 STAIR W

4STW

HOSE

CLOSET

4015W

2 BED ROOM

4024W

2 BED ROOM

4027W

TOILET

4026W

VERNACARE

4024aW

ELEC.

4049C

FEC

4053C

ELEC. CLOS.

4025aW

ELEC. CLOS.

4025bW

STORAGE

4001aW

STORAGE

4001bW

4 STAIR C

4STC

CONNECTION TO OR'S

(BUILDING 6)

OPEN TO

BELOW

STAFF

LOCKERS

4138N

STAFF TOILET

4137N

WAITING

4132N

TOILET

4130N

TOILET

4131N

CORRIDOR

4180N

11 14

17 19 21

20 2212.8 15.2

18.716.8

17.1

16.9

16.2

A

B

C

D

E

G

F

J.2

H

J

L

N

O

Q

R

S S.1

T

U.6

15.3

E.9

U.1

W.1

F.5

12.1 13 15.1 16

V

X.1

HOSPITAL

DIRECTOR

3022W

ADMIN

ASSISTANT

3029W

EXEC. CHIEF

OF STAFF

3021W

ASS. DIRECTOR

PATIENT SERV.

3020W

PERF. IMPROV

MGR

3019WSTAFF

ASSISTANT

3024W

HEALTH SYS.

SPEC. COS

3032W

STAFF

ASSISTANT

3033W

DATA

MANAGER

3034W

BUSINESS

OFFICER

3035W

CONFERENCE

A

3036W

ASSOCIATE

DIRECTOR

3023W

F.A.C.

3015W

EL. CLOS.

3011W

T. STAFF MALE

3009W

T. STAFF

FEMALE

3010W

CORRIDOR

3010AW

CONFERENCE

PM.

3011EW

WAITING

3011W

STORAGE

3011DW

ACNS OPC.

COORDINATOR

3011CW

INFO. MGR.

3011AW

ADMIN.

RESIDENT

3010W

LOCKERS-FAX-COPY

3008A-W

FILES

3008B-W

OFFICE

(F.FRASER)

3008W

PROGRAM

MNG. OFFICE

3007W

M.V.P.

CO-COORDINATOR

3005W

CLOSET

3006W

HOUSEKEEPING

3003C

CONFERENCE

B

3036BW

EEO

SPECIALIST

3036C

PATIENT REP.

PROG.

3037C

PATIENT REP.

PROG.

3038C

ELEC. CLOSET

3001C

3 STAIR C

3STC

ELEVATOR

LOBBY

3000C

CORRIDOR

3039C

F.E.C.

3045C

CORRIDOR

3040C

FILE STORAGE

3061AE

DISTR.

3077C

EQUIP. STOR

3078C

SERVICE

LOBBY

3076C

PAT. SERVICES

SUPERVISOR

3038C

SECRETARY

MEDICAL

3043S

DEPUTY PL

MANAGER

3043S

CORRIDOR

3041S

MED CARE LINE

MANAGEMENT

3075S

NURSE

EDUCATOR

3075AS

CONFERENCE

ROOM

3076S

DIET.

VOLUNTEER

3081E

SALAD PREP

3080C

CORRIDOR

3102E

J.C.

3103C

L.C.

3102C

STORAGE

ROOM

3101C

UTILITY

3100E

DISH WASHERS

3105C

KITCH. & DISH

WASHING

3107N

CORRIDOR

3109N

SEC. TO CHIEF

3123N

CHIEF

DIETETIC

SERVICE

3123N

PROGRAM

CLERK

3123BN

DIETECIAN

3123N

TOILET

3123EN

TOILET

3123EN

MECHANICAL

ROOM

3122N

3078C

3 STAIR W

3STW

NATIONAL

ETHICS CTR.

3011BW

ICRA & PHASING LEGEND

ICRA & PHASING KEYED NOTEX

PHASING IMPACT AREA - STAGE 1

PHASING IMPACT AREA - STAGE 2

GENERAL ICRA & PHASING NOTES

PHASING IMPACT AREA - STAGE 3

SPECIFIC ICRA & PHASING NOTES

TEMPORARY FULL HEIGHT ICRA BARRIER SEALED AIR-

TIGHT, REFER TO PARTITION TYPE 11b

A. TYPE OF CONSTRUCTION PROJECT ACTIVITY:

TYPE D - MAJOR DEMOLITION AND CONSTRUCTION

PROJECTS. INCLUDES, BUT IS NOT LIMITED TO ACTIVITIES

WHICH REQUIRE CONSECUTIVE WORK SHIFTS; REQUIRES

HEAVY DEMOLITION OR REMOVAL OF A COMPLETE

CABLING SYSTEM; NEW CONSTRUCTION; ASBESTOS

ABATEMENT WORK.

B. PATIENT RISK GROUPS THAT WILL BE AFFECTED:

HIGH RISK: CCU, EMERGENCY ROOM, LABORATORIES

(SPECIMEN), OUTPATIENT SURGERY, PHARMACY, POST

ANESTHESIA CARE UNIT, SURGICAL UNITS

C. DESCRIPTION OF REQUIRED INFECTION CONTROL

PRECAUTIONS BY CLASS (IV):

DURING CONSTRUCTION OF PROJECT:

1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING

DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.

2. COMPLETE ALL CRITICAL BARRIERS I.E. SHEETROCK,

PLYWOOD, PLASTIC, TO SEAL AREA FROM NON-WORK

AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH

PLASTIC COVERING AND SEALED CONNECTION TO WORK

SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT)

BEFORE CONSTRUCTION BEGINS.

3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE

UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS.

4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES

APPROPRIATELY.

5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL

TO PASS THROUGH THIS ROOM SO THEY CAN BE

VACUUMED USING A HEPA VACUUM CLEANER BEFORE

LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER

COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE

THE WORK SITE.

6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED

TO WEAR SHOE COVERS. SHOE COVERS MUST BE

CHANGED EACH TIME THE WORKER EXITS THE WORK

AREA.

7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL

COMPLETED PROJECT IS INSPECTED BY THE OWNER’S

SAFETY DEPARTMENT AND INFECTION CONTROL

DEPARTMENT AND THOROUGHLY CLEANED BY THE

OWNER’S ENVIRONMENTAL

SERVICES DEPARTMENT.

8. NOTE: ALL ASBESTOS ABATEMENT WORK SHALL BE

PERFORMED AS CLASS IV WORK, AND IS FURTHER

SUBJECT TO ADDITIONAL PROVISIONS OF THE NY STATE

ASBESTOS REGULATIONS (NY DEPARTMENT OF LABOR

INDUSTRIAL CODE RULE 56).

UPON COMPLETION OF PROJECT:

1. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE

SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH

CONSTRUCTION.

2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT

IN TIGHTLY COVERED CONTAINERS.

3. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE

COVERING UNLESS SOLID LID.

4. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.

5. WET MOP AREA WITH DISINFECTANT.

6. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE

WORK IS BEING PERFORMED.

7. FOR ASBESTOS ABATEMENT WORK, CONFIRM THAT THE

LICENSED PROJECT MONITOR HAS PERFORMED A FINAL

VISUAL INSPECTION AND CONDUCTED CLEARANCE AIR

SAMPLING AS REQUIRED UNDER NY STATE ASBESTOS

REGULATIONS (NY DEPARTMENT OF LABOR INDUSTRIAL

CODE RULE 56).

D. CONSTRUCTION BARRIER MUST BE APPROVED BY COR &

SAFETY MANAGER PRIOR TO START OF CONSTRUCTION WORK.

E. SWING SPACE WILL BE REQUIRED TO FACILITATE NEW WORK.

EXACT LOCATION TBD PRIOR TO NOTICE TO PROCEED FOR

CONSTRUCTION. COORDINATE SCOPE AND LOCATION WITH VA

PROJECT MANAGER.

F. PROVIDE STICKY WALK-OFF MATS ON BOTH SIDES OF ALL ICRA

DOORS AND ACCESS POINTS.

G. CONTRACTOR TO COORDINATE TEMP PARTITION LOCATIONS

WITH THE OPERATIONAL AND SECURITY REQUIREMENTS OF THE

VETERANS ASSOCIATION (VA). TEMP BARRIER TO BE PARTITION

TYPE 11b. CONTRACTOR TO PROVIDE 45 MINUTE DOOR TYPE F (3'-0" X 7'-0") WITH HOLLOW METAL FRAME TYPE a. DOOR TO

INCLUDE HARDWARE TYPE HW-5 WHICH INCLUDES AN EXIT

DEVICE, CLOSER AND STORAGE ROOM LOCKSET WITH 6 SETS OF

KEYS CREATED FOR USE BY CONTRACTOR & VA.

H. CONSTRUCTION BARRIER MUST BE INSTALLED AND APPROVED

BY COR & SAFETY MANAGER PRIOR TO START OF ANY

CONSTRUCTION WORK.

I. GC SHALL PROVIDE ALL ICRA ELEMENTS FOR ALL AREAS OF

WORK. COORDINATE WITH WORK SHOWN BY ALL DISCIPLINES,

ESPECIALLY WITH EXISTING OCCUPIED SPACES.

J. COORDINATE ICRA PLAN WITH CONSTRUCTION PHASES. NOT ALL

ICRA PARTITIONS ARE SHOWN ON THESE PLANS. ALL PHASES

MUST BE COORDINATED WITH THE OWNER PRIOR TO ANY WORK.

K. COORDINATE ALL SHUT-DOWNS WITH OWNER AND

COSNTRUCTION MANAGER AS PART OF ICRA REQUIREMENTS.

