265600-RIB-Exterior Lighting-12-24-2025.pdf
PDF 69 KB Posted
- Attached to
- Grand Junction Maintenance Project 2026-239M25
- Solicitation number
- IFB1 REAA 2026000155 3
- Issued by
- Mesa County, Colorado
About this file
This is a Scope of Work specification document for Section 265600 Exterior Lighting, which is part of Project 25-388 CBI HVAC and Lighting Upgrade. The specification outlines requirements for the installation of exterior luminaires, poles, and associated accessories. The work includes furnishing complete exterior lighting systems with luminaires from approved manufacturers including Acuity Brands, Alloy LED, Cooper Lighting, Electro-Matic Visual, Hubbell Lighting, and Philips Lighting North America Corporation. All luminaires must comply with UL 1598 standards and NFPA 70 requirements. Poles must be steel construction in square straight configuration, installed on concrete foundations at heights indicated on project drawings, and furnished with handholes, anchor bolts with leveling nuts, anchor base covers, and provisions for pole-mounted weatherproof GFI receptacles where specified. The specification requires coordination with utilities and other trades regarding pole placement and foundation elevation, with all conflicts or deviations to be reported to the Architect prior to proceeding.
Installation must comply with NECA/IESNA 501 standards for exterior lighting systems and manufacturer's written instructions. Luminaires must be installed plumb and square with proper alignment to building lines and adjacent units. All poles must be installed plumb using leveling nuts or shims as required, with anchor bolt nuts tightened to manufacturer specifications. Bonding of luminaires, metal accessories, metal poles, and foundation reinforcement to the branch circuit equipment grounding conductor is required. Service conductors of 12 AWG copper must be installed from each luminaire to the handhole for connection to branch circuit conductors. Upon completion, all luminaires must be cleaned according to NECA/IESNA 501 standards and manufacturer instructions to remove dirt and restore finishes to original factory condition. The specification references IEEE C2 National Electrical Safety Code (2023), NECA 1 Standard for Good Workmanship (2023), and the most recent edition of NFPA 70 adopted by the Authority Having Jurisdiction.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 265600 - 1 Exterior Lighting
SECTION 265600
EXTERIOR LIGHTING
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Exterior luminaires.
B. Poles and accessories.
C. Luminaire accessories.
1.02 RELATED REQUIREMENTS
A. Section 260526 - Grounding and Bonding for Electrical Systems.
B. Section 260529 - Hangers and Supports for Electrical Systems.
C. Section 260533.16 - Boxes for Electrical Systems.
D. Section 262726 - Wiring Devices: Receptacles for installation in poles.
E. Section 262813 - Fuses.
F. Section 265100 - Interior Lighting.
1.03 REFERENCE STANDARDS
A. IEEE C2 - National Electrical Safety Code(R) (NESC(R)); 2023.
B. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.
C. NECA/IESNA 501 - Standard for Installing Exterior Lighting Systems; 2000 (Reaffirmed 2006).
D. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having
Jurisdiction, Including All Applicable Amendments and Supplements.
E. UL 1598 - Luminaires; Current Edition, Including All Revisions.
1.04 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate placement of poles and associated foundations with utilities, curbs, sidewalks, trees, walls, fences, striping, etc. installed under other sections or by others. Coordinate elevation to obtain specified foundation height.
2. Notify Architect of any conflicts or deviations from Contract Documents to obtain direction prior to proceeding with work.
1.05 SUBMITTALS
A. See Section 013000 - Administrative Requirements, for submittal procedures.
B. Shop Drawings:
C. Product Data: Provide manufacturer's standard catalog pages and data sheets including detailed information on luminaire construction, dimensions, ratings, finishes, mounting requirements, listings, service conditions, photometric performance, weight, effective projected area (EPA), and installed accessories; include model number nomenclature clearly marked with all proposed features.
