26 0930 WDS Ealy CD Drawings.pdf
PDF 9 MB Posted
- Solicitation number
- RFP WDS 270000000188 1
- Issued by
- Michigan
About this file
This is a construction document set consisting of architectural, mechanical, and electrical drawings for an interior renovation project at Ealy Elementary School in Whitehall, Michigan, prepared for the Whitehall District Schools. The project scope includes demolition and replacement of horizontal unit ventilators (HUVs) with associated mechanical and electrical work, selective ceiling and finish replacement in areas impacted by mechanical work, media center finish updates, and carpet replacement in select classrooms. The exterior scope encompasses roof replacement at Roofs 1 and 22 with associated demolition, flashings, penetrations, insulation, and roof drainage work. The project documents indicate compliance with the 2021 Michigan Building Code, 2021 Michigan Rehabilitation Code, 2021 Michigan Energy Code, and 2021 Michigan Plumbing Code, with no changes to building use, occupancy classification, building area, building height, or means of egress. The drawings are issued for construction documents dated September 30, 2026, and include comprehensive floor plans, demolition plans, reflected ceiling plans, finish plans, and mechanical/electrical details organized by building units (A, B, C, and D).
The project includes significant mechanical system replacement featuring new unit ventilators, air handling units, condensing boilers with a combined 2000 MBH capacity, condensing units for cooling, and associated piping and ductwork. New roof construction specifies 60 mil fully adhered single-ply membrane on minimum 5 inches of polyisocyanurate insulation with an initial solar reflectance index of 82. The mechanical equipment schedule details specific manufacturers and models including Trane unit ventilators and condensing units, Fulton condensing hydronic boilers, and Bell & Gossett pumps. The construction documents note that the owner reserves the right to remove or modify scope items prior to commencement of work and may accept base bid or alternate at the time of award. Existing roof conditions may vary from information shown, with additional repairs or modifications potentially required based on field conditions to be coordinated with the owner prior to proceeding.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E a ly E le m e n ta ry
W h it e h a ll D is tr ic t
S c h o o ls
E
S o p h ia S t, W h it e h a ll
M
I
PROJECT NO. 25.147
G001
COVER SHEET
425 E Sophia St, Whitehall, MI 49461
ISSUED FOR: CONSTRUCTION DOCUMENTS
Ealy Elementary Whitehall District Schools
09.30.2026
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E a ly E le m e n ta ry
W h it e h a ll D is tr ic t
S c h o o ls
E
S o p h ia S t, W h it e h a ll
M
I
PROJECT NO. 25.147
G001
COVER SHEET
425 E Sophia St, Whitehall, MI 49461
ISSUED FOR: CONSTRUCTION DOCUMENTS
Ealy Elementary Whitehall District Schools
09.30.2026
SYM DATE ISSUED FORSYM DATE ISSUED FOR
TYPICAL SYMBOLS & REFERENCESLG
ND
REFERENCE CALLOUT SYMBOL
A101
SIM
DETAIL NUMBER
SHEET NUMBER
EXTERIOR ELEVATION
REFERENCE BUBBLE A101
A ELEVATION LETTER
BUILDING SECTION SYMBOL
A101
SIM
SECTION NUMBER
SHEET NUMBER
INTERIOR ELEVATION
REFERENCE BUBBLE
A101
SHEET NUMBER
A
A
A
A
SIMILAR CONDITION
OPP
OPPOSITE CONDITION
ELEVATION LETTER
SIMILAR CONDITION
OPP
OPPOSITE CONDITION VIEW DIRECTION
1. THE OWNER RESERVES THE RIGHT TO REMOVE OR
MODIFY SCOPE ITEMS PRIOR TO COMMENCEMENT OF
CONTRACTED WORK.
2. OWNER MAY ACCEPT BASE BID OR ALTERNATE AT TIME
OF AWARD.
3. ALL EXISTING CONDITIONS SHALL BE FIELD VERIFIED
PRIOR TO COMMENCEMENT OF WORK.
4. EXISTING ROOF CONDITIONS MAY VARY FROM
INFORMATION SHOWN. ADDITIONAL REPAIRS OR
MODIFICATIONS MAY BE REQUIRED BASED ON FIELD
CONDITIONS AND SHALL BE COORDINATED WITH THE
OWNER PRIOR TO PROCEEDING.
5. COORDINATE ROOF WORK WITH ONGOING BUILDING
OPERATIONS.
6. CONTRACTOR SHALL PROTECT EXISTING BUILDING, ROOF
AREAS, AND INTERIOR SPACES FROM WATER INTRUSION
DURING CONSTRUCTION.
GENERAL ARCHITECTURAL NOTESNO
TE
S
NOTE:
MOUNT EQUIPMENT AS SHOWN UNLESS SPECIFIED
OTHERWISE. SWITCHES (LOCATE ON LATCH SIDE, IF
SWITCH OR DEVICE CANNOT BE
LOCATED ON LATCH SIDE, LOCATE
ONE DOOR LEAF WIDTH AWAY ON
HINGE SIDE) STACK UP TO 2 HIGH
DEVICES TO KEEP WITHIN ADA REACH.
DOOR
LOW
DEVICES
RECEPTACLEVOICE/DATA
MASONRY COURSING
(WHERE APPLICABLE)
F.A. PULL STATION
THERMOSTAT
F.A. AUDIO/VISUAL
ALIGNMENT NOTES
• ALIGN AND LOCATE CLOSE TOGETHER ANY DEVICES INSTALLED WITHIN 6' HORIZONTALLY.
• CENTER ALL DEVICES WHERE INDICATED ON COLUMN WRAP OR BUMP OUT; STACK AND ALIGN VERTICALLY.
• INSTALL DEVICES AT HEIGHTS INDICATED IN SYMBOL LEGEND UNLESS STACKING PER THIS DETAIL.
• WHERE HEIGHT IS SPECIFICALLY NOTED ON FLOOR PLANS, USE THAT MOUNTING HEIGHT
• CENTER ON DOORFRAME OR WHITEBOARDS ANY DEVICES INDICATED ABOVE.
F
R O
M F
L O
O R
O R
L A
N D
IN
G
F R
O M
F L
O O
R O
R L
A N
D
IN
G
CARD READER
6' - 0" MIN.
4" MAX
CAMERAS, CLOCKS,
WALL OCCUPANCY
SENSORS
WHITE BOARD (WHERE
APPLICABLE - VERIFY WITH
DETAILS/PLANS PROPER
INSTALL HEIGHT) CENTER ANY
SINGLE DEVICE WITH CENTER
OF WHITE BOARD
ANY DEVICES
SHOWN OVER
DOOR TO BE
CENTERED.
EQ EQ
EQ EQ
F
R O
M F
L O
O R
O R
L A
N D
IN
G
SHORT THROW
PROJECTOR WHERE
APPLICABLE
~12"
MAX TWO DEVICES IN
ONE HIGHER MOUNT
LOCATION, PROVIDE RFI
IF MORE DEVICES ARE
NECESSARY
WHEN DEVICES ARE WITHIN DIMENSION,
STACK HIGH/LOW VERTICALLY AND GROUP
DEVICES AT SAME HEIGHT. UNLESS
DEVICES IS PART OF TECHNOLOGY DETAIL
GROUPING OR SERVING A FURNITURE
GROUP.
CASEWORK, COORDINATE DEVICE
BOTTOM TO BE 2" OVER
BACKSPLASH OR OVER
COUNTERTOP (IF NO BACKSPLASH).
FOR LARGE FORMAT TILE, ALIGN
EDGE OF DEVICE WITH HORIZONTAL
GROUT LINE CLOSEST TO
COUNTERTOP.
COORDINATE OUTLET LOCATIONS
WITH GROUT LINES, EDGE OF
DEVICE ON GROUT LINE IF POSSIBLE.
COORDINATE WITH INTERIOR
DESIGN DRAWINGS.
S
TYPICAL COLUMN
ENCLOSURE, CHASE
OR BUMP-OUT WITH
DEVICES INDICATED
IN PLANS.
EQ EQ
M A
X
4" MAX.
M
IN
PROTRUDING
OBJECTS
REDUCED VERTICAL
CLEARANCE
WATER CLOSET &
LAVATORY CLEARANCE
403.5
CLEAR WIDTH
ACCESSIBLE ROUTE
TRANSFER SHOWER
CLEARANCE
404.2.3.2(A)
FRONT APPROACH PULL SIDE
*IF BOTH CLOSER AND LATCH
ARE PROVIDED
404.2.3.2(B)
FRONT APPROACH PUSH SIDE
*IF BOTH CLOSER AND LATCH
ARE PROVIDED - NEW
BUILDINGS
404.2.3.2(E)
HINGE APPROACH PULL SIDE
404.2.3.2(F)
HINGE APPROACH PUSH SIDE
*48" MIN IF BOTH CLOSER AND
LATCH ARE PROVIDED
404.2.3.2(G)
LATCH APPROACH PULL SIDE
*54" IF CLOSER IS PROVIDED
404.2.3.2(H)
LATCH APPROACH PUSH SIDE
*48" IF CLOSER IS PROVIDED
CHANGES IN LEVEL
NOTE:
INFORMATION SHOWN IS TAKEN FROM THE AMERICAN
NATIONAL STANDARD INSTITUTE (ANSI) AND IS FOR
REFERENCE ONLY AS DESCRIBED IN: ANSI ICC A117.1-2017
M A
X
M
IN
" C L
E A
R
M
IN
CLEAR
60" MIN.
M
IN
MIN.
30"
MIN.
36"
MIN.
32"
M A
X
M
IN
M A
X
S E
A T
W
L
L
BACK
WALL
36"
48"
M
IN
MIN.
18" *
M
IN
MIN.
12" *
M
IN
42" MIN.
M
IN
MIN.
22"
M
IN
MIN.
24"
M
IN
MIN.
24"
1/
M A
X
1/
M A
X
1/
M A
X
1/
M A
X
ACCESSIBLE BUILDING CLEARANCESLG
ND
MIN.
15"
MIN.
