26 05 48.00 10.pdf

PDF 19 KB Posted

Attached to
TINKER AFB MAC BOA WWYK200323 REPAIR HVAC DIFFUSER AND DUCTWORK B3001
Solicitation number
WWYK200323-P
Issued by

About this file

This document is a Technical Specification for Seismic Protection for Electrical Equipment at Tinker Air Force Base. It specifies the seismic protection requirements for various types of electrical equipment and systems, including control panels, air handling units, pumps, switchgear, light fixtures, and transformers. The specification requires the contractor to submit detailed drawings, product data, and design calculations certified by a registered professional engineer for the seismic bracing. It provides detailed requirements for rigidly mounted equipment, flexibly mounted equipment, lighting fixture supports, and sway bracing. The related federal contract opportunity is for a repair project at Tinker AFB involving HVAC diffuser and ductwork repair in Building 3001. The contract is a set-aside for Tinker AFB MAC BOA holders only, with an estimated value between $1,000,000 and $5,000,000. Contractors must attend a mandatory site visit and submit an Entry Authorization List for base access.

View the file

Other files

File Type Posted
Attachment 1 EAL List - BLANK to Contractor_WWYK200323 .xlsx XLSX spreadsheet
32 13 11.pdf PDF
23 82 01.pdf PDF
07 72 20.pdf PDF
08 11 13.pdf PDF
23 08 01.00 20.pdf PDF
08 33 23.pdf PDF
23 05 48.00 40.pdf PDF
10 44 16.pdf PDF
01 33 16.00 10.pdf PDF
06 61 16.pdf PDF
23 25 00.pdf PDF
Tinker General Req Specs Nov22ChLog.pdf PDF
23 64 26.pdf PDF
07 41 13.pdf PDF
03 30 00.pdf PDF
26 28 01.00 10.pdf PDF
40 17 26.00 20.pdf PDF
06 20 00.pdf PDF
07 31 13.pdf PDF
23 05 15.pdf PDF
09 29 00.pdf PDF
21 13 13.pdf PDF
07 52 00.pdf PDF
07 62 13.pdf PDF
000 TABLE OF CONTENTS.pdf PDF
200323_Submittal Register.pdf PDF
23 82 43.00 40.pdf PDF
00 70 00.pdf PDF
32 01 17.pdf PDF
03 11 13.00 10.pdf PDF
03 20 00.00 10.pdf PDF
31 23 06.pdf PDF
09 72 00.pdf PDF
13 48 00.pdf PDF
04 20 00.pdf PDF
23 31 13.00 40.pdf PDF
08 52 00.pdf PDF
08 51 13.pdf PDF
32 92 23.pdf PDF
26 08 00.pdf PDF
10 28 13.pdf PDF
23 81 23.pdf PDF
32 11 23.pdf PDF
01 45 00.00 10.pdf PDF
05 40 00.pdf PDF
07 53 23.pdf PDF
10 26 00.pdf PDF
23 11 25.pdf PDF
23 57 10.pdf PDF
Show 40 more

Latest 50 of 183 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 26 05 48. 00 10

SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT

04/17

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN I NSTI TUTE OF STEEL CONSTRUCTI ON ( AI SC)

AI SC 325 ( 2011) St eel Const r uct i on Manual

ASTM I NTERNATI ONAL ( ASTM)

ASTM E580/ E580M ( 2014) St andar d Pr act i ce f or I nst al l at i on of Cei l i ng Suspensi on Syst ems f or Acoust i cal Ti l e and Lay- i n Panel s i n Ar eas Subj ect t o Ear t hquake Gr ound Mot i ons

U. S. DEPARTMENT OF DEFENSE ( DOD)

UFC 3- 310- 04 ( 2013) Sei smi c Desi gn f or Bui l di ngs

UNDERWRI TERS LABORATORI ES ( UL)

UL 1598 ( 2008; Repr i nt Oct 2012) Lumi nai r es

1. 2 SYSTEM DESCRI PTI ON

1. 2. 1 Gener al Requi r ement s

The r equi r ement s f or sei smi c pr ot ect i on measur es descr i bed i n t hi s sect i on shal l be appl i ed t o t he el ect r i cal equi pment and syst ems l i s t ed bel ow.

St r uct ur al r equi r ement s shal l be i n accor dance wi t h Sect i on 13 48 00

SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT.

