02 VAMC_4W MED SURG_STRUCT DWGS_ADD 01.pdf
PDF 174 KB Posted
- Solicitation number
- 36C24221B0001
About this file
This document package includes structural drawings and notes for renovations to a patient ward at a Veterans Affairs medical center, as well as details for the related federal contract opportunity.
The structural drawings detail revisions to an existing concrete floor slab, including infill of existing openings, underside repairs, and support frame connections. Notes provide specifications for structural concrete, steel, and decking work. The project involves renovating Ward 4W at the VA New York Harbor Healthcare System Manhattan VAMC to create a step-down unit. The solicitation was issued under contract number 36C24221B0001 by the Department of Veterans Affairs Veterans Health Administration VISN 2 for structural work required to complete the ward renovations. No other details are provided on procurement requirements, pricing, or response deadlines.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
6x6-W2.1xW2.1 WWF
L4x3x3/8 (LLV)
W/ 1/2" Ø KWIK HUS EZ
ANCHORS BY HILTI @ 12" OC
4 1/4" EMBED (TYP ALL SIDES)
2"-18 GA GALV (G60)
COMPOSITE STEEL DECK
W/ NORMAL WEIGHT
CONCRETE FILL
EXISTING
SLAB
/2
M
IN
M
IN
5'-0" MAX
M
IN
5/8"Ø
TYP
GENERAL NOTE:
1. ALL INFILL AND ASSOCIATED STEEL TO RECEIVE 2-HOUR SPRAY
FIREPROOFING. PATCH AND REPAIR EXISTING FIREPROOFING TO MAINTAIN
REQUIRED RATING.
2. PROVIDE AN ALLOWANCE FOR A 4'x4' OPENING AT 3 LOCATIONS. ACTUAL
LOCATION AND SIZE TO BE DETERMINED AFTER DEMOLITION.
@12"
CL
CL
CL
E Q
E Q
C8x11.5 C x .5
SEE NOTE 7
10'-0" MAX
C8
1-S001
SEE NOTE 6
MIN
1'-0"
AREA OF REPAIR
SEE NOTES
NOTES:
DETAIL APPLIES TO AREAS WHERE THE CONCRETE FLOOR SLAB HAS SPALLED AND THE
REINFORCEMENT IS EXPOSED.
1. PROVIDE THE STEEL FRAMING AND 60 SQ-FT OF PATCHING MORTAR IN THIS DETAIL AT 3
LOCATIONS.
2. PROVIDE 5 LOCATIONS OF 60 SQ-FT OF PATCHING WITHOUT STEEL FRAME
LOCATIONS OF REPAIRS WILL BE DETERMINED DURING CONSTRUCTION BASED ON THE
DOCUMENTATION PROVIDED BY THE CONTRACTOR.
DOCUMENTATION
1. CONTRACTOR IS TO DOCUMENT ALL AREAS WHERE REINFORCEMENT IS EXPOSED. PROVIDE
PHOTOS AND PLANS OF AREAS THAT REQUIRE REPAIR WITH SUPPORT STEEL INDICATED. DO
NOT PROCEED WITH THE REPAIR UNTIL THE DOCUMENTATION HAS BEEN REVIEWED BY THE
STRUCTURAL ENGINEER.
2.
REPAIR
1. DO NOT CUT ANY EXISTING REINFORCEMENT.
2. REMOVE LOOSE MATERIAL WITH HAND TOOLS.
3. APPLY BONDING AGENT TO UNDERSIDE AREA OF REPAIR AND 6" BEYOND.
4. APPLY REPAIR MORTAR TO AREA OF REPAIR AND 6" BEYOND. MORTAR THICKNESS SHOULD
EXTEND 1/2" BELOW THE BOTTOM OF SLAB.
5. INSTALL BONDING AGENT AND REPAIR MORTAR, DO NOT EXCEED ALLOWABLE MORTAR
THICKNESS FOR ANY SINGLE LAYER. IN ACCORDANCE WITH THE MANUFACTURER
REQUIREMENTS.
6. SET CHANNEL 1" BELOW UNDERSIDE OF EXISTING SLAB. GROUT SPACE BETWEEN CHANNEL
AND SLAB SOLID.
7. PROVIDE ADDITIONAL C8x11.5 WHEN DIMENSION EXCEEDS 10'-0".
EXISTING CONCRETE ENCASED STEEL BEAM
T/SLAB
WF OR CHANNEL
3/8" SHEAR TAB W/
(2) 3/4"Ø A325 BOLTS
1/4"
1/4"
NOTE:
ALL NEW STEEL AND EXPOSED EXISTING STEEL
IS TO BE 2-HOUR SPRAY FIREPROOFED.