16"
M
A X
M
IN
8" MIN
6" MIN 11"
MAX
25"
M
IN
KNEE
CLEARANCE
ø
304.3.1.1
NEW BUILDING
TURNING RADIUS
ø
304.3.1.2
EXISTING BUILDING
TURNING RADIUS
ø
OVERLAP AREA
304.3.2
T-SHAPED TURNING RADIUS
NEW BUILDINGS - OPTION 1
68" MIN.
M
IN
16" MIN. 36" MIN. 16" MIN.
M
IN
M
IN
304.3.2
T-SHAPED TURNING RADIUS
NEW BUILDINGS - OPTION 2
64" MIN.
M
IN
11" MIN. 42" MIN. 11" MIN.
M
IN
M
IN
304.3.2
T-SHAPED TURNING RADIUS
NEW BUILDINGS - OPTION 3
64" MIN.
M
IN
12" MIN. 40" MIN. 12" MIN.
M
IN
M
IN
304.3.2.2
T-SHAPED TURNING RADIUS
EXISTING BUILDINGS
60" MIN.
M
IN
12" MIN. 36" MIN. 12" MIN.
M
IN
M
IN
305.3.1
NEW BUILDING
CLEAR FLOOR SPACE
52" MIN.
M
IN
305.3.2
EXISTING BUILDING
CLEAR FLOOR SPACE
48" MIN.
M
IN
404.2.3.2(C)
FRONT APPROACH PUSH SIDE
*IF BOTH CLOSER AND LATCH
ARE PROVIDED - EXISTING
BUILDINGS
M
IN
MIN.
12" *
404.2.3.2(D)
HINGE APPROACH PULL SIDE
M
IN
36" MIN.
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
G002
DRAWING INDEX,
GENERAL NOTES, AND
ACCESSIBILITY
09.30.2026
SHEET LIST
SHEET # SHEET NAME
GENERAL
G001 COVER SHEET
G002 DRAWING INDEX, GENERAL NOTES, AND ACCESSIBILITY
G101 FIRST FLOOR CODE COMPLIANCE PLANS
DEMOLITION
D101 FIRST FLOOR DEMOLITION PLAN
D101A FIRST FLOOR DEMOLITION PLAN - UNIT A
D101B FIRST FLOOR DEMOLITION PLAN - UNIT B
D101C FIRST FLOOR DEMOLITION PLAN - UNIT C
D101D FIRST FLOOR DEMOLITION PLAN - UNIT D
D102 ROOF DEMOLITION PLAN
D201 FIRST FLOOR CEILING DEMOLITION PLAN
ARCHITECTURAL
A101 FIRST FLOOR PLAN
A101A FIRST FLOOR PLAN - UNIT A
A101B FIRST FLOOR PLAN - UNIT B
A101C FIRST FLOOR PLAN - UNIT C
A101D FIRST FLOOR PLAN - UNIT D
A102 ROOF PLAN
A201 FIRST FLOOR REFLECTED CEILING PLAN
INTERIORS
I101 FIRST FLOOR FINISH PLAN
MECHANICAL DEMOLITION
MD101A MECHANICAL DEMOLITION FIRST FLOOR PLAN - UNIT A
MD101B MECHANICAL DEMOLITION FIRST FLOOR PLAN - UNIT B
MD101C MECHANICAL DEMOLITION FIRST FLOOR PLAN - UNIT C
MD101D MECHANICAL DEMOLITION FIRST FLOOR PLAN - UNIT D
MECHANICAL
M101A MECHANICAL HVAC FIRST FLOOR PLAN - UNIT A
M101B MECHANICAL HVAC FIRST FLOOR PLAN - UNIT B
M101C MECHANICAL HVAC FIRST FLOOR PLAN - UNIT C
M101D MECHANICAL HVAC FIRST FLOOR PLAN - UNIT D
M102A MECHANICAL HVAC ROOF PLAN - UNIT A
M102B MECHANICAL HVAC ROOF PLAN - UNIT B
M102C MECHANICAL HVAC ROOF PLAN - UNIT C
M102D MECHANICAL HVAC ROOF PLAN - UNIT D
M200 MECHANICAL SCHEDULES
M201 MECHANICAL DETAILS
M202 MECHANICAL NOTES & ABBREVIATIONS
M300 MECHANICAL CONTROLS
M301 MECHANICAL CONTROLS
M302 MECHANICAL CONTROLS
ELECTRICAL DEMOLITION
ED101A ELECTRICAL DEMOLITION FIRST FLOOR PLAN - UNIT A
ED101B ELECTRICAL DEMOLITION FIRST FLOOR PLAN - UNIT B
ED101C ELECTRICAL DEMOLITION FIRST FLOOR PLAN - UNIT C
ED101D ELECTRICAL DEMOLITION FIRST FLOOR PLAN - UNIT D
ELECTRICAL
E101 ELECTRICAL POWER FIRST FLOOR PLAN - OVERALL
E101A ELECTRICAL POWER FIRST FLOOR PLAN - UNIT A
E101B ELECTRICAL POWER FIRST FLOOR PLAN - UNIT B
E101C ELECTRICAL POWER FIRST FLOOR PLAN - UNIT C
E101D ELECTRICAL POWER FIRST FLOOR PLAN - UNIT D
E102A ELECTRICAL POWER ROOF PLAN - UNIT A
E102C ELECTRICAL POWER ROOF PLAN - UNIT C
E102D ELECTRICAL POWER ROOF PLAN - UNIT D
E201A ELECTRICAL LIGHTING FIRST FLOOR CEILING PLAN - UNIT A
E300 ELECTRICAL NOTES & SYMBOLS
E301 ELECTRICAL ONE-LINE DIAGRAM
E302 ELECTRICAL DETAILS & SCHEDULES
E303 ELECTRICAL PANEL SCHEDULES
TECHNOLOGY
T101 TECHNOLOGY SYMBOL LEGEND
T102A TECHNOLOGY PLAN - UNIT A
T102B TECHNOLOGY PLAN - UNIT B
NOT TO SCALE
DEVICE ALIGNMENT GUIDELINES
SYM DATE ISSUED FOR
J
J
J
J J
J J
J
J
J
J
J
J
J
J
J
J
J
JJ
J
J
J
J
J
J
F A
C P
J
SD
SD
D
SD
D
CODE COMPLIANCE LEGEND
EGRESS SYMBOLS
EGRESS EXIT NUMBER
FROM ROOM OR SPACE
MAXIMUM NUMBER OF
OCCUPANTS PERMITTED
BY EGRESS WIDTH
EXISTING TRAVEL
DISTANCE TO
EGRESS DOOR
PERMITTED MAXIMUM
TRAVEL DISTANCE
PER CONDITION
DIRECTION OF EGRESS
FIRE SAFETY SYMBOLS
XFE
XFEC
FE
FEC
EXISTING FIRE EXTINGUISHER
EXISTING FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
1. LIGHTER LINES SHOWN ABOVE INDICATE EXISTING FIRE RATED
WALLS.
2. ALL PENETRATIONS THROUGH A FIRE OR SMOKE RATED PARTITION
SHOULD BE SEALED WITH AN APPROVED U.L. RATED PRODUCT.
3. THE TOPS OF ALL FIRE RATED PARTITIONS SHALL BE SEALED TO THE
CONTINUOUS STRUCTURE ABOVE WITH A U.L. RATED SYSTEM OR
ASSEMBLY.
4. WOOD BLOCKING IN FIRE-RATED PARTITIONS SHALL BE OF NON-
COMBUSTIBLE TREATED WOOD.
5. REFER TO SPECIFICATION FOR U.L. RATING INFORMATION.
6. FIRE-RATED WALLS ENDING INTO AN ACOUSTICAL DECK MUST HAVE
THE FLUTES FILLED, REFER TO 'TOP OF WALL DETAIL AT ACOUSTIC
DECK' SHOWN ON THIS SHEET.
• FOR MASONRY WALLS THE MASON SHALL FILL VOIDS AND FIRE
SPRAY WITH UL LISTED MATERIAL.
• FOR STUD WALLS USE FIRE SAFING AND FIRE CAULK.
PARTITION SYMBOL PARTITION RATING RATING PRIORITY
3 HOUR 01
2 HOUR FIRE/SMOKE
2 HOUR
1 HOUR FIRE/SMOKE
1HOUR
SMOKE RESISTANT
FIRE-RATING KEYLG
ND
LG
ND
COMMON PATH OF
TRAVEL DISTANCE: 00'-00"
PERMITTED TRAVEL DISTANCE: 00'-00"
1i - Level
150 SF GROSS / 300
Room name
GROSS OCCUPANCY BY SPACE TAG
ROOM NUMBER
ROOM NAME
CALCULATED OCCUPANCY
ACTUAL OCCUPANT LOAD
AREA CALCULATION
150 SF NET
Net Area / ### Net SF Reduction : ##
Room name
NET OCCUPANCY BY SPACE TAG
ROOM NUMBER
ROOM NAME
CALCULATED OCCUPANCY
NET SF REDUCTION
ACTUAL OCCUPANT LOAD
AREA CALCULATION
NUMBER OF OCCUPANTS
EGRESSING FROM SPACE #
# occs
ACTUAL OCCUPANTS
EGRESSING THROUGH EXIT
EXIT: #
# occs
EXISTING TRAVEL
DISTANCE TO
EGRESS DOOR
PERMITTED MAXIMUM
TRAVEL DISTANCE
PER CONDITION
DIRECTION OF EGRESS
EXIT ACCESS
TRAVEL DISTANCE: 00'-00"
PERMITTED TRAVEL DISTANCE: 00'-00"
1i - Level
AED AUTOMATED EXTERNAL DEFIBRILLATOR
CODE SUMMARY
Site Address: 425 E Sophia Street Whitehall, MI 49461
Project Description: Project consists of interior renovation work at the existing Ealy Elementary School including demolition and replacement of horizontal unit ventilators (HUVs) with associated mechanical and electrical work. Selective ceiling and finish replacement will occur in areas impacted by mechanical work. Additional interior scope includes media center finish updates and carpet replacement in select classrooms. Exterior scope includes roof replacement at Roofs 1 and 22 with associated demolition, flashings, penetrations, insulation, and roof drainage work.
There is no change to building use, occupancy classification, building area, building height, or means of egress.