1. 2. 2 El ect r i cal Equi pment

El ect r i cal equi pment shal l i ncl ude t he f ol l owi ng i t ems t o t he ext ent r equi r ed on t he dr awi ngs or i n ot her sect i ons of t hese speci f i cat i ons:

Cont r ol Panel s Ai r Handl i ng Uni t s

Pumps wi t h Mot or s Switchgear

Li ght Fi xt ur es Uni t Subst at i ons

Mot or Cont r ol Cent er s Transformers

Apr i l 2019 Page 1 SECTI ON 26 05 48. 00 10

Swi t chboar ds ( Fl oor Mount ed) St or age Racks

Sol ar Heat i ng Uni t s

1. 2. 3 El ect r i cal Syst ems

El ect r i cal syst ems shal l be i nst al l ed as r equi r ed on t he dr awi ngs and ot her sect i ons of t hese speci f i cat i ons and shal l be sei smi cal l y pr ot ect ed i n accor dance wi t h t hi s speci f i cat i on.

1. 2. 4 Cont r act or Desi gned Br aci ng

Submi t copi es of t he Desi gn Cal cul at i ons wi t h t he Dr awi ngs. Cal cul at i ons shal l be appr oved, cer t i f i ed, st amped and si gned by a Regi st er ed Pr of essi onal Engi neer . Cal cul at i ons shal l ver i f y t he capabi l i t y of st r uct ur al member s t o whi ch br aci ng i s at t ached f or car r y i ng t he l oad f r om t he br ace. Desi gn t he br aci ng i n accor dance wi t h UFC 3- 310- 04 and addi t i onal dat a f ur ni shed by t he Cont r act i ng Of f i cer . Resi st ance t o l at er al f or ces i nduced by ear t hquakes shal l be accompl i shed wi t hout consi der at i on of f r i c t i on r esul t i ng f r om gr avi t y l oads. UFC 3- 310- 04 uses par amet er s f or t he bui l di ng, not f or t he equi pment i n t he bui l di ng;

t her ef or e, cor r espondi ng adj ust ment s t o t he f or mul as shal l be r equi r ed.

Loadi ngs det er mi ned usi ng UFC 3- 310- 04 ar e based on st r engt h desi gn;

therefore, AI SC 325 shal l be used f or t he desi gn.

1. 2. 5 Condui t s Requi r i ng No Speci al Sei smi c Rest r ai nt s

Sei smi c r est r ai nt s may be omi t t ed f r om el ect r i cal condui t l ess t han 2- 1/ 2 i nches t r ade si ze, unl ess such r est r ai nt s woul d be necessar y t o meet t he r equi r ement s of UFC 4- 010- 01. Al l ot her i nt er i or condui t , shal l be sei smi cal l y pr ot ect ed as speci f i ed.

1. 3 EQUI PMENT REQUI REMENTS

Submi t det ai l dr awi ngs al ong wi t h cat al og cut s, t empl at es, and er ect i on and i nst al l at i on det ai l s, as appr opr i at e, f or t he i t ems l i s t ed.

Submi t t al s shal l be compl et e i n det ai l , i ndi cat i ng t hi ckness, t ype, gr ade, c l ass of met al , and di mensi ons; and shal l show const r uct i on det ai l s, r ei nf or cement , anchor age, and i nst al l at i on wi t h r el at i on t o t he bui l di ng const r uct i on. Submi t copi es of t he desi gn cal cul at i ons wi t h t he det ai l dr awi ngs. Cal cul at i ons shal l be st amped by a r egi st er ed engi neer and shal l ver i f y t he capabi l i t y of st r uct ur al member s t o whi ch br aci ng i s at t ached f or car r y i ng t he l oad f r om t he br ace.

1. 3. 1 Ri gi dl y Mount ed Equi pment

The f ol l owi ng speci f i c i t ems of equi pment t o be f ur ni shed under t hi s cont r act shal l be const r uct ed and assembl ed t o wi t hst and t he sei smi c f or ces speci f i ed i n UFC 3- 310- 04. Each i t em of r i gi d el ect r i cal equi pment shal l be ent i r el y l ocat ed and r i gi dl y at t ached on one si de onl y of a bui l di ng expansi on j oi nt . Pi pi ng, el ect r i cal condui t , et c. , whi ch cr oss t he expansi on j oi nt shal l be pr ovi ded wi t h f l exi bl e j oi nt s t hat ar e capabl e of accommodat i ng di spl acement s equal t o t he f ul l wi dt h of t he j oi nt i n bot h or t hogonal di r ect i ons.

