Appendix B6 - MC Cable.pdf
PDF 613 KB Posted
- Attached to
- Y1JZ--NCOTA 3B Completion Project
- Solicitation number
- 36C10F25B0002
About this file
This document is a technical specification sheet for Fire Alarm Control Cable – Type MC, a dual-rated plenum cable manufactured by AFC Cable Systems. The cable is designed for fire detection and alarm systems, with specifications including solid copper conductors using TFN (18 and 16 AWG) or THHN (14 and 12 AWG) insulation, an interlocked galvanized steel strip armor painted red, and a polyester assembly tape. The cable is rated for maximum temperatures of 105°C (FPLP) or 90°C (MC), with a maximum voltage rating of 300V (FPLP) or 600V (MC).
The technical specification provides detailed performance charts covering electrical properties such as reactance, resistance, effective impedance, mutual capacitance, and inductance. The cable meets various industry standards including UL certifications, NEC requirements, and NFPA 262 plenum rating. Product codes are provided for different conductor configurations, including 2-6 conductor options with various color combinations, and the cable is designed for use in fire alarm and control applications, particularly for fishing between walls in electrical installations.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C&C Contractors 209 Lyons Street Notasulga, Alabama 36866 Phone: (334) 257-4307
Project: 1901 - 1901 Alleghenies Major 2018 1158 Morgan Rd
Bridgeville, Pennsylvania 15017
Distribution Summary Distributed on 01/29/2021 by Brandon Johnson (C&C Contractors, LLC)
To: Leanne Pomponio (Vantage Corp ), Bill Kendall (Vantage Corp ) Message: See attached approved submittal.
Additional Attachments: 28 46 00-02 Fire Detection and Alarm- MC Cable for Fishing between Walls Submittal.pdf
NAME RESPONSE ATTACHMENTS COMMENT
Brandon Johnson (C&C Contractors, LLC)
Approved
Joyce Johnson (Department of Veteran Affairs)
Approved No Exception Taken
28 46 00-02 Fire Detection and Alarm- MC Cable for Fishing between Walls
REVISION: 0 SUBMITTAL MANAGER: Brandon Johnson (C&C Contractors, LLC)
STATUS: Closed DATE CREATED: 12/16/2020 ISSUE DATE: 12/16/2020 SPEC SECTION: 28 46 00 - Fire Detection and Alarm
RESPONSIBLE
CONTRACTOR:
Vantage Corp RECEIVED FROM: Bill Kendall
RECEIVED DATE: 12/16/2020 SUBMIT BY: 12/16/2020
FINAL DUE DATE: 01/13/2021 LOCATION:
COST CODE:
TYPE: Product Information
APPROVERS: Joyce Johnson (Department of Veteran Affairs), Brandon Johnson (C&C Contractors, LLC)
BALL IN COURT:
DISTRIBUTION:
Ashraf Wahba (NCA), Robert Meyer (C&C Contractors, LLC), Kimberly Giles (NCA), Jason Gerhart (Gordon), Carlton Fuqua (C&C Contractors, LLC), Peter Fuller (C&C Contractors, LLC), Paul Crowe (Vali Cooper International, LLC)
DESCRIPTION:
SUBMITTAL TRANSMITTAL
DEPARTMENT OF VETERANS AFFAIRS PROJECT: National Cemetery of the Alleghenies- Phase 3 Development
CONTRACT NO: 36C10F19C0002
Obligation No. 925CM20006
Contractor: C & C Contractors, LLC Supplier: Vantage Electric
Item No.
Specification Section No.:
28 46 00 Registered Submittal No.:
Paragraph No. Description of Item (Size, Type, Name, Manufacturer, Use, etc.)
