12-3.1 JACKSON GC STRUCTURAL DRAWINGS.pdf

PDF 2 MB Posted

Attached to
Renovations+Addition to Existing Building, New Storage Garage and Salt Storage Building
Solicitation number
US.261682
Issued by
York County, Pennsylvania

About this file

Summary of Jackson Township Municipal Center Structural Drawings

These are structural drawings for the proposed addition and renovations to the Jackson Township Municipal Center located at 439 Roths Church Road, Spring Grove, Pennsylvania 17362. The project encompasses structural design for a building addition, renovations to the existing township building, construction of a new storage garage, and a new salt storage building. The drawings detail foundation plans and site plans with finish floor elevations ranging from 580.36' to 583'-8 3/8", including specifications for foundation walls, footings, concrete slabs on grade, and underpinning procedures for the existing structure. The structural design incorporates concrete foundations with reinforced masonry and concrete walls, steel joists and beams, metal roof decking, and wood-framed roof trusses. The project is designed in accordance with the 2021 International Building Code and ASCE 7-16, with design loads including 20 PSF roof live load, 50 PSF office floor load, and 115 MPH ultimate design wind speed. The bid documents became available November 4, 2026, with sealed bids due December 8, 2026, at 1:00 PM EST via the PennBid Program. A pre-bid conference was scheduled for November 10, 2026, at 10:00 AM EST at the project site. The contract time is 400 calendar days from the Notice to Proceed, with contracts to be awarded at a regularly scheduled Jackson Township meeting on January 4, 2027.

The project is divided into four separate contracts: General Construction, Plumbing Construction, Mechanical Construction, and Electrical Construction. Each bidder must submit a bid bond or certified check equal to 10% of the maximum bid and provide evidence of qualifications to perform the work. The project is subject to the Pennsylvania Prevailing Wage Act (Act 442, P.L. 987), effective August 15, 1961, as amended. Structural specifications include soil bearing capacity of 3,000 PSF, concrete strength requirements ranging from 3,500 to 5,000 PSI depending on exposure class, reinforcing steel conforming to ASTM A615 Grade 60, and structural steel conforming to ASTM A992 for wide flange shapes and ASTM A500 Grade B for hollow structural sections. The drawings specify shop drawing requirements, special inspections by a registered geotechnical engineer for earthwork and fill placement, and quality assurance programs for masonry construction in accordance with TMS 402/ACI 530. Jackson Township reserves the right to accept any bid, waive informalities, or reject any or all bids.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S1.1

S1.2

S1.2

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.4

S1.5

S1.5

ADD-ALTERNATE

ANTI-RAM BOLLARD

& FOOTING BY OTHERS

- TYP. THIS SIDE

- SEE PLAN NOTE 1

SUBSURFACE RATE CONTROL FACILITY

SUBSURFACE STORAGE MRC FACILITY

25' FLAG POLE SONOTUBE FOUNDATION

- TYPE ST-1, SEE SCHEDULE FOR

REINFORCEMENT INFORMATION.

- TOP OF SONOTUBE TO BE +3" FROM GRADE.

- EMBEDMENT TO BE 6'-9" MINIMUM.

N

NOTES:

1. ANTI-RAM BOLLARD

A. BASIS OF DESIGN IS MODEL R-1009-04-R BY PATRIOT.

B. BOLLARD TO FOLLOW ASTM F2656-07 M30 P1.

C. FOUNDATIONS & FOOTINGS TO MEET REQUIREMENTS OF MANUF.

D A T E

S H E E T a rc h it e c tu re w o rk s h o p in c o n e s o u th r a ilr o a d s tr e e t h a n o v r n n s y lv a n ia p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

S tru ct _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

Fo un da tio n Si te P la n

P R

O P

O S

E D

A

D

IT

IO

N

R E

N O

V A

T

IO

N

S0.1

11.04.2026

BID

JA

C

K S

O N

T O

W N

S H

IP

M

U N

IC

IP

A L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

S P

R

IN

G G

R O

V

N

N S

Y

LV

A N

IA

SCALE: 3/32" = 1'-0"

FOUNDATION SITE PLAN

tag rev date revision note

CONTRACTOR SHALL VERIFY ALL CONDITIONS

AND DIMENSIONS FOR THE ENTIRE PROJECT

BEFORE PROCEEDING WITH THE WORK.

N

NOTES:

1. SEE CHART BELOW FOR FINISH FLOOR ELEVATION AND SLAB CONSTRUCTION

2. COORDINATE BRICK SHELF ELEVATIONS WITH FINISH GRADE

3. DENOTES SLEEVE LOCATIONS IN FOOTINGS/FOUNDATION WALLS

FOR UNDERGROUND PIPING - SEE TYPICAL PIPE SLEEVE THROUGH

FOUNDATION DETAIL

T.F. ***.**'

T.P. ***.**'

Step Footing Marker

Top of Pier Marker

Top of Footing Marker

Pier Size Marker

Column Footing Size Marker

Foundation Wall Size Marker

P**

W**

Foundation Wall Footing Size Marker

F*.*

WF****

Foundation Symbol Legend

T.W. ***.**' Top of Wall Marker

Transition from Standard Footing to Trench Footing Marker

Rectangular Pier Size Marker RP**

Combined Column Footing Size Marker CF*.*

Retaining Wall Footing Marker RW-*

MFW8

EWF24 EWF24

MFW8

3524135

M F

W

W F

MFW8

WF1224

M F

W

W F

M F

W

W F

M F

W

W F

M F

W

W F

M F

W

W F

MFW8

WF1224

S1.4

S1.4

MFW8-8

WF1230 MFW8-8

WF1230

M F

W

-8

W F

M F

W

-8

W F

T .F

.3

T.F. 582.36'

T .F

.3

T.F. 580.36'

T .F

.3

T.F. 582.36'

T.F. 582.36'

T.F. 580.36'

T.F. 582.36'

T.F. 580.36'

T.F. 582.36'

T.F. 580.36'

S1.4

S1.4

S1.1

S1.4TYP.

TYP.

TYP.

BOTT. OF FOOTING

TO MATCH EXISTING

T.F. 582.36'

BOTT. OF FOOTING

TO MATCH EXISTING

S3.1

S3.1

S3.1

DENOTES

UNDERPINNING

SEQUENCE

T .F

.3

T .F

.3

T .F

.3

T .F

.3

T.F. 576.36'

T.F. 578.36'

T.F. 580.36'

T.F. 574.36'

T .F

.3

T .F

.3

T .F

.3

T.F. 574.36'

W F

M F

W

-8

3" DRYPACK

#5 @ 12" o.c.

- HORIZONTAL

BAR DOWLED

PER SEQUENCE

DRAWINGS

EXISTING FDN

WALL & FTG TO

REMAIN

EXISTING FOOTING

WIDTH SAME AS

NEW SLAB ON GRADE

- SEE FDN PLAN

V .I

.F

M

IN

F

R O

M G

R A

D E

EXIST. SLAB TO

BE REMOVED

3" DRYPACK

NOTE 2

NOTE 1

1 3 5 2 4

NOTES:

1. SEQUENCE OF UNDERPINNING

2. EXCAVATE ONLY ONE 4'-0" SECTION AT A TIME

3. THE SAME NUMBER OF SEQUENCE MAY BE EXCAVATED SIMULTANEOUSLY (SEE PLAN)

1'-0"

DRIVE REBAR INTO

GROUND FOR SPLICE

20'-0"

4'-0" 4'-0" 4'-0" 4'-0" 4'-0"

UNDERPINNING PROCEDURE

1. CONTRACTOR: VERIFY CONDITIONS, ELEVATIONS & DIMENSIONS OF EXISTING WALL

2. FOUNDATIONS BEFORE PROCEEDING WITH UNDERPINNING OPERATIONS AND

NOTIFY THE ENGINEER OF ANY VARIANCE OR ADVERSE CONDITIONS THAT MAY NOT

BE PROVIDED FOR ON THE FOUNDATION DRAWINGS.

3. PERFORM ALL SHORING & BRACING AS REQUIRED TO ENSURE THE SAFETY OF THE

STRUCTURE. EXERCISE CARE THAT EXISTING STRUCTURE IS NOT FURTHER

DAMAGED IN ANY WAY.

4. REMOVE SECTIONS OF SUPPORTING EARTH 4 FEET IN LENGTH LEAVING NOT LESS

THAN 4 FEET OF SUPPORT ON EACH SIDE. SHORE AND BRACE EACH SECTION TO

PREVENT SETTLEMENT OR MOVEMENT OF STRUCTURE. DUE TO THE POOR SOIL

CONDITION BELOW THE FOOTING OF THE EXISTING BUILDING ONLY ONE 4-FOOT

SECTION SHALL BE UNDERPINNED AT ONE TIME. SEE FOUNDATION PLAN FOR

SEQUENCE AND LOCATION.

5. PORTLAND CEMENT ASTM C150 TYPE III, HIGH EARLY STRENGTH, IS REQUIRED FOR

THE UNDERPINNING CONCRETE.

6. 5.PLACE ONE-SIDED FORM TO EXTENT REQUIRED; HOWEVER, IF ADJACENT SIDES

OF THE UNDERPINNED SECTION IS UNSTABLE, THREE OR FOUR-SIDED FORMS

SHALL BE REQUIRED.

7. POUR CONCRETE IN UNDERPINNED SECTIONS TO WITHIN 3 INCHES OF BOTTOM OF

EXISTING WALL OR FOOTING.

8. AFTER SETTING A MINIMUM OF 24 HOURS, THE REMAINING 3 INCHES: PACK WITH A

DRY MIX (VERY LITTLE WATER OF NON-SHRINKING GROUT OR PART ONE SAND AND

PART ONE CEMENT. RAM MIXTURE THOROUGHLY TO FILL ALL VOIDS. STRIKE OFF

FLUSH WITH WALL OR FOOTING.

9. EACH UNDERPINNED SECTION SHALL BE DRY PACKED BEFORE THE NEXT SECTION

IS EXCAVATED.

10. A WAITING PERIOD OF 72 HOURS FOR CURING: ALLOW BETWEEN DRYPACKING AND

EXCAVATION OF ADJACENT SECTION.

11. CONTRACTOR: REPAIR ALL DAMAGE TO EXISTING BUILDINGS NECESSARY FOR OR

RESULTING FROM UNDERPINNING OPERATIONS.