PACK WITH
NON-SHRINK
GROUT
BUILDING CODE: 2012 INTERNATIONAL BUILDING CODE
OCCUPANCY CATEGORY: IV
EARTHQUAKE DESIGN DATA:
PER DEPARTMENT OF VETERANS AFFAIRS - SEISMIC DESIGN REQUIREMENTS H-18-8
1. SEISMIC IMPORTANCE FACTOR: I = 1.50
2. SPECTRAL RESPONSE ACCELERATIONS:
Ss = 0.361 S1 = 0.070
3. SITE CLASSIFICATION: D (ASSUMED)
4. DESIGN SPECTRAL RESPONSE ACCELERATIONS:
SDS = 0.364
SD1 = 0.112
5. SEISMIC DESIGN CATEGORY: D
SEISMIC BRACING OF ARCHITECTURAL, MECHANICAL AND ELECTRICAL COMPONENTS
1. FOR SEISMIC DESIGN CATEGORY D COMPONENT BRACING REQUIREMENTS ARE AS
FOLLOWS:
ARCHITECTURAL COMPONENTS:
Ip = 1.0 REQUIRED Ip = 1.5 REQUIRED
MECHANICAL/ELECTRICAL COMPONENTS:
Ip = 1.0 REQUIRED Ip = 1.5 REQUIRED
2. INTERSTORY DRIFTS:
DESIGN OF COMPONENTS SUPPORTED AT DIFFERENT ELEVATIONS
ARE TO BE DESIGNED TO ACCOMMODATE THE FOLLOWING INTERSTORY
ELASTIC DEFLECTION: 3/4" PER FLOOR
WIND LOADS
1. BASIC WIND SPEED = 110 MPH
2. WIND IMPORTANCE FACTOR = 1.15
3. WIND EXPOSURE CATEGORY = B
4. INTERNAL PRESSURE COEFFICIENT = ±0.18
5. WIND PRESSURE COMPONENTS AND CLADDING:
INTERIOR ZONE: P = + 50 PSF, P = - 50 PSF
END ZONE: P = + 50 PSF, P = - 85 PSF
(PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE
SURFACES, RESPECTIVELY. END ZONES EXTEND FROM CORNERS OF BUILDING A
DISTANCE EQUAL TO 5'-0" FROM THE CORNER)
6. WIND LOADS ARE BASED ON ASCE 7-05, METHOD 2
C1
SUBMIT ENGINEERED CONCRETE MIX DESIGNS, INCLUDING REQUIRED BACKUP DATA, FOR
EACH TYPE OF CONCRETE PROPOSED FOR USE TO THE ARCHITECT/ ENGINEER FOR
REVIEW. ALLOW ADEQUATE TIME FOR REVIEW PRIOR TO PERFORMING CONCRETE WORK.
C2
DETAIL, FABRICATE, LABEL, SUPPORT AND PLACE CONCRETE REINFORCEMENT IN
ACCORDANCE WITH ACI 315 "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT"
AND ACI 318 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE", LATEST
EDITIONS.
C3
SUBMIT DETAILED SHOP DRAWINGS INDICATING REINFORCEMENT SIZE, SPACING AND
PLACEMENT TO THE ARCHITECT/ENGINEER FOR REVIEW PRIOR TO FABRICATION.
C4
CLEAN AND MOISTEN CONSTRUCTION JOINTS TO A SATURATED SURFACE DRY (SSD)
BETWEEN NEW CONCRETE IMMEDIATELY PRIOR TO PLACING FRESH CONCRETE.
C5
DO NOT USE CALCIUM CHLORIDE IN CONCRETE.
C6
REFER TO THE ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS
FOR CURBS, PADS, DEPRESSIONS, WALL/SLAB OPENINGS, SPECIAL FLOOR FINISHES, ETC.
C7
REFER TO ACI 318, CHAPTER 7.7 FOR MINIMUM CONCRETE COVER REQUIREMENTS, UNO.
C8
REFER TO ACI 305 FOR REQUIREMENTS FOR PLACING CONCRETE IN HOT WEATHER AND
TO ACI 306 FOR REQUIREMENTS FOR PLACING CONCRETE IN COLD WEATHER.
C9
ADHESIVE ANCHORING SYSTEM HIT-HY 150 ADHESIVE BY HILTI.
C10
PROVIDE ONLY CONCRETE, REINFORCING AND MATERIALS OF THE TYPES AND GRADES
LISTED IN THE TABLE BELOW, UNLESS NOTED OTHERWISE.
