This mechanical drawings document provides comprehensive technical specifications and details for the proposed addition and renovation to the Jackson Township Municipal Center located at 439 Roths Church Road, Spring Grove, Pennsylvania 17362. The project scope includes HVAC system design with multiple rooftop units (RTU-1, RTU-2, RTU-3), make-up air units (MAU-1 through MAU-5), gas-fired unit heaters, electric baseboard heaters, exhaust fans, and a packaged terminal air conditioner. The mechanical work encompasses ductwork design and installation across the first floor and storage garage, with detailed schedules for diffusers, registers, grilles, and control systems. The contract time is 400 calendar days from the Notice to Proceed, with bids due by 1:00 PM EST on Tuesday, December 8, 2026, and contract awards scheduled for January 4, 2027. A pre-bid conference is planned for Tuesday, November 10, 2026, at 10:00 AM EST on-site. Bidding documents became available November 4, 2026, via the PennBid Program at no cost.
The mechanical contract requires compliance with the International Mechanical Code, SMACNA and ASHRAE standards, and Pennsylvania's Prevailing Wage Act (Act 442). All contractors must provide a bid bond or certified check equal to 10% of the maximum bid and demonstrate qualifications to perform the work. Key equipment specifications include three gas-fired rooftop units ranging from 1,200 to 1,600 CFM supply air capacity, five make-up air units with LP gas heating and variable speed drives, multiple exhaust fans with capacities up to 3,800 CFM, and specialized equipment such as washdown-rated electric unit heaters for the wash bay and a hose reel-mounted exhaust fan for fume extraction. The contractor is responsible for all labor, materials, offsets, elbows, fittings, hangers, accessories, cutting, patching, lintels, and housekeeping pads, with no additional costs to the owner. All equipment and materials must be installed per manufacturer specifications and current applicable codes and regulations.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE:
NOT ALL ABBREVIATIONS AND SYMBOLS INDICATED
MAY APPEAR ON THESE CONTRACT DRAWINGS.
THIS IS FOR REFERENCE ONLY.
ABBREVIATIONS
A/C
AFF
AFG
AMB
AMP
AP
APROX
ARR
ATC
AUTO
AUX
AVG
BF
BHP
BOD
BOP
BOT
BP
BSMT
BTU
CA
CAP
CF
CFM
CL
CO
COL
CONC
CONN
CONT
CTR
D
DB
DDC
DEG
DET
DIA
DISC
DN
DWG
EA
EAT
EER
EFF
EJ
EL
ELEC
ENT
ESP
EVAP
EWT
EXH
EXP
EXST
EXT
F&T
FC
FDW
FLA
FLR
FO
FPM
FPS
FS
FT
GA
GAL
GALV
GND
GPH
GPM
GR
HD
HG
HGT
HMD
HORIZ
HP
HTD
HTR
AIR CONDITIONING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMBIENT
AMPERE
ACCESS PANEL
APPROXIMATE
ARRANGEMENT
AUTOMATIC TEMPERATURE CONTROL
AUTOMATIC
AUXILIARY
AVERAGE
BOILER FEED
BRAKE HORSEPOWER
BOTTOM OF DUCT
BOTTOM OF PIPE
BOTTOM
BACK PRESSURE
BASEMENT
BRITISH THERMAL UNIT
COMPRESSED AIR
CAPACITY
CUBIC FOOT (FEET)
CUBIC FOOT (FEET) PER MINUTE
CENTER LINE
CLEANOUT
COLUMN
CONCRETE OR CONCENTRIC
CONNECT OR CONNECTION
CONTINUATION
CENTER
DRAIN OR DEEP
DRY BULB
DIRECT DIGITAL CONTROL
DEGREE
DETAIL
DIAMETER
DISCONNECT
DOWN
DRAWING
EACH
ENTERING AIR TEMPERATURE
ENERGY EFFICIENCY RATIO
EFFICIENCY
EXPANSION JOINT
ELEVATION
ELECTRICAL
ENTERING
EXTERNAL STATIC PRESSURE
EVAPORATOR
ENTERING WATER TEMPERATURE
EXHAUST
EXPANSION
EXISTING
EXTERNAL
FLOAT & THERMOSTATIC
FLEXIBLE CONNECTION
FEED WATER
FULL LOAD AMPS
FLOOR
FUEL OIL
FOOT (FEET) PER MINUTE
FOOT (FEET) PER SECOND
FLOW SWITCH
FOOT (FEET)
GAUGE
GALLONS
GALVANIZED
GROUND
GALLONS PER HOUR
GALLONS PER MINUTE
GRAIN
HEAD
HOT GAS
HEIGHT
HUMIDITY
HORIZONTAL
HORSEPOWER
HEATED
HEATER
Hz
INSUL
INTL
LAT
LBS
LIN
LP
LRA
LVL
LVR
LWT
MAN
MAX
MBH
MIN
MOD
MTD
MU
NA
NC
NEG
NIC
NO
NTS
OA
OED
OFCI
OV
PCR
PD
PG
PL
PNEU
PRESS
PROP
PSIG
QTY
REF
REQD
REV
RL
RM
RS
RTN
S
SCH
SD
SEC
SENS
SEP
SEQ
SER
SERV
SHT
SOL
SP
SPLY
SS
STL
SUCT
TD
TEMP
TH
THK
TSP
TYP.
