12-3.1 JACKSON GC STRUCTURAL DRAWINGS.pdf
PDF 2 MB Posted
- Solicitation number
- US.261682
- Issued by
- York County, Pennsylvania
About this file
Summary of Jackson Township Municipal Center Structural Drawings
These are structural drawings for the proposed addition and renovations to the Jackson Township Municipal Center located at 439 Roths Church Road, Spring Grove, Pennsylvania 17362. The project encompasses structural design for a building addition, renovations to the existing township building, construction of a new storage garage, and a new salt storage building. The drawings detail foundation plans and site plans with finish floor elevations ranging from 580.36' to 583'-8 3/8", including specifications for foundation walls, footings, concrete slabs on grade, and underpinning procedures for the existing structure. The structural design incorporates concrete foundations with reinforced masonry and concrete walls, steel joists and beams, metal roof decking, and wood-framed roof trusses. The project is designed in accordance with the 2021 International Building Code and ASCE 7-16, with design loads including 20 PSF roof live load, 50 PSF office floor load, and 115 MPH ultimate design wind speed. The bid documents became available November 4, 2026, with sealed bids due December 8, 2026, at 1:00 PM EST via the PennBid Program. A pre-bid conference was scheduled for November 10, 2026, at 10:00 AM EST at the project site. The contract time is 400 calendar days from the Notice to Proceed, with contracts to be awarded at a regularly scheduled Jackson Township meeting on January 4, 2027.
The project is divided into four separate contracts: General Construction, Plumbing Construction, Mechanical Construction, and Electrical Construction. Each bidder must submit a bid bond or certified check equal to 10% of the maximum bid and provide evidence of qualifications to perform the work. The project is subject to the Pennsylvania Prevailing Wage Act (Act 442, P.L. 987), effective August 15, 1961, as amended. Structural specifications include soil bearing capacity of 3,000 PSF, concrete strength requirements ranging from 3,500 to 5,000 PSI depending on exposure class, reinforcing steel conforming to ASTM A615 Grade 60, and structural steel conforming to ASTM A992 for wide flange shapes and ASTM A500 Grade B for hollow structural sections. The drawings specify shop drawing requirements, special inspections by a registered geotechnical engineer for earthwork and fill placement, and quality assurance programs for masonry construction in accordance with TMS 402/ACI 530. Jackson Township reserves the right to accept any bid, waive informalities, or reject any or all bids.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S1.1
S1.2
S1.2
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.4
S1.5
S1.5
ADD-ALTERNATE
ANTI-RAM BOLLARD
& FOOTING BY OTHERS
- TYP. THIS SIDE
- SEE PLAN NOTE 1
SUBSURFACE RATE CONTROL FACILITY
SUBSURFACE STORAGE MRC FACILITY
25' FLAG POLE SONOTUBE FOUNDATION
- TYPE ST-1, SEE SCHEDULE FOR
REINFORCEMENT INFORMATION.
- TOP OF SONOTUBE TO BE +3" FROM GRADE.
- EMBEDMENT TO BE 6'-9" MINIMUM.
N
NOTES:
1. ANTI-RAM BOLLARD
A. BASIS OF DESIGN IS MODEL R-1009-04-R BY PATRIOT.
B. BOLLARD TO FOLLOW ASTM F2656-07 M30 P1.
C. FOUNDATIONS & FOOTINGS TO MEET REQUIREMENTS OF MANUF.
D A T E
S H E E T a rc h it e c tu re w o rk s h o p in c o n e s o u th r a ilr o a d s tr e e t h a n o v r n n s y lv a n ia p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
S tru ct _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
Fo un da tio n Si te P la n
P R
O P
O S
E D
A
D
IT
IO
N
R E
N O
V A
T
IO
N
S0.1
11.04.2026
BID
JA
C
K S
O N
T O
W N
S H
IP
M
U N
IC
IP
A L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
S P
R
IN
G G
R O
V
N
N S
Y
LV
A N
IA
SCALE: 3/32" = 1'-0"
FOUNDATION SITE PLAN
tag rev date revision note
CONTRACTOR SHALL VERIFY ALL CONDITIONS
AND DIMENSIONS FOR THE ENTIRE PROJECT
BEFORE PROCEEDING WITH THE WORK.
N
NOTES:
1. SEE CHART BELOW FOR FINISH FLOOR ELEVATION AND SLAB CONSTRUCTION
2. COORDINATE BRICK SHELF ELEVATIONS WITH FINISH GRADE
3. DENOTES SLEEVE LOCATIONS IN FOOTINGS/FOUNDATION WALLS
FOR UNDERGROUND PIPING - SEE TYPICAL PIPE SLEEVE THROUGH
FOUNDATION DETAIL
T.F. ***.**'
T.P. ***.**'
Step Footing Marker
Top of Pier Marker
Top of Footing Marker
Pier Size Marker
Column Footing Size Marker
Foundation Wall Size Marker
P**
W**
Foundation Wall Footing Size Marker
F*.*
WF****
Foundation Symbol Legend
T.W. ***.**' Top of Wall Marker
Transition from Standard Footing to Trench Footing Marker
Rectangular Pier Size Marker RP**
Combined Column Footing Size Marker CF*.*
Retaining Wall Footing Marker RW-*
MFW8
EWF24 EWF24
MFW8
3524135
M F
W
W F
MFW8
WF1224
M F
W
W F
M F
W
W F
M F
W
W F
M F
W
W F
M F
W
W F
MFW8
WF1224
S1.4
S1.4
MFW8-8
WF1230 MFW8-8
WF1230
M F
W
-8
W F
M F
W
-8
W F
T .F
.3
T.F. 582.36'
T .F
.3
T.F. 580.36'
T .F
.3
T.F. 582.36'
T.F. 582.36'
T.F. 580.36'
T.F. 582.36'
T.F. 580.36'
T.F. 582.36'
T.F. 580.36'
S1.4
S1.4
S1.1
S1.4TYP.
TYP.
TYP.
BOTT. OF FOOTING
TO MATCH EXISTING
T.F. 582.36'
BOTT. OF FOOTING
TO MATCH EXISTING
S3.1
S3.1
S3.1
DENOTES
UNDERPINNING
SEQUENCE
T .F
.3
T .F
.3
T .F
.3
T .F
.3
T.F. 576.36'
T.F. 578.36'
T.F. 580.36'
T.F. 574.36'
T .F
.3
T .F
.3
T .F
.3
T.F. 574.36'
W F
M F
W
-8
3" DRYPACK
#5 @ 12" o.c.
- HORIZONTAL
BAR DOWLED
PER SEQUENCE
DRAWINGS
EXISTING FDN
WALL & FTG TO
REMAIN
EXISTING FOOTING
WIDTH SAME AS
NEW SLAB ON GRADE
- SEE FDN PLAN
V .I
.F
M
IN
F
R O
M G
R A
D E
EXIST. SLAB TO
BE REMOVED
3" DRYPACK
NOTE 2
NOTE 1
1 3 5 2 4
NOTES:
1. SEQUENCE OF UNDERPINNING
2. EXCAVATE ONLY ONE 4'-0" SECTION AT A TIME
3. THE SAME NUMBER OF SEQUENCE MAY BE EXCAVATED SIMULTANEOUSLY (SEE PLAN)
1'-0"
DRIVE REBAR INTO
GROUND FOR SPLICE
20'-0"
4'-0" 4'-0" 4'-0" 4'-0" 4'-0"
UNDERPINNING PROCEDURE
1. CONTRACTOR: VERIFY CONDITIONS, ELEVATIONS & DIMENSIONS OF EXISTING WALL
2. FOUNDATIONS BEFORE PROCEEDING WITH UNDERPINNING OPERATIONS AND
NOTIFY THE ENGINEER OF ANY VARIANCE OR ADVERSE CONDITIONS THAT MAY NOT
BE PROVIDED FOR ON THE FOUNDATION DRAWINGS.
3. PERFORM ALL SHORING & BRACING AS REQUIRED TO ENSURE THE SAFETY OF THE
STRUCTURE. EXERCISE CARE THAT EXISTING STRUCTURE IS NOT FURTHER
DAMAGED IN ANY WAY.
4. REMOVE SECTIONS OF SUPPORTING EARTH 4 FEET IN LENGTH LEAVING NOT LESS
THAN 4 FEET OF SUPPORT ON EACH SIDE. SHORE AND BRACE EACH SECTION TO
PREVENT SETTLEMENT OR MOVEMENT OF STRUCTURE. DUE TO THE POOR SOIL
CONDITION BELOW THE FOOTING OF THE EXISTING BUILDING ONLY ONE 4-FOOT
SECTION SHALL BE UNDERPINNED AT ONE TIME. SEE FOUNDATION PLAN FOR
SEQUENCE AND LOCATION.
5. PORTLAND CEMENT ASTM C150 TYPE III, HIGH EARLY STRENGTH, IS REQUIRED FOR
THE UNDERPINNING CONCRETE.
6. 5.PLACE ONE-SIDED FORM TO EXTENT REQUIRED; HOWEVER, IF ADJACENT SIDES
OF THE UNDERPINNED SECTION IS UNSTABLE, THREE OR FOUR-SIDED FORMS
SHALL BE REQUIRED.
7. POUR CONCRETE IN UNDERPINNED SECTIONS TO WITHIN 3 INCHES OF BOTTOM OF
EXISTING WALL OR FOOTING.
8. AFTER SETTING A MINIMUM OF 24 HOURS, THE REMAINING 3 INCHES: PACK WITH A
DRY MIX (VERY LITTLE WATER OF NON-SHRINKING GROUT OR PART ONE SAND AND
PART ONE CEMENT. RAM MIXTURE THOROUGHLY TO FILL ALL VOIDS. STRIKE OFF
FLUSH WITH WALL OR FOOTING.
9. EACH UNDERPINNED SECTION SHALL BE DRY PACKED BEFORE THE NEXT SECTION
IS EXCAVATED.
10. A WAITING PERIOD OF 72 HOURS FOR CURING: ALLOW BETWEEN DRYPACKING AND
EXCAVATION OF ADJACENT SECTION.
11. CONTRACTOR: REPAIR ALL DAMAGE TO EXISTING BUILDINGS NECESSARY FOR OR
RESULTING FROM UNDERPINNING OPERATIONS.