CONCRETE F'C (PSI) UNIT WEIGHT (PCF)
LIGHT WEIGHT CONCRETE FILL 3000 115
(FOR USE AT EXISTING DEPRESSION INFILLS)
ALL OTHER CONCRETE 3000 150
(MAX W/C 0.5)
REINFORCING GRADE
TYPICAL BARS ASTM A-615, GRADE 60
WELDED WIRE FABRIC ASTM A-185
S1
DETAIL, FABRICATE AND ERECT STRUCTURAL STEEL IN CONFORMANCE WITH THE
AISC SPECIFICATIONS AND CODES, LATEST EDITIONS.
S2
PERFORM WELDING USING CERTIFIED WELDERS AND IN ACCORDANCE WITH THE
AWS "STRUCTURAL WELDING CODE - STEEL", LATEST EDITION. COMPLY WITH AISC
SPECIFICATION FOR MINIMUM FILLET WELD SIZES, BUT DO NOT USE LESS THAN A
3/16 INCH FILLET UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.
S3
SUBMIT CHECKED SHOP DRAWINGS TO THE ARCHITECT/ ENGINEER FOR REVIEW.
SHOW SHOP FABRICATION DETAILS, FIELD ASSEMBLY DETAILS, AND ERECTION
DIAGRAMS FOR STRUCTURAL STEEL. SCHEDULE SUBMISSIONS TO ALLOW
ADEQUATE TIME FOR REVIEW PRIOR TO FABRICATION.
S4
USE BOLTED JOINTS IN FIELD CONNECTIONS WHENEVER POSSIBLE, UNLESS
WELDED JOINTS ARE DETAILED.
S5
PROVIDE A MINIMUM OF TWO (2) BOLTS AT EACH FAYING SURFACE.
S6
AFTER FABRICATION, CLEAN STEEL OF RUST, LOOSE MILL SCALE, DIRT, OIL,
GREASE OR OTHER FOREIGN MATERIALS.
S7
REFER TO THE ARCHITECTURAL DRAWINGS FOR THE REQUIRED FIRE RATINGS AND
UL ASSEMBLY NUMBERS.
S8
DO NOT FIELD CUT STRUCTURAL STEEL UNLESS REVIEWED AND APPROVED BY THE
ARCHITECT/ENGINEER IN WRITING.
S9
ERECTION PROCEDURES, SEQUENCES AND COORDINATION OF WORK WITH OTHER
TRADES IS THE RESPONSIBILITY OF THE CONTRACTOR. PROVIDE ADDITIONAL STEEL
REQUIRED FOR ERECTION PURPOSES AT NO COST TO THE VETERAN'S
ADMINISTRATION. REMOVE THIS ADDITIONAL STEEL UNLESS DIRECTED OTHERWISE
BY THE VETERAN'S ADMINISTRATION IN WRITING.
S10
PROVIDE NEW MATERIAL CONFORMING TO THE FOLLOWING REQUIREMENTS FOR
STRUCTURAL STEEL:
MEMBER GRADE
WIDE FLANGE SHAPES, WT SECTIONS ASTM A992
CHANNELS AND ANGLES ASTM A36
ALL OTHER STEEL MEMBERS ASTM A36 UNO
HIGH STRENGTH BOLTS, ASTM A-325
NUTS AND WASHERS (MIN. 3/4" DIAMETER)
STEEL SHAPE WELDING ELECTRODE E70XX
SD1
FABRICATE STEEL DECKING FROM STEEL TYPE ASTM A653, STRUCTURAL QUALITY
HAVING A MINIMUM YIELD STRENGTH OF 33,000 PSI. COMPLY WITH STEEL DECK
INSTITUTE SPECIFICATIONS FOR DESIGN, DETAILING, FABRICATION AND
ERECTION OF STEEL DECK. USE STRUCTURAL STEEL DECK WITH A MINIMUM
THICKNESS OF AT LEAST 20 GAGE, UNLESS NOTED OTHERWISE.
SD2
PROVIDE CONTINUOUS SHEET METAL CLOSURES AT SLAB OPENINGS AND SLAB
EDGES AND CONTINUOUS DECK CLOSURES AT DECK ENDS.
SD3
THE ASSUMED CONSTRUCTION LIVE LOAD USED IN DESIGN IS A 20 PSF UNIFORM
LOAD OR A 150-POUND CONCENTRATED LOAD ON A 1'-0" WIDE SECTION OF DECK.