Engine-Generators Substations

Apr i l 2019 Page 2 SECTI ON 26 05 48. 00 10

Transformers Swi t ch Boar ds and Swi t ch Gear s Mot or Cont r ol Cent er s Fr ee St andi ng El ect r i c Mot or s

1. 3. 2 Nonr i gi d or Fl exi bl y- Mount ed Equi pment

Equi pment , ot her t han t he i t ems speci f i ed above, shal l be const r uct ed and assembl ed t o r esi st a hor i zont al l at er al f or ces based on t he oper at i ng wei ght of t he equi pment at t he ver t i cal cent er of gr avi t y of t he equi pment .

Lat er al f or ces shal l be comput ed based on t he r equi r ement s of TI 809- 04 and UFC 4- 010- 01.

1. 4 SUBMITTALS

Gover nment appr oval i s r equi r ed f or al l submi t t al s. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Li ght i ng Fi xt ur es i n Bui l di ngs Equi pment Requi r ement s

SD- 03 Pr oduct Dat a

Li ght i ng Fi xt ur es i n Bui l di ngs Equi pment Requi r ement s Cont r act or Desi gned Br aci ng

PART 2 PRODUCTS

2. 1 LI GHTI NG FI XTURE SUPPORTS

Li ght i ng f i x t ur es and suppor t s shal l conf or m t o UL 1598.

2. 2 SWAY BRACI NG MATERI ALS

Sway br aci ng mat er i al s ( e. g. r ods, pl at es, r ope, angl es, et c. ) shal l be as speci f i ed i n Sect i on 13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS

EQUIPMENT.

PART 3 EXECUTI ON

3. 1 SWAY BRACES FOR CONDUI T

Condui t shal l be br aced as f or an equi val ent wei ght pi pe i n accor dance wi t h Sect i on 13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT.

3. 2 LI GHTI NG FI XTURES I N BUI LDI NGS

Li ght i ng f i x t ur es and suppor t s shal l conf or m t o t he f ol l owi ng:

3. 2. 1 Pendant Fi xt ur es

Pendant f i x t ur es shal l conf or m t o t he r equi r ement s of UFC 3- 310- 04.

Apr i l 2019 Page 3 SECTI ON 26 05 48. 00 10

3. 2. 2 Cei l i ng At t ached Fi xt ur es

3. 2. 2. 1 Recessed Fl uor escent Fi xt ur es

Recessed f l uor escent i ndi v i dual or cont i nuous- r ow mount ed f i xt ur es shal l be suppor t ed by a sei smi c- r esi st ant suspended cei l i ng suppor t syst em bui l t i n accor dance wi t h Sect i on 09 51 00 ACOUSTI CAL CEI LI NGS. Sei smi c pr ot ect i on f or t he f i x t ur es shal l conf or m t o t he r equi r ement s of UFC 3- 310- 04. Recessed l i ght i ng f i x t ur es not over 56 pounds i n wei ght may be suppor t ed by and at t ached di r ect l y t o t he cei l i ng syst em r unner s usi ng scr ews or bol t s, number and si ze as r equi r ed by t he sei smi c desi gn.

Fi xt ur e accessor i es, i ncl udi ng l ouver s, di f f user s, and l enses shal l have l ock or scr ew at t achment s.

3. 2. 2. 2 Sur f ace- Mount ed Fl uor escent Fi xt ur es

Sur f ace- mount ed f l uor escent i ndi v i dual or cont i nuous- r ow f i xt ur es shal l be at t ached t o a sei smi c- r esi st ant cei l i ng suppor t syst em bui l t i n accor dance wi t h Sect i on 09 51 00 ACOUSTI CAL CEI LI NGS. Sei smi c pr ot ect i on f or t he f i x t ur es shal l conf or m t o t he r equi r ement s of UFC 3- 310- 04.

3. 2. 3 Assembl y Mount ed on Out l et Box

A suppor t i ng assembl y, t hat i s i nt ended t o be mount ed on an out l et box, shal l be desi gned t o accommodat e mount i ng f eat ur es on 4 i nch boxes, pl ast er r i ngs, and f i xt ur e st uds.

3. 2. 4 Wal l - Mount ed Emer gency Li ght Uni t

At t achment s f or wal l - mount ed emer gency l i ght uni t s shal l be desi gned and secur ed f or t he wor st expect ed sei smi c di st ur bance at t he s i t e.

3. 2. 5 Lat er al For ce

St r uct ur al r equi r ement s f or l i ght f i x t ur e br aci ng shal l be i n accor dance wi t h Sect i on 13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT.

- - End of Sect i on - -

Apr i l 2019 Page 4 SECTI ON 26 05 48. 00 10

File details come from the government source that posted it. Updated .