This document provides details for a federal contract opportunity to renovate office space for the Veterans Benefits Administration. The scope of work involves renovating approximately 1,900 square feet of office space and includes demolition and construction of electrical, HVAC, data/voice systems, and interior finishes. The performance location is a Veterans Affairs medical center in West Palm Beach, Florida. The solicitation number is 36C10E21R0006 and offers are due on July 16, 2021. The procurement will be a firm-fixed price contract awarded to a single awardee. The project is set aside for total service-disabled veteran owned small businesses and has a NAICS code of 236220 with a small business size standard of $36.5 million. The estimated project magnitude is between $5-10 million and the period of performance is approximately 90 days following notice to proceed.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIGHTING GENERAL NOTES
SCOPE OF WORK
F E
C
FEC
D
D
D
D
DD
DD
DD
D
D
D
KEYNOTES
1. ELECTRICAL CONTRACTOR SHALL PULL UNSWITCHED LEG FOR CONNECTION OF
EMERGENCY/EXIT LIGHTS.
2. CIRCUIT ALL EXTERIOR LIGHTING THROUGH ONE PHOTOCELL RELAY PER
CIRCUIT.
3. REFER TO ARCHITCTURAL LAYOUT FOR LOCATION OF EXIT LIGHTS.
4. ALL LIGHT FIXTURES MAY HAVE AN EQUAL BUT REQUIRE APPROVAL BY
ENGINEER AND OWNER. ALL LIGHT FIXTURE PRIOR APPROVALS MUST BE IN
WRITING. THE ENGINEER RESERVERS THE RIGHT TO REQUIRE “TABLE TOP”
TESTING OF ANY FIXTURE SUBMITTED AS AN EQUAL.
5. ALL LIGHTS MOUNTED IN EXPOSED STRUCTURE AREAS SHALL BE FINISHED
BLACK.
6. ALL RECESSED LIGHTING FIXTURES MUST BE INSTALLED TO PROVIDE A NON-
COMBUSTIBLE FIRE RATED ASSEMBLY.
7. COORDINATE ALL LIGHT FIXTURE MOUNTING REQUIREMENTS WITH REFLECTED
CEILING PLAN PRIOR TO RELEASE OF FIXTURE.
8. ELECTRICAL CONTRACTOR SHALL NOT SHARE NEUTRALS, UNLESS
SPECIFICALLY NOTED OTHERWISE. ALL LIGHTING CIRCUITS SHALL HAVE A
SEPARATE INSULATED GROUNDING CONDUCTOR INSTALLED WITH EACH
CIRCUIT.
9. FOR ACTUAL LOCATIONS OF CEILING MOUNTED FIXTURES AND EQUIPMENT SEE
ARCHITECTURAL REFLECTED CEILING PLANS.
NO SCOPE OF WORK ASSOCIATED
WITH THIS AREA
SCOPE OF WORK AREA AS
DESIGNATED/NOTED
A2
A8
A2
A10
A3 A3 A3
C1
A4
A11
A8
A9
A7
A1
B1 B1
B1
B1 B1 B1
A5
A3 A3
OS
RC101
RC101
OS
OS
PPK
PPK
OS
PPKOS
O S
PPK
O S
A2
J
SLV
NS
NS
A3
PPK
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
Spinklered
Office of Construction and Facilities Management
PLAN NORTH
FULLY SPRINKLERED
AREA OF
WORK
BLDG 10
KEY PLAN
B
IM
/V B
A
W P
B B u ild in g
R e n o v a ti o n D e s ig n /W
P B
B u ild in g
R e n o v a ti o n
V
M E
P .r v t
/3
/2
:3
:4
P
M
JK DAW
VB3239
EL101
548 - WEST PALM BEACH
JULY 9, 2021
10-
FIRST FLOOR PARTIAL PLAN - LIGHTING 100% FINAL CONSTRUCTION
DOCUMENTS
WEST PALM BEACH BLDG. 10
RENOVATION
3/8" = 1'-0"
FIRST FLOOR PARTIAL PLAN - LIGHTING
EXT
EXT
EXT
1 PROVIDE WATTSTOPPER LMDI-100-U SERIAL DATA INTERFACE TO INTERLOCK THE
LIGHTING CONTROL SYSTEM TO THE AV SYSTEM TO CONTROL LIGHTING WITHIN THE
CONFERENCE ROOM. CONTRACT TO COORDINATE WITH THE LIGHTING CONTROLS
MANUFACTURER AND AV PROVIDER.
2 ROUTE 2-#12 AND 1-#12 E.G. IN 0.75” CONDUIT AND CONNECT TO AVAILABLE CIRCUIT
BREAKER IN PANEL “NH2”
Revisions: Date:
Addendum #1 7.16.21