25-8576_Exhibit_M2_-_Chikee_Hut_Electrical_Plans.pdf

PDF 1 MB Posted

Attached to
Barefoot Beach Restoration - Grant Funded
Solicitation number
25-8576
Issued by
Collier County, Florida

About this file

This file consists of electrical plans and specifications for the Chickee Hut Hurricane Ian restoration project located at 505 Barefoot Beach Boulevard, Naples, Florida 34134. The project is part of the grant-funded Barefoot Beach Restoration initiative, which addresses storm-related damage and restores park facilities to safe and functional conditions. The electrical plans, prepared by RG Architects P.A. and Peninsula Engineering, include general notes, fixture schedules, sheet indices, overall site plans for power distribution, and floor plans detailing power requirements for the Chickee Hut renovation. The drawings specify branch circuit configurations based on conductor length requirements, receptacle placements at various locations including the butterfly garden and parking areas, and coordination requirements with mechanical, plumbing, and structural trades. All work must comply with the 2020 National Electric Code and established work schedules, with contractors required to coordinate routing and existing conditions prior to bid submission.

The electrical specifications establish detailed requirements for conductor sizing, conduit installation, device mounting heights, and material standards, including provisions for weather-resistant and wet-location fixtures appropriate for the coastal environment within 30 miles of the coastline. Contractors are responsible for locating and protecting existing utilities, removing obsolete electrical equipment, maintaining circuit continuity where required, disposing of or recycling waste materials in compliance with Florida Statute 403.7186, and managing the transport and disposal of mercury-containing devices and lamps according to DEP and EPA guidelines. All devices must be gray with smooth metal 302 stainless steel plates unless otherwise noted, and new panel directories must be provided for all new panelboards. The contractor bears all expenses for utility repair or replacement damaged during construction and must provide written certification of accepted disposal for hazardous materials.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SCOTT LA IN

No 69099P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

PHONE (239) 332-1187

12467 Brantley Commons, Fort Myers, FL 33907

FAX (239) 332-5195CERT. OF AUTH. No. 5096 ENG. BUS. No. EB-0005096

A

B

C

D

RG ARCHITECTS P.A.

Fort Myers, FL 33901

P (239) 332-2040

F (239) 332-2049

2070 McGregor Boulevard, Suite 1 www.rgarchitectspa.com

CONSULTANT

OWNER

PROJECT TITLE

PROJECT ADDRESS

SHEET ID

SHEET TITLE

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

SEAL

a r c h i t e c t s

CHICKEE HUT - HURRICANE IAN

CHICKEE HUT - BAREFOOT BEACH

RESTORATION

/8

/2

:4

:0

P M

A u to d e s k D o c s /2

C C

B a re fo o t B e a c h R e s to ra ti o n

/2

-1

E le c tr ic a l

R e v it

B

IM

.r v t

E002

505 BAREFOOT BEACH BOULEVARD,

NAPLES, FL 34134

GENERAL NOTES,

FIXTURE SCHEDULE, &

SHEET INDEX

AB

SL

07.10.2025

AB

2332 000

PENINSULA ENGINEERING

2600 GOLDEN GATE PKWY, NAPLES,

FL 34105

GENERAL NOTES:

1. NO MULTI-WIRE BRANCH CIRCUITS ARE TO BE USED. EACH CIRCUIT IS TO HAVE SEPARATE INDIVIDUAL NEUTRAL.

2. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 0-100 FEET, ARE TO HAVE #12 MINIMUM BRANCH CIRCUIT WIRING THROUGHOUT CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC).

3. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 101-125 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (3/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #12 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC). NOT LESS THAN THE FIRST 75 FEET

OF COMBINED HOMERUN AND BRANCH CIRCUIT TO BE MINIMUM #10 WIRE (3/4"C).

4. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 126-160 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT WIRING THROUGHOUT CIRCUIT (3/4”C).

5. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 161-205 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 125 FEET OF COMBINED HOMERUN AND

BRANCH CIRCUIT TO BE MINIMUM #8 WIRE (1"C.)

6. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 206-230 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING THROUGHOUT CIRCUIT (1"C.).

7. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 231-250 FEET, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1-1/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 175 FEET OF COMBINED HOMERUN AND

BRANCH CIRCUIT TO BE MINIMUM #6 WIRE (1-1/4"C.).

8. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 326-370 FEET FROM THE PANEL, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING THROUGHOUT CIRCUIT (1-1/4"C.).

9. 120 VOLT BRANCH CIRCUITS SERVING RECEPTACLES FOR COMPUTER WORKSTATIONS (IE OUTLETS WITH 'C' DESIGNATION) SHALL HAVE MINIMUM CONDUCTOR SIZE OF #10. #10 MINIMUM CONDUCTOR SIZE SHALL BE INCREASED IF REQUIRED TO COMPLY WITH GENERAL NOTES ABOVE.

10. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES IN ALL MECH. ROOMS, AND SPACES WITH NO CEILING (EXPOSED STRUCTURE AREAS), SPACES, ETC., WITH DUCTWORK INSTALLER PRIOR TO ROUGH-IN. LOCATE BELOW DUCTWORK (8'-0" A.F.F. MINIMUM) CENTERED IN ROOM AS MUCH AS FEASIBLE.

11. VERIFY EXACT LOCATION OF ALL MECH. EQUIP. INCLUDING WALL SWITCHES, T'STATS, ETC. WITH MECH. CONTRACTOR AND MECH. DRAWINGS.

12. REFER TO PANEL SCHEDULES FOR CIRCUITS NUMBERS OF CIRCUITS FOR MECHANICAL AND PLUMBING EQUIPMENT.

13. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF

DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.

14. READ SPECIFICATIONS.

15. SEE BUILDING PLANS.

16. ALL EMPTY CONDUITS ARE TO HAVE PULL-STRINGS PROVIDED IN THEM.

17. WHERE CONDUIT ROUTING IS SHOWN, THE CONDUITS ARE SHOWN FOR DIAGRAMMATIC PURPOSES AND ARE NOT NECESSARILY REPRESENTATIVE OF EXACT PLACEMENT. THE ROUTINGS SHOWN ARE PROPOSED CONDUIT ROUTINGS. CONTRACTOR TO COORDINATE ALL ROUTING WITH OTHER TRADES PRIOR TO BID. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS AND ROUTING OF CONDUIT PRIOR TO BID. CONTRACTOR IS RESPONSIBLE FOR RELOCATING CONDUIT FROM THE PROPOSED ROUTING SHOWN TO THE ROUTING REQUIRED TO FACILITATE INSTALLATION PER SPECIFICATIONS AND APPLICABLE CODES, COMPLETE WITH ALL COORDINATION AND EXISTING CONDITIONS TAKEN INTO ACCOUNT. CONTRACTOR IS RESPONSIBLE FOR ALL CEILING AND WALL

REPAIR/REPLACEMENT AFTER ROUTING OF CONDUIT.

18. ALL CONDUIT TERMINATIONS AT TERMINAL BOARDS ARE TO HAVE BUSHED CONDUIT ENDS.

19. SPLICES IN POWER AND LIGHTING OUTLET BOXES SHALL BE KEPT TO A MINIMUM, PULL CONDUCTORS THROUGH TO DEVICES, EQUIPMENT CABINETS/PANELBOARDS. SPLICING IN WIREWAYS IS NOT PERMITTED UNLESS SPECIAL WRITTEN PERMISSION IS GRANTED BY A/E.

20. NO SPLICES SHALL BE MADE IN COMMUNICATIONS OUTLET BOXES OR PULL BOXES (I.E., FIRE ALARM, COMPUTER, TELEPHONE, ETC.) UNLESS SPECIFIC WRITTEN APPROVAL HAS BEEN GIVEN BY ENGINEER. PULL CABLES THROUGH TO EQUIPMENT/TERMINAL CABINETS.

21. NO SPLICES SHALL BE MADE IN UNDERGROUND (OR FLUSH) IN-GRADE PULL BOXES UNLESS ENGINEER HAS GIVEN SPECIFIC ACCEPTANCE.