L. PROTECTIVE COVERALLS AND SHOE COVERS ARE REQUIRED

FOR ALL WORK TO BE DONE IN EXISTING BUILDING.

M. FOR PHASE 3, DESCRIPTION OF REQUIRED INFECTION CONTROL

PRECAUTIONS BY CLASS (II):

DURING CONSTRUCTION OF PROJECT:

1. PROVIDE AVTICE MEANS TO PREVENT AIRBORNE DUST

FROM DISPERSING INTO ATMOSPHERE.

2. WATER MIST WORK SURFACES TO CONTROL DUST

WHILE CUTTING.

3. SEAL UNUSED DOORS WITH DUCT TAPE.

4. BLOCK OFF AND SEAL AIR VENTS.

5. PLACE DUCT MAT AT ENTRANCE AND EXIT OF WORK

AREA.

6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE

WORK IS BEING PERFORMED.

UPON COMPLETION OF PROJECT:

1. WIPE WORK SURFACES WITH DISINFECTANT.

2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT

IN TIGHTLY COVERED CONTAINERS.

3. WET MOP AND/OR VACUUM WITH HEPA FILTERED

VACUUM BEFORE LEAVING WORK AREA.

4. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE

WORK IS BEING PERFORMED.

PROJECT IMPACT AREA

EXISTING FULL HEIGHT PARTITION AS BARRIER

STAFF/PATIENT TRAFFIC FLOW

SECURE STAIR DURING CONSTRUCITON. PROVIDE

TEMPORARY LOCK TO RESTRICT RE-ENTRY INTO THE

UNIT, BUT PROVIDE FREE EGRESS INTO THE STAIRWELL,

COORDINATE WITH VA TO PROVIDE KEYS FOR SECURITY

AND FACILITIES..

PROVIDE TEMPORARY BARRIER, HM DOOR WITH CARD

READER ACCESS TO RESTRICT ACCESS INTO BUILDING 6

DURING CONSTRUCTION, COORDINATE WITH VA TO

PROVIDE KEYS FOR SECURITY AND FACILITIES..

CONTRACTOR TO COORDINATE SCHEDULED WORK NEAR

THE ENTRANCES TO 4N AND 4S WITH THE VA TO

FACILITATE NEW SCOPE OF 4 CENTRAL. CONCEPT

SHOWN IS TO SHUTDOWN ONLY ONE ENTRANCE AT A

TIME SO THAT TRAFFIC AND EGRESS FROM CENTRAL

ZONE IS ACCESSIBLE IN AT LEAST ONE DIRECTION. ICRA

PRECAUTIONS IN THIS ZONE IS LIMITED TO CLASS II (TYPE

C, LOW RISK).

4N AND 4S ONLY HAVE 1 MEANS OF EGRESS AVAILABLE IF

ENTRANCE IS SHUTDOWN. PROVIDE ABILITY TO EXIT

THROUGH AREA OF WORK IN CASE OF EMERGENCY.

PROVIDE TEMPORARY BARRIER, HM DOOR WITH CARD

READER ACCESS TO RESTRICT ACCESS INTO THE

CONSTRUCTION ZONE, COORDINATE WITH VA TO

PROVIDE KEYS FOR SECURITY AND FACILITIES.

EGRESS PATH

HEPA EXHAUST UNIT TO EXTERIOR

NEGATIVE AIR MONITOR (BALL-IN-WALL OR EQUAL)

UTILIZE EXISTING DOOR AS CONSTRUCTION ENTRANCE.

PROVIDE TEMPORARY HARDWARE TO ALLOW FOR

LOCKING, COORDINATE WITH VA TO PROVIDE KEYS FOR

SECURITY AND FACILITIES.

TEMPORARILY REMOVE RESTRICTED ACCESS

CAPABILITIES TO ALLOW ACCESS FROM ELEVATORS TO

4N, 4S AND 4 CENTRAL.

SECOND MEANS OF EGRESS FROM 4S, 4N AND 4CENTRAL

IS AVAILABLE IN BOTH 4S AND 4N WINGS.

TWO MEANS OF EGRESS IS AVAILABLE FROM

CONSTRUCTION PHASE 1 IN THE 4W WING WITHOUT

BEING REQUIRED TO EXIT THE ZONE.

MAINTAIN OPERATIONS OF 4 ELEVATOR BAYS DURING

CONSTRUCTION PHASE 1 AND 2. COORDINATE

SHUTDOWN AND ACCESS CONTROL OF ELEVATORS WITH

OWNER.

TEMPORARY ICRA POLY BARRIER WITH ZIPPER ACCESS

DOOR.

14 2012.8 15.2

18.716.8

17.1

16.9

16.2

O

Q

R

S S.1

T

U.6

15.3

U.1

W.1

12.1 13 15.1 16

V

X.1

STAFF

LOCKERS

4136N

LOUNGE

4088S

EQUIP. STOR.

4127aC

SOIL. EQUIP.

4086AC

STOR.

4086C

STAFF LOUNGE

4085S

DISTRIBUTION

4127C

SERV. LOBBY

4128C

TOILET

4054C

HAC

4053C

HAC

4052C

IT

4051C

DR. OFFICE

4046C

2 BED ROOM

4044W

HAC

4002W

ELEC.

4049C

FEC

4053C

4 STAIR C

4STC

STAFF

LOCKERS

4138N

WAITING

4132N

CORRIDOR

4180N

5 7

14 2012.8 15.2

18.716.8

17.1

16.9

16.2

O

Q

R

S S.1

T

U.6

15.3

U.1

W.1

12.1 13 15.1 16

V

X.1

STAFF

LOCKERS

4136N

LOUNGE

4088S

EQUIP. STOR.

4127aC

SOIL. EQUIP.

4086AC

STOR.

4086C

STAFF LOUNGE

4085S

DISTRIBUTION

4127C

SERV. LOBBY

4128C

TOILET

4054C

HAC

4053C

HAC

4052C

IT

4051C

DR. OFFICE

4046C

2 BED ROOM

4044W

HAC

4002W

ELEC.

4049C

FEC

4053C

4 STAIR C

4STC

STAFF

LOCKERS

4138N

WAITING

4132N

CORRIDOR

4180N

1412.8 15.2

18.716.8

17.1

16.9

16.2

T

U.6

15.3

U.1

W.1

12.1 13 15.1 16

V

STOR.

4086C

SERV. LOBBY

4128C

HAC

4053C

FEC

4053C

CORRIDOR

4180N

4 3

WEST

SOUTH NORTH

360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Revisions:

Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

Building Number

Approved:

Drawing Title Project Title

Date

Office of Construction &

Facilities Management

F

E

D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

C

B

A

Location

Checked Drawn

Drawing Number

Project Number

CONSULTANTS: ARCHITECT/ENGINEERS:

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

KEY PLAN:

NTS

VA FORM 08-6231

Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED

ASBESTOS ABATEMENT CONSULTANT:

14 HIGH STREET

MAHWAH, NEW JERSEY 07430

Tel: (914) 320-7924

Egan Environmental Consulting, Inc. 423 EAST 23RD STREET

NEW YORK, NY 10010

VA NY HARBOR HEALTHCARE SYSTEM

MANHATTAN VAMC -

BUILDING 1 WARD RENOVATIONS

Sheet Number 113of

1-G204W

ICRA & PHASING - 3RD & 4TH FLOOR

- WEST & CENTRAL

Checker Author

630-18-101

February 12, 2021 5

SCALE: 1/16" = 1'-0"

F4

ICRA & PHASING PLAN 4TH FLOOR

SCALE: 1/16" = 1'-0"

F6

ICRA & PHASING PLAN 3RD FLOOR

SCALE: 3/32" = 1'-0"

F1

ICRA & PHASING PLAN 4TH FLOOR - PHASE 1

SCALE: 3/32" = 1'-0"

C1

ICRA & PHASING PLAN 4TH FLOOR - PHASE 2

SCALE: 3/32" = 1'-0"

A4

ICRA & PHASING PLAN 4TH FLOOR - PHASE 3

0 16' 32'0 16' 32'0 21'-4"10'-8"

0 21'-4"10'-8"

0 21'-4"10'-8"

ADDENDUM 01 1 02/12/2021

PULL

PULL

2' -1

0"3' -6

2' -2

2'

-2

2' -4

6"

9" 1'-1"

PAPER

TOWEL

DISPENSER

SOAP

DISPENSER

FULL

LENGTH

MIRROR

ACCESSIBLE

COAT HOOK

COAT

HOOK

SOAP

DISPENSER

NOTE: ALL DIMENSIONS INCLUDE ALL OPERABLE LEVERS.

DIGITAL

CLOCK

SHARPS

RECEPTACLE

PAPER TOWEL

DISPENSER

GLOVE BOX

HOLDER

CLINICAL

SERVICE

SINK

DIAGNOSTIC

SET

HAND

SANITIZER

NOTE: LIGHT SWITCH ALWAYS LOCATED ON SIDE CLOSER TO ROOM ENTRY DOOR.

CL

1'-6" 2'-11" 1" FILLER

CL1'-6"

2' -6

2' -6

" 3' -8

4' -6

3'

-6

3' -8

9" 9"

FOOT WALL

5' -0

2' -5

1' -3

M

IN

DIAPER

CHANGING

TABLE

NAPKIN

DISPENSER

4' -0

NOTE: CONTRACTOR TO COORDINATE IN FIELD TO ASSURE THAT A 2'-0"

SPACING IS MAINTAINED BETWEEN RECEPTACLES THAT ARE BACK TO BACK

WITHIN THE SAME PARTITION AT THE SAME MOUNTING HEIGHT.

