2435.CSC_Dental Permit Docs.pdf
PDF 382 KB Posted
- Attached to
- BID# 2026-23 Sunnyside Clinic Remodel
- Solicitation number
- S-C01010-00016880
- Issued by
- Clackamas County, Oregon
About this file
This document comprises dental permit and construction specification drawings for the Clackamas County Sunnyside Sterilization Center located at 9775 SE Sunnyside Road Suite #200, Clackamas, OR 97015, prepared by Patterson Dental Supply. The project involves the installation of dental sterilization equipment and associated infrastructure modifications, including new sterilizers (Midmark M11-020 units), sterilization cabinets (A-DEC 594 models), an ultrasonic cleaner (Midmark UC300), and a Statim G4 autoclave. The drawings include general notes, floor plans, electrical and low-voltage specifications, and plumbing plans scaled at 1/4" = 1'-0" with detailed elevation views. The project is marked "FOR REFERENCE ONLY" and "NOT FOR CONSTRUCTION," indicating these are concept drawings prepared with issue date 12/10/2025 by Kevin Jamison, Equipment Representative #448-2753650, with contact information (503) 505-2284. The drawings establish the framework for construction coordination between Patterson Dental, the general contractor, and various subcontractors.
The document delineates clear responsibility divisions whereby Patterson Dental provides dental-specific shop drawings and periodic job site inspections at critical construction phases, while the general contractor assumes responsibility for all construction execution, ADA compliance, adherence to state and local building codes, and coordination with mechanical, plumbing, and electrical subcontractors. A mandatory pre-construction meeting between Patterson Dental representatives and all contractors must occur before work commences, with the general contractor required to sign off on specifications and maintain a complete set of drawings on-site. The contractor bears full responsibility for modifications to accommodate Patterson equipment, including support structures and clearances around sprinkler systems, with any deviations from specifications requiring prior written approval from the Patterson equipment specialist and the owner. All electrical, mechanical, plumbing, and low-voltage connections must comply with state and local codes, with the contractor responsible for obtaining necessary installation permits and procuring Med Gas certified plumbing subcontractors if nitrous-oxide systems are involved. Final inspection and completion of all infrastructure work must occur prior to equipment installation, and the contractor is responsible for maintaining a clean job site and removing all debris throughout construction.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THESE DRAWINGS AND SPECIFICATIONS ARE THE
PROPERTY OF PATTERSON DENTAL SUPPLY AND THE
USE LIMITED TO A SPECIFIED PROJECT FOR THE
PERSON OR PERSONS NAMED HEREON FOR THE
CONSTRUCTION OF ONE BUILDING ONLY. ANY USE OR
REPRODUCTIONS OF THESE DRAWINGS ARE STRICTLY
PROHIBITED WITHOUT THE WRITTEN PERMISSION OF
PATTERSON DENTAL SUPPLY, INC.
WRITTEN DIMENSIONS SHALL TAKE PREFERENCE OVER
SCALE DIMENSIONS AND SHALL BE VERIFIED ON THE
JOB SITE.
ANY DISCREPANCIES OR CHANGES SHALL BE BROUGHT
TO THE ATTENTION OF PATTERSON DENTAL SUPPLY
PRIOR TO THE COMMENCEMENT OF ANY WORK.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CURRENT AMERICAN DISABILITIES ACT, (ADA)
ACCESSABILITY GUIDELINES.
THE CONTRACTOR SHALL ALSO BE RESPOSIBLE FOR
ALL REQUIRED BACKFLOW PREVENTERS.
THE CONTRACTOR SHALL COMPLY WITH ALL STATE,
CITY AND LOCAL CODES, PERTAINNG TO THE
CONSTRUCTION OF THIS PROJECT.
DRAWN BY
ISSUE DATE:
NOTE:
MODIFICATIONS TO THIS SPACE TO ALLOW THE PROPER
FIT & FUNCTION OF THE EQUIPMENT SUPPLIED BY
PATTERSON DENTAL SHALL BE THE RESPONSIBILITY OF
THE OWNER/TENANT/LANDLORD/CONTRACTOR IN
REGARDS TO CODE COMPLIANCE OF STRUCTURAL,
ELECTRICAL, MECHANICAL, AND PLUMBING ISSUES. THIS
INCLUDES, BUT IS NOT LIMITED TO, SUPPORT
STRUCTURE FOR EQUIPMENT AND CLEARANCES IN
REGARD TO SPRINKLER HEADS AND/OR ANY DEVICE OR
STRUCTURE WHICH MAY IMPEDE OR CONFLICT WITH THE
FUNCTION OF PATTERSON SUPPLIED EQUIPMENT.
PATTERSON DENTAL SHALL NOT BEAR ANY COST TO
CORRECT THESE ISSUES. PLEASE CONSULT PATTERSON
FOR ASSISTANCE IN EQUIPMENT SUPPORT STRUCTURE &
CLEARANCE QUESTIONS.
