This document is a Request for Proposals (RFP) for the construction of a Maintenance Shop at the Smithsonian Tropical Research Institute facility in Gamboa, Panama. The Smithsonian is seeking proposals for a fixed-price construction contract with a budget estimated up to $1.2M. The applicable NAICS code is 236220 Commercial and Institutional Building Construction. The selected contractor must have a Unique Entity ID and be registered in the SAM system. The contractor must be legally registered and licensed to operate as a construction company in Panama for at least 5 years and have performed at least three construction projects valued at $1M or more in the past 3 years. Proposals are due by July 12, 2024 at 3:00 PM EST. The project must be completed within 270 calendar days from the notice to proceed. The document provides details on the facility, site access, and the questions and clarifications process.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

# Discipline Reference Query SF Reply Attachment

1 Schedule of Value Document 1680001

Maintenance Shop Bid Sch

The actual document only shows division items (33). The Query is that if You will Provide an broad Schedule of Values (as per previous bid in 2021)?. If answer is no. Are we allowed to expand it, or is mandatory to offer showing only those 33 Divisions?

No, you don’t have to submit a breakdown of prices; just present your proposal in one single value for each listed Division in the Schedule of Values document. Bidders need to submit proposals only in this format.

2 Drawings Document IFC_Gamboa_Maint

Shop_Drawings Can you supply it in DWG Format?. There is more precission to measure distance and areas. DWG drawings will be provided during construction.

3 Permits Scope of Work Does the project have an active construction permit? If yes, is this permit for the whole project or only the foundations and structure phase? Please share the construction permit information so we can properly estimate the costs of municipio, mitradel and safety plan transfer.

The construction permit is currently under the name of a contractor.

The transfer of this permit will need to be processed by the bidder.

4 Insurance Scope of Work Does the project have an active CAR insurance or should it be included as part of our scope? No, bidder must include it in the scope.

5 Scope Plan A-101 Plan indicates an Existing Sidewalk and Shed to Remain and Complete. Please share plan and detail for the metallic shed structure and foundations. Please indicate length of shed to complete, there is no mention in plans of existing shed location.

Refer to the attachment. RFI 5 - Shed Location

6 Electrical Plan E-100

In the electrical drawings there are no details or distances for the electrical or telecommunications connections to the existing electrical room in the Main Laboratory. Please share a plan with distances and details of the electrical room, so we can estimate the connection between the duct bank and the corresponding panelboards.

Distance estimation shall be done by the contractor. Attached reference floor plans.

RFI 6 - Electric duct beam

7 DIV 05 METALS

051200

2.8B What type of treatment will be required for the rusted steel structure on site?All paint will be removed?

Refer to Existing Metal Structure Notes & Notes for Metal Coating located on sheet A602 & S301, for the treatment to consider on the bid price.

8 DIV 03 CONCRETE

033000

3.2

Existing anchor bolts in the concrete foundations look rusted and seem to have lost the steel body.

Will the existing bolts remain? What treatment will be required for the existing anchor bolts, if left in place.

Existing Anchor bolts in concrete foundations to remain in place. Refer to note 1 on sheet S506 for instructions regarding the treatment to consider on the bid price. If during the execution is discovered that any bolt require to be replaced, will be evaluated in a RFI and further instructions provided in response.

9 DIV 03 CONCRETE

033000 3.14C

We will we receive quality control report of all concrete and steel cast-in place on site? Will we receive quality control report of all steel members fabricated and delivered to site?

It will be provided during construction.

10 DIV 05 METALS

055000

3.1 A,B

We cannot verify all dimensions of all the steel members on site to confirm that all pieces will fit together without field adjustments. Will field adjustments be permitted? Will field adjustments be considered extra work as we cannot quantify this work at the present time?

Refer to notes included on sheet S301 (Existing Metal Structure) & S201 (below the isometric), for the parameter to consider on the bid price.

The price should consider that this adjustments will be executed on site, as no major adjustments are forthseen at this time. If during the execution, a major adjustment in any element is required, will be evaluated in a RFI and further instructions provided in response.

Smithsonian Institution Office of Planning, Design and Construction Construction Division

STRI BRANCH

DATE: July 05, 2024 PROJECT NAME: Maintenance Shop at Gamboa - Santa Cruz PROJECT LOCATION: Gamboa PROJECT No.: 1680001

REQUEST FOR INFORMATION FINAL RESPONSE

DIV 01 GEN.

REQUIREMENTS

010000

31.1 Will STRI provide a list of existing approved submittals/materials to consider for use on the Project?

(i.e. Concrete blocks, mortar mix, ready mix concrete, steel fabricator, etc.)

It will be provided during construction.

DIV 01 GEN.

REQUIREMENTS

During the May 20th meeting with potential participants STRI briefly discussed evaluation factors.

There was mention of a type of Sealed Bid process for the price proposal, which Smithsonian Institution in Washington (SI) would review, while highlighting that a past performance factor would also be reviewed by STRI Panama. Please specify whether this solicitation will request a sealed bid response (based on best price only) or if a technical/management evaluation will be made in tandem. If selection is dependent on factors beyond price alone, please specify the additional evaluation factors, the selection criteria, and whether/how each factor will be weighted overall.

Refer to solicitation, Section M - Evaluation Factors for Award

DIV 01 GEN.

REQUIREMENTS

What type of contract is STRI contemplating for award? i.e., FFP, CPFF, T&M, other. Will it be based on the Federal Acquisition Regulations (FAR)?

Fixed Price construction contract. Yes it will be based on the FAR

DIV 01 GEN.

REQUIREMENTS

Please advise on the process and timeline for contract award?