5' -6

CL

5' -0

1'

-6

TELEVISION

5' -6

CL

MIRROR

INSULATE DRAIN

AND WATER PIPES

DASHED AREA

INDICATES

ACCESSIBLE KNEE

AND TOE CLEARANCE

SPACE

WALL MOUNTED LAVATORY

8" MIN

M

IN

N O

N A

C C

E S

S

IB

L E

A C

C E

S S

IB

L E

M

A X

1'-3" MIN

TOP OF

SPOUT

EQUIPMENT

PERMITTED IN

AREA SHOWN

DASHED

ELECTRIC WATER COOLER

"4

A5145.2

18" WIDE STAINLESS

STEEL SHELF

MOP HOLDER

SERVICE

FAUCET AND

CONTROLS

MOP BASIN

HAC

5" MAX

1'-3" MIN

PAPER TOWEL DISPENSER

6" MAX

FLOOR MOUNTED TOILET WITH

RETRACTABLE GRAB BARS

GRAB BARS

(ACCESSIBLE

ONLY)

SIDE

VIEW

FRONT

VIEW

SIDE

VIEW

FRONT

VIEW

SIDE

VIEW

FRONT

VIEW

1'-6" MIN

1'-8" MAX

TOILET PAPER

DISPENSER

NOTE: ACCESSIBLE AND NON-ACCESSIBLE PLUMBING FIXTURES ARE INDICATED IN THE PLUMBING DRAWINGS.

M

IN

6" MAX8" MIN

A

C C

E S

S

IB

L E

S T

A N

D A

R D

M

IN

PERPENDICULAR WALL OR

PROJECTING ELEMENT 4" MAX PROJECTION

/4

/4

1'-8" MAX

1'-6" MIN

S

T A

N D

A R

D

A

C C

E S

S

IB

L E

GRAB BARS

TOILET PAPER

DISPENSER

WATER

CLOSET

LOW HEIGHT

FLUSH VALVE

FLOOR MOUNTED TOILET

1'-0" 6"2'-0"1'-0" 3'-6"

SIDE

VIEW

FRONT

VIEW

2' -1

0"

1'-1"

A L

IG

N

CL

4' -8

WALL MOUNTED

LIGHT FIXTURE

9" ±

M

IN

". 2' -1

0"

M

IN

1' -3

" 2' -1

0"

1' -5

7"-9". 7"-9"

1'-3"

SOAP DISPENSER

PAPER TOWEL

DISPENSER

NC

1'-8"

3' -8

NURSE CALL

SOAP DISPENSER

1'-8"EQ EQ

"5

HALL LANTERNS

RAISED

BRAILLE

CHARACTERS

ON HOISTWAY

ENTRANCES

HALL CALL

BUTTON

BULLETIN

BOARD

INTERACTIVE

WHITE BOARD

LENGTH VARIES 2

C

L E

A R

FIRE ALARM

PULL BOX

M A

X

IM

U M

FIRE

EXTINGUISHER

WALL HUNG

FIRE EXTINGUISHER

IN RECESSED

CABINET

PULL HANDLE

LINE MOUNTED AT

TOP OF BASE

FIRE ALARM

SPEAKER

7' -6

U

.O .N

ALIG

N

FIRE ALARM

COMBINATION

SPEAKER/STROBE

OR STROBE

W.1 V

VAV BOX

LOCATION

CABLE TRAY

C L E

A R

VAV BOX

LOCATION

EQ EQ

ACCESS ZONE

2'-0"

ZONE

LIGHT FIXTURE

ACCESS ZONE

2'-0"

MECHANICAL

PIPING

FIRE PROTECTION

PIPING

M

IN

ELECTRICAL

CONDUIT

SCHEDULED

CEILING FINISH

M E

P Z

O N

E

/4

V

IF

SMOKE AND ACOUSTIC

SEALANT AT ALL

PERIMTER AND

PENETRATIONS OF

CORRIDOR FACING

WALLS. (TYP)

SCHEDULED

FLOOR FINISH

SCHEDULED SMOKE

BARRIER PARTITION.

TYPICAL AT

CORRIDORS

MECHANICAL

DUCT TRUNK

TYPICAL

CORRIDOR11

F

LO

O

R T

O U

N D

E R

S

ID

E O

F D

E C

K

N O

T E

D O

T H

E R

W

IS

E

U

N L E

S S

AUDIO FIRE

ALARM ONLY

EXIT SIGN FIRE ALARM

PULL STATION

(GENERALLY

LOCATE UNDER

A/V ALARM)

W

IT

H O

W N

E R

C O

O R

D

IN

A T

E

8"

COMBINATION

POWER/SIGNAL/OUTLET

FOR WALL MOUNTED

TELEVISION OR

MONITOR

T.V./DATA/

PHONE

POWER

RECEPTACLES

LIGHT

SWITCHES

DOME

LIGHT

OCCUPANCY

SENSOR

CARD

READER

POWER

DISCONNECT

REMOTE DOOR

RELEASE

"5

M

A X

RECEPTACLES AT

TYPICAL CASEWORK

ASSEMBLY

TYPICAL

WORKSTATION

ASSEMBLY

".3

CLEAR

2'-6"

TV

D/V

TV E

E

ED/V

L L OS CR DR E

E

E

D/V

EM

T

EQ EQ

ALIGN

THERMOSTAT AT

PERIMETER CONVECTOR

POWER/DATA

RECEPTACLES AT WALL

MOUNTED COMPUTER

STATIONS

P D

AUDIO/VISUAL FIRE ALARM,

NURSE CALL, THERMOSTAT,

HAND SANITIZER, WALL

SWITCH

NOTE: DOME LIGHTS AT END OF CORRIDORS ARE CEILING MOUNTED. DOME LIGHTS OUTISDE OF PATIENT TOILETS ON 10TH FLOOR ARE WALL MOUNTED.

EQ EQ

ALIGN

1' -6

3' -6

6' -5

/2

4' -6

NC

ALIGN

6"

D O

O R

F R

A M

E 1"

A B

O V

E

EQ EQ

DOME LIGHT ABOVE

DOOR FRAME

NOTE: CONTRACTOR TO COORDINATE IN FIELD TO ASSURE THAT A 2'-0" SPACING IS MAINTAINED BETWEEN RECEPTACLES THAT ARE BACK TO BACK WITHIN THE SAME PARTITION AT THE SAME MOUNTING HEIGHT.

NEW METAL

CONVECTOR

COVER

WINDOW

NIGHT LIGHT, THERMOSTAT,

WALL SWITCH, AND FIRE

ALARM WHERE APPLICABLE

AT PATIENT BATHS, PUBLIC

TOILET, AND STAFF TOILET.

6"

1' -6

3' -6

" 4' -6

NIGHT

LIGHT

PANIC

BUTTON

NC

3' -8

NURSE CALL

PULL

STATION

NC

PULL

STATION AT

SHOWER

PULL

STATION AT

WATER

CLOSET

6' -0

1' -6

ALIGN

TT

CL

M

IN

LOCATE

SIGN ON

LATCH SIDE

OF DOOR

D

IM

E N

S

IO

N S

S E

E C

O D

E S

IG

N

A G

E

A D

A D

E T

A

IL

S F

O R

2"

WALL MOUNTED

EXIT SIGN

NOTE: REFER TO 1-AG DRAWING SERIES (WAYFINDING)

FOR ADDITIONAL INFORMATION.

TACTILE CHARACTERS

BASELINE ZONE: 48" - 60"

MIN.

9"

CL

SINGLE DOOR

POSITION ON LATCH SIDE OF DOOR OR NEAREST

ADJACENT WALL, AT A 9" MIN DISTANCE FROM THE

CNTER OF THE RAISED CHARACTERS ON THE SIGN.

EXCEPTION: PERMITTED ON THE PUSH SIDE OF DOORS

WITH CLOSERS BUT WITHOUT HOLD OPEN DEVICES.

CL

INACTIVE ACTIVE

MIN.

9"

CL

MIN.

9"

LOWEST TACTILE CHARACTER

BASELINE NOT PERMITTED BELOW

CHARACTER BASELINE ZONE

DOUBLE DOOR

POSITION ON INACTIVE DOOR LEAF. IF TWO

ACTIVE LEAFS, SIGN GOES TO RIGHT OF RIGHT

HAND DOOR. IF NO SPACE THERE, THEN ON

NEAREST ADJACENT WALL.

LOREM

IPSUM

HIGHEST TACTILE

CHARACTER BASELINE

LOWEST TACTILE

CHARACTER BASELINE

SIGN

HIGHEST TACTILE CHARACTER

BASELINE NOT PERMITTED ABOVE

CHARACTER BASELINE ZONE

VACUUM BREAKER

SHOWER SLIDE WITH

HAND HELD SHOWER

AND 60" HOSE

1'-6" 6"

RECESSED SST

SHELF

CONTROL WALL

THERMOSTATIC

MIXING VALVE

4" 1'

-6

6"

3'-0"

2' -1

0"

SIDE WALL

1'-6" 6"

2' -1

0" 5"

NOTE: SHOWER HOSE VACUUM BREAKER SHALL BE LOCATED A MINIMUM OF

6" ABOVE HAND SPRAY AT UPPERMOST POSITION ON SLIDE BAR.

