25-8576_Exhibit_M4_-_Chikee_Hut_Structure_Plans.pdf
PDF 8 MB Posted
- Attached to
- Barefoot Beach Restoration - Grant Funded
- Solicitation number
- 25-8576
- Issued by
- Collier County, Florida
About this file
This document is a set of structural plans for a chickee hut structure, prepared in support of the Barefoot Beach Restoration project in Florida. The plans provide detailed architectural and engineering specifications for the repair and restoration of the chickee hut facility, which was damaged and requires restoration to safe and functional condition as part of the broader beach restoration initiative. The drawings and specifications included in this exhibit establish the technical requirements and design standards that contractors must follow when executing the chickee hut repair and reconstruction work, including structural components, materials, dimensions, and construction methodologies necessary to return the facility to its pre-storm operational status.
The chickee hut structure plans represent a critical component of the overall Barefoot Beach Restoration project, which is grant-funded and encompasses multiple restoration elements including civil and site improvements, accessibility upgrades, fencing, signage, and lighting. These structural plans serve as binding construction documents that establish the scope of work, technical specifications, and quality standards for the chickee hut restoration portion of the project, ensuring that all bidders and contractors operate from identical design documentation and can provide accurate pricing for this specific component of the overall restoration effort.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H C
H C
H C
H C
H C
LO
AD ING
ZO
N E
H C
H C
DNDNDNDNDN
STRUCTURAL NOTES
STRUCTURAL NOTES:
A. ELECTRONIC VERSIONS OF STRUCTURAL DRAWINGS ARE THE SOLE, COPYRIGHTED
PROPERTY OF TRC WORLDWIDE ENGINEERING. ELECTRONIC VERSIONS OF
DRAWINGS ARE NOT TO BE USED OR TRANSFERRED WITHOUT THE EXPRESS,
WRITTEN PERMISSION OF TRC WORLDWIDE ENGINEERING.
1010 GENERAL:
A. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB
SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND
SITE DRAWINGS. CONSULT THESE DRAWINGS FOR DEPRESSIONS, DIMENSIONS, AND
OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
B. DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY DISCREPANCIES
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING
WITH THE AFFECTED PART OF THE WORK.
C. WHERE DRAWINGS AND SPECIFICATIONS ARE IN CONFLICT, THE MORE STRINGENT
RESTRICTIONS AND REQUIREMENTS SHALL GOVERN.
D. PLAN NOTES, DETAILS AND SECTIONS SHALL TAKE PRECEDENCE OVER GENERAL
STRUCTURAL NOTES. TYPICAL DETAILS AND SECTIONS NOT CUT ON PLANS SHALL
APPLY UNLESS NOTED OTHERWISE.
E. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE
BUILDING IS COMPLETE. IT IS THE CONTRACTOR’S RESPONSIBILITY TO DETERMINE
ERECTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE BUILDING AND
IT’S COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF NECESSARY
SHORING, SHEETING, TEMPORARY BRACING, GUYS OR TIE DOWNS. CONTRACTOR IS
RESPONSIBLE FOR ENSURING THAT CONSTRUCTION COMPLIES WITH OSHA
REGULATION INCLUDING DESIGN OF CONNECTIONS OF MEMBERS THAT WILL NOT BE
FULLY COMPLETED AT THE TIME OF INSTALLATION.
F. TOWER CRANES ARE A CONTRACTOR RESPONSIBILITY AND SHALL BE DESIGNED FOR
APPLICABLE CRITERIA INCLUDING BUT NOT LIMITED TO INSURANCE REQUIREMENTS
AND APPLICABLE BUILDING CODES AT THE PROJECT LOCATION. THE CONTRACTOR
SHALL SUBMIT A CRANE LAYOUT, SHOP DRAWINGS, CALCULATIONS AND REACTIONS
FOR BOTH FOUNDATIONS AND CRANE TIE-IN LOCATIONS, SIGNED AND SEALED BY A
FLORIDA LICENSED PROFESSIONAL ENGINEER. THE ENGINEER OF RECORD SHALL BE
RETAINED BY THE CONTRACTOR TO EVALUATE CRANE TIE-IN FORCES ON THE
BUILDING STRUCTURE AND TO PROVIDE CRANE FOUNDATION DESIGN.