SHEET NO.
EQUIPMENT REP: EQUIPMENT REP #:
PROJECT #:
THE INFORMATION CONTAINED IN THESE DRAWINGS IS FOR
CONCEPT PURPOSES ONLY. THESE DRAWINGS ARE NOT
TO BE USED FOR CONSTRUCTION AND DO NOT TAKE THE
PLACE OF CONSTRUCTION PLANS AND SPECIFICATIONS.
THESE DRAWINGS ARE NOT TO SCALE; NOR HAVE FIELD
CONDITIONS BEEN VERIFIED. PATTERSON WILL NOT BE
HELD RESPONSIBLE FOR THE USE OR MISUSE OF THE
INFORMATION CONTAINED IN THESE DRAWINGS.
N O
T F
O R
C O
N S
T R
U C
T
IO
N N
O T
F O
R C
O N
S T
R U
C T
IO
N
OWNER:
LOCATION:
A u to d e s k D o c s /4
-C la c k a m a s C o u n ty
S u n n y s id e S te ri liz a ti o n
C e n te r-
/4
-C la c k a m a s C o u n ty S u n n y s id e S te ri liz a ti o n C e n te r-
.r v t
KWK
1031 MENDOTA HEIGHTS ROAD
MENDOTA HEIGHTS, MN
Clackamas County Sunnyside Sterilization Center
9775 SE. Sunnyside Road Suite #200 Clackamas, OR. 97015
12/10/2025
DA001DA001DA001DA001
Kevin Jamison (503) 505-2284
448-2753650
PATTERSON DENTAL:
PATTERSON DENTAL'S RESPONSIBILITIES WILL INCLUDE BUT NOT BE LIMITED TO THE
FOLLOWING:
1. PATTERSON DENTAL WILL PROVIDE A SET OF DENTAL SPECIFIC SHOP DRAWINGS
TO AID THE CONTRACTOR AND/OR ARCHITECT OF THE OWNER'S CHOOSING IN THE
CONSTRUCTION OF THE OWNER'S DENTAL OFFICE. THESE DRAWINGS WILL
PROVIDE CRITICAL DENTAL LOCATIONS OF ALL DENTAL EQUIPMENT. WRITTEN
DIMENSIONS WILL TAKE PRECEDENCE OVER SCALED DIMENSIONS.
2. PATTERSON DENTAL WILL ASSUME NO RESPONSIBILITY FOR DEVIATIONS FROM
THE DENTAL DRAWINGS AND SPECIFICATIONS WITHOUT PRIOR WRITTEN
ENDORSEMENT.
3. PATTERSON DENTAL'S REPRESENTATIVES WILL PROVIDE ASSISTANCE AS NEEDED
TO THE CONTRACTOR AND/OR ARCHITECT WITH PROPER ADVANCE NOTICE.
4. A PRE-CONSTRUCTION MEETING BETWEEN PATTERSON DENTAL'S
REPRESENTATIVES AND THE CONTRACTOR, ARCHITECT, AND SUB-CONTRACTORS
TO INCLUDE MECHANICAL, PLUMBING, AND ELECTRICAL IS REQUIRED. DENTAL
SPECIFIC TEMPLATES AND SPECIFIC CONSTRUCTION REQUIREMENTS WILL BE
PROVIDED DURING THIS MEETING.
5. PATTERSON DENTAL'S REPRESENTATIVES WILL MAKE PERIODIC VISITS TO THE JOB
SITE AT CRITICAL POINTS IN THE CONSTRUCTION PROCESS. THE CONTRACTOR IS
REQUIRED TO INFORM PATTERSON WHEN INSPECTIONS OF PLUMBING, WIRING,
AND BACKING IN THE WALLS CAN BE PERFORMED PRIOR TO BACKFILLING
TRENCHES, POURING OF THE SLAB, SEALING PARTITIONS AND INSTALLING
CEILINGS.
6. PATTERSON DENTAL'S REPRESENTATIVES WILL COORDINATE WITH THE
CONTRACTOR TO INSTALL THE DENTAL EQUIPMENT AS LAID OUT IN THE
INSTALLATION GUIDELINES AT A DATE AGREED UPON BY THE CONTRACTOR AND
PATTERSON. A FINAL INSPECTION PRIOR TO THE INSTALLATION OF THE DENTAL
EQUIPMENT WILL BE PERFORMED TO ENSURE THAT ALL PLUMBING, ELECTRICAL
AND MECHANICAL CONSTRUCTION IS COMPLETE. ALL FLOORING, PAINTING AND
CEILING WORK MUST BE COMPLETED PRIOR TO EQUIPMENT INSTALLATION.
7. THE CONTRACTOR AND SUB-CONTRACTORS ARE TO PROVIDE FINAL HOOK UP TO
ALL DENTAL EQUIPMENT AS SET FORTH THE INSTALLATION GUIDELINES.
BUILDING CONTRACTOR:
1. THE BUILDING CONTRACTOR WHO HAS ENTERED INTO A CONSTRUCTION
CONTRACT WITH THE OWNER IS RESPONSIBLE FOR ALL WORK DEFINED BY THAT
CONTRACT. IF THE PROJECT IS LET UNDER SEPARATE CONTRACTS TO MORE THAN
ONE CONTRACTOR, THE RESPONSIBILITIES LISTED BELOW APPLY TO EACH
CONTRACTOR.
2. THE CONTRACTOR IS RESPONSIBLE FOR THE COMPLETION OF THE PROJECT IN
THE TRUE INTENT OF THE DRAWINGS AND SPECIFICATIONS. THE CONTRACTOR IS
TO FURNISH ALL MATERIALS AND LABOR REQUIRED TO COMPLETE THE PROJECT,
THAT IS NOT SPECIFICALLY PROVIDED BY PATTERSON DENTAL, WHETHER OR NOT
EACH AND EVERY ITEM IS SPECIFICALLY MENTIONED.
3. THE CONTRACTOR SHALL ADVISE THE OWNER OF ANY CONFLICT BETWEEN THESE
DRAWINGS AND THE FIELD CONDITIONS BEFORE PROCEEDING WITH THE JOB. THE
CONTRACTOR SHALL ASSUME ALL RESPONSIBILITY FOR THE ACCURACY OF FIELD
MEASUREMENTS AND CONDITIONS AND SHALL BE RESPONSIBLE FOR THE PROPER
MODIFICATIONS TO ANY EXISTING WORK, PREVIOUSLY INSTALLED WORK, AND/OR
OTHER TRADES. WRITTEN APPROVAL MUST BE OBTAINED FROM THE PATTERSON
EQUIPMENT SPECIALIST ASSIGNED TO THE PROJECT BEFORE ANY CHANGES
AND/OR DEVIATIONS FROM THE DRAWINGS AND SPECIFICATIONS ARE MADE. THE
CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR THE EXECUTION OF
HIS/HER WORK AND FOR ANY CHANGES AND/OR DEVIATIONS FROM THE DRAWINGS
OR SPECIFICATIONS MADE WITHOUT PRIOR WRITTEN APPROVAL FROM THE
OWNER AND/OR THE PATTERSON EQUIPMENT SPECIALIST. ANY COSTS RESULTING
FROM CHANGES AND/OR DEVIATIONS SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
4. A COMPLETE SET OF DRAWINGS MUST BE KEPT AT THE JOB SITE AT ALL TIMES AND
ANY CHANGES MUST BE NOTED THEREON AND INITIALED AT THE TIME THE CHANGE
OR DEVIATION IS PERFORMED.
5. THE GENERAL CONTRACTOR SHALL DO ALL PATCHING TO CONFORM TO MATERIAL,
TEXTURE AND SURFACE ALIGNMENT WITH THE ADJOINING SURFACE AND FINAL
TOUCH UP/APPEARANCE OF ALL FINISHED SURFACES. THE CONTRACTOR SHALL
ENSURE THE PROTECTION OF ALL EQUIPMENT FURNISHED UNDER HIS/HER
CONTRACT AND BY OTHERS PRESENT AT THE JOB SITE.
6. THE CONTRACTOR SHALL REMOVE DEBRIS AND MAINTAIN THE PREMISES BROOM
CLEAN AT ALL TIMES. DEBRIS IS TO INCLUDE, BUT NOT LIMITED TO SHIPPING
CARTONS, BOXES, ETC., RESULTING FROM THE INSTALLATION OF DENTAL AND
OTHER EQUIPMENT BY CONTRACTORS CONCURRENTLY ENGAGED.
7. THE CONTRACTOR SHALL PARTICIPATE AT ALL JOB COORDINATION MEETINGS
WITH PATTERSON DENTAL AND ENSURE THE ATTENDANCE OF APPLICABLE
TRADES.
8. THE CONTRACTOR IS REQUIRED TO INFORM PATTERSON DENTAL
REPRESENTATIVES OF KEY EVENTS IN THE CONSTRUCTION PROCESS WITH
REASONABLE ADVANCE NOTICE, TO FACILITATE THE INSPECTION OF SAID EVENTS,
I.E. BACKFILLING TRENCHES, CLOSING WALLS, POURING CONCRETE TO BURY
PLUMBING AND ELECTRICAL WORK IN FLOORS AND INSTALLING CEILING TILES.
9. THE CONTRACTOR SHALL AFFORD THE OWNER AND SEPARATE CONTRACTORS
REASONABLE OPPORTUNITY FOR THE INTRODUCTION AND/OR STORAGE OF THEIR
MATERIALS AND EQUIPMENT AND EXECUTION OF THEIR WORK.
GENERAL NOTES:
1. THE ITEMS LISTED HERE IN THE GENERAL NOTES ARE INTENDED TO CLARIFY
OVERALL GENERAL CONDITIONS FOR A SMOOTH TRANSITION BETWEEN ALL SUB-
CONTRACTORS, THE GENERAL CONTRACTOR, EQUIPMENT INSTALLERS,
PATTERSON DENTAL AND THE OWNER FOR FINAL APPROVAL OF ALL WORK
PERFORMED BY THE RESPECTIVE TRADES. THROUGHOUT THESE PLANS ARE
VARIOUS DETAILS, REQUIREMENTS AND SPECIFICATIONS TO AID IN THIS PROCESS.
IT IS THE RESPONSIBILITY OF EACH TRADE, CONTRACTOR AND THE OWNER TO
READ ALL NOTES AND ILLUSTRATIONS THAT PERTAIN TO THEIR SPECIFIC TASK IN
THE PROCESS.
2. MOST OF THE DENTAL UTILITY AND SPECIFICATION REQUIREMENTS ARE OUTLINED
IN THE TEMPLATES AND DOCUMENTATION THAT PATTERSON WILL PROVIDE TO THE
CONTRACTOR. QUESTIONS WILL ARISE ON THE JOB SITE AND MOST CAN BE
ANSWERED BY TELEPHONE. THE CONTRACTOR WILL BE PROVIDED CONTACT
NUMBERS FOR PATTERSON DENTAL REPRESENTATIVES TO FACILITATE TIMELY
ANSWERS TO THOSE QUESTIONS. IN SOME CASES IT WILL BE NECESSARY FOR
THE PATTERSON REPRESENTATIVE TO BE PRESENT AT THE JOB SITE TO ANSWER
QUESTIONS OR SPOT LOCATIONS FOR DENTAL SPECIFIC ITEMS. IN THESE CASES
AN APPOINTMENT WILL BE REQUIRED WITH REASONABLE ADEQUATE
NOTIFICATION.
3. IF A JOB SITE APPOINTMENT IS REQUIRED, ALL TRADES SHOULD BE NOTIFIED OF
THE APPOINTMENT SO THE OPTION OF BEING PRESENT WITH ANY QUESTIONS
CONCERNING THEIR PORTION OF THE JOB CAN BE ADMINISTERED AT THAT
APPOINTMENT. THE PATTERSON DENTAL REPRESENTATIVE SHOULD BE INFORMED
AS TO THE MAGNITUDE OF THE APPOINTMENT PRIOR TO ARRIVAL ON THE JOB SITE
IN ORDER TO ALLOW ENOUGH TIME IN THE APPOINTMENT.
4. THE GENERAL CONTRACTOR MUST SIGN THIS SHEET STIPULATING THAT THEY
UNDERSTAND AND WILL COMPLY WITH ALL SPECIFICATIONS BEFORE ANY WORK
WILL COMMENCE. A SIGNED COPY OF THE PLANS ARE TO BE RETURNED TO
PATTERSON DENTAL AND A SECOND SIGNED COPY KEPT ON THE JOB SITE AT ALL
TIMES.
5. THE PATTERSON DENTAL REPRESENTATIVE SHALL GIVE INSTRUCTIONS TO THE
GENERAL CONTRACTOR ONLY. ALL COMMUNICATIONS AND COORDINATION WITH
TRADESMEN SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR
UNLESS PREDETERMINED TO BE OTHERWISE.
6. ALL ELECTRICAL, MECHANICAL AND PLUMBING CONNECTIONS TO DENTAL
EQUIPMENT WILL BE PERFORMED BY THE APPLICABLE TRADE RESPONSIBLE.
INSTALLATION PERMITS, IF REQUIRED, WILL BE OBTAINED BY THE TRADES THAT
PROVIDE THAT SERVICE.
7. IF NECESSARY, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROCURING A
MED GAS CERTIFIED PLUMBING SUB-CONTRACTOR FOR ANY LEVEL 3 NITROUS-
OXYGEN CONSCIOUS SEDATION SYSTEM DETAILED IN THESE PLANS. ANY NITROUS
OXIDE SYSTEM DESIGN SHOWN ON THESE PLANS IS TO BE USED AS AN
ILLUSTRATION ONLY FOR THE PURPOSE OF LOCATING END USER OUTLET
STATIONS, CYLINDER ROOM MANIFOLD AND ALARM PANEL. THE FINAL TRUNK
SYSTEM INSTALLATION SHALL STRICTLY ADHERE TO ONLY MECHANICALLY
ENGINEERED DRAWINGS, IF SUPPLIED.
8. THE PLUMBING SUB-CONTRACTOR SHALL PROVIDE MED GAS CERTIFICATION IN
ACCORDANCE WITH ANY REQUESTS BY THE OWNER, CONTRACTOR, BUILDING
DEPARTMENT OR PATTERSON DENTAL PRIOR TO COMMENCING WORK ON ANY
TYPE OF CUSTOMER INSTALLED NITROUS OXIDE SYSTEM BEING USED IN THE
CONSTRUCTION PROJECT.
9. ALL PLUMBING AND ELECTRICAL LINES TO BE CONCEALED UNLESS OTHERWISE
SPECIFIED.
10. ALL LABOR AND MATERIALS NECESSARY FOR CHANGES IN EXISTING PLUMBING,
CARPENTRY, AND ELECTRICAL WORK MUST BE DONE AND SUPPLIED BY THE
CONTRACTOR AND IS NOT INCLUDED IN THE COST OF THE DENTAL EQUIPMENT.
11. THE CONTRACTOR SHALL REMOVE ALL RUBBISH AND DO ALL PATCHING AFTER
ROUGHING IN IS COMPLETED.
12. ALL ROUGH IN AND FINISH WORK FOR DENTAL EQUIPMENT IS TO BE ACCORDING
TO TEMPLATES FURNISHED BY THE MANUFACTURERS OF THE EQUIPMENT BEING
INSTALLED. A REPRESENTATIVE OF PATTERSON DENTAL WILL POSITION THE
TEMPLATES IN THEIR PROPER LOCATIONS, AT WHICH TIME ALL SPECIFICATIONS ON
THE PLANS WILL BE EXPLAINED TO THE CONTRACTOR OR SUB-CONTRACTOR(S).
ALL SPECIFIED SIZES OF PIPES, TUBING, AND/OR FITTINGS, ETC., MUST BE RIGIDLY
FOLLOWED AS WELL AS PROPER HEIGHTS MARKED. ANY INFRACTIONS ON SIZES
OR HEIGHTS OF PIPES, TUBING AND/OR FITTINGS WILL HAVE TO BE CORRECTED
BEFORE THE EQUIPMENT CAN BE INSTALLED AND SUCH EXTRA EXPENSE WILL BE
THE RESPONSIBILITY OF THE CONTRACTOR AND/OR SUB-CONTRACTOR.
13. THE DOCTOR/OWNER SHALL DESIGNATE RESPONSIBILITY FOR PROVIDING AND
INSTALLING CABINETS AND COUNTERTOPS (OTHER THAN THOSE SPECIFIED
AND/OR CONTRACTED BY PATTERSON DENTAL).
14. THE DOCTOR SHALL MAKE ARRANGEMENTS FOR INSTALLATION OF NON-DENTAL
SYSTEMS BEFORE WALLS ARE CLOSED.
15. PATTERSON DENTAL SHALL NOT BE HELD RESPONSIBLE FOR MULTIMEDIA
SYSTEMS SUCH AS ENTERTAINMENT TVS, MONITORS, NETWORK COMPUTER
SYSTEMS OR ANY ITEMS NOT SHOWN ON THESE PLANS.
16. GC MUST CONFIRM ALL MEASUREMENTS OF SPACE CONDITIONS PRIOR TO
STARTING DEMOLITION
17. GC SHOULD NOTIFY PATTERSON EQUIPMENT SPECIALIST 1(ONE GC MUST CONFIRM
ALL MEASUREMENTS OF SPACE CONDITIONS PRIOR TO STARTING DEMOLITION)
WEEK PRIOR TO CLOSING OF ALL WALLS, CEILINGS, FLOORS TO ALLOW FINAL
INSPECTION OF INSTALLATION.
18. GC IS RESPONSIBLE FOR CONFIRMING ALL UTILITIES FOR EXISTING EQ BEING
MOVED FROM EXISTING LOCATION OR EQUIPMENT NOT SUPPLIED BY PATTERSON
19. GC IS RESPONSIBLE FOR CONFIRMING ALL UTILITIES FOR EXISTING EQ BEING
MOVED FROM EXISTING LOCATION OR EQUIPMENT NOT SUPPLIED BY PATTERSON
20. RADIATION PROTECTION: THE DOCTOR’S ARCHITECT/GC ARE REQUIRED TO
REVIEW ALL LOCAL AND NATIONAL RADIATION AND XRAY SHIELDING
REQUIREMENTS AND SUBMIT AN APPLICATION FOR REGISTRATION OF IONIZING
RADIATION SOURCES. PLANS MUST BE SUBMITTED TO RADIATION CONTROL
PROGRAM, IF APPLICABLE, ALONG WITH OTHER INFORMATION THEY WILL PROVIDE
A LETTER OF ACCEPTABLE X-RAY PROTECTION OR ADVISE OTHERWISE. THIS
APPLICATION AND PLAN SHOULD BE SUBMITTED PRIOR TO WALLS GOING UP.
COPY OF APPROVAL LETTER FROM LOCAL GOVERNING BODY MUST BE PROVIDED
TO PATTERSON EQUIPMENT SPECIALIST AND SERVICE TECHNICIAN. NOTE: IF
EXISTING X-RAYS TO BE REPLACED WITH NEW AND EXISTING SHIELDING IS TO BE
REUSED ARCHITECT/GC MUST VERIFY NEEDS WITH LOCAL CODE OFFICER.
Sheet List
Sheet Number Sheet Name
DA001 GENERAL NOTES
DA111 LVL 1 FLOOR PLAN
DE110 LVL 1 ELECTRICAL & LOW VOLTAGE
DP110 LVL 1 PLUMBING
ABBREVIATION LEGEND
AFF ABOVE FINISHED FLOOR
DR SUPPLIED BY DOCTOR
EC ELECTRICAL CONTRACTOR
ER EXISTING RELOCATED
EX EXISTING
FT FUTURE
GC GENERAL CONTRACTOR
MTD MOUNTED
NC NO CHANGE
NIC NOT INCLUDED
NIS NOT IN SCOPE
NW NEW
PC PLUMBING CONTRACTOR
PD PATTERSON DENTAL
TYP TYPICAL
VFY VERIFY
VIF VERIFY IN FIELD
REVISIONS
REV
# SCOPE
DRAWN
BY DATE
MalloryFair Text Box
FOR REFERENCE ONLY
DENTAL FURNITURE & EQUIPMENT
EQUIPMENT NUMBER TAG
(NUMBERS ARE RANDOM)
DENTAL FURNITURE & EQUIPMENT
EXISTING RELOCATED
DENTAL FURNITURE & EQUIPMENT
FUTURE
PLAN LEGEND
EXISTING WALL
DEMO WALL
NEW WALL
WALL LEGEND
SOUND PROOFING IN WALL
LEAD LINED WALL S
T
E R
IL
IZ
A T
IO
N
(E) OP
(E) MED GAS
(E) MECH
(E) DENTIST OFFICE
(E) WORKSATION
(E) OP
(E) RR
(E) OPEN OPS
(E) PANO
/4
/2
5' - 8 1/2"
51A
22A
THESE DRAWINGS AND SPECIFICATIONS ARE THE
PROPERTY OF PATTERSON DENTAL SUPPLY AND THE
USE LIMITED TO A SPECIFIED PROJECT FOR THE
PERSON OR PERSONS NAMED HEREON FOR THE
CONSTRUCTION OF ONE BUILDING ONLY. ANY USE OR
REPRODUCTIONS OF THESE DRAWINGS ARE STRICTLY
PROHIBITED WITHOUT THE WRITTEN PERMISSION OF
PATTERSON DENTAL SUPPLY, INC.
WRITTEN DIMENSIONS SHALL TAKE PREFERENCE OVER
SCALE DIMENSIONS AND SHALL BE VERIFIED ON THE
JOB SITE.
ANY DISCREPANCIES OR CHANGES SHALL BE BROUGHT
TO THE ATTENTION OF PATTERSON DENTAL SUPPLY
PRIOR TO THE COMMENCEMENT OF ANY WORK.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CURRENT AMERICAN DISABILITIES ACT, (ADA)
ACCESSABILITY GUIDELINES.
THE CONTRACTOR SHALL ALSO BE RESPOSIBLE FOR
ALL REQUIRED BACKFLOW PREVENTERS.
THE CONTRACTOR SHALL COMPLY WITH ALL STATE,
CITY AND LOCAL CODES, PERTAINNG TO THE
CONSTRUCTION OF THIS PROJECT.
DRAWN BY
ISSUE DATE:
NOTE:
MODIFICATIONS TO THIS SPACE TO ALLOW THE PROPER
FIT & FUNCTION OF THE EQUIPMENT SUPPLIED BY
PATTERSON DENTAL SHALL BE THE RESPONSIBILITY OF
THE OWNER/TENANT/LANDLORD/CONTRACTOR IN
REGARDS TO CODE COMPLIANCE OF STRUCTURAL,
ELECTRICAL, MECHANICAL, AND PLUMBING ISSUES. THIS
INCLUDES, BUT IS NOT LIMITED TO, SUPPORT
STRUCTURE FOR EQUIPMENT AND CLEARANCES IN
REGARD TO SPRINKLER HEADS AND/OR ANY DEVICE OR
STRUCTURE WHICH MAY IMPEDE OR CONFLICT WITH THE
FUNCTION OF PATTERSON SUPPLIED EQUIPMENT.
PATTERSON DENTAL SHALL NOT BEAR ANY COST TO
CORRECT THESE ISSUES. PLEASE CONSULT PATTERSON
FOR ASSISTANCE IN EQUIPMENT SUPPORT STRUCTURE &
CLEARANCE QUESTIONS.
SHEET NO.
EQUIPMENT REP: EQUIPMENT REP #:
PROJECT #:
THE INFORMATION CONTAINED IN THESE DRAWINGS IS FOR
CONCEPT PURPOSES ONLY. THESE DRAWINGS ARE NOT
TO BE USED FOR CONSTRUCTION AND DO NOT TAKE THE
PLACE OF CONSTRUCTION PLANS AND SPECIFICATIONS.
THESE DRAWINGS ARE NOT TO SCALE; NOR HAVE FIELD
CONDITIONS BEEN VERIFIED. PATTERSON WILL NOT BE
HELD RESPONSIBLE FOR THE USE OR MISUSE OF THE
INFORMATION CONTAINED IN THESE DRAWINGS.
N O
T F
O R
C O
N S
T R
U C
T
IO
N N
O T
F O
R C
O N
S T
R U
C T
IO
N
OWNER:
LOCATION:
A u to d e s k D o c s /4
-C la c k a m a s C o u n ty
S u n n y s id e S te ri liz a ti o n
C e n te r-
/4
-C la c k a m a s C o u n ty S u n n y s id e S te ri liz a ti o n C e n te r-
.r v t
KWK
1031 MENDOTA HEIGHTS ROAD
MENDOTA HEIGHTS, MN
Clackamas County Sunnyside Sterilization Center
9775 SE. Sunnyside Road Suite #200 Clackamas, OR. 97015
12/10/2025
DA111DA111DA111DA111
Kevin Jamison (503) 505-2284
448-2753650
REVISIONS
REV
# SCOPE
DRAWN
BY DATE
1/4" = 1'-0"
LVL 1 FLOOR PLAN
EQUIPMENT SCHEDULE
QTY
EQUIPMENT INFO
ITEM # DESCRIPTION STATUS MANUFACTURER MODEL S
U
P P
L
IE
D B
Y
IN
S
T A
L L E
D B
Y
EQUIPMENT
REMARKS
1 51 STERILIZER NW MIDMARK M11-020 PD PD
1 51A STERILIZER ER MIDMARK M11-020 DR PD
STERILIZATION
1 22 STERILIZATION CABINET NW A-DEC 594 PD PD
1 22A STERILIZATION CABINET NW A-DEC 594 PD PD
1 52 ULTRASONIC CLEANER ER MIDMARK UC300 DR PD
1 54 STATIM ER SCICAN STATIM G4 DR PD
MalloryFair
51A
+64"+42"+26"
+64"+42"+26"
+18"
+18"
PROVIDE POWER OUTLETS
IN BASE OF CABINETS FOR
EQUIPMENT
DRYER CABINET
REQUIRES DEDICATED
POWER
PROVIDE POWER OUTLETS
IN BASE OF CABINETS FOR
EQUIPMENT
18/3 WIRE, CABLE RUN IN WALLS
OR ABOVE FINISHED CEILING
18/4 WIRE, WIRES RUN IN WALLS
OR ABOVE FINISHED CEILING
CAT5e OR BETTER CABLE, CABLE RUN
IN WALLS OR ABOVE FINISHED CEILING
MANUFACTURER CABLE, CABLE RUN IN
WALLS OR ABOVE FINISHED CEILING
ELECTRICAL CONDUIT UNDER
FLOOR, SIZE AS INDICATED ON PLAN
ELECTRICAL CONDUIT ABOVE
CEILING, SIZE AS INDICATED ON PLAN
ELECTRICAL LEGEND
LVL 1
0"
7 1/2"
PROVIDE POWER FOR
EQUIPMENT IN BASE OF
CABINETS
22A
LVL 1
0"
51A
4' - 6 3/4" 4 1/2" 5' - 7 3/4"
PROVIDE DEDICATED POWER
FOR DRYER IN BASE OF
CABINETS
LVL 1
0"
2' - 5 1/2"11"
PROVIDE POWER FOR
EQUIPMENT IN BASE OF
CABINETS
THESE DRAWINGS AND SPECIFICATIONS ARE THE
PROPERTY OF PATTERSON DENTAL SUPPLY AND THE
USE LIMITED TO A SPECIFIED PROJECT FOR THE
PERSON OR PERSONS NAMED HEREON FOR THE
CONSTRUCTION OF ONE BUILDING ONLY. ANY USE OR
REPRODUCTIONS OF THESE DRAWINGS ARE STRICTLY
PROHIBITED WITHOUT THE WRITTEN PERMISSION OF
PATTERSON DENTAL SUPPLY, INC.
WRITTEN DIMENSIONS SHALL TAKE PREFERENCE OVER
SCALE DIMENSIONS AND SHALL BE VERIFIED ON THE
JOB SITE.
ANY DISCREPANCIES OR CHANGES SHALL BE BROUGHT
TO THE ATTENTION OF PATTERSON DENTAL SUPPLY
PRIOR TO THE COMMENCEMENT OF ANY WORK.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CURRENT AMERICAN DISABILITIES ACT, (ADA)
ACCESSABILITY GUIDELINES.
