This is a specification document for packaged outdoor central-station air-handling units as part of Project 25-388, a CBI HVAC and Lighting Upgrade. The specification details the requirements for roof-mounted units that combine gas burner heating and electric refrigeration cooling capabilities in a single, factory-assembled package. The units must be manufactured by Aaon, Inc. of Tulsa, Oklahoma, with no substitutions permitted. Key components include self-contained cabinets with baked enamel steel construction, stainless steel heat exchangers, copper tube aluminum fin coils for both evaporator and condenser sections, hermetic compressors with safety controls, and integrated damper systems for mixed air control. The specification requires units to comply with AHRI 210/240 performance ratings and NFPA 90A installation standards, with refrigerants limited to those having zero ozone depletion potential and global warming potential no greater than federal code limits.
The specification establishes comprehensive product and performance requirements, including mandatory five-year warranties covering refrigeration compressors. Manufacturers must have a minimum of three years documented experience, and all electrical components must be UL-listed and classified for their intended purpose. Installation must follow manufacturer's instructions with units mounted on factory-built roof mounting curbs to provide watertight enclosure. The specification requires one year of post-completion maintenance service with a maximum two-month interval between service calls, including minimum provisions for six filter replacements, one fan belt replacement, and controls adjustments. Detailed submittal requirements include product data, shop drawings, manufacturer's instructions, operation and maintenance documentation, and warranty registration in the owner's name. Control options include single-zone thermostats with programmable features and variable-volume units with supply air reset capabilities and BACnet MS/TP integration for building automation systems.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 237413 - 1 Packaged Outdoor Central-Station
Air-Handling Units
SECTION 237413
PACKAGED OUTDOOR CENTRAL-STATION AIR-HANDLING UNITS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Packaged roof top unit.
B. Unit controls.
C. Remote panel.
D. Roof mounting curb and base.
E. Maintenance service.
1.02 RELATED REQUIREMENTS
A. Section 230913 - Instrumentation and Control Devices for HVAC: Control components, time clocks.
B. Section 253519 - Integrated Automation Control Valves.
1.03 REFERENCE STANDARDS
A. AHRI 210/240 - Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump
Equipment; 2023.
B. NFPA 90A - Standard for the Installation of Air-Conditioning and Ventilating Systems; 2024.
1.04 SUBMITTALS
A. See Section 013000 - Administrative Requirements for submittal procedures.
B. Product Data: Provide capacity and dimensions of manufactured products and assemblies required for this project. Indicate electrical service with electrical characteristics and connection requirements, and duct connections.
C. Sustainable Design Documentation: Submit manufacturer's product data on refrigerant used, showing compliance with specified requirements.
D. Shop Drawings: Indicate capacity and dimensions of manufactured products and assemblies required for this project. Indicate electrical service with electrical characteristics and connection requirements, and duct connections.
E. Manufacturer's Instructions: Indicate assembly, support details, connection requirements, and include start-up instructions.
F. Operation and Maintenance Data: Include manufacturer's descriptive literature, operating instructions, installation instructions, maintenance and repair data, and parts listing.
G. Warranty: Submit manufacturer's warranty and ensure forms have been filled out in Owner's name and registered with manufacturer.
1.05 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacturing the type of products specified in this section, with minimum three years of documented experience.
B. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories
Inc. as suitable for the purpose specified and indicated.
1.06 WARRANTY
A. See Section 017800 - Closeout Submittals for additional warranty requirements.
B. Provide a five year warranty to include coverage for refrigeration compressors.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Aaon, Inc., Tulsa, Oklahoma.
Upgrade 237413 - 2 Packaged Outdoor Central-Station
Air-Handling Units
B.
C.
D. Substitutions: Not permitted.
2.02 MANUFACTURED UNITS
A. General: Roof mounted units having gas burner and electric refrigeration.
B. Description: Self-contained, packaged, factory assembled and prewired, consisting of cabinet and frame, supply fan, heat exchanger and burner, controls, air filters, refrigerant cooling coil and compressor, condenser coil and condenser fan.
C. Refrigerant: Use only refrigerants that have ozone depletion potential (ODP) of zero and global warming potential (GWP) no greater than that allowed by federal code.
D. Disconnect Switch: Factory mount disconnect switch in control panel.
2.03 FABRICATION
A. Cabinet: Steel with baked enamel finish, including access doors with piano hinges and locking handle. Structural members shall be minimum 18 gage, 0.0478 inch, with access doors or panels of minimum 20 gage, 0.0359 inch.
B. Insulation: 1 inch thick neoprene coated glass fiber with edges protected from erosion.
C. Heat Exchangers: Stainless steel, of welded construction.
D. Air Filters:
1. 1 inch thick glass fiber disposable media in metal frames.
E. Roof Mounting Curb: 14 inches high galvanized steel, channel frame with gaskets, nailer strips.
2.04 BURNER
A. Gas Burner: Atmospheric type burner with adjustable combustion air supply, pressure regulator, gas valves, manual shut-off, intermittent spark or glow coil ignition, flame sensing device, and automatic 100 percent shut-off pilot.
B. Gas Burner Safety Controls: Energize ignition, limit time for establishment of flame, prevent opening of gas valve until pilot flame is proven, stop gas flow on ignition failure, energize blower motor, and after airflow proven and slight delay, allow gas valve to open.