The award time will depend on the availability of OCON (contract office), however, it must be awarded before September 30.

DIV 01 GEN.

REQUIREMENTS

What process/framework will STRI follow under the awarded contract for Change Orders? As per contract clauses.

DIV 01 GEN.

REQUIREMENTS

In the past STRI has relied on in-house and third-party inspectors to determine acceptability of the work completed. Who will be responsible for acceptance criteria of the work under this contemplated award?

SI is responsible for the contract and COTR will be responsible for the acceptance criteria of this contract.

DIV 01 GEN.

REQUIREMENTS

33330224RF0010029 RFP

A-Solicitation/Contract form

52.211-10

Contract time:

Solicitation / Contract Form , Section A, 52.211-10 states 485 calendar days Solicitation/ Contract Form, Section C (Description/Specification) states 270 calendar days Division 01, General Requirements, 3.1 states 270 calendar days.

Please clarify the contract time, as we have two different times in the documents.

270 calendar days

DIV 01 GEN.

REQUIREMENTS

Solicitation/Contract form section D

Solicitation /Contract Forms : Instruction, Conditions and Notice to Bidders Plan of Accomplishment:

When is the due date to upload the Plan of Accomplishment?

The plan of accomplishment shall be included in the technical proposal.

Due date is july 12.

DIV 01 GEN.

REQUIREMENTS

General requirements, paragraph 4.3 and 4.4

Division 01 – General requirements Section 4 (Schedule of Unit Prices) Paragraph 4.3 and 4.4 refer to “unit prices shall include all direct and indirect costs, overhead, taxes, insurance and profit”. Line items on the bid schedule provided has the overhead and profit in a separate line item as well as the performance bond. There seems to be a contradiction if line items, for future reference, must have the overhead and Profit included as per paragraph 4.3 and there is a separate line item for overhead and profit and another line item for performance bond.

We also want clarification on paragraph 4.4 where it states that “unit prices shall be binding upon the Contractor for the duration of the Project”. What unit prices are we referring to?

Schedule of values was updated by removing overhead and profit and performance bond lines. Extras will be evaluated as indicated in the contract.

DIV 01 GEN.

REQUIREMENTS

31.3

Expand definition of shop drawings and scope. Indicate if the plan is not properly developed, it will be up to the contractor to finish developing the design through a "shop drawing."

Shop drawings are detailed plans that translate design intent. They provide the information necessary to manufacture, assemble and install all the components; Ensuring that the final product aligns with the designer’s vision, meets all relevant specifications and coordinate all the related trades as well as adjust as necessary to the existing conditions and any unforthseen condition.

The primary purpose of shop drawings is to translate design intent into actionable more precise information. They serve as a communication & coordination tool, facilitating a clear understanding of the intricate details and specifications outlined in the architectural and engineering plans. Shop drawings help ensure that the final product meets safety standards, design criteria, and client expectations.

As requested in the project specifications, the contractor is responsable to porvide shop drawings for all trades.

21 DIV 03 CONCRETE

033000 Cast-in-place concrete

Paragraph 1.9 B “hot-weather placement”

Hot-weather placement of concrete:

States “maintain concrete temperature below 90 deg F (32 grad C) at time of placement” ACI 318 S- 19 cap 26 R 26.5.5.1 and ACI 301 S-10 Sec 4 4.2.2.6, allows max temperature of concrete to be 35 deg F (95 deg C) at the time of placement. Clarify if 90 deg F temeperature is a mandatory requirement for this Project.

contractor shall comply with ACI.

22 DIV 05 METALS

051200 Structural Steel Framing

Paragraph 1.7 B. “Installer Qualifications”

The requirement for a AISC-Certified Erector, category CSE to perform the work is mandatory?

Please clarify.

Does not apply to this project. The contractor must submit the subcontractor's for this task and their qualifications including suitability.

23 DIV 05 METALS

051200 Stuctural Steel

Framing

All steel members are on site, and will be treated and re-painted on site.

Is this shop-painting applicator requirement no longer applies? Please clarify.

What is the extent the government expects on the site to comply with shop painted material. What are going to be the goverment requierements be to perform this on the site (humidity control, heat treatment...)

The contractors have to consider in the Bid Price that all the steel members that are currently on site will be treated and re-painted on site. Any new steel element, for ex. an element not in the inventory, shall comply with the shop-painting applicator requirements.

There will be no special environmental control requirements, just follow good practices for the application the finishe paint and anti-corrosion treatment of the products, following the recommendations of their manufacturers.

24 DIV 05 METALS

Section 053100 Steel Decking Paragraph 1.5 A Testing Agency Qualifications

States “qualified according to ASTM E329 for testing indicated”. Please clarify what testing is required under this section? Ommit Section 053100. Steel Decking is not on the scope of the project.

25 DIV 05 METALS

Section 053100 Steel Decking.

Section 2.2 A Manufacturers Please clarify if local suppliers of decking material will be acceptable (ie. Metales, Correagua)

Steel Decking was eliminated from this project, please omit section 053100. For the Standing seams system refer to section 076119. Refer to acceptable manufacturers on the point 2.1-C of this section.

DIV 32 EXTERIOR

IMPROVEMENTS

Section 321313 - Concrete Paving Paragraph 2.9 B.1

“Compressive strength (28 days): 4000 psi (27.6 MPa)” MOP requirement for pavement strength is 650 psi flexural strength which is roughly 5000 psi compressive strength. Please clarify which concrete strength is required for the pavement. DWG C- 1-0(6 OF 59) dETAIL 10/C-103 states 650 @ PSI @ 28 days de flexion.

Comply with 4000psi per specs.