1011 CONTRACTOR PROPOSED CHANGES AND SUBSTITUTIONS:
A. PROPOSED CHANGES OR SUBSTITUTIONS TO STRUCTURAL DETAILS OR PLANS
SHALL BE SUBMITTED TO THE ENGINEER OF RECORD (EOR) FOR REVIEW AND
APPROVAL. SUBMITTALS SHALL CONTAIN FULL DOCUMENTATION OF CHANGES OR
SUBSTITUTIONS WITH SUPPORTING, SEALED CALCULATIONS (WHERE APPLICABLE).
THE REVIEW OF CHANGES AND SUBSTITUTIONS, RE-ANALYSIS AND/OR RE-DRAFTING
TO INCORPORATE CHANGES OR SUBSTITUTIONS INTO CONTRACT DOCUMENTS ARE
ADDITIONAL SERVICES FOR EOR. EOR IS NOT RESPONSIBLE FOR DETERMINING THE
COST EFFECTIVENESS OF PROPOSED CHANGES.
1012 CONTRACTOR REQUIRED REMEDIAL WORK:
A. DESIGN OF REMEDIAL WORK RELATED TO CONSTRUCTION ERRORS, INSTALLATIONS
NOT IN CONFORMANCE WITH CONTRACT DOCUMENTS, OR IN ANY WAY BROUGHT
ABOUT BY ACTIVITIES OF THE CONTRACTOR, IS NOT WITHIN THE SCOPE OF
CONSTRUCTION ADMINISTRATION SERVICES PROVIDED BY TRC WORLDWIDE
ENGINEERING. THE CONTRACTOR SHALL CARRY IN THEIR BASE BID THE COSTS FOR
ENGINEERING WORK ASSOCIATED TRC PROVIDING ADDITIONAL SERVICES IN
REACTION TO NON-CONFORMING WORK.
1120 SHOP DRAWING REVIEW:
A. SHOP DRAWING SUBMITTALS ARE REQUIRED FOR ALL COMPONENTS SHOWN ON
THESE STRUCTURAL CONTRACT DOCUMENTS INCLUDING, BUT NOT LIMITED TO:
a. ALL FASTENERS, ANCHORS, BOLTS, EPOXY ADHESIVES
b. WOOD FRAMING CONNECTORS
c. WOOD FRAMING
d. PRESSURE TREATED MATERIAL
B. SHOP DRAWINGS SHALL PROVIDE ACCURATE, DETAILED DIMENSIONAL INFORMATION
AS WELL AS COMPLETE SHOP AND FIELD ERECTION DETAILS NOT SHOWN ON
CONTRACT DOCUMENTS NECESSARY FOR FABRICATION AND INSTALLATION OF
COMPONENT.
C. SHOP DRAWINGS SHALL BE REVIEWED AND APPROVED BY THE CONTRACTOR’S FIELD
ENGINEER PRIOR TO SUBMITTAL TO THE ARCHITECT/ENGINEER. DRAWINGS
SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED.
D. SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN
INTENT OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF
THE CONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO
QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
E. SHOP DRAWING SUBMITTALS SHALL BE SUBMITTED IN ELECTRONIC PDF FILE FORMAT
ONLY.
F. SHOP DRAWINGS SHALL NOT CONTAIN DETAILS COPIED OR REPRODUCED FROM THE
CONTRACT DOCUMENTS. REPRODUCTION OF THE CONTRACT DOCUMENTS WILL
RESULT IN A REJECTION OF THE SHOP DRAWINGS
G. ELECTRONIC VERSIONS OF STRUCTURAL CONTRACT DOCUMENTS ARE THE SOLE,
COPYRIGHTED PROPERTY OF TRC WORLDWIDE ENGINEERING. ELECTRONIC VERSIONS
OF DRAWINGS ARE NOT TO BE USED OR TRANSFERRED WITHOUT THE EXPRESS,
WRITTEN PERMISSION OF TRC WORLDWIDE ENGINEERING. USERS WILL SIGN A
RELEASE AND REIMBURSE TRC WORLDWIDE ENGINEERING. FOR EXPENSES INCURRED
IN PREPARING AND TRANSMITTING ELECTRONIC DRAWINGS AT THE RATE TO BE
DETERMINED UPON REQUEST.
