3-11 JACKSON EC ELECTRICAL DRAWINGS.pdf

PDF 684 KB Posted

Attached to
Renovations+Addition to Existing Building, New Storage Garage and Salt Storage Building
Solicitation number
US.261682
Issued by
York County, Pennsylvania

About this file

This file consists of electrical drawings and specifications for the proposed addition and renovation to the Jackson Township Municipal Center located at 439 Roths Church Road, Spring Grove, Pennsylvania. The electrical work includes design for a new 150 kilowatt diesel generator, new panelboards, lighting fixtures, power distribution systems, fire alarm signaling, low voltage cabling for data and communications, and site lighting for the main building, storage garage, and salt storage building. The project encompasses multiple floor plans with detailed lighting and power layouts, electrical panel schedules, one-line diagrams, and installation details. Sealed bids for the Electrical Construction contract are due December 8, 2026, at 1:00 PM EST via the PennBid Program, with a pre-bid conference scheduled for November 10, 2026, at 10:00 AM EST on-site. Contract award is scheduled for January 4, 2027, and the contract term is four hundred calendar days from the Notice to Proceed. Bidding documents became available November 4, 2026, at no cost through PennBid.

The drawings specify electrical standards compliance with the National Electrical Code (2020), International Building Code (2021), International Energy Conservation Code (2021), and ASHRAE Standard 90.1-2019. The electrical contractor is responsible for furnishing and installing all materials, equipment, wiring methods, conduit, grounding and bonding systems, lighting fixtures, panelboards, disconnects, receptacles, switches, and all related appurtenances necessary for complete operational systems. The contractor must provide a one-year unconditional guarantee on all materials, equipment, and workmanship from the date of owner acceptance and submit as-built drawings and operation and maintenance manuals upon project completion. A bid bond equal to 10% of the maximum bid is required with submission, and all work is subject to the Pennsylvania Prevailing Wage Act. No specific pricing information, set-asides, or incumbent contractor details are provided in these technical drawings.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

S

M

PS

JB

VC

FS

TS

KP

TC

DH

T

30/3/NF/12

FVNR/SIZE1/3R

PANELBOARDS

SURFACE MOUNTED PANEL

FLUSH MOUNTED PANEL

CIRCUITING

JUNCTION BOX

BRANCH CIRCUIT NUMBER FOR ALL ITEMS IN THIS

ROOM UNLESS OTHERWISE INDICATED - (*)

INDICATES CONNECTION TO CIRCUIT NUMBER

SHOWN NEXT TO DEVICE

CONTROL EQUIPMENT

MANUAL MOTOR STARTER - OVERLOADS SIZED TO ACCOMMODATE

MOTOR - 4'-0" AFF UNLESS OTHERWISE NOTED

COMBINATION MOTOR STARTER - TYPE/SIZE/NEMA ENCLOSURE AS

INDICATED - MOUNT 4'-6" AFF TO CENTERLINE OF OPERATING HANDLE

PROVIDE OVERCURRENT AND OVERLOADS IN ACCORDANCE WITH

MANUFACTURERS RECOMMENDATIONS FOR MOTOR HP

MOTOR - HORSEPOWER AS INDICATED

DISCONNECT SWITCH - AMPS/POLES/FUSES/NEMA ENCLOSURE AS

INDICATED - MOUNT 4'-6" AFF TO CENTERLINE OF OPERATING HANDLE

TRANSFORMER

SIGNAL SYSTEM

SMOKE DETECTOR

DUCT MOUNTED SMOKE DETECTOR

HEAT DETECTOR

DOOR HOLDER - PROVIDE CONNECTION TO DOOR

HARDWARE PROVIDE POWER FROM CIRCUIT SHOWN

FOR DOOR HARDWARE. PROVIDE CONNECTION TO

FIRE ALARM SYSTEM AND TO SMOKE DETECTORS.

PROVIDE CONNECTION TO PANIC BUTTON IN

RECEPTION.

TIME CLOCK

KEYPAD

PUSHBUTTON - PROVIDE IN CASEWORK AND PROVIDE

WIRING TO SECURITY SYSTEM FOR DOOR LOCKDOWN.

COORDINATE WITH CASEWORK AND DISTRICT

SECURITY VENDOR

VOLUME CONTROL

FLOW SWITCH

TAMPER SWITCH

PRESSURE SWITCH

CARD READER - EXTERIOR LOCATIONS - PROVIDE

SQUARE BACK BOX AND EXTEND 1" CONDUIT WITH

APPROPRIATE WIRING TO NEAREST DOOR HARDWARE

INTERFACE. INTERIOR LOCATIONS - PROVIDE SINGLE

BACK BOX AND EXTEND 1" CONDUIT WITH

APPROPRIATE WIRING TO NEAREST DOOR HARDWARE

INTERFACE COORDINATE FINAL LOCATION IN THE FIELD

WITH OWNER.

COMBINATION DATA/TELEPHONE OUTLET - PROVIDE A

4" SQUARE JUNCTION BOX WITH PLASTER RING AND A

3/4" CONDUIT STUB TO ABOVE ACCESSIBLE CEILING

SPACE. MOUNT 1'-6" AFF UNLESS OTHERWISE NOTED

DATA OUTLET WITH # OF JACKS (MINIMUM 2 JACKS

PER LOCATION) - MOUNT 1'-6" AFF

UNLESS OTHERWISE NOTED

TELEPHONE OUTLET - MOUNT 1'-6" AFF UNLESS

OTHERWISE NOTED

ABBREVIATIONS & SYMBOLS

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ATS AUTOMATIC TRANSFER SWITCH

CT COUNTER HEIGHT-44" AFF (UNLESS OTHERWISE NOTED)

DC DUCT COIL

DF DRINKING FOUNTAIN

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

GC GENERAL CONTRACTOR

GF GROUND FAULT INTERRUPTER

HC HVAC CONTRACTOR

HP HEAT PUMP

KES KITCHEN EQUIPMENT SUPPLIER

MW MICROWAVE

PC PLUMBING CONTRACTOR

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER

WM WALL MOUNTED

WP IN USE WEATHERPROOF

DRAWING NOTE BY SYMBOL1

SITE WORK

UTILITY POLE

POLE MOUNTED AREA LIGHTING FIXTURE

MANHOLE

GROUND ROD

MH

STANDARD MOUNTING HEIGHTS

9" BELOW

FINISHED

CEILING

WALL-MOUNTED CLOCKS, PROGRAM BELLS, (OR AS SHOWN

ON ARCHITECTURAL DETAIL)

6" ABOVE DOOR NURSE CALL DOME LIGHT

6" ABOVE FIRE

HOUSE

CABINET

RED SIGNAL LIGHT

10'-0"

BATTERY LIGHTING UNITS AND REMOTE WALL MOUNTED

LIGHT HEADS (OR 1'-0" BELOW FINISHED CEILING OF TOP

UNIT).

8'-6" PENDANT-HUNG INDUSTRIAL AND STRIP LIGHTING FIXTURES.

7'-8"+

TELEVISION OUTLET AND SERVICE RECEPTACLE-FOR

SHELF MOUNTED T.V. IN BEDROOMS.

7'-6" OR 6" BELOW FINISHED CEILING, WHICHEVER IS LOWER.

CENTER ABOVE

DOOR OR WINDOW

OPENING

WARNING AND SIGNALING FIXTURES/SIGNS.

6'-8"

OR 6" BELOW FINISHED CEILING WHICHEVER IS LOWER.

FIRE ALARM SIGNAL DEVICES AND ILLUMINATED FIRE

SIGNALS.

6'-6"

TOP OF FLUSH AND SURFACE MOUNTED ELECTRICAL

LIGHTING OR POWER PANELBOARDS AND TELEPHONE

CABINETS.

6'-3"

TOP OF BACK-MOUNTED WALL EXIT FIXTURES (NOT

MOUNTED ABOVE DOORS).

6'-0"

TOP OF HIGHEST ELECTRICAL SAFETY DISCONNECT

SWITCHES, MAGNETIC STARTERS, CONTACTORS.

4'-6"

CENTERLINE OF OPERATING HANDLE FOR WALL MOUNTED

DISCONNECT SWITCHES AND MOTOR STARTERS; WALL

MOUNTED TELEPHONE AND PAY STATIONS (3'-6" AT HANDICAP

LOCATIONS VERIFY EXACT HEIGHT PRIOR TO ROUGH IN)

3'-10"

WALL PHONE, ELECTRICAL DEVICE LIGHTING SWITCHES, MANUAL

MOTOR STARTERS, SECURITY CARD, AND GFI RECEPTACLES IN

TOILET ROOMS OR FOR SEPARATE SINKS NOT IN CASEWORK.

3'-6" FIRE ALARM PULL STATIONS

2'-0"

ELECTRICAL RECEPTACLES WITHIN MECHANICAL

SPACES, ELECTRICAL AND ELEVATOR ROOMS.

1'-6"

ELECTRICAL RECEPTACLES, TELEPHONE OUTLETS, DATA

OUTLETS, TELEPHONE/DATA OUTLETS

0" FINISHED FLOOR

CT

W

MOUNTING HEIGHT NOTES:

1. MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED. IN MASONRY

CONSTRUCTION THE ABOVE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO NEAREST

BLOCK OF BRICK COURSING.

2. THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS SPECIFICALLY NOTED OR DETAILED

OTHERWISE ON THE DRAWING OR SPECIFICATIONS.

3. A '+' BESIDE A DEVICE INDICATES THAT DEVICE IS MOUNTED ABOVE A COUNTER OR CASEWORK.

COORDINATE WITH ARCHITECTURAL ROOM ELEVATIONS, DETAILS AND CASEWORK CONTRACTOR.

P-1

ROOM #

ROOM NAME

M

M

THE ELECTRICAL SYSTEMS PRESENTED ON THE SUBSEQUENT

DRAWINGS WERE DESIGNED IN ACCORDANCE WITH THE

FOLLOWING APPLICABLE CODES AND STANDARDS:

THE NATIONAL ELECTRICAL CODE (NEC), 2020

INTERNATIONAL BUILDING CODE (IBC), 2021

INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2021

ASHRAE STANDARD 90.1 - 2019

MANUAL PULL STATION - SHALL BE MOUNTED SUCH

THAT THE HANDLE IS NOT LESS THAN 42" AND NOT

GREATER THAN 48" AFF.

AUDIO ALARM - SHALL BE MOUNTED WITH THEIR TOPS

AFF AT HEIGHTS OF NOT LESS 90" AFF

AUDIO/VISUAL ALARM - SHALL BE MOUNTED

SUCH THAT ENTIRE LENS IN NOT LESS THAN 80"

AND NOT GREATER THAN 96" AFF.

VISUAL ALARM - SHALL BE MOUNTED SUCH

THAT ENTIRE LENS IS NOT LESS THAN 80" AND NOT

GREATER THAN 96" AFF.

