EP 603 - POWER RISER DIAGRAM (ESSENTIAL).pdf
PDF 652 KB Posted
- Attached to
- Y1DA--Renovation of Building One (1) Veteran Affairs Medical Center (VAMC), Bay Pines Florida 33708 Federal contract opportunity
- Solicitation number
- 36C10F20R0043
About this file
This sources sought notice requests capability statements from small businesses for the construction of Project 516-005, the renovation of Building One at the Bay Pines VA Medical Center in Bay Pines, Florida. The construction work includes general construction, interior demolition and alterations, structural modifications, installation of healthcare equipment, and exterior construction. The estimated price range for the project is between $20-50 million. Responses were requested to include company information, small business status and certification, bonding capacity, and experience on similar renovation projects. Capability statements were due by October 8, 2020. The notice states that a solicitation for the project is expected to be issued in November 2020 and posted to beta.SAM.gov.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DENOTES NEW
DENOTES EXISTING TO REMAIN
G
SEE DRAWING EP 601 FOR CONTINUATION.
(UNIT SUBSTATION 1-US A)
3rd FLOOR
4th FLOOR
5th FLOOR
TO EXISTING PANEL 'EMDP'
TERM.
BOX
SWBD. @ ROOM 1B-115EDP
WEST ELECTRICAL RM1st FLOOR
WEST AREA B
LH1W LL1W
T-
1 LS
TO LDP
15 KVA
ATTIC
1200A./3P ET
ATS #2 ATS #1
TO 1-US A
LDP
LIFE
SAFETY
CDP
CRITICAL
BRANCH
QDP1
BRANCH
EQUIPMENT
800A 400A 225A
T-
1QW
GEN. CONTROL
PANEL
WEST ELECTRICAL RM
SOUTH ELECTRICAL ROOM
SOUTH ELECTRICAL ROOM
SOUTH ELECTRICAL ROOM
500A
100A., 3P, 600V. DISC.SW.
FUSED WITH 100A DUAL
ELEMENT TIME DELAY FUSES
(ELEV. #3 FUSED AT 100A.)
3 #3 & 1 #6 GND. 1" C. TO
ELEV. #1 CONTROLLER
3 #3 & 1 #6 GND. 1" C. TO
ELEV. #2 CONTROLLER
3 #3 & 1 #6 GND. 1 1/4" C. TO
ELEV. #3 CONTROLLER
WIREWAY
125A., 3P
ENCLOSED C.B.
EXISTING FEEDERS TO NEW PANEL QDP
2 SETS OF 3 #250 MCM, 1 #4EG
IN 3"C. EACH
3 #3 & 1 #6 GND. 1 1/4"C. TO
ELEV. #4 CONTROLLER
100A., 3P., 600V.
DISCONNECT SW.
FUSED WITH 100A.
DUAL ELEMENT TIME
DELAY FUSES
3 #4 & 1 #8 GND
1 1/4"C.
EXISTING
QL1W QH1W
EXISTING
15KVA
EXISTING
ELEVATOR MACH. RM. A-606
EXISTING EXISTING
EXISTING
EXISTING
23 25
18 19
19 22
EXISTING EXISTING
ATS #3
800A
400A 3P 3P 3P 3P3P
100A 3P
400A 250A
1000KVA/800KW
@ 0.8 P.F.
277/480V., 3Ø, 4W
CENTRAL ELECTRICAL ROOM
MAIN ELECTRICAL RM
GENERAL NOTES:
DRAWING NOTES:
1.
2.
TO 1-US ATO 1-US A
70A,3P,480V
ENCLOSED C.B.
IN NEMA TYPE-1
ENCLOSURE
25KAIC -
NEW
@ BUILDING 22
3.
4.
7 2
5 5
QL1W1
T-
1QW1
30KVA
SPACE
FP FIRE PUMP
CONTROLLER
WEST MECHANICAL PUMP RM
FIRE PUMP
TO BUILDING 23
SPLICE
BOX
(OLD QDP)
4P. 4P. 4P.
14 14
ELEVATOR MACH. RM. A-601
100A 3P
EXISTING EXISTING
EXISTING
T- C2W
30 KVA
50A,3P,480V
ENCLOSED C.B.
IN NEMA TYPE-1
ENCLOSURE
25KAIC -
TO QDP
25 23
2 2
TO CDP
WEST AREA B
FEEDER SCHEDULE
NUMBER WIRE NEUTRAL GROUND CONDUIT
3 #6 - 1 #6 1" C.
3 #4 - 1 #4 1 1/4" C.