27 DIV 05 METALS

Submittal 051200-seobra-073, dated 27 july 2022

(disapproved) Submittal 051200- seobra-

023a, dated 06 july 2022(disapproved)

Submittal 051200-seobra- 023b, dated 04 august 2022

(disapproved) Consultest report CO-AGA-01

Consultest report Code AGA-07

Based on the submittals and reports, confirm that all steel members fabricated and located on-site are approved as far as shop-welding;. and no additional submittals or testing are required for the welds of the steel members fabricated.

Confirmed.

28 DIV 22 PLUMBING

DWG S-1-101 (25 of 59) Det

1/S101: Ditch Detail Please indicate specification for sump drain. Zurn EZ-6 or similar.

29 DIV 22 PLUMBING

DWG S-1-101 (25 of 59) Det 1/S101: Ditch Detail + P-1-

01(42 of 59)

Dwg S-1-01 states that following the sump drain you install a 6” pvc pipe (and refers to plumbing sheets). Plumbing sheet P-1-101 page 42 of 59) shows 4” diameter pipe coming out of the ditch.

Clarify if 4” or 6” is required to connect the sump drains with the zurn oil interceptor.

4" pipe as indicated on sheet P-101.

30 DIV 22 PLUMBING DWG C-1-01 (4 of 59) Open drain at north-west corner of existing building states that drain “termination en zampeado de

1.5 m “. Provide detail of “zampeado” required. Refer to the attachment. RFI 30 - Zampeado

31 DIV 22 PLUMBING

DWG A-1-01 (9 of 59) “Canal rectangular con parrilla”

“Canal rectangular con parrilla”. Dimensions for the concrete drain are described. No detail is given for the grate over the drain

The exterior grilles to be the same type as the interior: Class D400 FUCASA. Dimensioned accordinly to the Trench opening for each use.

32 DIV 22 PLUMBING

DWG P-1-01 "Plumbing ground floor plan" Please confirm what underground piping has been installed (if any). No underground piping related to this project has been installed.

33 DIV 22 PLUMBING

Should the existing plumbing installations be demolished and everything new installed (buried and non-buried pipes)?

Correct. All the existing plumbing shall be removed/demolished and everything indicated in plumbing plans to be new unless otherwise indicated, as existing.

34 DIV 22 PLUMBING C-1-01

Is the supply and connection of the water meter the responsibility of the mechanical contractor or the project owner?

The Supply and connection of the water meter will be responsability of the contractor, so it should be included in the price.

DIV 23 HEATING

VENTILATION AND A/C

P-1-01 Are the A/C condensing units going to be hung on the wall or on the floor?

AC condensing units to be hung on the wall, following the "detail - wall mounting for mini-split condensers" located on sheet P-101. The application of each detail will be subject to the final position of the equipment in regards to the conditions and respecting a minimun of 7 feet of free height below any of the support elements.

DIV 23 HEATING

VENTILATION AND A/C

P-1-01 Can the extraction fans indicated in the box be of a different brand than the one described?

Models and brands indicated on the equipment table located on sheet P101 are reference suggestions. If the contractor want to propose a replacement shall present it through a submittal that will be subject of review and approval. The submission should clarify the reason of the replacement and convalidating the features of the replacement with the equipment on design. The contractor shall consider that the replacement shall be equal or superior in terms of features and specifications.

DIV 23 HEATING

VENTILATION AND A/C

P-5-01 Refrigerant piping schematic.

A detail of a 7.5 ton central unit is indicated on a plan sheet, but not in the capacity table. There is no 7.5 ton unit in this project?

Correct. There is no 7.5 Ton central unit in this project.

DIV 01 GEN.

REQUIREMENTS

In the original documents on the SAM Website as per May 14th it was stated: "This is a Federal Funded Contract and the selected contractor must have an Unique Entity ID number and be actively registered and current in SAM System (https://sam.gov ) before award."

In ammendment dated June 6th this has been edited to : "This is a Federal Funded Contract and the selected contractor must have an Unique Entity ID number and be actively registered and current in SAM System (https://sam.gov )"

Question: Bidder must be registered at time of solicitation?

Yes, bidder must be registered in SAM at time of solicitation.

39 DIV 05 METALS DWG AD-1-01: Note No. 1 Define and include repair procedures and quantify for roof structure to be supply by STRI . To be able to quote appropriately.

For the exisitng concrete columns and beams to be repair, the contractor shall consider the second note located at Sheet S201.

Not Clear what Roof structure this comment refer to. Sheet AD-101, note 1, doesn’t indicate anything about roof structures.

New structures between axis 10 to 13.9, shall consider the inventory as elements already on site that STRI will provide to the contractor.

Between axis 7 to 10, exisitng structure to remain, only following the modifications indicated on sheet AD-101 & A-102. Additional instructions and procedure for the transition on axis 10 refer to sheet S- 301.

DIV 01 GEN.

REQUIREMENTS

15 Permits, licenses, & fees Determine if contract errants and pay permits to IDAAN are included in bid. Yes, all errants and pay permits to IDAAN shall be included in bid.

41 DIV 03 CONCRETE Detail and procedure for anchoring tie columns to the existing slab in the existing area. Refer to DT03 on sheet A301.

42 DIV 03 CONCRETE Procedure for repairing cracks in the existing concrete slab, define which product to use.

Filling cracks with flexible epoxy of high biscosity, mend floor and appy a layer of floor hardness mate color.

DIV 01 GEN.

REQUIREMENTS

Define the use of SHOP DRAWINGS. In the absence of details in the plans, determine if the responsibility lies with the designer or if the contractor will have to develop the details and improve the design during project execution. For all trades

Refer to reply of RFI #20.