C. High Limit Control: Temperature sensor with fixed stop at maximum permissible setting, de-energize burner on excessive bonnet temperature and energize burner when temperature drops to lower safe value.
D. Supply Fan Control: Temperature sensor sensing bonnet temperatures and independent of burner controls, with provisions for continuous fan operation.
2.05 EVAPORATOR COIL
A. Provide copper tube aluminum fin coil assembly with galvanized drain pan and connection.
B. Provide capillary tubes or thermostatic expansion valves for units of 6 Tons of refrigeration capacity and less, and thermostatic expansion valves and alternate row circuiting for units 7.5 Tons of refrigeration cooling capacity and larger.
2.06 COMPRESSOR
A. Provide hermetic compressors, 3600 rpm maximum, resiliently mounted with positive lubrication, crankcase heater, high and low pressure safety controls, motor overload protection, suction and discharge service valves and gauge ports, and filter drier.
B. Five minute timed off circuit to delay compressor start.
C. Outdoor thermostat to energize compressor above 57 degrees F ambient.
2.07 CONDENSER COIL
A. Provide copper tube aluminum fin coil assembly with subcooling rows and coil guard.
Upgrade 237413 - 3 Packaged Outdoor Central-Station
Air-Handling Units
B. Provide direct drive propeller fans, resiliently mounted with fan guard, motor overload protection, wired to operate with compressor. Provide high efficiency fan motors.
C. Provide refrigerant pressure switches to cycle condenser fans.
2.08 MIXED AIR CASING
A. Dampers: Provide outside, return, and relief dampers with damper operator and control package to automatically vary outside air quantity. Outside air damper to fall to closed position.
Relief dampers may be gravity balanced.
B. Gaskets: Provide tight fitting dampers with edge gaskets.
C. Damper Operator: 24 volt with gear train sealed in oil.
D. Mixed Air Controls: Maintain selected supply air temperature and return dampers to minimum position on call for heating and above 75 degrees F ambient, or when ambient air enthalpy exceeds return air enthalpy.
2.09 OPERATING CONTROLS
A. Provide low voltage, adjustable room thermostat to control burner operation, compressor and condenser fan, and supply fan to maintain temperature setting.
1. Include system selector switch (heat-off-cool) and fan control switch (auto-on).
B. Provide terminal strip on unit for connection of operating controls to remote panel by others.
Control shall allow for two stages of heating and two stages cooling.
C. BAS, SCADA, or other Integrated Automation Link: ASHRAE Std 135 BACnet MS/TP.
D. Control Valves: Field-installed, modulating, ball type with position tracking; see Section
253519.
2.10 OPERATING CONTROLS - SINGLE ZONE UNITS
A. Electric solid state microcomputer based room thermostat, located as indicated in service area with remote sensor located as indicated.
B. Room thermostat shall incorporate:
1. Automatic switching from heating to cooling.
2. Preferential rate control to minimize overshoot and deviation from set point.
3. Set-up for four separate temperatures per day.
4. Instant override of set point for continuous or timed period from one hour to 31 days.
5. Short cycle protection.
6. Programming based on weekdays, Saturday and Sunday.
7. Switch selection features including imperial or metric display, 12 or 24 hour clock, keyboard disable, remote sensor, fan on-auto.
C. Room thermostat display shall include:
1. Time of day.
2. Actual room temperature.
3. Programmed temperature.
4. Programmed time.
5. Duration of timed override.
6. Day of week.
7. System model indication: heating, cooling, auto, off, fan auto, fan on.
8. Stage (heating or cooling) operation.
D. Provide low limit thermostat in supply air to close outside air dampers and stop supply fan.
2.11 OPERATING CONTROLS - VARIABLE VOLUME UNITS
A. Temperature transmitter located in supply air shall signal electronic logic panel to control mixing dampers and cooling in sequence. Mixing section shall operate as first stage of cooling and revert to minimum outside air above approximately 75 degrees F as determined by enthalpy of return and outdoor air.
Upgrade 237413 - 4 Packaged Outdoor Central-Station
Air-Handling Units
B. Control cooling by cycling compressors, cylinder unloading, and hot gas bypass.
C. Control logic shall allow supply air reset under low load or airflow conditions.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that roof is ready to receive work and opening dimensions are as indicated on shop drawings.
B. Verify that proper power supply is available.
3.02 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Mount units on factory built roof mounting curb providing watertight enclosure to protect ductwork and utility services. Install roof mounting curb level.
3.03 SYSTEM STARTUP
A. Prepare and start equipment. Adjust for proper operation.
3.04 CLOSEOUT ACTIVITIES
A. See Section 017800 - Closeout Submittals for closeout submittals.
B. See Section 017900 - Demonstration and Training for additional requirements.
C. Demonstrate operation to Owner's maintenance personnel.
3.05 MAINTENANCE
A. Provide service and maintenance of packaged roof top units for one year year from Date of
Substantial Completion.
B. Provide routine maintenance service with a two month interval as maximum time period between calls.
C. Include maintenance items as outlined in manufacturer's operating and maintenance data, including minimum of six filter replacements, minimum of one fan belt replacement, and controls check-out, adjustments, and recalibration.
D. After each service call, submit copy of service call work order or report that includes description of work performed.
END OF SECTION