22. CONTRACTOR SHALL INCLUDE IN HIS BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL RULES, REGULATIONS AND GUIDELINES APPLICABLE. CONTRACTOR SHALL COMPLY FULLY WITH FLORIDA STATUTE 403.7186 REGARDING MERCURY CONTAINING DEVICES AND LAMPS. LAMPS, BALLASTS AND OTHER MATERIALS SHALL BE TRANSPORTED AND DISPOSED OF IN ACCORDANCE WITH ALL DEP AND EPA GUIDELINES APPLICABLE AT TIME OF DISPOSAL. CONTRACTOR SHALL PROVIDE OWNER WITH WRITTEN CERTIFICATION

OF ACCEPTED DISPOSAL.

23. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN ON PLANS OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR REPAIR OR REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK. THE CONTRACTOR SHALL LOCATE ALL UTILITIES (BOTH KNOWN AND UNKNOWN) IN AREA OF WORK PRIOR TO EXCAVATION WITH THE USE OF ELECTRONIC LOCATOR/TRACER DEVICES AND EQUIPMENT SUITABLE FOR SUCH USE. REFLECT

LOCATED UTILITIES ON AS-BUILT DOCUMENTS.

24. EXISTING CONDITIONS AND UTILITIES INDICATED ARE TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS, VARIOUS SURVEYS, AND FIELD INVESTIGATIONS.

IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND/OR BURIAL DEPTHS AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED A PART OF THIS CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL SITE UTILITIES, ETC., PRIOR TO

BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.

25. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN ON PLANS OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR REPAIR OR REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK. THE CONTRACTOR SHALL LOCATE ALL UTILITIES (BOTH KNOWN AND UNKNOWN) IN AREA OF WORK PRIOR TO EXCAVATION WITH THE USE OF ELECTRONIC LOCATOR/TRACER DEVICES AND EQUIPMENT SUITABLE FOR SUCH USE. REFLECT

LOCATED UTILITIES ON AS-BUILT DOCUMENTS.

26. REMOVE EXISTING POWER, LIGHTING, SYSTEMS, MATERIAL AND EQUIPMENT WHICH ARE MADE OBSOLETE OR WHICH INTERFERE WITH THE CONSTRUCTION

OF THE PROJECT.

27. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS, MATERIALS AND EQUIPMENT WHICH ARE REQUIRED TO REMAIN ACTIVE FOR THE FACILITY TO BE FULLY

FUNCTIONAL.

28. REMOVE ALL EXISTING ELECTRICAL IN AREAS OF REMODELING UNLESS SPECIFICALLY NOTED OTHERWISE, OR UNLESS REQUIRED FOR CONTINUITY OF

CIRCUITS IN AREAS NOT IN REMODEL AREA.

29. ALL EXISTING ELECTRICAL IS NOT SHOWN. IT IS THE CONTRACTORS RESPONSIBILITY TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND INCLUDE IN HIS BID THE REMOVAL OF ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, DEVICES, FIXTURES, ETC. THAT IS NOT BEING REUSED, BACK TO ITS

SOURCE.

30. ALL RECEPTACLES, DEVICES AND EQUIPMENT NOT SHOWN, AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS OTHERWISE NOTED.

FURNISH AND INSTALL ACCESSIBLE JUNCTION BOXES AND REWORK EXISTING CIRCUITS AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO RECEPTACLES, DEVICES AND EQUIPMENT REMAINING.

31. ALL CONDUIT TO BE CONCEALED UNLESS IMPOSSIBLE DUE TO EXISTING CONDITIONS (I.E. EXPOSED CEILINGS, BUILDING EXTERIOR WALL RUNS, IMPOSSIBLE

UNDERGROUND RUNS). CONCEAL ALL CONDUITS ABOVE CEILINGS OR IN WALL/COUNTERS.