TAG

PER

MFW**

THE WALL TAG ON THE FOUNDATION PLAN AND

THE ASSOCIATED SCHEDULE IDENTIFIES THE

CONSTRUCTION OF THE STRUCTURAL PORTION

OF THE FOUNDATION WALL ONLY. ADDITIONAL

WYTHES OF NON STRUCTURAL MASONRY MAY

EXTEND TO THE FOUNDATION - COORDINATE

WITH ARCHITECTURAL DRAWINGS

WF** THE WALL FOOTING TAG ON THE FOUNDATION

PLAN AND THE ASSOCIATED SCHEDULE IDENTIFIES

THE WALL FOOTING SIZE AND REINFORCING

REQUIREMENTS. THE WALL FOOTING SHALL BE

CENTERED BELOW THE 'TOTAL WALL WIDTH'

NON-STRUCTURAL

WALL WYTHES -

COORDINATE WITH

ARCH. DWGS

TAG AND SCHEDULE

FOOTING WIDTH PER

WIDTH

TOTAL WALL

CONCRETE WALL FOOTING

Floor Schedule - Foundation Plan

TYPE SLAB REINFORCING FINISH FLOOR

4" Concrete 66-W2.9xW2.9 WWF 583'-8 3/8"

5" Concrete #4 @ 12" O.C. 583'-8 3/8"

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

S tru ct _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

Fo un da tio n Pl an

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

S1.1

11.04.2026

BID

JA

C

K S

O N

T O

W N

S H

IP

M

U N

IC

IP

A L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

SCALE: 1/8" = 1'-0"

MAIN BUILDING FOUNDATION PLAN

SCALE: 1/2" = 1'-0"S1.1

2 Underpinning Sequence

SCALE: 3/4" = 1'-0"S1.1

4 Masonry Foundation Wall Key

SCALE: 3/4" = 1'-0"S1.1

3 Typical Underpinning Detail

BEFORE PROCEEDING WITH THE WORK.

T.F. ***.**'

T.P. ***.**'

Step Footing Marker

Top of Pier Marker

Top of Footing Marker

Pier Size Marker

Column Footing Size Marker

Foundation Wall Size Marker

P**

W**

Foundation Wall Footing Size Marker

F*.*

WF****

Foundation Symbol Legend

T.W. ***.**' Top of Wall Marker

Transition from Standard Footing to Trench Footing Marker

Rectangular Pier Size Marker RP**

Combined Column Footing Size Marker CF*.*

Retaining Wall Footing Marker RW-*

S1.2

W20

W

W20

W20

24" MAT FOUNDATION

- SEE SECTION & FLOOR SCHEDULE

FOR REINFORCEMENT INFORMATION

S1.4

6'-0"

6'-0"

6'-0"6'-0"

W12

W

W F

W

R W

-1

RW-1

MFW12

WF1230

T.F. 572.83'

T .F

.8

T.F. 570.83'

T.F. 568.83'

S3.1

S3.1

S1.5

S1.5

TYP. @ TRENCH

DRAINS

T .F

.8

T .F

.8

T .F

.8

T .F

.8

T.F. 572.83'

T.F. 574.83'

S1.5

RW-1

RW-1

R W

-1

W

W12

W12

W

W F

T.F. 5 72.83'

T.F. 574.36'

M F

W

W F

T.F. 574.83'

T.F. 576.83'

T.F. 578.83'

T.F. 576.83'

T.F. 574.83'

T.F. 572.83'

SLOPE SLAB 1/4"

PER 1'-0"

TOWARDS DRAINS

SLOPE SLAB 1/4"

PER 1'-0"

TOWARDS DRAINS

TYP. @ TRENCH

DRAINS

NOTES:

1. SEE CHART BELOW FOR FINISH FLOOR ELEVATION AND SLAB CONSTRUCTION

2. COORDINATE BRICK SHELF ELEVATIONS WITH FINISH GRADE

3. DENOTES SLEEVE LOCATIONS IN FOOTINGS/FOUNDATION WALLS

FOR UNDERGROUND PIPING - SEE TYPICAL PIPE SLEEVE THROUGH

FOUNDATION DETAIL

N

NOTES:

1. SEE CHART BELOW FOR FINISH FLOOR ELEVATION AND SLAB CONSTRUCTION

2. COORDINATE BRICK SHELF ELEVATIONS WITH FINISH GRADE

3. DENOTES SLEEVE LOCATIONS IN FOOTINGS/FOUNDATION WALLS

FOR UNDERGROUND PIPING - SEE TYPICAL PIPE SLEEVE THROUGH

FOUNDATION DETAIL

N

F.F. ELEV. 582'-0"

T.O.W. ELEV. 602'-0"

T.O.W. ELEV. 612'-0"

S2.8

WOOD FRAMED ROOF

TRUSS @ 24" O.C.

- ALIGN TRUSS w/ WALL

STUD

2x6 @ 24" O.C. SHEAR WALL w/ 7/16" PLYWOOD @

EXTERIOR FACE - TYP. (3) SIDES

- PROVIDE 6" PANEL & FIELD NAILING (8d

FASTENERS)

- PROVIDE (2) STUDS @ EACH END

- PROVIDE SIMPSON HD5B HOLDDOWN OR

EQUIVALENT AT EACH END OF ALL SHEAR WALLS.

- PROVIDE BLOCKING AT PANEL EDGES

- ALL STUDS & SHEATHING TO BE PRESSURE

TREATED.

(2) 2x6 TOP PLATE

- PRESSURE TREATED WOOD

20" CONC. WALL

- SEE CONCRETE FOUNDATION WALL

SCHEDULE FOR REINFORCEMENT

INFORMATION.

- F'c = 5000 PSI

#9 @ 6" O.C. BENT BARS

- TYP. @ W20 WALLS

CONC. SLAB w/ SIKA H1000

- SEE PLAN FOR SLAB DEPTH & REINF.

- ALL SALT SHED SLAB REINF. TO BE

EPOXY COATED.

APPLY SIKA H1000 TO ALL

INTERIOR WALL SURFACES

1/2" KW-EZ CRC w/ 6"

EMBEDMENT @ 48" O.C.

- GALVANIZED

S

P L

IC

E

24" MAT FOUNDATION

- SEE PLAN FOR EXTENTS

- SEE FLOOR SCHEDULE FOR

REINFORCEMENT INFORMATION

- F'c = 5000 PSI

6'-0" TYP.

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

S tru ct _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

Fo un da tio n Pl an

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

S1.2

11.04.2026

BID

JA

C

K S

O N

T O

W N

S H

IP

M

U N

IC

IP

A L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

SCALE: 1/8" = 1'-0"

SALT SHED FOUNDATION PLAN

SCALE: 1/8" = 1'-0"

STORAGE GARAGE FOUNDATION PLAN

Floor Schedule - Storage Foundation Plan

TYPE SLAB REINFORCING FINISH FLOOR

6" Concrete #5 @ 12" O.C. 581'-6"

8" Concrete #5 @ 12" O.C. 581'-6"

Floor Schedule - Salt Shed Foundation Plan TYPE SLAB REINFORCING FINISH FLOOR Comments

8" Concrete #5 @ 12" O.C. 582'-0" SALT SHED SLAB REINF.

TO BE EXPOXY COATED

24" Mat Foundation #8 @ 9" O.C., E.W. T/B 579'-0"

SCALE: 1/2" = 1'-0"S1.2

3 WALL SECTION tag rev date revision note

DESIGN LOADS:

DESIGN FLOOR LIVE LOADS

ROOF LIVE LOAD 20 PSF

ROOF 20 PSF

FLOOR 15 PSF

SEISMIC IMPORTANCE FACTOR (Ie) 1.00

ADDITIONAL NOTES:

a. THE CONTRACTOR IS CAUTIONED AS TO NOT STORE ANY

CONSTRUCTION MATERIALS OR UNDERTAKE ANY CONSTRUCTION

OPERATION WILL EXCEED THE DESIGN LIVE LOAD CAPACITIES NOTED.

b. THE STRUCTURE HAS BEEN DESIGNED FOR THE DEAD AND LIVE

LOADS INDICATED ABOVE, ANY INCREASE OF LOADS DUE TO CHANGE

IN USAGE OR CONSTRUCTION MATERIALS, ETC. SHALL HAVE THE

WRITTEN APPROVAL OF THE ENGINEER.

c. THE STABILITY OF THE STRUCTURE IS DEPENDENT UPON THE

DIAPHRAGM ACTION OF THE ROOFS. THE CONTRACTOR IS

COMPLETELY RESPONSIBLE FOR THE METHODS OF CONSTRUCTION

AND SHALL PROVIDE ALL GUYS, BRACING AND SHORING REQUIRED TO

ACCOMMODATE ALL INTERIM LOADING CONDITIONS THROUGHOUT

THE CONSTRUCTION PHASE.

d. WEIGHT OF EQUIPMENT SHOWN ON THE STRUCTURAL DRAWINGS

HAVE BEEN CONSIDERED IN THE DESIGN OF THE FRAMING. ANY

ADDITIONAL EQUIPMENT NOT SHOWN ON THE STRUCTURAL

DRAWINGS AND EXCEEDING 300 POUNDS SHALL BE BROUGHT TO THE

ATTENTION OF THE ENGINEER FOR APPROVAL PRIOR TO

INSTALLATION.

GOVERNING DESIGN CODE

2021 INTERNATIONAL BUILDING CODE

ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES

BUILDING RISK CATEGORY

DESIGN ROOF LIVE LOADS

DESIGN DEAD LOADS - NOT INCL. STRUCTURE SELF WEIGHT

SEISMIC DESIGN DATA

DESIGN WIND LOAD PARAMETERS

CORRIDORS (ABOVE 1ST FLOOR) 80 PSF

LOBBIES AND FIRST FLOOR CORRIDORS 100 PSF

OFFICE 50 PSF

PARTITIONS (APPLIED TO OCCUPANCIES LESS THAN 80 PSF) 15 PSF

MECHANICAL UNIT LOADS SEE MECH DWGS

STAIRS AND EXITS 100 PSF

HANDRAILS, GUARDS AND GRAB BARS PER 1607.8

GROUND SNOW LOAD (Pg) 30 PSF

DESIGN ROOF SNOW LOADS

FLAT ROOF SNOW LOAD (Pf) 21 PSF

SNOW EXPOSURE FACTOR (Ce) 1.0

SNOW LOAD IMPORTANCE FACTOR (Is) 1.00

THERMAL FACTOR (Ct) 1.0

SNOW DRIFT SEE DIAGRAM

II

MINIMUM UNIFORM DESIGN SNOW LOAD (NOT REDUCIBLE) 30 PSF

ULTIMATE DESIGN WIND SPEED (Vult) 115 MPH

ALLOWABLE STRESS DESIGN WIND SPEED (Vasd) 89 MPH

INTERNAL PRESSURE COEFFICIENT +/- 0.18

WIND EXPOSURE CATEGORY - PLAN WEST-EAST B

MAPPED SPECTRAL ACCELERATION (Ss)

MAPPED SPECTRAL ACCELERATION (S1)

SITE CLASS

DESIGN SPECTRAL RESPONSE COEFF. (Sds)

DESIGN SPECTRAL RESPONSE COEFF. (Sd1)

SEISMIC DESIGN CATEGORY

PLAN NORTH-SOUTH DIRECTION

SEISMIC FORCE RESISTING SYSTEM

DESIGN BASE SHEAR (V)

0.149

0.044

C

0.130

0.044

A

STEEL SYSTEMS NOT

SPECIFICALLY DESIGNED

FOR SEISMIC RESISTANCE

-- KIPS

ANALYSIS PROCEDURE EQUIV. LATERAL FORCE

RESPONSE MODIFICATION COEFF. (R) 3.0

SEISMIC RESPONSE COEFF. (Cs) --

PLAN WEST-EAST DIRECTION

SEISMIC FORCE RESISTING SYSTEM

DESIGN BASE SHEAR (V)

STEEL SYSTEMS NOT

SPECIFICALLY DESIGNED

FOR SEISMIC RESISTANCE

-- KIPS

RESPONSE MODIFICATION COEFF. (R) 3.0

SEISMIC RESPONSE COEFF. (Cs) --

WIND EXPOSURE CATEGORY - PLAN NORTH-SOUTH B

EQUIPMENT PLATFORM STORAGE 250 PSF

GARAGE STORAGE FUTURE SOLAR 10 PSF

GENERAL NOTES

1. THE CONTRACTOR IS ADVISED THAT ALL PLANS, DIMENSIONS, AND DETAILS DEPICT

FIELD CONDITION AS SHOWN. MINOR VARIATIONS ARE TO BE EXPECTED AND ANY

DEVIATIONS FROM THE CONTRACT DOCUMENTS SHALL BE APPROVED BY THE

ARCHITECT IN WRITING PRIOR TO PROCEEDING.