Local Jurisdiction: City of Whitehall, MI - Building Department
Applicable Building Code: 2021 Michigan Building Code (MBC) 2021 Michigan Rehabilitation Code (MRC) 2021 Michigan Energy Code (MEC) 2021 Michigan Plumbing Code (MPC)
ENERGY CODE COMPLIANCE
SYSTEM PRODUCT R-VALUE U-VALUE
ROOF POLYISOCYANURATE
INSULATION
R-32.5 (6.5/IN) 0.030
BASIS OF DESIGN
ROOF MFR'S
STANDARD
1. THIS IS INTENDED TO CONVEY MEETING THE PRESCRIPTIVE ASHRAE 90.1 -
LATEST ADOPTED EDITION REQUIREMENTS
2. ENERGY CODE COMPLIANCE IS LIMITED TO ROOF ASSEMBLIES WITHIN
THE SCOPE OF WORK. NO MODIFICATIONS TO WALLS, FLOORS, SLABS,
OR OPENINGS ARE PROPOSED.
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
G101
FIRST FLOOR CODE
COMPLIANCE PLANS
09.30.2026NR
TH 1/16" = 1'-0"
FIRST FLOOR CODE COMPLIANCE PLAN
Path of Travel Schedule
Mark Length
Permitted
Travel
Distance Level
RECEPTION/WAITING
CONF. ROOM OFFICE
STAFF LOUNGE
ART ROOM ART ROOM
CAFETERIA
SERVING KITCHEN
GYM
PERFORMING
ARTS
GYM COMMONS
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
BOYS RR
GIRLS RR
CLASSROOM
CLASSROOM
COMMONS
CLASSROOM
CLASSROOM
CLASSROOM
MEDIA CENTER
LARGE GROUP
INSTRUCTION
CLASSROOM CLASSROOMCLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
CLASSROOMCLASSROOM
CORRIDORCORRIDOR
GIRLS RR
BOYS RR
UPPER MECH
BOYS RR
GIRLS RR
OFFICE
OFFICE
STORAGE
UNIT A
UNIT D
U N
IT A
U N
IT D
UNIT A
UNIT C
U N
IT B
U N
IT C
U N
IT C
U N
IT D
U N
IT
C
U N
IT
D
U N
IT
B U N
IT
A
1 2
1 2
1 2
1 2
1 2
4 4
4 4
Milles has finned tubue removal
Milles has finned tubue removal
No Mech. in this classroom. Has dedicated "RTU" from 2017.
1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE
EXISTING BUILDING PRIOR TO RELATED DEMOLITION
WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY
WALL, FLOOR OR CEILING INCLUDES ALL GENERAL
MECHANICAL AND ELECTRICAL ITEMS WHICH ARE A PART
OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE
CONDITIONS AND DIMENSIONS AND BE RESPONSIBLE
FOR THE SAME. ADVISE ARCHITECT OF ANY AND ALL
DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING
CONSTRUCTION AND DEMOLITION AS REQUIRED. FINISH
TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND
DETAILS FOR ADDITIONAL INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND
ELECTRICAL PLANS FOR ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN
NEW CONSTRUCTION, IF REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED
ITEMS ATTACHED TO THE WALL ARE TO BE REMOVED.
SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
GENERAL DEMOLITION NOTESNO
TE
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
D101
FIRST FLOOR
DEMOLITION PLAN
09.30.2026
DEMOLITION KEYED NOTES
1 REMOVE EXISTING MECHANICAL EQUIPMENT.
CORDINATE WITH MECHANICAL DRAWINGS. PREP FOR
NEW WORK.
2 REMOVE EXISTING WALL LOUVER. COORDINATE WITH
MECHANICAL. PREP FOR NEW WORK
3 REMOVE EXISTING CABINET HEATER CORDINATE WITH
MECHANICAL. PREP FOR NEW WORK.
4 SALVAGE EXISTING CARPET TILE AROUND MECHANICAL
EQUIPMENT FOR PATCH AND REPAIR
5 REMOVE EXISTING COUNTERTOPS AND PANEL
MOLDING. SALVAGE MOLDING FOR REUSE. CASEWORK
TO REMAIN. PREP FOR NEW SOLID SURFACE
COUNTERTOP MATERIAL.
6 REMOVE EXISTING FLOOR AND WALL BASE.
NR
TH 1/16" = 1'-0"
FIRST FLOOR DEMOLITION PLAN
NO
TE
1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE
EXISTING BUILDING PRIOR TO RELATED DEMOLITION
WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY
WALL, FLOOR OR CEILING INCLUDES ALL GENERAL
MECHANICAL AND ELECTRICAL ITEMS WHICH ARE A PART
OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE
CONDITIONS AND DIMENSIONS AND BE RESPONSIBLE
FOR THE SAME. ADVISE ARCHITECT OF ANY AND ALL
DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING
CONSTRUCTION AND DEMOLITION AS REQUIRED. FINISH
TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND
DETAILS FOR ADDITIONAL INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND
ELECTRICAL PLANS FOR ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN
NEW CONSTRUCTION, IF REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED
ITEMS ATTACHED TO THE WALL ARE TO BE REMOVED.
SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
GENERAL DEMOLITION NOTESNO
TE
RECEPTION/WAITING
CONF. ROOM OFFICE
STAFF LOUNGE
ART ROOM ART ROOM
CAFETERIA
SERVING KITCHEN
CLASSROOM
CLASSROOM
MEDIA CENTER
LARGE GROUP
INSTRUCTION
CLASSROOM CLASSROOMCLASSROOM
CLASSROOM
BOYS RR
GIRLS RR
4 4
4 4
UNIT A
UNIT D
U N
IT A
U N
IT D
UNIT A
UNIT C
U N
IT
B U N
IT
A
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
D101A
FIRST FLOOR
DEMOLITION PLAN -
UNIT A
09.30.2026
DEMOLITION KEYED NOTES
1 REMOVE EXISTING MECHANICAL EQUIPMENT.
CORDINATE WITH MECHANICAL DRAWINGS. PREP FOR
NEW WORK.
2 REMOVE EXISTING WALL LOUVER. COORDINATE WITH
MECHANICAL. PREP FOR NEW WORK
3 REMOVE EXISTING CABINET HEATER CORDINATE WITH
MECHANICAL. PREP FOR NEW WORK.
4 SALVAGE EXISTING CARPET TILE AROUND MECHANICAL
EQUIPMENT FOR PATCH AND REPAIR
5 REMOVE EXISTING COUNTERTOPS AND PANEL
MOLDING. SALVAGE MOLDING FOR REUSE. CASEWORK
TO REMAIN. PREP FOR NEW SOLID SURFACE
COUNTERTOP MATERIAL.
6 REMOVE EXISTING FLOOR AND WALL BASE.
NO
TE
NR
TH 1/8" = 1'-0"
Dmo
WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY
WALL, FLOOR OR CEILING INCLUDES ALL GENERAL
MECHANICAL AND ELECTRICAL ITEMS WHICH ARE A PART
OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE
CONDITIONS AND DIMENSIONS AND BE RESPONSIBLE
FOR THE SAME. ADVISE ARCHITECT OF ANY AND ALL
DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING
CONSTRUCTION AND DEMOLITION AS REQUIRED. FINISH
TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND
DETAILS FOR ADDITIONAL INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND
ELECTRICAL PLANS FOR ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN
NEW CONSTRUCTION, IF REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED
ITEMS ATTACHED TO THE WALL ARE TO BE REMOVED.
SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
GENERAL DEMOLITION NOTESNO
TE
GYM
PERFORMING
ARTS
GYM COMMONS
CLASSROOM
GIRLS RR
BOYS RR
UPPER MECH
1 2
U N
IT B
U N
IT C
U N
IT
B U N
IT
A
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
D101B
FIRST FLOOR
DEMOLITION PLAN -
UNIT B
09.30.2026
DEMOLITION KEYED NOTES
1 REMOVE EXISTING MECHANICAL EQUIPMENT.
CORDINATE WITH MECHANICAL DRAWINGS. PREP FOR
NEW WORK.
2 REMOVE EXISTING WALL LOUVER. COORDINATE WITH
MECHANICAL. PREP FOR NEW WORK
3 REMOVE EXISTING CABINET HEATER CORDINATE WITH
MECHANICAL. PREP FOR NEW WORK.
4 SALVAGE EXISTING CARPET TILE AROUND MECHANICAL
EQUIPMENT FOR PATCH AND REPAIR
5 REMOVE EXISTING COUNTERTOPS AND PANEL
MOLDING. SALVAGE MOLDING FOR REUSE. CASEWORK
TO REMAIN. PREP FOR NEW SOLID SURFACE
COUNTERTOP MATERIAL.
6 REMOVE EXISTING FLOOR AND WALL BASE.
NO
TE
NR
TH 1/8" = 1'-0"
UNIT B DEMOLITION PLAN
WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY
WALL, FLOOR OR CEILING INCLUDES ALL GENERAL
MECHANICAL AND ELECTRICAL ITEMS WHICH ARE A PART
OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE
CONDITIONS AND DIMENSIONS AND BE RESPONSIBLE
FOR THE SAME. ADVISE ARCHITECT OF ANY AND ALL
DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING
CONSTRUCTION AND DEMOLITION AS REQUIRED. FINISH
TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND
DETAILS FOR ADDITIONAL INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND
ELECTRICAL PLANS FOR ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN
NEW CONSTRUCTION, IF REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED
ITEMS ATTACHED TO THE WALL ARE TO BE REMOVED.
SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
GENERAL DEMOLITION NOTESNO
TE
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
BOYS RR
GIRLS RR
CLASSROOM
CLASSROOM
COMMONS
CLASSROOM
CLASSROOM
CORRIDOR
1 2
1 2
1 2
1 2
1 2
UNIT A
UNIT C
U N
IT B
U N
IT C
U N
IT C
U N
IT D
U N
IT
C
U N
IT
D
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
D101C
FIRST FLOOR
DEMOLITION PLAN -
UNIT C
09.30.2026
DEMOLITION KEYED NOTES
1 REMOVE EXISTING MECHANICAL EQUIPMENT.
CORDINATE WITH MECHANICAL DRAWINGS. PREP FOR
NEW WORK.