No. of Copies Submitted
1.4 Submittals- Fire Detection and Alarm
1 2.2. Wire 3
C&C Contractors Page 1 of 2 Printed On: 02/09/2021 02:36 PM
Submittal #28 46 00-2.0
28 46 00 - Fire Detection and Alarm https://storage.procore.com/v4/d/us-east-1/pro-core.com/prostore/20201216200427_production_2614879074.pdf?sig=328d7695143389f8a1805dd789df7651b3a21b01fede0971216b8fe65fd5ebdb
SUBMITTAL WORKFLOW
NAME SENT DATE DUE DATE RETURNED
DATE RESPONSE ATTACHMENTS COMMENTS
General Information Attachments
28 46 00-02 Fire Detection and Alarm- MC Cable for Fishing between Walls Submittal.pdf
Joyce Johnson 12/16/2020 12/30/2020 01/27/2021 Approved No Exception Taken
Brandon Johnson 01/27/2021 01/13/2021 01/29/2021 Approved
BY DATE COPIES TO
C&C Contractors Page 2 of 2 Printed On: 02/09/2021 02:36 PM
Submittal #28 46 00-2.0
28 46 00 - Fire Detection and Alarm https://app.procore.com/743331/project/submittal_logs/document_downloader?attachment_id=2614879074&item_id=27010917&item_type=SubmittalLog&project_id=743331&source=coversheet https://app.procore.com/743331/project/submittal_logs/document_downloader?attachment_id=2614879074&item_id=27010917&item_type=SubmittalLog&project_id=743331&source=coversheet https://app.procore.com/743331/project/submittal_logs/document_downloader?attachment_id=2614879074&item_id=27010917&item_type=SubmittalLog&project_id=743331&source=coversheet
SUBMITTAL TRANSMITTAL
SN: 28 46 00-02
Sheet: 1 of 05
DEPARTMENT OF
VETERANS AFFAIRS
PROJECT: National Cemetery of the Alleghenies- Phase 3 Development
CONTRACT NO: 36C10F19C0002
Obligation No. 925CM20006
Pkg.
No.
x
Date:
December 16, 2020
Contractor: C & C Contractors, LLC Supplier: Vantage Electric VA ACTION
Ite m
N o.
Specification Section No.:
28 46 00 Registered Submittal No.:
Pa ra gr ap h
Description of Item (Size, Type, Name, Manufacturer, Use, etc.) N o.
o f C op ie s Su bm itt ed o f
C op ie s
R et ur ne d
Ap pr ov
Ap pr w ith ot at io ns
D is ap pr
R es ub m it
1.4 Submittals- Fire Detection and Alarm
1 2.2. Wire 3 Contractor Signature:
Brandon Johnson
Recommended By:
Title, Date: Project Manager 12/16/2020
Title: Date:
I hereby certify that this submittal has been reviewed for accuracy, completeness, and compliance with contract requirements per the General Provisions (FAR 52.236-21) A/E/Sub:
Review Comments:
Action By:
Date:
Contracting Officer’s Representative
Approval of this submittal is subject to the provisions of the contract drawings and specifications. This action is for general concurrence only and the Government is not responsible for errors or omissions.
SUBMITTAL LOG DATES: From contractor (_________), To reviewer (_________), From reviewer (_________), To contractor (_________), DSC-1(CS) Rev.
Distribution: ( ) Contractor ( ) DSC File ( ) COR ( ) A/E ( ) DSC Interim ( ) COR Interim ( ) Contractor Interim 11/95
61 ARCH STREET – SUITE 202 CARNEGIE, PA 15106
PHONE 412-429-4750 FAX 412-429-4752
a Certified Woman-Owned Business
EQUAL OPPORTUNTIY EMPLOYER
Owner:Department of Veterans Affairs (CFM) 425 I Street, NW Washington, DC 20001
Contract No: VA25CM2006
Project Name: National Cemetery of the Alleghenies Phase 3 Development “Package A & B” Vantage Job No. 8663
Submittal Cover Letter
1. Submittal Number: 6B
2. Specification Number: 28 46 00 Fire Detection and Alarm
3. Material Description: Fire Alarm MC Cable for Fishing Existing Walls
4. Deviations: None
5. Contractor Review Certification
Signature:
William Kendall, PM
Date: 12-16-2020
M
C CA
BLES
29800-757-6996
Product Code
Trade Size Grounding
Conductor AWG Approx. Weight/
1,000ft (lbs) Approx. Armor O.D.