UON
V
VAC
VAV
VB
VEL
VERT
VIB
VOL
VSD
VTR
W
WB
WMS
HERTZ
INSULATION
INTERNAL
LEAVING AIR TEMPERATURE
POUNDS
LINEAL
LOW PRESSURE
LOCKED ROTOR AMPS
LEVEL
LOUVER
LEAVING WATER TEMPERATURE
MANUAL
MAXIMUM
THOUSAND BRITISH THERMAL UNITS PER HOUR
MINIMUM
MODEL
MOUNTED
MAKEUP
NOT APPLICABLE
NORMALLY CLOSED
NEGATIVE
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
OUTSIDE AIR
OPEN END DUCT
OWNER FURNISHED CONTRACTOR INSTALLED
OUTLET VELOCITY
PUMPED CONDENSATE RETURN
PRESSURE DROP
RESSURE GAUGE
PLATE
PNEUMATIC
PRESSURE
PROPELLER
POUNDS PER SQUARE INCH GAUGE
QUANTITY
REFERENCE
REQUIRED
REVISION
REFRIGERANT LIQUID
ROOM
REFRIGERANT SUCTION
RETURN
SWITCH
SCHEDULE
SMOKE DAMPER
SECONDARY SECONDS
SENSIBLE
SEPARATE
SEQUENCE
SERIES
SERVICE
SHEET
SOLENOID
STATIC PRESSURE
SUPPLY
STAINLESS STEEL
STEEL
SUCTION
TEMPERATURE DIFFERENTIAL
TEMPERATURE
THERMOMETER
THICK
TOTAL STATIC PRESSURE
TYPICAL
UNLESS OTHERWISE NOTED
VENT OR VOLT
VACUUM
VARIABLE AIR VOLUME
VACUUM BREAKER
VELOCITY
VERTICAL
VIBRATION
VOLUME
VARIABLE SPEED DRIVE
VENT THRU ROOF
WATT, WIDTH OR WIDE
WET BULB
WIRE MESH SCREEN
SYMBOL DESCRIPTION
SHUT-OFF VALVE
GLOBE VALVE
CHECK VALVE
FLOW SETTER
ANGLE GATE VALVE
RELIEF OR SAFETY VALVE
SOLENOID VALVE
BUTTERYFLY VALVE
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
PRESSURE REDUCING VALVE
UNION
STRAINER W/BLOW-OFF & CAP
PIPE GUIDE
PIPE ANCHOR
FLEXIBLE CONNECTOR
EXPANSION JOINT
THERMOMETER
PRESSURE GAUGE W/COCK
AUTOMATIC AIR VENT
MANUAL AIR VENT
DIRECTION OF FLOW
DIRECTION OF SLOPE
CONCENTRIC REDUCER
ECCENTRIC REDUCER
PIPE UP
PIPE DOWN
PIPE THROUGH
TOP TAKE-OFF
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW WORK
BOILER FEED WATER
COMPRESSED AIR
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CONDENSATE DRAIN OR DRAIN
FUEL OIL RETURN
FUEL OIL SUPPLY
FUEL OIL TANK VENT
HOT GAS
HIGH PRESSURE CONDENSATE RETURN
HIGH PRESSURE STEAM SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
LOW PRESSURE CONDENSATE RETURN
LOW PRESSURE STEAM SUPPLY
MEDIUM PRESSURE CONDENSATE RETURN
MEDIUM PRESSURE STEAM SUPPLY
PUMPED CONSENSATE RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
VENT LINE
PIPING SYMBOLS
A
M
36x14Ø
UP DN
24x36
DOUBLE LINE
ROUND DUCT UP
45°ELBOW (NO VANES)
DIRECTION OF FLOW
ROUND DUCT DOWN
36x14Ø
UP DN
24x36
SINGLE LINE
NEW WORK
SUPPLY AIR DOWN
SUPPLY AIR UP
EXISTING TO BE REMOVED
EXISTING TO REMAIN
DESCRIPTION
4-WAY DIFFUSER
EXHAUST OR RETURN GRILLE
FLAT OVAL DUCT SIZE
(FIRST FIGURE-SIDE SHOWN)
DUCT INCLINED RISE OR DROP
IN DIRECTION OF FLOW
90° ELBOW WITH
TURNING VANES
SUPPLY OR RETURN BRANCH CONNECTION
SUPPLY BRANCH WITH SPIN
COLLAR CONNECTION
LATERAL CONNECTION
ROUND DUCTWORK
CONICAL TEE ROUND DUCTWORK
EXHAUST OR RETURN AIR UP
EXHAUST OR RETURN AIR DOWN
DUCTWORK SYMBOLS
3-WAY, 2-WAY, OR 1-WAY GRILLE
GENERAL NOTES:
RECTANGULAR DUCT SIZE SHOWN IN
INCHES (FIRST FIGURE-SIDE SHOWN)
DUCT SMOKE DETECTOR SDT
MOTORIZED DAMPER
BACK DRAFT DAMPER
VOLUME DAMPER
MD
FLEXIBLE DUCTWORK
(DUCT PRESSURE CLASS)
SMOKE DAMPER WITH ACCESS DOOR
FIRE DAMPER WITH ACCESS DOOR
COMBINATION FIRE & SMOKE
DAMPER WITH ACCESS DOOR
MD
BDD BDD
BYPASS DAMPER
BD BD
STATIC PRESSURE SENSOR
SP SP
POINT OF CONNECTION-NEW TO EXISTING
H HUMIDISTAT
DRAWING NOTE SYMBOL
REVISION SYMBOL
# SECTION NUMBER
# DETAIL OR SECTION NUMBER
DIRECTION OF VIEW
MISCELLANEOUS SYMBOLS
T THERMOSTAT
DRAWING FROM WHICH SECTION
OR DETAIL IS TAKEN
DRAWING ON WHICH SECTION
OR DETAIL IS SHOWN
S SWITCH
POINT OF DEMOLITION CONCLUSION
CWS
V
LPR
LPS
PCR
MPS
RS
RL
MPR
FOR
FOS
HG
FOV
HPR
HPS
HWR
HWS
CD
CHWR
CA
BF
CHWS
CWR
VFD (VARIABLE FREQUENCY DRIVE)
1. CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE RELATION OF PIPING,
DUCTWORK, CONNECTIONS, AND EQUIPMENT. THE DRAWINGS DO NOT INDICATE ALL
OFFSETS, ELBOWS, AND FITTINGS THAT MAY BE REQUIRED. THEREFORE, THE
CONTRACTOR SHALL CAREFULLY INVESTIGATE THE STRUCTURAL AND FINISH
CONDITIONS AFFECTING THE WORK AND ACTUAL EQUIPMENT PROVIDED. THE
CONTRACTOR SHALL FURNISH ALL OFFSETS, ELBOWS, FITTINGS, HANGERS, AND
ACCESSORIES AS MAY BE REQUIRED TO MEET THESE CONDITIONS AT NO ADDITIONAL
COST TO THE OWNER
2. INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH THE
CURRENTLY ADOPTED INTERNATIONAL MECHANICAL CODE, ALL PERTINENT CODES,
LAWS, ORDINANCES, REGULATIONS, AND RESPECTIVE MANUFACTURER'S WRITTEN
INSTRUCTIONS.
3. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED IN STRICT ACCORDANCE
WITH SMACNA AND ASHRAE STANDARDS.
4. COORDINATE HVAC WORK WITH THE WORK OF ALL OTHER CONTRACTORS AND
OWNER.
5. THE HVAC CONTRACTOR SHALL ARRANGE THE PROGRESS OF THEIR WORK SO AS TO
CONFORM TO THE PROGRESS OF THE TRADES AND SHALL COMPLETE THE ENTIRE
INSTALLATION AS SOON AS THE CONDITION OF THE PROJECT WILL PERMIT.
6. ALL ITEMS OF LABOR, MATERIAL, AND EQUIPMENT NOT SPECIFICALLLY DESCRIBED
HEREIN NOR DETAILED ON THE DRAWINGS BUT INCIDENTAL TO OR NECESSARY FOR
THE COMPLETION OF THE WORK, SHALL BE CONSIDERED AS INCLUDED WITHOUT
EXTRA COST.
7. COORDINATE EXACT LOCATIONS OF DIFFUSERS/DUCTWORK WITH LIGHTS,
SPRINKLERS, AND CEILING WITH REFLECTED CEILING PLAN AND ARCHITECT.