32. ALL NEW DEVICES TO BE FLUSH MOUNTED UNLESS SPECIFICALLY NOTED OTHERWISE.

33. ALL CONDUIT TO BE CONCEALED UNLESS IMPOSSIBLE DUE TO EXISTING CONDITIONS (I.E. EXPOSED CEILINGS, BUILDING EXTERIOR WALL RUNS, IMPOSSIBLE

UNDERGROUND RUNS). CONCEAL ALL CONDUITS ABOVE CEILINGS OR IN WALL/COUNTERS.

34. ALL NEW DEVICES TO BE FLUSH MOUNTED UNLESS SPECIFICALLY NOTED OTHERWISE.

35. PROVIDE NEW TYPED PANEL DIRECTORIES FOR ALL NEW PANELBOARDS.

36. PAINT ALL EXPOSED CONDUIT, BOXES, ETC. TO MATCH WALL SURFACE.

37. WORK TO BE PERFORMED IN STRICT COMPLIANCE WITH ESTABLISHED WORK SCHEDULE BEING SET FORTH BY OWNER/TENANT. COORDINATE ALL WORK.

THE CONTRACTOR SHALL FURNISH ADEQUATE FORCES, CONSTRUCTION PLANT, AND EQUIPMENT, AND SHALL WORK SUCH HOURS, INCLUDING NIGHT SHIFTS, OVERTIME OPERATIONS, SUNDAY, AND HOLIDAYS IN ACCORDANCE WITH THE OWNERS OPERATIONAL SCHEDULE. IF THE CONTRACTOR FALLS BEHIND PROGRESS REQUIRED IN THE OPERATIONAL SCHEDULE, THE CONTRACTOR SHALL TAKE SUCH STEPS AS MAY BE NECESSARY TO IMPROVE HIS PROGRESS, AND THE OWNER MAY REQUIRE HIM TO INCREASE THE NUMBER OF SHIFTS AND/OR OVERTIME OPERATIONS, DAY OF WORK AND/OR THE AMOUNT OF CONSTRUCTION PLANT, AT NO ADDITIONAL COST TO THE OWNER UNDER THIS CONTRACT. (IT SHALL BE UNDERSTOOD THAT SEVERAL BID PACKAGES MAY BE CONSTRUCTED BY VARIOUS CONTRACTOR/SUB-CONTRACTORS WITHIN THE SAME WORK SPACE SIMULTANEOUSLY.)

38. USE OF MC CABLE IS NOT ACCEPTABLE.

39. MINIMUM CONDUIT SIZE IS ¾” EXCEPT FOR FIXTURE WHIPS NOT EXCEEDING 6 FEET IN LENGTH AND FINAL EQUIPMENT CONNECTIONS NOT EXCEEDING 6 FEET

IN LENGTH ARE PERMITTED TO BE ½”.

40. EMT FITTINGS SHALL BE STEEL COMPRESSION TYPE WITH INSULATED THROAT. CONDUIT FITTINGS FOR RACEWAYS OTHER THAN EMT SHALL BE MADE OF

STEEL OR MALLEABLE IRON AND SHALL HAVE AN INSULATED THROAT.

41. ALL CIRCUITS AND WIRING DEVICES SHALL BE RATED A MINIMUM OF 20 AMPS.

NOTES:

1. ALL DEVICES TO BE GREY WITH SMOOTH METAL #302 S.S. PLATES UNLESS OTHERWISE NOTED.

2. DASHED ITEM DENOTES "EXISTING".

3. "R" BY DEVICE DENOTES EXISTING TO BE REMOVED COMPLETELY.

4. "H" BY DEVICE DENOTES DEVICE TO BE MOUNTED HORIZONTALLY.

