This is a technical specifications document for Section 230529 - Hangers and Supports for HVAC Piping and Equipment, part of project 25-388 CBI HVAC and Lighting Upgrade. The specification establishes requirements for support and attachment components used in HVAC piping and equipment installation. The document does not specify quantities, response dates, due dates, site visits, bidders' meetings, award dates, or contract terms. Instead, it provides comprehensive technical requirements for materials, products, and installation methods that contractors must follow when executing this work. Key products include prefabricated trapeze-framed metal strut systems (with approved manufacturers Cooper B-Line and Unistrut), fiberglass strut systems (Enduro Composites), hanger rods, steel cable hanging systems, thermal insulated pipe supports, and various anchors and fasteners from specified manufacturers including Hilti, ITW Red Head, Powers Fasteners, and Simpson Strong-Tie.
The specification requires steel components to be corrosion-resistant based on location (zinc-plated for indoor dry locations; galvanized or stainless steel for outdoor and damp locations). Minimum channel thickness is 12 gauge (0.1046 inch) for metal strut systems, with minimum dimensions of 1-5/8 inch width by 13/16 inch height for steel and 1-5/8 inch by 1 inch for fiberglass. Fiberglass strut systems must meet NFPA 101 Class A flame spread index requirements (maximum 25) and self-extinguish per ASTM D635. The document requires compliance with referenced standards including ASTM A123/A123M, ASTM A153/A153M, MSS SP-58, and ICC-ES evaluation reports for anchors. Installation must follow manufacturer instructions, include independent support from building structure (not suspended from piping or ceiling systems), thermal insulation at specified locations, and proper concrete pad preparation per Section 033000. No pricing, funding sources, or contract award information is included in this specification document.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 230529 - 1 Hangers and Supports for HVAC
Piping and Equipment
SECTION 230529
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Support and attachment components.
1.02 RELATED REQUIREMENTS
A. Section 033000 - Cast-in-Place Concrete: Concrete equipment pads.
1.03 REFERENCE STANDARDS
A. ASTM A123/A123M - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products; 2024.
B. ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware; 2023.
C. ASTM B633 - Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel;
2023.
D. ASTM D635 - Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position; 2022.
E. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials;
2024.
F. ASTM E96/E96M - Standard Test Methods for Gravimetric Determination of Water Vapor Transmission Rate of Materials; 2024a.
G. MFMA-4 - Metal Framing Standards Publication; 2004.
H. MSS SP-58 - Pipe Hangers and Supports - Materials, Design, Manufacture, Selection, Application, and Installation; 2025.
I. NFPA 101 - Life Safety Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
J. UL 723 - Standard for Test for Surface Burning Characteristics of Building Materials; Current
Edition, Including All Revisions.
1.04 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate sizes and arrangement of supports and bases with the actual equipment and components to be installed.
2. Coordinate the work with other trades to provide additional framing and materials required for installation.
3. Coordinate compatibility of support and attachment components with mounting surfaces at the installed locations.
4. Coordinate the arrangement of supports with ductwork, piping, equipment and other potential conflicts installed under other sections or by others.
5. Notify Architect of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.
B. Sequencing:
1. Do not install products on or provide attachment to concrete surfaces until concrete has fully cured in accordance with Section 033000.
1.05 SUBMITTALS
A. See Section 013000 - Administrative Requirements for submittal procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for channel
(strut) framing systems, nonpenetrating rooftop supports, post-installed concrete and masonry anchors, and thermal insulated pipe supports.
Upgrade 230529 - 2 Hangers and Supports for HVAC
Piping and Equipment
1. Fiberglass Channel (Strut) Framing Systems: Include requirements for strength derating according to ambient temperature.
C. Shop Drawings: Include details for fabricated hangers and supports where materials or methods other than those indicated are proposed for substitution.
1. Application of protective inserts, saddles, and shields at pipe hangers for each type of insulation and hanger.
D. Derating Calculations for Fiberglass Channel (Strut) Framing Systems: Indicate load ratings adjusted for applicable service conditions.
E. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
1.06 QUALITY ASSURANCE
A. Comply with applicable building code.
B. Maintain at the project site a copy of each referenced document that prescribes execution requirements.
1.07 DELIVERY, STORAGE, AND HANDLING
A. Receive, inspect, handle, and store products in accordance with manufacturer's instructions.
PART 2 PRODUCTS
2.01 SUPPORT AND ATTACHMENT COMPONENTS
A. General Requirements:
1. Provide all required hangers, supports, anchors, fasteners, fittings, accessories, and hardware as necessary for the complete installation of plumbing work.