8. PROVIDE INDIVIDUAL VOLUME DAMPERS FOR BALANCING ON ALL SUPPLY, RETURN,
RELIEF, AND EXHAUST MAIN BRANCH AND BRANCH TAKE-OFFS. LOCATE VOLUME
DAMPER AS CLOSE AS POSSSIBLE TO TAKE OFF POINTS. PROVIDE CABLE CONTROL
VOLUME DAMPERS FOR ALL INACCESSIBLE CEILINGS.
9. THE CONTRACTOR SHALL PROVIDE ADEQUATE CLEARANCE FOR ALL UNIT CONTROLS.
10. MOUNT ALL SPACE SENSING DEVICES AT 48" AFF, COORDINATE ALL LOCATIONS WITH
ARCHITECT PRIOR TO ROUGH-IN AND INSTALLATION.
11. PROVIDE PROTECTION FOR ALL PENETRATIONS OF FIRE RESISTANCE RATED
ASSEMBLIES IN ACCORDANCE WITH THE REQUIREMENTS OF THE CURRENTLY
ADOPTED INTERNATIONAL BUILDING CODE.
12. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING TYPES. PROVIDE
APPROPRIATE FRAMES AND MOUNTING HARDWARE FOR ALL AIR DEVICES.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL MOUNTING
DETAILS AND REQUIREMENTS WITH CEILING CONTRACTOR.
13. ROUTE EQUIPMENT DRAIN PIPING TO FLOOR DRAINS TO PREVENT TRIPPING HAZARDS.
DO NOT INSTALL PIPING ON FLOOR IN ANY EQUIPMENT ACCESS AISLES.
14. PROVIDE DOUBLE WALL INSULATED ACCESS DOORS IN ALL INSULATED DUCTWORK
AND SINGLE WALL ACCESS DOORS IN UN-INSULATED DUCTWORK FOR FIRE DAMPER,
SMOKE DAMPER, AND REHEAT COIL INSPECTION AND SERVICE.
15. NO PIPING OR DUCTWORK FOREIGN TO ELECTRICAL, DATA, OR ELEVATOR MACHINE
ROOMS IS PERMITTED TO BE INSTALLED IN THESE SPACES.
16. ALL INDOOR FLOOR MOUNTED MECHANICAL EQUIPMENT SHALL BE MOUNTED ON 4"
MINIMUM HOUSEKEEPING PAD.
17. PROVIDED ALL PIPING, VALVING & EQUIPMENT SHOWN ON FLOW DIAGRAMS AND
DETAILS EVEN IF NOT SHOWN ON FLOOR PLANS.
18. PROVIDE PIPING TO ALL EQUIPMENT REQUIRING WATER SERVICE AND DUCTWORK TO
EVERY AIR DEVICE EVEN IF NOT SHOWN ON PLANS.
19. ALL PIPING AND DUCTWORK TO BE CONCEALED IN CEILINGS AND WALLS, EXCEPT IN
MECHANICAL ROOMS, SPACES WITHOUT CEILINGS, OR WHERE NOTED OTHERWISE.
20. PROVIDE FIRE DAMPERS AND SMOKE DAMPERS AS INDICATED ON FLOOR PLANS, AND
WHERE REQUIRED BY APPLICABLE CODES AT RATED CONSTRUCTION.
21. EC SHALL FURNISH DUCT SMOKE DETECTORS, MC SHALL INSTALL THEM AND A.T.C.
CONTRACTOR SHALL WIRE THEM TO AIR HANDLING UNIT STARTERS / VFD'S. EC TO
WIRE DUCT SMOKE DETECTORS TO FIRE ALARM SYSTEM.
22. HVAC CONTRACTOR SHALL PROVIDE SMOKE DAMPERS. EC SHALL WIRE THEM TO FIRE
ALARM SYSTEM.
23. WHERE PLENUM RETURN AIR SYSTEM ARE USED, PROVIDE ONLY MATERIALS IN THE
CEILING THAT ARE APPROVED FOR AIR PLENUM USE.
24. PROVIDE ACCESS PANELS FOR ALL VALVES AND DAMPERS ABOVE INACCESSIBLE
CEILINGS. ACCESS PANEL TO BE A MINIMUM OF 12"X12". COORDINATE FINAL LOCATION
WITH REFLECTED CEILING PLAN.
25. HVAC CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING IN EXISTING BUILDING.
HVAC CONTRACTOR TO PROVIDE NEW LINTELS AT WALL PENETRATIONS; REFER TO
STRUCTURAL DRAWINGS FOR LINTEL SPECIFICATIONS AND SIZES.
26. HVAC CONTRACTOR TO PROVIDE WOOD BLOCKING FOR ALL ROOF CURBS IN BOTH
EXISTING AND NEW CONSTRUCTION; COORDINATE WITH GC.
27. HVAC CONTRACTOR TO PROVIDE HOUSEKEEPING PADS FOR ALL EQUIPMENT.
28. THE EXISTING CONDITIONS ON THESE DRAWINGS ARE FROM HISTORICAL DOCUMENTS.
CHECK AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT THE SITE PRIOR TO
COMMENCING WORK. WHERE DISCREPANCY EXISTS, NOTIFY ENGINEER IN WRITING.
29. CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE IN WRITING ALL MATERIALS,
EQUIPMENT, AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF
ACCEPTANCE BY OWNER.
30. THE MECHANICAL CONTRACTOR SHALL SUBMIT TO THE ARCHITECT/ENGINEER AS-BUILT
DRAWINGS AND OPERATION AND MAINTENANCE MANUALS INCLUDING ALL NAMEPLATE
DATA, WIRING DIAGRAMS, MAINTENANCE INSTRUCTIONS, AND PARTS LIST UPON
PROJECT COMPLETION.
31. MAINTAIN A CLEAN AND SAFE WORK AREA AT ALL TIMES. ALL SAFETY PROCEDURES
AND ENFORCEMENT IS THE RESPONSIBILITY OF THE CONTRACTOR; CONFORM TO ALL
OSHA STANDARDS.
32. UNLESS SPECIFICALLY STATED OTHERWISE, OR APPROVED BY THE ARCHITECT IN
ADVANCE, NO EXPOSED CONDUIT OR PIPING WILL BE ACCEPTABLE IN NEW
CONSTRUCTION IN FINISHED SPACES AND NO CONDUIT OR PIPING OF ANY KIND WILL BE
PERMITTED IN THE CAVITY.