H. THE CONTRACT DOCUMENTS SHALL GOVERN OVER THE SHOP DRAWINGS UNLESS
OTHERWISE SPECIFIED IN WRITING BY THE ENGINEER.
I. CHANGES AND ADDITIONS MADE ON RE-SUBMITTALS SHALL BE CLEARLY FLAGGED AND
NOTED. THE PURPOSE OF THE RE-SUBMITTALS SHALL BE CLEARLY NOTED ON THE
LETTER OF TRANSMITTAL. ENGINEER REVIEW WILL BE LIMITED TO THOSE ITEMS
CAUSING THE RE-SUBMITTAL.
J. ELECTRONIC SUBMITTALS OF SHOP DRAWINGS WILL ONLY BE ACCEPTED AND
REVIEWED PENDING ABOVE CONDITIONS ARE MET. TRC WORLDWIDE ENGINEERING.
WILL ELECTRONICALLY RETURN SUBMITTAL IN PDF FORMAT AND WILL NOT BE
RESPONSIBLE FOR PRINTING MULTIPLE COPIES FOR DISTRIBUTION.
1122 RFI REVIEW:
A. ALL OF CONTRACTOR'S REQUEST(S) FOR INFORMATION (RFI's) SHALL STATE
CONTRACTOR’S SUGGESTION(S) FOR RESOLUTION AND COST IMPLICATIONS FOR
SUGGESTION(S). ENGINEER OF RECORD IS NOT RESPONSIBLE FOR DETERMINING
COST OR COST EFFECTIVENESS OF RFI RESPONSES.
1061 DESIGN LOADS:
A. THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED IN ACCORDANCE
WITH THE 2020 FLORIDA BUILDING CODE, 7TH EDITION.
B. LIVE LOADS ARE REDUCED FROM THE BASE LIVE LOADS SHOWN AS ALLOWED BY THE
REFERENCED BUILDING CODE. THE FOLLOWING SUPERIMPOSED DEAD LOADS AND LIVE
LOADS HAVE BEEN UTILIZED:
1015 ALTERATION OF EXISTING FACILITY:
A. INFORMATION SHOWN FOR THE EXISTING FACILITY ON THESE DRAWINGS WERE
TAKEN FROM THE DRAWINGS THAT WERE:
PREPARED BY: COASTAL ENGINEERING CONSULTANTS, INC
ENTITLED: DUNE CROSS WALKS, COLLIER COUNTY BAREFOOT
BEACH PRESERVE
DATED: OCT. 1989
PREPARED BY: COASTAL ENGINEERING CONSULTANTS, INC
BARANY SCHMITT WEAVER AND PARTNERS, INC
KRIS JAIN & ASSOCIATES, INC
U.C.I. ENGINEERING, INC
ENTITLED: BATHHOUSE AT BAREFOOT BEACH PRESERVE
DATED: NOV. 1990
B. WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION
WAS PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL
DRAWINGS INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER
SIZES, MATERIALS, DETAILS, ETC. IT SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE
AND TO NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR
CONFLICTS.
C. PRIOR TO SUBMISSION OF BIDS, THE CONTRACTOR SHALL HAVE VISITED THE SITE
AND THOROUGHLY ACQUAINTED HIMSELF WITH THE EXACT NATURE OF THE WORK
INDICATED ON THE DRAWINGS AND THE SPECIFICATIONS REQUIREMENTS. FAILURE
TO COMPLY WITH THE AFOREMENTIONED REQUIREMENTS SHALL NOT CONSTITUTE
A BASIS FOR CLAIMS FOR ADDITIONAL COMPENSATION.
D. ENGINEERING ANALYSIS HAS NOT BEEN PERFORMED BY TRC. TO DETERMINE THAT
THE EXISTING STRUCTURE IS IN COMPLIANCE WITH CURRENT CODE REQUIREMENTS
OR CODE REQUIREMENTS PREVALENT AT THE TIME OF ORIGINAL CONSTRUCTION.