5. MOUNT SWITCHES AT 48" AFF TO TOP.

6. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

7. ALL ITEMS NOTED ON THE LEGENDS DO NOT NECESSARILY APPEAR ON PLANS.

REMARKS:

a. U.L. LISTED FOR WET LOCATION IN CLOSED POSITION.

b. SUPPORT OUTLET BOX FROM STRUCTURE WITH (1) 3/8" ALL THREADS MINIMUM. BOXES LARGER THAN 25 SQUARE INCHES SHALL BE

SUPPORTED WITH (2) 3/8" ALL THREADS MINIMUM.

c. U.L. LISTED FOR WET LOCATION IN OPEN POSITION WITH ATTACHMENT PLUG INSERTED.

d. JUNCTION/OUTLET BOX SHALL BE SIZED AS REQUIRED FOR CONDUCTOR/DEVICE FILL PER N.E.C.

e. THREADED CONDUIT HUBS SHALL BE SIZED AND CONFIGURED AS REQUIRED FOR APPLICATION.

f. IF WITHIN 30 MILES OF THE COAST LINE, COPPER FREE CAST ALUMINUM OUTLET BOXES SHALL BE USED FOR EXTERIOR

APPLICATIONS.

g. PROVIDE KINDORF MTG. RACK FOR FREE STANDING APPLICATIONS. KINDORF SHALL BE PVC COATED FOR EXTERIOR APPLICATIONS.

ALL CUT ENDS ARE TO BE SEALED.

h. WHEN SURFACE JUNCTION BOX SYMBOL IS COMBINED WITH DEVICE SYMBOL, PROVIDE APPROPRIATE SURFACE PLATE FOR OUTLET

APPLICATION.

i. MAINTAIN WORKING CLEARANCES IN STRICT ACCORDANCE WITH N.E.C. CORRDINATE EXACT LOCATION OF EQUIPMENT WITH ALL DISCIPLINES (I.E. STRUCTURAA, HVAC, PLUMBING, FIRE PROTECTION, KITCHEN, MILLWORK, ETC.) PRIOR TO ROUTH-IN TO MAINTAIN

CLEARANCES.

j. OUTLET BOX SHALL BE SIZED PER SYSTEM INSTALLER REQUIREMENTS.

k. COORDINATE THE TELEPONE/DATA/SYSTEMS DEVICE, WIRE, CABLE, ETC. WITH THE TELE/DATA/SYSTEMS SPECIFICATIONS, DRAWINGS AND/OR SYMBOL LEGENDS..

l. [PROVIDE 1"C. TO CEILING SPACE] [PROVIDE 1"C. TO [TTB] [STB][CTB] [PROVIDE CONDUIT AS CALLED FOR ON SYSTEMS

PLANS/SYMBOL LEGENDS]

SYMBOL LEGEND

SYMBOL DESCRIPTION DESIGN SELECTION APPROVED SUBSTITUTION APPROVED SUBSTITUTION REMARKS

A - AMERAGE

A/C - AIR CONDITIONING

A.C. - ALTERNATING CURRENT

A/E - ARCHITECT/ENGINEER (OR ENGINEER

WHEN ARCHITECT NOT APPLICABLE)

AFD - ADJUSTABLE FREQUENCY DRIVE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AHU - AIR HANDLER UNIT

AIC - AMPS INTERRUPTING CAPACITY

AL - ALUMINUM

ALT - ALTERNATE

ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE

AWG - AMERICAN WIRE GAUGE

B.C. - BARE COPPER

BLDG - BUILDING

BRKR - BREAKER

C. - CONDUIT

C.B. - CIRCUIT BREAKER

CD. - CANDELA

CKT. - CIRCUIT

C/L - CENTER LINE

CLG. - CEILING

COMP. - COMPRESSOR

CONN. - CONNECTION

COND. - CONDENSER

CONT. - CONTINUOUS

C.R.I. - COLOR RENDERING INDEX

C.T. - CURRENT TRANSFORMER

CU. - COPPER

C.U. - COMPRESSOR CONDENSER UNIT

CW - COLD WATER

D - DEMO

D.B. - DIRECT BURIAL

D.W. - DIRECT CURRENT

C. - DISCONNECT

DPST - DOUBLE POLE SINGLE THROW

DWG - DRAWING

EC - ELECTRICAL CONTRACTOR

(OR GENERAL CONTRACTOR)