2 REMOVE EXISTING WALL LOUVER. COORDINATE WITH
MECHANICAL. PREP FOR NEW WORK
3 REMOVE EXISTING CABINET HEATER CORDINATE WITH
MECHANICAL. PREP FOR NEW WORK.
4 SALVAGE EXISTING CARPET TILE AROUND MECHANICAL
EQUIPMENT FOR PATCH AND REPAIR
5 REMOVE EXISTING COUNTERTOPS AND PANEL
MOLDING. SALVAGE MOLDING FOR REUSE. CASEWORK
TO REMAIN. PREP FOR NEW SOLID SURFACE
COUNTERTOP MATERIAL.
6 REMOVE EXISTING FLOOR AND WALL BASE.
NO
TE
NR
TH 1/8" = 1'-0"
UNIT C DEMOLITION PLAN
WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY
WALL, FLOOR OR CEILING INCLUDES ALL GENERAL
MECHANICAL AND ELECTRICAL ITEMS WHICH ARE A PART
OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE
CONDITIONS AND DIMENSIONS AND BE RESPONSIBLE
FOR THE SAME. ADVISE ARCHITECT OF ANY AND ALL
DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING
CONSTRUCTION AND DEMOLITION AS REQUIRED. FINISH
TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND
DETAILS FOR ADDITIONAL INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND
ELECTRICAL PLANS FOR ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN
NEW CONSTRUCTION, IF REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED
ITEMS ATTACHED TO THE WALL ARE TO BE REMOVED.
SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
GENERAL DEMOLITION NOTESNO
TE
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
CLASSROOM
CLASSROOM
CORRIDOR
BOYS RR
GIRLS RR
OFFICE
OFFICE
STORAGE
UNIT A
UNIT D
U N
IT A
U N
IT D
U N
IT C
U N
IT D
U N
IT
C
U N
IT
D
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
D101D
FIRST FLOOR
DEMOLITION PLAN -
UNIT D
09.30.2026
DEMOLITION KEYED NOTES
1 REMOVE EXISTING MECHANICAL EQUIPMENT.
CORDINATE WITH MECHANICAL DRAWINGS. PREP FOR
NEW WORK.
2 REMOVE EXISTING WALL LOUVER. COORDINATE WITH
MECHANICAL. PREP FOR NEW WORK
3 REMOVE EXISTING CABINET HEATER CORDINATE WITH
MECHANICAL. PREP FOR NEW WORK.
4 SALVAGE EXISTING CARPET TILE AROUND MECHANICAL
EQUIPMENT FOR PATCH AND REPAIR
5 REMOVE EXISTING COUNTERTOPS AND PANEL
MOLDING. SALVAGE MOLDING FOR REUSE. CASEWORK
TO REMAIN. PREP FOR NEW SOLID SURFACE
COUNTERTOP MATERIAL.
6 REMOVE EXISTING FLOOR AND WALL BASE.
NO
TE
NR
TH 1/8" = 1'-0"
UNIT D DEMOLITION PLAN
R.D.
AHU OR RTU
ROOF DRAIN - TO REMAIN
ROOF TOP UNIT - TO REMAIN
1. EXISTING ROOF MEMBRANES WITHIN DEMOLITION AREAS
ARE AT OR NEAR END OF SERVICE LIFE WITH OBSERVED
DETERIORATION AT FLASHINGS, FASTENERS, AND
PENETRATIONS.
2. EXISTING ROOF SYSTEMS CONSIST OF EPDM AND
MODIFIED BITUMEN ASSEMBLIES OF VARYING AGE AND
CONDITION.
3. EXISTING ROOF INSULATION THICKNESS AND CONDITION
VARY; PERIMETER AND EDGE CONDITIONS TO BE FIELD
VERIFIED.
4. EXISTING ROOF DRAINS OBSERVED WITHIN DEMOLITION
AND RENOVATION AREAS; CONDITION AND ELEVATION
VARY.
5. EXISTING ROOF SYSTEM INFORMATION IS BASED ON
AVAILABLE ROOF ASSET DATA AND SELECTIVE
INVESTIGATION; SEE CONSULTANT REPORTS FOR
ADDITIONAL INFORMATION.
DEMOLITION PLAN LEGEND
ROOF DEMOLITION NOTES
EXISTING TO REMAIN
LG
ND
NO
TE
AREAS TO BE DEMOLISHED - SEE NOTES
E.F.
ACCU
EXHAUST FAN / HOOD - TO REMAIN
CONDENSING UNIT - TO REMAIN
M.C. MECHANICAL ROOF CURB - TO REMAIN
ROOF SLOPE
ROOF 1
ROOF 22: REMOVE AND REPLACE
REMOVE EXISTING ROOF MEMBRANE, INSULATION
(INCLUDING ANY WET OR SATURATED INSULATION),
FLASHINGS, AND ASSOCIATED COMPONENTS DOWN TO
EXISTING STRUCTURAL DECK WITHIN DEMOLITION AREA.
PREPARE SUBSTRATE FOR NEW ROOF CONSTRUCTION.
EXISTING STRUCTURAL DECK TO REMAIN.
REFER TO A102 FOR NEW WORK.
ROOF 1: REMOVE AND REPLACE
REMOVE EXISTING ROOF MEMBRANE, INSULATION
(INCLUDING ANY WET OR SATURATED INSULATION),
FLASHINGS, AND ASSOCIATED COMPONENTS DOWN TO
EXISTING STRUCTURAL DECK WITHIN DEMOLITION AREA.
PREPARE SUBSTRATE FOR NEW ROOF CONSTRUCTION.
EXISTING STRUCTURAL DECK TO REMAIN.
REFER TO A102 FOR NEW WORK.
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
D102
ROOF DEMOLITION
PLAN
09.30.2026
NR
TH 1/16" = 1'-0"
ROOF DEMOLITION PLAN
D
A D
RECEPTION/WAITING
PRINCIPAL
CONF. ROOMMAIL OFFICE
STAFF LOUNGE
ART ROOM ART ROOM
CAFETERIA
SERVING KITCHEN
GYM COMMONS
GIRLS RR
BOYS RR
UPPER MECH GYM
PERFORMING
ARTS
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM CLASSROOM
CLASSROOM
COMMONS
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
GIRLS RR
BOYS RR
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
CLASSROOM
CORRIDOR CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
LARGE GROUP
INSTRUCTION
BOYS RR
GIRLS RR
OFFICE
OFFICE
CLASSROOM CLASSROOM
MEDIA CENTER
UNIT A
UNIT D
U N
IT A
U N
IT D
UNIT A
UNIT C
U N
IT B
U N
IT C
U N
IT C
U N
IT D
U N
IT
C
U N
IT
D
U N
IT
B U N
IT
A
CEILING TO BE REMOVED
1. CEILINGS WITH HATCH BELOW ARE TO BE REMOVED IN ITS
ENTIRETY
2. REFER TO MECHANICAL, PLUMBING, ELECTRICAL OR
TECHNOLOGY DRAWINGS FOR REMOVAL OF EXISTING
DEVICES, DIFFUSERS, LIGHTINGS, ETC. AND OTHER WORK
RELATED TO DEMOLITION.
REFLECTED CEILING DEMOLITION LEGENDLG
ND
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
D201
FIRST FLOOR CEILING
DEMOLITION PLAN
09.30.2026
NR
TH 1/16" = 1'-0"
FIRST FLOOR REFLECTED CEILING PLAN
RECEPTION/WAITING
STAFF LOUNGE
VESTIBULE
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
OFFICE
OFFICE
GIRLS RR
BOYS RR
FLEX
INSTRUCTIONAL
CLASSROOM
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
INTERIOR
COURTYARD
MEDIA CENTER
LARGE GROUP
INSTRUCTION
CLASSROOM
CLASSROOM
ART ROOM
ART ROOM
CAFETERIA
SERVING KITCHEN
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
GIRLS RR
BOYS RR
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
GYM COMMONS
GYM
PERFORMING
ARTS
GIRLS RR
BOYS RR
UNIT A
UNIT D
U N
IT A
U N
IT D
UNIT A
UNIT C
U N
IT B
U N
IT C
U N
IT C
U N
IT D
U N
IT
C
U N
IT
D
U N
IT
B U N
IT
A
RR
JC
A101
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
11'
/1
NOT IN SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
1X
EXP.
Room name
LG
ND
FLOOR PLAN LEGEND
ROOM TAG
ROOM NUMBER
ROOM NAME
EXPOSED CEILING
DOOR TAG
DOOR TAG NUMBER
CORRESPONDS TO THE
ROOM IN WHICH IT IS USED
THE DECIMAL NUMBER
REFERS TO DIFFERENT
DOORS IN THE SAME ROOM
WALL TAG
WALL TYPE
WALL FIRE RATING
NO
TE
FLOOR PLAN NOTES
1. REFER TO FINISH PLANS FOR FINISH INTENT.
2. REFER TO CODE COMPLIANCE PLANS FOR WALL RATINGS.
TOILET ACCESSORY TAG
ACCESSORY TYPE 1t
CLASSROOM
716 SF
Break metal pipe chase
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
A101
FIRST FLOOR PLAN
09.30.2026
NR
TH 1/16" = 1'-0"
FIRST FLOOR PLAN
FLOOR PLAN KEYED NOTES
1 COUNTERTOP, NEW SOLID SURFACE. CASEWORK
TO REMAIN
2 SALVAGE EXISTING CARPET TILE FOR PATCH AND
REPAIR AROUND NEW HUV UNIT
3 NEW HORIZONTAL UNIT VENTILATOR.
COORDINATE WITH MECHANICAL DRAWINGS.
4 NEW WALL LOUVER IN EXISTING OPENING.
COORDINATE WITH MECHANICAL DRAWINGS.
NO
TE
1/4" = 1'-0"1 TYPICAL CLASSROOM
1X
EXP.