NC

6"

9 1/2" 1'-5"

1'-6"

6"

9 1/2"

/4

/4

/4

" 6"

RED

WHITE TEXT

1/32" THK RAISED LASER CUT AND

APPLIED LETTERING

ROWMARK BLACK - ADA ALTERNATIVE

CLEAR RASTER BRAILLE

REDUNDANT, GRADE II

3/16" THK CLEAR NON-GLARE ACRYLIC LENS WITH

2ND SURFACE FLANGE AT TOP AND BOTTOM

1/4 W X 3/8" D FABRICATED ALUMINIUM OUTER

FRAME. SATIN ANODIZED FINISH

/4

/4

/4

2 3 4 1

1'-6"

ELEVATOR

3002.3 EMERGENY SIGNS

TOILET FACILITY

1111.1 ACCESSIBILITY SIGNAGE

BUILDING EXITING LOCATION MEANS OF EGRESS

1011 EXIT SIGNAGE

MEANS OF EGRESS

1023.9 STAIRWAY

IDENTIFICATION SIGNS

MEANS OF EGRESS

1007.9 SIGNAGE

CORRESPONDING GRADE II BRAILLE.

1/10" WITHIN CELL. 2/10" BETWEEN CELLS,

1/40" MIN. RAISE ABOVE THE

BACKGROUND. LOCATED 3/8" MIN. BELOW

TACTILE CHARACTERS

WALL MOUNTED SIGNAGE TO BE LOCATED ON LATCH SIDE

OF DOOR, CLEAR OF DOOR SWING. TACTILE CHARACTERS

SHALL BE CENTERED ON A MIN 18"X18" AREA LOCATED

OUTSIDE THE ARC SWING OF THE DOOR. BRAILLE SHALL

COMPLY WITH ADAAG 703.3.1, 703.3.2, FIGURE 703.31, AND

TABLE 703.3.1

AREA OF

RESCUE

ASSISTANCE

H

IG

H E

S T

L

IN

E O

F T

E X

T

M A

X T

O B

O T

T O

M O

F

O F

L O

W E

S T

L

IN

E O

F

M

IN

T O

B O

T T

O M

T A

C T

IL

E

C H

A R

A C

T E

R S

T A

C T

IL

E

C H

A R

A C

T E

R S

360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Revisions:

Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

Building Number

Approved:

Drawing Title Project Title

Date

Office of Construction &

Facilities Management

F

E

D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

C

B

A

Location

Checked Drawn

Drawing Number

Project Number

CONSULTANTS: ARCHITECT/ENGINEERS:

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

KEY PLAN:

VA FORM 08-6231

Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED

ASBESTOS ABATEMENT CONSULTANT:

14 HIGH STREET

MAHWAH, NEW JERSEY 07430

Tel: (914) 320-7924

Egan Environmental Consulting, Inc. 423 EAST 23RD STREET

NEW YORK, NY 10010

VA NY HARBOR HEALTHCARE SYSTEM

MANHATTAN VAMC -

BUILDING 1 WARD RENOVATIONS

Sheet Number 113of

1-A002

TYPICAL MOUNTING HEIGHTS

GV LP

630-18-101

February 12, 2021 12

SCALE: 1/4" = 1'-0"

EQUIPMENT AND ACCESSORIES

SCALE: 1/4" = 1'-0"

ACCESSORIES AND PLUMBING FIXTURES

SCALE: 1/4" = 1'-0"

ELEVATOR CONTROLS

SCALE: 1/4" = 1'-0"

VISUAL DISPLAY BOARDS

SCALE: 1/4" = 1'-0"

FIRE PROTECTION EQUIPMENT

0 4' 8'

0 4' 8'

0 4' 8'

0 4' 8' 0 4' 8'

0 4' 8'

0 4' 8'

0 4' 8'

SCALE: 1/2" = 1'-0"

TYPICAL CORRIDOR SECTION

SCALE: 1/4" = 1'-0"

ELECTRICAL CONTROL DEVICES

SCALE: 1/4" = 1'-0"

SPACE SIGNAGE

SCALE: 1/4" = 1'-0"

ACCESSIBLE SHOWERS

SCALE: 1" = 1'-0"

1-A002_3_

0 2' 4'

0 2'1'

UP

UP

UP

DN

DN

UP

18.716.816.9

A

B

C

D

E

G

F

J.2

H

J

L

N

O

Q

E.9

F.5

12.1 13 15.1 16

F5/1-A104W

W a

W a

W a

W

W

W a

W a

W a

W

W

W

W

W

W b

W b

W a .1

W

4001aW a .1

W

4002aW

4009aW

4033W

4032W

4029W

4023W 4014W

4022W 4016W

4020W 4017W

W

W

W

4202W

4021W

4030W

4031bW

4002W

4001W a

W

4031aW

EG1A

EG1E

EG1A

EG1A

EG1K

EG1A

EG1A

EG1A

EG1A

EG1E

EG1A

EG1A

EG1E

EG1A

EG1A EG1A

EG1A

EG1A

EG1A

EG1A

EG1F

EG1A

EG1D

EG1H

EG1H

EG1H

EG1G EG1H EG1H EG1H EG1H

EG1A EG1E EG1F EG1A

EG3B

EG5C

10"

6'-2 3/4"

1'-1"

6'-0 3/4" 1'-5 3/4"

HOLD

8'-0" 1'-1" 6'-8 3/4"

1'-1"

3/

4"

'-7

/4

8' -6

/4

'-6

/2

'-1

1" 8'

-3

4' -8

'-5

'-6

'-4

3"

'-9

8' -3

'-2

/2

'-0

/4

8'

-0

/4

'-9

/4

'-9

/4

8' -0

/4

'-0

/4

'-7

/4

8'

-3

'-5

/2

4STC

4013W

4STW

4015W

11a

27 2727

21a

12a

18 18

14bs

14b 11b

12a

42bs

41bs

11b 27

20 27 22

12a

11b11b

11b

11b

11b

11b11b

W 15a

11a

11a

12a

20a11b

41b

11a

41b

12a30

12a

27 21

12a

11a

12a

17a

12a

17a

12a

12a

11a

12a

12a

12a

21a

12a

11a

41bs41bs

12a

11a

12a

11a

12bs

12bs

20a

12a

21a

27 27

12 12a

12 20

F5/1-A104W

'-0

'-0

'-0

'-0

'-0

'-0

'-0

'-0

'-0

SERVICE WALL TYP.

11'-0" HOLD

1'-7 1/4" HOLD

2'-10 3/4"

8'-6 3/4"

1" 14'-5" 3'-6 3/4"

2'-1"

2'-11"

7' -1

1"

1' -1

4' -1

1"

2' -0

/2

H O

LD

8' -0

HOLD

2'-6"

6'-0" 1'-1"

8'-2" 9'-9 1/2" 18'-10"

15'-8"

HOLD

8'-0"

212121

10"

SERVICE WALL, TYP.

11'-0" 1'-7 1/4"1'-7 1/4"

SERVICE WALL, TYP.

11'-0" 7" 12'-11 3/4"

S E

R V

IC

E

W A

LL

8' -6

" 1' -7

/4

1-A607D1 1-A607 F1

1-A607 E1

BATH

4032aW

BATH

4033aW

MEDS

4028W

BATH

4029aW ANTE

4002aW

STF. TLT.

4005W

CLEAN

UTILITY

4006W

STORAGE

4007W

CLEAN

LINEN

4008W

BATH

4009aW

BATH

4011aW

DATA

4012W

PCTC

4025W

NOUR.

4024W

MED/SURG

1 BED

4023W

MED/SURG

1 BED

4014W

BATH

4022aW

BATH

4014aW

BATH

4016aW

BATH

4020aW

BATH

4018aW

BATH

4017aW

NURSE

STATION

4026W

MED/SURG

1 BED

4033W

ISO. BATH

4001bW

ANTE

4001aW

MED/SURG

ISOLATION

BED

4001W

MED/SURG

BARIATRIC

1 BED

4032W

MED/SURG

ISOLATION

BARIATRIC

BED

4002W

MED/SURG

1 BED

4029W

SOIL. UTL.

4003W

MED/SURG

1 BED

4011W

MED/SURG

1 BED

4009W

MED/SURG

1 BED

4016W

MED/SURG

1 BED

4017WMED/SURG

1 BED

4020W

MED/SURG

1 BED

4022W

MED/SURG

1 BED

4019W

ISO. BATH

4002bW

HAC

4004W

EXIST.

ELEC.CL.

4013W

EX. FEC

4015W

ELEC.

CLOSET

4030W

EQUIPMENT

ALCOVE

4201kW

ALCOVE

4201bW

FOOD

CART

ALCOVE

4010W

ELEC.

CLOSET

4031bW

BATH

4019aW

MACERATOR

ROOM

4021W

ALCOVE

4201cW

BATH

4023aW

CORRIDOR

4201W

CORRIDOR

4202W

ELEC.

CLOSET

4031aW

PATIENT

MONITORING

4026aW

1-A602 B1

1-A602 F1

EG1A

EG1A

EG1F

1-A603 B1

11a

C

H O

LD

4'

-1 0"

2"

TYP.

1'-7 1/4"

SERVICE WALL TYP.

11'-0"

H O

LD

4' -0

2' -1

T

Y P

3' -1

1"

'-6

6' -2

H

O

LD

2' -0

3'

-6

/2

'-5

/4

11b

1'-7 1/4"

12a

12a

11bs

TYP.

4'-6"

135° ALIGN

3' -0

4'-2 1/4"

1'-0"

A L

IG

N T

Y P

2' -1

S E

R V

IC

E

W A

LL

'-0

21a

2' -0

ALIGN

1' -3

/4

8'

-5

/4

'-0

'-7

/2

8' -3

8'

-3

/4

H O

LD

8' -0

1' -1

1"

7' -4

/2

1'-6" 3'-8 1/4"

5"A L

IG

N

3/

4"

ALIGN

7'-9 1/2" 4'-11"

2' -0

/2

2'

-6

12'-2"

1'-7 1/4" TYP.