E. PRIOR TO ORDERING ANY MATERIALS OR DOING ANY WORK, THE CONTRACTOR
SHALL VERIFY ALL MEASUREMENTS, DIMENSIONS AND OTHER CONDITIONS OF EACH
STRUCTURE SCHEDULED FOR WORK AS MAY BE NECESSARY OR REQUIRED IN THE
CONNECTION WITH THIS WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE CORRECTNESS OF SAME. PROVIDE TEN WORKING DAYS NOTICE TO THE
OWNER PRIOR TO COMMENCING EACH CUTTING OR ALTERATION ACTIVITY.
F. PROTECTION OF EXISTING EQUIPMENT, NEWLY INSTALLED EQUIPMENT, BUILDING
AND STRUCTURES:
a. THE CONTRACTOR SHALL FURNISH AND ERECT NECESSARY TEMPORARY DUST
TIGHT PROOF PARTITIONS WHERE DEMOLITION IS REQUIRED TO PROTECT
EXISTING EQUIPMENT, NEWLY INSTALLED EQUIPMENT, BUILDINGS AND
STRUCTURES AND AS DIRECTED BY THE OWNER OR ENGINEER.
b. PARTITIONS SHALL BE CONSTRUCTED OF WOOD STUDS WITH PLYWOOD OR
POLYETHYLENE SHEETING. PARTITIONS SHALL EXTEND FROM A CLOSURE PLATE
AT THE FLOOR TO EITHER THE BUILDING CEILING OR A TEMPORARY CEILING.
THE CONTRACTOR SHALL FURNISH AND INSTALL ONE DOOR IN EACH
ENCLOSURE COMPLETE WITH HARDWARE. SUCH ENCLOSURES WILL BE
REQUIRED IN ALL AREAS OF DEMOLITION WORK AND FOR PROTECTION OF
EXISTING EQUIPMENT AND NEWLY INSTALLED EQUIPMENT.
c. CONTRACTOR SHALL PROVIDE AN ADEQUATE VENTILATION SYSTEM FOR
WORKERS AND FOR DUST REMOVAL. CONTRACTOR SHALL PROVIDE ADEQUATE
LIGHTING AS REQUIRED FOR THE DEMOLITION WORK.
G. CONTRACTOR SHALL CARRY AN ALLOWANCE IN HIS BID FOR UNFORSEEN EXISTING
CONDITIONS.
GRAVITY LOADS
LOCATION
BOARDWALKS / PAVILIONS
LIVE LOAD REDUCTION ON SUPPORTING ELEMENTS SHALL BE IN
ACCORDANCE WITH THE BUILDING CODE. NO LIVE LOAD REDUCTION OF
ROOF LOADING IS PERMITTED. UNIFORMED DEAD LOAD IS ADDITIVE TO
ACTUAL STRUCTURAL WEIGHTS.
UNIFORM LIVE LOADSUPERIMPOSED
DEAD LOAD
10010
WIND LOADS
ULT. WIND SPEED (3 SECOND GUST) 150 MPH
ASD WIND SPEED (3 SECOND GUST) 90 MPH
BUILDING RISK CATEGORY I
WIND EXPOSURE C
BUILDING CLASSIFICATION OPEN
INTERNAL PRESSURE COEFFICIENT ±0.18
VELOCITY PRESSURE ** PSF
2355 WOOD PILES:
A. PILES SHALL COMPLY WITH ASTM D25 AND BE TREATED (AWPB STD-MLP P5-72)
SOUTHERN PINE WITH A MINIMUM BUTT DIAMETER OF 8". PILES SHALL BE DRIVEN A
MINIMUM OF 12 FEET INTO BEARING STRATA AND ACHIEVE A MINIMUM SAFE BEARING
CAPACITY OF 6 TONS AS COMPUTED BY AN APPROPRIATE DRIVING FORMULA. PILE
DRIVING OPERATIONS SHALL BE PERFORMED UNDER THE SUPERVISION OF A
REGISTERED PROFESSIONAL ENGINEER WITHIN THE JURISDICTION OF THE PROJECT.
3601 POST-INSTALLED ANCHORS:
A. POST INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE
DRAWINGS.