LIGHTING

2'x2' LIGHTING FIXTURE

2'x4' LIGHTING FIXTURE

2'x4' LIGHTING FIXTURE-EMERGENCY

1'x8' LIGHTING FIXTURE

2'x8' LIGHTING FIXTURE

1'x4' LIGHTING FIXTURE

6"X4' LIGHTING FIXTURE

6"x2' LIGHTING FIXTURE

WALL PACK LIGHTING FIXTURE

STRIP LIGHT

WALL WASHER FIXTURE

ROUND RECESSED DOWNLIGHT FIXTURE

NORMAL EMERGENCY FIXTURE

EMERGENCY BATTERY UNIT

REMOTE HEAD

EXIT SIGN-DOUBLE FACE

EXIT SIGN-CEILING MOUNTED WITH DIRECTIONAL

ARROWS

EXIT SIGN-SINGLE FACE

WALL SCONCE

CR

1. CONTRACTOR SHALL PROVIDE BRANCH CIRCUIT WIRING TO ALL ITEMS WHICH REQUIRE ELECTRICAL CONNECTIONS. WHERE BRANCH CIRCUIT WIRING IS NOT SHOWN, CONTRACTOR SHALL CONNECT ITEMS TO THE CIRCUITS INDICATED. EXACT ROUTING OF CONDUITS AND WIRING SHALL BE DETERMINED BY THE

CONTRACTOR IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND SPECIFICATIONS.

2. CONTRACTOR SHALL USE ONLY THOSE WIRING METHODS ALLOWED IN THE SPECIFICATIONS.

3. A MAXIMUM OF 3 CIRCUITS SHALL BE RUN IN ONE CONDUIT, CIRCUITS MUST BE ON SEPARATE PHASES.

CIRCUITS SHALL NOT SHARE A COMMON NEUTRAL.

4. MINIMUM WIRE SIZE SHALL BE #12AWG. MINIMUM CONDUIT SIZE SHALL BE 3/4".

5. THE ELECTRICAL CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE.

6. ALLOW CLEAR SPACE IN FRONT OF ALL PANELBOARDS, SWITCHBOARDS, ELECTRICAL EQUIPMENT, ETC., AS

REQUIRED BY NEC.

7. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES WITH HVAC DUCTWORK, PIPING AND EQUIPMENT.

8. ALL LIGHTING FIXTURES TO BE COMPATIBLE WITH THE CEILING CONSTRUCTION.

9. ELECTRICAL CONTRACTOR TO SUPPLY ALL GROUNDING & BONDING REQUIREMENTS PER NEC.

10. SEE FIRE PROTECTION SIGNALING SYSTEM RISER DIAGRAM NOTES AND SPECIFICATIONS FOR INFORMATION

ON DUCT DETECTORS AND SMOKE DAMPERS. SEE SPECIFICATIONS FOR ITEMS NEEDING ADDRESSABLE CONNECTIONS WITH SUPERVISED INTERFACE. THESE ITEMS MAY NOT BE QUANTIFIED ON THE ELECTRICAL DRAWINGS, BUT SHALL BE COORDINATED WITH ALL OTHER TRADES AND DRAWINGS CONTRACTOR TO

ACCOUNT FOR VOLTAGE DROP WHERE LONG RUNS ARE TO BE PROVIDED.

11. ELECTRICAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING IN EXISTING BUILDING RELATED TO THE

NEW ELECTRICAL WORK.

12. ELECTRICAL CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE IN WRITING ALL MATERIALS EQUIPMENT

AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE BY OWNER

13. THE ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE ARCHITECT & ENGINEER AS-BUILT DRAWINGS AND

OPERATION AND MAINTENANCE MANUALS INCLUDING ALL NAMEPLATE DATA, WIRING DIAGRAMS,

MAINTENANCE INSTRUCTIONS AND PARTS LIST UPON PROJECT COMPLETION.

14. ELECTRICAL CONTRACTOR SHALL MAINTAIN A CLEAN AND SAFE WORK AREA AT ALL TIMES. ALL SAFETY PROCEDURES AND ENFORCEMENT IS THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL

CONFORM TO ALL OSHA STANDARDS.

15. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL ACESS PANELS NECESSARY FOR A CODE COMPLIENT

INSTALLATION.

16. THESE DRAWINGS AND SPECIFICATIONS ARE NOT INTENDED TO SHOW THE LOCATION OF EVERY WIRE, CONDUIT, FITTING, ETC., BUT IS UNDERSTOOD THAT THE CONTRACTOR SHALL FURNISH AND INSTALL ALL

MATERIALS AND LABOR FOR COMPLETE WORKABLE SYSTEMS UNLESS NOTED OTHERWISE IN THIS

SPECIFICATION OR ON THE DRAWINGS.

17. THE CONTRACTOR SHALL PROVIDE BUT NOT BE LIMITED TO:

A. COMPLETE SYSTEM OF WIRING FOR EMERGENCY LIGHTING, LIGHT AND POWER, PLUMBING, HVAC

EQUIPMENT, FIRE ALARM ALONG WITH TELEPHONE AND DATA EQUIPMENT INSTALLATION.

B. ALL PANELS, SWITCHBOARDS, MOTOR CONTROLLERS, TRANSFORMERS, DISCONNECTS, RECEPTACLES, SWITCHES, OUTLETS AND PLATES FOR SAME, FEEDERS FROM PANELS AND RELATED APPURTENANCES.

C. LIGHTING FIXTURES, LAMPS, BALLASTS AND APPURTENANCES.

18. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS, ELBOWS, FITTINGS OR OTHER SPECIFIC ELEMENTS WHICH MAY BE REQUIRED FOR COMPLETE INSTALLATION OF THE WORK. SUCH WORK MAY BE ACCOMPLISHED AT THE SITE. ADDITIONAL BENDS, OFFSETS AND CONDUIT AS REQUIRED BY VERTICAL AND HORIZONTAL EQUIPMENT LOCATIONS OR OTHER JOB CONDITIONS SHALL BE PROVIDED TO

COMPLETE THE WORK AT NO ADDITIONAL COST TO THE OWNER.

19. NO RACEWAY/CONDUIT SHALL BE INSTALLED VERTICALLY OR HORIZONTALLY IN MASONRY CAVITIES BETWEEN WALL FINISH AND MASONRY WALL. PENETRATIONS THROUGH THE CAVITY ARE PERMITTED FOR ELECTRICAL FIXTURES AND DEVICES. ALL PENETRATIONS SHALL BE HORIZONTAL, PERPENDICULAR

THROUGH THE CAVITY, AND LOCATED DIRECTLY AT THE INTENDED ITEM.

20. IN NEW CONSTRUCTION , UNLESS SPECIFIED OTHERWISE OR APPROVED IN WRITING IN ADVANCE BY ARCHITECT AND/OR ENGINEER, NO EXPOSED RACEWAY/CONDUIT WILL BE ACCEPTED IN FINISHED SPACES.

21. EXCEPT WHERE SHOWN IN DIMENSIONAL DETAIL, THE LOCATIONS OF SWITCHES, RECEPTACLES, LIGHTS AND OTHER EQUIPMENT SHOWN ON PLANS ARE APPROXIMATE. SUCH ITEMS SHALL BE PLACED SO AS TO ELIMINATE INTERFERENCE WITH DUCTS, PIPING AND EQUIPMENT. THE EXACT LOCATION SHALL BE DETERMINED IN THE FIELD. ALL DOOR SWINGS SHALL BE VERIFIED SO THAT LIGHT SWITCHES ARE PROPERLY

LOCATED.

22. FIELD VERIFY EXISTING CONDITIONS AND COORDINATE ALL WORK WITH ALL OTHER TRADES, AND ACTUAL

CONDITIONS IN FIELD.

GENERAL NOTES:

1. DEMOLITION OF ALL EXISTING ELECTRICAL EQUIPMENT AND ASSOCIATED PIPING SHALL BE COORDINATED

WITH NEW WORK INSTALLATION.

2. THIS CONTRACTOR WILL BE HELD RESPONSIBLE FOR ANY/ALL DAMAGES TO EXISTING FLOORS, FLOOR TILES, WALLS, CEILINGS, FURNISHINGS, ETC. DUE TO THE REMOVAL PROCESS OF ELECTRICAL EQUIPMENT AND ALL

ASSOCIATED ITEMS.

3. ALL MATERIAL AND EQUIPMENT REMOVED SHALL BE PROPERLY DISPOSED OF BY THE CONTRACTOR.

4. CONTRACTOR SHALL REMOVE ALL EXISTING LIGHTING FIXTURES WHERE NEW FIXTURES ARE SHOWN. THIS

SHALL INCLUDE FITTINGS, SUPPORT DEVICES, ETC AND MAKE PROVISIONS TO EXISTING CEILING SO THAT

THE NEW FIXTURE MAY BE PROPERLY INSTALLED.

5. MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS REMAINING IN OTHER AREAS.

6. ALL EXISTING CONDUITS AND WIRING NOT BEING USED SHALL BE REMOVED BACK TO SOURCE.

7. WHERE MODIFICATIONS OR ADDITIONS TO EXISTING WORK IS TO BE DONE BY ANOTHER CONTRACTOR, EXISTING EQUIPMENT, CONDUIT, DEVICES, SUPPORTS, AND APPURTENANCES SHALL BE REMOVED AND REINSTALLED TO ACCOMMODATE MODIFICATIONS OR ADDITIONS. THIS SHALL INCLUDE THE ADDITION OF DOORS, WALLS, STRUCTURAL SUPPORTS, UNITS, ETC. COORDINATE WITH OTHER CONTRACTORS IN THE FIELD PRIOR TO WORK COMMENCING. WHERE THE QUANTITY OF WORK CANNOT BE DETERMINED PRIOR TO

BID DUE TO CONCEALED CONDITIONS, PROVIDE $5,000 ALLOWANCE.

8. DEVICES SHOWN ARE BASED ON EXISTING DRAWINGS AND SITE SURVEY WHILE BUILDING WAS IN

OPERATION. ACTUAL LOCATIONS AND QUANTITIES MAY VARY. VERIFY IN THE FIELD.

9. ALL DORMANT CABLING AND WIRING SHALL BE REMOVED UNLESS NOTED AS FOR FUTURE OR AS

INSTRUCTED OTHERWISE BY OWNER.

10. COORDINATE THE REMOVAL OF THE POWER CONNECTIONS TO ALL MECHANICAL EQUIPMENT TO BE

REMOVED WITH THE MECHANICAL CONTRACTOR.

11. ALL CIRCUIT BREAKERS WHERE THE LOAD SERVING HAS BEEN REMOVED SHALL BE MARKED AS SPARE.

12. ALL PANELBOARDS MODIFIED UNDER THE WORK SHALL RECEIVED REVISED, TYPED PANEL SCHEDULES AS

PROVIDED WITH ALL NEW PANELBOARDS.