SERVICE WALL TYP.

11'-0"

1'-1" 6'-1 1/2"

1'-11 1/4"

8'-0" HOLD 2'-5" 5'-9 1/2"

1'-1"

11 1/4"

SERVICE WALL TYP.

11'-0"

1'-7 1/4" TYP.

TYP.

TYP.

4'-6"

2' -1

T

Y P

.4' -7

/4

1' -4

4' -0

2'

-2

/4

2' -1

/4

2'

-6

4' -0

H

O

LD

1'-6 1/2"

5'-4 1/2" 1'-10"

8'-6"

1' -6

2'

-3

/4

3' -8

T

Y P

2' -8

/2

4'

-1

ALIGN

TYP.

2 222

10.2

10.1

10.1

10.1

10.1

10.1

1-A604

E7

1-A602 D1

1-A603 E1

1-A603 F1

11c

1'-7 1/4" HOLD

SERVICE WALL TYP.

11'-0" HOLD

1' -2

4'

-8

/4

2'-5" 4'-6"

A L

IG

N

T Y

P

27a

A L

IG

N

T Y

P

ALIGN

10"

3' -1

1"

2' -6

/2

3'-10"

10'-1 1/4"

41bs

CONNECTION

TO OR'S

(BUILDING 6)

OPEN TO

BELOW

A L

IG

N T

Y P

SERVICE WALL TYP.

11'-0" 1'-7 1/4"

1'-1"

6'-3 3/4"

11"

1-A801 F6

SIM

12a

11a

4011aW

TYP.

TYP.

TYP.

TYP.

TYP.

1-A606 E1

A L

IG

N

2'-1"

EG1A

1-A801 F8

1-A801 F8

1-A801 F8

1' -7

1-A605 F1

1-A606

F1

CRASH

CART

ALCOVE

4201mW

1' -4

/4

4'

-0

MED/SURG

1 BED

4018W

ALCOVE

4201aW

ALCOVE

4201jW

ALCOVE

4201dW

ALCOVE

4201eWALCOVE

4201hW

DAY

LOUNGE

4201fW

4019W 4018W

12a

12a

12 21

12a

21a

12a 12a

12a

27a

12a12a

12a

12211221a

27 27

12 21 12 21

12211220 a

W a

W a

W a

W

4 STAIR

WEST

4STW

4 STAIR

CENTER

4STC

2' -1

T

Y P

. 9' -3

/4

5'

-1

1/ 2"

ALIGN

10"

1'-9 1/4" 1'-1" 6'-1 1/2"

1'-1 1/4"

1'-4" 5'-9 1/2" 1'-1"

1'-10 1/2"

3' -6

/2

"1 '-4

ALIGN

1' -0

1' -0

10.1 10.1

10.1

10.110.1

10.110.1

10.110.1

TYP

CORRIDOR

4200aW

1-A607C1 F1

14 18 2012.8 15.2

18.716.8

17.1

16.9

16.2

O

Q

R

S S.1

T

U.6

15.3

U.1

W.1

18.1

12.1

12.1

13 15.1 16

V

1-A606

F4

.1 C

C

4076bC

4079C

4076aC

C

C

C

4034W

4051C

4052C

EG1A EG1A EG1A EG1A EG1A EG1A

EG1A

EG1A

EG1A

EG1A

8' -2

/4

1'

-1

/4

4049C

C

C

.2 C

4000.1C

4203C

11bs

11b

17a

212121

11a

11a

11a

41b

40c

40c

40c

11b

11b11b

41bs

11a

10 12

12a

11a

11a

20'-0" 20'-0" 20'-0" 20'-0"

1'-5 3/4"

27'-11 1/4"

1'-4 3/4"

18'-1 3/4" 12'-6 1/2"

ALIGN

1-A607

A1

A5

SHARED

STOR.

4080C

4S

STORAGE

4075C

TEAM

ROOM

4034W

MED/SURG

1 BED

4033W

PUB. TLT.

4037C

EXIST. IT

CLOSET

4052C

DAY

RM./FAMILY

LOUNGE

4035C

EXIST. FHC

4053C

EX. ELEC.

CLOS.

4049C

EXIST.

DISTRIBUTION

4127C

ELEVATOR

LOBBY

4000C

STORAGE

4036C

SERVICE

ELEVATOR

LOBBY

4076C

CORRIDOR

4208C

CORRIDOR

4200C

CENTRAL

COR. B

4203C

STAFF

LOUNGE

4079aC

EXIST. IT

CLOSET

4051C

F1/1-A104W

1-A604 E1

A L

IG

N T

Y P

2' -4

5'

-9

2' -7

/2

H O

LD

8' -0

ALIGN

21a

TYP.

TYP.

9 ALIGN

A L

IG

N

2' -7

/2

H

O

LD

8' -0

3'-1 1/2" 7'-9 1/4" 12'-11 3/4"

HOLD

6'-0"

3'-3 1/2"

HOLD

3'-6"

11bs

3'-5 1/2"

ALIGN

8'-7 1/4"

HOLD

8'-0"

12a

ALIGN

4'-7" 8'-0" HOLD

1'-9 1/4"

20a

1-A606 D1

4'-8 1/2"

1'-6" MIN.

41b

40c

X.1

1-A801 F6

SIM

CONNECTION TO OR'S

(BUILDING 6)

1-A604 C1

C

4'-0"

8" 7'

-4

EQ 5'-0" EQ

1' -6

/4

8'

-0

M

IN

4STC

1-A801 F2

SIM

1-A801 B1

SIM

AREA OF 4S IS NOT IN

CANNONDESIGNS SCOPE OF

SERVICES. GRAPHICS INDICATED

REFLECT THE PROPOSED

DESIGN BY OTHERS AT THE TIME

OF DOCUMENT PRODUCTION.

ACTUAL SCOPE MAY VARY

PENDING CONSTRUCTION

COMPLETION. COORDINATE 4S

SCOPE TIE-IN WITH OWNER.

AREA OF 4N IS NOT IN CANNONDESIGNS

SCOPE OF SERVICES. GRAPHICS

INDICATED REFLECT THE PROPOSED

DESIGN BY OTHERS AT THE TIME OF

DOCUMENT PRODUCTION. ACTUAL SCOPE

MAY VARY PENDING CONSTRUCTION

COMPLETION. COORDINATE 4N SCOPE TIE-

IN WITH OWNER.

F1/1-A104W

1-A607C1 F1

1. ALL DIMENSIONS ARE TO FINISHED FACE OF PARTITION UNLESS

NOTED OTHERWISE.

2. ALL DIMENSIONS SHOWN IN RENOVATED AREAS ARE TO BE

VERIFIED IN THE FIELD BEFORE PROCEEDING WITH WORK.

3. WHERE A FIXED RATED PARTITION IS SHOWN ABUTTING

EXTERIOR WALLS, THE FIRE RATED ASSEMBLY IS TO EXTEND TO

THE EXTERIOR WALL CONSTRUCTION.

4. IN ALL ROOMS BELOW AREAS WHICH RECEIVE UNDER FLOOR

SERVICES, REMOVE A PORTION OF EXISTING CEILING AS

REQUIRED. PATCH FINISHES TO MATCH EXISTING OR AS

INDICATED ON ROOM FINISH SCHEDULE.

5. REFER TO M.E.P. DRAWINGS FOR EXISTING AND NEW FIXTURES

AND SERVICES TO BE REMOVED AND/OR INSTALLED. EXISTING

FINISHES DISTURBED BY THIS WORK SHALL BE PATCHED TO

MATCH ADJACENT UNDISTURBED FINISHES.

6. WHENEVER EXISTING EQUIPMENT, PIPING, DUCTS, ETC ARE

REQUIRED TO BE REMOVED, SUCH REMOVAL SHALL INCLUDE ALL

ANCHORS, HANGERS, ETC. AFTER REMOVAL, FLOORS, WALLS

AND CELINGS SHALL BE FINISHED TO MATCH ADJOINING

SURFACES OR AS INDICATED ON ROOM FINISH SCHEDULE.

7. ALL PENETRATIONS THROUGH NEW & EXISTING RATED

CONSTRUCTION TO BE FIRESTOPPED W/ U.L. APPROVED

SYSTEMS. FIRESTOP AT ALL OPENINGS RESULTING FROM THE

RENOVATIONS OF EXISTING M.E.P. SYSTEMS. SEE M.E.P.

DRAWINGS TO DETERMINE FULL SCOPE OF WORK. REFER TO

E8/1-A1002 FOR DETAILS AND SCHEDULE OF THROUGH

PENETRATION FIRESTOPPING REQUIREMENTS. CONTRACTOR TO

MAINTAIN THE INTEGRITY OF THE RATED ASSEMBLY AT ALL

PENETRATIONS.

8. PATIENT BEDS ARE SHOWN IN PLAN FOR REFERENCE. REFER

TO '1-A1200' DRAWING SERIES FOR FURNITURE AND '1-Q104W'

DRAWING SERIES FOR EQUIPMENT PLANS FOR REFERENCE AND

COORDINATION. PROVIDE BLOCKING AT ALL EQUIPMENT AND

ACCESSORIES, REFER TO DETAIL E8/1-A901.

9. PROVIDE PARTITION TYPE 32 AT THE INTERIOR FACE OF WALL

ALONG THE PERIMETER U.O.N. SPRAY FOAM INSULATION TO BE

APPLIED ALONG EXTERIOR PERIMETER IN LINE WITH DETAILS IN

1-A400 SERIES.