DN. - ELEVATOR

EMT - ELECTRIC METALLIC TUBING

EPA - ENVIRONMENTAL PROTECTION AGENCY

EQUIP. - EQUIPMENT

EST - ESTIMATE

ETR - EXISTING TO REMAIN

FAAP - FIRE ALARM ANNUNCIATOR PANEL

FACP - FIRE ALARM CONTROL PANEL

FATC - FIRE ALARM TERMINAL CABINET

FCCP - FIRE ALARM COMMAND CENTER PANEL

ELECTRICAL ABBREVIATIONS

FLA - FULL LOAD AMPERES

FT. - FEET

FLR - FLOOR

F.C. - FOOTCANDLES

G - GROUND FAULT CIRCUIT INTERRUPTER

GAL. - GALLON

GALV. - GALVANIZED

GPH - GALLONS PER HOUR

GPM - GALLONS PER MINUTE

GFI - GROUND FAULT INTERRUPTING

GRS - GALVANIZED RIGID STEEL CONDUIT

GND. - GROUND

HTG - HEATERS

HT - HEIGHT

HZ - HERTZ (CYCLES)

H.P.F. - HIGH POWER FACTOR

HP. - HORSEPOWER

HR. - HOUR

H.S. - HEAT STRIP

IMC - INTERMEDIATE METALLIC CONDUIT

IN. - INCHES

J.B. - JUNCTION BOX

KVA - KILOVOLT AMPERE

KW - KILOWATTS

KWH - KILOWATT HOUR

K - KELVIN

L.L.D. - LAMP LUMEN DEPRECIATION

LED - LIGHT EMITTING DIODE

LIU - LIGHT INTERFACE UNIT

LT. - LIGHT

LTG. - LIGHTING

LTS. - LIGHTS

L.P.F. - LOW POWER FACTOR

M.C.B. - MAIN CIRCUIT BREAKER

M.L.O. - MAIN LUGS ONLY

MAINT. - MAINTENANCE

MH. - METAL HALIDE

MFG. - MANUFACTURER

MCM - THOUSAND CIRCULAR MILS

MOCP - MINIMUM OVERCURRENT

PROTECTION

MIN - MINIMUM

MCP - MOTOR CIRCUIT PROTECTOR

MTD - MOUNTED

N. - NEUTRAL

NEC - NATIONAL ELECTRIC CODE

NEMA - NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NFPA - NATIONAL FIRE PROTECTION ASSOCIATION

N.P.T. - NATIONAL PIPE THREAD

NF - NON FUSED

N.C. - NORMALLY CLOSED

N.O. - NORMALLY OPEN

NIC. - NOT IN CONTRACT

NO. - NUMBER

O.L. - OVERLOAD

% - PERCENT

∅ - PHASE

P. - POLE

P.T. - POTENTIAL TRANSFORMER

PB - PULLBOX

PNL - PANEL

PR - PAIR

PRI. - PRIMARY

R - REMOVED

RECEP - RECEPTACLE

REL - RELOCATE

RPM - REVOLUTIONS PER MINUTE

R.S. - RAPID START

SCA - SHORT CIRCUIT AMPS

SEC. - SECONDARY

S/N - SOLID NEUTRAL

SPST - SINGLE POLE SINGLE THROW

SF - SQUARE FOOT

SW. - SWITCH

SWBD - SWITCHBOARD

SYS. - SYSTEM

THHN - THWN NYLON JACKETED WIRE

TTB - TELEPHONE TERMINAL BOARD

TTC - TELEPHONE TERMINAL CABINET

TV - TELEVISION

TVTC - TELEVISION TERMINAL CABINET

TVEC - TELEVISION EQUIP. CABINET

TYP - TYPICAL TEMP. - TEMPERATURE

U.L. - UNDERWRITERS' LABORATORIES

VFD - VARIABLE FREQUENCY DRIVE

VHF - VERY HIGH FREQUENCY

VHO - VERY HIGH OUTPUT

V - VOLT

VA - VOLT AMPERES

VOL. - VOLUME

W - WIRE

W.G. - WIRE GUARD

W.P. - WEATHERPROOF

XFMR - TRANSFORMER

Y - WYE

YD. - YARD

YR. - YEAR

3R - RAINPROOF

4X - STAINLESS STEEL DUSTIGHT,

WATERTIGHT

T O

METER, AS NOTED

DISCONNECT SWITCH, SIZE AS NOTED

TRANSFORMER

SQUARE "D" G.E. SIEMENS g, i

SQUARE "D" G.E. SIEMENS i

TV

WPG

WALL OUTLET BOX AND 20 AMP

DUPLEX RECEPTACLE

WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE FOR

TELEVISION, MOUNT ADJACENT TO TELEVISION OUTLET AT

84"AFF UNLESS OTHERWISE NOTED.