13. REPLACE ANY DAMAGED EXISTING TO REMAIN ELECTRICAL, LIGHTING, AND LOW VOLTAGE EQUIPMENT IN

KIND.

14. EXTEND WIRING IN KIND FOR DEVICES TO BE REINSTALLED IN NEW CEILING AS NECESSARY.

15. ALL SURFACE MOUNTED DEVICES SHALL BE INSTALLED IN 1 OR 2 SECTION SURFACE MOUNTED RACEWAY AS

REQUIRED TO ACCOMMODATE BOTH LOW VOLTAGE AND LINE VOLTAGE CABLES IN THE SAME RACEWAY.

REFER TO SURFACE MOUNTING DETAIL FOR MORE INFORMATION.

16. VERIFY IF BUILDING HAS PLENUM RETURN. IF A PLENUM RETURN EXISTS, PROVIDE ALL EXPOSED CABLING

INSTALLED WITHIN PLENUM AS PLENUM RATED CABLE.

GENERAL ELECTRICAL DEMOLITION NOTES:

1. EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL UNTIL THE NEW FIRE ALARM

SYSTEM IS INSTALLED, TESTED, INSPECTED, AND ACCEPTED. ENSURE EXISTING SYSTEM

REMAINS ON EMERGENCY POWER UNTIL REMOVED. REMOVE ALL COMPONENTS OF

EXISTING FIRE ALARM SYSTEM ONCE NEW SYSTEM IS ACCEPTED. NEW SYSTEM SHALL

NOT RELY ON ANY EXISTING COMPONENTS. ALL EXISTING DEVICES IN AREAS NOT

INCLUDED IN THIS CONTRACT SHALL REMAIN FULLY OPERATIONAL.

2. PROVIDE ALL 120V POWER TO NEW FIRE ALARM SYSTEM FROM LIFE SAFETY EMERGENCY

PANELBOARDS. PROVIDE ALL NECESSARY WIRE, CONDUIT, CIRCUIT BREAKERS AND

CONNECTIONS AS REQUIRED BY SELECTED FIRE ALARM SYSTEM.

GENERAL FIRE ALARM INSTALLATION NOTES:

1. DEMOLITION OF ALL EXISTING FIRE ALARM EQUIPMENT AND ASSOCIATED RACEWAY

SHALL BE COORDINATED WITH NEW WORK INSTALLATION.

2. ALL EXISTING DEVICES IN AREAS WHERE NEW ARE SHOWN SHALL BE REMOVED IN THEIR

ENTIRETY. ALL ASSOCIATED RACEWAY AND WIRE SHALL BE REMOVED.

3. THIS CONTRACTOR WILL BE HELD RESPONSIBLE FOR ANY/ALL DAMAGES TO EXISTING

FLOORS, FLOOR TILES, WALLS, CEILINGS, FURNISHINGS, ETC. DUE TO THE REMOVAL

PROCESS OF FIRE ALARM EQUIPMENT AND ALL ASSOCIATED ITEMS.

4. ALL MATERIAL AND EQUIPMENT REMOVED SHALL BE PROPERLY DISPOSED OF BY THE

CONTRACTOR.

5. ALL EXISTING CONDUITS AND WIRING NOT BEING USED SHALL BE REMOVED BACK TO

SOURCE.

GENERAL FIRE ALARM DEMOLITION NOTES:

CARBON MONOXIDE/HEAT DETECTOR

CAMERA - PROVIDE BACK BOX ABOVE CEILING WITH 6'

WHIP WHERE LOCATED OUTSIDE, PROVIDE

WEATHERTIGHT DOUBLE GANG BACK BOX WITH COVER

AS PER OWNER'S REQUIREMENTS. WHERE LOCATED IN A

SPACE WITHOUT CEILINGS (OR HIGH CEILINGS).

COORDINATE MOUNTING HEIGHT ON WALL WITH OWNER

PRIOR TO ROUGH-IN, BOX MAYBE RECESSED IN WALL.

PROVIDE CAT 6E CABLE BACK TO NEAREST DATA

CLOSET. COORDINATE EXACT LOCATION IN THE FIELD

WITH THE OWNER.

DC

DOOR CONTACT - PROVIDE DOUBLE GANG BOX ABOVE

ACCESSIBLE CEILING.

SP CEILING MOUNTED SPEAKER

PA PA HORN SPEAKER

PA PA HORN SPEAKER OUTDOOR WEATHER PROOFWP

HV HIGH VOLUME

ETR EXISTING TO REMAIN

ETD EXISTING TO BE DEMOLISHED

ERL EXISTING TO BE RELOCATED

DEMOLITION DRAWING LINETYPE DESIGNATIONS

EXISTING TO REMAIN

EXISTING TO BE REMOVED

LOW VOLTAGE NOTES:

1. IN GENERAL, FOR ALL DATA, PHONE, SECURITY, CARD ACCESS AND

OTHER LOW VOLTAGE SYSTEMS, UNLESS NOTED OTHERWISE, PROVIDE

CABLING BACK TO NEAREST DATA RACK. EXTEND CONDUIT NOTED TO 6"

ABOVE ACCESSIBLE CEILING AND SUPPORT CABLING AS PER

SPECIFICATIONS FOR THE REST OF RUN.

2. PROVIDE ALL TERMINATIONS, TESTING, AND CERTIFY CABLING.

3. PROVIDE DEVICE COVERPLATES WITH OUTLETS TO MATCH TERMINATION

CONNECTIONS.

4. TERMINATED KEYSTONE JACKS ARE TO BE COLORED ON BOTH ENDS TO

MATCH CABLING COLOR.

5. PROVIDE FIRESTOP SLEEVES IN ALL RATED FIRE OR SMOKE

WALLS/FLOORS. PROVIDE SLEEVES IN ALL WALL PENETRATIONS ABOVE

CEILING TO PROTECT CABLING.

6. CARD READERS ARE INTEGRAL TO THE DOOR HARDWARE AND WILL BE

PROVIDE BY THE GC. POWER SUPPLIES ARE PROVIDED BY THE GC.

RELATED CONDUIT AND WIRING TO THE DOOR IS BY THE EC. CONTROL

PANELS AND FINAL CONNECTIONS ARE BY THE OWNER'S ACCESS

CONTROL VENDOR.

7. CONDUITS AND CABLING FOR CAMERAS SHALL BE BY THE EC. CAMERAS

AND ASSOCIATED HEADEND EQUIPMENT ALONG WITH FINAL

CONNECTIONS ARE BY THE OWNER'S VENDOR.

8. DOOR CONTACTS AND ASSOCIATED POWER SUPPLIES ARE PROVIDED BY

THE GC. RELATED CONDUIT AND WIRING TO THE DOOR CONTACTS IS BY

THE EC. ALL HEADEND EQUIPMENT AND FINAL CONNECTIONS ARE BY THE

OWNER'S SECURITY VENDOR.

LOW VOLTAGE CABLING COLOR CHART

TYPE COLOR DESIGNATION

DATA BLUE C, D, F, G, H, J, K & L

PHONE BLACK FIRE ALARM PANEL &

ELEVATOR

ACCESS POINT ORANGE AP

CAMERAS GREEN

S

D

C

H

M

F

F

F

M

F

F

F

GENERAL LIGHTING FIXTURE SCHEDULE NOTES:

1. PROVIDE CORRECT TRIM FOR ALL FIXTURES INSTALLED IN A HARD CEILING OR SPECIALTY CEILING TYPE.

2. PROVIDE ALL APPROPRIATE MOUNTING HARDWARE. PROVIDE BACK/MOUNTING BOXES AS RECOMMENDED BY MANUFACTURER.

3. COORDINATE LOCATION OF ALL EXIT SIGNS IN THE FIELD WITH OWNER SUPPLIED EQUIPMENT, BULK HEADS AND SIGNAGE TO ENSURE VISIBILITY FROM AT LEAST HALFWAY TO NEXT SIGN OR TO THE EXIT.

4. PROVIDE DOUBLE OR SINGLE FACE EXIT SIGNS AS INDICATED ON THE DRAWINGS. PROVIDE ARROWS AS INDICATED.

5. ALL FIXTURE FINISHES AND DECORATIVE DETAILS SHALL BE SELECTED BY THE ARCHITECT PRIOR TO FINAL ORDER.

COLORS SHALL BE SELECTED FROM FULL COLOR LINE (BOTH STANDARD, CUSTOM, AND PREMIUM).

6. FIXTURES INDICATED ARE THE BASIS OF DESIGN. ALL EQUALS SHALL HAVE THE SAME PERFORMANCE AND GENERAL SHAPE AND OPTIONS. ALL EQUALS ARE TO BE APPROVED BY THE ARCHITECT AND ENGINEER

PRIOR TO ORDERING.

7. ALL FIXTURES CONNECTED TO A DIMMER, LIGHTING CONTROL SYSTEM, OR STAGE LIGHTING CONTROL SYSTEM SHALL HAVE DRIVER THAT COORDINATES WITH CONTROLLER. COORDINATE BEFORE ORDERING.

AUDITORIUM FIXTURE DRIVERS SHALL BE SELECTED AS PER THEATRICAL SYSTEM BASIS OF DESIGN REQUIREMENTS AND THEN COORDINATED PRIOR TO FINAL ORDERING WITH SELECTED SYSTEM.

F

F

F AUDIO ALARM - CEILING MOUNTED

AUDIO/VISUAL ALARM - CEILING MOUNTED

VISUAL ALARM - CEILING MOUNTED

NOTE:

NOT ALL ABBREVIATIONS AND SYMBOLS INDICATED MAY APPEAR ON

THESE CONTRACT DRAWINGS. THIS IS FOR REFERENCE ONLY.