2. THE CONTRACTOR SHALL FIELD CHECK AND VERIFY ALL DIMENSIONS AND

ELEVATIONS OF EXISTING WORK PRIOR TO FABRICATION OF ANY NEW MATERIALS.

IF THE EXISTING FIELD CONDITIONS DO NOT PERMIT THE INSTALLATION OF THE

WORK IN ACCORDANCE WITH THE DETAILS SHOWN, THE CONTRACTOR SHALL

NOTIFY THE ENGINEER IMMEDIATELY AND PROVIDE A SKETCH OF THE CONDITION

WITH THEIR PROPOSED MODIFICATION OF THE DETAILS GIVEN ON THE CONTRACT

DOCUMENTS. DO NOT COMMENCE WORK UNTIL CONDITION IS RESOLVED AND

MODIFICATION IS APPROVED BY THE ENGINEER.

3. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE LOCATION OF

UTILITIES IN THE IMMEDIATE VICINITY OF CONSTRUCTION SO AS TO PREVENT

DAMAGE TO THEM. SHOULD DAMAGE TO SUCH UTILITIES OCCUR, THE CONTRACTOR

SHALL BE REQUIRED TO REPAIR SUCH DAMAGE AT THEIR OWN EXPENSE AND TO

THE SATISFACTION OF THE OWNER.

4. SHOP DRAWINGS FOR ALL STRUCTURAL ELEMENTS SHOWN ON THE CONTRACT

DOCUMENTS MUST BE SUBMITTED BY THE GENERAL CONTRACTOR AND REVIEWED

BY THE ENGINEER. IF THE CONTRACTOR OR OWNER FAILS TO OBTAIN ENGINEER'S

REVIEW OF THE SHOP DRAWINGS, THE ENGINEER WILL NOT BE RESPONSIBLE FOR

THE STRUCTURAL CERTIFICATION AND DESIGN OF THE PROJECT. SHOP DRAWINGS

ARE REVIEWED BY THE ENGINEER AS A CONVENIENCE TO THE GENERAL

CONTRACTOR AND ARE NOT A CONTRACT DOCUMENT.

5. LOADS GREATER THAN THE DESIGN LIVE LOADS SHALL NOT BE PLACED ON THE

STRUCTURE. A CONCRETE STRUCTURE MAY NOT SUPPORT IT'S DESIGN LIVE LOAD

FOR 28 DAYS. CONTRACTOR SHALL SUPPORT ADJACENT STRUCTURES, UTILITIES,

AND EXCAVATIONS AS REQUIRED. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS

FOR ALL TEMPORARY FORM WORK, SHEETING, SHORING AND UNDERPINNING

SEALED BY A PROFESSIONAL ENGINEER AS A PART OF THE CONTRACTOR'S WORK.

6. THE CONTRACTOR SHALL CONSULT THE ARCHITECTURAL, MECHANICAL, AND

ELECTRICAL DRAWINGS FOR THE QUANTITY, LOCATION, AND DIMENSION OF HOLES

THROUGH FLOOR AND ROOF: CHASES, INSERTS, OPENINGS, SLEEVES, WASHERS,

DRIPS, REVEALS, DEPRESSIONS AND OTHER PROJECT REQUIREMENTS. REFER TO

ARCHITECTURAL DRAWINGS FOR THE FOLLOWING INFORMATION:

a. LOCATION AND THICKNESS OF MASONRY PARTITIONS

b. FULL EXTENT OF MASONRY INFILL AREAS

c. LOCATION AND THICKNESS OF STUD PARTITIONS

d. LOCATION AND SIZE OF WINDOWS, DOORS AND WALL OPENINGS

e. STAIRS, FLOOR AND WALL FINISHES

f. DETAIL DIMENSIONS AND SECTION DETAILS AS REQUIRED

7. THIS STRUCTURE HAS BEEN DESIGNED TO BE SELF-SUPPORTING AND STABLE

AFTER THE CONSTRUCTION OF THE BUILDING IS TO BE COMPLETED. THE STABILITY

OF THE STRUCTURE PRIOR TO COMPLETION IS SOLELY THE RESPONSIBILITY OF

THE CONTRACTOR. THIS RESPONSIBILITY EXTENDS TO ALL RELATED ASPECTS OF

THE CONSTRUCTION ACTIVITY INCLUDING, BUT NOT LIMITED TO, ERECTION

METHODS, ERECTION SEQUENCE, TEMPORARY BRACING, FORMS, SHORING, USE OF

EQUIPMENT AND SIMILAR CONSTRUCTION PROCEDURES.

8. THE CONTRACTOR SHALL BE RESPONSIBLE TO DETERMINE ALLOWABLE

CONSTRUCTION LOADS AND TO PROVIDE DESIGN AND CONSTRUCTION OF

FALSEWORK, FORMWORK, STAGING, BRACING, SHEETING, SHORING, AND

UNDERPINNING AS NECESSARY TO PREVENT ANY LATERAL OR VERTICAL

MOVEMENTS TO, AND TO INSURE THE STRUCTURAL INTEGRITY OF EXISTING

BUILDINGS, STREETS, AND ANY EXISTING UTILITY LINES.

9. BRACING, SHEETING, SHORING, ETC., REQUIRED TO INSURE THE STRUCTURAL

INTEGRITY OF THE EXISTING BUILDINGS OR NEW CONSTRUCTION, SIDEWALKS,

UTILITIES ETC., SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER ENGAGED BY

THE CONTRACTOR. DETAILED SIGNED AND SEALED SHOP DRAWINGS SHALL BE

PREPARED INDICATING ALL WORK TO BE PERFORMED. SUBMIT THE SHOP

DRAWINGS IN ACCORDANCE WITH THE CONTRACT REQUIREMENTS.

SHOP DRAWINGS

1. DUPLICATION/PHOTOCOPYING OF THESE STRUCTURAL DRAWINGS SHALL NOT BE

PERMITTED FOR SHOP DRAWINGS. THIS INCLUDES PARTIAL AND/OR COMPLETE

DUPLICATION OF PLAN SHEETS AS BACKGROUNDS FOR SHOP DRAWINGS. ALL

SECTIONS INCLUDED IN THESE CONTRACT DRAWINGS MAY NOT BE

DUPLICATED/PHOTOCOPIED ON ANY SHOP DRAWINGS.

2. ORIGINAL SHOP DRAWINGS SHALL BE SUBMITTED FOR THE ARCHITECT/ENGINEER

REVIEW FOR THE FOLLOWING ITEMS AND AS PER THE SPECIFICATIONS:

a. CONCRETE AND MASONRY REINFORCING

b. SLAB ON GRADE CONTROL JOINT LAYOUT

c. CONCRETE MIX DESIGNS

• FOUNDATIONS

• RETAINING WALLS

• ELEVATED SLABS

• SLAB ON GRADE LISTING FIBER MESH REINFORCEMENT & DOSAGE RATE

d. MASONRY CERTIFICATIONS AND GROUT DESIGN

e. STEEL JOIST AND DECKING

f. STRUCTURAL STEEL

g. LIGHT GAGE METAL FRAMING

h. PRECAST CONCRETE

3. CONTRACTOR SHALL SUBMIT, FOR REVIEW, DRAWINGS AND CALCULATIONS FOR

ALL PERFORMANCE ASSEMBLIES IDENTIFIED IN THE GENERAL NOTES AND SPECIFIC

MATERIAL NOTES AS WELL AS LISTED BELOW: THE DESIGN OF THESE ASSEMBLIES

IS THE RESPONSIBILITY OF THE CONTRACTOR'S ENGINEER REGISTERED IN THE

PROJECT'S JURISDICTION. ALL SUBMITTALS SHALL BEAR THIS ENGINEER'S SEAL

AND SIGNATURE. REVIEW SHALL BE FOR GENERAL CONFORMANCE WITH THE

PROJECT REQUIREMENTS AS INDICATED ON THE DRAWINGS AND IN THE GENERAL

NOTES.

a. METAL STAIRS AND METAL RAILINGS: DESIGNS SHALL TAKE INTO ACCOUNT

ALL VERTICAL AND LATERAL LOADS REQUIRED BY APPLICABLE BUILDING

CODES. WHERE HEADERS OR OTHER TYPES OF STRUCTURAL MEMBERS

HAVE BEEN DESIGNATED BY THE STRUCTURAL ENGINEER OF RECORD TO

SUPPORT THE STAIRS, THE CONNECTIONS FROM THE STAIRS SHALL BE

DESIGNED SO THAT NO ECCENTRIC OR TORSIONAL FORCES ARE INDUCED

IN THESE STRUCTURAL MEMBERS. THE CONTRACTOR SHALL BE

RESPONSIBLE FOR FURNISHING AND INSTALLING HARDWARE AS REQUIRED

BY THE STAIR DESIGN.

CONTRACTOR SHALL VERIFY ALL CONDITIONS

AND DIMENSIONS FOR THE ENTIRE PROJECT

BEFORE PROCEEDING WITH THE WORK.