TAG
PER
MFW**
THE WALL TAG ON THE FOUNDATION PLAN AND
THE ASSOCIATED SCHEDULE IDENTIFIES THE
CONSTRUCTION OF THE STRUCTURAL PORTION
OF THE FOUNDATION WALL ONLY. ADDITIONAL
WYTHES OF NON STRUCTURAL MASONRY MAY
EXTEND TO THE FOUNDATION - COORDINATE
WITH ARCHITECTURAL DRAWINGS
WF** THE WALL FOOTING TAG ON THE FOUNDATION
PLAN AND THE ASSOCIATED SCHEDULE IDENTIFIES
THE WALL FOOTING SIZE AND REINFORCING
REQUIREMENTS. THE WALL FOOTING SHALL BE
CENTERED BELOW THE 'TOTAL WALL WIDTH'
NON-STRUCTURAL
WALL WYTHES -
COORDINATE WITH
ARCH. DWGS
TAG AND SCHEDULE
FOOTING WIDTH PER
WIDTH
TOTAL WALL
CONCRETE WALL FOOTING
Floor Schedule - Foundation Plan
TYPE SLAB REINFORCING FINISH FLOOR
4" Concrete 66-W2.9xW2.9 WWF 583'-8 3/8"
5" Concrete #4 @ 12" O.C. 583'-8 3/8"
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
S tru ct _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
Fo un da tio n Pl an
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
S1.1
11.04.2026
BID
JA
C
K S
O N
T O
W N
S H
IP
M
U N
IC
IP
A L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
SCALE: 1/8" = 1'-0"
MAIN BUILDING FOUNDATION PLAN
SCALE: 1/2" = 1'-0"S1.1
2 Underpinning Sequence
SCALE: 3/4" = 1'-0"S1.1
4 Masonry Foundation Wall Key
SCALE: 3/4" = 1'-0"S1.1
3 Typical Underpinning Detail
BEFORE PROCEEDING WITH THE WORK.
T.F. ***.**'
T.P. ***.**'
Step Footing Marker
Top of Pier Marker
Top of Footing Marker
Pier Size Marker
Column Footing Size Marker
Foundation Wall Size Marker
P**
W**
Foundation Wall Footing Size Marker
F*.*
WF****
Foundation Symbol Legend
T.W. ***.**' Top of Wall Marker
Transition from Standard Footing to Trench Footing Marker
Rectangular Pier Size Marker RP**
Combined Column Footing Size Marker CF*.*
Retaining Wall Footing Marker RW-*
S1.2
W20
W
W20
W20
24" MAT FOUNDATION
- SEE SECTION & FLOOR SCHEDULE
FOR REINFORCEMENT INFORMATION
S1.4
6'-0"
6'-0"
6'-0"6'-0"
W12
W
W F
W
R W
-1
RW-1
MFW12
WF1230
T.F. 572.83'
T .F
.8
T.F. 570.83'
T.F. 568.83'
S3.1
S3.1
S1.5
S1.5
TYP. @ TRENCH
DRAINS
T .F
.8
T .F
.8
T .F
.8
T .F
.8
T.F. 572.83'
T.F. 574.83'
S1.5
RW-1
RW-1
R W
-1
W
W12
W12
W
W F
T.F. 5 72.83'
T.F. 574.36'
M F
W
W F
T.F. 574.83'
T.F. 576.83'
T.F. 578.83'
T.F. 576.83'
T.F. 574.83'
T.F. 572.83'
SLOPE SLAB 1/4"
PER 1'-0"
TOWARDS DRAINS
SLOPE SLAB 1/4"
PER 1'-0"
TOWARDS DRAINS
TYP. @ TRENCH
DRAINS
NOTES:
1. SEE CHART BELOW FOR FINISH FLOOR ELEVATION AND SLAB CONSTRUCTION
2. COORDINATE BRICK SHELF ELEVATIONS WITH FINISH GRADE
3. DENOTES SLEEVE LOCATIONS IN FOOTINGS/FOUNDATION WALLS
FOR UNDERGROUND PIPING - SEE TYPICAL PIPE SLEEVE THROUGH
FOUNDATION DETAIL
N
NOTES:
1. SEE CHART BELOW FOR FINISH FLOOR ELEVATION AND SLAB CONSTRUCTION
2. COORDINATE BRICK SHELF ELEVATIONS WITH FINISH GRADE
3. DENOTES SLEEVE LOCATIONS IN FOOTINGS/FOUNDATION WALLS
FOR UNDERGROUND PIPING - SEE TYPICAL PIPE SLEEVE THROUGH
FOUNDATION DETAIL
N
F.F. ELEV. 582'-0"
T.O.W. ELEV. 602'-0"
T.O.W. ELEV. 612'-0"
S2.8
WOOD FRAMED ROOF
TRUSS @ 24" O.C.
- ALIGN TRUSS w/ WALL
STUD
2x6 @ 24" O.C. SHEAR WALL w/ 7/16" PLYWOOD @
EXTERIOR FACE - TYP. (3) SIDES
- PROVIDE 6" PANEL & FIELD NAILING (8d
FASTENERS)
- PROVIDE (2) STUDS @ EACH END
- PROVIDE SIMPSON HD5B HOLDDOWN OR
EQUIVALENT AT EACH END OF ALL SHEAR WALLS.
- PROVIDE BLOCKING AT PANEL EDGES
- ALL STUDS & SHEATHING TO BE PRESSURE
TREATED.
(2) 2x6 TOP PLATE
- PRESSURE TREATED WOOD
20" CONC. WALL
- SEE CONCRETE FOUNDATION WALL
SCHEDULE FOR REINFORCEMENT
INFORMATION.
- F'c = 5000 PSI
#9 @ 6" O.C. BENT BARS
- TYP. @ W20 WALLS
CONC. SLAB w/ SIKA H1000
- SEE PLAN FOR SLAB DEPTH & REINF.
- ALL SALT SHED SLAB REINF. TO BE
EPOXY COATED.
APPLY SIKA H1000 TO ALL
INTERIOR WALL SURFACES
1/2" KW-EZ CRC w/ 6"
EMBEDMENT @ 48" O.C.
- GALVANIZED
S
P L
IC
E
24" MAT FOUNDATION
- SEE PLAN FOR EXTENTS
- SEE FLOOR SCHEDULE FOR
REINFORCEMENT INFORMATION
- F'c = 5000 PSI
6'-0" TYP.
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
S tru ct _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
Fo un da tio n Pl an
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
S1.2
11.04.2026
BID
JA
C
K S
O N
T O
W N
S H
IP
M
U N
IC
IP
A L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
SCALE: 1/8" = 1'-0"
SALT SHED FOUNDATION PLAN
SCALE: 1/8" = 1'-0"
STORAGE GARAGE FOUNDATION PLAN
Floor Schedule - Storage Foundation Plan
TYPE SLAB REINFORCING FINISH FLOOR
6" Concrete #5 @ 12" O.C. 581'-6"
8" Concrete #5 @ 12" O.C. 581'-6"
Floor Schedule - Salt Shed Foundation Plan TYPE SLAB REINFORCING FINISH FLOOR Comments
8" Concrete #5 @ 12" O.C. 582'-0" SALT SHED SLAB REINF.
TO BE EXPOXY COATED
24" Mat Foundation #8 @ 9" O.C., E.W. T/B 579'-0"
SCALE: 1/2" = 1'-0"S1.2
3 WALL SECTION tag rev date revision note
DESIGN LOADS:
DESIGN FLOOR LIVE LOADS
ROOF LIVE LOAD 20 PSF
ROOF 20 PSF
FLOOR 15 PSF
SEISMIC IMPORTANCE FACTOR (Ie) 1.00
ADDITIONAL NOTES:
a. THE CONTRACTOR IS CAUTIONED AS TO NOT STORE ANY
CONSTRUCTION MATERIALS OR UNDERTAKE ANY CONSTRUCTION
OPERATION WILL EXCEED THE DESIGN LIVE LOAD CAPACITIES NOTED.
b. THE STRUCTURE HAS BEEN DESIGNED FOR THE DEAD AND LIVE
LOADS INDICATED ABOVE, ANY INCREASE OF LOADS DUE TO CHANGE
IN USAGE OR CONSTRUCTION MATERIALS, ETC. SHALL HAVE THE
WRITTEN APPROVAL OF THE ENGINEER.
c. THE STABILITY OF THE STRUCTURE IS DEPENDENT UPON THE
DIAPHRAGM ACTION OF THE ROOFS. THE CONTRACTOR IS
COMPLETELY RESPONSIBLE FOR THE METHODS OF CONSTRUCTION
AND SHALL PROVIDE ALL GUYS, BRACING AND SHORING REQUIRED TO
ACCOMMODATE ALL INTERIM LOADING CONDITIONS THROUGHOUT
THE CONSTRUCTION PHASE.
d. WEIGHT OF EQUIPMENT SHOWN ON THE STRUCTURAL DRAWINGS
HAVE BEEN CONSIDERED IN THE DESIGN OF THE FRAMING. ANY
ADDITIONAL EQUIPMENT NOT SHOWN ON THE STRUCTURAL
DRAWINGS AND EXCEEDING 300 POUNDS SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER FOR APPROVAL PRIOR TO
INSTALLATION.
GOVERNING DESIGN CODE
2021 INTERNATIONAL BUILDING CODE
ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
BUILDING RISK CATEGORY
DESIGN ROOF LIVE LOADS
DESIGN DEAD LOADS - NOT INCL. STRUCTURE SELF WEIGHT
SEISMIC DESIGN DATA
DESIGN WIND LOAD PARAMETERS
CORRIDORS (ABOVE 1ST FLOOR) 80 PSF
LOBBIES AND FIRST FLOOR CORRIDORS 100 PSF
OFFICE 50 PSF
PARTITIONS (APPLIED TO OCCUPANCIES LESS THAN 80 PSF) 15 PSF
MECHANICAL UNIT LOADS SEE MECH DWGS
STAIRS AND EXITS 100 PSF
HANDRAILS, GUARDS AND GRAB BARS PER 1607.8
GROUND SNOW LOAD (Pg) 30 PSF
DESIGN ROOF SNOW LOADS
FLAT ROOF SNOW LOAD (Pf) 21 PSF
SNOW EXPOSURE FACTOR (Ce) 1.0
SNOW LOAD IMPORTANCE FACTOR (Is) 1.00
THERMAL FACTOR (Ct) 1.0
SNOW DRIFT SEE DIAGRAM
II
MINIMUM UNIFORM DESIGN SNOW LOAD (NOT REDUCIBLE) 30 PSF
ULTIMATE DESIGN WIND SPEED (Vult) 115 MPH
ALLOWABLE STRESS DESIGN WIND SPEED (Vasd) 89 MPH
INTERNAL PRESSURE COEFFICIENT +/- 0.18
WIND EXPOSURE CATEGORY - PLAN WEST-EAST B
MAPPED SPECTRAL ACCELERATION (Ss)
MAPPED SPECTRAL ACCELERATION (S1)
SITE CLASS
DESIGN SPECTRAL RESPONSE COEFF. (Sds)
DESIGN SPECTRAL RESPONSE COEFF. (Sd1)
SEISMIC DESIGN CATEGORY
PLAN NORTH-SOUTH DIRECTION
SEISMIC FORCE RESISTING SYSTEM
DESIGN BASE SHEAR (V)
0.149
0.044
C
0.130
0.044
A
STEEL SYSTEMS NOT
SPECIFICALLY DESIGNED
FOR SEISMIC RESISTANCE
-- KIPS
ANALYSIS PROCEDURE EQUIV. LATERAL FORCE
RESPONSE MODIFICATION COEFF. (R) 3.0
SEISMIC RESPONSE COEFF. (Cs) --
PLAN WEST-EAST DIRECTION
SEISMIC FORCE RESISTING SYSTEM
DESIGN BASE SHEAR (V)
STEEL SYSTEMS NOT
SPECIFICALLY DESIGNED
FOR SEISMIC RESISTANCE
-- KIPS
RESPONSE MODIFICATION COEFF. (R) 3.0
SEISMIC RESPONSE COEFF. (Cs) --
WIND EXPOSURE CATEGORY - PLAN NORTH-SOUTH B
EQUIPMENT PLATFORM STORAGE 250 PSF
GARAGE STORAGE FUTURE SOLAR 10 PSF
GENERAL NOTES
1. THE CONTRACTOR IS ADVISED THAT ALL PLANS, DIMENSIONS, AND DETAILS DEPICT
FIELD CONDITION AS SHOWN. MINOR VARIATIONS ARE TO BE EXPECTED AND ANY
DEVIATIONS FROM THE CONTRACT DOCUMENTS SHALL BE APPROVED BY THE
ARCHITECT IN WRITING PRIOR TO PROCEEDING.