DIV 23 HEATING

VENTILATION AND A/C

A-3-02 Define the model and size of wall fans. Refer to Fan Table on sheet P-101.

DIV 01 GEN.

REQUIREMENTS

Methodology for payment for extra work on the existing roof structure. KC suggests that it be done individually for each case and not estimated at 10% for the project, as it is not clear how much of the existing structure will need to be repaired, nor the methodology or scope of the repair.

This can be determinate after the award.

46 DIV 09 FINISHES Define the procedure for repairing the finish paint on the roof structure.

Refer to Existing Metal Structure Notes & Notes for Metal Coating located on sheet A602 & S301, for the treatment to consider on the bid price.

47 DIV 09 FINISHES A-4-01

Elevation 03-A-401. Include structural details, type of wood, model of handles, rails, baseboard, type of countertop (granite, silestone).

Contactor to provide shop drawing in compliance with Specs section 064116. Countertop finsh Rausolid or similar as indicated below notes at sheet A401.

DIV 01 GEN.

REQUIREMENTS

Based on the supplied plans, many construction details are missing. Will be asked to create shop drawings to complement the deficiencies in the plans.

Refer to reply of RFI #20.

49 DIV 09 FINISHES DWG A-6-01 Define the type of paint required for the door finish, color code, and required thickness.

Contractor to comply with Section 081113. Color code reference per Sherwin William Color Chart: Passive SW7064.

50 DIV 21 FIRE SUPRESSION

211313

1.16

Specification 211313 in point 1.6 requests different criteria that the design must comply with, however we are not designing, we are going to execute the design that is presented in the plans, confirm that the design meets everything requested at this point and that we will not have to make modifications to it.

The responsibility of the contractor is to provide shop drawings based on the design intention reflected on the construction documents, coordinating them with other trades, like other systems to be reflected on ceilings. If during the execution any modification is requested it will be reviewed and negotiated through a PCN.

51 DIV 21 FIRE SUPRESSION

211313

1.7

The specification in point 1.7 B requests that manufacturers' data and system calculations, water supply data and a complete set of work drawings must be submitted. Since the design has already been completed and will be installed according to the plans, do we need to submit hydraulic calculations and information on the water supply? The information on the hydraulic calculations is not found with the documentation sent for the preparation of the offer and the information on the water supply is indicated on plan F101.

Only manufacture's data and shop drawings will be requested. No hidraulic calculations are required to be provided by the contractror.

52 DIV 21 FIRE SUPRESSION

211313

2.2.

F.5

Specification 211313 in point F.5 indicates that we must place supports in accordance with NFPA 13, in the floor plans we can see anti-seismic supports indicated, but we do not see pipe restrainers indicated, because we are not the designers we request that If they are required, please indicate them in the positions that we must place them to include them in the budget.

Pipe Restrainers must be placed in compliance with applicable code, for example when there are changes of turns or at the end of branches.

53 DIV 21 FIRE SUPRESSION

211313

2.2.

N

In specification 212313 point N, it is indicated that we must provide passes for pipes that pass walls and that we must place fire seals in constructions with fire walls, but these passes and the fire resistance are not indicated on the fire protection drawings. Please indicate on the drawings the passes that require fire seals and their resistance.

The contractor shall estimate it, considering that all pipes that pass through a wall will have fire resistance seals acording to detail DT01 located on sheet A0001.

54 DIV 21 FIRE SUPRESSION 3.4C

Specification 212313 in point 3.4 C indicates that pipes in unfinished areas should only have one coat of anti-corrosion paint and that pipes in other areas should have 2 coats of paint similar to adjacent surfaces, in the drawing of the sprinkler system doesn’t show color, finish, or any other paint specification or requirements o if it is a special type of paint. No paint color is indicated, if any type of special paint or color is required, please indicate it on the sprinkler systems drawings so that it can be taken into account.

Anticorrosive paint color Red , refer to paint specs for additional indormacion.

55 DIV 21 FIRE SUPRESSION DWG F101

On drawing F101 there is the symbology of the sprinklers and there is no sprinkler with a special finish requirement. We are asking the Smithsonian if they will request any areas to have sprinklers with special finishes to be indicated on the drawing to take this into account for the proposal.

There are no special consideration for this project.

56 DIV 21 FIRE SUPRESSION DWG F101

In the notes on the fire system on drawing F001 it is indicated that air vents must be installed, as indicated in NFPA 13 ED 2016, 7.1.5 and 8.16.6. Reviewing the plan we see that in the floor plan F101 is not indicated, but in F601 in the one-line diagram an air relief valve is indicated. This is the only air relief valve that needs to be installed, if it is necessary to install another one please indicate.

Yes, as indicated on sheet F601. However, if the Contractor's proposal or model requires drain lines, it must be extended to the Shop Sink and redundancy must be considered.

57 DIV 21 FIRE SUPRESSION DWG F501, DWG F101

The drawing F501 show the detail of the sidewall and upright sprinkler with a protective cage, but when reviewing the floor plan where the symbology is located (F101), there is no indication of sprinklers guards. Indicate if there are any areas where sprinklers should have sprinkler guards to take this into account in the budget.

Consider Guards for sprinklers located on spaces without ceiling between axis 7 to 10. Electric Room & OIT Room also.

58 DIV 21 FIRE SUPRESSION DWG F501

The drawing F501 show a detail of a cabinet with an angle valve for firefighters in which only the cabinet and the valve are shown. Please clarify whether or not it is necessary to place a hose rack, hoses, or fire extinguisher in these cabinets.

It is not required as shown on desgin drawings.