Room name
LG
ND
FLOOR PLAN LEGEND
ROOM TAG
ROOM NUMBER
ROOM NAME
EXPOSED CEILING
DOOR TAG
DOOR TAG NUMBER
CORRESPONDS TO THE
ROOM IN WHICH IT IS USED
THE DECIMAL NUMBER
REFERS TO DIFFERENT
DOORS IN THE SAME ROOM
WALL TAG
WALL TYPE
WALL FIRE RATING
NO
TE
FLOOR PLAN NOTES
1. REFER TO FINISH PLANS FOR FINISH INTENT.
2. REFER TO CODE COMPLIANCE PLANS FOR WALL RATINGS.
TOILET ACCESSORY TAG
ACCESSORY TYPE 1t
UNIT A
UNIT D
U N
IT A
U N
IT D
UNIT A
UNIT C
RECEPTION/WAITING
878 SF
RR
47 SF
VESTIBULE
153 SF
109 SF
PRINCIPAL
184 SF
OFFICE
146 SF
FILE
65 SF
RR
37 SF
CONF. ROOM
205 SF
OFFICE
112 SF
STAFF LOUNGE
436 SF
ART ROOM
1149 SF
ART ROOM
Redundant Room
KILN
86 SF
CAFETERIA
2261 SF
SERVING
302 SF
KITCHEN
402 SF
DISHES
93 SF
COOLER
41 SF
STORAGE
65 SF
CLASSROOM
686 SF
LARGE GROUP
INSTRUCTION
1354 SF
MEDIA CENTER
1812 SF
CLASSROOM
647 SF
CLASSROOM
676 SF
OFFICE
132 SF COPY
115 SF
STAIR
58 SF
JC
128 SF
IT
79 SF
RR
50 SF
SAFE ROOM
44 SF
BROADCAST
95 SF
WORK ROOM
121 SF
AV STORAGE
117 SF130
CLASSROOM
705 SF
BOYS RR
187 SF
GIRLS RR
206 SF
CLASSROOM
676 SF
CLASSROOM
661 SF
U N
IT
B U N
IT
A
4 3
NOT IN SCOPE
2 2
2 2
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
A101A
FIRST FLOOR PLAN -
UNIT A
09.30.2026
FLOOR PLAN KEYED NOTES
1 COUNTERTOP, NEW SOLID SURFACE. CASEWORK
TO REMAIN
2 SALVAGE EXISTING CARPET TILE FOR PATCH AND
REPAIR AROUND NEW HUV UNIT
3 NEW HORIZONTAL UNIT VENTILATOR.
COORDINATE WITH MECHANICAL DRAWINGS.
4 NEW WALL LOUVER IN EXISTING OPENING.
COORDINATE WITH MECHANICAL DRAWINGS.
NO
TE
NR
TH 1/8" = 1'-0"
UNIT A FLOOR PLAN
UNIT A
KEY PLAN
N.T.S.
EXP.
Room name
LG
ND
FLOOR PLAN LEGEND
ROOM TAG
ROOM NUMBER
ROOM NAME
EXPOSED CEILING
DOOR TAG
DOOR TAG NUMBER
CORRESPONDS TO THE
ROOM IN WHICH IT IS USED
THE DECIMAL NUMBER
REFERS TO DIFFERENT
DOORS IN THE SAME ROOM
WALL TAG
WALL TYPE
WALL FIRE RATING
NO
TE
FLOOR PLAN NOTES
1. REFER TO FINISH PLANS FOR FINISH INTENT.
2. REFER TO CODE COMPLIANCE PLANS FOR WALL RATINGS.
TOILET ACCESSORY TAG
ACCESSORY TYPE 1t
U N
IT B
U N
IT C
CLASSROOM
912 SF
UPPER MECH
398 SF
BOYS RR
249 SF
GIRLS RR
237 SF
GYM COMMONS
1812 SF
GYM STOR.
134 SF
GYM
5029 SF 85
CHOIR STOR.
128 SF
OFFICE
129 SF
PRACTICE
67 SF
PRACTICE
79 SF
PERFORMING
ARTS
1135 SF
PRACTICE
130 SF
MUSIC STORAGE
222 SF
RR
51 SF
JC
54 SF
NOT IN SCOPE
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
A101B
FIRST FLOOR PLAN -
UNIT B
09.30.2026
FLOOR PLAN KEYED NOTES
1 COUNTERTOP, NEW SOLID SURFACE. CASEWORK
TO REMAIN
2 SALVAGE EXISTING CARPET TILE FOR PATCH AND
REPAIR AROUND NEW HUV UNIT
3 NEW HORIZONTAL UNIT VENTILATOR.
COORDINATE WITH MECHANICAL DRAWINGS.
4 NEW WALL LOUVER IN EXISTING OPENING.
COORDINATE WITH MECHANICAL DRAWINGS.
NO
TE
NR
TH 1/8" = 1'-0"
UNIT B FLOOR PLAN
UNIT B
KEY PLAN
EXP.
Room name
LG
ND
FLOOR PLAN LEGEND
ROOM TAG
ROOM NUMBER
ROOM NAME
EXPOSED CEILING
DOOR TAG
DOOR TAG NUMBER
CORRESPONDS TO THE
ROOM IN WHICH IT IS USED
THE DECIMAL NUMBER
REFERS TO DIFFERENT
DOORS IN THE SAME ROOM
WALL TAG
WALL TYPE
WALL FIRE RATING
NO
TE
FLOOR PLAN NOTES
1. REFER TO FINISH PLANS FOR FINISH INTENT.
2. REFER TO CODE COMPLIANCE PLANS FOR WALL RATINGS.
TOILET ACCESSORY TAG
ACCESSORY TYPE 1t
UNIT A
UNIT C
U N
IT B
U N
IT C
U N
IT C
U N
IT D
CLASSROOM
661 SF
CLASSROOM
673 SF
COMMONS
661 SF
CLASSROOM
661 SF
CLASSROOM
716 SF
GIRLS RR
270 SF
BOYS RR
273 SF
RR
52 SF
JC
66 SF
CLASSROOM
710 SF
CLASSROOM
705 SF
CLASSROOM
835 SF
CLASSROOM
861 SF
BREAK OUT
166 SF
BREAK OUT
124 SF
RR
87 SF
CLASSROOM
723 SF
CLASSROOM
912 SF
CORRIDOR
822 SF
U N
IT
C
U N
IT
D
NOT IN SCOPE
NOT IN SCOPE
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
A101C
FIRST FLOOR PLAN -
UNIT C
09.30.2026
FLOOR PLAN KEYED NOTES
1 COUNTERTOP, NEW SOLID SURFACE. CASEWORK
TO REMAIN
2 SALVAGE EXISTING CARPET TILE FOR PATCH AND
REPAIR AROUND NEW HUV UNIT
3 NEW HORIZONTAL UNIT VENTILATOR.
COORDINATE WITH MECHANICAL DRAWINGS.
4 NEW WALL LOUVER IN EXISTING OPENING.
COORDINATE WITH MECHANICAL DRAWINGS.
NO
TE
NR
TH 1/8" = 1'-0"
FIRST FLOOR PLAN
UNIT C
KEY PLAN
EXP.
Room name
LG
ND
FLOOR PLAN LEGEND
ROOM TAG
ROOM NUMBER
ROOM NAME
EXPOSED CEILING
DOOR TAG
DOOR TAG NUMBER
CORRESPONDS TO THE
ROOM IN WHICH IT IS USED
THE DECIMAL NUMBER
REFERS TO DIFFERENT
DOORS IN THE SAME ROOM
WALL TAG
WALL TYPE
WALL FIRE RATING
NO
TE
FLOOR PLAN NOTES
1. REFER TO FINISH PLANS FOR FINISH INTENT.
2. REFER TO CODE COMPLIANCE PLANS FOR WALL RATINGS.
TOILET ACCESSORY TAG
ACCESSORY TYPE 1t
UNIT A
UNIT D
U N
IT A
U N
IT D
U N
IT C
U N
IT D
AV STORAGE
117 SF130
CLASSROOM
705 SF
BOYS RR
187 SF
GIRLS RR
206 SF
OFFICE
147 SF
CLASSROOM
704 SF
CLASSROOM
705 SF
CLASSROOM
701 SF
CLASSROOM
725 SF
OFFICE
180 SF
STORAGE
136 SF
CLASSROOM
766 SF
CLASSROOM
841 SF
FLEX
INSTRUCTIONAL
CLASSROOM
769 SF
CLASSROOM
735 SF
RAMP
194 SF
WORK AREA
61 SF
J.C.
75 SF
FLEX
INSTRUCTIONAL
CLASSROOM
1140 SF
FLEX
INSTRUCTIONAL
CLASSROOM
1184 SF
RR
32 SF
COAT ROOM
121 SF
U N
IT
C
U N
IT
D
3 4
CLASSROOM
704 SF
NOT IN SCOPE
2 2
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
A101D
FIRST FLOOR PLAN -
UNIT D
09.30.2026
FLOOR PLAN KEYED NOTES
1 COUNTERTOP, NEW SOLID SURFACE. CASEWORK
TO REMAIN
2 SALVAGE EXISTING CARPET TILE FOR PATCH AND
REPAIR AROUND NEW HUV UNIT
3 NEW HORIZONTAL UNIT VENTILATOR.
COORDINATE WITH MECHANICAL DRAWINGS.
4 NEW WALL LOUVER IN EXISTING OPENING.
COORDINATE WITH MECHANICAL DRAWINGS.
NO
TE
NR
TH 1/8" = 1'-0"
UNIT D FLOOR PLAN
UNIT D
KEY PLAN
R.D.
AHU OR RTU
ROOF DRAIN - TO REMAIN
ROOF TOP UNIT - TO REMAIN
1. ROOF WORK IS LIMITED TO AREAS INDICATED ON THE
DRAWINGS.
2. EXISTING ROOF AREAS NOT INDICATED FOR WORK SHALL
REMAIN.
3. TYPICAL ROOF SLOPE 1/4" / 1'-0" UNLESS NOTED
OTHERWISE.
4. PROVIDE ROOFING MANUFACTURER'S STANDARD
ROOFING TERMINATION DETAILS AT ALL PARAPETS, PRE-
MANUFACTURED ROOF EDGE SYSTEMS, CURBS, PIPE
PENETRATIONS, ETC.