2. THE CONTRACTOR SHALL FIELD CHECK AND VERIFY ALL DIMENSIONS AND
ELEVATIONS OF EXISTING WORK PRIOR TO FABRICATION OF ANY NEW MATERIALS.
IF THE EXISTING FIELD CONDITIONS DO NOT PERMIT THE INSTALLATION OF THE
WORK IN ACCORDANCE WITH THE DETAILS SHOWN, THE CONTRACTOR SHALL
NOTIFY THE ENGINEER IMMEDIATELY AND PROVIDE A SKETCH OF THE CONDITION
WITH THEIR PROPOSED MODIFICATION OF THE DETAILS GIVEN ON THE CONTRACT
DOCUMENTS. DO NOT COMMENCE WORK UNTIL CONDITION IS RESOLVED AND
MODIFICATION IS APPROVED BY THE ENGINEER.
3. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE LOCATION OF
UTILITIES IN THE IMMEDIATE VICINITY OF CONSTRUCTION SO AS TO PREVENT
DAMAGE TO THEM. SHOULD DAMAGE TO SUCH UTILITIES OCCUR, THE CONTRACTOR
SHALL BE REQUIRED TO REPAIR SUCH DAMAGE AT THEIR OWN EXPENSE AND TO
THE SATISFACTION OF THE OWNER.
4. SHOP DRAWINGS FOR ALL STRUCTURAL ELEMENTS SHOWN ON THE CONTRACT
DOCUMENTS MUST BE SUBMITTED BY THE GENERAL CONTRACTOR AND REVIEWED
BY THE ENGINEER. IF THE CONTRACTOR OR OWNER FAILS TO OBTAIN ENGINEER'S
REVIEW OF THE SHOP DRAWINGS, THE ENGINEER WILL NOT BE RESPONSIBLE FOR
THE STRUCTURAL CERTIFICATION AND DESIGN OF THE PROJECT. SHOP DRAWINGS
ARE REVIEWED BY THE ENGINEER AS A CONVENIENCE TO THE GENERAL
CONTRACTOR AND ARE NOT A CONTRACT DOCUMENT.
5. LOADS GREATER THAN THE DESIGN LIVE LOADS SHALL NOT BE PLACED ON THE
STRUCTURE. A CONCRETE STRUCTURE MAY NOT SUPPORT IT'S DESIGN LIVE LOAD
FOR 28 DAYS. CONTRACTOR SHALL SUPPORT ADJACENT STRUCTURES, UTILITIES,
AND EXCAVATIONS AS REQUIRED. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS
FOR ALL TEMPORARY FORM WORK, SHEETING, SHORING AND UNDERPINNING
SEALED BY A PROFESSIONAL ENGINEER AS A PART OF THE CONTRACTOR'S WORK.
6. THE CONTRACTOR SHALL CONSULT THE ARCHITECTURAL, MECHANICAL, AND
ELECTRICAL DRAWINGS FOR THE QUANTITY, LOCATION, AND DIMENSION OF HOLES
THROUGH FLOOR AND ROOF: CHASES, INSERTS, OPENINGS, SLEEVES, WASHERS,
DRIPS, REVEALS, DEPRESSIONS AND OTHER PROJECT REQUIREMENTS. REFER TO
ARCHITECTURAL DRAWINGS FOR THE FOLLOWING INFORMATION:
a. LOCATION AND THICKNESS OF MASONRY PARTITIONS
b. FULL EXTENT OF MASONRY INFILL AREAS
c. LOCATION AND THICKNESS OF STUD PARTITIONS
d. LOCATION AND SIZE OF WINDOWS, DOORS AND WALL OPENINGS
e. STAIRS, FLOOR AND WALL FINISHES
f. DETAIL DIMENSIONS AND SECTION DETAILS AS REQUIRED
7. THIS STRUCTURE HAS BEEN DESIGNED TO BE SELF-SUPPORTING AND STABLE
AFTER THE CONSTRUCTION OF THE BUILDING IS TO BE COMPLETED. THE STABILITY
OF THE STRUCTURE PRIOR TO COMPLETION IS SOLELY THE RESPONSIBILITY OF
THE CONTRACTOR. THIS RESPONSIBILITY EXTENDS TO ALL RELATED ASPECTS OF
THE CONSTRUCTION ACTIVITY INCLUDING, BUT NOT LIMITED TO, ERECTION
METHODS, ERECTION SEQUENCE, TEMPORARY BRACING, FORMS, SHORING, USE OF
EQUIPMENT AND SIMILAR CONSTRUCTION PROCEDURES.
8. THE CONTRACTOR SHALL BE RESPONSIBLE TO DETERMINE ALLOWABLE
CONSTRUCTION LOADS AND TO PROVIDE DESIGN AND CONSTRUCTION OF
FALSEWORK, FORMWORK, STAGING, BRACING, SHEETING, SHORING, AND
UNDERPINNING AS NECESSARY TO PREVENT ANY LATERAL OR VERTICAL
MOVEMENTS TO, AND TO INSURE THE STRUCTURAL INTEGRITY OF EXISTING
BUILDINGS, STREETS, AND ANY EXISTING UTILITY LINES.
9. BRACING, SHEETING, SHORING, ETC., REQUIRED TO INSURE THE STRUCTURAL
INTEGRITY OF THE EXISTING BUILDINGS OR NEW CONSTRUCTION, SIDEWALKS,
UTILITIES ETC., SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER ENGAGED BY
THE CONTRACTOR. DETAILED SIGNED AND SEALED SHOP DRAWINGS SHALL BE
PREPARED INDICATING ALL WORK TO BE PERFORMED. SUBMIT THE SHOP
DRAWINGS IN ACCORDANCE WITH THE CONTRACT REQUIREMENTS.
SHOP DRAWINGS
1. DUPLICATION/PHOTOCOPYING OF THESE STRUCTURAL DRAWINGS SHALL NOT BE
PERMITTED FOR SHOP DRAWINGS. THIS INCLUDES PARTIAL AND/OR COMPLETE
DUPLICATION OF PLAN SHEETS AS BACKGROUNDS FOR SHOP DRAWINGS. ALL
SECTIONS INCLUDED IN THESE CONTRACT DRAWINGS MAY NOT BE
DUPLICATED/PHOTOCOPIED ON ANY SHOP DRAWINGS.
2. ORIGINAL SHOP DRAWINGS SHALL BE SUBMITTED FOR THE ARCHITECT/ENGINEER
REVIEW FOR THE FOLLOWING ITEMS AND AS PER THE SPECIFICATIONS:
a. CONCRETE AND MASONRY REINFORCING
b. SLAB ON GRADE CONTROL JOINT LAYOUT
c. CONCRETE MIX DESIGNS
• FOUNDATIONS
• RETAINING WALLS
• ELEVATED SLABS
• SLAB ON GRADE LISTING FIBER MESH REINFORCEMENT & DOSAGE RATE
d. MASONRY CERTIFICATIONS AND GROUT DESIGN
e. STEEL JOIST AND DECKING
f. STRUCTURAL STEEL
g. LIGHT GAGE METAL FRAMING
h. PRECAST CONCRETE
3. CONTRACTOR SHALL SUBMIT, FOR REVIEW, DRAWINGS AND CALCULATIONS FOR
ALL PERFORMANCE ASSEMBLIES IDENTIFIED IN THE GENERAL NOTES AND SPECIFIC
MATERIAL NOTES AS WELL AS LISTED BELOW: THE DESIGN OF THESE ASSEMBLIES
IS THE RESPONSIBILITY OF THE CONTRACTOR'S ENGINEER REGISTERED IN THE
PROJECT'S JURISDICTION. ALL SUBMITTALS SHALL BEAR THIS ENGINEER'S SEAL
AND SIGNATURE. REVIEW SHALL BE FOR GENERAL CONFORMANCE WITH THE
PROJECT REQUIREMENTS AS INDICATED ON THE DRAWINGS AND IN THE GENERAL
NOTES.
a. METAL STAIRS AND METAL RAILINGS: DESIGNS SHALL TAKE INTO ACCOUNT
ALL VERTICAL AND LATERAL LOADS REQUIRED BY APPLICABLE BUILDING
CODES. WHERE HEADERS OR OTHER TYPES OF STRUCTURAL MEMBERS
HAVE BEEN DESIGNATED BY THE STRUCTURAL ENGINEER OF RECORD TO
SUPPORT THE STAIRS, THE CONNECTIONS FROM THE STAIRS SHALL BE
DESIGNED SO THAT NO ECCENTRIC OR TORSIONAL FORCES ARE INDUCED
IN THESE STRUCTURAL MEMBERS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR FURNISHING AND INSTALLING HARDWARE AS REQUIRED
BY THE STAIR DESIGN.
CONTRACTOR SHALL VERIFY ALL CONDITIONS
AND DIMENSIONS FOR THE ENTIRE PROJECT
BEFORE PROCEEDING WITH THE WORK.