3 #4/0 1 #4/0 1 #4 2 1/2" C.
23 3 #3 1 #3 1 #6 1 1/2" C.
24 3 #2/0 1 #2/0 1 #4 2" C.
25 3 #2 1 #2 1 #4 1 1/2" C.
26 3 #6 2 #6 1 #8 1 1/4" C.
27 3 #3 - 1 #6 1 1/2" C.
28 3 #2 2 #2 1 #4 1 1/2" C.
29 3 #3 2 #3 1 #6 1 1/2" C.
30 3 #3 2 #3 1 #4 1 1/2" C.
3-500 KCMIL
2 #1/0 2 - 3 1/2" C.
2 SETS
2-500 KCMIL
3-500 KCMIL 1-500 KCMIL 1 #2 3 1/2" C.
3-500 KCMIL
3 #2/0 3 - 3 1/2" C.
3 SETS
3-500 KCMIL
14 3 #6 2 #6 1 #8 1 1/4" C.
31 3 #6 1 #6 1 #8 1 1/4" C.
3 #1 2 #1 1 #4 2" C.
32 3 #1/0 1 #1/0 1 #6 2" C.
33 - 1 #1 2-2" C.3-250 KCMIL
2 SETS
34 3-400 KCMIL 1-400 KCMIL 1 #2 3 1/2" C.
FEEDER SCHEDULE
NUMBER WIRE NEUTRAL GROUND CONDUIT
SOUTH ELECTRICAL ROOMWEST ELECTRICAL ROOM
14 14 14 14
14 14 1414
20 20
9 3 #4 1 #4 1 #8 1 1/4" C.
ALL CONDUCTORS SHALL BE COPPER WITH DUAL RATED TYPE INSULATION (THHN/THWN-2),
UNLESS OTHERWISE NOTED. SEE ELECTRICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND/OR REFER TO EQUIPMENT AND/OR DEVICES MANUFACTURER'S RECOMMENDATION FOR
EXACT TYPE OF CONDUCTOR TO BE USED. THE BASIS OF DESIGN IS TAKEN FROM NEC TABLE
310.16 AT 75 DEGREE C COLUMN.
CONTRACTOR TO FIELD VERIFY THE EXACT LENGTH OF ALL HOMERUN FEEDERS AND/OR
BRANCH CIRCUITS WIRING (CONDUITS & CONDUCTORS) PRIOR TO COMMENCING WORK.
INCREASE THE SIZE OF FEEDERS AND/OR BRANCH CIRCUITS WIRING TO LIMIT THE VOLTAGE
DROP TO 3% MAXIMUM FOR BRANCH CIRCUITS AND 2% MAXIMUM FOR FEEDERS.
PROVIDE CIRCUIT DIRECTORY CARDS FOR ALL SWITCHBOARD, DISTRIBUTION PANELBOARDS,
PANELBOARDS. DIRECTORIES SHALL BE UPDATED/TYPEWRITTEN WITH ACCURATE AND CURRENT
INFORMATION BY THE CONTRACTOR AT THE END OF CONSTRUCTION. DIRECTORIES SHALL
REFLECT AS-BUILT RECORD CONDITIONS AND INCLUDE CIRCUIT NUMBER, TYPE AND LOCATION
OF LOAD. TURN TO "OFF" POSITION AND IDENTIFY ALL NEW AND/OR ABANDONED BRANCH
BREAKERS AS SPARE. DATE DIRECTORY CARD AT FINAL COMPLETION
AT EACH PANELBOARD - PROVIDE "GROUPING" OF MULTIWIRE BRANCH CIRCUITS AS REQUIRED
TO COMPLY WITH 2014 EDITION NEC 210.4. THE UNGROUNDED AND NEUTRAL CONDUCTORS OF
MULTIWIRE BRANCH CIRCUITS MUST BE GROUPED TOGETHER IN AT LEAST ONE LOCATION BY
WIRE TIES OR SIMILAR MEANS AT THE POINT OF ORIGIN.
REFER TO PANEL SCHEDULE SHEETS FOR PANEL INFORMATION.
5.
3-350 KCMIL
4-350 KCMIL 4#3/0 4 - 3" C.
FOUR SETS
35 15
1414 14 14
14 14
QDP2
BRANCH
EQUIPMENT
REFER TO EP 601
EXISTING ELECTRICAL EQUIPMENT TO REMAIN - RECONNECT TO NEW DISTRIBUTION PANELS
AND/OR UNIT SUBSTATION WITH NEW FEEDER AS SHOWN PER FEEDER SCHEDULE ON THIS
SHEET.