2. Provide products listed, classified, and labeled as suitable for the purpose intended, where applicable.
3. Where support and attachment component types and sizes are not indicated, select in accordance with manufacturer's application criteria as required for the load to be supported with a minimum safety factor of _____. Include consideration for vibration, equipment operation, and shock loads where applicable.
4. Do not use wire, chain, perforated pipe strap, or wood for permanent supports unless specifically indicated or permitted.
5. Steel Components: Use corrosion resistant materials suitable for the environment where installed.
a. Indoor Dry Locations: Use zinc-plated steel or approved equivalent unless otherwise indicated.
b. Outdoor and Damp or Wet Indoor Locations: Use galvanized steel, stainless steel, or approved equivalent unless otherwise indicated.
c. Zinc-Plated Steel: Electroplated in accordance with ASTM B633.
d. Galvanized Steel: Hot-dip galvanized after fabrication in accordance with ASTM
A123/A123M or ASTM A153/A153M.
B. Prefabricated Trapeze-Framed Metal Strut Systems:
1. Manufacturers:
a. Cooper B-Line, a division of Eaton Corporation: www.cooperindustries.com/#sle.
b. Unistrut, a brand of Atkore International Inc: www.unistrut.com/#sle.
c. Substitutions: See Section 016000 - Product Requirements.
d. Source Limitations: Furnish hardware, fittings, and accessories from single manufacturer.
2. Strut Channel or Bracket Material:
a. Indoor Dry Locations: Use painted steel, zinc-plated steel, or galvanized steel.
b. Outdoor and Damp or Wet Indoor Locations: Use galvanized steel.
3. Minimum Channel Thickness: Steel sheet, 12 gauge, 0.1046 inch.
Upgrade 230529 - 3 Hangers and Supports for HVAC
Piping and Equipment
4. Minimum Channel Dimensions: 1-5/8 inch width by 13/16 inch height.
5. Accessories: Provide bracket covers, cable basket clips, cable tray clips, clamps, conduit clamps, fire-retarding brackets, j-hooks, protectors, and vibration dampeners.
C. Prefabricated Trapeze-Framed Fiberglass Strut Systems:
1. Manufacturers:
a. Enduro Composites; ______: www.endurocomposites.com/#sle.
b. Substitutions: See Section 016000 - Product Requirements.
c. Source Limitations: Furnish hardware, fittings, and accessories from single manufacturer.
2. MSS SP-58 type 59, prefabricated continuous-slot fiberglass strut channel, associated fittings, and related accessories.
3. Channel Material: Use polyester resin or vinyl ester resin.
4. Minimum Channel Dimensions: 1-5/8 inch width by 1 inch height.
5. Flammability: Fire retardant with NFPA 101, Class A flame spread index (maximum of 25) when tested in accordance with ASTM E84; self-extinguishing in accordance with ASTM D635.
D. Hanger Rods:
1. Threaded zinc-plated steel unless otherwise indicated.
2. Minimum Size, Unless Otherwise Indicated or Required:
a. Equipment Supports: 1/2 inch diameter.
b. Piping up to 1 inch: 1/4 inch diameter.
c. Piping larger than 1 inch: 3/8 inch diameter.
d. Trapeze Support for Multiple Pipes: 3/8 inch diameter.
E. Steel Cable:
1. Manufacturers:
a. Ductmate Industries, Inc, a DMI Company; Clutcher Cable Hanging System:
www.ductmate.com/#sle.
b. Substitutions: See Section 016000 - Product Requirements.
c. Source Limitations: Furnish hardware, fittings, and accessories from single manufacturer.
F. Thermal Insulated Pipe Supports:
1. Manufacturers:
a. Substitutions: See Section 016000 - Product Requirements.
2. General Requirements:
a. Insulated pipe supports to be provided at hanger, support, and guide locations on pipe requiring insulation or additional support.
b. Surface Burning Characteristics: Flame spread index/smoke developed index of
5/30, maximum, when tested in accordance with ASTM E84 or UL 723.
c. Pipe supports to be provided for nominally sized, 1/2 to 30 inch iron pipes.
d. Insulation inserts to consist of rigid polyisocyanurate (urethane) insulation surrounded by a 360 degree, PVC jacketing.
3. PVC Jacket:
a. Pipe insulation protection shields to be provided with a ball bearing hinge and locking seam.
b. Moisture Vapor Transmission: 0.0071 perm inch, when tested in accordance with
ASTM E96/E96M.
c. Thickness: 60 mil.
4. Pipe insulation protection shields to be provided at the hanger points and guide locations on pipes requiring insulation as indicated on drawings.