A.F.F. Above Finish Floor BCX Bottom Chord Extension B.O.F. Bottom of Footing B.S. Brick Shelf Elevation (plans) B.S. Both Sides (sections) CANT. Cantilever CJ Control Joints CL Center Line CMU Concrete Masonry Units CONT. Continuous DIA. Diameter DBA Deformed Bar Anchor E.E. Each End E.F. Each Face E.S. Each Side E.W. Each Way EXIST Existing F.F. Finish Floor F.S. Flat Strap GA Gage GALV Galvanized HORIZ Horizontal HSS Hollow Structural Section L Angle

ABBREVIATION LIST

LG Long LLH Long Leg Horizontal LLV Long Leg Vertical LSH Long Side Horizontal LSV Long Side Vertical N.T.S. Not To Scale o.c. On Center PL Plate REINF. Reinforcing REM. To Remain S.F. Step Footing STIFF PL Stiffener Plate T.B.R. To Be Removed T&B Top and Bottom T.F. Top of Footing T.O.S. Top of Steel T.O.W. Top of Wall T.P. Top of Pier TYP Typical U.N.O. Unless Noted Otherwise VERT. Vertical V.I.F. Verify In Field WWF Welded Wire Fabric XE Extended End - Type R

FOUNDATIONS AND BACKFILL

1. SOIL BEARING CAPACITY OF 3,000 PSF WAS UTILIZED IN THE DESIGN OF THE

FOUNDATION SYSTEM.

2. SLAB ON GRADE DESIGN BASED ON MODULUS OF SUBGRADE REACTION OF 125 PCI.

3. PLACE EXTERIOR FOOTINGS AND FROST WALLS EXPOSED TO WEATHER AT LEAST

36" BELOW THE ADJACENT OUTSIDE FINISHED GRADE TO PROTECT FROM FROST

DAMAGE.

4. THE OWNER SHALL ENGAGE THE SERVICES OF A REGISTERED PROFESSIONAL

GEOTECHNICAL ENGINEER TO MONITOR AND INSPECT ALL EARTH WORK AND TO

PERFORM THE SPECIAL INSPECTIONS REQUIRED BY THE SCHEDULE OF SPECIAL

INSPECTIONS. THE GEOTECHNICAL ENGINEER SHALL SUPERVISE THE PLACING OF

THE COMPACTED FILL AND ALL THE MATERIALS AND EQUIPMENT USED FOR THIS

PURPOSE. THE GEOTECHNICAL ENGINEER SHALL CERTIFY, BY SEAL AND

SIGNATURE, THAT THE EARTH-WORK IS IN ACCORDANCE WITH THE GEOTECHNICAL

REPORT, PLANS AND SPECIFICATIONS.

5. THE SUB-FLOOR MATERIALS SHALL CONSIST OF AT LEAST FOUR TO SIX INCHES OF

GRAVEL OR CRUSHED STONE. THE SUB-FLOOR MATERIALS SHALL BE COMPACTED

BY AT LEAST FOUR COVERAGES OF A HEAVY-DUTY VIBRATORY ROLLER OR UNTIL

NO FURTHER COMPACTION IS OBSERVED. SEE THE DRAWINGS AND

SPECIFICATIONS FOR THE VAPOR BARRIER SIZE, TYPE AND LOCATION.

6. PRIOR TO CONCRETE PLACEMENT THE FOUNDATION BOTTOM SHALL BE

COMPACTED USING A WALK BEHIND VIBRATORY ROLLER OR GAS-POWERED

TAMPER.

7. IF SOIL OF THE BEARING CAPACITY NOTED ABOVE IS NOT ENCOUNTERED AT THE

ELEVATIONS SHOWN ON PLAN, UNSUITABLE SOILS SHALL BE REMOVED AND

REPLACED WITH STRUCTURAL FILL IN ACCORDANCE WITH THE GEOTECHNICAL

ENGINEER'S DIRECTION.

8. IF BEDROCK IS ENCOUNTERED AT OR ABOVE FOUNDATION SUBGRADE ELEVATION,

THE BEDROCK SURFACE SHALL BE OVER EXCAVATED A MINIMUM OF SIX INCHES

AND BACKFILLED WITH CRUSHED STONE TO THE SUBGRADE ELEVATION.

9. THE GEOTECHNICAL ENGINEER SHALL APPROVE SAMPLES OF ALL CONTRACTOR

PROPOSED COMPACTED FILL MATERIAL. IMPORTED STRUCTURAL FILL SHALL BE

FREE OF ORGANIC MATTER, ASH, CINDERS AND DEMOLITION DEBRIS.

10. CONTROL OF MOISTURE FOR PLACING FILL WILL BE BASED ON THE RESULTS OF

ASTM D-1557 MODIFIED PROCTOR TESTS.

11. ALL COMPACTED FILL SHALL HAVE A DENSITY OF AT LEAST 98% OF MAXIMUM DRY

DENSITY AS DETERMINED BY THE ASTM D-1557 MODIFIED PROCTOR TEST. PLACING

OF FILL WITH MOISTURE CONTENT OUTSIDE THE LIMITS FOR PROPER COMPACTION

SHALL NOT BE PERMITTED.

12. THE EXISTING SUBGRADE IN ALL FILL AND CUT AREAS SHALL BE COMPACTED TO A

FIRM, STABLE CONDITION AS DETERMINED BY THE GEOTECHNICAL ENGINEER,

PRIOR TO PLACEMENT OF FILLS AND EXCAVATION FOR FOOTINGS.

13. FILL MATERIAL SHALL BE PLACED IN LOOSE LIFTS NOT EXCEEDING 8" IN THICKNESS

AND SHALL BE MIXED, SPREAD, AND PLACED IN SUCH A WAY AS TO PRODUCE A

UNIFORM THICKNESS OF MATERIAL AFTER PLACING.

14. EACH LAYER OF FILL MATERIAL SHALL BE COMPACTED ON ALL PORTIONS OF THE

SURFACE OF EACH LIFT OF FILL BY RUBBER TIRE ROLLERS, SHEEP'S FOOT

ROLLERS, VIBRATORY ROLLERS, ETC. AS NECESSARY TO ATTAIN THE MAXIMUM DRY

DENSITY NOTED ABOVE AND AS APPROVED BY THE GEOTECHNICAL ENGINEER.

15. WHENEVER IN PLACE DENSITIES ARE FOUND TO BE BELOW LIMITS ACCEPTABLE TO

THE GEOTECHNICAL ENGINEER, ADDITIONAL ROLLING TO PRODUCE THE SPECIFIED

DENSITIES SHALL BE REQUIRED.

16. PLACING OF FILL WHEN FREE WATER IS STANDING ON THE EXISTING SURFACE

SHALL NOT BE PERMITTED.

17. PLACING OF FILL IN A FROZEN CONDITION OR ON TOP OF FROZEN MATERIAL SHALL

NOT BE PERMITTED.

18. SUBGRADE SUITABILITY SHALL BE VERIFIED BY GEOTECHNICAL ENGINEER WITHIN

24 HOURS PRIOR TO PLACING CONCRETE FOUNDATIONS AND CONCRETE SLABS ON

GRADE TO CONFIRM THAT NO DETERIORATION HAS OCCURRED SUBSEQUENT TO

TESTING PERFORMED AT TIME OF FILL PLACEMENT. UNSUITABLE CONDITIONS

SHALL BE CORRECTED PER GEOTECHNICAL ENGINEER'S RECOMMENDATION.

19. EXCAVATIONS SHOULD BE BACKFILLED OR HAVE CONCRETE PLACED AS SOON AS

POSSIBLE DURING CONSTRUCTION TO MINIMIZE ADVERSE AFFECTS TO SUBGRADE

CONDITIONS. GRADING DEPRESSIONS SHOULD BE AVOIDED.

20. WATER SHALL BE PREVENTED FROM ENTERING OPEN EXCAVATIONS. ANY

ACCUMULATED WATER SHALL BE REMOVED AS SOON AS POSSIBLE. IT IS

RECOMMENDED THAT CONCRETE BE PLACED THE SAME DAY THE EXCAVATION IS

MADE.

21. THE CONTRACTOR SHALL PROVIDE FOR DEWATERING AS REQUIRED DURING

EXCAVATION AND CONSTRUCTION.

CONCRETE

1. ALL WORK SHALL CONFORM TO THE "SPECIFICATIONS FOR STRUCTURAL

CONCRETE" (AMERICAN CONCRETE INSTITUTE, ACI 301) AND THE "BUILDING CODE

REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318), LATEST EDITIONS, UNLESS

NOTED OTHERWISE IN THE DRAWINGS OR PROJECT SPECIFICATIONS.

2. CONSTRUCTION TOLERANCES SHALL CONFORM TO THE "SPECIFICATION FOR

TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS" (ACI 117), LATEST

EDITION.

3. SHOP DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH THE "GUIDE TO

PRESENTING REINFORCING STEEL DESIGN DETAILS" (ACI 315) AND THE "ACI

DETAILING MANUAL" (SP-066), LATEST EDITIONS.

4. CONCRETE MATERIALS SHALL BE PROVIDED IN ACCORDANCE WITH THE

FOLLOWING SPECIFICATIONS:

• PORTLAND CEMENT ASTM C150

• HYDRAULIC CEMENT ASTM C1157

• FLY ASH AND NATURAL POZZOLAN ASTM C618

• SLAG CEMENT ASTM C989

• SILICA FUME ASTM C1240

• NORMAL WEIGHT AGGREGATE ASTM C33

• LIGHTWEIGHT AGGREGATE ASTM C330

• MIXING WATER ASTM C1602

• ADMIXTURES

• WATER REDUCTION AND SETTING TIME MODIFICATION ASTM C494

• PRODUCING FLOWING CONCRETE ASTM C107

• AIR ENTRAINMENT ASTM C260

• INHIBITING CHLORIDE-INDUCED CORROSION ASTM C1582

5. REINFORCING MATERIALS:

• REINFORCING BARS PLAIN-STEEL ASTM A615, GRADE 60, DEFORMED

• REINFORCING BARS LOW-ALLOY-STEEL ASTM A706, DEFORMED

(WELDABLE)

• REINFORCING BARS EPOXY-COATED ASTM A775

• WELDED WIRE FABRIC ASTM A1064

• EPOXY-COATED WELDED WIRE FABRIC ASTM A884, CLASS A COATING

6. REINFORCING SHALL COMPLY WITH ACI FOR FABRICATING, PLACING, AND

SUPPORTING REINFORCEMENT, AND THE FOLLOWING:

• BAR SPLICE LOCATIONS SHALL CONFORM TO ACI 318

• HORIZONTAL REINFORCING BARS IN WALLS AND FOOTINGS SHALL BE

CONTINUOUS AROUND CORNERS.

• UNLESS DETAILED CALCULATIONS ARE PROVIDED, REINFORCING BARS

DEVELOPMENT LENGTHS, EMBEDMENT DEPTHS AND LAP SPLICE DISTANCES

FOR f'c = 4000psi, NORMAL-WEIGHT CONCRETE, SHALL BE PER BELOW

7. EMBEDDED AND MISCELLANEOUS STEEL SHALL COMPLY WITH ASTM A36.

8. CONTINUOUS WALL OR FOOTING PLACEMENT SHALL NOT EXCEED 60 FEET

BETWEEN CONSTRUCTION JOINTS.

