VBA B10_MH400 HVAC Schedules - Addendum 1.pdf
PDF 187 KB Posted
- Attached to
- Y1AZ--Renovate Building Number 10 Veterans Benefits Administration Office Space, West Palm Beach, FL.
- Solicitation number
- 36C10E21R0006
About this file
This pre-solicitation notice describes a forthcoming solicitation for renovation services. The Veterans Benefits Administration will solicit proposals to renovate approximately 1,900 square feet of office space at their facility in West Palm Beach, Florida. Renovations will include demolition and construction of new electrical, HVAC, data/voice systems, and interior finishes. The solicitation number will be 36C10E21R0006, with offers due by July 16, 2021 at 4:30 PM CST. The project value is estimated between $5-10 million. The NAICS code is 236220 and small business size standard is $36.5 million. The acquisition has been set aside for a Total Service-Disabled Veteran Owned Small Business. The period of performance is expected to be approximately 90 days from notice to proceed. Offerors must register in SAM.gov and complete online representations and certifications. The point of contact is provided.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V B
A
W P
B B u ild in g
R e n o v a ti o n D e s ig n /W
P B
B u ild in g
R e n o v a ti o n
V
M E
P .r v t
/3
/2
:4
:2
P
M
AW DAW
VB3239
MH400
548 - WEST PALM BEACH
JULY 9, 2021
10-
HVAC SCHEDULES 100% FINAL CONSTRUCTION
DOCUMENTS
WEST PALM BEACH BLDG. 10
RENOVATION
TOTALS 1,617 150 29,907 8,765 5,332 1,563 6,887 2,018 1,488 702 970 720 1,540 727 1,740 821
AHU-1 135 OFFICE 118 11.0 9 2.7 VAV 1661 486.9 310 90.9 136 39.7 83 39 4 20.5 71 53 4 83 39 130 61 90 32 EXHAUST VAV 0
AHU-1 131 OFFICE 118 11.0 9 2.7 VAV 1661 486.9 310 90.9 136 39.7 83 39 4 20.5 71 53 4 83 39 130 61 90 32 EXHAUST VAV 0
AHU-1 130 OFFICE 118 11.0 9 2.7 VAV 1661 486.9 310 90.9 136 39.7 83 39 4 20.5 71 53 4 83 39 130 61 90 32 EXHAUST VAV 0
AHU-1 128 OFFICE 118 11.0 9 2.7 VAV 1661 486.9 310 90.9 136 39.7 83 39 4 20.5 71 53 4 83 39 130 61 90 32 EXHAUST VAV 0
AHU-1 126 CORRIDOR 160 14.9 9 2.7 VAV 1042 305.4 0 0.0 184 53.9 44 21 4 20.5 96 71 4 96 45 100 47 90 32 EXHAUST CV +
AHU-1 125 LOBBY 160 14.9 9 2.7 VAV 3544 1038.7 417 122.2 910 266.8 167 79 4 20.5 96 71 4 167 79 170 80 90 32 EXHAUST VAV 0
AHU-1 132 SUPERVISOR OFFICE 110 10.2 9 2.7 VAV 2019 591.6 335 98.2 692 202.8 99 47 4 20.5 66 49 4 99 47 100 47 90 32 EXHAUST VAV 0