K-13 RATED TYPE TRANSFORMER. SEE TRANSFORMER SCHEDULE ON SHEET EP 604 FOR
FEEDER AND GROUNDING SIZES AND ADDITIONAL INFORMATION.
SEE FEEDER SIZE ON SHEET EP 601.
FURNISH AND INSTALL NEW 3/4" DIA. X 20'-0" LONG COPPER CLAD STEEL GROUND ROD, DRIVEN
INTO THE GROUND AND MAKE APPROVED EXOTHERMIC CADWELD GROUNDING & BONDING
CONNECTION FROM THE GENERATOR TO THE MAIN BUILDING GROUNDING SYSTEM WITH 1 NO.
3/0 THWN CU IN 1 INCH CONDUIT. SEE GROUNDING & BONDING DETAILS ON SHEET E007 FOR
ADDITIONAL INFORMATION.
(NOTE: REUSE EXISTING GENERATOR GROUNDING SYSTEM, IF SUITABLE FOR REUSE. FIELD
VERIFY PRIOR TO COMMENCING WORK.).
FURNISH AND INSTALL 2 NO. 12, 1 NO. 12 EG IN 1/2" C FOR ENGINE START CIRCUIT FROM ATS
TO GENERATOR CONTROL PANEL. ALSO, FURNISH AND INSTALL CONTROL WIRING PER
GENERATOR MANUFACTURER RECOMMENDATION.
27 NO. 14 (WITH 4 NO. 14 SPARE) IN 1" C. FOR GENERATOR REMOTE ANNUNCIATOR. FIELD
VERIFY EXACT LOCATION OF NEW REMOTE ANNUNCIATOR PRIOR TO ROUGH-IN. COORDINATE
EXACT SIZE AND QUANTITIES OF CONDUCTORS WITH APPROVED GENERATOR SHOP
DRAWINGS PRIOR TO COMMENCING WORK.
SAME AS DRAWING NOTE EXCEPT, GENERAL PURPOSE TYPE TRANSFORMER.
EXISTING FEEDERS TO REMAIN SHALL BE HIGH-PRESS SPLICED IN SPLICE BOX AND EXTENDED
TO NEW DISTRIBUTION PANEL AS SHOWN. NEW FEEDER CONDUCTORS/CONDUIT SHALL
MATCH EXISTING.
FURNISH AND INSTALL #3/0 GROUND CONDUCTOR IN 1 INCH C. FURNISH AND INSTALL
CADWELD GROUNDING CONNECTION TO THE MAIN BUILDING GROUNDING SYSTEM.
NEW 50A, 3 POLE, 65 KAIC ENCLOSED CIRCUIT BREAKER.
FURNISH AND INSTALL 2#12, 1/2"C. TO ELEVATORS #1 & 3 CONTROLLERS(FOR NOTIFICATION TO
ELEVATORS #1 & 3 CONTROLLERS FOR ELEVATORS #1 & 3 TO COME DOWN TO FIRST FLOOR
AND CEASE OPERATING UPON LOSS OF NORMAL POWER PROVIDE NECESSARY RELAYS AND
CONTACTS IN ATS #3. ELEVATORS #2 ARE EMERGENCY ELEVATORS AND SHALL CONTINUE TO
OPERATE AFTER LOSS OF NORMAL POWER.
FURNISH AND INSTALL NEW AUTOMATIC TRANSFER SWITCH. REFER TO SPECIFICATIONS.
MOUNT ON NEW 4 INCH HOUSEKEEPING PAD. PROVIDE AN ENGINE GENERATOR EXERCISING
TIMER INCLUDING ASSOCIATED WIRING IN ACCORDANCE WITH NFPA-110, CHAPTER 4-2.5.9.
FURNISH AND INSTALL HIGH-PRESS SPLICE IN SPLICE BOX AND EXTEND EXISTING BUILDINGS 22 AND 23
FEEDERS AS REQUIRED TO RECONNECT TO NEW SWITCHBOARD EDP.
FURNISH AND INSTALL SURGE PROTECTION DEVICE. SEE SPECIFICATIONS. CONNECT WITH 4
NO. 10, 1 NO. 10 E.G. - 3/4 INCH C. MAXIMUM LENGTH OF CONDUCTORS SHALL NOT EXCEED 18
INCHES.
FURNISH 100% RATED BREAKER.
SWITCHBOARD SHALL BE FRONT AND SIDE ACCESSIBLE.
