This addendum provides specifications for metal lockers to be installed as part of the renovation of the patient ward 4W step down unit at the Manhattan VA Medical Center. The lockers will be knocked-down corridor style constructed of cold-rolled or galvanized steel sheets. Doors and frames will be welded channel shapes while bodies will be assembled by riveting or bolting. Continuous sloping tops and zee bases will be provided along with filler panels and boxed end panels. Each locker will include an identification plate and shelf with a double and two single hooks. The lockers must meet accessibility requirements and have a two-year warranty on materials and workmanship.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Manhattan VAMC Issued: February 19, 2021
Bldg. 1 Ward Renovations - 4W Addendum No. 2
Manhattan Veteran's Affairs Medical Center
New York, New York
10 51 13 - 1
SECTION 10 51 13
METAL LOCKERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Knocked-down corridor lockers.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of metal locker.
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each type of metal locker.
B. Shop Drawings: For metal lockers.
1. Include plans, elevations, sections, details, and attachments to other work.
Show locker trim and accessories.
Include locker identification system and numbering sequence.
Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.
Samples for Verification: For the following products, in manufacturer's standard size:
2. Lockers and equipment.
1.3 CLOSEOUT SUBMITTALS
A. Maintenance Data: For adjusting, repairing, and replacing locker doors and latching mechanisms to include in maintenance manuals.
1.4 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Full-size units of the following metal locker hardware items equal to
10 percent of amount installed for each type and finish installed, but no fewer than five units:
a. Identification plates.
Hooks.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Do not deliver metal lockers until spaces to receive them are clean, dry, and ready for their installation.
10 51 13 - 2
1.6 FIELD CONDITIONS
A. Field Measurements: Verify actual dimensions of recessed openings by field measurements before fabrication.
1.7 COORDINATION
A. Coordinate sizes and locations of bases for metal lockers.
Coordinate sizes and locations of framing, blocking, furring, reinforcements, and other related units of work specified in other Sections to ensure that metal lockers can be supported and installed as indicated.
1.8 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of metal lockers that fail in materials or workmanship, excluding finish, within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Structural failures.
Faulty operation of latches and other door hardware.
2. Damage from deliberate destruction and vandalism is excluded.
Warranty Period for Knocked-Down Metal Lockers: Two years from date of
Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Accessibility Requirements: For lockers indicated to be accessible, comply with applicable provisions in the U.S. Architectural & Transportation
Barriers Compliance Board's ADA-ABA Accessibility Guidelines and ICC
A117.1.
2.2 KNOCKED-DOWN CORRIDOR LOCKERS
A. Doors: One piece; fabricated from 0.060-inch nominal-thickness steel sheet; formed into channel shape with double bend at vertical edges and with right-angle single bend at horizontal edges.
1. Doors less than 12 inches wide may be fabricated from 0.048-inch nominal-thickness steel sheet.
Doors for box lockers less than 15 inches wide may be fabricated from
0.048-inch nominal-thickness steel sheet.
Reinforcement: Manufacturer's standard reinforcing angles, channels, or stiffeners for doors more than 15 inches wide; welded to inner face of doors.
Stiffeners: Manufacturer's standard full-height stiffener fabricated from 0.048-inch nominal-thickness steel sheet; welded to inner face of doors.
Door Style: Unperforated panel.
10 51 13 - 3
B. Body: Assembled by riveting or bolting body components together.
Fabricate from unperforated steel sheet with thicknesses as follows:
1. Tops, Bottoms, and Intermediate Dividers: 0.024-inch nominal thickness, with single bend at sides.
Backs and Sides: 0.024-inch nominal thickness, with full-height, double-flanged connections.
C. Frames: Channel formed; fabricated from 0.060-inch nominal-thickness steel sheet; lapped and factory welded at corners; with top and bottom main frames factory welded into vertical main frames. Form continuous, integral, full-height door strikes on vertical main frames.
1. Cross Frames between Tiers: Channel formed and fabricated from same material as main frames; welded to vertical main frames.
D. Hinges: Welded to door and attached to door frame with no fewer than two factory-installed rivets per hinge that are completely concealed and tamper resistant when door is closed; fabricated to swing 180 degrees.
1. Hinges: Manufacturer's standard, steel, continuous or knuckle type.
E. Recessed Door Handle and Latch: Stainless-steel cup with integral door pull, recessed so locking device does not protrude beyond door face; pry and vandal resistant.
1. Single-Point Latching: Nonmoving latch hook with steel padlock loop that projects through recessed cup and is finished to match metal locker body.
a. Latch Hook: Equip each door with one latch hook, fabricated from
0.105-inch nominal-thickness steel sheet; welded midway up full-height door strike; with resilient silencer.
F. Door Handle and Latch for Box Lockers: Stainless-steel strike plate with integral pull; with steel padlock loop that projects through metal locker door.
Identification Plates: Manufacturer's standard, etched, embossed, or stamped aluminum plates, with numbers and letters at least 3/8 inch high.