FLUSH WALL OUTLET BOX AND 20 AMP WEATHER RESISTANT

SELF-TESTING GFCI DUPLEX RECEPTACLE WITH CAST

ALUMINUM WEATHER PROOF IN USE COVER

P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d

P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d

P&S #2097TRWRGRY WITH

THOMAS & BETTS #CKMGV

OR INTERMATIC

#WP1010MC

HUBBELL #GF5362SGGY WITH

THOMAS & BETTS #CKMGV OR

HUBBELL #WP26M COVER

LEVITON #G5362-WTG WITH

THOMAS & BETTS #CKMGV

OR INTERMATIC

#WP1010MC

a, d

G

HOME RUN WIRING. ONE CIRCUIT PER ARROW HEAD

CONDUIT CAPPED OFF

CONDUIT CONTINUED

CONDUIT RUN UP

CONDUIT RUN DOWN

CONDUIT SEAL-OFF FITTING

GROUND WIRE, CONCEALED

GROUND OR GROUND ROD AS NOTED

CROUSE HINDS APPLETON e

WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE

MOUNTED ABOVE COUNTER. COORDINATE WITH

ARCHITECTURAL PLANS

P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d

CAST IRON ZINC PLATED SURFACE MTD. OUTLET BOX AND

WEATHERPROOF BLANK PLATE

APPLETON #FS-ID

WITH #DS-100G COVER

a, d, e, f, g, hWP

120/208V BRANCH CIRCUIT PANELBOARD SURFACE MOUNTED SQUARE "D" G.E. SIEMENS i

ELECTRICAL SHEET INDEX - CHICKEE HUT

SHEET

NUMBER SHEET NAME

E002 GENERAL NOTES, FIXTURE SCHEDULE, & SHEET INDEX

E013 OVERALL SITE PLAN - POWER

E102 CHICKEE HUT - FLOOR PLAN - POWER

CODE REFERENCE:

NATIONAL ELECTRIC CODE, 2020

NO. DESCRIPTION DATE

SCOTT LA IN

No 69099P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

PHONE (239) 332-1187

12467 Brantley Commons, Fort Myers, FL 33907

FAX (239) 332-5195CERT. OF AUTH. No. 5096 ENG. BUS. No. EB-0005096

A

B

C

D

RG ARCHITECTS P.A.

Fort Myers, FL 33901

P (239) 332-2040

F (239) 332-2049

2070 McGregor Boulevard, Suite 1 www.rgarchitectspa.com

CONSULTANT

OWNER

PROJECT TITLE

PROJECT ADDRESS

SHEET ID

SHEET TITLE

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

SEAL

a r c h i t e c t s

CHICKEE HUT - HURRICANE IAN

CHICKEE HUT - BAREFOOT BEACH

RESTORATION

/8

/2

:4

:0

P M

A u to d e s k D o c s /2

C C

B a re fo o t B e a c h R e s to ra ti o n

/2

-1

E le c tr ic a l

R e v it

B

IM

.r v t

E013

505 BAREFOOT BEACH BOULEVARD,

NAPLES, FL 34134

OVERALL SITE PLAN -

POWER

AB

SL

07.10.2025

AB

2332 000

PENINSULA ENGINEERING

2600 GOLDEN GATE PKWY, NAPLES,

FL 34105

1/32" = 1'-0"

1 SITE PLAN B - PROPOSED PARKING LOT #1 - POWER

1/32" = 1'-0"

16' 32' 64'

GENERAL NOTES:

1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.