5. PROVIDE CRICKETS AS REQUIRED AT MECHANICAL UNITS,
VENTS, AND SIMILAR PROJECTIONS TO PROMOTE POSITIVE
DRAINAGE.
6. ROOF DETAILS SHOWN ARE TYPICAL AND INTENDED TO
ILLUSTRATE GENERAL ROOF ASSEMBLY AND FLASHING
CONDITIONS. FINAL ROOF SYSTEM COMPONENTS AND
CONFIGURATIONS SHALL BE COORDINATED WITH
MANUFACTURER REQUIREMENTS AND FIELD CONDITIONS.
7. PROVIDE ROOF CURBS, FLASHINGS, AND SUPPORTS AS
REQUIRED FOR ROOFTOP EQUIPMENT AFFECTED BY ROOF
WORK.
8. ALL EXISTING ROOF PENETRATIONS REMOVED AS PART OF
THE WORK SHALL BE PATCHED AND MADE WATERTIGHT
TO MATCH ADJACENT ROOF CONDITIONS.
9. SLOPE AND DRAINAGE PATTERNS SHOWN ARE
DIAGRAMMATIC AND INTENDED TO ILLUSTRATE DESIGN
INTENT. FINAL TAPERED INSULATION LAYOUT SHALL BE BY
ROOFING CONTRACTOR.
ROOF PLAN LEGEND
ROOF GENERAL NOTES
60 MIL, FULLY ADHERED, SINGLE PLY
ROOF MEMBRANE ON MIN 5"
POLYISOCYANURATE ROOF INSULATION.
INITIAL SRI : 82
EXISTING TO REMAIN
LG
ND
NO
TE
FLUID-APPLIED ROOF
RESTORATION SYSTEM
E.F.
ACCU
EXHAUST FAN / HOOD - TO REMAIN
CONDENSING UNIT - TO REMAIN
M.C. MECHANICAL ROOF CURB - TO REMAIN
R.C. ROUND CURB PENETRATION - TO REMAIN
ROOF SLOPE
ROOF 1: REMOVE AND REPLACE
INSTALL NEW ROOF ASSEMBLY INCLUDING CONTINUOUS INSULATION, ROOF MEMBRANE,
FLASHINGS, AND ACCESSORIES AS REQUIRED FOR A COMPLETE AND WARRANTABLE ROOF
SYSTEM. ROOF ASSEMBLY SHALL BE DESIGNED TO MEET APPLICABLE ENERGY CODE AND
DRAINAGE REQUIREMENTS.
VERIFY ROOF DRAIN LOCATIONS, PARAPET HEIGHTS, AND EDGE METAL COMPATIBILITY WITH
FINAL ROOF ASSEMBLY THICKNESS AND DRAINAGE CONDITIONS. MODIFY OR EXTEND AS
REQUIRED FOR CODE COMPLIANCE AND MANUFACTURER REQUIREMENTS.ROOF 1
R.D.
RTU
ROOF 22: REMOVE AND REPLACE
INSTALL NEW ROOF ASSEMBLY INCLUDING CONTINUOUS INSULATION, ROOF MEMBRANE,
FLASHINGS, AND ACCESSORIES AS REQUIRED FOR A COMPLETE AND WARRANTABLE ROOF
SYSTEM. ROOF ASSEMBLY SHALL BE DESIGNED TO MEET APPLICABLE ENERGY CODE AND
DRAINAGE REQUIREMENTS.
VERIFY ROOF DRAIN LOCATIONS, PARAPET HEIGHTS, AND EDGE METAL COMPATIBILITY WITH
FINAL ROOF ASSEMBLY THICKNESS AND DRAINAGE CONDITIONS. MODIFY OR EXTEND AS
REQUIRED FOR CODE COMPLIANCE AND MANUFACTURER REQUIREMENTS.
A102
Sim
A102
Sim
A102
Sim
R.D.
RTU
A102
Sim
UNIT A
UNIT C
U N
IT
C
U N
IT
D
U N
IT C
U N
IT D
U N
IT A
U N
IT D
UNIT A
UNIT D
U N
IT
A
U N
IT
B
U N
IT B
U N
IT C
A102
Sim
A102
Sim
A102
Sim
ROOF DECK
ROOF
INSULATION
FLASHING PER ROOF
MANUFACTURERS
STANDARD DETAILS
VENT PIPE
CONTINOUS SEALANT
SINGLE PLY ROOFING
STAINLESS STEEL FLASHING AND
COUNTER FLASHING - TURN UP AND
SECURE TO MASONRY WALL @ 12"
O.C. - PROVIDE CONTINUOUS SEALANT
@ TOP EDGE
MEMBRANE ROOF SYSTEM OVER
COVER BOARD ON 2 LAYERS OF 2 1/2"
RIGID INSULATION (STAGGER JOINTS)
1" CAVITY FILLER NET MATERIAL
EXISTING STEEL ROOF DECK
EXISTING STRUCTURE
EXIST. WALL
MEMBRANE
CONTINUES
INTO ROOF
DRAIN
ROOF DRAIN
14 GAGE COATED
STEEL BEARING PAN
FURNISHED WITH
ROOF DRAIN
CLAMPING RING FURNISHED
WITH ROOF DRAIN
1 1/2" METAL DECK
REINFORCED AT OPENING
WITH 3"x3"x1/4" STEEL ANGLES
MEMBRANE ROOFING ON RIGID
INSULATION, TAPER TO DRAIN
/2
CENTER LINE OF VALLEY
OF FINISHED ROOF
1" THICK
INSULATION
PIPE INSULATION ON
DRAIN LEADERS
ROOF STRUCTURE (REFER
TO STRUCTURAL)
TREATED NAILERS AS REQUIRED
ROOF DECK
CANT STRIP
11/2" RIGID INSULATION
PREFAB ROOF CURB
COUNTER FLASHING WITH
APPROVED SEALING
WASHER AND FASTENER
@ 6" O.C.
ROOF MOUNTED EQUIPMENT
TREATED 2"x4" NAILER
M
IN
LAP SEALANT
MEMBRANE ROOF
EXISTING ROOF DECK
TREATED NAILERS AS
REQUIRED FOR ATTACHMENT
EXISTING ROOF DECK
EXISTING WALL
EXISTING WALL CONSTRUCTION
EXISTING INSULATION
EXISTING ROOF MEMBRANE
RIGID POLYISO INSULATION
COVER BOARD
ROOF MEMBRANE
PREFINISHED METAL COPING
SYSTEM SIZE FOR NEW ROOF
ASSEMBLY THICKNESS
NEW PREFABRICATED INSULATED
METAL ROOF CURB
FASTEN TO STRUCTURAL DECK PER
ENGINEER / MFR REQUIREMENTS
P.T Blocking 2x12
P.T Blocking 2x4
ALUMINUM DRIP EDGE TO
MATCH EXISTING PROFILE
RIGID POLYISO INSULATION
(BASE & TAPERED) OVER
EXISTING ROOF DECK.
ROOF MEMBRANE
EXTEND MEMBRANE PER
MFR. REQUIREMENTS
NEW 1/2" COVER BOARD
(HIGH DENSITY RIGID INSUL.)
OVER TAPERED INSULATION
EXISTING WALL
EXISTING ROOF DECK
P.T Blocking 2x12
P.T Blocking 2x4
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
A102
ROOF PLAN
09.30.2026
NR
TH 1/16" = 1'-0"
ROOF PLAN
1 1/2" = 1'-0"5 TYPICAL ROOF PENETRATION
1 1/2" = 1'-0"1 ROOF TO WALL DETAIL
1 1/2" = 1'-0"2 ROOF DRAIN DETAIL
1 1/2" = 1'-0"6 TYPICAL ROOF CURB DETAIL
1 1/2" = 1'-0"4 ROOF CURB DETAIL AT EPDM TRANSITION
1 1/2" = 1'-0"3 PARAPET CAP MEMBRANE DETAIL
UNIT A
UNIT D
U N
IT A
U N
IT D
UNIT A
UNIT C
U N
IT B
U N
IT C
U N
IT C
U N
IT D
U N
IT
C
U N
IT
D
U N
IT
B U N
IT
A
FLEX
INSTRUCTIONAL
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
FLEX
INSTRUCTIONAL
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CORRIDOR CORRIDOR COMMONS
CLASSROOM
CLASSROOM
GIRLS RR
BOYS RR
CLASSROOM
CLASSROOM
CLASSROOM
BREAK OUT
CLASSROOM
BREAK OUTRR
CLASSROOMCLASSROOM
CLASSROOMCLASSROOM
CLASSROOM
UPPER MECH
GYM COMMONS
GYM
PERFORMING
ARTS
OFFICE
GIRLS RR
BOYS RR
COPYOFFICE
JCJC
CLASSROOMCLASSROOM
KITCHEN
SERVING
CAFETERIA
ART ROOM
ART ROOMSTAFF LOUNGE
RECEPTION/WAITING
CONF. ROOMMAIL OFFICE
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
STORAGE
OFFICE
CLASSROOM CLASSROOM
BOYS RR
GIRLS RR
OFFICE
MEDIA CENTERLARGE GROUP
INSTRUCTION
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
GYPSUM BOARD
ACP01: 24' x 24' LAY-IN ACOUSTICAL
TILE GRID
1. REFER TO MATERIAL SELECTION SCHEDULE FOR CEILING
SELECTIONS.
2. WHERE CEILING TILE IS LESS THAN 3" AT PERIMETER OF
ROOM PROVIDE A CUT 2x4 TILE IN LIEU OF FULL 2x2 TILE AND SMALL PIECE OF TILE OR DOUBLE GRID - MATCH 2x2
FOR STYLE AND COLOR.
3. AT AREAS OF EXPOSED CEILING PAINT ALL STRUCTURE,
DUCTWORK, PIPING, CONDUIT, HANGERS ETC.,
COORDINATE WITH MECHANICAL, ELECTRICAL AND
PLUMBING SPECIFICATIONS. REFER TO THE REFLECTED
CEILING PLANS FOR PAINT COLORS.