RUNOUT SCHEDULE
FLEXIBLE DUCT
SCHEDULE
0.0 - 3.0
3.1 - 6.5
6.6 - 11.5
11.6 - 18.5
18.6 - 40.0
40.1 - 69.0
69.1 - 122.0
3/4"
1"
1 1/4"
1 1/2"
2"
2-1/2"
3"
GPM PIPE SIZE
CFM
UP TO 125
126 TO 280
281 TO 380
381 TO 550
551 TO 750
DUCT DIAMETER
6"
8"
10"
12"
14"
122.1 - 255.0 4"
255.1 - 750.0 6"
S*
AIR TERMINAL DESIGNATION
AIR TERMINAL NECK SIZE
AIR TERMINAL CFM
DOUBLE-WALL SPIRAL DUCT
(COLOR SHALL BE SELECTED BY ARCHITECT)
MEDIUM PRESSURE DUCTWORK
D
D A T E
S H E E T a rc h it e c tu re w o rk s h o p in c o n e s o u th r a ilr o a d s tr e e t h a n o v r n n s y lv a n ia p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
M E
P _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
M
EC
H
AN
IC
AL
IN
FO
RM
AT
IO
N
S H
EE
T
P R
O P
O S
E D
A
D
IT
IO
N
R E
N O
V A
T
IO
N
M0.0
11.04.2026
BID
J A
C K
S O
N T
O W
N S
H
IP
M U
N
IC
IP
A
L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
S P
R
IN
G G
R O
V
N
N S
Y
LV
A N
IA
MECHANICAL DRAWING LIST
M0.0 MECHANICAL INFORMATION SHEET
M1.0 FIRST FLOOR PLAN - MECHANICAL
M1.1 STORAGE GARAGE PLANS - MECHANICAL
M2.1 ROOF PLAN - MECHANICAL DUCT
M4.0 MECHANICAL DETAILS
M5.0 MECHANICAL SCHEDULES
MD1.1 FIRST FLOOR PLAN - DEMOLITION - MECHANICAL
tag rev date revision note
(EX)UH
(EX)UH
UH-1
(EX)EA (EX)EA (EX)EA
14x14
20x28 20x20
18x2018x20 x x x x x
REPAIR GARAGE
REPAIR GARAGE
ARCHIVE
HALL
MEETING ROOM
WOMEN
MEN
STORAGE
OFFICE
LOBBY
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HALL
CONFERENCE
BREAK ROOM
MEN
WOMEN
STORAGE
MEN
SHOWER
WOMEN
JANITOR
TELE-COM
OFFICE
HALL
WORK ROOM
10ø10ø
10ø10ø
10ø
10ø
S-1
250 CFM
(TYP. OF 6)
RA-1
750 CFM
(TYP. OF 2)
S-3
1,000 CFM
(TYP. OF 5)
S-3
1,700 CFM
(TYP. OF 2)
x x x x
SA-2
650 CFM
(TYP. OF 4)
UH-3
UH-4
EBB-1
EBB-2
EBB-3
20x14
E-1
70 CFM
E-1
60 CFM
E-1
70 CFM
x
S-1
240 CFM
S-1
130 CFM
S-2
90 CFM
E-1
75 CFM
S-1
130 CFM
S-1
130 CFM
S-1
130 CFM
S-1
130 CFM
S-1
25 CFM
S-1
25 CFM
S-2
80 CFM
E-1
75 CFM
E-1
50 CFM R-1
240 CFM
R-1
130 CFMR-1
130 CFM
R-1
130 CFM
R-1
130 CFM
R-1
130 CFM
R-1
130 CFM
S-1
250 CFM
S-1
250 CFM
S-1
100 CFM
S-1
25 CFM
S-1
25 CFM
S-1
100 CFM
S-1
150 CFM
S-1
125 CFM
S-1
225 CFM
S-1
350 CFM
R-1
410 CFM
E-1
75 CFM
E-1
75 CFM
R-1
100 CFM
R-1
150 CFM
R-1
125 CFM
R-1
225 CFM
R-1
350 CFM
x
10x6
6x6
6x6
8x68x8
8x6
8x128x12
12x12
14x128x12 8x12 x
S-2
90 CFM
x
8x8
8x8 10x8 10x810x10
10x10 x
10x1224x14 x
8x8
12x8
14x814x10 x
24x16
2 2
PTAC-1
EWH-1
20x20
6"Ø EA UP
THRU ROOF
VEF-1
6ø
T
T
T
T
T
(RTU-2)
(RTU-3)T
10x10
4ø ø ø ø
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
M E
P _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
FI
RS
T
FL
OO
R
PL
AN
M
EC
H
AN
IC
AL
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
M1.0
11.04.2026
BID
J A
C K
S O
N T
O W
N S
H
IP
M U
N
IC
IP
A
L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
NOTES BY SYMBOL: #
(THIS DRAWING ONLY)
1 TERMINATE EXHAUST DUCTWORK +/- 1'-6" BELOW ROOF DECK WITH
WIRE MESH SCREEN.
SUPPLY AND RETURN DUCTWORK FROM RTU ON ROOF ABOVE.
SUPPLY DUCTWORK FROM MAU UN ROOF ABOVE.
MAU-2 CONTROL PANEL, FINAL LOCATION TO BE FIELD VERIFIED WITH
OWNER.
MAU-3 AND VEF-1 CONTROL PANELS, FINAL LOCATION TO BE FIELD
VERIFIED WITH OWNER.
PROVIDE FUME-A-VENT, OR APPROVED EQUAL, MODEL HRS-3-0635-W
6"x35' SPRING HOSE REEL, MODEL DIRECT MOUNT HOSE REEL BLOWER
(VEF-1), MODEL TPA-03-0606-P 6" SOFT RUBBER TAILPIPE ADAPTER WITH
SPRING CLAMP & PLUG, AND MODEL CBS-2-230-18 FAN CONTROL PANEL.
MOUNT HOSE REEL AND FAN ON WALL, FINAL LOCATION TO BE FIELD
VERIFIED WITH OWNER. SEE EXHAUST FAN SCHEDULE FOR VEF-1
REQUIREMENTS. FAN SHALL RUN CONTINUOUSLY DURING OCCUPIED
HOURS.
EXHAUST DUCTWORK UP TO EXHAUST FAN ON ROOF ABOVE.
UNIT HEATER VENT UP THRU ROOF.
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - MECHANICAL DUCT1
tag rev date revision note
STORAGE
WASH BAY
UH-6
UH-7
WDUH-1
WDUH-2
UH-5
S-3
1,265 CFM
(TYP. OF 3
SIDES)
S-3
700 CFM
(TYP. OF
2 SIDES)
EF-4EF-5
L O
W R
O O
F
H
IG
H R
O O
F ø ø
4ø
MAU-4MAU-5
4" UNIT
HEATER
VENT
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
M E
P _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
ST
O
RA
G
E G
AR
AG
E
PL
AN
S
M
EC
H
AN
IC
AL
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
M1.1
11.04.2026
BID
J A
C K
S O
N T
O W
N S
H
IP
M U
N
IC
IP
A
L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
NOTES BY SYMBOL: #
(THIS DRAWING ONLY)
1 INSTALL SIDEWALL UPBLAST FAN +/- 20'-0" AFF, TERMINATE WITH
STAINLESS STEEL DUCTWORK +/- 6" INSIDE OF WALL WITH STAINLESS
STEEL WIRE MESH SCREEN.
DUCTWORK AND REGISTERS IN WASH BAY SHALL BE STAINLESS STEEL.
INSTALL SIDEWALL EXHAUST FAN +/- 20'-0" AFF.