10. FLOAT ENTIRE SLAB WITH HYDRAULIC CEMENT

UNDERLAYMENT. PROVIDE BONDING AGENT. REFER TO

SPECIFICATION SECTION 03 54 16 FOR ADDITIONAL INFORMATION.

11. PROVIDE ALL NEW EXTERIOR WINDOWS, HEAD/JAMB/SILL

RECEIVERS, TRIM, HARDWARE, INTEGRAL SHADES, OPERATORS,

INSECT SCREENS, ETC. REFER TO WINDOW SCHEDULES,

SECTIONS, DETAILS AND RELATED SPECIFICATIONS FOR

ADDITIONAL INFORMATION. CONTRACTOR IS TO FIELD VERIFY ALL

EXISTING CONDITIONS INCLUDING WINDOW SIZES, QUANTITY,

ETC. PROTECT ALL EXTERIOR WALL OPENINGS AND ADJACENT

CONDITIONS INCLUDING ORIGINAL STEEL WINDOW FRAMES TO

REMAIN, MASONRY, FLASHING, SEALANT ETC. PATCH, INFILL,

REPAIR, AND RESECURE EXISTING MATERIALS AND

ATTACHMENTS IN KIND AND AS REQUIRED FOR NEW WORK.

12. REFER TO SPECIFICATION SECTION 13 05 41 AND SEISMIC

DESIGN PARAMETERS LISTED IN STRUCTURAL DRAWINGS FOR

ALL SEISMIC BRACING REQUIREMENTS.

13. ALL LOOSE EXISTING CONCRETE MATERIAL AROUND BEAMS

AND/OR COLUMNS TO BE REMOVED TO EXPOSE BARE

STRUCTURAL STEEL. PREPARE STRUCTURAL STEEL TO RECEIVE

AND APPLY FIREPROOFING. ALL CRACKS TO BE FILLED WITH NON-

SHRINK GROUT.

14. REPAIR UNDERSIDE OF EXISTING CONCRETE SLAB WHERE

REQUIRED. REFER TO DRAWING 1-S001 FOR ADDITIONAL

INFORMATION.

15. PROVIDE SOLID SURFACE SILL AT ALL NEW WINDOWS. REFER

TO DRAWING 1-A400 FOR ADDITIONAL INFORMATION.

16. PROVIDE PERMANENT SIGNAGE ABOVE ALL SMOKE BARRIERS

AND RATED PARTITIONS TO COMPLY WITH 2012 IBC 703.7.

17. CONTRACTOR IS TO REVIEW AND FIELD VERIFY ALL

DIMENSIONS AND CONDITIONS RELATING TO THE EXISTING

BUILDINGS THAT INTERFACE WITH THE NEW CONSTRUCTION.

PRIOR TO COMMENCEMENT OF SCOPE OF WORK NOTIFY THE

ARCHITECT OF RECORD AND OWNERS REPRESENTATIVE WHEN

EXISTING CONDITIONS VARY FROM THE CONSTRUCTION

DOCUMENTS.

18. DIMENSIONS ALONG EXTERIOR WALL ARE ANCHORED TO GRID

LINES, U.O.N.

19. REFER TO 1-H SERIES FOR ADDITIONAL ASBESTOS

ABATEMENT REQUIREMENTS PRIOR TO COMMENCEMENT OF

WORK.

20. ALL CABINETRY WITHIN PATIENT SPACES, OTHER THAN THE

PATIENT WARDROBE, SHALL BE LOCKABLE WITH STAINLESS

STEEL CAM LOCK.

DRAWING SERIES ORGANIZATION FOLLOWS THE ORDER NOTED

BELOW. SEE DETAILED DRAWING INDEX FOR DETAILED LIST.

A100'S - ARCHITECTURAL PLANS

A200'S - VOID

A300'S - VOID

A400'S - EXTERIOR SECTION DETAILS

A500'S - VOID

A600'S - INTERIOR ENLARGED PLANS AND ELEVATIONS

A700'S - REFLECTED CEILING PLANS AND DETAILS

A800'S - INTERIOR DETAILS

A900'S - MILLWORK

A1000'S - PARTITION TYPES, OPENING SCHEDULES AND DETAILS

A1100'S - VOID

A1200'S - FINISH LEGEND AND PLANS

A1300'S - SIGNAGE AND WAYFINDING

A1400'S - FURNISHINGS

ALTERNATE #1

ALTERNATE #2

4000C, 4034C, 4035C, 4036C, 4037C, 4049C, 4051C,4052C, 4200C, 4203C, 4204C, 4208C

4075C, 4076C, 4079C, 4080C

CONSTRUCTION PLAN LEGEND

EXISTING CONDITIONS REMAIN

NEW CONSTRUCTION

EXISTING WINDOW ASSEMBLY TO REMAIN

GENERAL CONSTRUCTION NOTES

NEW DOOR ASSEMBLY

EXISTING DOOR ASSEMBLY TO REMAIN

MATCH LINE

CURTAIN TRACK (CEILING MOUNTED)

F1/1-AXXXX-X

F1/1-AXXXX-X

PATIENT LIFT TRACK (CEILING MOUNTED)

NEW WINDOW ASSEMBLY

DEDUCT ALT #1 - SERVICE CORE SCOPE REMOVAL.

REFER TO SPEC SECTION 012300 ALTERNATES

DEDUCT ALT #2 - CENTRAL CORE SCOPE REMOVAL.

REFER TO SPEC SECTION 012300 ALTERNATES

PROVIDE AUTOMATIC DOOR OPENER. REFER TO 1-A600

DRAWING SERIES, AND ELECTRICAL AND

TELECOMMUNICATION DRAWINGS FOR ADDITIONAL

INFORMATION.

PROVIDE NEW EXPANSION JOINT COVER AT FLOOR, WALLS,

AND CEILING. REFER TO DETAILS B2/1-A801 & C2/1-A801 FOR

ADDITIONAL INFORMATION.

PROVIDE NEW FIRE EXTINGUISHER BRACKET WITHIN

EXISTING FIRE HOSE CLOSET.

PROVIDE NEW METAL LOCKERS. REFER TO SPECIFICATION

SECTION 10 51 13 FOR ADDITIONAL INFORMATION.

SECURE STAIR DURING CONSTRUCTION. PROVIDE

TEMPORARY LOCK TO RESTRICT RE-ENTRY INTO THE UNIT,

BUT PROVIDE FREE EGRESS INTO THE STAIRWELL.

PROVIDE RATED SHAFTWALLWITHIN EXISTING STEEL

WINDOW SURROUND, AS SHOWN IN DETAIL F8/1-A452.

PROVIDE PEDESTRIAN PROTECTION SCAFFOLDING BELOW

DURING WINDOW REPLACEMENT. COORDINATE EXTENT

WITH VA PROJECT TEAM.

SPECIFIC CONSTRUCTION NOTES

PROVIDE AND INSTALL EXTENSION BACK BOXES FOR ALL

ELEVATOR CALL BUTTON ASSEMBLIES AND CALL LIGHTS,

AND EXTEND CONDUIT AND POWER TO BE FLUSH WITH NEW

FACE OF ELEVATOR WALL. REFER TO SHEET 1-A803 AND

ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.

PROVIDE NEW CONVECTOR ENCLOSURE.

NEW RATED WALL ACCESS PANEL. MATCH RATING OF

EXISTING WALL.

NEW DRINKING FOUNTAIN. REFER TO PLUMBING DRAWINGS

FOR ADDITIONAL INFORMATION.

EXISTING NOTIFIER FIRE ALARM CONTROL PANEL AND

WIREWAY TO REMAIN AND BE ACCESSIBLE. REFER TO

DRAWING 1-A803 AND ELECTRICAL DRAWINGS FOR

ADDITIONAL INFORMATION.

INFILL EXISTING SHAFT. REFER TO DETAIL B8/1-S001.

PAINT ALL EXPOSED PIPING WITH NEW COAT OF PAINT TO

MATCH EXISTING. SPRINKLER PIPING TO BE PAINTED RED.

PROVIDE NEW SKIM COAT OF SETTING TYPE JOINT

COMPOUND ALONG EXISTING WALL.

NEW FIN TUBE ENCLOSURE. REFER TO DETAIL E6/1-A451.

PROVIDE NEW PREFABRICATED PATIENT BED SERVICE WALL

TYPE 1A. REFER TO D6/1-A601 AND SPECIFICATION SECTION

10 25 13 FOR ADDITIONAL INFORMATION.

PROVIDE NEW PREFABRICATED PATIENT BED SERVICE WALL

TYPE 1B. REFER TO F6/1-A601 AND SPECIFICATION SECTION

10 25 13 FOR ADDITIONAL INFORMATION.

PROVIDE ACCESS PANEL IN NEW PARTITION FOR EXISTING

ELECTRICAL SERVICES. REFER TO ELECTRICAL DWGS FOR

ADDITIONAL INFORMATION. COORDINATE EXACT SIZE/

LOCATION WITH EXISTING EQUIPMENT.

PATIENT LIFT CABINET PROVIDED AS PART OF

PREFABRICATED PATIENT BED SERVICE WALL. REFER TO

'1-A601' DRAWING SERIES AND SPECIFICATION SECTION 10

25 13 FOR ADDITIONAL INFORMATION.

REFER TO M.E.P. DWGS FOR ADDITIONAL SCOPE OF WORK

IN THIS AREA. PATCH AND REPAIR EXISTING FINISHES TO

ACCOMMODATE INFRASTRUCTURE SCOPE.