A.F.F. Above Finish Floor BCX Bottom Chord Extension B.O.F. Bottom of Footing B.S. Brick Shelf Elevation (plans) B.S. Both Sides (sections) CANT. Cantilever CJ Control Joints CL Center Line CMU Concrete Masonry Units CONT. Continuous DIA. Diameter DBA Deformed Bar Anchor E.E. Each End E.F. Each Face E.S. Each Side E.W. Each Way EXIST Existing F.F. Finish Floor F.S. Flat Strap GA Gage GALV Galvanized HORIZ Horizontal HSS Hollow Structural Section L Angle
ABBREVIATION LIST
LG Long LLH Long Leg Horizontal LLV Long Leg Vertical LSH Long Side Horizontal LSV Long Side Vertical N.T.S. Not To Scale o.c. On Center PL Plate REINF. Reinforcing REM. To Remain S.F. Step Footing STIFF PL Stiffener Plate T.B.R. To Be Removed T&B Top and Bottom T.F. Top of Footing T.O.S. Top of Steel T.O.W. Top of Wall T.P. Top of Pier TYP Typical U.N.O. Unless Noted Otherwise VERT. Vertical V.I.F. Verify In Field WWF Welded Wire Fabric XE Extended End - Type R
FOUNDATIONS AND BACKFILL
1. SOIL BEARING CAPACITY OF 3,000 PSF WAS UTILIZED IN THE DESIGN OF THE
FOUNDATION SYSTEM.
2. SLAB ON GRADE DESIGN BASED ON MODULUS OF SUBGRADE REACTION OF 125 PCI.
3. PLACE EXTERIOR FOOTINGS AND FROST WALLS EXPOSED TO WEATHER AT LEAST
36" BELOW THE ADJACENT OUTSIDE FINISHED GRADE TO PROTECT FROM FROST
DAMAGE.
4. THE OWNER SHALL ENGAGE THE SERVICES OF A REGISTERED PROFESSIONAL
GEOTECHNICAL ENGINEER TO MONITOR AND INSPECT ALL EARTH WORK AND TO
PERFORM THE SPECIAL INSPECTIONS REQUIRED BY THE SCHEDULE OF SPECIAL
INSPECTIONS. THE GEOTECHNICAL ENGINEER SHALL SUPERVISE THE PLACING OF
THE COMPACTED FILL AND ALL THE MATERIALS AND EQUIPMENT USED FOR THIS
PURPOSE. THE GEOTECHNICAL ENGINEER SHALL CERTIFY, BY SEAL AND
SIGNATURE, THAT THE EARTH-WORK IS IN ACCORDANCE WITH THE GEOTECHNICAL
REPORT, PLANS AND SPECIFICATIONS.
5. THE SUB-FLOOR MATERIALS SHALL CONSIST OF AT LEAST FOUR TO SIX INCHES OF
GRAVEL OR CRUSHED STONE. THE SUB-FLOOR MATERIALS SHALL BE COMPACTED
BY AT LEAST FOUR COVERAGES OF A HEAVY-DUTY VIBRATORY ROLLER OR UNTIL
NO FURTHER COMPACTION IS OBSERVED. SEE THE DRAWINGS AND
SPECIFICATIONS FOR THE VAPOR BARRIER SIZE, TYPE AND LOCATION.
6. PRIOR TO CONCRETE PLACEMENT THE FOUNDATION BOTTOM SHALL BE
COMPACTED USING A WALK BEHIND VIBRATORY ROLLER OR GAS-POWERED
TAMPER.
7. IF SOIL OF THE BEARING CAPACITY NOTED ABOVE IS NOT ENCOUNTERED AT THE
ELEVATIONS SHOWN ON PLAN, UNSUITABLE SOILS SHALL BE REMOVED AND
REPLACED WITH STRUCTURAL FILL IN ACCORDANCE WITH THE GEOTECHNICAL
ENGINEER'S DIRECTION.
8. IF BEDROCK IS ENCOUNTERED AT OR ABOVE FOUNDATION SUBGRADE ELEVATION,
THE BEDROCK SURFACE SHALL BE OVER EXCAVATED A MINIMUM OF SIX INCHES
AND BACKFILLED WITH CRUSHED STONE TO THE SUBGRADE ELEVATION.
9. THE GEOTECHNICAL ENGINEER SHALL APPROVE SAMPLES OF ALL CONTRACTOR
PROPOSED COMPACTED FILL MATERIAL. IMPORTED STRUCTURAL FILL SHALL BE
FREE OF ORGANIC MATTER, ASH, CINDERS AND DEMOLITION DEBRIS.
10. CONTROL OF MOISTURE FOR PLACING FILL WILL BE BASED ON THE RESULTS OF
ASTM D-1557 MODIFIED PROCTOR TESTS.
11. ALL COMPACTED FILL SHALL HAVE A DENSITY OF AT LEAST 98% OF MAXIMUM DRY
DENSITY AS DETERMINED BY THE ASTM D-1557 MODIFIED PROCTOR TEST. PLACING
OF FILL WITH MOISTURE CONTENT OUTSIDE THE LIMITS FOR PROPER COMPACTION
SHALL NOT BE PERMITTED.
12. THE EXISTING SUBGRADE IN ALL FILL AND CUT AREAS SHALL BE COMPACTED TO A
FIRM, STABLE CONDITION AS DETERMINED BY THE GEOTECHNICAL ENGINEER,
PRIOR TO PLACEMENT OF FILLS AND EXCAVATION FOR FOOTINGS.
13. FILL MATERIAL SHALL BE PLACED IN LOOSE LIFTS NOT EXCEEDING 8" IN THICKNESS
AND SHALL BE MIXED, SPREAD, AND PLACED IN SUCH A WAY AS TO PRODUCE A
UNIFORM THICKNESS OF MATERIAL AFTER PLACING.
14. EACH LAYER OF FILL MATERIAL SHALL BE COMPACTED ON ALL PORTIONS OF THE
SURFACE OF EACH LIFT OF FILL BY RUBBER TIRE ROLLERS, SHEEP'S FOOT
ROLLERS, VIBRATORY ROLLERS, ETC. AS NECESSARY TO ATTAIN THE MAXIMUM DRY
DENSITY NOTED ABOVE AND AS APPROVED BY THE GEOTECHNICAL ENGINEER.
15. WHENEVER IN PLACE DENSITIES ARE FOUND TO BE BELOW LIMITS ACCEPTABLE TO
THE GEOTECHNICAL ENGINEER, ADDITIONAL ROLLING TO PRODUCE THE SPECIFIED
DENSITIES SHALL BE REQUIRED.
16. PLACING OF FILL WHEN FREE WATER IS STANDING ON THE EXISTING SURFACE
SHALL NOT BE PERMITTED.
17. PLACING OF FILL IN A FROZEN CONDITION OR ON TOP OF FROZEN MATERIAL SHALL
NOT BE PERMITTED.
18. SUBGRADE SUITABILITY SHALL BE VERIFIED BY GEOTECHNICAL ENGINEER WITHIN
24 HOURS PRIOR TO PLACING CONCRETE FOUNDATIONS AND CONCRETE SLABS ON
GRADE TO CONFIRM THAT NO DETERIORATION HAS OCCURRED SUBSEQUENT TO
TESTING PERFORMED AT TIME OF FILL PLACEMENT. UNSUITABLE CONDITIONS
SHALL BE CORRECTED PER GEOTECHNICAL ENGINEER'S RECOMMENDATION.
19. EXCAVATIONS SHOULD BE BACKFILLED OR HAVE CONCRETE PLACED AS SOON AS
POSSIBLE DURING CONSTRUCTION TO MINIMIZE ADVERSE AFFECTS TO SUBGRADE
CONDITIONS. GRADING DEPRESSIONS SHOULD BE AVOIDED.
20. WATER SHALL BE PREVENTED FROM ENTERING OPEN EXCAVATIONS. ANY
ACCUMULATED WATER SHALL BE REMOVED AS SOON AS POSSIBLE. IT IS
RECOMMENDED THAT CONCRETE BE PLACED THE SAME DAY THE EXCAVATION IS
MADE.
21. THE CONTRACTOR SHALL PROVIDE FOR DEWATERING AS REQUIRED DURING
EXCAVATION AND CONSTRUCTION.
CONCRETE
1. ALL WORK SHALL CONFORM TO THE "SPECIFICATIONS FOR STRUCTURAL
CONCRETE" (AMERICAN CONCRETE INSTITUTE, ACI 301) AND THE "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318), LATEST EDITIONS, UNLESS
NOTED OTHERWISE IN THE DRAWINGS OR PROJECT SPECIFICATIONS.
2. CONSTRUCTION TOLERANCES SHALL CONFORM TO THE "SPECIFICATION FOR
TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS" (ACI 117), LATEST
EDITION.
3. SHOP DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH THE "GUIDE TO
PRESENTING REINFORCING STEEL DESIGN DETAILS" (ACI 315) AND THE "ACI
DETAILING MANUAL" (SP-066), LATEST EDITIONS.
4. CONCRETE MATERIALS SHALL BE PROVIDED IN ACCORDANCE WITH THE
FOLLOWING SPECIFICATIONS:
• PORTLAND CEMENT ASTM C150
• HYDRAULIC CEMENT ASTM C1157
• FLY ASH AND NATURAL POZZOLAN ASTM C618
• SLAG CEMENT ASTM C989
• SILICA FUME ASTM C1240
• NORMAL WEIGHT AGGREGATE ASTM C33
• LIGHTWEIGHT AGGREGATE ASTM C330
• MIXING WATER ASTM C1602
• ADMIXTURES
• WATER REDUCTION AND SETTING TIME MODIFICATION ASTM C494
• PRODUCING FLOWING CONCRETE ASTM C107
• AIR ENTRAINMENT ASTM C260
• INHIBITING CHLORIDE-INDUCED CORROSION ASTM C1582
5. REINFORCING MATERIALS:
• REINFORCING BARS PLAIN-STEEL ASTM A615, GRADE 60, DEFORMED
• REINFORCING BARS LOW-ALLOY-STEEL ASTM A706, DEFORMED
(WELDABLE)
• REINFORCING BARS EPOXY-COATED ASTM A775
• WELDED WIRE FABRIC ASTM A1064
• EPOXY-COATED WELDED WIRE FABRIC ASTM A884, CLASS A COATING
6. REINFORCING SHALL COMPLY WITH ACI FOR FABRICATING, PLACING, AND
SUPPORTING REINFORCEMENT, AND THE FOLLOWING:
• BAR SPLICE LOCATIONS SHALL CONFORM TO ACI 318
• HORIZONTAL REINFORCING BARS IN WALLS AND FOOTINGS SHALL BE
CONTINUOUS AROUND CORNERS.
• UNLESS DETAILED CALCULATIONS ARE PROVIDED, REINFORCING BARS
DEVELOPMENT LENGTHS, EMBEDMENT DEPTHS AND LAP SPLICE DISTANCES
FOR f'c = 4000psi, NORMAL-WEIGHT CONCRETE, SHALL BE PER BELOW
7. EMBEDDED AND MISCELLANEOUS STEEL SHALL COMPLY WITH ASTM A36.
8. CONTINUOUS WALL OR FOOTING PLACEMENT SHALL NOT EXCEED 60 FEET
BETWEEN CONSTRUCTION JOINTS.