REFLECTED CEILING LEGEND
GENERAL NOTES - REFLECTED CEILINGS
ACP02: 24' x 48' LAY-IN ACOUSTICAL
TILE GRID
1t Y X 1'-0"
CEILING HEIGHT ABOVE
FINISHED FLOOR
CEILING FINISH TYPE
CEILING FINISH INSTANCE
LG
ND
NO
TE
INFILL WITH NEW CEILING TILES AND GRID TO
MATCH EXISTING ADJACENT TILES
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
A201
FIRST FLOOR
REFLECTED CEILING
PLAN
09.30.2026
NR
TH 1/16" = 1'-0"
FIRST FLOOR REFLECTED CEILING PLAN
BULKHEAD TO BE
PAINTED, P03. IN MEDIA
CENTER PAINT BAND TO
CONTINUE AROUND
WALL PERIMETER AT
CEILING REPLACING
"HUNTER GREEN"
VCT-0 CPT-0
WALL FINISH
FLOOR BASE
FLOOR FINISH
COUNTER FINISH
CABINET FINISH (BASE AND UPPER)
INDICATES EXTENT OF ATYPICAL FINISH
INDICATES FLOOR MATERIAL TRANSITION
NOTE - REFER TO MATERIAL SELECTION
SCHEDULE REMARKS FOR FLOOR
TRANSITION TYPE
REFER TO MATERIAL
SELECTION SCHEDULE FOR
FINISH INFORMATION
PL0#
P0#
PTB0#
CPTL0#
P0#
INDICATES MULTIPLE MATERIAL TYPES ON A
SURFACE. REFER TO DETAIL OR ELEVATIONS.
INDICATES MATERIAL PATTERN. REFER TO
DETAILS
MULTI
- P
FINISH PLAN LEGENDLG
ND
MANUAL ROLLER SHADE, PEARL/LINEN,
E SCREEN 3% OPEN
WT0#
INDICATES MATERIAL PATTERN DIRECTION
ETR CPT
ETR CPT
CPT ETR
C P
T E
TR
P-P
RB01
CPT02
WP01
SSM01
WP01
COVER FACE OF BUILT-IN
BENCH ONLY
EXISTING MOLDING TO BE
SALVAGED, STAINED WS01, AND
REINSTALLED. SOME PATCH AND
REPAIR REQUIRED
P-P
RB01
CPT02
P-P
RB01
CPT02
EXISTING SHELVING TO
REMAIN AS IS. PROTECT
IN PLACE.
ETR
ETR
ETR
RB01
CPT03
P
NO PAINT SCOPE. OWNER
RESPONSIBLE FOR MATERIAL
AND LABOR TO THIS AREA
PATCH IN ATTIC STOCK
AND WALL BASE
WT01
CARPET TILE TO SEALED OR POLISHED
CONCRETE (CPT - SC - PC)
CARPET TILE
JOHNSONITE REDUCER, FINISH: COOL METAL VL4
_______SEALED OR POLISHED
CONCRETE
1. REFER TO SHEET I001 FOR ADDITIONAL INFORMATION ON
INTERIOR MATERIALS.
2. REFER TO REFLECTED CEILING PLANS FOR CEILING FINISH AND
HEIGHTS.
3. REFER TO DOOR SCHEDULE FOR FINISH ON DOORS AND FRAMES.
4. FINISH TAGS APPLY TO LIKE MATERIALS IN ENTIRE ROOM. I.E.
CASEWORK TAG MAY ONLY CALLOUT ONE RUN OF CASEWORK,
BUT ALL CASEWORK IN ROOM RECEIVE THE SAME FINISHES,
UNLESS TAGGED DIFFERENTLY.
5. CASEWORK FINISH TAGS DO NOT APPLY TO CUSTOM MILLWORK
PIECES. REFER TO ENLARGED MILLWORK DETAILS FOR FINISH
MATERIALS.
6. WALL MOUNTED DIFFUSERS, GRILLES, ACCESS PANELS,
ELECTRICAL PANELS, ETC. ARE TO BE PAINTED WITH AN OIL-BASED
PAINT TO MATCH THE ADJACENT WALL FINISH.
7. CEILING ACCESS PANELS ARE TO BE PAINTED TO MATCH
ADJACENT CEILING FINISH.
8. ALL FLOORING TRANSITIONS TO OCCUR CENTERED UNDERNEATH
FLOOR LEAF.
9. REFER TO SHEET I101 FOR MATERIAL TRANSITIONS.
10. REFER TO SPECIFICATION FOR MORE INFORMATION.
11. REFER TO FLOOR PLANS, EXTERIOR ELEVATIONS AND FRAME
TYPES FOR HEIGHT AND WIDTH OF OPENINGS.
12. VERIFY ALL DIMENSIONS IN FIELD PRIOR TO FABRICATION.
GENERAL NOTES - INTERIORSNO
TE
3" = 1'-0"3 TYPICAL FLOOR TRANSITION DETAILS
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
E al y E le m en ta ry W h it eh al l D is tr ic t S ch o o ls
E
S o p h ia S t, W h it e h a ll
, M I
PROJECT NO. 25.147
I101
FIRST FLOOR FINISH
PLAN
09.30.2026
NR
TH 1/8" = 1'-0"1 FIRST FLOOR FINISH PLAN
NR
TH 1/8" = 1'-0"2 FIRST FLOOR FINISH PLAN TYP CLASSROOM
MATERIAL SELECTION SCHEDULE
ABBREV ITEM MANUFACTURER PATTERN COLOR PRODUCT NO. SIZE REMARKS PRODUCT REP.
ACP01 ACOUSTIC CEILING PANEL ARMSTRONG CORTEGA ANGLED TEGULAR EDGE WHITE 704A 24" X 24" BUILDING STANDARD, 15/16" GRID
ACP02 ACOUSTIC CEILING PANEL USG CEILINGS RADAR SQUARE EDGE WHITE 2410 24" X 48" BUILDING STANDARD
CPT02 CARPET TILE SHAW CONTRACT HEX LINEAR SHIFT CHARCOAL TWEED 5T056 24" X 24" PATTERN DISCONTINUED, ORDER MINIMUM REQUIRED. ASHLAR
INSTALL. SEE FINISH PLAN FOR LOCATION
ASHLEY HAZEL, SHAW CONTRACT //
ashley.hazel@shawcontract.com, 616-980-7391
CPT03 CARPET TILE INTERFACE HAPPENING TOTAL RECALL
1463202500 24" X 24' PATTERN DISCONTINUED, ORDER MINIMUM REQUIRED. ATTIC
STOCK TO BE USED FIRST FOR PATCH AND REPAIR AROUND HUV
INSTALLATION. MATCH EXISTING INSTALL PATTERN
SHELBE OGBURN, INTERFACE //
Shelbe.Ogburn@interface.com, 616-370-6087
ETR EXISITING TO REMAIN -- -- -- -- -- PROTECT IN PLACE
P01 EPOXY PAINT (FIELD) SHERWIN WILLIAMS PRO INDUSTRIAL HIGH PERFORMANCE EPOXY MINDFUL GRAY SW 7016 -- SHEEN: SATIN
P02 EPOXY PAINT (FIELD) SHERWIN WILLIAMS PRO INDUSTRIAL HIGH PERFORMANCE EPOXY SNOWBOUND SW 7004 -- SHEEN: SATIN
P03 EPOXY PAINT (ACCENT) SHERWIN WILLIAMS PRO INDUSTRIAL HIGH PERFORMANCE EPOXY POSITIVE RED SW 6871 -- SHEEN: SATIN
P04 EPOXY PAINT (ACCENT) SHERWIN WILLIAMS PRO INDUSTRIAL HIGH PERFORMANCE EPOXY GRIZZLE GRAY SW 7068 -- SHEEN: SATIN
P-P PAINT PATTERN SHERWIN WILLIAMS BASE PAINT TO BE P01, 6" BAND OF P03 AT TOP
OF WALL, 4" BAND OF P04 RIGHT BELOW
VARIES -- --
RB01 RUBBER BASE JOHNSONITE BASEWORKS THERMOSET RUBBER (TYPE TS) COOL METAL VL4 -- 4"H
SSM01 SOLID SURFACE MATERIAL CORIAN EASED EDGE SILVER BIRCH DS95602X2SV
WP01 WALL PROTECTION 3M DI-NOC
ARCHITECTURAL
FINISHES
WOOD GRAIN PALETTE OAK STRAIGHT
GRAIN
WG-2442 48" X 54 YDS MATERIAL APPLIED TO EXISTING VENEER CASEWORK,
INSTALLER TO PREP SURFACE ACCORDING TO MANUFACTURER
RECOMMEDATION
WS01 WOOD STAIN BOD: SHERWIN
WILLIAMS MINWAX
-- HABITAT MW427 -- STAIN APPLIED TO MOLDING AT RESOURCE DESK ONLY.
COORDINATE WITH WP01. SAMPLE TO SUBMITTED TO PURE
ARCHITECTS FOR APPROVAL
WT01-A3 ALTERNATE: WINDOW
TREATMENT - MANUAL
ROLLER SHADE
BOD: MERMET/DRAPER E SCREEN 3% OPEN PEARL/LINEN -- -- PRICE AS ALTERNATE: FACIA TO BE BLACK OR BRONZE, MATCH
IN FIELD TO WINDOW FRAME FINISH
AD AD
T
T
T T
T T
T
T
UNIT A
UNIT D
UNIT AUNIT D
UNIT A
UNIT C
UNIT
BUNIT
A
RECEPTION/WAITING
PRINCIPAL
3 OFFICE
FILE
RR
STAFF LOUNGE
OFFICE
CONF. ROOM
RR
CL
VESTIBULE
CLASSROOM
CLASSROOM
CLASSROOM
BOYS RR
GIRLS RR
ART ROOM
ART ROOM
KILN
JC
STAIR
41COPY
IT
SAFE ROOM
OFFICE
RR
CLASSROOM
CLASSROOM
BROADCAST
WORK ROOM
MEDIA CENTER
AV STORAGE
LARGE GROUP
INSTRUCTION
CAFETERIA
SERVING
KITCHEN
COOLER
STORAGE
DISHES
CLASSROOM
CLASSROOM
EX UV EX UV
EX UV
EX UV EX UV
EX UV
REMOVE EX
UV - TYP
1 1
1 1
EX BC
REMOVE EX
BLOWER COIL
REMOVE EX FT
REMOVE EX UH
REMOVE AHU
EX 24"/36"
EX AH
EX S/A DUCTWORK
TO REMAIN - TYP
EX R/A GRILLE
AND ASSOCIATED
DUCTWORK TO
REMAIN
EX O/A LOUVER
AND ASSOCIATED
DUCTWORK TO
REMAIN
EX 12"/12"
R/A
EX 12"/12"
S/A
REMOVE EX SLOT
DIFFUSER - TYP
6 6
REMOVE EX
TRANSFER AIR
GRILLE
EX S/A DIFFUSERS
AND ASSOCIATED
DUCTWORK TO
REMAIN - TYP
EX T/A GRILLES AND
ASSOCIATED
DUCTWORK TO
REMAIN - TYP
EX 30"/12"
EX 24"/20"
EX 16"/12"
L/S L/S
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
Copyright © 2026 Millies Engineering Group
Ea ly
E le m en ta ry
W hi te ha ll D is tr ic t S ch oo ls
E
S o p h ia S t, W h it eh al l, M
I 4
PROJECT NO. 25.147
MECHANICAL DEMOLITION
FIRST FLOOR PLAN - UNIT
A
09.30.2026
NR
TH 1/8" = 1'-0"
MECHANICAL DEMOLITION FLOOR PLAN - UNIT A
UNIT A
KEY PLAN
N.T.S.