G. Nonpenetrating Rooftop Supports for Low-Slope Roofs:
H. Anchors and Fasteners:
1. Manufacturers - Mechanical Anchors:
Upgrade 230529 - 4 Hangers and Supports for HVAC
Piping and Equipment
a. Hilti, Inc: www.us.hilti.com/#sle.
b. ITW Red Head, a division of Illinois Tool Works, Inc: www.itwredhead.com/#sle.
c. Powers Fasteners, Inc: www.powers.com/#sle.
d. Simpson Strong-Tie Company Inc: www.strongtie.com/#sle.
e. Substitutions: See Section 016000 - Product Requirements.
2. Manufacturers - Powder-Actuated Fastening Systems:
a. Hilti, Inc: www.us.hilti.com/#sle.
b. ITW Ramset, a division of Illinois Tool Works, Inc: www.ramset.com/#sle.
c. Powers Fasteners, Inc: www.powers.com/#sle.
d. Simpson Strong-Tie Company Inc: www.strongtie.com/#sle.
e. Substitutions: See Section 016000 - Product Requirements.
3. Unless otherwise indicated and where not otherwise restricted, use the anchor and fastener types indicated for the specified applications.
4. Concrete: Use preset concrete inserts, expansion anchors, or screw anchors.
5. Solid or Grout-Filled Masonry: Use expansion anchors or screw anchors.
6. Hollow Masonry: Use toggle bolts.
7. Hollow Stud Walls: Use toggle bolts.
8. Sheet Metal: Use sheet metal screws.
9. Wood: Use wood screws.
10. Plastic and lead anchors are not permitted.
11. Powder-actuated fasteners are permitted only as follows:
a. Where approved by Architect.
12. Hammer-driven anchors and fasteners are permitted only as follows:
a. Nails are permitted for attachment of nonmetallic boxes to wood frame construction (when specified).
b. Staples are permitted for attachment of nonmetallic-sheathed cable to wood frame construction (when specified).
13. Preset Concrete Inserts: Continuous metal channel (strut) and spot inserts specifically designed to be cast in concrete ceilings, walls, and floors.
a. Comply with MFMA-4.
b. Channel Material: Use galvanized steel.
c. Minimum Channel Thickness: Steel sheet, 12 gauge, 0.1046 inch minimum base metal thickness.
d. Manufacturer: Same as manufacturer of metal channel (strut) framing system.
14. Post-Installed Concrete and Masonry Anchors: Evaluated and recognized by ICC Evaluation Service, LLC (ICC-ES) for compliance with applicable building code.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that field measurements are as indicated.
B. Verify that mounting surfaces are ready to receive support and attachment components.
3.02 INSTALLATION
A. Install products in accordance with manufacturer's instructions.
B. Install anchors and fasteners in accordance with ICC Evaluation Services, LLC (ICC-ES) evaluation report conditions of use where applicable.
C. Provide independent support from building structure. Do not provide support from piping, ductwork, conduit, or other systems.
D. Unless specifically indicated or approved by Architect, do not provide support from suspended ceiling support system or ceiling grid.
E. Unless specifically indicated or approved by Architect, do not provide support from roof deck.
Upgrade 230529 - 5 Hangers and Supports for HVAC
Piping and Equipment
F. Do not penetrate or otherwise notch or cut structural members without approval of Structural Engineer.
G. Provide thermal insulated pipe supports complete with hangers and accessories. Install thermal insulated pipe supports during the installation of the piping system.
H. Equipment Support and Attachment:
1. Use metal fabricated supports or supports assembled from metal channel (strut) to support equipment as required.
2. Use metal channel (strut) secured to studs to support equipment surface-mounted on hollow stud walls when wall strength is not sufficient to resist pull-out.
3. Use metal channel (strut) to support surface-mounted equipment in wet or damp locations to provide space between equipment and mounting surface.
4. Unless otherwise indicated, mount floor-mounted equipment on properly sized 3 inch high concrete pad constructed in accordance with Section 033000.
5. Securely fasten floor-mounted equipment. Do not install equipment such that it relies on its own weight for support.
I. Preset Concrete Inserts: Use manufacturer-provided closure strips to inhibit concrete seepage during concrete pour.
J. Secure fasteners according to manufacturer's recommended torque settings.
K. Remove temporary supports.
3.03 FIELD QUALITY CONTROL
A. See Section 014000 - Quality Requirements for additional requirements.
B. Inspect support and attachment components for damage and defects.
C. Repair cuts and abrasions in galvanized finishes using zinc-rich paint recommended by manufacturer. Replace components that exhibit signs of corrosion.
D. Correct deficiencies and replace damaged or defective support and attachment components.
END OF SECTION