(In)250' Coil 1000' Reel
Solid TFN
1801R42-00 1801R60-00 18-2 Solid (Black, White) 18 bare 110 0.470
1803R42-00 1803R60-00 18-4 Solid (Black, White, Red, Blue) 18 bare 130 0.430
1805R42-00 1805R60-00 18-6 Solid (Black, White, Red, Blue, Yellow, Orange) 18 bare 170 0.490
1810R42-00 1810R60-00 16-2 Solid (Black, White) 16 bare 120 0.470
1813R42-00 1813R60-00 16-4 Solid (Black, White, Red, Blue) 16 bare 147 0.491
Solid THHN
1834R42-00 1834R60-00 14-2 Solid (Black, White) 14 Solid (Green) 142 0.471
1837R42-00 1837R60-00 14-4 Solid (Black, White, Red, Blue) 14 Solid (Green) 192 0.529
1835R42-00 1835R60-00 12-2 Solid (Black, White) 12 Solid (Green) 177 0.514
1840R42-00 1840R60-00 12-4 Solid (Black, White, Red, Blue) 12 Solid (Green) 249 0.584
Twisted Shielded Pairs
1895R42-05 1895R60-05 16-2 Solid (1 TSP) (Blue, White) † 16 Solid (Green) 147 0.526
1895R42-06 1895R60-06 16-2 Solid (1 TSP) (Black, Red) † 16 Solid (Green) 147 0.526
4901R42-00 4901R60-00 16-2 Solid (1 TSP) (Black, White) & un-shielded 12-2 Solid (Black, Red) † 12 Solid (Green) 236 0.606
1828R42-00 1828R60-00 14-2 Solid (1 TSP) (Black, White) † 14 Solid (Green) 217 0.565
1828R42-05 1828R60-05 14-2 Solid (1 TSP) (Blue, White) † 14 Solid (Green) 217 0.565
1881R42-00 1881R60-00 14-4 Solid (2 TSP) (Black, Red) (Blue, White) † 14 Solid (Green) 255 0.690
Specialty Colors
1828R42-05 1828R60-05 14-2 Solid (1TSP) (Blue, White) † 14 Solid (Green) 217 0.565
1834R42-05 1834R60-05 14-2 Solid (Blue, White) 14 Solid (Green) 195 0.627
1834R42-06 1834R60-06 14-2 Solid (Black, Red) 14 Solid (Green) 195 0.627
1834R42-23 1834R60-23 14-2 Solid (Orange, Yellow) 14 Solid (Green) 195 0.627
1834R42-37 1834R60-37 14-2 Solid (Brown, Purple) 14 Solid (Green) 195 0.627
1834R42-44 1834R60-44 14-2 Solid (Gray, Gray*) 14 Solid (Green) 195 0.627
1835R42-05 1835R60-05 12-2 Solid (Blue, White) 12 Solid (Green) 177 0.514
1837R42-05 1837R60-05 14-4 Solid (Blue, Blue*, White, White*) 14 Solid (Green) 192 0.529
1837R42-06 1837R60-06 14-4 Solid (Black, Black*, Red, Red*) 14 Solid (Green) 192 0.529
1895R42-06 1895R60-06 16-2 Solid (1 TSP) (Black, Red) † 16 Solid (Green) 147 0.526
NOTE: All dimensions and weights are subject to normal manufacturing tolerances.
* One conductor insulation has identifying stripe † All drain wires are 18AWG Tinned Copper in TSP construction Mylar is a Registered trademark of DuPont
Armor Interlocked Galvanized Steel Strip (Painted Red)
Conductors Solid Copper Conductor Insulation TFN 18 & 16 AWG and/or THHN 14 & 12 AWG Assembly Polyester Assembly Tape; Twisted Shielded: Laminated Aluminum/Mylar® Shield with Tinned Copper Drain Wire Maximum Temperature Rating FPLP: 105°C (Dry) MC: 90°C (Dry) Grounding One or More Grounding Conductors May Be Bare or Insulated Green, See Chart Below
Neutral Conductor White (Where Applicable) Maximum Voltage Rating
300V (FPLP)
600V (MC)
References & Ratings
• UL 66, 83, 1424, 1479, 1569, 1581, 2556, File Reference E80042
• NEC® 300.22(C), 392, 330, 430.2, 501, 502, 503, 530, 504, 505, 518, 530,
645, 725, 760, 760.154(A)
• Cable Tray Rated, install per NEC®
• Federal Specification A-A-59544 (formerly J-C-30B)
• UL Classified 1, 2, and 3 hour through (Fire) penetration product, R14141
• NFPA 262 (formerly UL 910) Plenum Rated - Type FPLP
• Made in USA of US and/or imported materials
Fire Alarm® Control Cable – Type MC – Dual Rated Type MC/FPLP Plenum Rated Technical Specifications
For the electrical properties of Fire Alarm® Control Cable and twists per foot information, see page 30.