Hooks: Manufacturer's standard ball-pointed type hooks, aluminum or steel;
zinc plated.
G. Continuous Zee Base: Fabricated from manufacturer's standard thickness, but not less than 0.060-inch nominal-thickness steel sheet.
1. Height: 4 inches unless otherwise indicated on Drawings.
H. Continuous Sloping Tops: Fabricated from manufacturer's standard thickness, but not less than 0.036-inch nominal-thickness steel sheet.
1. Closures: Vertical -end type.
Sloping-top corner fillers, mitered.
Filler Panels: Fabricated from manufacturer's standard thickness, but not less than 0.036-inch nominal-thickness steel sheet.
Boxed End Panels: Fabricated from 0.060-inch nominal-thickness steel sheet.
Center Dividers: Fabricated from 0.024-inch nominal-thickness steel sheet.
10 51 13 - 4
Materials:
2. Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B, suitable for exposed applications.
Metallic-Coated Steel Sheet: ASTM A 653/A 653M, Commercial Steel (CS), Type B; with A60 zinc-iron, alloy (galvannealed) coating designation.
I. Finish: Baked enamel or powder coat.
1. Color: As selected by Resident Engineer from manufacturer's full range.
2.3 FABRICATION
A. Fabricate metal lockers square, rigid, without warp, and with metal faces flat and free of dents or distortion. Make exposed metal edges safe to touch and free of sharp edges and burrs.
1. Form body panels, doors, shelves, and accessories from one-piece steel sheet unless otherwise indicated.
Provide fasteners, filler plates, supports, clips, and closures as required for complete installation.
B. Fabricate each metal locker with an individual door and frame; individual top, bottom, and back; and common intermediate uprights separating compartments. Factory weld frame members of each metal locker together to form a rigid, one-piece assembly.
Equipment: Provide each locker with an identification plate and the following equipment:
1. Single-Tier Units: Shelf, one double-prong ceiling hook, and two single-prong wall hooks.
C. Knocked-Down Construction: Fabricate metal lockers using nuts, bolts, screws, or rivets for nominal assembly at Project site.
Accessible Lockers: Fabricate as follows:
1. Locate bottom shelf no lower than 15 inches above the floor.
Where hooks, coat rods, or additional shelves are provided, locate no higher than 48 inches above the floor.
D. Continuous Base: Formed into channel or zee profile for stiffness, and fabricated in lengths as long as practical to enclose base and base ends of metal lockers; finished to match lockers.
Continuous Sloping Tops: Fabricated in lengths as long as practical, without visible fasteners at splice locations; finished to match lockers.
1. Sloping-top corner fillers, mitered.
Filler Panels: Fabricated in an unequal leg angle shape; finished to match lockers. Provide slip-joint filler angle formed to receive filler panel.
Boxed End Panels: Fabricated with 1-inch- wide edge dimension, and designed for concealing fasteners and holes at exposed ends of nonrecessed metal lockers; finished to match lockers.
2. Provide one-piece panels for double-row (back-to-back) locker ends.
10 51 13 - 5
E. Center Dividers: Full-depth, vertical partitions between bottom and shelf;
finished to match lockers.
2.4 ACCESSORIES
A. Fasteners: Zinc- or nickel-plated steel, slotless-type, exposed bolt heads; with self-locking nuts or lock washers for nuts on moving parts.
Anchors: Material, type, and size required for secure anchorage to each substrate.
1. Provide nonferrous-metal or hot-dip galvanized anchors and inserts on inside face of exterior walls, and elsewhere as indicated,for corrosion resistance.
Provide toothed-steel or lead expansion sleeves for drilled-in-place anchors.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine walls, floors, and support bases, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.
Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. General: Install lockers level, plumb, and true; shim as required, using concealed shims.
1. Anchor locker runs at ends and at intervals recommended by manufacturer, but not more than 36 inches o.c. Using concealed fasteners, install anchors through backup reinforcing plates, channels, or blocking as required to prevent metal distortion.
Anchor single rows of metal lockers to walls near top and bottom of lockers.
Anchor back-to-back metal lockers to floor.
B. Knocked-Down Lockers: Assemble with standard fasteners, with no exposed fasteners on door faces or face frames.
Equipment:
1. Attach hooks with at least two fasteners.
Identification Plates: Identify metal lockers with identification indicated on Drawings.
a. Attach plates to each locker door, near top, centered, with at least two aluminum rivets.
Attach plates to upper shelf of each open-front metal locker, centered, with a least two aluminum rivets.
10 51 13 - 6
3.3 ADJUSTING
A. Clean, lubricate, and adjust hardware. Adjust doors and latches to operate easily without binding.
3.4 PROTECTION
A. Protect metal lockers from damage, abuse, dust, dirt, stain, or paint. Do not permit use during construction.
Touch up marred finishes, or replace metal lockers that cannot be restored to factory-finished appearance. Use only materials and procedures recommended or furnished by locker manufacturer.
END OF SECTION