UNIT HEATER VENT UP THRU ROOF.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - MECHANICAL1
SCALE: 1/8" = 1'-0"
ROOF PLAN - MECHANICAL2
tag rev date revision note
MAU-1
(EX)EF (EX)EF (EX)EF
RTU-1
MAU-2
EF-2
EF-3
MAU-3
RTU-2
RTU-3
EF-1
6"Ø EXHAUST,
TERMINATE WITH
NO LOSS STACK
EXISTING UNIT
HEATER VENT
EXISTING UNIT
HEATER VENT
4" UNIT
HEATER
VENT
4" UNIT
HEATER
VENT
3" UNIT
HEATER
VENT
3" UNIT
HEATER
VENT
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
M E
P _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
RO
OF
P
LA
N
M
EC
H
AN
IC
AL
D U
CT
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
M2.1
11.04.2026
BID
J A
C K
S O
N T
O W
N S
H
IP
M U
N
IC
IP
A
L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS.
SCALE: 1/8" = 1'-0"
ROOF PLAN - MECHANICAL1
BAND OF SAME SIZE
AS HANGER STRAP
HANGER PER SCHEDULE
LOAD RATED FASTENER
SECURE WIRE
HANGER STRAPS
PER SCHEDULE
SCREWS
HANGER STRAPS
OR ROD PER
SCHEDULE
STEEL ANGLE
BOLTS/NUTS
RECTANGULAR DUCT HANGER SCHEDULE
MAXIMUM
HALF OF
DUCT
PERIMETER
PAIR AT 10' SPACING PAIR AT 8' SPACING PAIR AT 5' SPACING PAIR AT 14' SPACING
STRAP WIRE / ROD STRAP WIRE / ROD STRAP WIRE / ROD STRAP WIRE / ROD
P/2 = 30" 1" x 22 GA 10 GA (0.135") 1" x 22 GA 10 GA (0.135") 1" x 22 GA 12 GA (0.106") 1" x 22 GA 12 GA (0.106")
P/2 = 72" 1" x 18 GA 3/8" 1" x 20 GA 1/4" 1" x 22 GA 1/4" 1" x 22 GA 1/4"
P/2 = 96" 1" x 16 GA 3/8" 1" x 18 GA 3/8" 1" x 20 GA 3/8" 1" x 22 GA 1/4"
P/2 = 120" 11/2" x 16 GA 1/2" 1" x 16 GA 3/8" 1" x 18 GA 3/8" 1" x 20 GA 1/4"
P/2 = 168" 11/2" x 16 GA 1/2" 11/2" x 16 GA 1/2" 1" x 16 GA 3/8" 1" x 18 GA 3/8"
P/2 = 192" - 1/2" 11/2" x 16 GA 1/2" 1" x 16 GA 3/8" 1" x 16 GA 3/8"
P/2 = 193"+ SPECIAL ANALYSIS REQUIRED
NOTES: TAKEN FROM SMACNA DUCT DESIGN TABLE 5-1. FOLLOW ALL SMACNA REQUIREMENTS DURING INSTALLATION.
ROUND DUCT HANGER SCHEDULE
DIAMETER
MAXIMUM
SPACING
WIRE
DIAMETER
ROD STRAP
10" 12' (1) 12 GA 1/4" 1" x 22 GA
11-18" 12'
(2) 12 GA or (1)
8 GA
1/4" 1" x 22 GA
19-24" 12' (2) 10 GA 1/4" 1" x 22 GA
25-36" 12' (2) 8 GA 3/8" 1" x 20 GA
37-50" 12' N/A (2) 3/8" (2) 1" x 20 GA
51-60" 12' N/A (2) 3/8" (2) 1" x 18 GA
61-84" 12' N/A (2) 3/8" (2) 1" x 16 GA
85-96" 12' N/A (2) 1/2" (2) 11/2" x 16 GA
NOTES: TAKEN FROM SMACNA DUCT DESIGN TABLE 5-2. FOLLOW ALL SMACNA
REQUIREMENTS DURING INSTALLATION.
DUCT HANGER DETAIL
NO SCALE
W R
RETURN OR
EXHAUST
DUCT
AIR FLOW
VOLUME DAMPER
RETURN OR
EXHAUST DUCT
NOTE: L = W/4, MIN 4"
SQUARE OR RECTANGULAR BOOT TAP
L
W
SQUARE OR RECTANGULAR BOOT TAP
MAINS, SUB
MAINS, & BRANCH
MAINS
45°
SUPPLY DUCT
AIR FLOW
VOLUME DAMPER
SUPPLY DUCT
NOTE: L = W/4, MIN 4"
L
W45°
A= W3xD3 W2xD2+W3xD3
B= W2xD2
W2xD2+W3xD3
AxD1
AIR
FLOW
W1xD1
BxD1
W2xD2
AIR FLOW
W3xD3
DOUBLE SIDE SINGLE SIDE
TRANSITIONS
ROUND CONICAL TAP
SUPPLY
DUCT
AIR
FLOW
VOLUME DAMPER
SUPPLY DUCT
NOTE: L = W/4, MIN 4"
L
W45°
30°
15°
NOTE: R=W
RADIUS
DOUBLE-
THICKNESS
TURNING VANES
VANED
ELBOWS
NOTE:
PROVIDE VOLUME DAMPER IN
ALL BRANCH DUCTS.
ROUND CONNECTION
BOOT WITH COLLAR
DIFFUSER
FLEX DUCT BRANCH
DIA. NOTED ON PLAN
CEILING
RIGID DUCT SHALL BE
SAME SIZE AS FLEX
PROVIDE SADDLES
UNDER DUCT TO
PREVENT COMPRESSING
SUPPORT STRAP: MAX.
2'-0" ON CENTER;
SECURE TO DUCT
INSULATE RIGID DUCT
FROM VOLUME DAMPER
TO FLEX CONNECTION
TAKEOFF FITTING
WITH DAMPER, SEAL
AT CONNECTION TO
MAIN AND TAPE
VOLUME DAMPER
CONNECT FLEX DUCT
TO DUCT COLLARS
WITH STAINLESS
STEEL CLAMPING
RINGS WITH SCREW
ADJUSTERS
SUPPLY AIR DUCT
OPPOSED BLADE DAMPER
RIGID METAL DUCT
45° TAKE-OFF BOOT
CEILING
CEILING
LCD
LRR
SQUARE TO ROUND ADAPTER
OPPOSED BLADE DAMPER
RIGID METAL DUCT
45° SQUARE TO ROUND
TRANSITION TAKE-OFF BOOT
SUPPLY AIR DUCT
MANUAL DAMPER
MANUAL DAMPER
HEATING/COOLING UNIT
ECONOMIZER
RELIEF AIR
FLEXIBLE
CONNECTION
CURB WITH RIGID INSULATION
IN VOID SPACE MINIMUM 2" THICK
ANGLE IRON FRAMED OPENING
DUCTWORKACOUSTICAL CAULK
AROUND ALL OPENINGS
NOTE: VERIFY UNIT CONFIGURATION WITH MFR.