AHU-1 133 WORK AREA, COPY 485 45.1 9 2.7 VAV 8437 2472.8 1724 505.2 2414 707.5 429 203 4 20.5 291 216 4 429 203 430 203 90 32 EXHAUST VAV 0
AHU-1 134 CONFERENCE ROOM 230 21.4 9 2.7 VAV 8220 2409.2 1616 473.7 2145 628.6 415 196 4 20.5 138 102 4 415 196 420 198 90 32 EXHAUST VAV 0
SF M² FT M VAV / CV BTUH W BTUH W BTUH W CFM L/S ACH dT CFM L/S ACH CFM L/S CFM L/S F° C° VAV / CV (+) / (-) / (0)
AREA HEIGHT
SYSTEM
TYPE
SENSIBLE LATENTAHU NO. ROOM NO ROOM NAME
ROOM SIZE
AHU PEAK ROOM COOLING LOAD
PEAK ROOM HEATING
LOAD
CALCULATED ROOM AIRFLOW REQUIRED ROOM AIRFLOW
SELECTED DESIGN
ROOM AIRFLOW
SELECTED DESIGN
ROOM MINIMUM
AIRFLOW
DESIGN REHEAT
TEMPERATURE ROOM AIR
RETURN,
EXHAUST
ROOM STATUS
ROOM AIR
BALANCE
ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE: 1-AHU-01
ALL ROOMS 75 [ 24 ] 51.5 [ 11 ] 50 70 [ 21 ] 32.6 [ ] 25
INDOOR AREA DESIGN CONDITIONS
OUTDOOR DESIGN
CONDITIONS
91.4 [ 33 ] 77.6 [ 25 ] 75 43.9 [ 7 ] 43.9 [ 7 ] NA 43.9 [ 7 ]
°F [°C] °F [°C] °F [°C] °F [°C] °F [°C]
TEMP WET BULB TEMP
HUMIDITY
TEMP DEWPOINT TEMP
HUMIDITY
DESIGN CONDITIONS
SUMMER WINTER
LOWEST AVERAGE
ANNUAL DEWPOINT
HVAC DESIGN DATA
9. PROVIDE WITH REMOVEABLE SP300 AIRFLOW SENSOR.
8. PROVIDE SOUND ATTENUATION AFTER-SECTION AS REQUIRED TO MEET ROOM NC LEVEL. MAXIMUM DISCHARGE AIR AND RADIATED SOUND OF 27 NC.
7. INLET STATIC BASED ON ARI 885-98. TOTAL AIR PRESSURE LOSS OF TERMINAL UNIT AND REHEAT COIL SHALL NOT EXCEED 0.40" WC.
6. FIBER-FREE FOAM INSULATION OR FOIL FACED INSULATION.
5. ELECTRIC REHEAT AIRFLOWS TO BE SET TO MEET THE MANUFACTURERS REQUIREMENTS FOR PROPER OPERATION. INCLUDE MINIMUM HEATING AIRFLOW RATES WITH SUBMITTALS. NOTED "KW" VALUES ARE MINIMUM OUTPUT VALUES. PROVIDE COIL TO MEET OR EXCEED NOTED "KW" VALUE. PROVIDE SCR
CONTROL.
4. REHEAT COIL TO BE INTEGRAL OR DUCT MOUNTED NEAR AIR TERMINAL DISCHARGE AS REQUIRED TO MEET PERFORMANCE SPECIFICATIONS, OR SELECT THE NEXT LARGEST TERMINAL UNIT SIZE. PROVIDE MULTIPLE ROW COIL AS REQUIRED.
3. DIGITAL CONTROLLED AND PRESSURE INDEPENDENT. ACTUATORS AND CONTROL ACCESSORIES BY CONTROLS CONTRACTOR. CONTROL DEVICE VOLTAGE OUTPUT DETERMINED BY CONTROLS CONTRACTOR OR EXISTING AUTOMATION SYSTEM. CONTROL SEQUENCE SHALL BE AS INDICATED ON THE AIR
TERMINAL UNIT SCHEDULE.
2. THIS SCHEDULE IS USED WITH THE TERMINAL UNIT SCHEDULE.
1. THIS SCHEDULE IS A PERFORMANCE SPECIFICATION ONLY. CONTRACTOR SHALL COORDINATE FINAL SELECTIONS TO MEET OR EXCEED PERFORMANCE.