CEILING/

DOME

WALL/

DOME

BULLET

CAMERA

EXISTING SURFACE MOUNTED PANEL

EXISTING FLUSH MOUNTED PANEL

IM

R ADDRESSABLE RELAY

ADDRESSABLE INPUT MODULE

OS

S

S

S

S

S

S

S

S

S

S

S

S

CT

FB

WIRING DEVICES

SINGLE POLE SWITCH - 3'-10" AFF UNLESS OTHERWISE

NOTED

3-WAY SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED

4-WAY SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED

KEY SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED

SPRING WOUND TIME SWITCH, 5-MINUTE MAXIMUM

DURATION - 3'-10" AFF UNLESS OTHERWISE NOTED

SPRING WOUND TIME SWITCH, 1-HOUR MAXIMUM

DURATION - 3'-10" AFF UNLESS OTHERWISE NOTED

DIMMER SWITCH - 3'-10" AFF UNLESS OTHERWISE

NOTED

MANUAL MOTOR STARTER SWITCH - 3'-10" AFF UNLESS

OTHERWISE NOTED

3-WAY DIMMER SWITCH - 3'-10" AFF UNLESS

OTHERWISE NOTED

OCCUPANCY SENSOR SWITCH - 3'-10" AFF UNLESS

OTHERWISE NOTED

PILOT LIGHT SWITCH - 3'-10" AFF UNLESS OTHERWISE

NOTED

MANUAL OVERRIDE

TAMPERPROOF DUPLEX RECEPTACLE - NEMA

5-20R, MOUNT 1'-6" AFF UNLESS OTHERWISE NOTED

TAMPERPROOF COUNTER TOP DUPLEX RECEPTACLE

MOUNT 3" ABOVE BACKSPLASH OR AT 3'-10"

TAMPERPROOF SINGLE RECEPTACLE - MOUNT 1'-6"

AFF UNLESS OTHERWISE NOTED

TAMPERPROOF GFI DUPLEX RECEPTACLE - MOUNT AT

1'-6" AFF UNLESS OTHERWISE NOTED

TAMPERPROOF QUAD RECEPTACLE - NEMA 5-20R,

MOUNT 1'-6" AFF UNLESS OTHERWISE NOTED

SINGLE PHASE SPECIAL RECEPTACLE - MOUNT 1'-6" AFF

UNLESS OTHERWISE NOTED

FLOOR BOX MOUNTED TAMPERPROOF DUPLEX

RECEPTACLE

COMBINATION POWER/COMMUNICATIONS FLOOR

BOX-DEVICES AS INDICATED

DUAL TECHNOLOGY OCCUPANCY SENSOR - 360°

3D

OS

P

MO

K

T5

T

D

M

S

MULTIPLE BUTTON DIGITAL CONTROL STATION WITH

CONTROL AS REQUIRED BY ROOM ZONING AND/OR

REQUIREMENTS IN THE SEQUENCE OF OPERATION -

3'-10"AFF UNLESS OTHERWISE NOTED.

LC

S SWITCH WITH OCCUPANCY SENSOR AND DIMMING

CAPABILITY 3' 10"AFF UNLESS NOTED OTHERWISEDos

TAMPERPROOF DUPLEX RECEPTACLE WITH TOP

SWITCHED - 1'-8" AFF UNLESS NOTED OTHERWISE

OS

DUAL TECHNOLOGY OCCUPANCY SENSOR - CORRIDOR

PATTERN

THREE PHASE SPECIAL RECEPTACLE - MOUNT 1'-6" AFF

UNLESS OTHERWISE NOTED

R CORD REEL

OS DUAL TECHNOLOGY OCCUPANCY SENSOR - HIGH BAY

HB

PS

PHOTOCELL SENSOR - WEATHERPROOFWP

D A T E

S H E E T a rc h it e c tu re w o rk s h o p in c o n e s o u th r a ilr o a d s tr e e t h a n o v r n n s y lv a n ia p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

M E

P _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

EL

EC

TR

IC

AL

IN

FO

RM

AT

IO

N S

H

EE

T

P R

O P

O S

E D

A

D

IT

IO

N

R E

N O

V A

T

IO

N

E0.0

11.04.2026

BID

J A

C K

S O

N T

O W

N S

H

IP

M U

N

IC

IP

A

L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

P

R

IN

G G

R O

V

N

N S

Y

LV

A N

IA

LIGHTING FIXTURE SCHEDULE

SYMBOL MANUFACTURER & CATALOG NUMBER

MOUNTING

TYPE

DESCRIPTION LAMP REMARKS

B COLUMBIA - CBT22-B-LSCS-EDD-4000K RECESSED LED 2X2 FLAT PANEL SWITCHABLE CCT SET TO MEDIUM LIGHTING, 4000K LED

B1

COLUMBIA - CBT22-B-LSCS-EDD-4000K

ACCESSORY: FK22 FLANGE KIT (DRYWALL MOUNT)

RECESSED LED 2X2 FLAT PANEL SWITCHABLE CCT SET TO MEDIUM LIGHTING, 4000K LED

B1E

COLUMBIA - CBT22-B-LSCS-EDD-4000K-ELL14

ACCESSORY: FK22 FLANGE KIT (DRYWALL MOUNT)

RECESSED LED 2X2 FLAT PANEL SWITCHABLE CCT SET TO MEDIUM LIGHTING, 4000K WITH BATTERY BACK UP LED

BE COLUMBIA - CCL22-LSCS-MED-4000K-ELL14 RECESSED LED 2X2 FLAT PANEL SWITCHABLE CCT SET TO MEDIUM LIGHTING, 4000K WITH BATTERY BACK UP LED

D COLUMBIA - CRN2-1-LSCS-ED-MV-SO-W PENDANT NEMA 4X WET LOCATION HIGH BAY LIGHTS 150W 21K LUMEN 4000K LED

D1 LUMINIS - OC750-L20-FLD-35K-120 PENDANT NEMA 4X WET LOCATION HIGH BAY LIGHTS 150W 21K LUMEN 4000K LED

D1E LUMINIS - OC750-L20-FLD-35K-120-REM7 PENDANT NEMA 4X WET LOCATION HIGH BAY LIGHTS 150W 21K LUMEN 4000K LED

DE COLUMBIA - CRN2-1-LSCS-ED-MV-SO-W-IRH-ELL40 PENDANT NEMA 4X WET LOCATION HIGH BAY LIGHTS 150W 21K LUMEN 4000K WITH BATTERY BACK UP LED

F1 COLUMBIA - CSL4-A-LSCS-CM24SCF5-KIT PENDANT PENDANT MOUNT 4' LINEAR STRIP LED LIGHT LED

F2 COLUMBIA - CSL4-A-LSCS SURFACE WALL MOUNT 4' LINEAR STRIP LED LIGHT LED

S1 SOLAR ILLUMINATIONS - SL15-30W-TYPE2-COMPLETE SYSTEM POLE SINGLE LAMP HEAD SITE LIGHT AND POLE WITH COMPLETE ALL ENCLOSED SOLAR SYSTEM LED

S2 SOLAR ILLUMINATIONS - SL22-30W-TYPE2-COMPLETE SYSTEM POLE TWO LAMP HEAD SITE LIGHT AND POLE WITH COMPLETE ALL ENCLOSED SOLAR SYSTEM LED

W1E COLUMBIA - SGW1-70-LSCS-UNVC-PC-EH SURFACE WALLPACK WITH INTEGRAL PHOTOCELL AND BATTERY BACK-UP LED

X COLUMBIA - CERGB SURFACE UNIVERSAL EXIT SIGN WITH BATTERY BACKUP AND DAMP RATING LED

X2 COLUMBIA - EXE4X SURFACE NEMA 4X EXIT SIGN WITH BATTERY BACK UP LED

ELECTRICAL DRAWING LIST

E0.0 ELECTRICAL INFORMATION SHEET

E0.1 SITE PLAN - ELECTRICAL

E1.0 FIRST & MEZZ. FLOOR PLANS - LIGHTING

E2.0 FIRST & MEZZ. FLOOR PLANS - POWER

E2.1 ROOF PLANS - POWER

E3.0 ENLARGED PLANS - ELECTRICAL

E4.0 ELECTRICAL DETAILS

E5.0 ONE-LINE DIAGRAM AND PANEL SCHEDULES

ED1.0 FIRST FLOOR PLAN - DEMOLITION

tag rev date revision note

JB

SALT SHED

STORAGE GARAGE

MAIN BUILDING

150KVA GENERATOR

SEE SINGLE LINE DIAGRAM ON E5.0 FOR FEEDER SIZES

SEE DETAIL 7/E4.0 FOR ADDITIONAL INFORMATION

E.C. TO ROUTE CONDUITS UNDERGROUND AND CONNECT TO 600A ATS-1

UTILITY APPROVED CT CABINET

EXACT LOCATION TO BE

COORDINATED WITH UTILITY

SEE SINGLE LINE DIAGRAM

FEEDER SIZES

PANEL 'SG'

CONCRETE PAD2

E2.0

S2

S1

S1

S1

S2

S2

APPROXIMATE LOCATION

OF UTILITY POLE

E.C. TO PROVIDE 4" CONDUIT FOR NEW SERVICE

CONDUCTORS PER UTILITY REQUIREMENTS

S1

SPARE 5" CONDUIT

FOR FUTURE SOLAR EQUIPMENT

E.C. TO PROVIDE (2) 1" CONDUIT, CAPPED WITH PULL

STRING, FOR FUTURE GATE CONNECTIONS.

COORDINATE EXACT LOCATION IN FIELD WITH OWNER. 'C'-96

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

M E

P _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

SI

TE

P

LA

N

EL

EC

TR

IC

AL

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

E0.1

11.04.2026

BID

J A

C K

S O

N T

O W

N S

H

IP

M U

N

IC

IP

A

L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

SCALE: 1" = 20'-0"

SITE PLAN1

NOTES BY SYMBOL: #

(THIS DRAWING ONLY)

1 EC SHALL FURNISH AND INSTALL NEW 150 KW DIESEL GENERATOR,

FUEL PUMP, LOAD BANK, ACCESSORIES, CONTROLS, AND

REQUIRED PAD OR SUPPORTS.

CONCRETE PAD TO BE PROVIDED BY OTHERS. FINAL CONCRETE PAD

DIMENSIONS, REINFORCEMENT, AND ANCHORAGE REQUIREMENTS

MUST BE COORDINATED WITH AND VERIFIED AGAINST THE SELECTED

GENERATOR VENDOR'S REQUIREMENTS PRIOR TO CONSTRUCTION.

SOLAR SITE LIGHT IS A COMPLETE SELF-CONTAINED SOLAR LIGHTING

SYSTEM INCLUDING POLE, SOLAR PANEL, BATTERIES, CONTROLLER,

FIXTURE AND ALL ASSOCIATED WIRING. NO BRANCH CIRCUIT

CONNECTION REQUIRED.

3 3

3D

OS OS

D

DOS

OS

O S

OS

D D DD D D

O S

O S

D

OS

OS

OS

OS OS

OS

OS

OS

OS OS OS OS OS

OS

OS

OS

OS

OS

OS

OS

OS OSOSOS

OS OS

OS OSOS

OS

OS

OS

OS

3 3 3

OS OSOS

OS OS

3 3

OS

OS

OS

D

OS

OS

OS

REPAIR GARAGE

REPAIR GARAGE

ARCHIVE

HALL

MEETING ROOM

WOMEN

MEN

STORAGE

OFFICE

LOBBY

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HALL

CONFERENCE

BREAK ROOM

MEN

WOMEN

STORAGE

HALL

MEN

SHOWER

WOMEN

JANITOR

TELE-COM

OFFICE

HALL

WORK ROOM

D

DE

DE

DE

DE

D

D

DE

D

DE

DE

DE

D

D

B1E

B1

B1

B1

B1E

B1

B1

B1

B1

B1E

B1

B1

B1

B1

B1

B1E

DE

DE

DE

DE

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

DE

D

DE

D

DE

D

DE

DE

DE

D

DE

B

BE

BE

BE

B

BE

BE

BE

B

B

B

B

B

BE

B

B

BE

B

B

BE

B

B

B

BE

B

B

B

B

BE

B

B

B

B

BE

B

B

B

B

B

B

B

BE

B

BE

B

B

B

BE

B

B

B

BE

B

B

B

B

BE

BE

BE

BE

B

B

B

B

BE

B

BE

5 BE

3 B

BE

B

BE

B1

B1

B1

B1

B1

B1E

B1

B1

B1

BE

BE

B1

B1

B1

B1E

B1E

B1

F2

F2

F2

F2

F2

HB

HB

HB

HBHBHB

HBHB

'C'

D

D a a a a aa a a a b b b b b b b b b b b b a a a a a a a a aaaa a a a a b b b b

HBHBHB

HBHB

HB

HB

a a a a aa a a a b b bbb b b a a a a

B1 a a

X

X

X

X

X X

X

X

X

X

XX

WP WP

WPWP

WP WP WP

WPWPWP

WP WP

WPWP

BE

5D

D a a

D a

W1E

W1E

W1E

W1E

W1E

W1E

W1E

W1E

+15'-0"

W1E

W1E

+15'-0"

W1E

W1E

W1E

W1E

+15'-0" +15'-0" +15'-0" +15'-0"

+15'-0"

+15'-0"

+15'-0"

W1E

+15'-0"

+15'-0"+15'-0"+15'-0"

+15'-0"

+15'-0"

D1E

D1

D1

D1E

PS

WP

+15'-0"

W1E

F1

STORAGE

F1

F1

F1

F1

F1

F1

OPEN TO BELOW

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

M E

P _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

FI

RS

T

M

EZ

Z.

F

LO

O

R

PL

AN

S

LI

G H

TI

N

G

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

E1.0

11.04.2026

BID

J A

C K

S O

N T

O W

N S

H

IP

M U

N

IC

IP

A

L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

NOTES BY SYMBOL: #

(THIS DRAWING ONLY)

1 EC TO FIELD COORDINATE LOCATION OF LIGHT SWITCH WITH

LOCATION OF REMOVABLE RAILING ACCESS.

PROVIDE EXTERIOR PHOTOCELL CONTROL FOR CANOPY

LIGHTING. PHOTOCELL SHALL AUTOMATICALLY CONTROL

LIGHTING FROM DUSK TO DAWN.

GENERAL NOTES:

1. CONNECT EXIT SIGNS AND EMERGENCY BATTERY DRIVERS WITHIN

LIGHTS TO NEAREST UNSWITCHED LIGHTING CIRCUIT WITH 2#12 &

1 12G IN MC CABLE.

2. ALL ASSOCIATED ROOM CONTROLLERS SHALL BE LOCATED

ABOVE ACCESSIBLE CEILINGS.

3. ALL LIGHT FIXTURES ARE CIRCUITED TO PANEL 'CL', UNLESS

OTHERWISE NOTED.

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - LIGHTING1

SCALE: 1/8" = 1'-0"

MEZZANINE PLAN - LIGHTING2

FB

FB

M M

M M

M

F S S F S

F

F

F

F

F

FF

F

M

F

F

F

F

FF

F

F

F

F S

S

SSSSS

F S

SS

C

C

C

C

C

C

C

C

C

C

C C

S

S

S

S

S

S

JB JB JB JB JB

JB

JB

JB

JB

JB

C R

CR

C R

F

F F

FB

FB

M

F F

C

M

M

FB

FB

C R

JB

JB

M

JB

S

C R

C R

C R

CR

S S

S

S SS

S

S

S

M M

M

(ETR) PANEL 'A'

(ETR) DISCONNECT SWITCH

(ETR) PANEL 'B'

UH-1

(EX)UH

UH-2

REPAIR GARAGE

REPAIR GARAGE

ARCHIVE

HALL

MEETING ROOM

WOMEN

MEN

STORAGE

OFFICE

LOBBY

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HALL

CONFERENCE

BREAK ROOM

MEN

WOMEN

STORAGE

HALL

MEN

SHOWER

WOMEN

JANITOR

TELE-COM

OFFICE

HALL

WORK ROOM

CT CTCT

CTCTCT

CT

CT

CT

WP

WP

WP

WP WP

WP

WP

WP

WPWP

WP WP

WP

WP

WP

WP

WP

WP

WP

WP

WP

WP WP

WP

WP WP

WP

WP

WP

WP

ATS-1

PANEL 'MDP'

PANEL 'C'

30 30

WP

+72"

WP

+72"

WP

+72"

WP

+72"

WP

+72"

WP

+72"

WP

+72"

WP

+72"

WP

+72"

WP

+72"

WP

+72"

WP

+72"

WP

+72"

CT

CT

CT

CTCT

29 29 33

+78" +78"

47 47

3739354143

23 25

27 1 1 7 7

46 46

44 48

38 36 3440

52 52

32 +78"

+78"

+78"

+78"

19 11 13 15

EBB-3

EBB-2

EBB-1

106812

12 8

UH-4

UH-3

1"C

1"C

PANEL 'CL'

EXISTING WATER

WELL PUMP

(3)#10, #10G - 3/4"C

30/1/NF/12

'C'-66

30/1/NF/12

'C'-66

30/1/NF/12

'C'-68

30/1/NF/12

'C'-68

'C'

'C'

'C'

'C'

'C'

'C' 'C'

'C'

'C'

'C'

'C' 'C' 'C' 'C' 'C'

'C'

'C'

'C'

'C'

'C'

'C'

'C' 'C' 'C'

'C'

'C'

'C'-62,64

FACP

FIRE ALARM

ANNUNCIATOR PANEL

75,77

WP

WP

70,72 74,76

WP

78,80

WP

82,84

WP

79,81 86,88

1"C

1"C

15 15

15 15

75 75

IEWH-1IEWH-2

85 83

OIL MONITORING

ALARM PANEL

3/4"C 6

OWS1

'C'

2 1"C

1"C

+78"

+78"

+78" +78"93

59 59

9 9 9 9

EWH-1

PTAC-1

30/2/NF/12

'C'-95,97

71,73 99

92,94

WP

'C'

'C'

VEF-1

GWH2 GWH1

HWRP1

56 54

14 14

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

M E

P _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

FI

RS

T

M

EZ

Z.

F

LO

O

R

PL

AN

S

PO

W

ER

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

E2.0

11.04.2026

BID

J A

C K

S O

N T

O W

N S

H

IP

M U

N

IC

IP

A

L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

NOTES BY SYMBOL: #

(THIS DRAWING ONLY)

1 EXISTING PANEL TO REMAIN IN SERVICE. NO NEW LOADS, CIRCUITS,

OR EQUIPMENT SHALL BE CONNECTED TO THIS PANEL. EXISTING

LOADS SHALL REMAIN AS CURRENTLY CONFIGURED UNLESS

OTHERWISE NOTED.

POWER AND DATA FOR TV. E.C. TO COORDINATE FINAL DEVICE

LOCATION AND MOUNTING HEIGHT WITH OWNER PRIOR TO ROUGH IN.

EXISTING WATER WELL PUMP TO REMAIN. EXISTING WATER WELL

PUMP IS A 'CENTRIPRO M05422, 1/2 HP, 240V, 1Ø, 4A'. E.C. SHALL

PROVIDE NEW CONDUCTORS AS INDICATED AND RECONNECT FOR

PROPER OPERATION.

PROVIDE AND INSTALL FOUR COMPARTMENT DIVIDED FLOOR BOX

WITH (2) DUPLEX RECEPTACLES AND (2) CAT6 DATA PORTS.

BASIS OF DESIGN: WIREMOLD EF4BS SERIES.

COORDINATE EXACT LOCATION WITH OWNER REPRESENTATIVE PRIOR

TO ROUGH-IN.

WIRE HOT WATER RECIRCULATION PUMP THROUGH TIME CLOCK AND

AQUASTAT PROVIDED BY PLUMBING CONTRACTOR. EC SHALL INSTALL

TIME CLOCK PROVIDE ALL REQUIRED CONNECTIONS FOR A COMPLETE

AND OPERATIONAL SYSTEM. COORDINATE EXACT CONTROL

SEQUENCE AND DEVICE LOCATIONS WITH PLUMBING CONTRACTOR.

ADD ALTERNATE: PROVIDE CONDUIT AND ASSOCIATED WIRING

BETWEEN OIL STORAGE TANK AND OIL LEVEL MONITORING ALARM

PANEL. COORDINATE EXACT REQUIREMENTS WITH SYSTEM

MANUFACTURER.

ADD ALTERNATE: OIL LEVEL MONITORING SYSTEM TO BE 120V, SINGLE

PHASE 'SLICK STICK' PANEL OR APPROVED EQUAL. COORDINATE

ELECTRICAL REQUIREMENTS, POWER CONNECTIONS, CONTROL

WIRING, AND ASSOCIATED ACCESSORIES WITH MANUFACTURER'S

REQUIREMENTS.

THIS SPACE IS CLASSIFIED AS A HAZARDOUS LOCATION IN

ACCORDANCE WITH NEC ARTICLE 511. INSTALL ALL RECEPTACLES AND

WIRING DEVICES A MINIMUM OF 24" ABOVE FINISHED FLOOR.

E.C. TO PROVIDE FINAL POWER AND CONTROL CONNECTIONS TO

DOOR CONTROLLER. E.C. SHALL INSTALL DOOR CONTROL WIRING

BETWEEN CONTROLLER AND DOOR OPERATOR/MOTOR AND

COMPLETE SYSTEM WIRING REQUIRED FOR A FULLY FUNCTIONAL

INSTALLATION. COORDINATE EXACT REQUIREMENTS WITH DOOR

CONTROL SYSTEM SUPPLIER AND EXACT LOCATION WITH OWNER.

CARD READER SHALL BE COMBINATION KEYPAD AND PROXIMITY TYPE.

COORDINATE FINAL DEVICE LOCATIONS, MOUNTING AND SYSTEM

REQUIREMENTS WITH OWNER.

PROVIDE FIRE ALARM CONNECTION TO ROLLING FIRE DOOR RELEASE

DEVICE. DOOR SHALL AUTOMATICALLY DESCEND UPON FIRE ALARM

ACTIVATION.

PROVIDE WHITE CHIEF PAC525FC IN-WALL TV POWER AND CABLE

MANAGEMENT BOX AT TV LOCATION. COORDINATE EXACT MOUNTING

HEIGHT AND REQUIREMENTS WITH OWNER.

EMERGENCY RESPONDER RADIO COVERAGE SYSTEM (ERRCS/ERCES)

NOT INCLUDED IN ELECTRICAL CONTRACTOR SCOPE. OWNER TO

COORDINATE WITH AHJ REGARDING APPLICABILITY, WAIVER

REQUESTS, TESTING, PERMITTING, PROCUREMENT, INSTALLATION,

AND ALL ASSOCIATED REQUIREMENTS.

JUNCTION BOX FOR FUTURE SIGN. COORDINATE EXACT LOCATION

WITH ARCHITECTURAL DRAWINGS AND IN FIELD WITH OWNER.

SWITCH FOR OUTDOOR SIGNAGE. COORDINATE EXACT LOCATION

WITH OWNER IN FIELD.

GENERAL NOTES:

1. WHERE CONDUIT AND WIRE PENETRATES THE WALL, THE WALL

SHALL NOT ACT AS A SUPPORT. THE RACEWAY SHALL BE

INDEPENDENTLY SUPPORTED ON EACH SIDE OF THE WALL. IF THE

WALL PENETRATION IS NOT SEALED, PROVIDE WALL SLEEVE TO

PROTECT RACEWAY FROM DAMAGE. WALL AND FLOOR

PENETRATIONS SHALL BE CUT USING HOLE SAWS OR EQUIVALENT.

PENETRATIONS SHALL NOT HAVE JAGGED EDGES.

2. COORDINATE THE HEIGHT AND LOCATION OF ALL RECEPTACLES

WITH OWNER PRIOR TO INSTALLATION/ROUGH-IN.

3. ALL FINAL DATA JACK LOCATIONS ARE TO BE COORDINATED WITH

OWNER.

4. CONTRACTOR SHALL LABEL EACH RECEPTACLE WITH THE CIRCUIT

NUMBER THAT SERVES IT.

5. ALL EXISTING TO REMAIN RECEPTACLES, EQUIPMENT, AND

ASSOCIATED DEVICES SHALL NOT BE EXTENDED, MODIFIED, OR

CONNECTED TO SERVE NEW LOADS ASSOCIATED WITH THIS

PROJECT.

6. ALL NEW POWER LOADS ARE CIRCUITED TO PANEL 'C', UNLESS

OTHERWISE NOTED

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - POWER1

SCALE: 1/8" = 1'-0"

MEZZANINE PLAN - POWER2

tag rev date revision note

RTU-1

(EX)EF

MAU-2

(EX)EF

MAU-3

(EX)EF

MAU-1

EF-3

EF-2EF-1

RTU-3 RTU-2

WPWP

WP

WP

WP

'C'-16'C'-16

60/2/NF/3R

MDP-10,12

60/2/NF/3R

MDP-6,8

60/2/NF/3R

MDP-14,16

60/2/NF/3R

MDP-18,20

60/2/NF/3R

MDP-13,15

30/2/NF/3R

MDP-2,4

30/2/NF/3R

PANEL C-67,69

30/1/NF/3R

PANEL C-65

30/1/NF/3R

PANEL C-65

PANEL C-18

PANEL C-18

PANEL C-18

MAU-5

MAU-4

WP

'SG'-23

'SG'-23

60/2/NF/3

'SG'-10,12

30/2/NF/3R

PANEL 'SG'-18,20

WP

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

M E

P _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

RO

O

F

PL

AN

S

PO

W

ER

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

E2.1

11.04.2026

BID

J A

C K

S O

N T

O W

N S

H

IP

M U

N

IC

IP

A

L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

GENERAL NOTES:

1. WHERE CONDUIT AND WIRE PENETRATES THE WALL, THE

WALL SHALL NOT ACT AS A SUPPORT. THE RACEWAY SHALL

BE INDEPENDENTLY SUPPORTED ON EACH SIDE OF THE

WALL. IF THE WALL PENETRATION IS NOT SEALED, PROVIDE

WALL SLEEVE TO PROTECT RACEWAY FROM DAMAGE. WALL

AND FLOOR PENETRATIONS SHALL BE CUT USING HOLE

SAWS OR EQUIVALENT. PENETRATIONS SHALL NOT HAVE

JAGGED EDGES.

2. COORDINATE THE HEIGHT AND LOCATION OF ALL

RECEPTACLES WITH OWNER PRIOR TO

INSTALLATION/ROUGH-IN.

3. CONTRACTOR SHALL LABEL EACH RECEPTACLE WITH THE

CIRCUIT NUMBER THAT SERVES IT.

4. ALL EXISTING TO REMAIN RECEPTACLES, EQUIPMENT, AND

ASSOCIATED DEVICES SHALL NOT BE EXTENDED, MODIFIED,

OR CONNECTED TO SERVE NEW LOADS ASSOCIATED WITH

THIS PROJECT.

SCALE: 1/8" = 1'-0"

ROOF PLAN - POWER1

SCALE: 1/8" = 1'-0"

STORAGE GARAGE ROOF PLAN - POWER2

CR CR

F

F F

F

F

C

C

C C

C

C

OS OS OS OS OS OS

WP

WP

WP

WP

WP

WP

WP

WP

WPWP WPWPWP

WP

WP

WP WP WP

WP

1313139

11 11

PANEL 'SG'

WDUH-1 WDUH-2

STORAGE

WASH BAY

UH-5

UH-6

UH-7

60/2/NF/4X

'SG'-2,4

60/2/NF/4X

'SG'-6,8

30/1/NF/3R

'SG'-17

30/1/NF/3R

'SG'-19

30/1/NF/3R

'SG'-19

30 30

WP

+72

WP

+72

WP

+72

WP

+72

WP

+72

WP

+72

WP

WPWP

WP

WP

EF-4

EF-5 30/2/NF/4X

'SG'-14,1630/1/NF/3R

'SG'-22

DE

DE

D

DE

DE

DE

D

DE

D

D

DE

DE

D

DE

D

DE

D

DE

D

D

DE

1 D

DE

D

DE

D

DE

HBHBHBHBHBHB

X X X2

STORAGE

STORAGE

WASH BAY

WP

d

WP

W1E

W1E

+15'-0"+15'-0" +15'-0" +15'-0" +15'-0" +15'-0" +15'-0"

W1E

W1E

W1E

W1E

W1E

W1E

W1E

+15'-0" +15'-0" a b a a a a a a a a a a a a a a a bbbb f g c c c c c c d d d d d d c

WP

f

WP

g

WP

3 3

2 2 2 222222 gb

3 a

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

M E

P _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

EN

LA

RG

ED

P

LA

N S

EL

EC

TR

IC

AL

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

E3.0

11.04.2026

BID

J A

C K

S O

N T

O W

N S

H

IP

M U

N

IC

IP

A

L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

GENERAL NOTES:

1. CONNECT EXIT SIGNS AND EMERGENCY BATTERY DRIVERS WITHIN

LIGHTS TO NEAREST UNSWITCHED LIGHTING CIRCUIT WITH 2#12 &

1 12G IN MC CABLE.

2. ALL LIGHT FIXTURES ARE CIRCUITED TO PANEL 'SG', UNLESS

OTHERWISE NOTED.

SCALE: 1/8" = 1'-0"

STORAGE GARAGE FLOOR PLAN - POWER1

SCALE: 1/8" = 1'-0"

STORAGE GARAGE FLOOR PLAN - LIGHTING2

tag rev date revision note

NOTES BY SYMBOL: #

(THIS DRAWING ONLY)

1 DEVICE BOXES FOR RECEPTACLES LOCATED IN THE WASH

BAY AREA SHALL BE NONMETALLIC, CORROSION-RESISTANT

PVC. RACEWAYS SERVING ALL DEVICES IN THE WASH BAY

AREA SHALL BE PVC-COATED IMC COMPLETE WITH FITTINGS

LISTED AND IDENTIFIED FOR USE WITH THE PVC-COATED

CONDUIT SYSTEM TO MAINTAIN CORROSION PROTECTION.

PROVIDE CORROSION-RESISTANT PVC EXTRA-DUTY

WEATHERPROOF IN-USE COVERS FOR ALL RECEPTACLES.

EXTERIOR LIGHT FIXTURE IS TO OPERATE WITH INTEGRAL

DUSK-TO-DAWN PHOTOCELL CONTROL.

MANUAL OVERRIDE SWITCH FOR EXTERIOR LIGHTING.

LIGHTING SHALL NORMALLY OPERATE VIA DUSK-TO-DAWN

PHOTOCELL CONTROL WHEN SWITCH IS IN THE OFF

POSITION. LIGHTING SHALL OPERATE REGARDLESS OF

PHOTOCELL STATUS WHEN SWITCH IS IN THE ON POSITION.

LC

POLE SEE LIGHTING

SCHEDULE

MINIMUM OF 3"

MINERAL WOOL

INSULATION

FIRMLY PACKED

CONDUIT

STEEL SLEEVE

MINIMUM 1" THICK COMPOUND

APPLIED WITHIN OPENING ,

FLUSH WITH BOTH SURFACES

OF THE WALL

STEEL SLEEVE

CONDUIT

NOTE:

• MINIMUM 3HR FIRE RATING OF SEALING ASSEMBLY

• -UL SYSTEM C-AJ-1081

SECTION 'A-A'

AA

MINIMUM 1" THICK COMPOUND

WITHIN OPENING, FLUSH WITH

BOTH SURFACES OF THE WALL

GYPSUM WALLBOARD/STUD WALL ASSEMBLY

CONDUIT

MINIMUM 2-1/2" THICK MINERAL

WOOL INSULATION FIRMLY PACKED

SECTION 'A-A'

NOTE:

• MINIMUM 2HR FIRE RATING OF SEALING ASSEMBLY

• UL SYSTEM W-L-1027

A

A

CONDUIT

MIN 2-1/2" THICK MINERAL WOOL

INSULATION FIRMLY PACKED

A

MIN 1" THICK COMPOUND

APPLIED WITHIN OPENING, FLUSH

WITH BOTH SURFACES OF THE WALL

GYPSUM WALLBOARD/STUD WALL

ASSEMBLY

SECTION 'A-A'

NOTE:

MINIMUM 2HR FIRE RATING OF SEALING FOR

ASSEMBLY SYSTEM.

W-L-1027

A

PROVIDE CABLING AND

RACEWAY BACK TO

MDF/IDF. PROVIDE

BUSHINGS AT THE END OF

ALL CONDUIT RUNS.

SUSPENDED CEILING

3/4" EMT CONDUIT IN WALL

SINGLE GANG BOX WITH

COVER PLATE, SIDE

MOUNTED TO STUD

NEW WALL OR PARTITION

FLOOR

BATTERYDACT

120 VAC

EARTH

GROUND

F SD F

(1) #18STP

JB FJB

(1) #18STP &

(2) #14AWG

(1) #18STP

SD

ANNUNCIATOR

STROBE CIRCUIT

(2) #12AWG FPL

AUDIO CIRCUIT

SDF SD SD SD SD F

STROBE

CIRCUIT

AUDIO

CIRCUIT

SD F

JB JB F SD SD SD SD SD FSD

AUDIO

CIRCUIT

STROBE

CIRCUIT

1 1 1 1 1 1 1

FD/SDFD/SD LOCATED NEAR

MAIN ENTRANCE

(VERIFY W/ AHJ)

REFER TO

FLOOR

PLANS FOR

LOCATION

FIRE ALARM

PANEL

PROVIDE (2) TELCO LINES

TERMINATED TO RJ31X TELEPHONE

BLOCKS INSTALLED BY

ELECTRICAL CONTRACTOR.