B. CONTRACTOR SHALL OBTAIN APPROVAL FROM ENGINEER OF RECORD PRIOR TO
USING POST-INSTALLED ANCHORS FOR MISSING OR MISPLACED CAST-IN ANCHORS.
C. CARE SHALL BE GIVEN TO AVOID DAMAGING EXISTING REBAR WHEN DRILLING HOLES.
HOLES SHALL BE DRILLED AND CLEANED PER MANUFACTURER’S INSTRUCTIONS.
D. UNLESS SPECIFIED OTHERWISE, ANCHORS SHALL BE EMBEDDED IN THE
APPROPRIATE SUBSTRATE WITH A MINIMUM EMBEDMENT OF 8 TIMES THE NOMINAL
ANCHOR DIAMETER OR THE EMBEDMENT REQUIRED FOR SUPPORT OF THE INTENDED
LOAD. ANCHORS SHALL BE INSTALLED PER THE MANUFACTURER’S INSTALLATION
INSTRUCTIONS AT NOT LESS THAN MINIMUM EDGE DISTANCE AND/OR SPACING
INDICATED IN THE MANUFACTURER’S LITERATURE.
E. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE LISTED BELOW SHALL
BE SUBMITTED TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL WITH
CALCULATIONS PREPARED, SIGNED AND SEALED BY AN ENGINEER REGISTERED IN
THE JURISDICTION OF THE PROJECT SHOWING THAT THE SUBSTITUTED PRODUCT
WILL ACHIEVE AN EQUIVALENT CAPACITY USING THE APPROPRIATE DESIGN
PROCEDURE.
F. ACCEPTABLE PRODUCTS FOR ANCHORS EXPOSED TO WEATHER OR FOR
ENVIRONMENTAL STRUCTURES ARE AS FOLLOWS:
a. CONCRETE MECHANICAL ANCHORS:
• TRUBOLT BY ITW REDHEAD - AISI 316 STAINLESS STEEL
• KWIK BOLT 3 BY HILTI - AISI 316 STAINLESS STEEL
• POWER STUD BY POWERS - AISI 316 STAINLESS STEEL
b. SCREW ANCHORS:
• TAPPER BY POWERS - AISI 316 STAINLESS STEEL
• HUS-H BY HILTI
6100 ROUGH CARPENTRY:
A. CONTRACTOR SHALL MAKE ALLOWANCE FOR SUPPLYING AND ERECTING 1000 BOARD
FEET OF VARIOUS LUMBER SIZES TO BE 20 IN ADDITION TO THAT SHOWN ON PLAN,
WITHIN SECTIONS, DETAIL AND SCHEDULES TO BE USED IN PLACE AT THE DISCRETION
OF THE STRUCTURAL ENGINEER.
B. STRUCTURAL WOOD COMPONENTS (STUDS, BEAMS, JOISTS, RAFTERS, ETC.) SHALL
HAVE THE FOLLOWING MINIMUM DESIGN VALUES OF No. 2 SOUTHERN PINE
CONFORMING TO THE LATEST EDITION OF NDS, AS FOLLOWS:
a. JOISTS & BEAMS:
• SHEAR Fv = 175 PSI
• BENDING 2x4 Fb = 1,100 PSI
• BENDING 2x6 Fb = 1,000 PSI
• BENDING 2x8 Fb = 925 PSI
• BENDING 2x10 Fb = 800 PSI
• BENDING 2x12 Fb = 750 PSI
NOTE: THE ABOVE VALUES HAVE NOT BEEN MODIFIED BY APPROPRIATE
ADJUSTMENT FACTORS.
A. WOOD IN CONTACT WITH CONCRETE OR MASONRY, AND AT OTHER LOCATIONS AS
SHOWN ON STRUCTURAL DRAWINGS, SHALL BE PROTECTED OR PRESSURE TREATED
IN ACCORDANCE WITH AMERICAN WOOD - PRESERVERS' ASSOCIATION STANDARDS.