59 DIV 22 PLUMBING C-1-01 Provide specifications for water meter. Water meter to be AWWA 2" and comply with IDAAN Regulations. RFI 59 - Medidor

60 DIV 21 FIRE SUPRESSION

F-0-01

H

Contractor’s interpretation is: The contractor responsibility is to bring to the government representatives attention to discrepancies in the drawings prior to BID. Due to the fact the government is providing material and work that has already been performed at the site. As well as shop drawings that were not approved from the previous contractor. The only responsibility is to install and construct the project as per the documentation received. The contractor cannot be responsible for any design flaws.

In regards to the note H at Sheet F001, related to Fire sprinkler system:

The contractor is responsible for preparing shop drawings to identify conflicts and in that case, if a conflict is found, solutions will be evaluated and, if a PCN is required, it will be negotiated.

Instructions and clarifications regarding the material and work that has been already performed at site, doesnt relate to the highlighted note.

61 DIV 21 FIRE SUPRESSION

F-0-01

B.2

Please elaborate on what is considered “obviously necessary” to complete the work and who is financially responsible for any material or labor which is neither shown on the drawings nor called for in the specifications

The highlighted note refers to works and materials that without them the task cannot be executed and the system could not operate according to the design intentions. Any element and work that doesn't fall into this description requested during the exceution will beevaluated and negotiated on a PCN.

62 DIV 21 FIRE SUPRESSION

F-0-01

D.1 Since work has already started we assume the Smithsonian has a construction permit, is it required for the new contractor to file to issue a new construction permit?

Refer to SI Reply to RFI #3.

63 Fire protection General Do you require a specific supplier for sprinkler work? No specific Supplier is required.

64 Electric General Do you require a specific supplier for fire alarm work?

All equipment must be Simplex. To date, the official supplier of this brand for the existing systems in these facilities is electrosystems; to avoid issues it should be considered the same.

65 Mechanics General Do you require a specific supplier for A/C work? No specific supplier is required.

66 Electric General Do you require a specific supplier for special systems work?

The wiring and installation of structured cabling and OIT equipment is not within the scope of this BID. Neither CCTV or CA. The scope of this Bid price is to provide empty conduits, boxes, cable trays, and all previsions for the instalation of the special systems. So at this time, no special system supplier shall be considered.

67 Structure General Existing o n - s i t e materials can be used (columns, beams, connections, blocks). Yes, exisisting site materials can be used.

68 Structure General Will the existing elements (columns, beams and connections) require an anticorrosive repainting?

Or will they be used painted as they are?

Refer to Existing Metal Structure Notes & Notes for Metal Coating located on sheet A602 & S301, for the treatment to consider on the bid price.

69 Structure General For this repainting, a cleaning of the element will be required. Does this cleaning require any kind of cleaning?

Refer to Existing Metal Structure Notes & Notes for Metal Coating located on sheet A602 & S301, for the treatment to consider on the bid price.

70 Structure General An inventory of the existing materials on site is requested in order to make a more precise proposal.

The only existing inventory has already been provided, for the other materials we cannot guarantee their integrity for use, this must be reviewed by the contractor.

71 Structure General If repainting is required on the metal elements, would it be required with a specific paint? Refer to Notes for Metal Coating on sheet A602.

72 Structure General Would it be necessary to rectify or make any repairs to the elements? If so, could these repairs be carried out on site? or must they be carried out in the workshop?

Refer to notes included on sheet S301 (Existing Metal Structure) & S201 (below the isometric), for the parameter to consider on the bid price.

The price should consider that this adjustments will be executed on site, as no major adjustments are forthseen at this time. If during the execution, a major adjustment in any element is required, will be evaluated in a RFI and further instructions provided in response.

73 General General Will it be necessary to obtain a permit to work in this area (worker's license or similar)? All workers must comply with contractual requirements

74 General General Would you provide drinking water and electricity?

Yes, drinking water and electricity will be provided, but in case of shortages, the contractor must have a contingency plan in place to guarantee continuity of work.

75 General General Will it be possible to use the existing electrical storm?

If this questions refers to the existing temporary facility, it is enabled.

Otherwise explain the question.

76 Architecture General Is it considered within the scope to repair exterior walls up to axis 6?

The scope of the repair for exterior walls on the south façade will be up to axis 5 as indicated on elevation ED02 and at the north façade up to axis 7 as indicated on elevation ED03, both located at sheet AD101.

77 Architecture A201 For the roof and exterior walls they request that it be "Standing Seam" however this material is not currently on the market, could it be approved with another material such as thermopanel?

Thermopanel is not allowed to be used in Smithsonian projects.

Standing Seams shall remain as specified in the construction documents.

78 Architecture A201 Are exhaust fans part of the scope? Yes, it does.

79 Architecture A201 Details of the louvers are requested Refer to wall section on sheet A202, Window Schedule on sheet A602 and specs 089119.

80 Architecture A201 Extractor specifications required Refer to Fan Table on sheet P-101.

81 Architecture C103 Should the existing access gate be removed and the one mentioned in the plans be installed or will the existing one be used?

The existing acess gate was a tempoarary gate build by the previous contractor using the position of exisitng poles. The bid price shall consider that the existing gate shall be removed and a new one will be provided per construction documents details.

82 Architecture C103 Will the location of this access gate remain where it is currently located? Or will it be relocated to where the plans say?

The access gate to be located per construction documents.

83 Architecture A102 What gauge would the roof gutters be? Aluminum 18ga.

84 Architecture A102 Which paint would be suitable for interior and exterior walls?

Benjamin Moore paint with high resitance to moinsture and fungi. Refer to specs 099113 & 099123 also.

85 Architecture A601 In the doors table in the frame finish column appears "PTD" what does this mean?...(in the frame finish legend).... doors appears PT and means painted in gray, do you mean this).