10.1

10.2

WEST

SOUTH NORTH

360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Revisions:

Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

Building Number

Approved:

Drawing Title Project Title

Date

Office of Construction &

Facilities Management

F

E

D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

C

B

A

Location

Checked Drawn

Drawing Number

Project Number

CONSULTANTS: ARCHITECT/ENGINEERS:

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

KEY PLAN:

NTS

VA FORM 08-6231

Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered

ASBESTOS ABATEMENT CONSULTANT:

14 HIGH STREET

MAHWAH, NEW JERSEY 07430

Tel: (914) 320-7924

Egan Environmental Consulting, Inc.

Scale: 1/8" = 1'-0"

PARTITION FIRE RATING LEGEND

1 HOUR FIRE

1 HOUR FIRE /

SMOKE BARRIER

423 EAST 23RD STREET

NEW YORK, NY 10010

VA NY HARBOR HEALTHCARE SYSTEM

MANHATTAN VAMC -

BUILDING 1 WARD RENOVATIONS

Area Not in Scope =

45 MIN. RATED DOOR

ASSEMBLY, TYP.

20 MIN. RATED DOOR

ASSEMBLY, TYP.

2 HOUR FIRE

90 MIN. RATED DOOR

ASSEMBLY, TYP.

2 HOUR FIRE /

SMOKE

BARRIER

90 MIN. RATED DOOR

ASSEMBLY, TYP.

Sheet Number 113of

1-A104W

ARCHITECTURAL PLAN 4TH FLOOR -

WEST & CENTRAL

AH/JKC CJO

630-18-101

February 12, 2021 13

0 8' 16'SCALE: 1/8" = 1'-0"

F1

ARCHITECTURAL PLAN 4TH FLOOR - WEST

SCALE: 1/8" = 1'-0"

F5

ARCHITECTURAL PLAN 4TH FLOOR - CENTRAL

0 8' 16'

ADDENDUM 01 1 02/12/2021

R.O.

+/- 7'-1"

R .O

- 6

'-9

2' -3

- 6

2' -9

9' -6

RELOCATE STEEL CHANNELS AS REQUIRED

TO ACCOMMODATE NEW HEATING UNIT, MAINTAIN

CHANNELS FOR SILL SUPPORT

EXISTING ORIGINAL STEEL WINDOW FRAME/ STEEL

SURROUND AND STEEL CHANNEL

ASSEMBLY TO REMAIN

EXTENT OF WINDOW REMOVAL, SEE DEMO DETAIL FOR ADDITIONAL INFO.

NEW DEMO

NOTE: VIEW SHOWN IS TYPICAL FROM THE INTERIOR AND

NEGATES EXISTING FINISHES AND RADIATOR COVER TO BE

REMOVED FOR DIAGRAMMATIC PURPOSES. SEE FLOOR

PLANS AND SCHEDULES FOR ADDITIONAL INFORMATION.

LOCATION/ CONFIGURATION OF PROPOSED

METAL RADIATOR COVERCOORD WITH MECH

+/- 4'-0"

LOCATION/ OF PROPOSED RADIATOR

B6

1-A451

OPH

SCOPE OF WORK AT EXISTING ORIGINAL WINDOW FRAMES AND STEEL SURROUND TO REMAIN:

- PATCH, INFILL, AND REPAIR EXISTING MASONRY WALL CONSTRUCTION IN KIND - AS REQUIRED

TO MAKE READY FOR NEW WORK. SEE SECTION AND WINDOW DETAILS FOR ADDITIONAL INFO.

-REINFORCE, RE-ATTACH, OR REPLACE DETERIORATED STEEL TABS, CLIPS, ANGLES, AND

ANCHORS FOR STEEL WINDOW FRAMES IN KIND - AS REQUIRED TO MAKE READY FOR NEW

WORK.

+/- 8"

- 5

+/- 8"

F1

1-A451

F5

1-A451

SCOPE OF WORK FOR EXISTING ORIGINAL STEEL WINDOW MULLION/ SUPPORT MEMBER TO REMAIN:

-REINFORCE, RE-ATTACH, AND REPLACE DETERIORATED STEEL CLIPS, ANGLES, AND ANCHORS FOR STEEL MULLION IN KIND - AS REQUIRED TO MAKE READY FOR NEW WORK. SEE TYPICAL WINDOW CENTER MULLION DETAIL FOR ADDITIONAL INFO. INCLUDE (1) 2X6 INTERMEDIATE VERTICAL MULLION

(ALUMINUM TUBE, 6063-75 MATERIAL MIN.)

F8

1-A451

1'-4 3/4" +/-

CL

+/- 1'-3 1/2"

+/- 1'-3 1/2"

HEAD

JAMB

SILL

- 2

'-8

/4

- 6

- 5

- 1

/2

- 2

'-6

- 2

/4

3"

E X

IS

TI

N G

M .O

- 7

'-0

- 1

/2

REMOVE ALUMINUM WINDOW

SYSTEM AND ASSOCIATED

EXTERIOR AND INTERIOR TRIM,

INCLUDING ATTACHMENTS,

CAULKING, BACKER ROD, ETC.

EXISTING ORIGINAL STEEL

WINDOW FRAME/ STOOL

ASSEMBLY TO REMAIN

EXISTING MASONRY

WALL CONSTRUCTION

EXISTING ALCOA SILL

TO REMAIN, REMOVE

ALL CAULK, CLEAN

AND PREP FOR NEW

WORK

REMOVE CEILING SYSTEM,

SUPPORTS AND

ATTACHMENTS IN ITS

ENTIRETY

R .O

REMOVE EXISTING

RADIATOR COVER AND

ATTACHEMENTS AS

REQUIRED FOR NEW

WORK

SILL BELOW TO REMAIN

EXISTING ORIGINAL STEEL

WINDOW FRAME AND STEEL

CHANNEL FRAMING ASSEMBLY TO

REMAIN

EXISTING ORIGINAL STEEL

WINDOW FRAME AND STEEL

CHANNEL FRAMING ASSEMBLY TO

REMAIN

REMOVE ALUMINUM WINDOW

SYSTEM AND ASSOCIATED

EXTERIOR AND INTERIOR TRIM,

INCLUDING ATTACHMENTS,

CAULKING, BACKER ROD, ETC.

+/- 9 1/2"

1'-4 3/4" +/-

+/- 1'-3 1/2"

+/- 1'-3 1/2"

HEAD

- 5

WORK POINT

GWB AT JAMB BEYOND

REFER TO REFLECTED CEILING

PLANS AND DETAILS FOR

CEILING/ SOFFIT CONFIGURATION

2 1/2" METAL STUD FURRING AT

16" O.C., MECHANICALLY

FASTENED TO EXISTING STEEL

WINDOW SURROUND TO REMAIN

INFILL STUDS WITH 1 1/2" SPRAY FOAM

INSULATION, INSTALL CONTINUOUS 1" SPRAY

FOAM INSULATION BEHIND FURRING, TOTAL

= 2 1/2" SPRAY FOAM INSUALTION

4" SPRAY FOAM INSULATION

SCHEDULED BASE

GWB WITH 1 5/8" METAL STUD

FURRING, 16" O.C., INSTALL STUDS

1" MIN. FROM EXISTING MASONRY

EXTERIOR WALL

EXISTING

MASONRY WALL

CONSTRUCTION

EXISTING ORIGINAL GROUTED STEEL

WINDOW FRAME/ SURROUND ASSEMBLY AND

ATTACHMENTS TO REMAIN

NOTE:

CONTRACTOR IS RESPONSIBLE TO INFILL,

REPAIR, REPLACE, OR RE-ATTACH

MATERIALS AS REQUIRED FOR NEW WORK.

SEE DETAIL B1 THIS SHEET FOR ADDITIONAL

INFO.

FACE OF EXISTING WALL

1/ 2"

S E

E S

C H

E D

U

LE

W

IN

D O

W

- 3

S E

E S

C H

E D

U

LE

R O

U G

H O

P E

N

IN

G

1/

2" 2'

-6 " 2' -9

/2

5/8" GWB TO DECK ABOVE, SPACKLED AND SANDED

3/ 4"

1/ 4"

PAINT EXPOSED JOINT

CONT 'J' BEAD

EXISTING ORIGINAL GROUTED STEEL WINDOW

FRAME/ SURROUND ASSEMBLY AND

ATTACHMENTS TO REMAIN

NOTE:

CONTRACTOR IS RESPONSIBLE TO INFILL,

REPAIR, REPLACE, OR RE-ATTACH MATERIALS

AS REQUIRED FOR NEW WORK. SEE DETAIL

B1 THIS SHEET FOR ADDITIONAL INFO.

EXISTING ORIGINAL GROUTED STEEL WINDOW

FRAME/ SURROUND ASSEMBLY AND

ATTACHMENTS TO REMAIN

NOTE:

CONTRACTOR IS RESPONSIBLE TO LEVEL, INFILL,

REPAIR, REPLACE, OR RE-ATTACH MATERIALS

AS REQUIRED FOR NEW WORK. SEE DETAIL B1

THIS SHEET FOR ADDITIONAL INFO.

EXISTING CONCRETE

CURB

SILL

FIRESTOPPING

2 1/2" SPRAY FOAM INSULATION

WOOD BLOCKING

GWB, PTD.