DO NOT EXCEED THE ASSUMED CONSTRUCTION DESIGN LIVE LOAD WITHOUT
FIRST TAKING PROPER SAFETY PRECAUTIONS, INCLUDING TEMPORARY SHORING.
FOLLOW APPLICABLE LOCAL CODE AND AISI REQUIREMENTS.
M1
CHECK DIMENSIONS AGAINST THE REQUIREMENTS OF OTHER CONTRACT
DOCUMENTS. RESOLVE APPARENT INCONSISTENCIES IN THE CONTRACT
DOCUMENTS WITH THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH WORK.
M2
SHOW OPENINGS THROUGH STRUCTURAL MEMBERS ON THE SHOP DRAWINGS
SUBMITTED FOR REVIEW. OPENINGS WHICH ARE NOT SHOWN ON THE STRUCTURAL
DRAWINGS ARE SUBJECT TO REVIEW AND ACCEPTANCE AND ARE TO BE CLEARLY
INDICATED FOR REVIEW AND ACCEPTANCE ON THE SHOP DRAWINGS.
M3
DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE
CONDITIONS ARE NOT SPECIFICALLY SHOWN, USE DETAILS OF SIMILAR
CONSTRUCTION, SUBJECT TO APPROVAL BY THE ENGINEER.
M4
WHEREVER THERE IS CONFLICT BETWEEN DETAILS OR TWO DETAILS APPLYING TO
THE SAME CONDITION, THE ENGINEER WILL HAVE SOLE AUTHORITY TO DETERMINE
WHICH DETAIL IS THE MOST APPROPRIATE FOR THE CONDITION.
M5
PROMPTLY NOTIFY THE ENGINEER OF ANY STRUCTURAL MEMBER CALLED OUT ON
THE ARCHITECTURAL, MECHANICAL, PLUMBING OR ELECTRICAL DRAWINGS THAT IS
NOT IDENTIFIED ON THE STRUCTURAL DRAWINGS. DESIGN OF THESE MEMBERS
WILL BE PROVIDED AS NECESSARY BY THE STRUCTURAL ENGINEER UPON
NOTIFICATION.
M6
THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE LOCATION
AND PLACEMENT OF INSERTS, HANGERS AND OTHER MISCELLANEOUS ITEMS
REQUIRED FOR THE SUPPORT OF MECHANICAL, ELECTRICAL AND PLUMBING ITEMS
SUSPENDED FROM THE STRUCTURE.
M7
DO NOT MAKE MODIFICATIONS, ALTERATIONS OR REPAIRS TO THE STRUCTURE
WITHOUT PRIOR REVIEW BY THE STRUCTURAL ENGINEER. SUBMIT DETAILS AND
CALCULATIONS PREPARED BY A PROFESSIONAL ENGINEER REGISTERED IN NEW
YORK STATE AND EMPLOYED BY CONTRACTOR.
360 Madison Avenue, New York, New York 10017 212.972.9800 o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Revisions:
Date o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
Building Number
Approved:
Drawing Title Project Title
Date
Office of Construction &
Facilities Management
F
E
D o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
C
B
A
Location
Checked Drawn
Drawing Number
Project Number
CONSULTANTS: ARCHITECT/ENGINEERS:
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
KEY PLAN:
VA FORM 08-6231
Contractor to Provide Seismic Bracing for All Utilities Building is Fully Sprinklered Scale: AS NOTED
ASBESTOS ABATEMENT CONSULTANT:
14 HIGH STREET
MAHWAH, NEW JERSEY 07430
Tel: (914) 320-7924
Egan Environmental Consulting, Inc. 423 EAST 23RD STREET
NEW YORK, NY 10010
VA NY HARBOR HEALTHCARE SYSTEM
MANHATTAN VAMC -
BUILDING 1 WARD RENOVATIONS
Sheet Number 113of
1-S001
STRUCTURAL DETAILS AND
GENERAL NOTES
BA RP
630-18-101
JANUARY 17, 2020 10
NTSSCALE:
B8
EXISTING SLAB OPENING INFILL DETAIL
SCALE: 0 4' 8'1/4" = 1'-0"
F8
TYPICAL UNDERSIDE OF SLAB REPAIR
NTSSCALE:
C8
SUPPORT FRAME CONNECTION DETAIL
STRUCTURAL DESIGN LOADS
STRUCTURAL CONCRETE NOTES
STRUCTURAL STEEL NOTES
STRUCTURAL STEEL DECK NOTES
MISCELLANEOUS
ADDENDUM 01 1 02/12/2021
| Sheets |
| 1-S001 - STRUCTURAL DETAILS AND GENERAL NOTES |