Correct. The accurate leyend for the doors finish is PT = Painted Gray.

86 Architecture A601 Where are these corner protectors located? More information is required on these Provide Corner Guards on the positions marked with red dots on the attached document. Similar to WADFOW WYJ5A06.

RFI 86 - Corner Guards

87 Architecture A401 In the bathroom accessories box, it mentions 2" metal pipe + curtain. Specifications are required for its finishing and installation (base). And the curtain would be part of the range? Which curtain would it be?

No curtain is required to be provided, only the metal pipe.

88 Architecture A602 In the "finish frame legend" box in the ceramic notes "Pl:4" appears, information about this is required.

PEI 4: 1500+ revolutions Moderate to heavy traffic. All residential applications as well as medium commercial and light institutional.

89 Architecture S201

Drawing S-201 states "METALLIC STRUCTURE INCLUDED IN THE INVENTORY HAS BEEN DELIVERED AND STORED ON SITE. THE CONTRACTOR SHALL USE THE SHOP DRAWINGS AS A REFERENCE AND IS

RESPONSIBLE FOR VERIFYING THE ACCURACY OF THE FABRICATED METAL STRUCTURE,

CONSIDERING THAT 5% TO 10% OF THE CONNECTIONS SHOULD REQUIRE ADJUSTMENTS DUE TO

MANUFACTURING ERRORS OR OMISSIONS." These adjustments would be on-site?

The price should consider that this adjustments will be executed on site, as no major adjustments are forthseen at this time. If during the execution, the need of a major adjustment in any element is required, will be evaluated in a RFI and further instructions provided in response.

90 Architecture A602 Do you require a specific brand for the paint? Benjamin Moore.

91 Plumbing P101 Please indicate on the plan which pipes on the perimeter of the building should be considered as existing and which are new to be quoted (potable water, sanitary and pluvial), it is not clearly distinguished on the plan.

Refer to attachment. All the highligted to be consider new. RFI 91 - New plumbing infra

92 Infrastructure C101 From the general location plan indicate if everything is existing or if any of what is on t h e exterior of the building should be quoted.

Refer to reply of RFI #91 & 200

93 Infrastructure C101 Note in the plan it indicates to change the existing supply line of the new building from 1 1/2'' to a new one o f 2''. Indicate if it should be quoted in full and in what material?

Yes, should be quoted all the highlighted in the attachment document.

PVC as indicated on sheet P601.

RFI 93 - New potable water line

94 General General AutoCAD drawings are required for better handling and understanding of the project. Refer to replay of REF #2 95 Plumbing General What height should be considered for split drains in planes. 2.10m

96 Electric E602 For the alarm system you need to know if they require it attached to the existing system, if so, you need to know the brands of these equipment.

Connections to the existing system is indicated on the Fire protection Schematic diagram on sheet E602, as well as the band/model of the exisitng panel. All devices of the FA system to be Simplex.

97 Fire protection General The plans do not show a control station A zone valve to be located in the Riser shown in plan. Details of the elements to be included in the riser are shown on sheet F-501.

98 Fire protection General How will the forecast for the connection with Infrastructure be left?

This Query is not clear. The fire protection system of the maintenance shop buildiing shall be connected to the existing infrastructure as indicated in the contract documents and explained on the site visits. No infrastructure forecast for this system is considered in the design.

99 Alarm system E141 Will there be detection on the left side of the building? The architectural plans of the sky show elements in that area. Clarify PACI connection in that area, as connection to other buildings is established.

Fire alarm on the left side (West) of the building is already existing. As indicated on sheet E141 and the Fire alarm diagram (E602), the new panel PACI to be located on the right side (east) that is part of the scope of work shall be connected to the exisitng PACI located at the West side of the building.

100 Alarm system A111 Mandatory use of simplex marking in alarm systems? Yes, is mandatory.

101 General G02 Will the construction of temporary sidewalks be required as stated in the plans in general guidelines point No. 2, if so, they should be give us the route of these temporary sidewalks

Temporary sidewalks wont be required.

102 Architecture A101 More details of the floor joints are requested.

Provide Isolation Joints as marked on sheet A101. Refer to Specs Section 033000, point 3.6 joints and comply with ACI 302.1R 3.2.5

RFI 102 - Isolation Joints

103 Architecture S301 Can the existing roof be removed for the installation of the insulation between shafts 7 and 10?

It is prefered not to. The design intent is that between the axis 7 and 10 the insulation is installed below the purlins. Fro that purpose on axis 10 a lateral closure and ventilation grilles are indicated on section SC01 located on sheet A301.

104 electricity E100 For the electrical system we must make the connection (civil and electrical) to the existing box. And then just wiring up to the electrical room? Confirm

Confirmed. Civil vork form the Maint. Shop Building up to the existing electric chamber and complete electrical wiring form maint shop panel to MPE panel located in the Main Laboratory building (using the existing route composed of Chambers and duct beams that arrive to the Laboratory electric room). At the interior of the Laboratory electric Room, aditional works shall be executed in terms of running exposed conduits from the position where the duct beams enter the room up to the panel MPE.

105 Will the roof gutter require any waterproofing treatment? Include a Toff 6080 Waterproofing treatment or similar.

106 Roof channel could be galvanized or stainless steel?

The material of the gutters to be compatible with the material of the standing seams sheets and gutters supports, to avoid bi-metallic corrotion. Refer to Specs section 076119 point 2.1D for the materials options.

107 Architecture General How many keys should be included per door? The final core and 3 keys per door.

108 General General Please send complete inventory of existing materials on site to be used in the work. Refer to replay of RFI #70 109 Systems General For the sprinkler system, at what level will they be installed in open ceilings? Refer to notes on sheet F601.