5/8" GWB, SPACKLED

AND SANDED

1/ 2"

3 1/4" FROM FACE OF EXISTING STEEL SURROUND

FACE OF FURRED OUT WALL-VARIES,

REFER TO FLOOR PLANS

METAL STUD FURRING TO DECK ABOVE,

INFILL STUDS WITH 1 1/2" SPRAY FOAM

INSULATION

JAMB

SOLID SURFACE SILL WITH EASED EDGES

ON FIRE RETARDENT PLYWOOD

ALUMINUM WINDOW SYSTEM

ALUMINUM WINDOW SYSTEM

3 5/8" BATT INSULATION

3 1/4" FROM FACE OF EXIST STEEL SURROUND

3 1/4" FROM FACE OF

EXISTING STEEL SURROUND

COL

1" GAP, MIN.

1 5/8" METAL STUD FURRING AT

16" O.C., MECHANICALLY

FASTENED TO EXISTING STEEL

WINDOW SURROUND TO REMAIN

SEALANT

1" GAP

1-A453 B7

1-A453 F7

EXIST. STL CHANNEL BEYOND

EXIST.

EXTERIOR

MASONRY WALL

FACTORY PTD. MTL

RADIATOR REMOVABLE

COVER

FIN TUBE RADIATOR,

REFER TO MECH DWGS.

MTL TOE CLIP

EXIST. CONC.

OPEN BACK DESK WHERE OCCURS,

REFER TO FLOOR PLANS

SCHEDULED BASE

FIRE RETARDENT WD.

BLOCKING ON 1-5/8" MTL.

STUDS @ 16" O.C.

SEALANT

1 1/4" FLUID APPLIED THERMAL

BARRIER COATING OVER 4"

SPRAY FOAM INSULATION.

NEW WINDOW SYSTEM

NOTE: REFER TO SECTION DETAILS AND

WINDOW SCHEDULE FOR WINDOW

TYPES, DIMENSIONS, AND TYPICAL NOTES

BENT SHEET MTL SPACED

1" FROM FIN TUBE

1-5/8" MTL. STUDS

3/ 4"

1/ 4"

4" 6"

4" 6"

4"

TO FACE OF NEW WALL

1'-7 1/2"

6"

R A

D

IA

T O

R C

O V

E R

2' -0

1"

2 1/2" SPRAY FOAM INSULATION

1" 1"

B6

1-A451

/2

EXIST. STL CHANNEL TO REMAIN

EXIST. EXT MASONRY WALL

FACTORY PTD. METAL

RADIATOR REMOVABLE COVER

FIN TUBE RADIATOR,

REFER TO MECH DWGS.

PTD. FIRE RETARDANT WD.

BLOCKING AND SHIMS

5/8" GWB PTD.

1-5/8" MTL STUDS @ 16"

OC

A L

IG

N

J-BEAD

4" SPRAY FOAM INSULATION

OVER EXISTING MASONRY WALL

REFER TO SECTION VIEW, PROVIDE

SHEET METAL BETWEEN SPRAY

FOAM INSULATION AND FIN TUBE

LINE OF EXIST. CONCRETE CURB

BELOW

1. SPRAY FOAM INSULATION IS TO BE INSTALLED CONTINUOUSLY AS

INDICATED, NOT LESS THAN 2 1/2" THICK OR IN THICKNESS INDICATED

AT ALL EXTERIOR WALLS FROM FLOOR TO DECK ABOVE WITHIN

PROJECT SCOPE AREA U.N.O.

2. SPRAY FOAM INSUALTION AT ALL LOCATIONS INSTALLED IS TO BE

COMPLETELY ENCLOSED AND SEALED WITH 5/8" GYPSUM BOARD TYPE

"X", OR ALTERNATE THERMAL BARRIER APPROVED BY RE, FROM

FLOOR TO DECK ABOVE, AT AND AROUND MASONRY OPENINGS.

3. REFER TO 1-A453 FOR H/J/S DETAILS UNLESS OTHERWISE NOTED.

4. REFER TO SPECIFICATION SECTION 072129 FOR ADDITIONAL

INFORMATION ON FLUID APPLIED THERMAL BARRIERS.

GENERAL NOTES

360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Revisions:

Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

Building Number

Approved:

Drawing Title Project Title

Date

Office of Construction &

Facilities Management

F

E

D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

C

B

A

Location

Checked Drawn

Drawing Number

Project Number

CONSULTANTS: ARCHITECT/ENGINEERS:

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

KEY PLAN:

VA FORM 08-6231

Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED

ASBESTOS ABATEMENT CONSULTANT:

14 HIGH STREET

MAHWAH, NEW JERSEY 07430

Tel: (914) 320-7924

Egan Environmental Consulting, Inc. 423 EAST 23RD STREET

NEW YORK, NY 10010

VA NY HARBOR HEALTHCARE SYSTEM

MANHATTAN VAMC -

BUILDING 1 WARD RENOVATIONS

Sheet Number 113of

1-A451

EXTERIOR SECTION DETAILS

AH/GV GP

630-18-101

February 12, 2021 14

SCALE: 1/2" = 1'-0"

B1

WALL ELEVATION AT WINDOW DEMOLITION

SCALE: 1 1/2" = 1'-0"

F1

SECTION DETAIL AT TYPICAL WINDOW DEMOLITION

SCALE: 1 1/2" = 1'-0"

F5

SECTION DETAIL: AT TYPICAL WINDOW REPLACEMENT

SCALE: 1 1/2" = 1'-0"

F8

RADIATOR DETAIL - TYPICAL

SCALE: 1 1/2" = 1'-0"

B6

RADIATOR PLAN DETAIL - TYPICAL

0 2' 4'

0 8" 16" 0 8" 16" 0 8" 16"

0 8" 16"

12.8

1'-9"2'-0"3'-6"2'-0"1'-9"

11'-0"

2' -0

6"

6" 1'

-8

1' -4

6"

1' -6

EQEQ

2' -0

2'

-0

6"

T O

T O

P O

F E

Q U

IP

. R

A

IL

3' -6

NOTE: OPPOSITE HANDED ROOMS INCLUDE 4009W

8' -0

WORKSURFACE PROVIDED

AS PART OF PATIENT BED

SERVICE WALL

REVEAL

PATIENT LIFT CABINET

PROVIDED AS PART OF

PATIENT BED SERVICE WALL

EQ 6" 6" 6" EQ

9"

EQ 6" 6" 6" EQ3"

2' -3

1'

-1

3"

PATIENT LIFT TRACK

OPENING

AOVVVVOA

1'-6" 1'-9" 3'-6" 1'-9"

8'-6"

1' -6

1'

-1 0"

1' -8

6"

6" 2'

-0

EQ 5" 5" 5" EQ

2' -0

2'

-0

6"

T O

T O

P O

F E

Q U

IP

. R

A

IL

3' -6

8' -0

REVEAL

PATIENT LIFT CABINET

PROVIDED AS PART OF

PATIENT BED SERVICE WALL

WORKSURFACE PROVIDED

AS PART OF PATIENT BED

SERVICE WALL

EQ EQ

3"

EQ 5" 5" 5" EQ

2' -3

PATIENT LIFT TRACK

OPENING

AOVVVVOA

TELECOMMUNICATIONS OUTLETS, REFER TO

TELECOMMUNICATION DRAWINGS FOR ADDITIONAL

INFORMATION

1. PATIENT BED SERVICE WALLS TO BE PREFABRICATED

MODULAR UNITS; COORDINATE INSTALLATION WITH

MANUFACTURER. CONTRACTOR TO COORDINATE ALL

WALL MOUNTED EQUIPMENT AT PATIENT BED SERVICE

WALL. REFER TO 1-A1200 SERIES FOR FINISH

INFORMATION. REFER TO CONSTRUCTION PLANS AND

SPECIFICATION SECTION 10 25 13 FOR ADDITIONAL

INFORMATION.

2. REFER TO 1-A1400 SERIES FOR FURNITURE PLANS.

3. A5145 GARMENT HOOKS ARE TO BE INSTALLED

CENTERED ON DOORS WITHIN ALL TOILET AND BATH

ROOMS, AS WELL AS IN PCTC ROOMS.

4. REFER TO SHEET 1-A002 FOR ALL TYPICAL MOUNTING

HEIGHTS.

5. A5135 STAINLESS STEEL SHELF, 18" WIDE, AND MOP

HOLDER RACK IS TO BE INSTALLED WITHIN ALL

HOUSEKEEPING AIDE CLOSETS (HAC). INSTALL

ADJACENT TO MOP SINK.

6. REFER TO 1-A700 DRAWING SERIES FOR REFLECTED

CEILING PLAN LEGENDS.

7. REFER TO FINISH LEGEND 1-A1200 SERIES FOR

ABBREVIATIONS OF FINISHES.

8. REFER TO SHEET 1-Q001 FOR EQUIPMENT LIST AND

THE 1-Q100 SERIES FOR EQUIPMENT PLANS.

GENERAL CONSTRUCTION NOTES

PATIENT BED SERVICE WALL

ELEVATION LEGEND

ELECTRICAL OUTLETS, REFER TO ELECTRICAL

DRAWINGS FOR ADDITIONAL INFORMATION

OXYGEN MEDICAL GAS OUTLET, REFER TO PLUMBING

DRAWINGS FOR ADDITIONAL INFORMATION

O

VACUUM OUTLET, REFER TO PLUMBING DRAWINGS

FOR ADDITIONAL INFORMATION

V

MEDICAL AIR OUTLET, REFER TO PLUMBING DRAWINGS

FOR ADDITIONAL INFORMATION

A

VACUUM SLIDE

DIALYSIS UNIT

MONITOR RAIL

AUDIO STATION BED CONNECTOR

EQUIPMENT RAIL

ELECTRICAL SWITCH REFER TO ELECTRICAL

DRAWINGS…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .