2435.CSC_Dental Permit Docs.pdf

PDF 382 KB Posted

Attached to
BID# 2026-23 Sunnyside Clinic Remodel
Solicitation number
S-C01010-00016880
Issued by
Clackamas County, Oregon

About this file

This document comprises dental permit and construction specification drawings for the Clackamas County Sunnyside Sterilization Center located at 9775 SE Sunnyside Road Suite #200, Clackamas, OR 97015, prepared by Patterson Dental Supply. The project involves the installation of dental sterilization equipment and associated infrastructure modifications, including new sterilizers (Midmark M11-020 units), sterilization cabinets (A-DEC 594 models), an ultrasonic cleaner (Midmark UC300), and a Statim G4 autoclave. The drawings include general notes, floor plans, electrical and low-voltage specifications, and plumbing plans scaled at 1/4" = 1'-0" with detailed elevation views. The project is marked "FOR REFERENCE ONLY" and "NOT FOR CONSTRUCTION," indicating these are concept drawings prepared with issue date 12/10/2025 by Kevin Jamison, Equipment Representative #448-2753650, with contact information (503) 505-2284. The drawings establish the framework for construction coordination between Patterson Dental, the general contractor, and various subcontractors.

The document delineates clear responsibility divisions whereby Patterson Dental provides dental-specific shop drawings and periodic job site inspections at critical construction phases, while the general contractor assumes responsibility for all construction execution, ADA compliance, adherence to state and local building codes, and coordination with mechanical, plumbing, and electrical subcontractors. A mandatory pre-construction meeting between Patterson Dental representatives and all contractors must occur before work commences, with the general contractor required to sign off on specifications and maintain a complete set of drawings on-site. The contractor bears full responsibility for modifications to accommodate Patterson equipment, including support structures and clearances around sprinkler systems, with any deviations from specifications requiring prior written approval from the Patterson equipment specialist and the owner. All electrical, mechanical, plumbing, and low-voltage connections must comply with state and local codes, with the contractor responsible for obtaining necessary installation permits and procuring Med Gas certified plumbing subcontractors if nitrous-oxide systems are involved. Final inspection and completion of all infrastructure work must occur prior to equipment installation, and the contractor is responsible for maintaining a clean job site and removing all debris throughout construction.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

THESE DRAWINGS AND SPECIFICATIONS ARE THE

PROPERTY OF PATTERSON DENTAL SUPPLY AND THE

USE LIMITED TO A SPECIFIED PROJECT FOR THE

PERSON OR PERSONS NAMED HEREON FOR THE

CONSTRUCTION OF ONE BUILDING ONLY. ANY USE OR

REPRODUCTIONS OF THESE DRAWINGS ARE STRICTLY

PROHIBITED WITHOUT THE WRITTEN PERMISSION OF

PATTERSON DENTAL SUPPLY, INC.

WRITTEN DIMENSIONS SHALL TAKE PREFERENCE OVER

SCALE DIMENSIONS AND SHALL BE VERIFIED ON THE

JOB SITE.

ANY DISCREPANCIES OR CHANGES SHALL BE BROUGHT

TO THE ATTENTION OF PATTERSON DENTAL SUPPLY

PRIOR TO THE COMMENCEMENT OF ANY WORK.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL

CURRENT AMERICAN DISABILITIES ACT, (ADA)

ACCESSABILITY GUIDELINES.

THE CONTRACTOR SHALL ALSO BE RESPOSIBLE FOR

ALL REQUIRED BACKFLOW PREVENTERS.

THE CONTRACTOR SHALL COMPLY WITH ALL STATE,

CITY AND LOCAL CODES, PERTAINNG TO THE

CONSTRUCTION OF THIS PROJECT.

DRAWN BY

ISSUE DATE:

NOTE:

MODIFICATIONS TO THIS SPACE TO ALLOW THE PROPER

FIT & FUNCTION OF THE EQUIPMENT SUPPLIED BY

PATTERSON DENTAL SHALL BE THE RESPONSIBILITY OF

THE OWNER/TENANT/LANDLORD/CONTRACTOR IN

REGARDS TO CODE COMPLIANCE OF STRUCTURAL,

ELECTRICAL, MECHANICAL, AND PLUMBING ISSUES. THIS

INCLUDES, BUT IS NOT LIMITED TO, SUPPORT

STRUCTURE FOR EQUIPMENT AND CLEARANCES IN

REGARD TO SPRINKLER HEADS AND/OR ANY DEVICE OR

STRUCTURE WHICH MAY IMPEDE OR CONFLICT WITH THE

FUNCTION OF PATTERSON SUPPLIED EQUIPMENT.

PATTERSON DENTAL SHALL NOT BEAR ANY COST TO

CORRECT THESE ISSUES. PLEASE CONSULT PATTERSON

FOR ASSISTANCE IN EQUIPMENT SUPPORT STRUCTURE &

CLEARANCE QUESTIONS.

SHEET NO.

EQUIPMENT REP: EQUIPMENT REP #:

PROJECT #:

THE INFORMATION CONTAINED IN THESE DRAWINGS IS FOR

CONCEPT PURPOSES ONLY. THESE DRAWINGS ARE NOT

TO BE USED FOR CONSTRUCTION AND DO NOT TAKE THE

PLACE OF CONSTRUCTION PLANS AND SPECIFICATIONS.

THESE DRAWINGS ARE NOT TO SCALE; NOR HAVE FIELD

CONDITIONS BEEN VERIFIED. PATTERSON WILL NOT BE

HELD RESPONSIBLE FOR THE USE OR MISUSE OF THE

INFORMATION CONTAINED IN THESE DRAWINGS.

N O

T F

O R

C O

N S

T R

U C

T

IO

N N

O T

F O

R C

O N

S T

R U

C T

IO

N

OWNER:

LOCATION:

A u to d e s k D o c s /4

-C la c k a m a s C o u n ty

S u n n y s id e S te ri liz a ti o n

C e n te r-

/4

-C la c k a m a s C o u n ty S u n n y s id e S te ri liz a ti o n C e n te r-

.r v t

KWK

1031 MENDOTA HEIGHTS ROAD

MENDOTA HEIGHTS, MN

Clackamas County Sunnyside Sterilization Center

9775 SE. Sunnyside Road Suite #200 Clackamas, OR. 97015

12/10/2025

DA001DA001DA001DA001

Kevin Jamison (503) 505-2284

448-2753650

PATTERSON DENTAL:

PATTERSON DENTAL'S RESPONSIBILITIES WILL INCLUDE BUT NOT BE LIMITED TO THE

FOLLOWING:

1. PATTERSON DENTAL WILL PROVIDE A SET OF DENTAL SPECIFIC SHOP DRAWINGS

TO AID THE CONTRACTOR AND/OR ARCHITECT OF THE OWNER'S CHOOSING IN THE

CONSTRUCTION OF THE OWNER'S DENTAL OFFICE. THESE DRAWINGS WILL

PROVIDE CRITICAL DENTAL LOCATIONS OF ALL DENTAL EQUIPMENT. WRITTEN

DIMENSIONS WILL TAKE PRECEDENCE OVER SCALED DIMENSIONS.

2. PATTERSON DENTAL WILL ASSUME NO RESPONSIBILITY FOR DEVIATIONS FROM

THE DENTAL DRAWINGS AND SPECIFICATIONS WITHOUT PRIOR WRITTEN

ENDORSEMENT.

3. PATTERSON DENTAL'S REPRESENTATIVES WILL PROVIDE ASSISTANCE AS NEEDED

TO THE CONTRACTOR AND/OR ARCHITECT WITH PROPER ADVANCE NOTICE.

4. A PRE-CONSTRUCTION MEETING BETWEEN PATTERSON DENTAL'S

REPRESENTATIVES AND THE CONTRACTOR, ARCHITECT, AND SUB-CONTRACTORS

TO INCLUDE MECHANICAL, PLUMBING, AND ELECTRICAL IS REQUIRED. DENTAL

SPECIFIC TEMPLATES AND SPECIFIC CONSTRUCTION REQUIREMENTS WILL BE

PROVIDED DURING THIS MEETING.

5. PATTERSON DENTAL'S REPRESENTATIVES WILL MAKE PERIODIC VISITS TO THE JOB

SITE AT CRITICAL POINTS IN THE CONSTRUCTION PROCESS. THE CONTRACTOR IS

REQUIRED TO INFORM PATTERSON WHEN INSPECTIONS OF PLUMBING, WIRING,

AND BACKING IN THE WALLS CAN BE PERFORMED PRIOR TO BACKFILLING

TRENCHES, POURING OF THE SLAB, SEALING PARTITIONS AND INSTALLING

CEILINGS.

6. PATTERSON DENTAL'S REPRESENTATIVES WILL COORDINATE WITH THE

CONTRACTOR TO INSTALL THE DENTAL EQUIPMENT AS LAID OUT IN THE

INSTALLATION GUIDELINES AT A DATE AGREED UPON BY THE CONTRACTOR AND

PATTERSON. A FINAL INSPECTION PRIOR TO THE INSTALLATION OF THE DENTAL

EQUIPMENT WILL BE PERFORMED TO ENSURE THAT ALL PLUMBING, ELECTRICAL

AND MECHANICAL CONSTRUCTION IS COMPLETE. ALL FLOORING, PAINTING AND

CEILING WORK MUST BE COMPLETED PRIOR TO EQUIPMENT INSTALLATION.

7. THE CONTRACTOR AND SUB-CONTRACTORS ARE TO PROVIDE FINAL HOOK UP TO

ALL DENTAL EQUIPMENT AS SET FORTH THE INSTALLATION GUIDELINES.

BUILDING CONTRACTOR:

1. THE BUILDING CONTRACTOR WHO HAS ENTERED INTO A CONSTRUCTION

CONTRACT WITH THE OWNER IS RESPONSIBLE FOR ALL WORK DEFINED BY THAT

CONTRACT. IF THE PROJECT IS LET UNDER SEPARATE CONTRACTS TO MORE THAN

ONE CONTRACTOR, THE RESPONSIBILITIES LISTED BELOW APPLY TO EACH

CONTRACTOR.

2. THE CONTRACTOR IS RESPONSIBLE FOR THE COMPLETION OF THE PROJECT IN

THE TRUE INTENT OF THE DRAWINGS AND SPECIFICATIONS. THE CONTRACTOR IS

TO FURNISH ALL MATERIALS AND LABOR REQUIRED TO COMPLETE THE PROJECT,

THAT IS NOT SPECIFICALLY PROVIDED BY PATTERSON DENTAL, WHETHER OR NOT

EACH AND EVERY ITEM IS SPECIFICALLY MENTIONED.

3. THE CONTRACTOR SHALL ADVISE THE OWNER OF ANY CONFLICT BETWEEN THESE

DRAWINGS AND THE FIELD CONDITIONS BEFORE PROCEEDING WITH THE JOB. THE

CONTRACTOR SHALL ASSUME ALL RESPONSIBILITY FOR THE ACCURACY OF FIELD

MEASUREMENTS AND CONDITIONS AND SHALL BE RESPONSIBLE FOR THE PROPER

MODIFICATIONS TO ANY EXISTING WORK, PREVIOUSLY INSTALLED WORK, AND/OR

OTHER TRADES. WRITTEN APPROVAL MUST BE OBTAINED FROM THE PATTERSON

EQUIPMENT SPECIALIST ASSIGNED TO THE PROJECT BEFORE ANY CHANGES

AND/OR DEVIATIONS FROM THE DRAWINGS AND SPECIFICATIONS ARE MADE. THE

CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR THE EXECUTION OF

HIS/HER WORK AND FOR ANY CHANGES AND/OR DEVIATIONS FROM THE DRAWINGS

OR SPECIFICATIONS MADE WITHOUT PRIOR WRITTEN APPROVAL FROM THE

OWNER AND/OR THE PATTERSON EQUIPMENT SPECIALIST. ANY COSTS RESULTING

FROM CHANGES AND/OR DEVIATIONS SHALL BE THE RESPONSIBILITY OF THE

CONTRACTOR.

4. A COMPLETE SET OF DRAWINGS MUST BE KEPT AT THE JOB SITE AT ALL TIMES AND

ANY CHANGES MUST BE NOTED THEREON AND INITIALED AT THE TIME THE CHANGE

OR DEVIATION IS PERFORMED.

5. THE GENERAL CONTRACTOR SHALL DO ALL PATCHING TO CONFORM TO MATERIAL,

TEXTURE AND SURFACE ALIGNMENT WITH THE ADJOINING SURFACE AND FINAL

TOUCH UP/APPEARANCE OF ALL FINISHED SURFACES. THE CONTRACTOR SHALL

ENSURE THE PROTECTION OF ALL EQUIPMENT FURNISHED UNDER HIS/HER

CONTRACT AND BY OTHERS PRESENT AT THE JOB SITE.

6. THE CONTRACTOR SHALL REMOVE DEBRIS AND MAINTAIN THE PREMISES BROOM

CLEAN AT ALL TIMES. DEBRIS IS TO INCLUDE, BUT NOT LIMITED TO SHIPPING

CARTONS, BOXES, ETC., RESULTING FROM THE INSTALLATION OF DENTAL AND

OTHER EQUIPMENT BY CONTRACTORS CONCURRENTLY ENGAGED.

7. THE CONTRACTOR SHALL PARTICIPATE AT ALL JOB COORDINATION MEETINGS

WITH PATTERSON DENTAL AND ENSURE THE ATTENDANCE OF APPLICABLE

TRADES.

8. THE CONTRACTOR IS REQUIRED TO INFORM PATTERSON DENTAL

REPRESENTATIVES OF KEY EVENTS IN THE CONSTRUCTION PROCESS WITH

REASONABLE ADVANCE NOTICE, TO FACILITATE THE INSPECTION OF SAID EVENTS,

I.E. BACKFILLING TRENCHES, CLOSING WALLS, POURING CONCRETE TO BURY

PLUMBING AND ELECTRICAL WORK IN FLOORS AND INSTALLING CEILING TILES.

9. THE CONTRACTOR SHALL AFFORD THE OWNER AND SEPARATE CONTRACTORS

REASONABLE OPPORTUNITY FOR THE INTRODUCTION AND/OR STORAGE OF THEIR

MATERIALS AND EQUIPMENT AND EXECUTION OF THEIR WORK.

GENERAL NOTES:

1. THE ITEMS LISTED HERE IN THE GENERAL NOTES ARE INTENDED TO CLARIFY

OVERALL GENERAL CONDITIONS FOR A SMOOTH TRANSITION BETWEEN ALL SUB-

CONTRACTORS, THE GENERAL CONTRACTOR, EQUIPMENT INSTALLERS,

PATTERSON DENTAL AND THE OWNER FOR FINAL APPROVAL OF ALL WORK

PERFORMED BY THE RESPECTIVE TRADES. THROUGHOUT THESE PLANS ARE

VARIOUS DETAILS, REQUIREMENTS AND SPECIFICATIONS TO AID IN THIS PROCESS.

IT IS THE RESPONSIBILITY OF EACH TRADE, CONTRACTOR AND THE OWNER TO

READ ALL NOTES AND ILLUSTRATIONS THAT PERTAIN TO THEIR SPECIFIC TASK IN

THE PROCESS.

2. MOST OF THE DENTAL UTILITY AND SPECIFICATION REQUIREMENTS ARE OUTLINED

IN THE TEMPLATES AND DOCUMENTATION THAT PATTERSON WILL PROVIDE TO THE

CONTRACTOR. QUESTIONS WILL ARISE ON THE JOB SITE AND MOST CAN BE

ANSWERED BY TELEPHONE. THE CONTRACTOR WILL BE PROVIDED CONTACT

NUMBERS FOR PATTERSON DENTAL REPRESENTATIVES TO FACILITATE TIMELY

ANSWERS TO THOSE QUESTIONS. IN SOME CASES IT WILL BE NECESSARY FOR

THE PATTERSON REPRESENTATIVE TO BE PRESENT AT THE JOB SITE TO ANSWER

QUESTIONS OR SPOT LOCATIONS FOR DENTAL SPECIFIC ITEMS. IN THESE CASES

AN APPOINTMENT WILL BE REQUIRED WITH REASONABLE ADEQUATE

NOTIFICATION.

3. IF A JOB SITE APPOINTMENT IS REQUIRED, ALL TRADES SHOULD BE NOTIFIED OF

THE APPOINTMENT SO THE OPTION OF BEING PRESENT WITH ANY QUESTIONS

CONCERNING THEIR PORTION OF THE JOB CAN BE ADMINISTERED AT THAT

APPOINTMENT. THE PATTERSON DENTAL REPRESENTATIVE SHOULD BE INFORMED

AS TO THE MAGNITUDE OF THE APPOINTMENT PRIOR TO ARRIVAL ON THE JOB SITE

IN ORDER TO ALLOW ENOUGH TIME IN THE APPOINTMENT.

4. THE GENERAL CONTRACTOR MUST SIGN THIS SHEET STIPULATING THAT THEY

UNDERSTAND AND WILL COMPLY WITH ALL SPECIFICATIONS BEFORE ANY WORK

WILL COMMENCE. A SIGNED COPY OF THE PLANS ARE TO BE RETURNED TO

PATTERSON DENTAL AND A SECOND SIGNED COPY KEPT ON THE JOB SITE AT ALL

TIMES.

5. THE PATTERSON DENTAL REPRESENTATIVE SHALL GIVE INSTRUCTIONS TO THE

GENERAL CONTRACTOR ONLY. ALL COMMUNICATIONS AND COORDINATION WITH

TRADESMEN SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR

UNLESS PREDETERMINED TO BE OTHERWISE.

6. ALL ELECTRICAL, MECHANICAL AND PLUMBING CONNECTIONS TO DENTAL

EQUIPMENT WILL BE PERFORMED BY THE APPLICABLE TRADE RESPONSIBLE.

INSTALLATION PERMITS, IF REQUIRED, WILL BE OBTAINED BY THE TRADES THAT

PROVIDE THAT SERVICE.

7. IF NECESSARY, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROCURING A

MED GAS CERTIFIED PLUMBING SUB-CONTRACTOR FOR ANY LEVEL 3 NITROUS-

OXYGEN CONSCIOUS SEDATION SYSTEM DETAILED IN THESE PLANS. ANY NITROUS

OXIDE SYSTEM DESIGN SHOWN ON THESE PLANS IS TO BE USED AS AN

ILLUSTRATION ONLY FOR THE PURPOSE OF LOCATING END USER OUTLET

STATIONS, CYLINDER ROOM MANIFOLD AND ALARM PANEL. THE FINAL TRUNK

SYSTEM INSTALLATION SHALL STRICTLY ADHERE TO ONLY MECHANICALLY

ENGINEERED DRAWINGS, IF SUPPLIED.

8. THE PLUMBING SUB-CONTRACTOR SHALL PROVIDE MED GAS CERTIFICATION IN

ACCORDANCE WITH ANY REQUESTS BY THE OWNER, CONTRACTOR, BUILDING

DEPARTMENT OR PATTERSON DENTAL PRIOR TO COMMENCING WORK ON ANY

TYPE OF CUSTOMER INSTALLED NITROUS OXIDE SYSTEM BEING USED IN THE

CONSTRUCTION PROJECT.

9. ALL PLUMBING AND ELECTRICAL LINES TO BE CONCEALED UNLESS OTHERWISE

SPECIFIED.

10. ALL LABOR AND MATERIALS NECESSARY FOR CHANGES IN EXISTING PLUMBING,

CARPENTRY, AND ELECTRICAL WORK MUST BE DONE AND SUPPLIED BY THE

CONTRACTOR AND IS NOT INCLUDED IN THE COST OF THE DENTAL EQUIPMENT.

11. THE CONTRACTOR SHALL REMOVE ALL RUBBISH AND DO ALL PATCHING AFTER

ROUGHING IN IS COMPLETED.

12. ALL ROUGH IN AND FINISH WORK FOR DENTAL EQUIPMENT IS TO BE ACCORDING

TO TEMPLATES FURNISHED BY THE MANUFACTURERS OF THE EQUIPMENT BEING

INSTALLED. A REPRESENTATIVE OF PATTERSON DENTAL WILL POSITION THE

TEMPLATES IN THEIR PROPER LOCATIONS, AT WHICH TIME ALL SPECIFICATIONS ON

THE PLANS WILL BE EXPLAINED TO THE CONTRACTOR OR SUB-CONTRACTOR(S).

ALL SPECIFIED SIZES OF PIPES, TUBING, AND/OR FITTINGS, ETC., MUST BE RIGIDLY

FOLLOWED AS WELL AS PROPER HEIGHTS MARKED. ANY INFRACTIONS ON SIZES

OR HEIGHTS OF PIPES, TUBING AND/OR FITTINGS WILL HAVE TO BE CORRECTED

BEFORE THE EQUIPMENT CAN BE INSTALLED AND SUCH EXTRA EXPENSE WILL BE

THE RESPONSIBILITY OF THE CONTRACTOR AND/OR SUB-CONTRACTOR.

13. THE DOCTOR/OWNER SHALL DESIGNATE RESPONSIBILITY FOR PROVIDING AND

INSTALLING CABINETS AND COUNTERTOPS (OTHER THAN THOSE SPECIFIED

AND/OR CONTRACTED BY PATTERSON DENTAL).

14. THE DOCTOR SHALL MAKE ARRANGEMENTS FOR INSTALLATION OF NON-DENTAL

SYSTEMS BEFORE WALLS ARE CLOSED.

15. PATTERSON DENTAL SHALL NOT BE HELD RESPONSIBLE FOR MULTIMEDIA

SYSTEMS SUCH AS ENTERTAINMENT TVS, MONITORS, NETWORK COMPUTER

SYSTEMS OR ANY ITEMS NOT SHOWN ON THESE PLANS.

16. GC MUST CONFIRM ALL MEASUREMENTS OF SPACE CONDITIONS PRIOR TO

STARTING DEMOLITION

17. GC SHOULD NOTIFY PATTERSON EQUIPMENT SPECIALIST 1(ONE GC MUST CONFIRM

ALL MEASUREMENTS OF SPACE CONDITIONS PRIOR TO STARTING DEMOLITION)

WEEK PRIOR TO CLOSING OF ALL WALLS, CEILINGS, FLOORS TO ALLOW FINAL

INSPECTION OF INSTALLATION.

18. GC IS RESPONSIBLE FOR CONFIRMING ALL UTILITIES FOR EXISTING EQ BEING

MOVED FROM EXISTING LOCATION OR EQUIPMENT NOT SUPPLIED BY PATTERSON

19. GC IS RESPONSIBLE FOR CONFIRMING ALL UTILITIES FOR EXISTING EQ BEING

MOVED FROM EXISTING LOCATION OR EQUIPMENT NOT SUPPLIED BY PATTERSON

20. RADIATION PROTECTION: THE DOCTOR’S ARCHITECT/GC ARE REQUIRED TO

REVIEW ALL LOCAL AND NATIONAL RADIATION AND XRAY SHIELDING

REQUIREMENTS AND SUBMIT AN APPLICATION FOR REGISTRATION OF IONIZING

RADIATION SOURCES. PLANS MUST BE SUBMITTED TO RADIATION CONTROL

PROGRAM, IF APPLICABLE, ALONG WITH OTHER INFORMATION THEY WILL PROVIDE

A LETTER OF ACCEPTABLE X-RAY PROTECTION OR ADVISE OTHERWISE. THIS

APPLICATION AND PLAN SHOULD BE SUBMITTED PRIOR TO WALLS GOING UP.

COPY OF APPROVAL LETTER FROM LOCAL GOVERNING BODY MUST BE PROVIDED

TO PATTERSON EQUIPMENT SPECIALIST AND SERVICE TECHNICIAN. NOTE: IF

EXISTING X-RAYS TO BE REPLACED WITH NEW AND EXISTING SHIELDING IS TO BE

REUSED ARCHITECT/GC MUST VERIFY NEEDS WITH LOCAL CODE OFFICER.

Sheet List

Sheet Number Sheet Name

DA001 GENERAL NOTES

DA111 LVL 1 FLOOR PLAN

DE110 LVL 1 ELECTRICAL & LOW VOLTAGE

DP110 LVL 1 PLUMBING

ABBREVIATION LEGEND

AFF ABOVE FINISHED FLOOR

DR SUPPLIED BY DOCTOR

EC ELECTRICAL CONTRACTOR

ER EXISTING RELOCATED

EX EXISTING

FT FUTURE

GC GENERAL CONTRACTOR

MTD MOUNTED

NC NO CHANGE

NIC NOT INCLUDED

NIS NOT IN SCOPE

NW NEW

PC PLUMBING CONTRACTOR

PD PATTERSON DENTAL

TYP TYPICAL

VFY VERIFY

VIF VERIFY IN FIELD

REVISIONS

REV

# SCOPE

DRAWN

BY DATE

MalloryFair Text Box

FOR REFERENCE ONLY

DENTAL FURNITURE & EQUIPMENT

EQUIPMENT NUMBER TAG

(NUMBERS ARE RANDOM)

DENTAL FURNITURE & EQUIPMENT

EXISTING RELOCATED

DENTAL FURNITURE & EQUIPMENT

FUTURE

PLAN LEGEND

EXISTING WALL

DEMO WALL

NEW WALL

WALL LEGEND

SOUND PROOFING IN WALL

LEAD LINED WALL S

T

E R

IL

IZ

A T

IO

N

(E) OP

(E) MED GAS

(E) MECH

(E) DENTIST OFFICE

(E) WORKSATION

(E) OP

(E) RR

(E) OPEN OPS

(E) PANO

/4

/2

5' - 8 1/2"

51A

22A

THESE DRAWINGS AND SPECIFICATIONS ARE THE

PROPERTY OF PATTERSON DENTAL SUPPLY AND THE

USE LIMITED TO A SPECIFIED PROJECT FOR THE

PERSON OR PERSONS NAMED HEREON FOR THE

CONSTRUCTION OF ONE BUILDING ONLY. ANY USE OR

REPRODUCTIONS OF THESE DRAWINGS ARE STRICTLY

PROHIBITED WITHOUT THE WRITTEN PERMISSION OF

PATTERSON DENTAL SUPPLY, INC.

WRITTEN DIMENSIONS SHALL TAKE PREFERENCE OVER

SCALE DIMENSIONS AND SHALL BE VERIFIED ON THE

JOB SITE.

ANY DISCREPANCIES OR CHANGES SHALL BE BROUGHT

TO THE ATTENTION OF PATTERSON DENTAL SUPPLY

PRIOR TO THE COMMENCEMENT OF ANY WORK.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL

CURRENT AMERICAN DISABILITIES ACT, (ADA)

ACCESSABILITY GUIDELINES.

THE CONTRACTOR SHALL ALSO BE RESPOSIBLE FOR

ALL REQUIRED BACKFLOW PREVENTERS.

THE CONTRACTOR SHALL COMPLY WITH ALL STATE,

CITY AND LOCAL CODES, PERTAINNG TO THE

CONSTRUCTION OF THIS PROJECT.

DRAWN BY

ISSUE DATE:

NOTE:

MODIFICATIONS TO THIS SPACE TO ALLOW THE PROPER

FIT & FUNCTION OF THE EQUIPMENT SUPPLIED BY

PATTERSON DENTAL SHALL BE THE RESPONSIBILITY OF

THE OWNER/TENANT/LANDLORD/CONTRACTOR IN

REGARDS TO CODE COMPLIANCE OF STRUCTURAL,

ELECTRICAL, MECHANICAL, AND PLUMBING ISSUES. THIS

INCLUDES, BUT IS NOT LIMITED TO, SUPPORT

STRUCTURE FOR EQUIPMENT AND CLEARANCES IN

REGARD TO SPRINKLER HEADS AND/OR ANY DEVICE OR

STRUCTURE WHICH MAY IMPEDE OR CONFLICT WITH THE

FUNCTION OF PATTERSON SUPPLIED EQUIPMENT.

PATTERSON DENTAL SHALL NOT BEAR ANY COST TO

CORRECT THESE ISSUES. PLEASE CONSULT PATTERSON

FOR ASSISTANCE IN EQUIPMENT SUPPORT STRUCTURE &

CLEARANCE QUESTIONS.

SHEET NO.

EQUIPMENT REP: EQUIPMENT REP #:

PROJECT #:

THE INFORMATION CONTAINED IN THESE DRAWINGS IS FOR

CONCEPT PURPOSES ONLY. THESE DRAWINGS ARE NOT

TO BE USED FOR CONSTRUCTION AND DO NOT TAKE THE

PLACE OF CONSTRUCTION PLANS AND SPECIFICATIONS.

THESE DRAWINGS ARE NOT TO SCALE; NOR HAVE FIELD

CONDITIONS BEEN VERIFIED. PATTERSON WILL NOT BE

HELD RESPONSIBLE FOR THE USE OR MISUSE OF THE

INFORMATION CONTAINED IN THESE DRAWINGS.

N O

T F

O R

C O

N S

T R

U C

T

IO

N N

O T

F O

R C

O N

S T

R U

C T

IO

N

OWNER:

LOCATION:

A u to d e s k D o c s /4

-C la c k a m a s C o u n ty

S u n n y s id e S te ri liz a ti o n

C e n te r-

/4

-C la c k a m a s C o u n ty S u n n y s id e S te ri liz a ti o n C e n te r-

.r v t

KWK

1031 MENDOTA HEIGHTS ROAD

MENDOTA HEIGHTS, MN

Clackamas County Sunnyside Sterilization Center

9775 SE. Sunnyside Road Suite #200 Clackamas, OR. 97015

12/10/2025

DA111DA111DA111DA111

Kevin Jamison (503) 505-2284

448-2753650

REVISIONS

REV

# SCOPE

DRAWN

BY DATE

1/4" = 1'-0"

LVL 1 FLOOR PLAN

EQUIPMENT SCHEDULE

QTY

EQUIPMENT INFO

ITEM # DESCRIPTION STATUS MANUFACTURER MODEL S

U

P P

L

IE

D B

Y

IN

S

T A

L L E

D B

Y

EQUIPMENT

REMARKS

1 51 STERILIZER NW MIDMARK M11-020 PD PD

1 51A STERILIZER ER MIDMARK M11-020 DR PD

STERILIZATION

1 22 STERILIZATION CABINET NW A-DEC 594 PD PD

1 22A STERILIZATION CABINET NW A-DEC 594 PD PD

1 52 ULTRASONIC CLEANER ER MIDMARK UC300 DR PD

1 54 STATIM ER SCICAN STATIM G4 DR PD

MalloryFair

51A

+64"+42"+26"

+64"+42"+26"

+18"

+18"

PROVIDE POWER OUTLETS

IN BASE OF CABINETS FOR

EQUIPMENT

DRYER CABINET

REQUIRES DEDICATED

POWER

PROVIDE POWER OUTLETS

IN BASE OF CABINETS FOR

EQUIPMENT

18/3 WIRE, CABLE RUN IN WALLS

OR ABOVE FINISHED CEILING

18/4 WIRE, WIRES RUN IN WALLS

OR ABOVE FINISHED CEILING

CAT5e OR BETTER CABLE, CABLE RUN

IN WALLS OR ABOVE FINISHED CEILING

MANUFACTURER CABLE, CABLE RUN IN

WALLS OR ABOVE FINISHED CEILING

ELECTRICAL CONDUIT UNDER

FLOOR, SIZE AS INDICATED ON PLAN

ELECTRICAL CONDUIT ABOVE

CEILING, SIZE AS INDICATED ON PLAN

ELECTRICAL LEGEND

LVL 1

0"

7 1/2"

PROVIDE POWER FOR

EQUIPMENT IN BASE OF

CABINETS

22A

LVL 1

0"

51A

4' - 6 3/4" 4 1/2" 5' - 7 3/4"

PROVIDE DEDICATED POWER

FOR DRYER IN BASE OF

CABINETS

LVL 1

0"

2' - 5 1/2"11"

PROVIDE POWER FOR

EQUIPMENT IN BASE OF

CABINETS

THESE DRAWINGS AND SPECIFICATIONS ARE THE

PROPERTY OF PATTERSON DENTAL SUPPLY AND THE

USE LIMITED TO A SPECIFIED PROJECT FOR THE

PERSON OR PERSONS NAMED HEREON FOR THE

CONSTRUCTION OF ONE BUILDING ONLY. ANY USE OR

REPRODUCTIONS OF THESE DRAWINGS ARE STRICTLY

PROHIBITED WITHOUT THE WRITTEN PERMISSION OF

PATTERSON DENTAL SUPPLY, INC.

WRITTEN DIMENSIONS SHALL TAKE PREFERENCE OVER

SCALE DIMENSIONS AND SHALL BE VERIFIED ON THE

JOB SITE.

ANY DISCREPANCIES OR CHANGES SHALL BE BROUGHT

TO THE ATTENTION OF PATTERSON DENTAL SUPPLY

PRIOR TO THE COMMENCEMENT OF ANY WORK.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL

CURRENT AMERICAN DISABILITIES ACT, (ADA)

ACCESSABILITY GUIDELINES.

THE CONTRACTOR SHALL ALSO BE RESPOSIBLE FOR

ALL REQUIRED BACKFLOW PREVENTERS.

THE CONTRACTOR SHALL COMPLY WITH ALL STATE,

CITY AND LOCAL CODES, PERTAINNG TO THE

CONSTRUCTION OF THIS PROJECT.

DRAWN BY

ISSUE DATE:

NOTE:

MODIFICATIONS TO THIS SPACE TO ALLOW THE PROPER

FIT & FUNCTION OF THE EQUIPMENT SUPPLIED BY

PATTERSON DENTAL SHALL BE THE RESPONSIBILITY OF

THE OWNER/TENANT/LANDLORD/CONTRACTOR IN

REGARDS TO CODE COMPLIANCE OF STRUCTURAL,

ELECTRICAL, MECHANICAL, AND PLUMBING ISSUES. THIS

INCLUDES, BUT IS NOT LIMITED TO, SUPPORT

STRUCTURE FOR EQUIPMENT AND CLEARANCES IN

REGARD TO SPRINKLER HEADS AND/OR ANY DEVICE OR

STRUCTURE WHICH MAY IMPEDE OR CONFLICT WITH THE

FUNCTION OF PATTERSON SUPPLIED EQUIPMENT.

PATTERSON DENTAL SHALL NOT BEAR ANY COST TO

CORRECT THESE ISSUES. PLEASE CONSULT PATTERSON

FOR ASSISTANCE IN EQUIPMENT SUPPORT STRUCTURE &

CLEARANCE QUESTIONS.

SHEET NO.

EQUIPMENT REP: EQUIPMENT REP #:

PROJECT #:

THE INFORMATION CONTAINED IN THESE DRAWINGS IS FOR

CONCEPT PURPOSES ONLY. THESE DRAWINGS ARE NOT

TO BE USED FOR CONSTRUCTION AND DO NOT TAKE THE

PLACE OF CONSTRUCTION PLANS AND SPECIFICATIONS.

THESE DRAWINGS ARE NOT TO SCALE; NOR HAVE FIELD

CONDITIONS BEEN VERIFIED. PATTERSON WILL NOT BE

HELD RESPONSIBLE FOR THE USE OR MISUSE OF THE

INFORMATION CONTAINED IN THESE DRAWINGS.

N O

T F

O R

C O

N S

T R

U C

T

IO

N N

O T

F O

R C

O N

S T

R U

C T

IO

N

OWNER:

LOCATION:

A u to d e s k D o c s /4

-C la c k a m a s C o u n ty

S u n n y s id e S te ri liz a ti o n

C e n te r-

/4

-C la c k a m a s C o u n ty S u n n y s id e S te ri liz a ti o n C e n te r-

.r v t

KWK

1031 MENDOTA HEIGHTS ROAD

MENDOTA HEIGHTS, MN

Clackamas County Sunnyside Sterilization Center

9775 SE. Sunnyside Road Suite #200 Clackamas, OR. 97015

12/10/2025

DE110DE110DE110DE110

Kevin Jamison (503) 505-2284

448-2753650

1/4" = 1'-0"

LVL 1 POWER & LOW VOLTAGE PLAN

ALL DEVICES ARE TO BE INSTALLED PER STATE AND LOCAL CODES.

GENERAL NOTES

EQUIPMENT POWER & LOW VOLTAGE SCHEDULE

QTY

EQUIPMENT INFO ELECTRICAL INFO LOW VOLTAGE INFO

ITEM # DESCRIPTION STATUS E

C

C O

N N

E C

T

IO

N B

Y

POWER CONNECTION TYPE

ELECTRICAL REMARKS L

V

C O

N N

E C

T

IO

N B

Y

E M

P T

Y C

O N

D U

IT

/4

E

M P

T Y

C O

N D

U

IT

E M

P T

Y C

O N

D U

IT

/3

W

IR

E

/4

W

IR

E

J B

O X

L V

C A

T e

O R

B E

T T

E R

M F

G C

A B

L E

M O

N

IT

O R

C A

B L E

LV REMARKSVOLTS AMPS S

IN

G L

E O

U T

L E

T

D U

P L E

X O

U T

L E

T

Q U

A D

O U

T L

E T

D

IR

E C

T W

IR

E

D E

D

IC

A T

E D

P O

W E

R

J B

O X

1 22 STERILIZATION CABINET NW EC 120v 20.0 ● EC TO LEAVE MIN 3' FLEXIBLE CONDUIT EC ● RUN LOW VOTLTAGE WIRES AND OR CABLES TO LOCATIONS

INDICATED ON PLANS

1 22A STERILIZATION CABINET NW EC 120v 20.0 ● EC TO LEAVE MIN 3' FLEXIBLE CONDUIT EC ● RUN LOW VOTLTAGE WIRES AND OR CABLES TO LOCATIONS

INDICATED ON PLANS

1 51 STERILIZER NW EC 120v 12.0 ● ● DEDICATED POWER EC

1 51A STERILIZER ER EC 120v 12.0 ● ● DEDICATED POWER EC

1 52 ULTRASONIC CLEANER ER EC 120v 2.0 ● EC

1 54 STATIM ER EC 120v 11.0 ● ● EC

+XX" - INDICATES HEIGHT FROM FINISHED FLOOR TO CENTER OF DEVICE UNLESS OTHERWISE

NOTED BELOW, IF ITEM NOT TAGGED HEIGHT IS 18" A.F.F.

ALL DEVICES SHALL BE INSTALLED PER STATE AND LOCAL CODE.

ALL LOCATIONS SHOULD BE VERIFIED WITH PATTERSON REP OR OWNER PRIOR TO PLACEMENT.

ELECTRICAL SYMBOLS

QTY. SYM. DESCRIPTION

PDSI_Vent And Exhaust Remarks

PDSI_Exhaust Comments

3 120v DUPLEX DEDICATED OUTLET WALL, IF TAG NOT

PRESENT HEIGHT IS 18" A.F.F. TO CENTER OF DEVICE

2 120v QUAD OUTLET WALL, IF TAG NOT PRESENT

HEIGHT IS 18" A.F.F. TO CENTER OF DEVICE

+XX" - INDICATES HEIGHT FROM FINISHED FLOOR TO CENTER OF DEVICE

UNLESS OTHERWISE NOTED BELOW, IF ITEM NOT TAGGED HEIGHT IS 18" A.F.F.

ALL DEVICES SHALL BE INSTALLED PER STATE AND LOCAL CODE. ALL

LOCATIONS SHOULD BE VERIFIED WITH PATTERSON REP OR OWNER PRIOR TO

PLACEMENT.

LOW VOLTAGE SYMBOLS

QTY. SYM. DESCRIPTION

3 DATA DEVICE WALL, IF TAG NOT PRESENT HEIGHT IS 18"

A.F.F.

REVISIONS

REV

# SCOPE

DRAWN

BY DATE

3/4" = 1'-0"

ELEVATION STERILIZATION WALL LEG 1

3/4" = 1'-0"

ELEVATION STERILIZATION WALL LEG 2

3/4" = 1'-0"

ELEVATION STERILIZATION WALL LEG 3

MalloryFair

DE1103

THESE DRAWINGS AND SPECIFICATIONS ARE THE

PROPERTY OF PATTERSON DENTAL SUPPLY AND THE

USE LIMITED TO A SPECIFIED PROJECT FOR THE

PERSON OR PERSONS NAMED HEREON FOR THE

CONSTRUCTION OF ONE BUILDING ONLY. ANY USE OR

REPRODUCTIONS OF THESE DRAWINGS ARE STRICTLY

PROHIBITED WITHOUT THE WRITTEN PERMISSION OF

PATTERSON DENTAL SUPPLY, INC.

WRITTEN DIMENSIONS SHALL TAKE PREFERENCE OVER

SCALE DIMENSIONS AND SHALL BE VERIFIED ON THE

JOB SITE.

ANY DISCREPANCIES OR CHANGES SHALL BE BROUGHT

TO THE ATTENTION OF PATTERSON DENTAL SUPPLY

PRIOR TO THE COMMENCEMENT OF ANY WORK.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL

CURRENT AMERICAN DISABILITIES ACT, (ADA)

ACCESSABILITY GUIDELINES.

THE CONTRACTOR SHALL ALSO BE RESPOSIBLE FOR

ALL REQUIRED BACKFLOW PREVENTERS.

THE CONTRACTOR SHALL COMPLY WITH ALL STATE,

CITY AND LOCAL CODES, PERTAINNG TO THE

CONSTRUCTION OF THIS PROJECT.

DRAWN BY

ISSUE DATE:

NOTE:

MODIFICATIONS TO THIS SPACE TO ALLOW THE PROPER

FIT & FUNCTION OF THE EQUIPMENT SUPPLIED BY

PATTERSON DENTAL SHALL BE THE RESPONSIBILITY OF

THE OWNER/TENANT/LANDLORD/CONTRACTOR IN

REGARDS TO CODE COMPLIANCE OF STRUCTURAL,

ELECTRICAL, MECHANICAL, AND PLUMBING ISSUES. THIS

INCLUDES, BUT IS NOT LIMITED TO, SUPPORT

STRUCTURE FOR EQUIPMENT AND CLEARANCES IN

REGARD TO SPRINKLER HEADS AND/OR ANY DEVICE OR

STRUCTURE WHICH MAY IMPEDE OR CONFLICT WITH THE

FUNCTION OF PATTERSON SUPPLIED EQUIPMENT.

PATTERSON DENTAL SHALL NOT BEAR ANY COST TO

CORRECT THESE ISSUES. PLEASE CONSULT PATTERSON

FOR ASSISTANCE IN EQUIPMENT SUPPORT STRUCTURE &

CLEARANCE QUESTIONS.

SHEET NO.

EQUIPMENT REP: EQUIPMENT REP #:

PROJECT #:

THE INFORMATION CONTAINED IN THESE DRAWINGS IS FOR

CONCEPT PURPOSES ONLY. THESE DRAWINGS ARE NOT

TO BE USED FOR CONSTRUCTION AND DO NOT TAKE THE

PLACE OF CONSTRUCTION PLANS AND SPECIFICATIONS.

THESE DRAWINGS ARE NOT TO SCALE; NOR HAVE FIELD

CONDITIONS BEEN VERIFIED. PATTERSON WILL NOT BE

HELD RESPONSIBLE FOR THE USE OR MISUSE OF THE

INFORMATION CONTAINED IN THESE DRAWINGS.

N O

T F

O R

C O

N S

T R

U C

T

IO

N N

O T

F O

R C

O N

S T

R U

C T

IO

N

OWNER:

LOCATION:

A u to d e s k D o c s /4

-C la c k a m a s C o u n ty

S u n n y s id e S te ri liz a ti o n

C e n te r-

/4

-C la c k a m a s C o u n ty S u n n y s id e S te ri liz a ti o n C e n te r-

.r v t

KWK

1031 MENDOTA HEIGHTS ROAD

MENDOTA HEIGHTS, MN

Clackamas County Sunnyside Sterilization Center

9775 SE. Sunnyside Road Suite #200 Clackamas, OR. 97015

12/10/2025

DP110DP110DP110DP110

Kevin Jamison (503) 505-2284

448-2753650

1/4" = 1'-0"

LVL 1 PLUMBING PLAN

ALL ITEMS TO BE INSTALLED PER STATE AND LOCAL CODES..

GENERAL NOTES:

EQUIPMENT PLUMBING-DENTAL COMPRESSED AIR-VAC SCHEDULE

Q

T Y

PLUMBING PLUMBING INFO VAC INFO DENTAL COMPRESSED AIR

ITEM # DESCRIPTION STATUS

SUPPLY SANITARY

PLUMBING REMARKS

RISERS

MAIN &

BRANCHES

VAC REMARKS 1

/2

C

O P

P E

R T

Y P

E L

O R

K

/8

C

O P

P E

R T

Y P

E M

COMPRESSED AIR REMARKSP

L U

M B

IN

G

C O

N N

E C

T

IO

N B

Y

/4

C

O L D

W A

T E

R F

L E

X T

U B

IN

G

/2

C

O L D

W A

T E

R C

O P

P E

R

/2

H

O T

W A

T E

R C

O P

P E

R

/4

C

O L D

W A

T E

R C

O P

P E

R

/4

H

O T

W A

T E

R C

O P

P E

R

C O

L D

W A

T E

R C

O P

P E

R

/4

C

O P

P E

R T

Y P

E M

-1

/2

P V

C W

A S

T E

S C

H E

D U

L E

D R

A

IN

D

IR

E C

T

D R

A

IN

I N

D

IR

E C

T

D R

A

IN

S T

A N

D P

IP

E

/2

P

V C

S C

H E

D U

L E

/8

P

V C

S C

H E

D U

L E

/4

P

V C

S C

H E

D U

L E

-1

/2

P V

C S

C H

E D

U L

E

P V

C S

C H

E D

U L E

P V

C S

C H

E D

U L E

1 22 STERILIZATION CABINET NW PC ● ● ● ● ●

1 22A STERILIZATION CABINET NW PC ● ● ● ● ●

+XX" - INDICATES HEIGHT FROM FINISHED FLOOR TO CENTER OF DEVICE

UNLESS OTHERWISE NOTED BELOW, IF ITEM NOT TAGGED HEIGHT IS 18" A.F.F.

ALL DEVICES SHALL BE INSTALLED PER STATE AND LOCAL CODES. ALL

LOCATIONS SHOULD BE VERIFIED WITH PATTERSON REP OR OWNER PRIOR

TO PLACEMENT.

PLUMBING SYMBOLS

QTY. SYM. DESCRIPTION

2 1/2" OD. TO 3/8" OD.SHUT OFF AIR CONNECTION WALL,

HEIGHT 3" A.F.F. TO CENTER IF TAG NOT PRESENT

2 DIRECT DRAIN WALL

2 SHUT OFF VALVE COLD WATER WALL

2 SHUT OFF VALVE HOT WATER WALL

REVISIONS

REV

# SCOPE

DRAWN

BY DATE

MalloryFair

DA001 GENERAL NOTES
DA111 LVL 1 FLOOR PLAN
DE110 LVL 1 ELECTRICAL & LOW VOLTAGE
DP110 LVL 1 PLUMBING

File details come from the government source that posted it. Updated .