F FF F

FF

F

FFFFF

SD

D

SD

D

NOTES:

1. FURNISH ALL DUCT DETECTORS AND ASSOCIATED WIRING. MECHANICAL CONTRACTOR TO INSTALL DETECTORS. CONTRACTOR

SHALL REFER TO MECHANICAL PLANS FOR DUCT DETECTOR LOCATIONS AND QUANTITIES.

2. DIAGRAMMATIC ONLY - NUMBER OF DEVICES DOES NOT MATCH THOSE SHOWN ON THE DRAWING.

3. PROVIDE CONNECT TO ALL ZONE VALVES, FLOW AND TAMPER SWITCHES. SEE FIRE PROTECTION DRAWINGS FOR QUANTITIES

AND LOCATIONS.

4. PROVIDE CONNECTION TO SMOKE AND FIRE/SMOKE DAMPERS. SEE MECHANICAL PLANS FOR LOCATIONS AND QUANTITIES.

5. FOR ALL COMPONENTS INCLUDING THE MAIN FIRE ALARM PANEL AND EXTENDER PANELS THAT REQUIRE POWER, PROVIDE 120V, 20A DEDICATED CIRCUIT FROM NEAREST PANEL WITH SPACE. EXTEND 2#12 & 1#12GRD IN 3/4"C FOR POWER.

6. PROVIDE SMOKE DETECTOR AND HEAT DETECTOR ABOVE MAIN FIRE ALARM PANEL.

(2) #12AWG FPL

STROBE CIRCUIT

AUDIO CIRCUIT

(2) #12AWG FPL

(2) #12AWG FPL

(1) #18STP (1) #18STP

FIRE ALARM

CONNECTIONS FROM

THE STORAGE BUILDING

PIER SECTION DETAIL

NO SCALE

NOTES:

3" (TYP.)3" (TYP.)

2'-0"

DIA.

PROVIDE #1 RGS RUNOUT CONDUIT (TYP.)

3/4" CHAMFER (TYP.)

1. HEIGHT IS THE TOTAL HEIGHT MEASURED FROM FINISHED

GRADE

2. CONCRETE F'

C

=3500 PSI @ 28 DAYS

REINFORCING STEEL F

Y

=60,000 PSI

3. PROJECTED AREA OF LIGHT FIXTURE 2.0 SF OR LESS

4. NOTIFY ENGINEER IF POLE OR FIXTURE SIZE EXCEEDS LIMITS LISTED

GRADE

'A

HEIGHT A

UP TO 15'-0" 4'-6"

20'-0" 5'-0"

25'-0" 5'-6"

30'-0" 5'-6"

35'-0" 6'-0"

3"

#6 BARE COPPER WIRE AND

5/8" DIA X 10'-0" COPPER

GROUND ROD. BOND GROUND

WIRE TO ALL CONDUIT AND

POLE BASE.

FROM PREVIOUS POLE

TO NEXT POLE

(6) #5 BARS

#4 @ 10"o.c.

3" CC.

VERTICAL AND HORIZONTAL

BARS TO BE FIELD TIED.

SUPPORT REINFORCEMENT FOR

PROPER LOCATION FROM THE

FORM WORK DURING CONCRETE

PLACEMENT.

SEE PIER SECTION FOR

HORIZONTAL BAR SIZING

INSTALLATION IN CONCRETE

REQUIRES CONTINUOUS 1/2"

EXPANSION JOINT MATERIAL ALL

AROUND. SEAL WITH JOINT SEALER

PER SPECS BITUMINOUS SEALER

WHEN LOCATED IN A PAVED AREA

LIGHT POLE AND ANCHOR BOLTS

SUPPLIED BY ELECTRICAL

CONTRACTOR

POLE SEE LIGHTING

SCHEDULE FOR LENGTH OF

POLE

SEE PIER SECTION

FOR

VERTICAL BAR

SPACING AND SIZING

M

IN

4"

4"

4"

4"

TOP OF FINISHED GRADE

MAGNETIC WARNING TAPE

SUITABLE COMPACTED

BACKFILL TO MEET

LOCAL CODE

REQUIREMENTS

CONCRETE ENCASEMENT

NOTE:

ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR

CONCRETE, TRENCHING , AND BACKFILL.

EQUIPMENT GROUND BAR

EQUIPMENT GROUND

INSTALLED WITH FEEDER

ISOLATED NEUTRAL BAR

NEUTRAL CONDUCTOR

INSTALLED WITH THE FEEDER

#6 COPPER GROUND TO MINIMUM OF 2

8'-0" LONG X 5/8" DIA DRIVEN COPPER

GROUND RODS INSTALLED 6'-0" APART

CONNECT A COPPER GROUND, SIZE EQUIVALENT

TO EQUIPMENT GROUND INSTALLED WITH

FEEDER, TO ALL GROUNDING ELECTRODES

INDICATED IN NEC 250.52 PRESENT IN STRUCTURE

NEW PANEL "SG"

FEEDER SUPPLYING STRUCTURE

2-POLE TRANSFER

SWITCH

LOADS

N

N

N

N

G

SERVICE

EQUIPMENT

EQUIPMENT GROUNDING

CONDUCTOR

GROUNDING

ELECTRODE EQUIPMENT

GROUNDING

CONDUCTOR

GENERATOR

NON-SEPERATELY DERIVED

SYSTEM

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

M E

P _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

EL

EC

TR

IC

AL

D

ET

AI

LS

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

E4.0

11.04.2026

BID

J A

C K

S O

N T

O W

N S

H

IP

M U

N

IC

IP

A

L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

SCALE: 12" = 1'-0"

CONDUIT CONCRETE FLOOR/WALL PENETRATION1

SCALE: 12" = 1'-0"

WALL CONDUIT PENETRATION - FIRE SEALING2

SCALE: 12" = 1'-0"

WALL PENETRATION - FIRE SEALING3

SCALE:NO SCALE

DATA/TELEPHONE DEVICE LOCATION MOUNTING DETAIL4

SCALE:NO SCALE

TYPICAL FIRE PROTECTION SIGNALING SYSTEM RISER DIAGRAM7

SCALE: 12" = 1'-0"

POLE BASE DETAIL5

SCALE: 12" = 1'-0"

1-WAY DUCT BANK DETAIL6

tag rev date revision note

SCALE: 12" = 1'-0"

GROUNDING DETAIL - STRUCTURE SUPPLIED BY A FEEDER9

SCALE: 12" = 1'-0"

GENERATOR GROUNDING DIAGRAM10

FROM UNDERGROUND FEED TO

UTILITY POLE. REFER TO 'E0.1 -

SITE PLAN - ELECTRIC' FOR

ADDITIONAL INFORMATION

1,3 5,7

NEW MAIN DISTRIBUTION PANELBOARD 'MDP' - MAIN BUILDING

800A, 240/120V, 1Ø, 3W

(ETR)

PNL

'B'

150KW

GENERATOR

(2) SETS OF(4)350KCMIL, #1G - 3"C

400A

(ETR)

PNL

'A'

600A

LSI

N E

PNL

'SG'

100A

9,11

M

800A

ATS-1

SERVICE ENTRANCE RATED

20A 20A

13,15 17,19

STORAGE

GARAGE

400A

PNL

'C'

21,23

(2) SETS OF(4)350KCMIL, #1G - 3"C

(3)500KCMIL, #3G - 3"C

(3)#4/0, #4G - 2"C

EXISTING

50A 25A 60A 35A 60A 60A

2,4 6,8 10,12 14,16 18,20

M

RTU-3

400A

22,24

SPARE SPARE

M

MAU-1

M

MAU-2

M

RTU-1

M

RTU-2

M

MAU-3

(2)#4, #10G - 1"C

(2)#10, #10G - 3/4"C

(3)#6, #10G - 1"C

PNL

'CL'

(3)#2, #8G - 1 1/4"C

UTILITY COMPANY

APPROVED CT CABINET

SPARE

(SOLAR ARRAY EQUIPMENT)

(2)#8, #10G - 3/4"C

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

M E

P _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

O N

E-

LI

N E

D

IA

G

RA

M A

N D

P

AN

EL

S

CH

ED

U

LE

S

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

E5.0

11.04.2026

BID

J A

C K

S O

N T

O W

N S

H

IP

M U

N

IC

IP

A

L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

SCALE: 1/8" = 1'-0"

ONE-LINE DIAGRAM1

TOTAL AMPS PANEL 618

TOTAL KVA PANEL 148.4

TOTAL KVA/PHASE 75.7 72.7

23 0.0 0.0 24

SPARE 2 100 --

0.0 0.0

-- 400 2 SOLAR EQUIPMENT (FUTURE)

19 0.0 6.3 20

SPARE 2 20 --

0.0 6.3 <None> 60 2 RTU-2

15 5.7 6.3 16

RTU-3 2 50 <None>

5.7 6.3 <None> 60 2 RTU-1

11 15.9 2.7 12

PANEL 'SG' 2 225 <None>

16.3 2.7 <None> 35 2 MAU-3

7 29.0 5.0 8

PANEL 'C' 2 400 <None>

29.6 5.0 <None> 60 2 MAU-2

3 0.0 1.9 4

EXISTING PANEL 'B' 2 400 <None>

1.9 1.9 <None> 25 2 MAU-1

NO SZ NO SZ NO SZ NO SZ NO SZ NO SZ

P AMP A B AMP P

CKT CIRCUIT DESCRIPTION

BREAKER

WIRE GND

COND

KVA/PH

COND

WIRE GND

BREAKER

CIRCUIT DESCRIPTION CKT

MOUNTING: SURFACE PHASE: 1 WIRE: 3 VOLTAGE: 120/240 Single AIC: 65,000

PANEL: MDP BUS AMP: 800 A AMPS MAIN BREAKER: 800 A

TOTAL AMPS PANEL 244

TOTAL KVA PANEL 58.6

TOTAL KVA/PHASE 29.6 29.0

119 SPARE 1 20 -- 0.0 2.6 120

117 SPARE 1 20 -- 0.0 2.6

1 1/2 <None> 100 2 PANEL 'CL'