PIPING OR ELECTRICAL CONDUIT
INSIDE CURB TO UNIT
CONDENSATE DRAIN WITH TRAP
TO SPILL ON ROOF
2 LAYERS 3" RIGID FIBERGLASS
INSULATION WITH 2 LAYERS OF
WATER RESISTANT 1/2" DRYWALL
ALTERNATE LAYERS OF
INSULATION AND DRYWALL.
REMOVABLE MOTOR
DOME
FAN
WHEEL
INLET
VENTURI
EXHAUST DUCT
18" HIGH INSULATED ROOF CURB
NEOPRENE GASKET
BIRDSCREEN
MOTOR
FOR DETAILS SEE ARCH. DWGS.
ROOF MEMBRANE
ROOF INSULATION
METAL DECK
ANGLE FRAMING
ADJUSTABLE PITCH
MOTOR SHEAVE
VIBRATION
ELIMINATOR
BACKDRAFT OR AUTOMATIC
DAMPER (SEE ATC
DIAGRAMS)
PRESSURE TREATED
WOOD BLOCKING
WALL
STAINLESS STEEL
WIRE MESH SCREEN
SPUN ALUMINUM WALL
EXHAUSTER HOUSING
BACKDRAFT
DAMPER
x x x x x x x x x x
STAINLESS STEEL
DUCT EXTENSION
EXHAUST AIR
REAR
GUARD
WALL
SLEEVE
ANGLE
SUPPORT
WALL
SHUTTER
WALL
OUTSIDE
PROPELLOR
FAN
MOVABLE PERIMETER
ANGLE FRAME
AIR
FLOW
WEATHERHOOD
WIRE MESH
SCREEN
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
M E
P _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
M
EC
H
AN
IC
AL
D
ET
AI
LS
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
M4.0
11.04.2026
BID
J A
C K
S O
N T
O W
N S
H
IP
M U
N
IC
IP
A
L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A tag rev date revision note
SCALE: NO SCALE
TYPICAL DUCT CONNECTION DETAIL
SCALE: NO SCALE
FLEXIBLE DUCT CONNECTION DETAIL
SCALE: NO SCALE
RIGID DUCT CONNECTION DETAIL
SCALE: NO SCALE
ROOFTOP UNIT CURB DETAIL
SCALE: NO SCALE
DOWNBLAST EXHAUST FAN DETAIL
SCALE: NO SCALE
WASH BAY WALL EXHAUSTER DETAIL
SCALE: NO SCALE
WALL PROPELLOR FAN MOUNTING DETAIL
GAS FIRED ROOFTOP UNIT SCHEDULE
TAG MANUFACTURER MODEL NO. BLOWER
SUPPLY
AIR CFM
O.A.
CFM
V/P/Hz MCA MOCP ESP (IN. W.C.)
COOLING DATA CONDENSING SECTION DATA GAS HEATING DATA
OPER. WEIGHT
(LBS.)
REMARKS
TOTAL MBH SENS MBH
ENT. AIR
DB/WB (°F)
LVG. AIR
(UNIT) DB/WB
(°F) NO. COMP. NO. FANS GAS TYPE STAGES INPUT MBH OUTPUT MBH ENT. AIR (°F) LVG. AIR (°F)
RTU-1 RUPPAIR RARTU1-I.100-15-5T 15P-1 1,500 330 230/1/60 52.3 60 0.7 64.0 43.6 79.4/66.8 52.7/52.7 1 1 LP MODULATING 100 81.0 54.0 103.0 1,388 1-7
RTU-2 RUPPAIR RARTU1-I.100-15-5T 15P-1 1,600 240 230/1/60 52.3 60 0.7 63.9 44.1 78.0/66.0 52.7/52.7 1 1 LP MODULATING 100 81.0 58.8 105.8 1,386 1-6
RTU-3 RUPPAIR RARTU1-I.75-15-4T 15P-1 1,200 180 230/1/60 47.6 50 0.7 51.0 34.4 78.0/66.0 51.6/51.6 1 1 LP MODULATING 74.7 60.5 58.8 105.8 1,374 1-6
REMARKS:
1. PROVIDE 20" ROOF CURB.
2. PROVIDE WITH DISCONNECT SWITCH AND 120V POWERED CONVENIENCE RECEPTACLE,
3. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT WITH OCCUPIED OVERRIDE PUSHBUTTON.
4. PROVIDE WITH ENTHALPY CONTROLLED ECONOMIZER AND BAROMETRIC RELIEF DAMPER.
5. PROVIDE WITH STAINLESS STEEL HEAT EXCHANGER.
6. PROVIDE WITH VARIABLE SPEED COMPRESSOR MODULATING HOT GAS REHEAT.
7. PROVIDE WITH DEMAND CONTROL VENTILATION.
MAKE-UP AIR UNIT SCHEDULE
TAG NO. MANUFACTURER FAN UNIT MODEL NO. CFM O/A CFM E.S.P. HP GAS TYPE MBH INPUT MBH OUTPUT BURNER EFF. (%) TEMP. RISE V/P/Hz MCA MOCP OPER WT. REMARKS
MAU-1 RUPPAIR R2D.250-20D 2,600 2,600 0.6 1.5 LP 214 197 92 70 DEG. F 230/1/60 16.1 25 1,008 LBS. 1-12
MAU-2 RUPPAIR R3D.500-24D 5,000 5,000 0.6 5.0 LP 411 378 92 70 DEG. F 230/1/60 41.4 60 1,310 LBS. 1-11, 13
MAU-3 RUPPAIR R2D.500-20D 3,400 3,400 0.6 3.0 LP 304 280 92 70 DEG. F 230/1/60 22.5 35 1,016 LBS. 1-11, 14
MAU-4 RUPPAIR R2D.500-20D 3,800 3,800 0.6 3.0 LP 313 288 92 70 DEG. F 230/1/60 22.5 35 1,016 LBS. 1-12
MAU-5 RUPPAIR R1D.250-15D 1,400 1,400 0.6 1.0 LP 115 106 92 70 DEG. F 230/1/60 9.2 15 725 LBS. 1-12
REMARKS:
1. PROVIDE 20" ROOF CURB WITH CURB DUCT HANGER.
2. PROVIDE WITH 7-DAY PROGRAMMABLE HMI CONTROLLER WITH PUSHBUTTON OVERRIDE.
2. PROVIDE INSULATED V-BANK FILTER SECTION WITH MERV 8 FILTERS.
3. PROVIDE WITH INLET PRESSURE GAUGES, MANIFOLD PRESSURE GAUGES, AND FREEZESTAT.
4. PROVIDE WITH MOTORIZED BACK DRAFT DAMPER.
5. PROVIDE WITH SINGLE POINT ELECTRICAL CONNECTION.
6. PROVIDE WITH VAV PACKAGE INCLUDING FACTORY MOUNTED AND WIRED VFD.
7. PROVIDE WITH GFCI POWERED CONVENIENCE OUTLET.
8. PROVIDE WITH OCCUPIED SCHEDULING, CLOGGED FILTER SWITCH, AND LED LIGHTS.
9. PROVIDE WITH STAINLESS STEEL FURNACE.
10. PROVIDE WITH CONTROLS TO SUPPLY 70° DISCHARGE AIR TEMPERATURE.
11. UNIT SHALL RUN CONTINUOUSLY DURING OCCUPIED HOURS.
12. UNIT SHALL BE INTERLOCKED WITH EXHAUST FAN, SEE EXHAUST FAN SCHEDULE.
13. UNIT SHALL BE INTERLOCKED WITH EXISTING EXHAUST FANS SERVING THE SPACE.
14. UNIT SHALL BE INTERLOCKED WITH EXISTING EXHAUST FAN SERVING THE SPACE AND VEHICLE EXHAUST SYSTEM FAN.
EXHAUST FAN SCHEDULE
TAG NO.