110 Systems General For the alarm system, at what level will they be installed in open ceilings? Refer to "notas de altura" at sheet E141.

111 Architecture A111 Are there any specifications for the type of panel to be used in the suspended ceilings and IT room walls?

Type X moisture resistant gypsum board

112 Preliminary General Should the costs for construction and occupancy permit taxes be included in our scope?

- Refer to replay of RFI #3 - Occupancy permit taxes shall be included.

113 Template Template Should we submit the proposal in the provided template? It's very general for all activities. Will another be sent?

Please use the provided template.

114 General General Can the work required for interconnections or adjustments within operational areas be done during regular hours, or will special work hours be required?

It can be done during regular hours but must be coordinated 48 hours before

115 Preliminary During the site visit, it was mentioned that the current camps could be used. Is this still valid? And once the project is completed, are we responsible for dismantling and removal?

Yes, this is still valid. The existing camp can be use and the contractor will be responsible for the removal.

116 Preliminary During construction, we need to perform activities with heavy equipment. Are there any restrictions on using backhoes, for example?

There are no restrictions on using heavy equipment.

117 CCTV System Is there a specific brand that should be used for the CCTV system?

The wiring and installation of structured cabling and OIT equipment is not within the scope of this BID. Neither CCTV or CA. The scope of this Bid price is to provide empty conduits, boxes, cable trays, and all previsions for the instalation of the special systems. So at this time, no special system supplier shall be considered.

118 Lighting At what level will the lights be installed in areas with high ceilings? Refer to "notas de altura" at sheet E111.

119 Fire Extinguishers There are no details about the fire extinguisher specifications.

For Fire Extinguishers types and locations refer to sheet A001. For additional information on the specifications to follow refer to section 104400 on the specs docs.

120 Voice and Data We do not see specifications for the cabling to be used. Will a rack be installed, or will you handle the system installation?

The wiring and installation of structured cabling and OIT equipment is not within the scope of this BID.

Architecture Architecture

A201 A202

121 Cable Tray Systems We need a layout with cable tray routes, as it's not detailed in the plans. Cable tray route is included on sheet E131.

122 Special Systems Will the supply and installation of special systems such as voice and data, CCTV, access control, racks, etc., be part of our scope?

The wiring and installation of structured cabling and OIT equipment is not within the scope of this BID. Neither CCTV or CA. The scope of this Bid price is to provide empty conduits, boxes, cable trays, and all previsions for the instalation of the special systems.

123 Architecture C-101 What are the specifications for the exterior grilles? Will they be the same as the interior ones?

The exterior grilles to be the same type as the interior: Class D400 FUCASA. Dimensioned accordinly to the Trench opening for each use.

124 Structure A-302 Reviewing the plan details, do the internal wall footings follow the DT06 detail? Does this apply to walls with existing floors?

Detail DT06 located on sheet A302 apply for the walls where a new slab will be build (Axis 10 to 13.9). For the walls to be build on the area where the exisitng slab will remain (Axis 7 to 10), Details DT01, DT02 & DT03 located on sheet A301 shall be applied.

125 Structure S-102 The column to be installed at the intersection of grid 10 and grid B.5, will it require any type of footing or foundation?

No footing / foundation is required.

Metal structure on axis 10 will be support from the existing concrete structure (that shall be reinforced). Please refer to further details on sheets S201, S301 & S506.

126 Structure Floors During the visit, there was a discussion about the condition of the current base layer. Will we need to include the removal of a few centimeters?

Only a general cleaning and root removal of vegetation.

127 Electricity E-603 Where is the SWB02 panel located, and what will be connected to it? The panel indicated for connection is the MPE, but it has the same name as the SWB02. From which panel should we start?

Nothing will be connected to SWB02 panel. The information regarding this panel located on sheet E-603 shall be used as reference, considering that Panel MPE (where the Maint. shop will be connected) is feed from SWB02.

128 Electricity General What type of conduit will be used in open areas? EMT or Metallic Conduit? EMT

129 Air Conditioning General For air conditioning units, do you have a preferred brand, or can we propose one?

The Minisplit unit schedule indicate a proposed brand/model of reference. Refer to specs section 238126 for acceptable manufacturers.

130 Plumbing P-0-01/Sheet 42 of 49 In notes on plumbing plans, point No.15, it is indicated to insulate the cold water pipe (drink water).

This requirements will be applied to entire rout of pipe within the Building?

Consider insulation on all the aereal route.

131 Plumbing Page 207-412, Item J, should the fire systems designed?

The responsibility of the contractor is to provide shop drawings based on the design intention reflected on the construction documents, coordinating them with other trades, like other systems to be reflected on ceilings. If during the execution any modification is requested it will be reviewed and negotiated through a PCN.

132 Plumbing Page 207-412, Item D, Drain Pan , where does this point apply within the drawings provided? Electric room #116 & OIT Room #110.

133 Plumbing Page 207-412, Item J, required to supply hidraulic calculations Only manufacture's data and shop drawings will be requested. No hidraulic calculations are required to be provided by the contractror.

134 Plumbing Page 216-412, Item 2.3 where it a backflow preventer required? Indicate model and size?

At this stage it is not necessary to install a backflow preventer. This device is already present in the existing main fire pump room.

135 Plumbing Page 216-412, Item C, where " Guard" is required for sprinklers heads?

Consider Guards for sprinklers located on spaces without ceiling between axis 7 to 10. Electric Room & OIT Room also.

136 Plumbing Specs 104400 Page 201 of 412, Item 2.04 Indicate the type of gabinet to be used. The specificaction mark type I and Type III

The point 2.4 of spec 104400 indicate a size of cabinet refering to the type of fire extinguisher (Type I & Type III, vs Type II).