1.06 QUALITY ASSURANCE
A. Comply with requirements of NFPA 70.
1.07 DELIVERY, STORAGE, AND HANDLING
A. Receive, handle, and store products according to NECA/IESNA 501 and manufacturer's written instructions.
B. Keep products in original manufacturer's packaging and protect from damage until ready for installation.
PART 2 PRODUCTS
Upgrade 265600 - 2 Exterior Lighting
2.01 LUMINAIRE TYPES
A. Furnish products as indicated in luminaire schedule included on the drawings.
2.02 LUMINAIRES
A. Manufacturers:
1. Acuity Brands, Inc: www.acuitybrands.com/#sle.
2. Alloy LED; www.alloyled.com/#sle.
3. Cooper Lighting, a division of Cooper Industries: www.cooperindustries.com/#sle.
4. Electro-Matic Visual, Inc; www.empvisual.com/#sle.
5. Hubbell Lighting, Inc: www.hubbelllighting.com/#sle.
6. Philips Lighting North America Corporation; www.lightingproducts.philips.com/#sle.
B. Provide products that comply with requirements of NFPA 70.
C. Provide products that are listed and labeled as complying with UL 1598, where applicable.
D. Provide products listed, classified, and labeled as suitable for the purpose intended.
E. Unless otherwise indicated, provide complete luminaires including lamp(s) and all sockets, ballasts, reflectors, lenses, housings and other components required to position, energize and protect the lamp and distribute the light.
F. Unless specifically indicated to be excluded, provide all required conduit, boxes, wiring, connectors, hardware, poles, foundations, supports, trims, accessories, etc. as necessary for a complete operating system.
G. Provide products suitable to withstand normal handling, installation, and service without any damage, distortion, corrosion, fading, discoloring, etc.
2.03 POLES
A. Manufacturers:
1. Acuity Brands, Inc: www.acuitybrands.com/#sle.
B. All Poles:
1. Provide poles and associated support components suitable for the luminaire(s) and associated supports and accessories to be installed.
2. Material: Steel, unless otherwise indicated.
3. Shape: Square straight, unless otherwise indicated.
4. Finish: Match luminaire finish, unless otherwise indicated.
5. Mounting: Install on concrete foundation, height as indicated on the drawings, unless otherwise indicated.
6. Unless otherwise indicated, provide with the following features/accessories:
a. Handhole.
b. Anchor bolts with leveling nuts or leveling shims.
c. Anchor base cover.
d. Provision for pole-mounted weatherproof GFI receptacle where indicated.
C. Metal Poles: Provide ground lug, accessible from handhole or transformer base.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that field measurements are as indicated.
B. Verify that outlet boxes are installed in proper locations and at proper mounting heights and are properly sized to accommodate conductors in accordance with NFPA 70.
C. Verify that suitable support frames are installed where required.
D. Verify that branch circuit wiring installation is completed, tested, and ready for connection to luminaires.
E. Verify that conditions are satisfactory for installation prior to starting work.
Upgrade 265600 - 3 Exterior Lighting
3.02 INSTALLATION
A. Coordinate locations of outlet boxes provided under Section 260533.16 as required for installation of luminaires provided under this section.
B. Install products in accordance with manufacturer's instructions.
C. Install luminaires in accordance with NECA/IESNA 501.
D. Provide required support and attachment in accordance with Section 260529.
E. Install luminaires plumb and square and aligned with building lines and with adjacent luminaires.
F. Pole-Mounted Luminaires:
1. Maintain the following minimum clearances:
a. Comply with IEEE C2.
b. Comply with utility company requirements.
2. Foundation-Mounted Poles:
a. Install foundations plumb.
b. Install poles plumb, using leveling nuts or shims as required to adjust to plumb.
c. Tighten anchor bolt nuts to manufacturer's recommended torque.
3. Grounding:
a. Bond luminaires, metal accessories, metal poles, and foundation reinforcement to branch circuit equipment grounding conductor.
4. Install separate service conductors, 12 AWG copper, from each luminaire down to handhole for connection to branch circuit conductors.
G. Install accessories furnished with each luminaire.
H. Bond products and metal accessories to branch circuit equipment grounding conductor.
I. Install lamps in each luminaire.
3.03 ADJUSTING
A. Aim and position adjustable luminaires to achieve desired illumination as indicated or as directed by Architect. Secure locking fittings in place.
3.04 CLEANING
A. Clean surfaces according to NECA/IESNA 501 and manufacturer's instructions to remove dirt, fingerprints, paint, or other foreign material and restore finishes to match original factory finish.
3.05 PROTECTION
A. Protect installed luminaires from subsequent construction operations.
END OF SECTION
265600 - Exterior Lighting