NOTES:
1-TU-1-8 135 135 AHU-1 6 150 VAV 130 61 80 38 80 38 40 19 0.6 150 0.3 75 55 13 90 32 3.1 1.0 277 1 SEE NOTES PRICE - SDV NOTES 1 -9
1-TU-1-7 131 131 AHU-1 6 150 VAV 130 61 80 38 80 38 40 19 0.6 150 0.3 75 55 13 90 32 3.1 1.0 277 1 SEE NOTES PRICE - SDV NOTES 1 -9
1-TU-1-6 130 130 AHU-1 6 150 VAV 130 61 80 38 80 38 40 19 0.6 150 0.3 75 55 13 90 32 3.1 1.0 277 1 SEE NOTES PRICE - SDV NOTES 1 -9
1-TU-1-5 128 128 AHU-1 6 150 VAV 130 61 80 38 80 38 40 19 0.6 150 0.3 75 55 13 90 32 3.1 1.0 277 1 SEE NOTES PRICE - SDV NOTES 1 -9
1-TU-1-4 125 125 AHU-1 8 200 VAV 270 130 200 94 200 94 100 47 0.6 150 0.3 75 55 13 90 32 7.8 2.5 277 1 SEE NOTES PRICE - SDV NOTES 1 -9
1-TU-1-3 132 132 AHU-1 6 150 VAV 100 47 70 33 70 33 40 19 0.6 150 0.3 75 55 13 90 32 2.7 1.0 277 1 SEE NOTES PRICE - SDV NOTES 1 -9
1-TU-1-2 133 133 AHU-1 9 230 VAV 430 200 300 140 300 140 150 71 0.6 150 0.3 75 55 13 90 32 11.7 3.5 277 1 SEE NOTES PRICE - SDV NOTES 1 -9
1-TU-1-1 134 134 AHU-1 7 180 VAV 420 200 140 66 140 66 70 33 0.6 150 0.3 75 55 13 90 32 5.4 1.5 277 1 SEE NOTES PRICE - SDV NOTES 1 -9
IN [mm] CFM [L/s] CFM [L/s] CFM [L/s] CFM [L/s] IN WG [Pa] IN WG [Pa] °F [°C] °F [°C]
MBH MODEL NUMBER
SERVED HANDLING SIZE (VARIABLE/
CONSTANT)
COOL HEAT FLOW OA PRESSURE APD MIN CAP. KW VOLT PH AND
MARK LOCATION AREA / ROOM SYSTEM AIR DUCT INLET CONTROL MAX. MAX. MIN MIN MIN INLET MAX EAT LAT ELECTRICAL MANUFACTURER NOTES
SYSTEM AIRFLOW ELECTRIC HEATING COIL
ADDITIONAL
SOUND
ATTUNATION
REQUIRED
DESIGN BASIS
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE
1. PROVIDE SQUARE TO ROUND ADAPTER.
NOTES:
RG-25 PERFORATED 320 [ 150 ] 500 [ 240 ] 0.087 22.000 CEILING 24 x 24 [ 600 x 600 ] 14 DIAM [ 356 DIAM ] 14 NONE WHITE -----
RG-22 PERFORATED 110 [ 52 ] 170 [ 80 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 8 DIAM [ 203 DIAM ] 13 NONE WHITE -----
RG-21 PERFORATED 60 [ 28 ] 100 [ 47 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 6 DIAM [ 152 DIAM ] 13 NONE WHITE -----
CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]
MIN MAXMARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKS
AIR DEVICE SCHEDULE (RETURN)
3. PROVIDE SQUARE TO ROUND ADAPTER.
2. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.
1. SEE FLOOR PLAN FOR THROW PATTERN.
NOTES:
SD-12 LOUVERED FACE 70 [ 33 ] 280 [ 130 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 8 ø [203 ø] 23 NONE WHITE -----
SD-11 LOUVERED FACE 40 [ 19 ] 160 [ 76 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 6 ø [152 ø] 19 NONE WHITE ----
CFM [L/s] CFM [L/s] IN WG [Pa]
MIN MAX
IN x IN [mm x mm] IN [mm ]
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKS
AIR DEVICE SCHEDULE (SUPPLY)
Revisions: Date:
Addendum #1 7.16.21
| Sheets |
| MH101 - FIRST FLOOR PARTIAL PLAN - HVAC |
| MH400 - HVAC SCHEDULES |