RTU / MAU
INTERLOCK
MANUFACTURER MODEL NO. TYPE CFM ESP
SP WITH BD
DAMPER
V/P/Hz HP RPM AMPS MCA MOP SONES
WEIGHT
(LBS.)
REMARKS
EF-1 MAU-1 GREENHECK GB-140
ROOF MTD. /
DOWNBLAST
2,600 0.35 0.48 230/1/60 1 1,561 8 10 15 17.1 150 1,2
EF-2 RTU-2 GREENHECK G-097-VG
ROOF MTD. /
DOWNBLAST
150 0.50 0.51 115/1/60 1/4 1,251 3.8 4.8 15 5.7 75 1,2
EF-3 RTU-3 GREENHECK G-097-VG
ROOF MTD. /
DOWNBLAST
200 0.75 0.77 115/1/60 1/4 1,584 3.8 4.8 15 8.3 75 1,2
EF-4 MAU-4 GREENHECK CUBE-200 SIDEWALL 3,800 0.35 0.85 230/1/60 1-1/2 968 10 12.5 20 14.9 200 2,3
EF-5 MAU-5 GREENHECK AER-20-02-0310-VG WALL MTD. 1,400 0.30 0.33 120/1/60 1/2 1,248 6.6 8.2 15 14.1 250 2,3,5
VEF-1 MAU-3 FUME-A-VENT HRF-1.5-1
HOSE REEL
MTD.
840 4.0 - 230/1/60 1.5 3,450 - - - - 65 4
REMARKS:
1. PROVIDE WITH 14" ROOF CURB AND BIRDSCREEN.
2. PROVIDE WITH DISCONNECT SWITCH AND GRAVITY BACKDRAFT DAMPER.
3. PROVIDE MISCELLANEOUS HARDWARE FOR WALL MOUNTING.
4. HOSE REEL MOUNTED EXHAUST FAN, COORDINATE FINAL FAN LOCATION AND FAN REQUIREMENTS WITH OWNER AND FAN MANUFACTURER.
5. PROVIDE WITH WALL SLEEVE, MOTOR GUARD, ANGLE SUPPORTS, AND 45° WEATHERHOOD.
ELECTRIC BASEBOARD SCHEDULE
TAG NO. MANUFACTURER MODEL NO. WATTS ELEMENT LENGTH
ENCLOSURE
V/P/Hz AMPS LOCATION REMARKS W H
EBB-1 BERKO BKOC25126W 500 30" 3" 7" 120/1/60 4.2 125 WOMEN 1,2
EBB-2 BERKO BKOC25126W 500 30" 3" 7" 120/1/60 4.2 126 SHOWER 1,2
EBB-2 BERKO BKOC25126W 500 30" 3" 7" 120/1/60 4.2 128 MEN 1,2
REMARKS:
1. COORDINATE FINAL INSTALLATION LOCATION AND FINISH WITH ARCHITECT.
2. PROVIDE TAMPER RESISTANT INTEGRAL THERMOSTAT.
GAS FIRED UNIT HEATER SCHEDULE
TAG NO. MANUFACTURER MODEL NO. FUEL INPUT MBH OUTPUT MBH CFM RPM HP V/P/Hz TOTAL AMPS HORIZONTAL THROW MOUNTING HEIGHT REMARKS
UH-1 MODINE HD100 PROPANE 100 83.0 1,490 1,050 1/6 115/1/60 5.1 42 FT. -- 1-3
UH-2 MODINE HD100 PROPANE 100 83.0 1,490 1,050 1/6 115/1/60 5.1 42 FT. -- 1-3
UH-3 MODINE HD75 PROPANE 75 62.3 1,160 1,625 1/12 115/1/60 3.75 38 FT. -- 1-3
UH-4 MODINE HD75 PROPANE 75 62.3 1,160 1,625 1/12 115/1/60 3.75 38 FT. -- 1-3
UH-5 MODINE HD100 PROPANE 100 83.0 1,490 1,050 1/6 115/1/60 5.1 42 FT. -- 1-3
UH-6 MODINE HD100 PROPANE 100 83.0 1,490 1,050 1/6 115/1/60 5.1 42 FT. -- 1-3
UH-7 MODINE HD100 PROPANE 100 83.0 1,490 1,050 1/6 115/1/60 5.1 42 FT. -- 1-3
REMARKS:
1. PROVIDE VENT KIT.
2. PROVIDE MISCELLANEOUS HARDWARE FOR WALL OR CEILING MOUNTING.
3. PROVIDE 7-DAY PROGRAMMABLE WALL MOUNTED THERMOSTAT.
WASHDOWN RATED ELECTRIC UNIT HEATER SCHEDULE
TAG NO. MANUFACTURER MODEL NO. CFM KW V/P/Hz AMPS LOCATION WEIGHT (LBS.)
HORIZONTAL
THROW
MOUNTING
HEIGHT
REMARKS
WDUH-1 MODINE MEW1-240160-075 700 7.5 240/1/60 34.3 900 WASHBAY 100 22 FT. 12'-8" 1,2,3
WDUH-2 MODINE MEW1-240160-075 700 7.5 240/1/60 34.3 900 WASHBAY 100 22 FT. 12'-8" 1,2,3
NOTES:
1. PROVIDE WALL/CEILING BRACKET.
2. PROVIDE NEMA 4R RATED WALL MOUNTED THERMOSTAT.
3. COORDINATE WITH ARCHITECT/OWNER FOR EXACT MOUNTING LOCATION PRIOR TO INSTALLATION.
DIFFUSER/REGISTER/GRILLE SCHEDULE
SYMBOL MANUFACTURER MODEL NO. MODULE SIZE NECK SIZE PATTERN CFM RANGE REMARKS
S-1
(CEILING
MOUNT)
TITUS TMSA 12"x12" 6"∅ 4-WAY 0-100 1-2
TITUS TMSA 24"x24" 8"∅ 4-WAY 101-200 1-2
TITUS TMSA 24"x24" 10"∅ 4-WAY 201-350 1-2
TITUS TMSA 24"x24" 12"∅ 4-WAY 351-550 1-2
S-2
TITUS TMSA 12"x12" 6"∅ 2-WAY 0-100 1-2
TITUS TMSA 24"x24" 8"∅ 2-WAY 101-200 1-2
TITUS TMSA 24"x24" 10"∅ 2-WAY 201-350 1-2
S-3
TITUS 300RL 10"x8" 8"x6" ADJ. 25-120 2-3
TITUS 300RL 14"x8" 12"x6" ADJ. 121-225 2-3
TITUS 300RL 20"x8" 18"x6" ADJ. 226-320 2-3
TITUS 300RL 20"x10" 18"x8" ADJ. 321-450 2-3
TITUS 300RL 22"x12" 24"x10" ADJ. 451-750 2-3
TITUS 300RL 26"x16" 24"x14" ADJ. 751-1,200 2-3
TITUS 300RL 32"x18" 30"x16" ADJ. 1,201-1,850 2-3
R-1/E-1
(CEILING
MOUNT)
TITUS 355RL 10"x10" 8"x8" R/A 0-185 1-2
TITUS 355RL 14"x14" 12"x12" R/A 186-450 1-2
TITUS 355RL 18"x18" 16"x16" R/A 451-800 1-2
TITUS 355RL 24"x24" 22"x22" R/A 801-1500 1-2
R-2/E-2
TITUS S355RL 12"x8" 10"x6" R/A 25-170 2-3
TITUS S355RL 20"x8" 18"x6" R/A 171-350 2-3
TITUS S355RL 24"x12" 22"x10" R/A 351-750 2-3
REMARKS:
1. PROVIDE WITH BORDER TO MATCH CEILING TYPE.
2. COORDINATE FINAL FINISH WITH ARCHITECT.
3. PROVIDE WITH OPPOSED BLADE DAMPER.
GENERAL NOTES:
1. PROVIDE ALUMINUM GRILLES, REGISTERS, AND DIFFUSERS IN AREAS SUBJECT TO MOISTURE.
2. PROVIDE STAINLESS STEEL GRILLES AND REGISTERS IN WASH BAY.
PACKAGED TERMINAL AIR CONDITIONER SCHEDULE
TAG NO. MFG. MODEL NO.
S/A CFM
MIN / MAX
O/A
CFM
VARIABLE SPEED COOLING CAPACITY
RANGE (BTU)
EER
VARIABLE SPEED HEATING CAPACITY
RANGE (BTU)
COP
ELECTRIC
HEAT
CAPACITY
REFRIGERANT V/P/Hz AMPS MCA MOCP
POWER
CONNECTION
OPERATING
WEIGHT
MIN. COOLING
CAPACITY (BTU)
MAX. COOLING
CAPACITY (BTU)
MIN. HEATING
CAPACITY (BTU)
MAX. HEATING
CAPACITY (BTU)
PTAC-1 GE AZVS15DMXWA 525 / 250 40 4,000 15,000 10.7 4,000 14,000 3.4 3.4 kW 454B 230/1/60 15.1 20 20 RECEPTACLE 105 LBS
REMARKS:
1. PROVIDE VARIABLE SPEED HEAT PUMP UNIT WITH OUTSIDE AIR DEHUMIDIFICATION.
2. PROVIDE WITH MANUFACTURER'S WALL SLEEVE, EXTERIOR WALL LOUVER, INTERNAL/EXTERNAL CONDENSATE DRAIN KIT, AND SUB-BASE KIT.
3. EXTERIOR OUTDOOR AIR LOUVER COLOR TO BE SELECTED BY ARCHITECT.
4. PROVIDE UNIT WITH INTEGRAL MAKE-UP AIR VENTILATION SYSTEM CAPABLE OF OPENING AND CLOSING OA DAMPER BASED ON ROOM OCCUPANCY.
5. PROVIDE REMOTE WALL MOUNTED THERMOSTAT WITH INTEGRAL OCCUPANCY DETECTION FOR CONTROLLING PTAC UNIT VENTILATION SYSTEM.
ELECTRIC WALL HEATER SCHEDULE
TAG NO. MANUFACTURER MODEL NO. KW V/P/Hz AMPS LOCATION REMARKS
EWH-1 BERKO FRC1512F 1.5 120/1/60 12.5 HALL 119 1-4
REMARKS:
1. PROVIDE WITH INTEGRAL THERMOSTAT.
2. PROVIDE 2 IN. SEMI-RECESS MOUNTING FRAME.
3. PROVIDE WITH VANDAL-RESISTANT KEY LOCKED FRONT COVER.
4. COLOR BY ARCHITECT.
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
M E
P _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
M
EC
H
AN
IC
AL
S
CH
ED
U
LE
S
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
M5.0
11.04.2026
BID
J A
C K
S O
N T
O W
N S
H
IP
M U
N
IC
IP
A
L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
D A T E
S H E E T a rc h it e c tu re w o rk s h o n e s o u th r a ilr o a d s tr e n o v n n s y lv a p h o n e
-6
-5
THIS BAR MUST MEASURE ONE INCH (1")
THIS DRAWING CAN ONLY BE PROPERLY VIEWED IF
PRINTED ON 24" x 36" SHEET
0 1
A ut od es k D oc s:
//1
.0
_J ac ks on
_T w p_ B ui ld in g/
M E
P _1
.0
_J ac ks on _T w p_
B ui ld in g_ R
.rv t
FI
RS
T
FL
O O
R
PL
AN
D
EM
O
LI
TI
O
N
M
EC
H
AN
IC
AL
P R
O P
O S
D
IT
IO
N
R E
N O
V A
T
IO
N
MD1.1
11.04.2026
BID
J A
C K
S O
N T
O W
N S
H
IP
M U
N
IC
IP
A
L
C E
N T
E R
R
O T H
S C
H U
R C
H R
O
R
IN
G G
R O
N
N S
Y
LV
A
NOTES BY SYMBOL: #
(THIS DRAWING ONLY)
1 REMOVE EXISTING GAS-FIRED FURNACE AND ASSOCIATED DUCTWORK
AND CONTROLS.
EXISTING EXHAUST FAN ON ROOF AND ASSOCIATED DUCTWORK TO
REMAIN AND BE REUSED.
EXISTING UNIT HEATER TO REMAIN AND BE REUSED.
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - DEMOLITION - MECHANICAL1
tag rev date revision note
| Sheets |
| M0.0 - MECHANICAL INFORMATION SHEET |
| M1.0 - FIRST FLOOR PLAN - MECHANICAL |
| M1.1 - STORAGE GARAGE PLANS - MECHANICAL |
| M2.1 - ROOF PLAN - MECHANICAL DUCT |
| M4.0 - MECHANICAL DETAILS |
| M5.0 - MECHANICAL SCHEDULES |
| MD1.1 - FIRST FLOOR PLAN - DEMOLITION - MECHANICAL |