MEMBER SIZES SHOWN ARE NOMINAL UNLESS NOTED OTHERWISE.
a. WOOD POSTS (4x, 6x, 8x NOMINAL THICKNESS) SHALL BE PRESSURE TREATED WITH
AWPA WATERBORNE PRESERVATIVE FOR MARINE LUMBER AND TIMBER TO
ACHIEVE 0.60 POUNDS PER CUBIC FOOT RETENTION WITH ONE OF THE FOLLOWING:
• ALKALINE COPPER QUAT (ACQ)
• AMMONIACAL COPPER ZINC ARSENATE (ACZA)
• CHROMATED COPPER ARSENATE (CCA)
b. DIMENSIONAL LUMBER (2x NOMINAL THICKNESS) SHALL BE PRESERVATIVE
TREATED WITH ECOLIFE MANUFACTURED BY VIANCE, LLC IN ACCORDANCE WITH
ICC-ES EVALUATION REPORT ESR-2067.
B. SUSPENSION FROM ROOF STRUCTURE: CONDUIT, PIPING, OR EQUIPMENT SUSPENDED
FROM STRUCTURE, UNLESS SPECIFICALLY NOTED ON ROOF FRAMING PLANS, MUST BE
CONNECTED IN SUCH A FASHION TO NOT EXCEED DESIGN LOADS FOR TOP OR
BOTTOM CHORD AS INDICATED ON THESE DRAWINGS. SPACING OF CONNECTIONS
SHALL NOT EXCEED TRUSS SPACING IN EITHER DIRECTION. DO NOT ATTACH TO ROOF
DECK.
C. TIMBER FASTENING SHALL BE IN ACCORDANCE FBC FASTENING SCHEDULE TYPICAL
UNLESS NOTED OTHERWISE.
D. BOLTS FOR WOOD CONSTRUCTION AT INTERIOR LOCATIONS NOT EXPOSED TO
WEATHER SHALL BE ASTM A307. BOLTS EXPOSED TO WEATHER SHALL BE AISI 316
STAINLESS STEEL. SCREWS EXPOSED TO WEATHER SHALL BE AISI 316 STAINLESS
STEEL.
E. BOLT HOLES IN WOOD SHALL BE A MINIMUM OF 1/32" TO 1/16" MAX. LARGER THEN BOLT
DIAMETER. A METAL PLATE, METAL STRAP, OR WASHER NOT LESS THAN A STANDARD
CUT WASHER SHALL BE BETWEEN THE WOOD AND THE BOLT HEAD AND THE WOOD
AND THE NUT.
F. ALL NAILS FOR STRUCTURAL WORKS SHALL USE COMMON WIRE NAILS UNLESS NOTED
OTHERWISE. NAIL HOLES SHALL BE SUB-DRILLED WHERE NECESSARY TO PREVENT
SPLITTING WOOD. SEE BELOW MINIMUM REQUIREMENTS FOR SPECIFIED NAILS:
a. 8D NAILS = 0.131” DIAMETER x 2 1/2”
b. 10D NAILS = 0.148” DIAMETER x 3”
c. 16D NAILS = 0.162” DIAMETER x 3 1/2”
G. ALL COMMON HORIZONTAL FRAMING MEMBERS SUCH AS FLOOR OR CEILING JOIST,
ROOF RAFTERS, AND BEAM SHALL HAVE A MINIMUM OF 2 1/2" OF FULL BEARING OR
SHALL HAVE JOIST HANGERS. END NAILING OR TOE NAILING ALONE WITHOUT
HANGERS NOT PERMITTED UNLESS SHOWN ON DRAWINGS.
6105 WOOD FRAMING CONNECTORS:
A. CONNECTOR MODEL NUMBERS SHOWN ARE STRONG-TIE CONNECTORS AS
MANUFACTURED BY SIMPSON STRONG-TIE CO., 1450 DOOLITTLE DR., P.O. BOX 1568, SAN
LEANDRO, CA 94577. SUBSTITUTIONS ARE ACCEPTABLE WITH THE APPROVAL OF THE
STRUCTURAL ENGINEER. UNLESS NOTED OTHERWISE, INSTALL SIZE AND NUMBER OF
FASTENERS SHOWN IN LATEST SIMPSON CATALOG.