9. ALL EXPOSED CONCRETE CORNERS SHALL BE CHAMFERED 3/4" AT 45 DEGREES

UNLESS NOTED OTHERWISE.

10. SHALLOW INTERIOR FOUNDATIONS AND SLABS ON GRADE ARE NOT DESIGNED FOR

OR INTENDED TO BE EXPOSED TO FREEZE/THAW CYCLING OR RESIST FROST

HEAVE FORCES. GENERAL CONTRACTOR TO COORDINATE CONSTRUCTION AND

PROVIDE INTERIOR FOOTINGS BELOW FROST PENETRATION AS REQUIRED FOR

WINTER CONSTRUCTION.

11. PROVIDE CONSTRUCTION / CONTROL JOINT INSTALLATION PLAN AND PLACEMENT

SEQUENCE PLAN SUBMITTALS FOR REVIEW OF STRUCTURAL ENGINEER OF

RECORD PRIOR TO PLACING CONCRETE.

12. PROVIDE WALL AND SLAB THRU-SLEEVE PLAN SUBMITTALS FOR REVIEW OF

STRUCTURAL ENGINEER OF RECORD PRIOR TO PLACING CONCRETE.

13. CORE-DRILLING CONCRETE WALLS, SLABS, BEAMS OR COLUMNS WITHOUT

REINFORCING LOCATION SCANS AND PRIOR APPROVAL OF STRUCTURAL ENGINEER

OF RECORD SHALL NOT BE PERMITTED.

14. CONDUITS AND PIPES SHALL NOT BE EMBEDDED IN ELEVATED CONCRETE SLABS

SUPPORTED BY METAL DECK OR CONCRETE SLABS ON GRADE.

15. FIBER REINFORCED CONCRETE SHALL COMPLY WITH "GUIDE TO DESIGN WITH

FIBER-REINFORCED CONCRETE" (ACI 544.4), LATEST EDITION. DESIGN

CALCULATIONS SHALL BE SUBMITTED AS PER THE SHOP DRAWING NOTES AND

SPECIFICATIONS.

16. NON-SHRINK GROUT SHALL CONFORM TO ASTM C1107 AND ACHIEVE A MINIMUM 28

DAY COMPRESSIVE STRENGTH OF 8,000 psi.

17. STRUCTURAL ADHESIVES SHALL ONLY BE USED WITH PRIOR PERMISSION OF THE

STRUCTURAL ENGINEER OF RECORD OR AS SHOWN ON CONSTRUCTION

DOCUMENTS. THE BASIS OF DESIGN FOR ADHESIVES IS HY-200 BY "HILTI" OR SET BY

"SIMPSON" - THE USE OF ANY OTHER STRUCTURAL ADHESIVES SHALL BE SUBJECT

TO REVIEW BY THE EOR PRIOR TO INSTALLATION.

18. MINIMUM WIRE WELDED FABRIC REQUIREMENTS FOR SLABS:

• 3-1/2" FLOOR SLAB ON METAL DECK 66-W2.9xW2.9

• 5" FLOOR SLAB ON METAL DECK 66-W2.9xW2.9

• 4" FLOOR SLAB ON GRADE 66-W2.9xW2.9

• 5" FLOOR SLAB ON GRADE 44-W4.0xW4.0

19. COLD-WEATHER CONCRETE PLACEMENT SHALL COMPLY WITH THE PROVISIONS OF

ACI 306R. THE USE OF CALCIUM CHLORIDE, SALT, AND OTHER MATERIALS

CONTAINING ANTI- FREEZE AGENTS OR CHEMICAL ACCELERATORS SHALL NOT

BE PERMITTED UNLESS ACCEPTED IN THE MIX DESIGN.

20. HOT-WEATHER CONCRETE PLACEMENT SHALL COMPLY WITH THE PROVISIONS OF

ACI 305.

21. MINIMUM CONCRETE CLEAR COVER SHALL BE PROVIDED FOR REINFORCEMENT

PER ACI AND THE FOLLOWING:

• CONCRETE CAST AGAINST EARTH & PERMANENTLY 3"

EXPOSED

• CONCRETE EXPOSED TO EARTH OR WEATHER

#6 & LARGER 2"

#5 & SMALLER 1-1/2"

• CONCRETE NOT EXPOSED TO WEATHER OR GROUND

SLABS, WALLS, AND JOINTS 3/4"

BEAMS AND COLUMNS 1-1/2"

BAR LOCATION

VERT. & HORIZ. WALL BARS

FOOTING TOP BARS

FOOTING BOTTOM BARS

BAR SIZE

#3 ld ls ldh

20" 25" 8"

15" 19" 8"

#4 ld ls ldh

25" 33" 10"

19" 25" 10"

#5 ld ls ldh

32" 41" 12"

24" 31" 12"

REBAR LAP SPLICE LENGTHS

20" 25" 8" 25" 33" 10" 32" 41" 12"

VERT. & HORIZ. WALL BARS

FOOTING TOP BARS

FOOTING BOTTOM BARS

#6 ld ls ldh

38" 50" 15"

29" 38" 15"

#7 ld ls ldh

55" 71" 17"

42" 54" 17"

#8 ld ls ldh

62" 81" 19"

47" 62" 19"

38" 50" 15" 55" 71" 17" 62" 81" 19"

NOTE:

• VALUES ABOVE ARE FOR NORMAL WEIGHT CONCRETE ONLY.

• ld = MINIMUM TENSION DEVELOPMENT LENGTH

• ldh = MINIMUM 90 DEGREE HOOKED BAR DEVELOPMENT LENGTH

• ls = MINIMUM LENGTH OF LAP SPLICES IN TENSION

BAR SIZE

CONCRETE MIX DESIGN CRITERIA

FOOTINGS AND

FOUNDATION WALLS

INTERIOR SLABS ON

GRADE

EXPOSURE

CLASS

F1,S0,W0,C1

MAX. w/c

RATIO

0.55

MIN. f'c

3,500

AIR

CONTENT

5%

CEMENT

TYPE

I or II

INTERIOR ELEVATED

SLABS

EXTERIOR SLABS

F0,S0,W0,C1 0.50 4,000 N/A I or II

F0,S0,W0,C1 0.50 4,000 N/A I or II

F3,S0,W0,C2 0.40 5,000 6% I or II

SALT SHED RETAINING

WALL AND FOOTINGS F3,S2,W1,C2 0.50 5,000 5% I or II

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

S tru ct _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

Fo un da tio n N ot es

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

S1.3

11.04.2026

BID

JA

C

K S

O N

T O

W N

S H

IP

M

U N

IC

IP

A L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

BENT

BARS (B)

CONT.

BARS

D E

P T

H

WIDTHNOTES:

1. CONTINUOUS BARS SHALL HAVE 3" MINIMUM COVER

ON ALL SIDES.

2. BENT BARS SHALL BE PER THE FOUNDATION WALL

SCHEDULE.

BENT

BARS (B)

NOTES:

1. GROUT ALL CORES SOLID BELOW GRADE w/ 3,000 psi CONCRETE GROUT.

2. REINFORCING SHALL BE CENTERED IN WALL U.N.O.

3. PROVIDE HORIZONTAL JOINT REINFORCING PER SPECIFICATIONS -

SPACING NOT TO EXCEED 16" o.c.

4. WALLS WITH MULTIPLE WYTHES SHALL HAVE (1) LAYER OF REINFORCING

PER WYTHE

VERT.

BARS (V)

2'-0" MIN.

SPLICE

WIDTH

JOINT

REINF.

NOTES

1. BOTTOM OF NEW FOOTING TO MATCH BOTTOM OF EXISTING.

2. ADJUST OVERALL FOOTING THICKNESS AND WIDTH AS REQUIRED

TO MEET MINIMUM DIMENSIONS SHOWN.

3. BENT BAR SIZE AND SPACING SHALL MATCH NEW WALL VERTICAL

REINFORCING.

D

WIDTH

M

IN

D - EPOXY INTO

EXISTING FOOTING 8"

B

T

EXISTING WALL

AND FOOTING

NEW FOUNDATION

WALL - SEE PLAN FOR

FOR FOUNDATION

WALL SIZE AND

REINFORCEMENT

D E

P T

H

NOTES:

1. ALL REINFORCING SHALL HAVE 3" MINIMUM COVER

ON ALL SIDES.

2. SEE FOUNDATION PLAN AND FOUNDATION WALL

SCHEDULE FOR WALL THICKNESS, REINFORCING

AND BENT BAR (B) SIZE AND SPACING U.N.O.

HFT

BFT

T

B

S P

L

IC

E

HEEL

SEE PLAN

WALL TOE

CONT. HORIZ

TRUSS TYPE JOINT

REINF - 9 GA GALV

METAL @ 16" o.c.

#5 @ 48" o.c. - GROUT

CORES SOLID AT

REINF. w/ 3000 psi

CONC GROUT

(2) #5

CONT

#5 BENT BARS

@ 48" o.c.

CMU WALL

NOTE:

• CONDUIT NOT PERMITTED TO PENETRATE THRU THICKENED SLAB.

STEP CONDUIT BELOW THICKENED SLAB AS REQUIRED.

S E

E P

L A

N

3t

WRAP MESH

AROUND #4

NOSING BAR

#4 BENT BARS @

16" o.c. AROUND #4

NOSING BAR

SEE FOUNDATION

PLAN FOR FOOTING

SIZE AND

REINFORCING

(2) #5

SEE PLAN

FOR WALL

SIZE AND

REINF.

(M

IN

8"

SEE PLAN FOR LIMITS

DOOR LOC.

COORD w/

(2) #5

WRAP MESH

AROUND #4

NOSING BAR

EXTERIOR GRADE

COORDINATE w/ SITE

DRAWINGS

(M

IN

8"

1'-0"

#5 BENT

BARS @

16" o.c.

(2) #5 CONT.

(M

IN

(M

IN

(TYP)

8"

EQUIPTMENT SUPPLIER

COORDINATE WITH

#5 BARS @

12" o.c. (E.W.)

COMPACTED

STONE BASE

FROST WALL

EACH SIDE

NOTES:

1. COORDINATE EQUIPMENT PAD SIZE AND

LOCATION WITH M.E.P.CONTRACTORS.

2. PAD SHALL EXTEND 6" MINIMUM BEYOND

UNIT IN ALL DIRECTIONS

(MIN)

1'-0"

CONT. HORIZ TRUSS TYPE

JOINT REINF - 9 GA GALV

METAL @ 16" o.c. VERT.