SHEET NOTES
1 REMOVE EXISTING UNIT VENTILATOR AND ASSOCIATED
STEAM/CONDENSATE PIPING, OUTSIDE AIR INTAKE
LOUVER, THERMOSTAT, CONTROLS, ELECTRICAL
CONNECTIONS, ETC. COMPLETE AS REQUIRED. CUT
AND PERMANENTLY CAP PIPING FLUSH WITH OR
BELOW FINISHED FLOOR ELEVATION; ABANDON
REMAINING PIPING IN TUNNELS.
2 REMOVE EXISTING STEAM BLOWER COIL AND
ASSOCIATED THERMOSTAT, STEAM/CONDENSATE PIPE,
SUPPLY AND RETURN DUCT AND DIFFUSERS,
CONTROLS, ELECTRICAL CONNECTIONS, ETC.
COMPLETE AS REQUIRED. CUT AND PERMANENTLY CAP
PIPING FLUSH WITH OR BELOW FINISHED FLOOR
ELEVATION; ABANDON REMAINING PIPING IN TUNNELS.
3 REMOVE EXISTING FIN TUBE AND ASSOCIATED
STEAM/CONDENSATE PIPING, THERMOSTATS AND
CONTROL WIRING COMPLETE AS REQUIRED. CUT AND
PERMANENTLY CAP PIPING FLUSH WITH OR BELOW
FINISHED FLOOR ELEVATION; ABANDON REMAINING
PIPING IN TUNNELS.
4 REMOVE EXISTING UNIT HEATER AND ASSOCIATED
STEAM/CONDENSATE PIPING, THERMOSTAT,
CONTROLS, ELECTRICAL CONNECTIONS, ETC.
COMPLETE AS REQUIRED. CUT AND PERMANENTLY CAP
PIPING FLUSH WITH OR BELOW FINISHED FLOOR
ELEVATION; ABANDON REMAINING PIPING IN TUNNELS.
5 REMOVE EXISTING AIR HANDLING UNIT AND
ASSOCIATED DUCTWORK, STEAM/CONDENSATE PIPING,
THERMOSTAT, CONTROLS, ELECTRICAL CONNECTIONS,
ETC. COMPLETE AS REQUIRED. CUT AND
PERMANENTLY CAP PIPING FLUSH WITH OR BELOW
FINISHED FLOOR ELEVATION; ABANDON REMAINING
PIPING IN TUNNELS.
6 REMOVE EXISTING SLOT SUPPLY AIR DIFFUSER AND
ASSOCIATED DUCTWORK COMPLETE AS REQUIRED.
TEST EXISTING SUPPLY AIR DIFFUSER AIRFLOW
CAPACITY PRIOR TO WORK. SUBMIT TEST REPORT FOR
REVIEW.
7 REMOVE EXISTING TRANSFER AIR GRILLE AND
ASSOCIATED DUCTWORK COMPLETE AS REQUIRED.
UNIT BUNIT C
UNIT
BUNIT
A
STAIR
CLASSROOM
UPPER MECH
BOYS RR
GIRLS RR
GYM
CHOIR STOR.
GYM STOR.
GYM COMMONS
JC
MUSIC STORAGE
PRACTICE
PERFORMING
ARTS
PRACTICE
PRACTICE
OFFICE
RR
EX B EX B
REMOVE EX STEAM
BOILER - TYP
REMOVE EX FT
REMOVE EX BOILER
FLUE -TYP
EX P
REMOVE EX STEAM
CONDENSATE PUMP
EX LPS
EX LPS/LCR PIPE TO
BE ABANDONED IN
TUNNELS - TYP
EX GAS PIPE
REMOVE EXISTING PORTION OF
GAS PIPING REQUIRED FOR
INSTALLATION OF NEW BOILERS
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
Copyright © 2026 Millies Engineering Group
Ea ly
E le m en ta ry
W hi te ha ll D is tr ic t S ch oo ls
E
S o p h ia S t, W h it eh al l, M
I 4
PROJECT NO. 25.147
MECHANICAL DEMOLITION
FIRST FLOOR PLAN - UNIT
B
09.30.2026
UNIT B
KEY PLAN
N.T.S.
NR
TH 1/8" = 1'-0"
MECHANICAL DEMOLITION FLOOR PLAN - UNIT B
SHEET NOTES
1 REMOVE EXISTING STEAM BOILERS, STEAM AND
CONDENSATE PIPING, BOILER FEED WATER SYSTEM,
DOMESTIC COLD WATER MAKE-UP CONNECTIONS, GAS
PIPE CONNECTIONS, ELECTRICAL CONNECTIONS,
CONTROLS, ETC COMPLETE AS REQUIRED WITHIN
BOILER ROOM. CAP STEAM AND CONDENSATE PIPING
AT WALL PRIOR TO ENTERING CRAWL SPACE. STEAM
AND CONDENSATE PIPING IN CRAWL SPACE SHALL BE
ABANDONED IN PLACE.
2 REMOVE EXISTING FIN TUBE AND ASSOCIATED
STEAM/CONDENSATE PIPING, THERMOSTATS, AND
CONTROL WIRING COMPLETE AS REQUIRED. CUT AND
PERMANENTLY CAP PIPING FLUSH WITH OR BELOW
FINISHED FLOOR ELEVATION; ABANDON REMAINING
PIPING IN TUNNELS.
3 REMOVE EXISTING STEAM CONDENSATE PUMP AND
ASSOCIATED CONDENSATE PIPING, VALVES,
CONTROLS, ELECTRICAL CONNECTIONS, ETC.
COMPLETE AS REQUIRED.
T
T
T
T
T
T
T
T
UNIT A
UNIT C
UNIT BUNIT C
UNIT
CUNIT
D
UNIT CUNIT D
INTERIOR
COURTYARD
CORRIDOR
COMMONS
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
BREAK OUT
CLASSROOM
RR
BREAK OUT
CLASSROOM
CLASSROOM
GIRLS RR
BOYS RR
CLASSROOM
CLASSROOM
RR
JC
EX UV
EX UV
EX UV
EX UV
EX FT
EX FT
EX UV
EX UV
EX UV
EX UV
EX UV
EX UV
REMOVE EX
UV - TYP
REMOVE EX
FT - TYP
EX FT
REMOVE EX AH
EX FT
EX CUH
EX 18"/12"
R/A
EX 12"/10"
S/A
EX S/A & R/A
DUCTWORK TO
REMAIN - TYP
EXISTING GAS METER
AND ASSOCIATED
GAS PIPING TO
REMAIN
REMOVE EX CUH
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
SHEET NUMBER
SHEET NAME
REVISIONS
ISSUE DATE
©2026
SHEET SIZE
30 x 42
Copyright © 2026 Millies Engineering Group
Ea ly
E le m en ta ry
W hi te ha ll D is tr ic t S ch oo ls
E
S o p h ia S t, W h it eh al l, M
I 4
PROJECT NO. 25.147
MECHANICAL DEMOLITION
FIRST FLOOR PLAN - UNIT
C
09.30.2026
UNIT C
KEY PLAN
N.T.S.
NR
TH 1/8" = 1'-0"
MECHANICAL DEMOLITION FLOOR PLAN - UNIT C
SHEET NOTES
1 REMOVE EX UNIT VENTILATOR AND ASSOCIATED
STEAM/CONDENSATE PIPING, OUTSIDE AIR INTAKE
LOUVER, THERMOSTAT, CONTROLS, ELECTRICAL
CONNECTIONS, ETC. COMPLETE AS REQUIRED. CUT
AND PERMANENTLY CAP PIPING FLUSH WITH OR
BELOW FINISHED FLOOR ELEVATION; ABANDON
REMAINING PIPING IN TUNNELS.
2 REMOVE EXISTING FIN TUBE AND ASSOCIATED
STEAM/CONDENSATE PIPING, THERMOSTATS, AND
CONTROL WIRING COMPLETE AS REQUIRED. CUT AND
PERMANENTLY CAP PIPING FLUSH WITH OR BELOW
FINISHED FLOOR ELEVATION; ABANDON REMAINING
PIPING IN TUNNELS.
3 REMOVE EXISTING AIR HANDLING UNIT AND
ASSOCIATED DUCTWORK, STEAM PIPING,
THERMOSTAT, ELECTRICAL CONNECTIONS, ETC.
COMPLETE AS REQUIRED. CUT AND PERMANENTLY CAP
PIPING FLUSH WITH OR BELOW FINISHED FLOOR
ELEVATION; ABANDON REMAINING PIPING IN TUNNELS.
4 REMOVE EXISTING CABINET UNIT HEATER AND
ASSOCIATED STEAM/CONDENSATE PIPING,
THERMOSTAT, CONTROLS, ELECTRICAL CONNECTIONS,
ETC. COMPLETE AS…
This is the start of the file's text. The full file is on GovTribe.