B. CONNECTORS SHALL BE HOT-DIPPED GALVANIZED TO A G185 COATING (1.85 OZ. PER
SQUARE FT.) PER ASTM A653 (SIMPSON ZMAX) WHEN ATTACHED TO UNTREATED WOOD
OR WOOD TREATED WITH: CHROMATED COPPER ARSENATE (CCA-C); DOT SODIUM
BORATE (SBX); ALKALINE COPPER QUAT ACQ-C AND ACQ-D (CARBONATE); COPPER
AZOLE (CBA-A AND CA-B); BORATE (NON-DOT).
C. CONNECTORS SHALL BE TYPE 316L STAINLESS STEEL (SIMPSON SST300) WHEN
ATTACHED TO WOOD TREATED WITH AMMONIACAL COPPER ZINC ARSENATE (ACZA) OR
OTHER PRESERVATIVES NOT LISTED ABOVE.
D. FASTENERS SHALL BE HOT-DIPPED GALVANIZED TO G90 WHEN USED WITH GALVANIZED
CONNECTORS AND STAINLESS STEEL WHEN USED WITH STAINLESS STEEL
CONNECTORS.
E. ALL STRAPS, JOIST HANGERS, AND METAL CONNECTORS SHALL BE INSTALLED
DIRECTLY TO SOLID LUMBER. DO NOT INSTALL OVER PLYWOOD SHEATHING OR
GYPSUM.
9900 PAINTING:
A. CONTRACTOR TO RE-PAINT/TOUCHUP EXISTING SURFACES WHERE DAMAGED BY
CONSTRUCTION ACTIVITIES AND TO RENDER THE COMPLETED PROJECT VISUALLY
CONTINUOUS AS NOT TO APPEAR AS RE-PAINT/TOUCHUP HAS OCCURRED.
B. USE PRIMER AND PAINT TO BE COMPATIBLE W/ EXISTING PAINT AND TO MATCH
EXISTING COLOR.
1060 DESIGN AND CONSTRUCTION STANDARDS:
A. THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED IN ACCORDANCE
WITH THE FOLLOWING CODES AND REFERENCED STANDARDS:
(FBC 2023) FLORIDA BUILDING CODE 8th EDITION BY THE INTERNATIONAL CODE
COUNCIL, INC
(AISC 15 ED) FIFTEENTH EDITION OF THE STEEL CONSTRUCTION MANUAL BY THE
AMERICAN INSTITUTE OF STEEL CONSTRUCTION
(ASCE 7-22) MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS
AND OTHER STRUCTURES BY THE AMERICAN SOCIETY OF CIVIL
ENGINEERS
(NDS-18) 2018 EDITION OF NATIONAL DESIGN SPECIFICATIONS FOR WOOD
CONSTRUCTION WITH 2018 SUPPLEMENT BY AMERICAN FOREST &
PAPER ASSOCIATION
2011 FOUNDATIONS:
A. SEE THE FOLLOWING REPORT FOR COMPLETE GEOTECHNICAL RECOMMENDATIONS
AND INSTALLATION PROCEDURES:
REPORT NO. VS240951
PREPARED BY: Socotec Cconsulting, Inc.
TITLED: PROPOSED PAVILIONS AND BOARDWALK BAREFOOT BEACH
DATED: May 2024
THIS REPORT SHALL BE CONSIDERED PART OF THE CONTRACT DOCUMENTS.
B. NO APPROVAL OR VERIFICATION OF RECOMMENDATIONS MADE WITHIN THE ABOVE
NOTED GEOTECHNICAL REPORT IS IMPLIED THROUGH REFERENCE OR USE BY TRC.
A
S100
1 C
D
CERTIFICATE OF AUTHORIZATION NO. 35826
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.
All rights reserved.
11926 Fairway Lakes Drive
FORT MYERS, FL 33913
PHONE: (239) 939-1414
FAX: (239) 278-4289
A
B
C
D
RG ARCHITECTS P.A.