9. ALL EXPOSED CONCRETE CORNERS SHALL BE CHAMFERED 3/4" AT 45 DEGREES
UNLESS NOTED OTHERWISE.
10. SHALLOW INTERIOR FOUNDATIONS AND SLABS ON GRADE ARE NOT DESIGNED FOR
OR INTENDED TO BE EXPOSED TO FREEZE/THAW CYCLING OR RESIST FROST
HEAVE FORCES. GENERAL CONTRACTOR TO COORDINATE CONSTRUCTION AND
PROVIDE INTERIOR FOOTINGS BELOW FROST PENETRATION AS REQUIRED FOR
WINTER CONSTRUCTION.
11. PROVIDE CONSTRUCTION / CONTROL JOINT INSTALLATION PLAN AND PLACEMENT
SEQUENCE PLAN SUBMITTALS FOR REVIEW OF STRUCTURAL ENGINEER OF
RECORD PRIOR TO PLACING CONCRETE.
12. PROVIDE WALL AND SLAB THRU-SLEEVE PLAN SUBMITTALS FOR REVIEW OF
STRUCTURAL ENGINEER OF RECORD PRIOR TO PLACING CONCRETE.
13. CORE-DRILLING CONCRETE WALLS, SLABS, BEAMS OR COLUMNS WITHOUT
REINFORCING LOCATION SCANS AND PRIOR APPROVAL OF STRUCTURAL ENGINEER
OF RECORD SHALL NOT BE PERMITTED.
14. CONDUITS AND PIPES SHALL NOT BE EMBEDDED IN ELEVATED CONCRETE SLABS
SUPPORTED BY METAL DECK OR CONCRETE SLABS ON GRADE.
15. FIBER REINFORCED CONCRETE SHALL COMPLY WITH "GUIDE TO DESIGN WITH
FIBER-REINFORCED CONCRETE" (ACI 544.4), LATEST EDITION. DESIGN
CALCULATIONS SHALL BE SUBMITTED AS PER THE SHOP DRAWING NOTES AND
SPECIFICATIONS.
16. NON-SHRINK GROUT SHALL CONFORM TO ASTM C1107 AND ACHIEVE A MINIMUM 28
DAY COMPRESSIVE STRENGTH OF 8,000 psi.
17. STRUCTURAL ADHESIVES SHALL ONLY BE USED WITH PRIOR PERMISSION OF THE
STRUCTURAL ENGINEER OF RECORD OR AS SHOWN ON CONSTRUCTION
DOCUMENTS. THE BASIS OF DESIGN FOR ADHESIVES IS HY-200 BY "HILTI" OR SET BY
"SIMPSON" - THE USE OF ANY OTHER STRUCTURAL ADHESIVES SHALL BE SUBJECT
TO REVIEW BY THE EOR PRIOR TO INSTALLATION.
18. MINIMUM WIRE WELDED FABRIC REQUIREMENTS FOR SLABS:
• 3-1/2" FLOOR SLAB ON METAL DECK 66-W2.9xW2.9
• 5" FLOOR SLAB ON METAL DECK 66-W2.9xW2.9
• 4" FLOOR SLAB ON GRADE 66-W2.9xW2.9
• 5" FLOOR SLAB ON GRADE 44-W4.0xW4.0
19. COLD-WEATHER CONCRETE PLACEMENT SHALL COMPLY WITH THE PROVISIONS OF
ACI 306R. THE USE OF CALCIUM CHLORIDE, SALT, AND OTHER MATERIALS
CONTAINING ANTI- FREEZE AGENTS OR CHEMICAL ACCELERATORS SHALL NOT
BE PERMITTED UNLESS ACCEPTED IN THE MIX DESIGN.
20. HOT-WEATHER CONCRETE PLACEMENT SHALL COMPLY WITH THE PROVISIONS OF
ACI 305.
21. MINIMUM CONCRETE CLEAR COVER SHALL BE PROVIDED FOR REINFORCEMENT
PER ACI AND THE FOLLOWING:
• CONCRETE CAST AGAINST EARTH & PERMANENTLY 3"
EXPOSED
• CONCRETE EXPOSED TO EARTH OR WEATHER
#6 & LARGER 2"
#5 & SMALLER 1-1/2"
• CONCRETE NOT EXPOSED TO WEATHER OR GROUND
SLABS, WALLS, AND JOINTS 3/4"
BEAMS AND COLUMNS 1-1/2"
BAR LOCATION
VERT. & HORIZ. WALL BARS
FOOTING TOP BARS
FOOTING BOTTOM BARS
BAR SIZE
#3 ld ls ldh
20" 25" 8"
15" 19" 8"
#4 ld ls ldh
25" 33" 10"
19" 25" 10"
#5 ld ls ldh
32" 41" 12"
24" 31" 12"
REBAR LAP SPLICE LENGTHS
20" 25" 8" 25" 33" 10" 32" 41" 12"
VERT. & HORIZ. WALL BARS
FOOTING TOP BARS
FOOTING BOTTOM BARS
#6 ld ls ldh
38" 50" 15"
29" 38" 15"
#7 ld ls ldh
55" 71" 17"
42" 54" 17"
#8 ld ls ldh
62" 81" 19"
47" 62" 19"
38" 50" 15" 55" 71" 17" 62" 81" 19"
NOTE:
• VALUES ABOVE ARE FOR NORMAL WEIGHT CONCRETE ONLY.
• ld = MINIMUM TENSION DEVELOPMENT LENGTH
• ldh = MINIMUM 90 DEGREE HOOKED BAR DEVELOPMENT LENGTH
• ls = MINIMUM LENGTH OF LAP SPLICES IN TENSION
BAR SIZE
CONCRETE MIX DESIGN CRITERIA
FOOTINGS AND
FOUNDATION WALLS
INTERIOR SLABS ON
GRADE
EXPOSURE
CLASS
F1,S0,W0,C1
MAX. w/c
RATIO
0.55
MIN. f'c
3,500
AIR
CONTENT
5%
CEMENT
TYPE
I or II
INTERIOR ELEVATED
SLABS
EXTERIOR SLABS
F0,S0,W0,C1 0.50 4,000 N/A I or II
F0,S0,W0,C1 0.50 4,000 N/A I or II
F3,S0,W0,C2 0.40 5,000 6% I or II
SALT SHED RETAINING
WALL AND FOOTINGS F3,S2,W1,C2 0.50 5,000 5% I or II
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
S tru ct _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
Fo un da tio n N ot es
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
S1.3
11.04.2026
BID
JA
C
K S
O N
T O
W N
S H
IP
M
U N
IC
IP
A L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
BENT
BARS (B)
CONT.
BARS
D E
P T
H
WIDTHNOTES:
1. CONTINUOUS BARS SHALL HAVE 3" MINIMUM COVER
ON ALL SIDES.
2. BENT BARS SHALL BE PER THE FOUNDATION WALL
SCHEDULE.
BENT
BARS (B)
NOTES:
1. GROUT ALL CORES SOLID BELOW GRADE w/ 3,000 psi CONCRETE GROUT.
2. REINFORCING SHALL BE CENTERED IN WALL U.N.O.
3. PROVIDE HORIZONTAL JOINT REINFORCING PER SPECIFICATIONS -
SPACING NOT TO EXCEED 16" o.c.
4. WALLS WITH MULTIPLE WYTHES SHALL HAVE (1) LAYER OF REINFORCING
PER WYTHE
VERT.
BARS (V)
2'-0" MIN.
SPLICE
WIDTH
JOINT
REINF.
NOTES
1. BOTTOM OF NEW FOOTING TO MATCH BOTTOM OF EXISTING.
2. ADJUST OVERALL FOOTING THICKNESS AND WIDTH AS REQUIRED
TO MEET MINIMUM DIMENSIONS SHOWN.
3. BENT BAR SIZE AND SPACING SHALL MATCH NEW WALL VERTICAL
REINFORCING.
D
WIDTH
M
IN
D - EPOXY INTO
EXISTING FOOTING 8"
B
T
EXISTING WALL
AND FOOTING
NEW FOUNDATION
WALL - SEE PLAN FOR
FOR FOUNDATION
WALL SIZE AND
REINFORCEMENT
D E
P T
H
NOTES:
1. ALL REINFORCING SHALL HAVE 3" MINIMUM COVER
ON ALL SIDES.
2. SEE FOUNDATION PLAN AND FOUNDATION WALL
SCHEDULE FOR WALL THICKNESS, REINFORCING
AND BENT BAR (B) SIZE AND SPACING U.N.O.
HFT
BFT
T
B
S P
L
IC
E
HEEL
SEE PLAN
WALL TOE
CONT. HORIZ
TRUSS TYPE JOINT
REINF - 9 GA GALV
METAL @ 16" o.c.
#5 @ 48" o.c. - GROUT
CORES SOLID AT
REINF. w/ 3000 psi
CONC GROUT
(2) #5
CONT
#5 BENT BARS
@ 48" o.c.
CMU WALL
NOTE:
• CONDUIT NOT PERMITTED TO PENETRATE THRU THICKENED SLAB.
STEP CONDUIT BELOW THICKENED SLAB AS REQUIRED.
S E
E P
L A
N
3t
WRAP MESH
AROUND #4
NOSING BAR
#4 BENT BARS @
16" o.c. AROUND #4
NOSING BAR
SEE FOUNDATION
PLAN FOR FOOTING
SIZE AND
REINFORCING
(2) #5
SEE PLAN
FOR WALL
SIZE AND
REINF.
(M
IN
8"
SEE PLAN FOR LIMITS
DOOR LOC.
COORD w/
(2) #5
WRAP MESH
AROUND #4
NOSING BAR
EXTERIOR GRADE
COORDINATE w/ SITE
DRAWINGS
(M
IN
8"
1'-0"
#5 BENT
BARS @
16" o.c.
(2) #5 CONT.
(M
IN
(M
IN
(TYP)
8"
EQUIPTMENT SUPPLIER
COORDINATE WITH
#5 BARS @
12" o.c. (E.W.)
COMPACTED
STONE BASE
FROST WALL
EACH SIDE
NOTES:
1. COORDINATE EQUIPMENT PAD SIZE AND
LOCATION WITH M.E.P.CONTRACTORS.
2. PAD SHALL EXTEND 6" MINIMUM BEYOND
UNIT IN ALL DIRECTIONS
(MIN)
1'-0"
CONT. HORIZ TRUSS TYPE
JOINT REINF - 9 GA GALV
METAL @ 16" o.c. VERT.