#5 @ 48" o.c. - GROUT

CORES SOLID @ REINF.

w/ 3000 psi CONC GROUT

BENT BARS -

GROUT CORES

SOLID @ REINF

8" CMU WALL

OR WIDER

P L A

N

S E

E

P L A

N

S E

E

PLAN

SEE

1/2" DIA. x 18" LONG

SMOOTH DOWELS @

24" o.c. - EPOXY INTO

EXISTING SLAB AND

GREASE END INTO NEW

CONCRETE

SAWCUT EXISTING SLAB -

PROVIDE BONDING AGENT

(SIKADUR 32 HI-MOD OR

APPROVED EQUAL) TO BOND

OLD CONCRETE TO NEW

NOTE: DOWELS ARE NOT REQUIRED IF BOTH SLABS

BEAR 4" MIN ON A FOUNDATION WALL OR

FOOTING

NEW CONCRETE SLAB

SLAB

EXIST CONCRETE

9"

BENT

BARS (B)

NOTES:

1. ALL REINFORCING BARS SHALL HAVE 2" MINIMUM COVER ON ALL SIDES. 8" WALLS

SHALL HAVE ONLY ONE LAYER OF REINFORCING CENTERED IN THE WALL

2. BENT BARS SHALL BE THE SAME SIZE AND SPACING AS FOUNDATION WALL

VERTICAL REINFORCING, U.N.O.

3. FOR WALL WITH SHELF - 'Z' BARS SIZE AND SPACING SHALL MATCH (V) BARS.

4. FOR WALLS BACKING VENEER INSTALL DOVETAIL SLOTS @ 24" o.c. HORIZONTALLY

AND METAL TIES @ 16" o.c. VERTICALLY

5. COORDINATE SHELF LOCATIONS AND ELEVATIONS WITH ARCHITECTURAL

DRAWINGS

VERT.

BARS (V)

HORIZ.

BARS (H)

WIDTH DOWELS @ MASONRY

WALLS - SIZE AND

SPACING TO MATCH

MASONRY WALL VERTICAL

REINFORCING

'Z' BARS

VERT.

BARS (V)

HORIZ.

BARS (H)

WALL AT SHELF

'X' 'Y'

W10-6

'X' - WIDTH OF CONC. STEM

'Y' - WIDTH OF CONC. BRICK SHELF

NOTES:

1. ALL TIE SIZES TO BE (3) - #3 BARS AT 1 1/2" o.c. (T&B) REMAINDER @ 12" o.c.

2. SEE FOUNDATION PLAN FOR PIER SIZES

4 BARS

SINGLE TIE

8 BARS

2 TIES PER SET

SCALE: 3/4" = 1'-0"S1.4

Typical Thickened Slab Detail At Masonry Walls

SCALE: 3/4" = 1'-0"S1.4

Wall Footing Schedule with Masonry Foundation Walls

SCALE: 3/4" = 1'-0"S1.4

2 Masonry Foundation Wall Schedule

Schedule - Wall Footing

MARK DEPTH WIDTH REINFORCING

WF1224 1'-0" 2'-0" (3) #5 CONT.

WF1230 1'-0" 2'-6" (3) #5 CONT.

WF1436 1'-2" 3'-0" (4) #5 CONT.

SCALE: 3/4" = 1'-0"S1.4

Wall Footing Adjacent To Existing Schedule

Schedule - Wall Footing at Existing

MARK WIDTH REINFORCING

EWF24 24" T - (4) #5; B - (3) #5; D - #5 @ 32" o.c.

Schedule - Masonry Foundation Wall

MARK WIDTH REINFORCING

MFW8 8" #5 @ 48" o.c. (V) - #5 @ 24" o.c. (B)

MFW8-8 16" #5 @ 48" o.c. (V) - #5 @ 24" o.c. (B)

MFW12 12" #5 @ 48" o.c. (V) - #5 @ 24" o.c. (B)

SCALE: 3/4" = 1'-0"S1.4

9 Typical Exterior Wall At Door Detail

SCALE: 3/4" = 1'-0"S1.4

10 Typical Frost Wall

SCALE: 3/4" = 1'-0"S1.4

11 Typical Exterior Equipment Pad

SCALE: 3/4" = 1'-0"S1.4

7 Typical Interior Wall Footing

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

S tru ct _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

Fo un da tio n Sc he du le a nd D et ai ls

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

S1.4

11.04.2026

BID

JA

C

K S

O N

T O

W N

S H

IP

M

U N

IC

IP

A L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

SCALE: 3/4" = 1'-0"S1.4

12 Typical New to Existing Slab

SCALE: 3/4" = 1'-0"S1.4

6 Retaining Wall Footing Schedule

Schedule - Retaining Wall Footing

MARK HEEL TOE DEPTH REINFORCING

RW-1 4'-6" 3'-6" 1'-8" T - #8 @ 12" o.c.; HFT - (9) #6 CONT.; BFT - (4) #6 CONT.; SPLICE 4'-0"

SCALE: 3/4" = 1'-0"S1.4

3 Concrete Foundation Wall Schedule

Schedule - Concrete Foundation Wall

MARK WIDTH REINFORCING

W12 12" #7 @ 12" o.c. (V) #5 @ 12" o.c. (H)

W20 20" #8 @ 12" o.c. (V) #6 @ 12" o.c. (H) tag rev date revision note

SCALE: 3/4" = 1'-0"S1.4

5 Sonotube Footing Schedule

Schedule - Sonotube Footings

MARK DIAMETER

VERTICAL

BARS TIES

ST-1 24" (8) #8 (2) #3 @ 12" o.c.

SAME SIZE

AND QUANTITY

DIA

36 BAR

2d (MIN) d

3" 3"

(2) - #4 x 3'-0" BARS @ MID

DEPTH OF SLAB @ EACH WALL

JAMB

CONCRETE OR

MASONRY WALL

NOTES

1. BENT BAR SPACING TO BE 2x VERTICAL BAR SPACING - NOT TO EXCEED 32" o.c.

2. CONT. PL. WIDTH TO BE 'S' MINUS 1".

3. HEADED STUDS ON CONT. PL. TO BE 1/2" DIA. x 4" LONG @ 48" o.c.

4. HEADED STUDS TO BE LOCATED INSIDE HORIZONTAL BARS

VERTICAL

BARS

CONCRETE

WALL

BENT

BARS

CONCRETE

SLAB ON

GRADE

CONCRETE

WALL (SEE

PLAN)

COATED #6

DOWELS - 24"

LG @ 24" o.c.

PREMOLDED

EXPANSION JOINT

MATERIAL

3/4" CHAMFER

EACH SIDE OF

JOINT

CONCRETE WALL

EXPANSION JOINT

CONCRETE

WALL (SEE

PLAN)

3/4" CHAMFER EACH

SIDE OF WALL AT

CONTROL JOINT

CONCRETE WALL

CONTROL JOINT

CONCRETE WALL

CONSTRUCTION

JOINT

CONCRETE

WALL (SEE

PLAN)

1 1/2" x 5 1/5" SHEAR KEY w/

WATERSTOP

PLAN

SEE

REINFORCED CONCRETE NOTES

SPLICE LENGTH PER

NEW FDN.

WALL - SEE

SECTIONS

CONT. WALL

FTG. REINF.

EPOXY GROUT

DOWELS INTO

EXISTING FOOTING -

SIZE & QUANTITY TO

MATCH CONT. WALL

REINF.

EXISTING

WALL AND

FOOTING

8"

MATCH BOTTOM OF NEW

FOOTING w/ BOTTOM OF

EXIST FOOTING

PIPE

6" 6"

SLEEVE

TOP OF

FOOTING

NOTE:

• IF DIMENSION TO PIPE SLEEVE IS LESS THAN

THE FOOTING DEPTH, LOWER FOOTING TO

PERMIT PIPE TO PASS THRU WALL ABOVE

FOOTING. REFER TO CONDITION #3 &

FOOTING STEP DOWN DETAILS.

S E

E N

O T

E

T O

P O

F

IP

E S

L E

E V

E

UNDERGROUND

PIPE

NOTE:

• WHERE TOP OF PIPE / CONDUIT IS BELOW

BOTTOM OF FOOTING BY AT LEAST FOOTING

WIDTH OR 4'-0" WHICHEVER IS GREATER,

PIPE MAY BE RUN UNDER FOOTING WITHOUT

A SLEEVE OR CONCRETE ENCASEMENT .

BOTTOM OF

FOOTING

S E

E N

O T

E

REINFORCED

CONCRETE

FOOTING

PIPE

(SEE MEP

DWGS.)

PIPE SLEEVE

GROUT

M

IN

NOTE:

• STEP FOOTING DOWN AS REQUIRED IN

ACCORDANCE WITH TYPICAL WALL

FOOTING STEP DETAIL.

D E

P T

H

F T

G

2'-8" MIN.

TOOL OR SAW CUT - 1/4

DEPTH (SAW WITHIN 24 HRS.

OF PLACING CONCRETE)

NOTE: CONTRACTORS OPTION

FOR TYPE OF JOINT

PREMOLDED

KEYED JOINT

STOP REINFORCING 6"

FROM JOINT

SAWED CONTROL JOINT

CONSTRUCTION JOINT

T /3

T

T /3

T

1'-6" 1'-6"

SEE ARCH. DRAWINGS

WALL OPENING

CONSTRUCTION

JOINT

CONCRETE OR

MASONRY WALL

(1) - #4 x 3'-0" LG.

BAR AT MID

DEPTH OF SLAB

@ EA WALL JAMB

3"

MID DEPTH OF SLAB

BENT BARS 3"

CONTROL OR

CONSTRUCTION JOINTS

CONCRETE OR

MASONRY WALL

MIN

44db

0" TYP

CORNER BARS

SAME SIZE AND

SPACING AS HORIZ.

WALL REINF.

HORIZONTAL AND

VERTICAL WALL

REINFORCEMENT

(PER DESIGN)

HORIZONTAL AND

VERTICAL WALL

REINFORCEMENT

(PER DESIGN)

BENT BARS SAME

SIZE AND SPACING AS

HORIZONTAL WALL

REINFORCEMENT

HORIZONTAL AND

VERTICAL WALL

REINFORCEMENT

(PER DESIGN)

DEVELOPEMENT LENGTH

D E

V E

L O

P E

M E

N T

L E

N G

T H

(2) #5 - 5'-0" LG

- 2'-6" LEG -

TYP.

BOND BEAM

REINFORCING

(2) #5

2'-0" MIN. BAR

SPLICE

FILL PIPE WITH CONCRETE AND

SMOOTH MOUND AT TOP OF PIPE

8" DIA. SCH.

40 STAINLESS

STEEL PIPE

BOLLARD

SEALANT

CONCRETE

ENCASEMENT

FINISH GRADE

TYP.

6"

M

IN

T Y

P

#3 @ 12" o.c. E.W.

1/4" CONT. BENT

PL. w/ 1/2" DIA.

SHEAR STUDS

@ 12" o.c.

WATERSTOP

1" STEEL GRATING

INSTALLED FLUSH

w/ SLAB

2" MIN.