137 Plumbing Specs 221116 Page 244 of 412 "Valve Schedule" the valve type is indicated but there not specifications on valve body materials, operation pressure, etc.

Bronce, accordinly with the use.

138 Plumbing Specs 238126 Page 267-412 ,Item 1.6 Supply extra materials. Which point would apply for split type air conditioning units. If paragraph talk about an air handler. The split unit have a permanent filter, don use access door , dont use belt.

Not applicable for Split units.

139 Plumbing G-0-01 The Plan Index show a plan labeled P-602 Air line Isometric. Is this part of the scope Sheet label P-602 is not found in the plan index. It was at the previous set, but was eliminated from the set prior to this Bid. It is not part of the scope.

140 Plumbing C-1-01 On the plan shown " Exterior infrac cut exist 1-1/2" pipe at corner and construct new valve box for 2" and 2" valve. We required size and specification of valve box

Refer to the attachement. RFI 140 - Valve Box

141 Plumbing P-1-01 We required size and specification for concrete pit to use in ZURN 21188-ST-E interceptor Consider similar specs as the one for Caja tipo SA located at sheet C101.

Dimensions 2.5 x 3m. Lid to be Metallic and divided in 3 to 4 sections.

142 Plumbing 211313 In paragraph 1.06 A and B, should sprinkler system design costs be included?.

The responsibility of the contractor is to provide shop drawings based on the design intention reflected on the construction documents, coordinating them with other trades, like other systems to be reflected on ceilings. If during the execution any modification is requested it will be reviewed and negotiated through a PCN.

143 Plumbing 211313 Paragraph 1.06 C, we do not find within the document section 21 11 00 for installation of exterior water supply Main for fire protection service.

Contractor should execute the related work according to contract drawings.

144 Plumbing 211313 Paragraph 1.07 Performance requirements, consideration should be given to performing the hydraulic calculations again on the plans provided by Smithsonian.

Only manufacture's data and shop drawings will be requested. No hidraulic calculations are required to be provided by the contractror.

145 Plumbing 211313 Paragraph 1.08 f, costs for hydraulic calculations must be considered when delivering the AS-Built Hidraulic calculations wont be required as part of the AS-Built.

211313

146 Plumbing 211313 Paragraph 1.09.C.2. A NICET level III or IV engineer or technician must be considered in the proposal during the execution of the project.

It is not required. It is only required that the subcontractor must be certified to carry out the type of work in Panama.

147 Electrical Specs 260520 Paragraph 3.3.E: We assume that specs lists fire different OPTIONS. Pls confirm Contractor should execute the related work according to contract drawings.

148 Electrical Specs 260526 Para. 1.2.B.2: provide lightning design, if applicable Lighting system is not part of the scope.

149 Electrical Specs 260526 Para. 1.4.A.3, 4 & 5: provide design of ground rings, if applicable Gound rings not applicable for this project.

150 Electrical Specs 260526 Para. 1.6.A: provide a list of acceptable Testing Agencies This doesnt apply to the project. Only continuity tests should be done.

151 Electrical Specs 260526 Para. 2.2.A: provide a list of acceptable manufacturers and models This doesnt apply to the project.

152 Electrical Specs 260526 Para. 2.3.B: conflict with Detail 1 Dwg E-5-03.

Contractor should execute the related work according to contract drawings.

153 Electrical Specs 260526 Para 3.1.A & B: conflict with Item 1 of Material List Dwg E-5-03 Contractor should execute the related work according to contract drawings.

154 Electrical Specs 260526 Para. 3.1.C: provide design of isolated grounding system Contractor should execute the related work according to contract drawings.

155 Electrical Specs 260526 Para 3.1.D: conflict with DG02 in Dwg E-5-03 Contractor should execute the related work according to contract drawings.

156 Electrical Specs 260526 Para 3.1.E: conflict with DG01 in Dwg E-5-03 Contractor should execute the related work according to contract drawings.

157 Electrical Specs 260526 Para. 3.3.E: provide design for separate grounding system per TIA Contractor should execute the related work according to contract drawings.

158 Electrical Specs 260526 Para. 3.4.F & 3.4.G: provide grounding design for piping and metal ducts This doesnt apply to the project.

159 Electrical Specs 260526 Para. 3.4.J: provide floor plan location and detail Contractor should execute the related work according to contract drawings.

160 Electrical Specs 260526 Para. 3.6.B: provide a list of acceptable Field Service Agencies Not required.

161 Electrical Specs 260526 Para. 3.6.G: We assume the project requirement is 10 ohms minimum. Pls confirm Refer to detail 1 at sheet E503.

162 Electrical Specs 262416 Main Panelboard in the project is described with 400 Amp bars. Therefore, we consider that following paragraphs do not apply to such small piece of equipment: 1.5.B.,5,6.7 & 8, 1.6.B, 1.7.A.2, 1.9.A, 2.1.B.5, 2.1.D.4, 2.1.F, 2.1.H, 2.6, 3.3.A, 3.4.B, 3.4.D and 3.4.E.3. Pls advise otherwise

The contractor shall apply the specs considering the related devices to be installed as dimensioned on the construction drawings.

163 Electrical Specs 262416 Para. 2.1.B.1: we assume all enclosures are required to comply with Nema 1. Pls confirm Correct.

164 Electrical Specs 262416 DWG E-6-03 does not show requirements indicated in paragraphs 2.1.I, 2.2.H, 2.3.E & 2.5 Does not apply.

165 Electrical Specs 262416 Para 2.4 & 2.5: provide…