Fort Myers, FL 33901
P (239) 332-2040
F (239) 332-2049
2070 McGregor Boulevard, Suite 3 www.rgarchitectspa.com
CONSULTANT
OWNER
PROJECT TITLE
PROJECT ADDRESS
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
SEAL
a r c h i t e c t s
/8
/2
:1
:5
P M
A u to d e s k D o c s /2
C
C B a re fo o t B e a c h
R e s to ra ti o n /2
F
T M
-B a re fo o t B e a c h
H u rr ic a n e
R e s to ra ti o n -R
.r v t
CHIKEE HUT - HURRICANE IAN
S001
CONCESSIONS-BAREFOOT BEACH
RESTORATION
505 BAREFOOT BEACH BOULEVARD,
BONITA SPRINGS, FLORIDA 34134
STRUCTURAL NOTES
AND DESIGN CRITERIA
KLI
PSM
07.10.2025
PSM
23FTM249
23FTM249
1 : 8000
SITE PLAN
No. 60487
STATE OFP
R
O F
E
SS I ONA L ENG
I N E
E R
L EI CENS
P A
U L
S. MOE RSCH
E L
FLORI DA
This item has been electronically signed and sealed by Paul S. Moerschel, PE on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
NO. DESCRIPTION DATE
SHEET INDEX
SHT # DESCRIPTION
S001 STRUCTURAL NOTES AND DESIGN CRITERIA
S102 CHIKEE HUT BENCH PLAN & DETAIL
S102
1'-5"
4'-0" OC MAX
PT 4x4 POST @
4'-0" OC MAX
12"x12" x 2'-0" DEEP
CONC FTG AT EA POST
TYP
1'-6"
2x2 RAILING PICKET
@ 6" OC BEYOND
(3) PT 2x6 W/ (2) 16d NAILS INTO EA HORIZ 2x6
PT 2x6 DIAG BRACE W/ (3) 16d NAILS INTO 2x EA END
PT 2x6 VERT @ 4'-0" OC MAX, LOCATE AT EA 4x4 POST
CONT PT 2x6 HORIZ W/
(2) 16d NAILS INTO EA
2x6 COMPOSITE TOP RAIL TO
MARCH EXIST, REFER TO MFR FOR
INSTALLATION REQUIREMENTS
PT 2x6 HORIZ
@ 4'-0" OC
1'-0"
PT 4x4 POST
@ 4'-0" MAX,
SEE PLAN
CONC FTG,
SEE PLAN
2x6 CONT, MATCH EXIST
2x8 CONT, MATCH EXIST
CERTIFICATE OF AUTHORIZATION NO. 35826
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.
All rights reserved.
11926 Fairway Lakes Drive
FORT MYERS, FL 33913
PHONE: (239) 939-1414
FAX: (239) 278-4289
A
B
C
D
RG ARCHITECTS P.A.
Fort Myers, FL 33901
P (239) 332-2040
F (239) 332-2049
2070 McGregor Boulevard, Suite 3 www.rgarchitectspa.com
CONSULTANT
OWNER
PROJECT TITLE
PROJECT ADDRESS
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
SEAL
a r c h i t e c t s
/8
/2
:1
:5
P M
A u to d e s k D o c s /2
C
C B a re fo o t B e a c h
R e s to ra ti o n /2
F
T M
-B a re fo o t B e a c h
H u rr ic a n e
R e s to ra ti o n -R
.r v t
CHIKEE HUT - HURRICANE IAN
S102
CONCESSIONS-BAREFOOT BEACH
RESTORATION
505 BAREFOOT BEACH BOULEVARD,
BONITA SPRINGS, FLORIDA 34134
CHIKEE HUT BENCH
PLAN & DETAIL
KLI
PSM
07.10.2025
PSM
23FTM249
23FTM249
NO. DESCRIPTION DATE
1/2" = 1'-0"S102
1 CHIKEE HUT BENCH PLAN
3/4" = 1'-0"S102
2 BENCH SECTION
No. 60487
STATE OFP
R
O F
E
SS I ONA L ENG
I N E
E R
L EI CENS
P A
U L
S. MOE RSCH
E L
FLORI DA
This item has been electronically signed and sealed by Paul S. Moerschel, PE on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
| S001 - STRUCTURAL NOTES AND DESIGN CRITERIA |
| S102 - CHIKEE HUT BENCH PLAN & DETAIL |
| 2025-08-22T10:12:21-0400 | |
| Paul Moerschel |