Copper GroundNylon Thermoplastic TFN or THHN Insulation
Interlocked Galvanized Steel Strip (Color-Coded Red)
Copper Conductors
Assembly Tape
29AFC Cable Catalogwww.afcweb.com
BKendall Highlight
BKendall Rectangle
BKendall Highlight
BKendall Rectangle
BKendall Typewritten Text 28 46 00 Fire Detection and Alarm MC Cable
BKendall Line
BKendall Line
M C
CA
BL
ES
30 800-757-6996
Fire Alarm® Control Cable Performance Charts
Conductor Size
AWG
XL,
Reactance1
Rac, Resistance, 75°C2
Z, Effective3 Impedance
Electrical Properties (ohms to neutral per 1000 feet)
18 0.047 7.77 6.24
16 0.043 4.89 3.93
14 0.042 3.07 2.48
12 0.04 1.93 1.57 1 In Steel Armor 2 To correct for 90°C, multiply by 1.048 3 Effective Impedance is defined as R cos (Theta) + X sin (Theta) where Theta is the power factor angle of the circuit. Effective impedance values shown in the table above are valid at 80% power factor.
Conductor Size
AWG
Twisted Pair1
Twisted Shielded Pair2
Mutual Capacitance (pico farads per foot)
18 30 47.3
16 33.5 54.8
14 36.3 60.7
12 38.8 66.4 1 In Steel Armor 2 To correct for 90°C, multiply by 1.048 3 Effective Impedance is defined as R cos (Theta) + X sin (Theta) where Theta is the power factor angle of the circuit. Effective impedance values shown in the table above are valid at 80% power factor.
Inductance (L) to neutral, per 1000 feet is typically 0.0002mH for sizes 18 AWG through 250 kcmil
= 0.1404 Log10(GMD/GMR) x 10-3 Henrys to neutral per 1000 feet]
Size Total Number of Conductors
Including Ground Conductor Diameter Length of Lay Twists per Foot
Twists per Foot
18 2 0.08 2.4 5
18 3 0.08 2.8 4.3
18 4 0.08 3.2 3.8
18 5 0.08 3.3 3.7
16 2 0.09 2.7 4.4
16 3 0.09 3.2 3.8
16 4 0.09 3.6 3.3
16 5 0.09 3.7 3.3
14 2 0.105 3.15 3.8
14 3 0.105 3.7 3.3
14 4 0.105 4.2 2.9
14 5 0.105 4.3 2.8
12 2 0.125 3.75 3.2
12 3 0.125 4.4 2.7
12 4 0.125 5 2.4
12 5 0.125 5.1 2.4
Copper Ground Nylon Thermoplastic TFN or THHN Insulation
Interlocked Galvanized Steel Strip (Color-Coded Red)
Copper Conductors
Assembly Tape
AFC Cable Catalog30 www.afcweb.com
31800-757-6996
Product Code
Trade Size Approx. Weight/
1,000ft (lbs) Approx. Armor O.D.
(In)250' Coil 1000' Reel
Metal Sheathed Type FPLP Cable
1850R42-00 1850R60-00 18-2 Solid (1 TSP) (Black, White) † 111 0.470
1827R42-00 1827R60-00 18-2 Solid (1 TSP) (Black, Red) & 14-2 Solid (1 TSP) (Black, White) † 204 0.637
1860R42-00 1860R60-00 16-2 Solid (1 TSP) (Black, White) † 118 0.470
1843R42-00 1843R60-00 16-4 Solid (2 TSP) (Black, White) (Red, Blue) † 195 0.627
NOTE: All dimensions and weights are subject to normal manufacturing tolerances.
* One conductor insulation has identifying stripe † All drain wires are 18AWG Tinned Copper in TSP construction Mylar is a Registered trademark of DuPont
Armor Interlocked Galvanized Steel Strip (Red-Striped)
Conductors Solid Copper Conductor Insulation TFN 18 & 16 AWG and/or THHN 14 & 12 AWG Assembly Polyester Assembly Tape; Twisted Shielded: Laminated Aluminum/Mylar® Shield with Tinned Copper Drain Wire Maximum Temperature Rating FPLP: 105°C (Dry) Neutral Conductor White (Where Applicable)
References & Ratings
• UL 66, 83, 1424, 1479, 1581, 2556, File Reference E83514
• NEC® 300.22(C), 392, 330, 430.2, 501, 502, 503, 530, 504, 505, 518, 530,
645, 725, 760, 760.154(A)
• Cable Tray Rated, install per NEC®
• Federal Specification A-A-59544 (formerly J-C-30B)
• UL Classified 1, 2, and 3 hour through (Fire) penetration product, R14141
• NFPA 262 (formerly UL 910) Plenum Rated - Type FPLP
• Made in USA of US and/or imported materials
Power Limited Fire Alarm Circuit Cable – Type FPLP Plenum Rated Technical Specifications
For the electrical properties of Fire Alarm® Control Cable and twists per foot information, see page 30.
31AFC Cable Catalogwww.afcweb.com
Submittal #6A 8663.pdf