#5 @ 48" o.c. - GROUT
CORES SOLID @ REINF.
w/ 3000 psi CONC GROUT
BENT BARS -
GROUT CORES
SOLID @ REINF
8" CMU WALL
OR WIDER
P L A
N
S E
E
P L A
N
S E
E
PLAN
SEE
1/2" DIA. x 18" LONG
SMOOTH DOWELS @
24" o.c. - EPOXY INTO
EXISTING SLAB AND
GREASE END INTO NEW
CONCRETE
SAWCUT EXISTING SLAB -
PROVIDE BONDING AGENT
(SIKADUR 32 HI-MOD OR
APPROVED EQUAL) TO BOND
OLD CONCRETE TO NEW
NOTE: DOWELS ARE NOT REQUIRED IF BOTH SLABS
BEAR 4" MIN ON A FOUNDATION WALL OR
FOOTING
NEW CONCRETE SLAB
SLAB
EXIST CONCRETE
9"
BENT
BARS (B)
NOTES:
1. ALL REINFORCING BARS SHALL HAVE 2" MINIMUM COVER ON ALL SIDES. 8" WALLS
SHALL HAVE ONLY ONE LAYER OF REINFORCING CENTERED IN THE WALL
2. BENT BARS SHALL BE THE SAME SIZE AND SPACING AS FOUNDATION WALL
VERTICAL REINFORCING, U.N.O.
3. FOR WALL WITH SHELF - 'Z' BARS SIZE AND SPACING SHALL MATCH (V) BARS.
4. FOR WALLS BACKING VENEER INSTALL DOVETAIL SLOTS @ 24" o.c. HORIZONTALLY
AND METAL TIES @ 16" o.c. VERTICALLY
5. COORDINATE SHELF LOCATIONS AND ELEVATIONS WITH ARCHITECTURAL
DRAWINGS
VERT.
BARS (V)
HORIZ.
BARS (H)
WIDTH DOWELS @ MASONRY
WALLS - SIZE AND
SPACING TO MATCH
MASONRY WALL VERTICAL
REINFORCING
'Z' BARS
VERT.
BARS (V)
HORIZ.
BARS (H)
WALL AT SHELF
'X' 'Y'
W10-6
'X' - WIDTH OF CONC. STEM
'Y' - WIDTH OF CONC. BRICK SHELF
NOTES:
1. ALL TIE SIZES TO BE (3) - #3 BARS AT 1 1/2" o.c. (T&B) REMAINDER @ 12" o.c.
2. SEE FOUNDATION PLAN FOR PIER SIZES
4 BARS
SINGLE TIE
8 BARS
2 TIES PER SET
SCALE: 3/4" = 1'-0"S1.4
Typical Thickened Slab Detail At Masonry Walls
SCALE: 3/4" = 1'-0"S1.4
Wall Footing Schedule with Masonry Foundation Walls
SCALE: 3/4" = 1'-0"S1.4
2 Masonry Foundation Wall Schedule
Schedule - Wall Footing
MARK DEPTH WIDTH REINFORCING
WF1224 1'-0" 2'-0" (3) #5 CONT.
WF1230 1'-0" 2'-6" (3) #5 CONT.
WF1436 1'-2" 3'-0" (4) #5 CONT.
SCALE: 3/4" = 1'-0"S1.4
Wall Footing Adjacent To Existing Schedule
Schedule - Wall Footing at Existing
MARK WIDTH REINFORCING
EWF24 24" T - (4) #5; B - (3) #5; D - #5 @ 32" o.c.
Schedule - Masonry Foundation Wall
MARK WIDTH REINFORCING
MFW8 8" #5 @ 48" o.c. (V) - #5 @ 24" o.c. (B)
MFW8-8 16" #5 @ 48" o.c. (V) - #5 @ 24" o.c. (B)
MFW12 12" #5 @ 48" o.c. (V) - #5 @ 24" o.c. (B)
SCALE: 3/4" = 1'-0"S1.4
9 Typical Exterior Wall At Door Detail
SCALE: 3/4" = 1'-0"S1.4
10 Typical Frost Wall
SCALE: 3/4" = 1'-0"S1.4
11 Typical Exterior Equipment Pad
SCALE: 3/4" = 1'-0"S1.4
7 Typical Interior Wall Footing
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
S tru ct _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
Fo un da tio n Sc he du le a nd D et ai ls
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
S1.4
11.04.2026
BID
JA
C
K S
O N
T O
W N
S H
IP
M
U N
IC
IP
A L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
SCALE: 3/4" = 1'-0"S1.4
12 Typical New to Existing Slab
SCALE: 3/4" = 1'-0"S1.4
6 Retaining Wall Footing Schedule
Schedule - Retaining Wall Footing
MARK HEEL TOE DEPTH REINFORCING
RW-1 4'-6" 3'-6" 1'-8" T - #8 @ 12" o.c.; HFT - (9) #6 CONT.; BFT - (4) #6 CONT.; SPLICE 4'-0"
SCALE: 3/4" = 1'-0"S1.4
3 Concrete Foundation Wall Schedule
Schedule - Concrete Foundation Wall
MARK WIDTH REINFORCING
W12 12" #7 @ 12" o.c. (V) #5 @ 12" o.c. (H)
W20 20" #8 @ 12" o.c. (V) #6 @ 12" o.c. (H) tag rev date revision note
SCALE: 3/4" = 1'-0"S1.4
5 Sonotube Footing Schedule
Schedule - Sonotube Footings
MARK DIAMETER
VERTICAL
BARS TIES
ST-1 24" (8) #8 (2) #3 @ 12" o.c.
SAME SIZE
AND QUANTITY
DIA
36 BAR
2d (MIN) d
3" 3"
(2) - #4 x 3'-0" BARS @ MID
DEPTH OF SLAB @ EACH WALL
JAMB
CONCRETE OR
MASONRY WALL
NOTES
1. BENT BAR SPACING TO BE 2x VERTICAL BAR SPACING - NOT TO EXCEED 32" o.c.
2. CONT. PL. WIDTH TO BE 'S' MINUS 1".
3. HEADED STUDS ON CONT. PL. TO BE 1/2" DIA. x 4" LONG @ 48" o.c.
4. HEADED STUDS TO BE LOCATED INSIDE HORIZONTAL BARS
VERTICAL
BARS
CONCRETE
WALL
BENT
BARS
CONCRETE
SLAB ON
GRADE
CONCRETE
WALL (SEE
PLAN)
COATED #6
DOWELS - 24"
LG @ 24" o.c.
PREMOLDED
EXPANSION JOINT
MATERIAL
3/4" CHAMFER
EACH SIDE OF
JOINT
CONCRETE WALL
EXPANSION JOINT
CONCRETE
WALL (SEE
PLAN)
3/4" CHAMFER EACH
SIDE OF WALL AT
CONTROL JOINT
CONCRETE WALL
CONTROL JOINT
CONCRETE WALL
CONSTRUCTION
JOINT
CONCRETE
WALL (SEE
PLAN)
1 1/2" x 5 1/5" SHEAR KEY w/
WATERSTOP
PLAN
SEE
REINFORCED CONCRETE NOTES
SPLICE LENGTH PER
NEW FDN.
WALL - SEE
SECTIONS
CONT. WALL
FTG. REINF.
EPOXY GROUT
DOWELS INTO
EXISTING FOOTING -
SIZE & QUANTITY TO
MATCH CONT. WALL
REINF.
EXISTING
WALL AND
FOOTING
8"
MATCH BOTTOM OF NEW
FOOTING w/ BOTTOM OF
EXIST FOOTING
PIPE
6" 6"
SLEEVE
TOP OF
FOOTING
NOTE:
• IF DIMENSION TO PIPE SLEEVE IS LESS THAN
THE FOOTING DEPTH, LOWER FOOTING TO
PERMIT PIPE TO PASS THRU WALL ABOVE
FOOTING. REFER TO CONDITION #3 &
FOOTING STEP DOWN DETAILS.
S E
E N
O T
E
T O
P O
F
IP
E S
L E
E V
E
UNDERGROUND
PIPE
NOTE:
• WHERE TOP OF PIPE / CONDUIT IS BELOW
BOTTOM OF FOOTING BY AT LEAST FOOTING
WIDTH OR 4'-0" WHICHEVER IS GREATER,
PIPE MAY BE RUN UNDER FOOTING WITHOUT
A SLEEVE OR CONCRETE ENCASEMENT .
BOTTOM OF
FOOTING
S E
E N
O T
E
REINFORCED
CONCRETE
FOOTING
PIPE
(SEE MEP
DWGS.)
PIPE SLEEVE
GROUT
M
IN
NOTE:
• STEP FOOTING DOWN AS REQUIRED IN
ACCORDANCE WITH TYPICAL WALL
FOOTING STEP DETAIL.
D E
P T
H
F T
G
2'-8" MIN.
TOOL OR SAW CUT - 1/4
DEPTH (SAW WITHIN 24 HRS.
OF PLACING CONCRETE)
NOTE: CONTRACTORS OPTION
FOR TYPE OF JOINT
PREMOLDED
KEYED JOINT
STOP REINFORCING 6"
FROM JOINT
SAWED CONTROL JOINT
CONSTRUCTION JOINT
T /3
T
T /3
T
1'-6" 1'-6"
SEE ARCH. DRAWINGS
WALL OPENING
CONSTRUCTION
JOINT
CONCRETE OR
MASONRY WALL
(1) - #4 x 3'-0" LG.
BAR AT MID
DEPTH OF SLAB
@ EA WALL JAMB
3"
MID DEPTH OF SLAB
BENT BARS 3"
CONTROL OR
CONSTRUCTION JOINTS
CONCRETE OR
MASONRY WALL
MIN
44db
0" TYP
CORNER BARS
SAME SIZE AND
SPACING AS HORIZ.
WALL REINF.
HORIZONTAL AND
VERTICAL WALL
REINFORCEMENT
(PER DESIGN)
HORIZONTAL AND
VERTICAL WALL
REINFORCEMENT
(PER DESIGN)
BENT BARS SAME
SIZE AND SPACING AS
HORIZONTAL WALL
REINFORCEMENT
HORIZONTAL AND
VERTICAL WALL
REINFORCEMENT
(PER DESIGN)
DEVELOPEMENT LENGTH
D E
V E
L O
P E
M E
N T
L E
N G
T H
(2) #5 - 5'-0" LG
- 2'-6" LEG -
TYP.
BOND BEAM
REINFORCING
(2) #5
2'-0" MIN. BAR
SPLICE
FILL PIPE WITH CONCRETE AND
SMOOTH MOUND AT TOP OF PIPE
8" DIA. SCH.
40 STAINLESS
STEEL PIPE
BOLLARD
SEALANT
CONCRETE
ENCASEMENT
FINISH GRADE
TYP.