115 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 116

113 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 114

111 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 112

109 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 110

107 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 108

105 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 106

103 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 104

101 SIGN (FUTURE) 1 20 <None> 3/4 1.0 0.0 -- 20 1 SPARE 102

99 EWH-1 1 20 <None> 3/4 0.5 0.0 -- 20 1 SPARE 100

97 2.4 0.0 -- 20 1 SPARE 98

VEF-1 2 30 <None> 3/4

2.4 0.0 1" <None> 20 1 SECURITY GATE (FUTURE) 96

93 SOUTH SIDE MEETING RM TV 1 20 <None> 3/4 0.2 0.8 94

91 NORTH SIDE MEETING RM TV 1 20 <None> 3/4 0.2 0.8 3/4 <None> 20 2 MISC EQPMT - STOR 122

89 OIL MONITOR ALARM PANEL 1 20 <None> 3/4 0.1 0.2 3/4 <None> 20 1 TELE-COM 121 RECEPT 90

87 FIRE ALARM CONTROL PANEL 1 20 <None> 3/4 0.0 0.8 88

85 IEWH-2 1 40 <None> 3/4 3.5 0.8 3/4 <None> 30 2 MISC EQPMT 2 - STOR 123

83 IEWH-1 1 40 <None> 3/4 3.5 0.8 84

81 0.8 0.8 1 <None> 60 2 WELDING STATION - GARAGE 129

MISC EQPMT 1 - STOR 123 2 30 <None> 3/4

0.8 0.8 80

77 0.8 0.8 1 <None> 60 2 AIR COMPRESSOR - GARAGE 129

MISC EQPMT - STOR 122 2 30 <None> 3/4

0.8 0.8 76

73 1.7 0.8 1 <None> 60 2 WELDING STATION - GARAGE 130

PTAC-1 2 20 <None> 3/4

1.7 0.8 72

69 0.6 0.8 1 <None> 60 2 AIR COMPRESSOR - GARAGE 130

EF-1 2 20 <None> 3/4

0.6 1.2 3/4 <None> 20 1 UH-3,4 68

65 EF-2/3 1 20 <None> 3/4 0.9 1.2 3/4 <None> 20 1 UH-1,2 66

63 HALL AND LOBBY CONV RECPTS. 1 20 <None> 3/4 1.4 0.0 64

61 WOMEN 125, MEN 128 RECPTS 1 20 <None> 3/4 0.5 0.0 3/4 <None> 20 2 WATERWELL PUMP

59 TELE-COM IT RACK RECPT 1 20 <None> 3/4 0.5 1.0 3/4 <None> 20 1 EBB-1,2,3 60

57 JANITOR 120 RECPT 1 20 <None> 3/4 0.2 0.1 3/4 <None> 20 1 HWRP1 58

55 TELE-COM 121 QUAD 1 20 <None> 3/4 0.2 0.5 3/4 <None> 20 1 GWH2 56

53 CONF. RM 105 QUAD 1 20 <None> 3/4 0.2 0.5 3/4 <None> 20 1 GWH1 54

51 CONF. RM 105 CONV RECPTS. 1 20 <None> 3/4 0.5 0.4 3/4 <None> 20 1 WOMEN 116, MEN 118 - RECEPT 52

49 OFFICE 115, 117 - CONV, RECEPTS 1 20 <None> 3/4 1.1 0.4 3/4 <None> 20 1 MEN 103, WOMEN 104 RECPTS 50

47 OFFICE 108, 112 - CONV, RECEPTS 1 20 <None> 3/4 1.1 0.4 3/4 <None> 20 1 OFFICE 110 WORKSTATIONS 48

45 OFFICE 107 CONV. RECPTS 1 20 <None> 3/4 0.5 0.4 3/4 <None> 20 1 WORK 109 WORK STATIONS 46

43 OFFICE 117 WORKSTATION 1 20 <None> 3/4 0.2 0.4 3/4 <None> 20 1 WORK 109 OFFICE 110 WORKSTATIONS 44

41 OFFICE 115 WORKSTATION 1 20 <None> 3/4 0.2 0.7 3/4 <None> 20 1 BREAK RM 114 CONV. RECPTS 42

39 OFFICE 108 WORKSTATION 1 20 <None> 3/4 0.2 0.2 3/4 <None> 20 1 BREAK RM 114 REFRIG 40

37 OFFICE 107 WORKSTATION 1 20 <None> 3/4 0.2 0.2 3/4 <None> 20 1 BREAK RM 114 MICROWAVE 38

35 OFFICE 112 WORKSTATION 1 20 <None> 3/4 0.2 0.2 3/4 <None> 20 1 BREAK RM 114 COUNTER RECPT 2 36

33 STOR. 133 RECEPTS E. WALL 1 20 <None> 3/4 0.3 0.2 3/4 <None> 20 1 BREAK RM 114 COUNTER RECPT 1 34

31 STOR. 133 RECEPTS S. WALL 1 20 <None> 3/4 0.3 0.2 3/4 <None> 20 1 MEETING RM 101 TV 3 32

29 STOR. 133 RECEPTS N. WALL 1 20 <None> 3/4 0.4 0.2 3/4 <None> 20 1 MEETING RM 101 TV 2 30

27 REPAIR GARAGE 130 RECPTS 4 1 20 <None> 3/4 0.2 0.2 3/4 <None> 20 1 MEETING RM 101 TV 1 28

25 REPAIR GARAGE 130 RECPTS 3 1 20 <None> 3/4 0.3 0.7 3/4 <None> 20 1 MEETING RM 101 CONV RECPTS 26

23 REPAIR GARAGE 130 RECPTS 2 1 20 <None> 3/4 0.2 0.4 3/4 <None> 20 1 MEETING RM 101 BOARD RECPTS 24

21 REPAIR GARAGE 130 RECPTS 1 1 20 <None> 3/4 0.2 0.2 3/4 <None> 20 1 GFCI HALL 102 WATER FOUNTAIN 2 22

19 REPAIR GARAGE 130 ROLL-UP DOOR 2 1 20 <None> 3/4 0.0 0.2 3/4 <None> 20 1 GFCI HALL 102 WATER FOUNTAIN 1 20

17 REPAIR GARAGE 130 ROLL-UP DOOR 1 1 20 <None> 3/4 0.0 0.2 3/4 <None> 20 1 REC - ROOF 18

15 REPAIR GARAGE 129 ROLL-UP DOOR 3 1 20 <None> 3/4 0.0 0.3 3/4 <None> 20 1 REC - ROOF 16

13 REPAIR GARAGE 129 ROLL-UP DOOR 2 1 20 <None> 3/4 0.0 0.4 3/4 <None> 20 1 MEZZANINE RECPTS 14

11 REPAIR GARAGE 129 ROLL-UP DOOR 1 1 20 <None> 3/4 0.0 0.4 3/4 <None> 20 1 REC - OFFICE 123 WORKSTATION 12

9 STOR 122 ROLL-UP DOOR 1 20 <None> 3/4 0.0 0.4 3/4 <None> 20 1 REC - OFFICE 123 WORKSTATION 10

7 REPAIR GARAGE 129 RECPTS 4 1 20 <None> 3/4 0.2 0.5 3/4 <None> 20 1 REC - OFFICE 123 8

5 REPAIR GARAGE 129 RECPTS 3 1 20 <None> 3/4 0.3 0.5 3/4 <None> 20 1 REC - OFFICE 123 6

3 REPAIR GARAGE 129 RECPTS 2 1 20 <None> 3/4 0.3 0.0 3/4 <None> 20 1 FLOORBOX - RM 105 4

1 REPAIR GARAGE 129 RECPTS 1 1 20 <None> 3/4 0.3 0.0 3/4 <None> 20 1 FLOORBOX - RM 101 2

A B

NO SZ NO SZ NO SZ NO SZ NO SZ NO SZ

P AMP A B AMP P

CKT CIRCUIT DESCRIPTION

BREAKER

WIRE GND

COND

KVA/PH

COND

WIRE GND

BREAKER

CIRCUIT DESCRIPTION CKT

MOUNTING: SURFACE PHASE: 1 WIRE: 3 VOLTAGE: 120/240 Single AIC: 42,000

PANEL: 'C' BUS AMP: 400 A AMPS MAIN BREAKER: 1 A

TOTAL AMPS PANEL 134

TOTAL KVA PANEL 32.1

TOTAL KVA/PHASE 16.3 15.9

41 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 42

39 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 40

37 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 38

35 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 36

33 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 34

31 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 32

29 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 30

27 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 28

25 SPARE 1 20 -- 0.0 0.0 -- 20 1 SPARE 26

23 ROOFTOP RECPTS 1 20 <None> 3/4 0.2 0.0 -- 20 1 SPARE 24

21 LIGHTING - EXTERIOR 1 20 <None> 3/4 0.6 0.8 3/4 <None> 20 1 EF-5 22

19 UH-5,7 1 20 <None> 3/4 1.2 1.1 20

17 UH-6 1 20 <None> 3/4 0.6 1.1 1 <None> 20 2 MAU-5

15 STOR 901 RECPTS 4 1 20 <None> 3/4 0.4 1.2 16

13 STOR 901 RECPTS 3 1 20 <None> 3/4 0.3 1.2 3/4 <None> 20 2 EF-4

11 STOR 901 RECPTS 2 1 20 <None> 3/4 0.4 2.7 12

9 STOR 901 RECPTS 1 1 20 <None> 3/4 0.3 2.7 1 <None> 35 2 MAU-4

7 WASH BAY 900 RECPTS 2 1 20 <None> 3/4 0.3 4.1 8

5 WASH BAY 900 RECPTS 1 1 20 <None> 3/4 0.2 4.1 1 <None> 40 2 WDUH-2

3 NORMAL LIGHTING 1 20 <None> 3/4 0.2 4.1 4

1 LIGHTS WITH EMERGENCY PACKS 1 20 <None> 3/4 0.3 4.1 1 <None> 40 2 WDUH-1

A B

NO SZ NO SZ NO SZ NO SZ NO SZ NO SZ

P AMP A B AMP P

CKT CIRCUIT DESCRIPTION

BREAKER

WIRE GND

COND

KVA/PH

COND

WIRE GND

BREAKER

CIRCUIT DESCRIPTION CKT

MOUNTING: SURFACE PHASE: 1 WIRE: 3 VOLTAGE: 120/240 Single AIC: 22,000

PANEL: 'SG' BUS AMP: 225 A AMPS MAIN BREAKER: 225 A

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#10, 1-#10, 1-#10

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#10, 1-#10, 1-#10

2-#10, 1-#10, 1-#10

2-#8, 1-#8, 1-#8

2-#8, 1-#8, 1-#8

2-#12, 1-#12, 1-#12

2-#12, 1-#12, 1-#12

2-#4, 1-#4, 1-#10

SEE ONE LINE

DIAGRAM

SEE ONE LINE

DIAGRAM

SEE ONE LINE

DIAGRAM

SEE ONE LINE

DIAGRAM

SEE ONE LINE

DIAGRAM

SEE ONE LINE

DIAGRAM

SEE ONE LINE

DIAGRAM

SEE…