6" 1'-0" 6"

2'-0"

1 1/2"x 1 1/2"x 3/16' ANGLE w/ HEADED STUDS @ 24" o.c

(GALV.)

/4

METAL OVERHEAD

DOOR

CHANNEL

BEYOND

CONCRETE SLAB ON

GRADE

SEE PLAN FOR

FOUNDATION

WALL SIZE AND

REINFORCING

#5 BENT BARS @

16" o.c AROUND #5

NOSING BAR

SCALE: 3/4" = 1'-0"S1.5

1 Typical Step Footing Detail

SCALE: 3/4" = 1'-0"S1.5

12 Typical Pipe at Wall Footing Details

SCALE: 3/4" = 1'-0"S1.5

8 Typical Crack Control Joints

SCALE: 3/4" = 1'-0"S1.5

Typical Slab on Grade Construction at Openings Construction at Building Entrance

SCALE: 3/4" = 1'-0"S1.5

Typical Slab on Grade Reinforcement at Wall Corners Reinforcement at Wall Corners

SCALE: 3/4" = 1'-0"S1.5

9 Typical Slab to Wall Connections

SCALE: 3/4" = 1'-0"S1.5

10 Typical Concrete Wall Joints

SCALE: 3/4" = 1'-0"S1.5

3 Typical Reinforcing Around Corner

SCALE: 3/4" = 1'-0"S1.5

Typical Concrete Wall Intersection Reinforcing

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

S tru ct _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

Fo un da tio n De ta ils

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

S1.5

11.04.2026

BID

JA

C

K S

O N

T O

W N

S H

IP

M

U N

IC

IP

A L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

SCALE: 3/4" = 1'-0"S1.5

5 Typical Bond Beam Detail At Corner

SCALE: 3/4" = 1'-0"S1.5

Typical Detail Of New Footing Adjacent To Existing

SCALE: 3/4" = 1'-0"S1.5

11 Typical Pipe Bollard Detail

SCALE: 3/4" = 1'-0"S1.5

13 Typical Foundation Drain Detail tag rev date revision note

SCALE: 3/4" = 1'-0"S1.5

14 Typical Depressed Slab Detail

BEFORE PROCEEDING WITH THE WORK.

Denotes Beam to Column Moment Connection to be Designed by Fabricator for Forces Indicated

Steel Symbol Legend

Denotes Beam to Column Cantilever Moment Connection to be Designed by Fabricator for Forces Indicated

Denotes Beam to Beam Moment Connection to be Designed by Fabricator for Forces Indicated

Denotes Beam Cantilever - Beam to Extend over top of Column

Denotes Continuous Beam

Denotes Beam to Column/Beam Slip Connection - Ref. Typical Details

Denotes Bent Beam - Cut, Miter and Full Penetration Weld Beam to Create Change in Elevation

NOTES:

1.

2. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES

3. VARIATIONS IS TOP OF STEEL ELEVATION (T.O.S.) SHALL BE NOTES AS (+/- 0'-0")

4. PROVIDE CONT. L3x3x5/16" AT ALL ROOF EDGES AND OPENINGS. WHERE SLAB EDGE

ANGLE OVERLAPS BEAM FLANGE BY LESS THAN 2" PROVIDE 3/8" FLANGE EXTENSION

PLATE AND 3/8" STIFFENERS @ 48" o.c.

N

NOTES:

1.

2. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES

3. VARIATIONS IS TOP OF STEEL ELEVATION (T.O.S.) SHALL BE NOTES AS (+/- 0'-0")

5. PROVIDE CONT. L5x5x1/4" AT ALL SLAB EDGES AND OPENINGS. WHERE SLAB EDGE

ANGLE OVERLAPS BEAM FLANGE BY LESS THAN 2" PROVIDE 3/8" FLANGE EXTENSION

PLATE AND 3/8" STIFFENERS @ 48" o.c.

N

E X

L

A

E X

L

A

E X

L

A

E X

L

A

E X

L

A

E X

L

A

E X

L

A

E X

L

A

E X

L

A

E X

L

A

E X

L

A

E X

L

A

E X

L

A

EX. W16x26

EX. W16x26

EX. W16x26

EX. W16x26

EX. W16x26

EX. W16x26

EX. W16x26

EX. W16x26

E X

L x x

/4

E X

L x x

/4

E X

L x x

/4

E X

L x x

/4

S2.1

L H s

L H s

L H s

L H s

L H s

L H s

K

C S s

K

C S s

L H s

L H s

L H s

L H s

L H s

K

C S s

K

C S s

L H s

L H s

K

C S s

K

C S s

L H s

L H s

L H s

L H s

L H s

L H s

L H s

T.O.S. ELEV. 1'-3 1/2"

T.O.S. ELEV. 3/4"

S3.1

S3.1

S3.1

RTU-1

1338#

RTU-2

1386#

RTU-3

1374#

MAU-1

1008#

MAU-3

1008# MAU-2

1309#

L7x4x3/8s (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH) L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

T.O.S. ELEV. 7 1/4"

T.O.S. ELEV. 0"

C x

C x

C6x13 C6x13 C6x13 C6x13

C6x13C6x13C6x13C6x13

C6x13

C6x13

C6x13

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)L7x4x3/8 (LLH)

COORD. CURB SUPPORT w/

MEP EQUIPMENT SIZE,

LOCATION, & PENETRATIONS

- TYP.

C x

S3.1

Sim

S3.1

Sim

W x

W x

W x

S3.1

S3.1

S2.5

W x

W x

W x

W x

W x

S2.5

S2.5

S2.5

Sim

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

S2.4

S2.4

S2.4

W x

S3.1

PRE-ENGINEERED LIGHT GAUGE

METAL TRUSSES @ 24" O.C.

PRE-ENGINEERED LIGHT GAUGE

METAL TRUSSES @ 24" O.C.

CONT. HSS7x5x5/16 (LSH) w/

3/8" STL. PL - TYP., SEE

SECTION FOR ADDITIONAL

INFORMATION

N

NOTES:

1.

2. 3/4" SHEATHING APA SPAN RATED 24"o.c.

3. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

S tru ct _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

Ro of

F ra m in g Pl an

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

S2.1

11.04.2026

BID

JA

C

K S

O N

T O

W N

S H

IP

M

U N

IC

IP

A L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

Floor Schedule - Roof

TYPE DECK TYPE/GA/FINISH

MAX. BEAM

SPACING

1 1/2" Metal Roof Deck TYPE B - 20 GA - GALVANIZED 5'-6"

OFFICE MEZZANINE FLOOR TOS ELEVATION (U.N.O.): 592'-11 3/8"

Floor Schedule - Platform Floor

TYPE DECK TYPE/GA/FINISH

MAX. BEAM

SPACING

SLAB

REINFORCING

5" Concrete on 2" Composite Metal Deck

TYPE VLI - 20 GA -

GALVANIZED

5'-6" 66-W2.9xW2.9 WWF

SCALE: 1/8" = 1'-0"

ROOF FRAMING PLAN

SCALE: 1/8" = 1'-0"S2.1

EQUIPMENT PLATFORM FLOOR

FRAMING PLAN

OFFICE ADDITION ROOF TOS ELEVATION (U.N.O.): 600'-1 3/8"

tag rev date revision note

SCALE: 1/8" = 1'-0"S2.1

CANOPY VESTIBULE FRAMING

PLAN

TRUSS BEARING CANOPY ELEVATION (U.N.O.): 593'-11 3/8"

WOOD FRAMED TRUSSES @ 24"

O.C.

CONTRACTOR SHALL VERIFY ALL CONDITIONS

AND DIMENSIONS FOR THE ENTIRE PROJECT

BEFORE PROCEEDING WITH THE WORK.

Denotes Beam to Column Moment Connection to be Designed by Fabricator for Forces Indicated

Steel Symbol Legend

Denotes Beam to Column Cantilever Moment Connection to be Designed by Fabricator for Forces Indicated

Denotes Beam to Beam Moment Connection to be Designed by Fabricator for Forces Indicated

Denotes Beam Cantilever - Beam to Extend over top of Column

Denotes Continuous Beam

Denotes Beam to Column/Beam Slip Connection - Ref. Typical Details

Denotes Bent Beam - Cut, Miter and Full Penetration Weld Beam to Create Change in Elevation

S3.1

MAU-5 MAU-3

940#

W x s

/8

K

C S s

K

C S s W x s

/4

K

C S s

K s

W x s

/8

+11 1/8"

W10x19s

K

C S s

/8

W x s

/8

+9 1/4"

W10x19s

K

C S s

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

W x s

K s

K

C S s

T.O.S. ELEV. 0"

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH) L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

T.O.S. ELEV. 1'-3 5/8"SUPPORT ANGLES FOR RAILING ABOVE - COORD.

LOCATION & SPACING w/ REQUIREMENTS OF

RAILING MANUF, TYP.

L7x4x3/8 (LLH)

COORDINATE LOCATION

w/ RAIL ABOVE - TYP.

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH) L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

L7x4x3/8 (LLH)

W x s

COORDINATE LOCATION

w/ RAIL ABOVE - TYP.

SUPPORT ANGLES FOR RAILING ABOVE - COORD.

LOCATION & SPACING w/ REQUIREMENTS OF

RAILING MANUF, TYP.

S2.2

K

C S s

K

C S s

K

C S s

K

C S s

S3.1

S3.1

S3.1

Sim

S3.1

S3.1

Sim

W x s

K s

K s

K s

K s

K s

K s

K s

K s

K s

K s

K s

K s

SPACING @ SNOWDRIFT = 4'-0" MAX.

T.O.S. ELEV. 0"

T.O.S. ELEV. 1'-3 5/8"

S1.2

2x6 SHEAR WALL - TYP.

- SEE SECTION FOR

ADDITIONAL INFORMATION

- ALL STUDS & SHEATHING TO

BE PRESSURE TREATED.

NOTES:

1.

2. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES

3. VARIATIONS IS TOP OF STEEL ELEVATION (T.O.S.) SHALL BE NOTES AS (+/- 0'-0")

4. PROVIDE CONT. L3x3x5/16" AT ALL ROOF EDGES AND OPENINGS. WHERE SLAB EDGE

ANGLE OVERLAPS BEAM FLANGE BY LESS THAN 2" PROVIDE 3/8" FLANGE EXTENSION

PLATE AND 3/8" STIFFENERS @ 48" o.c.

N

NOTES:

1.

2. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES

3. VARIATIONS IS TOP OF STEEL ELEVATION (T.O.S.) SHALL BE NOTES AS (+/- 0'-0")

4. PROVIDE CONT. L3x3x5/16" AT ALL ROOF EDGES AND OPENINGS. WHERE SLAB EDGE

ANGLE OVERLAPS BEAM FLANGE BY LESS THAN 2" PROVIDE 3/8" FLANGE EXTENSION

PLATE AND 3/8" STIFFENERS @ 48" o.c.