17 FURNISH 1200A SUB-FEED LUG KIT.
18 FURNISH AND INSTALL 1200A, 100% RATED, DUAL PURPOSE LOAD BANK/ GENERATOR DOCKING STATION -
TRISTAR DBD5-125W-LMF-ACIKP OR APPROVED EQUAL. LOAD BANK BREAKER SHALL BE EQUIPPED
WITH SHUNT TRIP CONNECTED TO ENGINE START CIRCUIT WITH 2 NO. 12, 1 NO. 12 E.G. IN 1/2 INCH C.
LSIA
LSI LSI LSI LSI LSI LSI LSI
EXTERIOR
K
ST
K
ELECTRONIC TRIP UNIT DESIGNATIONS
L = LONG TIME PICKUP & DELAY
S = SHORT TIME PICKUP & DELAY
I = INSTANTANEOUS
G = GROUND FAULT
A = GROUND FAULT ALARM
19 DENOTES KIRK KEY INTERLOCK.
20 DENOTES SHUNT TRIP.
21 FURNISH AND INSTALL ESSENTIAL FIRE PUMP FEEDER CONDUIT/WIRE
ENCASED IN 2 INCHES OF CONCRETE OR FURNISH AND INSTALL UL LISTED
2-HOUR FIRE RESISTIVE CABLE.
22 ELECTRICAL CONTRACTOR SHALL TRACE OUT EXISTING CONDUIT/FEEDER
PATHWAY AND REROUTE IF IN CONFLICT WITH NEW CONSTRUCTION.
3rd FLOOR
2nd FLOOR
4th FLOOR
QL4N
5th FLOOR
QL5N
LH1N LL1N
QL1K QL1K1
CH5S
T- C5S
T- C4S
T-
1LN
T-
1QM
30 KVA
30 KVA
ATTIC
TO
LDP
ELECTRICAL
NORTH ELECTRICAL ROOM
NORTH ELECTRICAL ROOM
NORTH ELECTRICAL ROOM
15 KVA 45 KVA
EXISTING
TO REMAIN
EXISTING
TO REMAIN
CL5S1
CL4S2
LH5NCL5S2QL5S
CL4S1CH4S
NORTH ELECTRICAL ROOM
1st FLOOR
QL4S
TO CDP
ROOM 1B-115A ROOM 1B-115A ROOM 1B-115A
QH5NQH5S
12 12 12
NORTH
ROOM
ELECTRICAL
NORTH
ROOM
T- Q5N
30 KVA
TO QDPTO QDP
T- Q5S
30 KVA
CH5N
T- C5S
T- C4N
30 KVA
30 KVA
CL5N1
CL4N2
CL5N2
CL4N1CH4N
TO CDP
TO
LDP
LH5S
QH2N
QL3NLH3N
T- C2S
T- C3S
T- Q2N
30 KVA
30 KVA 30 KVA
TO CDP
CL3S2CL3S1QL3S
CL2S CL2N
CH3S
CH2S QL2NCL2W2CL2W1
TO
LDP
T- Q2S
30 KVA
QL2SQH2S
T- C3N
30 KVA
CL3N2CL3N1CH3N
TO QDP
CH2N
T- C2N
30 KVA2nd FLOOR
LL5N
T- L5N
30 KVA
LL3N
T- L3N
30 KVA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
BAY PINES VAMC
INPATIENT AND OUTPATIENT
IMPROVEMENTS
BAY PINES, FL
FULLY SPRINKLERED
516CA2005
U.S. Department of Veterans Affairs
BID - CONSTRUCTION
DOCUMENTS
CONSULTANT
Stantec/AECOM LLC.
4798 New Broad St., Suite 200
Orlando, FL 32814
(312) 554-1400
B1
CONSULTING ENGINEERS EB-0001160
2609 W. DE LEON STREET, TAMPA, FLORIDA 33609
TELEPHONE: (813) 874-9494
FAX: (813) 874-9794
CARASTRO &
ASSOCIATES, INC.
Approved: PROJECT DIRECTOR
/9
/2
:5
:3
P M
NJ BH/AN
EP 603
POWER RISER DIAGRAM (ESSENTIAL)
04/21/20 No: Revisions: Date:
1 Issued for Bid 04/21/20
2 ADDENDUM 1 01/21/21
| Sheets |
| EP 603 - POWER RISER DIAGRAM (ESSENTIAL) |
| Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. | |
| 2021-04-09T17:05:21-0400 | |
| Nathan R. Jones, P.E. on | |
| Nathan R. Jones, P.E. | |
| This item has been digitally signed and sealed by |
File details come from the government source that posted it. Updated .