6"
M
IN
T Y
P
#3 @ 12" o.c. E.W.
1/4" CONT. BENT
PL. w/ 1/2" DIA.
SHEAR STUDS
@ 12" o.c.
WATERSTOP
1" STEEL GRATING
INSTALLED FLUSH
w/ SLAB
2" MIN.
6" 1'-0" 6"
2'-0"
1 1/2"x 1 1/2"x 3/16' ANGLE w/ HEADED STUDS @ 24" o.c
(GALV.)
/4
METAL OVERHEAD
DOOR
CHANNEL
BEYOND
CONCRETE SLAB ON
GRADE
SEE PLAN FOR
FOUNDATION
WALL SIZE AND
REINFORCING
#5 BENT BARS @
16" o.c AROUND #5
NOSING BAR
SCALE: 3/4" = 1'-0"S1.5
1 Typical Step Footing Detail
SCALE: 3/4" = 1'-0"S1.5
12 Typical Pipe at Wall Footing Details
SCALE: 3/4" = 1'-0"S1.5
8 Typical Crack Control Joints
SCALE: 3/4" = 1'-0"S1.5
Typical Slab on Grade Construction at Openings Construction at Building Entrance
SCALE: 3/4" = 1'-0"S1.5
Typical Slab on Grade Reinforcement at Wall Corners Reinforcement at Wall Corners
SCALE: 3/4" = 1'-0"S1.5
9 Typical Slab to Wall Connections
SCALE: 3/4" = 1'-0"S1.5
10 Typical Concrete Wall Joints
SCALE: 3/4" = 1'-0"S1.5
3 Typical Reinforcing Around Corner
SCALE: 3/4" = 1'-0"S1.5
Typical Concrete Wall Intersection Reinforcing
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
S tru ct _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
Fo un da tio n De ta ils
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
S1.5
11.04.2026
BID
JA
C
K S
O N
T O
W N
S H
IP
M
U N
IC
IP
A L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
SCALE: 3/4" = 1'-0"S1.5
5 Typical Bond Beam Detail At Corner
SCALE: 3/4" = 1'-0"S1.5
Typical Detail Of New Footing Adjacent To Existing
SCALE: 3/4" = 1'-0"S1.5
11 Typical Pipe Bollard Detail
SCALE: 3/4" = 1'-0"S1.5
13 Typical Foundation Drain Detail tag rev date revision note
SCALE: 3/4" = 1'-0"S1.5
14 Typical Depressed Slab Detail
BEFORE PROCEEDING WITH THE WORK.
Denotes Beam to Column Moment Connection to be Designed by Fabricator for Forces Indicated
Steel Symbol Legend
Denotes Beam to Column Cantilever Moment Connection to be Designed by Fabricator for Forces Indicated
Denotes Beam to Beam Moment Connection to be Designed by Fabricator for Forces Indicated
Denotes Beam Cantilever - Beam to Extend over top of Column
Denotes Continuous Beam
Denotes Beam to Column/Beam Slip Connection - Ref. Typical Details
Denotes Bent Beam - Cut, Miter and Full Penetration Weld Beam to Create Change in Elevation
NOTES:
1.
2. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES
3. VARIATIONS IS TOP OF STEEL ELEVATION (T.O.S.) SHALL BE NOTES AS (+/- 0'-0")
4. PROVIDE CONT. L3x3x5/16" AT ALL ROOF EDGES AND OPENINGS. WHERE SLAB EDGE
ANGLE OVERLAPS BEAM FLANGE BY LESS THAN 2" PROVIDE 3/8" FLANGE EXTENSION
PLATE AND 3/8" STIFFENERS @ 48" o.c.
N
NOTES:
1.
2. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES
3. VARIATIONS IS TOP OF STEEL ELEVATION (T.O.S.) SHALL BE NOTES AS (+/- 0'-0")
5. PROVIDE CONT. L5x5x1/4" AT ALL SLAB EDGES AND OPENINGS. WHERE SLAB EDGE
ANGLE OVERLAPS BEAM FLANGE BY LESS THAN 2" PROVIDE 3/8" FLANGE EXTENSION
PLATE AND 3/8" STIFFENERS @ 48" o.c.
N
E X
L
A
E X
L
A
E X
L
A
E X
L
A
E X
L
A
E X
L
A
E X
L
A
E X
L
A
E X
L
A
E X
L
A
E X
L
A
E X
L
A
E X
L
A
EX. W16x26
EX. W16x26
EX. W16x26
EX. W16x26
EX. W16x26
EX. W16x26
EX. W16x26
EX. W16x26
E X
L x x
/4
E X
L x x
/4
E X
L x x
/4
E X
L x x
/4
S2.1
L H s
L H s
L H s
L H s
L H s
L H s
K
C S s
K
C S s
L H s
L H s
L H s
L H s
L H s
K
C S s
K
C S s
L H s
L H s
K
C S s
K
C S s
L H s
L H s
L H s
L H s
L H s
L H s
L H s
T.O.S. ELEV. 1'-3 1/2"
T.O.S. ELEV. 3/4"
S3.1
S3.1
S3.1
RTU-1
1338#
RTU-2
1386#
RTU-3
1374#
MAU-1
1008#
MAU-3
1008# MAU-2
1309#
L7x4x3/8s (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH) L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
T.O.S. ELEV. 7 1/4"
T.O.S. ELEV. 0"
C x
C x
C6x13 C6x13 C6x13 C6x13
C6x13C6x13C6x13C6x13
C6x13
C6x13
C6x13
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)L7x4x3/8 (LLH)
COORD. CURB SUPPORT w/
MEP EQUIPMENT SIZE,
LOCATION, & PENETRATIONS
- TYP.
C x
S3.1
Sim
S3.1
Sim
W x
W x
W x
S3.1
S3.1
S2.5
W x
W x
W x
W x
W x
S2.5
S2.5
S2.5
Sim
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
S2.4
S2.4
S2.4
W x
S3.1
PRE-ENGINEERED LIGHT GAUGE
METAL TRUSSES @ 24" O.C.
PRE-ENGINEERED LIGHT GAUGE
METAL TRUSSES @ 24" O.C.
CONT. HSS7x5x5/16 (LSH) w/
3/8" STL. PL - TYP., SEE
SECTION FOR ADDITIONAL
INFORMATION
N
NOTES:
1.
2. 3/4" SHEATHING APA SPAN RATED 24"o.c.
3. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
S tru ct _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
Ro of
F ra m in g Pl an
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
S2.1
11.04.2026
BID
JA
C
K S
O N
T O
W N
S H
IP
M
U N
IC
IP
A L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
Floor Schedule - Roof
TYPE DECK TYPE/GA/FINISH
MAX. BEAM
SPACING
1 1/2" Metal Roof Deck TYPE B - 20 GA - GALVANIZED 5'-6"
OFFICE MEZZANINE FLOOR TOS ELEVATION (U.N.O.): 592'-11 3/8"
Floor Schedule - Platform Floor
TYPE DECK TYPE/GA/FINISH
MAX. BEAM
SPACING
SLAB
REINFORCING
5" Concrete on 2" Composite Metal Deck
TYPE VLI - 20 GA -
GALVANIZED
5'-6" 66-W2.9xW2.9 WWF
SCALE: 1/8" = 1'-0"
ROOF FRAMING PLAN
SCALE: 1/8" = 1'-0"S2.1
EQUIPMENT PLATFORM FLOOR
FRAMING PLAN
OFFICE ADDITION ROOF TOS ELEVATION (U.N.O.): 600'-1 3/8"
tag rev date revision note
SCALE: 1/8" = 1'-0"S2.1
CANOPY VESTIBULE FRAMING
PLAN
TRUSS BEARING CANOPY ELEVATION (U.N.O.): 593'-11 3/8"
WOOD FRAMED TRUSSES @ 24"
O.C.
CONTRACTOR SHALL VERIFY ALL CONDITIONS
AND DIMENSIONS FOR THE ENTIRE PROJECT
BEFORE PROCEEDING WITH THE WORK.
Denotes Beam to Column Moment Connection to be Designed by Fabricator for Forces Indicated
Steel Symbol Legend
Denotes Beam to Column Cantilever Moment Connection to be Designed by Fabricator for Forces Indicated
Denotes Beam to Beam Moment Connection to be Designed by Fabricator for Forces Indicated
Denotes Beam Cantilever - Beam to Extend over top of Column
Denotes Continuous Beam
Denotes Beam to Column/Beam Slip Connection - Ref. Typical Details
Denotes Bent Beam - Cut, Miter and Full Penetration Weld Beam to Create Change in Elevation
S3.1
MAU-5 MAU-3
940#
W x s
/8
K
C S s
K
C S s W x s
/4
K
C S s
K s
W x s
/8
+11 1/8"
W10x19s
K
C S s
/8
W x s
/8
+9 1/4"
W10x19s
K
C S s
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
W x s
K s
K
C S s
T.O.S. ELEV. 0"
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH) L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
T.O.S. ELEV. 1'-3 5/8"SUPPORT ANGLES FOR RAILING ABOVE - COORD.
LOCATION & SPACING w/ REQUIREMENTS OF
RAILING MANUF, TYP.
L7x4x3/8 (LLH)
COORDINATE LOCATION
w/ RAIL ABOVE - TYP.
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH) L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
L7x4x3/8 (LLH)
W x s
COORDINATE LOCATION
w/ RAIL ABOVE - TYP.
SUPPORT ANGLES FOR RAILING ABOVE - COORD.
LOCATION & SPACING w/ REQUIREMENTS OF
RAILING MANUF, TYP.
S2.2
K
C S s
K
C S s
K
C S s
K
C S s
S3.1
S3.1
S3.1
Sim
S3.1
S3.1
Sim
W x s
K s
K s
K s
K s
K s
K s
K s
K s
K s
K s
K s
K s
SPACING @ SNOWDRIFT = 4'-0" MAX.
T.O.S. ELEV. 0"
T.O.S. ELEV. 1'-3 5/8"
S1.2
2x6 SHEAR WALL - TYP.
- SEE SECTION FOR
ADDITIONAL INFORMATION
- ALL STUDS & SHEATHING TO
BE PRESSURE TREATED.
NOTES:
1.
2. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES
3. VARIATIONS IS TOP OF STEEL ELEVATION (T.O.S.) SHALL BE NOTES AS (+/- 0'-0")
4. PROVIDE CONT. L3x3x5/16" AT ALL ROOF EDGES AND OPENINGS. WHERE SLAB EDGE
ANGLE OVERLAPS BEAM FLANGE BY LESS THAN 2" PROVIDE 3/8" FLANGE EXTENSION
PLATE AND 3/8" STIFFENERS @ 48" o.c.
N
NOTES:
1.