N

Bundle Stud Marker *B

Load Bearing Wall Marker L**-*

Symbol Legend

Shear Wall Marker S**-*

(2) Load Bearing Walls Marker 2L**-*

(2) Shear Walls Marker 2S**-*

(2) Load Bearing Walls Marker Staggered Studs

2L**-*-S

(2) Shear Walls Marker Staggered Studs

2S**-*-S

NOTES:

1.

2. MAXIMUM ROOF TRUSS SPACING 2'-0" U.N.O.

3. ALL WOOD-TO-WOOD CONNECTIONS TO BE MADE WITH APPLICABLE SIMPSON PRODUCT OR EQUAL.

4. ROOF CONSTRUCTION 3/4" SHEATHING, APA RATED @ 24" O.C.

N

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

S tru ct _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

Ro of

F ra m in g Pl an

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

S2.2

11.04.2026

BID

JA

C

K S

O N

T O

W N

S H

IP

M

U N

IC

IP

A L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

SCALE: 1/8" = 1'-0"S2.2

1 HIGH ROOF FRAMING PLAN

SCALE: 1/8" = 1'-0"

LOW ROOF FRAMING PLAN

SCALE: 1/8" = 1'-0"

SALT SHED ROOF FRAMING PLAN

Floor Schedule - Roof

TYPE DECK TYPE/GA/FINISH

MAX. BEAM

SPACING

1 1/2" Metal Roof Deck TYPE B - 20 GA - GALVANIZED 5'-6"

Floor Schedule - Roof

TYPE DECK TYPE/GA/FINISH

MAX. BEAM

SPACING

1 1/2" Metal Roof Deck TYPE B - 20 GA - GALVANIZED 5'-6"

LOW ROOF FRAMING TOS ELEVATION (U.N.O.): 598'-4 5/8"

HIGH ROOF FRAMING TOS ELEVATION (U.N.O.): 608'-4 7/8"

SALT SHED TRUSS BEARING ELEVATION (U.N.O.): 612'-0"

BEFORE PROCEEDING WITH THE WORK.

MLW8

M S

W

M S

W

M L

W

MLW8

MSW8

M L

W

M S

W

M L

W

M L

W

M L

W

S3.1

S3.1

S3.1

MSW8 MLW8

MP824

MP824

H S

S x x

/4 w

/8

P

L

W16x31 w/ 3/8" PL.

MP824 MP824

2L5x3-1/2x5/16LLBB

MP816 MP816

W8x15 w/ 3/8" PL.

MP816 MP816

H S

S x x

/1 w

/8

P

L

MP816

MP816

MP816

MP816

MP816

MP816

H S

S x x

/1 w

/8

P

L

H S

S x x

/1 w

/8

P

L

H S

S x x

/1 w

/8

P

L

MP816

MP816

HSS8x4x5/16 w/ 3/8" PL.

MP816MP816

MP816MP816MP816MP816

HSS8x4x5/16 w/ 3/8" PL.

HSS8x4x5/16 w/ 3/8" PL.

2L6x3-1/2x5/16LLBBs

2L6x3-1/2x5/16LLBBs

2L6x3-1/2x5/16LLBBs

MP816 MP816 MP816 MP816 MP816 MP816

HSS8x4x5/16s HSS8x4x5/16s HSS8x4x5/16s HSS8x4x5/16s

MP816 MP816 MP816 MP816

HSS8x4x5/16s

MP816MP816 MP816 MP816

2L5x3-1/2x5/16LLBB

MP816MP816

MP816 MP816

2L5x3-1/2x5/16LLBB

H S

S x x

/1 w

/8

P

L

MP816

MP816

W x w

/8

P L

W x w

/8

P L

W x w

/8

P L

MP1016

MP1016

MP1016

MP1016

MP1016

MP1016

W8x10 w/ 3/8" PL.W8x10 w/ 3/8" PL.

MP1016MP1016 MP1016 MP1016

NOTES:

1. LINTEL PLANS SHOW LOAD BEARING MASONRY OPENINGS (EXCEPT AT MEP/FP)

OPENINGS, AND OTHER SPECIAL CASES. REFER TO TYPICAL LINTEL SCHEDULES

FOR LINTELS AT ALL OTHER OPENINGS.

2. REFER TO TYPICAL LINTEL SCHEDULES FOR ADDITIONAL REQUIREMENTS.

3. PROVIDE 3/8" PLATE BELOW ALL W-SHAPE AND HSS LINTELS UNLESS NOTED

OTHERWISE. REFER TO TYPICAL DETAILS. NO PLATE REQUIRED FOR SINGLE OR

DOUBLE ANGLE LINTELS.

DENOTES MASONRY PILASTER. SEE SCHEDULE.

N

S3.1

S3.1

M S

W

B

M S

W

B

MSW12B

MLW12

EXTENT OF SHEAR WALL

40'-0"

MSW12A

M S

W

A

MLW12

HSS16x4x5/16 HSS8x4x5/16 HSS16x4x5/16 HSS16x4x5/16 HSS16x4x5/16 HSS8x4x5/16 HSS16x4x5/16 HSS8x4x5/16 HSS16x4x5/16

MP1224 MP1224 MP1216 MP1216 MP1224 MP1224 MP1224 MP1224 MP1224 MP1224 MP1216 MP1216 MP1224 MP1224 MP1224 MP1216 MP1224 MP1224

EXTENT OF SHEAR WALL

FULL LENGTH OF HIGH WALL

NOTES:

1. LINTEL PLANS SHOW LOAD BEARING MASONRY OPENINGS (EXCEPT AT MEP/FP)

OPENINGS, AND OTHER SPECIAL CASES. REFER TO TYPICAL LINTEL SCHEDULES

FOR LINTELS AT ALL OTHER OPENINGS.

2. REFER TO TYPICAL LINTEL SCHEDULES FOR ADDITIONAL REQUIREMENTS.

3. PROVIDE 3/8" PLATE BELOW ALL W-SHAPE AND HSS LINTELS UNLESS NOTED

OTHERWISE. REFER TO TYPICAL DETAILS. NO PLATE REQUIRED FOR SINGLE OR

DOUBLE ANGLE LINTELS.

DENOTES MASONRY PILASTER. SEE SCHEDULE.

WHERE PILASTERS ARE LOCATED IN EXIST. PORTIONS OF BUILDING,

PROVIDE A MIN. OF (2) COURSES OF SOLID GROUTED MASONRY BELOW

LINTEL BEARING.

N

D A T E

S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e

-6

-5

THIS BAR MUST MEASURE ONE INCH (1")

THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF

PRINTED ON 24" x 36" SHEET

0 1

A ut od es k D oc s:

//1

.0

_J ac ks on

_T w p_ B ui ld in g/

S tru ct _1

.0

_J ac ks on _T w p_

B ui ld in g_ R

.rv t

Li nt el P la n

P R

O P

O S

D

IT

IO

N

R E

N O

V A

T

IO

N

S2.3

11.04.2026

BID

JA

C

K S

O N

T O

W N

S H

IP

M

U N

IC

IP

A L

C E

N T

E R

R

O T H

S C

H U

R C

H R

O

R

IN

G G

R O

N

N S

Y

LV

A

SCALE: 1/8" = 1'-0"

MAIN BUILDING ADDITION LINTEL PLAN

SCALE: 1/8" = 1'-0"

STORAGE BUILDING LINTEL PLAN

CAULK & JOINT

FILLER (B.S.)

3000 PSI CONC GROUT

BUILDING PAPER

(1) #5 (TYP) GROUT

CORES SOLID AT REINF

NOTES:

1. DO NOT EXTEND MASONRY REINF. THROUGH CONTROL JOINTS

2. CONTRACTOR'S OPTION FOR TYPE OF JOINT

SYNTHETIC RUBBER

CONTROL JOINT

#5 BENT BAR

CAULK BOTH SIDES

SYNTHETIC RUBBER

CONTROL JOINT

BOND BEAM w/ (2) #5

BARS DO NOT

EXTEND BARS

THROUGH JOINT

CONT. HORIZ TRUSS TYPE

JOINT REINF - 9 GA GALV

METAL @ 16" o.c. VERT.

BOND BEAM w/

(2) #5 BARS

TYPICAL

WALL REINF

CMU WALL

ROOF

JOIST

METAL

ROOF

DECK

CLIP ANGLE 5x3x1/4" x 0'-8" LG. (LLV) EA

SIDE @ EA JOIST

(TYP)

1 1/2" CLR MIN

3/16 2" MIN

TYP

CONT. HORIZ TRUSS TYPE

JOINT REINF - 9 GA GALV

METAL @ 16" o.c. VERT.

CLIP L5x3x1/4"x0'-8" LG.

(LLV) EA SIDE @ 4'-0" o.c.

BOND BEAM w/

(2) #5 BARS

METAL ROOF

DECK

TYPICAL

WALL REINF

CMU WALL

L3x3x1/4" @ 4'-0" o.c.

/2

C L

R M

IN

3/16 3/16 2" MIN

NOTE:

1. L6x4x5/16 ANGLE HEADERS AT 5'-0" o.c. w/ L6x4x3/8x0'-6" CLIP ANGLES (LLV)

EACH END OF HEADER.

2. PROVIDE L6x4x5/16 EACH SIDE OF WALL AT EVERY OTHER 5'-0" HEADER

SPACING.

METAL

DECK

HEADER

3/16 4"

TYP

3/16 2"

TYP

3/16 4"

TYP

FLOOR OR ROOF

CONSTRUCTION

CMU WALL

CLIP L5x3x1/4" x

0'-6" LG. (LLV)

@ 48" o.c. (B.S.)

10 GA PL x 8" LG.

CONT. HORIZ TRUSS

TYPE JOINT REINF - 9

GA GALV METAL @

16" o.c. VERT.

BOND BEAM

w/ (2) #5 BARS

NOTCH BLOCK AT

REBAR LOC AND

GROUT SOLID

AT EACH BLOCKTYPICAL

WALL REINF

3/16

1/8 8

S E

E P

L A

N

S T

E E

L J

O

IS

T

JOIST & WALL

C L R

S E

E P

L A

N

S T

E E

L B

E A

M

BEAM & WALL

L1 1/2x1 1/2x1/4 @ 48" o.c. BETWEEN JOISTS, NOTE:

1. CLIP L6x4x5/16x0'-8" (LLV) EACH SIDE OF WALL AT 48" o.c.

3/16 3 @ 12

TYP

L3x3x1/4 w/ 1/4" CONN.

PLATE E.E .

45.00°

ROOF BEAML3x3x1/4

BETWEEN TWO

BEAMS

L6x4x5/16"

LENGTH TO MATCH THE

LEGTH OF WALL

- CONNECT WITH 1/2" DIA

EPOXY ANCHOR (2)…