2. REFER TO SPECIFICATIONS.

3. ALL HEX NOTES NOT NECESSARILY USED ON ALL SHEETS.

HEX NOTES

1 DISCONNECT AND REMOVE EXISTING RECEPTACLE IS THIS AREA.

2 NEW RECEPTACLE AT BUTTERFLY GARDEN.

3 CONNECT NEW RECEPTACLE TO EXISTING SPARE CIRCUIT.

CONTRACTOR SHALL PROVIDE UPDATED PANEL SCHEDULE.

NO. DESCRIPTION DATE

AREA A

AREA B

AREA B

AREA C

WPG

WPG

WPG

WPG

WPG

TV

6' AFF 6' AFF

6' AFF

6' AFF

6' AFF

WPG

6' AFF

2 2

SCOTT LA IN

No 69099P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

PHONE (239) 332-1187

12467 Brantley Commons, Fort Myers, FL 33907

FAX (239) 332-5195CERT. OF AUTH. No. 5096 ENG. BUS. No. EB-0005096

A

B

C

D

RG ARCHITECTS P.A.

Fort Myers, FL 33901

P (239) 332-2040

F (239) 332-2049

2070 McGregor Boulevard, Suite 1 www.rgarchitectspa.com

CONSULTANT

OWNER

PROJECT TITLE

PROJECT ADDRESS

SHEET ID

SHEET TITLE

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

SEAL

a r c h i t e c t s

CHICKEE HUT - HURRICANE IAN

CHICKEE HUT - BAREFOOT BEACH

RESTORATION

/8

/2

:4

:0

P M

A u to d e s k D o c s /2

C C

B a re fo o t B e a c h R e s to ra ti o n

/2

-1

E le c tr ic a l

R e v it

B

IM

.r v t

E102

505 BAREFOOT BEACH BOULEVARD,

NAPLES, FL 34134

CHICKEE HUT - FLOOR

PLAN - POWER

AB

SL

07.10.2025

AB

2332 000

PENINSULA ENGINEERING

2600 GOLDEN GATE PKWY, NAPLES,

FL 34105

1/4" = 1'-0"

2 RENOVATION - CHIKEE HUT - POWER

1/4" = 1'-0"

2' 4' 8' 1/4" = 1'-0"

1 DEMOLITION - CHIKEE HUT - POWER

1/4" = 1'-0"

2' 4' 8'

GENERAL NOTES:

1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.

2. REFER TO SPECIFICATIONS.

3. ALL HEX NOTES NOT NECESSARILY USED ON ALL SHEETS.

HEX NOTES

1 CLEAN AND REMOVE EXISTING HANDHOLE. REMOVE ALL

ELECTRICAL WIRE AND CONDUIT ASSOICATED WITH ELECTRICAL

EQUIPMENT BACK TO SOURCE. CONTRACTOR SHALL TRACE

EXISTING CIRCUIT BACK TO SOURCE.

2 DISCONNECT AND REMOVE EXISTING ELECTRICAL/LIGHT

FIXTURES.CONTRACTOR SHALL TRACE EXISTING CIRCUIT BACK

TO SOURCE AND USE EXISTING CIRCUIT BREAKER FOR

RENOVATION.

3 NEW HANDHOLE, FLUSH IN GRADE.

4 NEW FAN/LIGHT COMBINATION FIXTURE. BASIS OF DESIGN:

HUNTER #52589 WITH #99779 60" WIRE EXTENSION KIT AND #99742

48" DOWNROD OR EQUAL.

5 RUN CONDUIT UP CHICKEE HUT COLUMN AND ALONG ROOF TO

FAN/LIGHT FIXTURES.

6 CONNECT NEW ELECTRICAL AND LIGHT FIXTURES TO EXISTING

SPARE CIRCUIT. CONTRACTOR SHALL PROVIDE UPDATED PANEL

SCHEDULE.

NO. DESCRIPTION DATE

E002
E013
E102
FL PE 69099
2025-08-21T12:06:39-0400
Scott M Lain
Printed copies of this document are not considered signed and sealed and the SHA authentication code must be verified on any electronic copies.

File details come from the government source that posted it. Updated .