2. SEE CHART BELOW FOR FLOOR SLAB AND/OR ROOF DECK TYPES
3. VARIATIONS IS TOP OF STEEL ELEVATION (T.O.S.) SHALL BE NOTES AS (+/- 0'-0")
4. PROVIDE CONT. L3x3x5/16" AT ALL ROOF EDGES AND OPENINGS. WHERE SLAB EDGE
ANGLE OVERLAPS BEAM FLANGE BY LESS THAN 2" PROVIDE 3/8" FLANGE EXTENSION
PLATE AND 3/8" STIFFENERS @ 48" o.c.
N
Bundle Stud Marker *B
Load Bearing Wall Marker L**-*
Symbol Legend
Shear Wall Marker S**-*
(2) Load Bearing Walls Marker 2L**-*
(2) Shear Walls Marker 2S**-*
(2) Load Bearing Walls Marker Staggered Studs
2L**-*-S
(2) Shear Walls Marker Staggered Studs
2S**-*-S
NOTES:
1.
2. MAXIMUM ROOF TRUSS SPACING 2'-0" U.N.O.
3. ALL WOOD-TO-WOOD CONNECTIONS TO BE MADE WITH APPLICABLE SIMPSON PRODUCT OR EQUAL.
4. ROOF CONSTRUCTION 3/4" SHEATHING, APA RATED @ 24" O.C.
N
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
S tru ct _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
Ro of
F ra m in g Pl an
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
S2.2
11.04.2026
BID
JA
C
K S
O N
T O
W N
S H
IP
M
U N
IC
IP
A L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
SCALE: 1/8" = 1'-0"S2.2
1 HIGH ROOF FRAMING PLAN
SCALE: 1/8" = 1'-0"
LOW ROOF FRAMING PLAN
SCALE: 1/8" = 1'-0"
SALT SHED ROOF FRAMING PLAN
Floor Schedule - Roof
TYPE DECK TYPE/GA/FINISH
MAX. BEAM
SPACING
1 1/2" Metal Roof Deck TYPE B - 20 GA - GALVANIZED 5'-6"
Floor Schedule - Roof
TYPE DECK TYPE/GA/FINISH
MAX. BEAM
SPACING
1 1/2" Metal Roof Deck TYPE B - 20 GA - GALVANIZED 5'-6"
LOW ROOF FRAMING TOS ELEVATION (U.N.O.): 598'-4 5/8"
HIGH ROOF FRAMING TOS ELEVATION (U.N.O.): 608'-4 7/8"
SALT SHED TRUSS BEARING ELEVATION (U.N.O.): 612'-0"
BEFORE PROCEEDING WITH THE WORK.
MLW8
M S
W
M S
W
M L
W
MLW8
MSW8
M L
W
M S
W
M L
W
M L
W
M L
W
S3.1
S3.1
S3.1
MSW8 MLW8
MP824
MP824
H S
S x x
/4 w
/8
P
L
W16x31 w/ 3/8" PL.
MP824 MP824
2L5x3-1/2x5/16LLBB
MP816 MP816
W8x15 w/ 3/8" PL.
MP816 MP816
H S
S x x
/1 w
/8
P
L
MP816
MP816
MP816
MP816
MP816
MP816
H S
S x x
/1 w
/8
P
L
H S
S x x
/1 w
/8
P
L
H S
S x x
/1 w
/8
P
L
MP816
MP816
HSS8x4x5/16 w/ 3/8" PL.
MP816MP816
MP816MP816MP816MP816
HSS8x4x5/16 w/ 3/8" PL.
HSS8x4x5/16 w/ 3/8" PL.
2L6x3-1/2x5/16LLBBs
2L6x3-1/2x5/16LLBBs
2L6x3-1/2x5/16LLBBs
MP816 MP816 MP816 MP816 MP816 MP816
HSS8x4x5/16s HSS8x4x5/16s HSS8x4x5/16s HSS8x4x5/16s
MP816 MP816 MP816 MP816
HSS8x4x5/16s
MP816MP816 MP816 MP816
2L5x3-1/2x5/16LLBB
MP816MP816
MP816 MP816
2L5x3-1/2x5/16LLBB
H S
S x x
/1 w
/8
P
L
MP816
MP816
W x w
/8
P L
W x w
/8
P L
W x w
/8
P L
MP1016
MP1016
MP1016
MP1016
MP1016
MP1016
W8x10 w/ 3/8" PL.W8x10 w/ 3/8" PL.
MP1016MP1016 MP1016 MP1016
NOTES:
1. LINTEL PLANS SHOW LOAD BEARING MASONRY OPENINGS (EXCEPT AT MEP/FP)
OPENINGS, AND OTHER SPECIAL CASES. REFER TO TYPICAL LINTEL SCHEDULES
FOR LINTELS AT ALL OTHER OPENINGS.
2. REFER TO TYPICAL LINTEL SCHEDULES FOR ADDITIONAL REQUIREMENTS.
3. PROVIDE 3/8" PLATE BELOW ALL W-SHAPE AND HSS LINTELS UNLESS NOTED
OTHERWISE. REFER TO TYPICAL DETAILS. NO PLATE REQUIRED FOR SINGLE OR
DOUBLE ANGLE LINTELS.
DENOTES MASONRY PILASTER. SEE SCHEDULE.
N
S3.1
S3.1
M S
W
B
M S
W
B
MSW12B
MLW12
EXTENT OF SHEAR WALL
40'-0"
MSW12A
M S
W
A
MLW12
HSS16x4x5/16 HSS8x4x5/16 HSS16x4x5/16 HSS16x4x5/16 HSS16x4x5/16 HSS8x4x5/16 HSS16x4x5/16 HSS8x4x5/16 HSS16x4x5/16
MP1224 MP1224 MP1216 MP1216 MP1224 MP1224 MP1224 MP1224 MP1224 MP1224 MP1216 MP1216 MP1224 MP1224 MP1224 MP1216 MP1224 MP1224
EXTENT OF SHEAR WALL
FULL LENGTH OF HIGH WALL
NOTES:
1. LINTEL PLANS SHOW LOAD BEARING MASONRY OPENINGS (EXCEPT AT MEP/FP)
OPENINGS, AND OTHER SPECIAL CASES. REFER TO TYPICAL LINTEL SCHEDULES
FOR LINTELS AT ALL OTHER OPENINGS.
2. REFER TO TYPICAL LINTEL SCHEDULES FOR ADDITIONAL REQUIREMENTS.
3. PROVIDE 3/8" PLATE BELOW ALL W-SHAPE AND HSS LINTELS UNLESS NOTED
OTHERWISE. REFER TO TYPICAL DETAILS. NO PLATE REQUIRED FOR SINGLE OR
DOUBLE ANGLE LINTELS.
DENOTES MASONRY PILASTER. SEE SCHEDULE.
WHERE PILASTERS ARE LOCATED IN EXIST. PORTIONS OF BUILDING,
PROVIDE A MIN. OF (2) COURSES OF SOLID GROUTED MASONRY BELOW
LINTEL BEARING.
N
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
S tru ct _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
Li nt el P la n
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
S2.3
11.04.2026
BID
JA
C
K S
O N
T O
W N
S H
IP
M
U N
IC
IP
A L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
SCALE: 1/8" = 1'-0"
MAIN BUILDING ADDITION LINTEL PLAN
SCALE: 1/8" = 1'-0"
STORAGE BUILDING LINTEL PLAN
CAULK & JOINT
FILLER (B.S.)
3000 PSI CONC GROUT
BUILDING PAPER
(1) #5 (TYP) GROUT
CORES SOLID AT REINF
NOTES:
1. DO NOT EXTEND MASONRY REINF. THROUGH CONTROL JOINTS
2. CONTRACTOR'S OPTION FOR TYPE OF JOINT
SYNTHETIC RUBBER
CONTROL JOINT
#5 BENT BAR
CAULK BOTH SIDES
SYNTHETIC RUBBER
CONTROL JOINT
BOND BEAM w/ (2) #5
BARS DO NOT
EXTEND BARS
THROUGH JOINT
CONT. HORIZ TRUSS TYPE
JOINT REINF - 9 GA GALV
METAL @ 16" o.c. VERT.
BOND BEAM w/
(2) #5 BARS
TYPICAL
WALL REINF
CMU WALL
ROOF
JOIST
METAL
ROOF
DECK
CLIP ANGLE 5x3x1/4" x 0'-8" LG. (LLV) EA
SIDE @ EA JOIST
(TYP)
1 1/2" CLR MIN
3/16 2" MIN
TYP
CONT. HORIZ TRUSS TYPE
JOINT REINF - 9 GA GALV
METAL @ 16" o.c. VERT.
CLIP L5x3x1/4"x0'-8" LG.
(LLV) EA SIDE @ 4'-0" o.c.
BOND BEAM w/
(2) #5 BARS
METAL ROOF
DECK
TYPICAL
WALL REINF
CMU WALL
L3x3x1/4" @ 4'-0" o.c.
/2
C L
R M
IN
3/16 3/16 2" MIN
NOTE:
1. L6x4x5/16 ANGLE HEADERS AT 5'-0" o.c. w/ L6x4x3/8x0'-6" CLIP ANGLES (LLV)
EACH END OF HEADER.
2. PROVIDE L6x4x5/16 EACH SIDE OF WALL AT EVERY OTHER 5'-0" HEADER
SPACING.
METAL
DECK
HEADER
3/16 4"
TYP
3/16 2"
TYP
3/16 4"
TYP
FLOOR OR ROOF
CONSTRUCTION
CMU WALL
CLIP L5x3x1/4" x
0'-6" LG. (LLV)
@ 48" o.c. (B.S.)
10 GA PL x 8" LG.
CONT. HORIZ TRUSS
TYPE JOINT REINF - 9
GA GALV METAL @
16" o.c. VERT.
BOND BEAM
w/ (2) #5 BARS
NOTCH BLOCK AT
REBAR LOC AND
GROUT SOLID
AT EACH BLOCKTYPICAL
WALL REINF
3/16
1/8 8
S E
E P
L A
N
S T
E E
L J
O
IS
T
JOIST & WALL
C L R
S E
E P
L A
N
S T
E E
L B
E A
M
BEAM & WALL
L1 1/2x1 1/2x1/4 @ 48" o.c. BETWEEN JOISTS, NOTE:
1. CLIP L6x4x5/16x0'-8" (LLV) EACH SIDE OF WALL AT 48" o.c.
3/16 3 @ 12
TYP
L3x3x1/4 w/ 1/4" CONN.
PLATE E.E .
45.00°
ROOF BEAML3x3x1/4
BETWEEN TWO
BEAMS
L6x4x5/16"
LENGTH TO MATCH THE
LEGTH OF WALL
- CONNECT WITH 1/2" DIA
EPOXY ANCHOR (2)…