THE CONTRACTOR SHALL ALSO BE RESPOSIBLE FOR
ALL REQUIRED BACKFLOW PREVENTERS.
THE CONTRACTOR SHALL COMPLY WITH ALL STATE,
CITY AND LOCAL CODES, PERTAINNG TO THE
CONSTRUCTION OF THIS PROJECT.
DRAWN BY
ISSUE DATE:
NOTE:
MODIFICATIONS TO THIS SPACE TO ALLOW THE PROPER
FIT & FUNCTION OF THE EQUIPMENT SUPPLIED BY
PATTERSON DENTAL SHALL BE THE RESPONSIBILITY OF
THE OWNER/TENANT/LANDLORD/CONTRACTOR IN
REGARDS TO CODE COMPLIANCE OF STRUCTURAL,
ELECTRICAL, MECHANICAL, AND PLUMBING ISSUES. THIS
INCLUDES, BUT IS NOT LIMITED TO, SUPPORT
STRUCTURE FOR EQUIPMENT AND CLEARANCES IN
REGARD TO SPRINKLER HEADS AND/OR ANY DEVICE OR
STRUCTURE WHICH MAY IMPEDE OR CONFLICT WITH THE
FUNCTION OF PATTERSON SUPPLIED EQUIPMENT.
PATTERSON DENTAL SHALL NOT BEAR ANY COST TO
CORRECT THESE ISSUES. PLEASE CONSULT PATTERSON
FOR ASSISTANCE IN EQUIPMENT SUPPORT STRUCTURE &
CLEARANCE QUESTIONS.
SHEET NO.
EQUIPMENT REP: EQUIPMENT REP #:
PROJECT #:
THE INFORMATION CONTAINED IN THESE DRAWINGS IS FOR
CONCEPT PURPOSES ONLY. THESE DRAWINGS ARE NOT
TO BE USED FOR CONSTRUCTION AND DO NOT TAKE THE
PLACE OF CONSTRUCTION PLANS AND SPECIFICATIONS.
THESE DRAWINGS ARE NOT TO SCALE; NOR HAVE FIELD
CONDITIONS BEEN VERIFIED. PATTERSON WILL NOT BE
HELD RESPONSIBLE FOR THE USE OR MISUSE OF THE
INFORMATION CONTAINED IN THESE DRAWINGS.
N O
T F
O R
C O
N S
T R
U C
T
IO
N N
O T
F O
R C
O N
S T
R U
C T
IO
N
OWNER:
LOCATION:
A u to d e s k D o c s /4
-C la c k a m a s C o u n ty
S u n n y s id e S te ri liz a ti o n
C e n te r-
/4
-C la c k a m a s C o u n ty S u n n y s id e S te ri liz a ti o n C e n te r-
.r v t
KWK
1031 MENDOTA HEIGHTS ROAD
MENDOTA HEIGHTS, MN
Clackamas County Sunnyside Sterilization Center
9775 SE. Sunnyside Road Suite #200 Clackamas, OR. 97015
12/10/2025
DE110DE110DE110DE110
Kevin Jamison (503) 505-2284
448-2753650
1/4" = 1'-0"
LVL 1 POWER & LOW VOLTAGE PLAN
ALL DEVICES ARE TO BE INSTALLED PER STATE AND LOCAL CODES.
GENERAL NOTES
EQUIPMENT POWER & LOW VOLTAGE SCHEDULE
QTY
EQUIPMENT INFO ELECTRICAL INFO LOW VOLTAGE INFO
ITEM # DESCRIPTION STATUS E
C
C O
N N
E C
T
IO
N B
Y
POWER CONNECTION TYPE
ELECTRICAL REMARKS L
V
C O
N N
E C
T
IO
N B
Y
E M
P T
Y C
O N
D U
IT
/4
E
M P
T Y
C O
N D
U
IT
E M
P T
Y C
O N
D U
IT
/3
W
IR
E
/4
W
IR
E
J B
O X
L V
C A
T e
O R
B E
T T
E R
M F
G C
A B
L E
M O
N
IT
O R
C A
B L E
LV REMARKSVOLTS AMPS S
IN
G L
E O
U T
L E
T
D U
P L E
X O
U T
L E
T
Q U
A D
O U
T L
E T
D
IR
E C
T W
IR
E
D E
D
IC
A T
E D
P O
W E
R
J B
O X
1 22 STERILIZATION CABINET NW EC 120v 20.0 ● EC TO LEAVE MIN 3' FLEXIBLE CONDUIT EC ● RUN LOW VOTLTAGE WIRES AND OR CABLES TO LOCATIONS
INDICATED ON PLANS
1 22A STERILIZATION CABINET NW EC 120v 20.0 ● EC TO LEAVE MIN 3' FLEXIBLE CONDUIT EC ● RUN LOW VOTLTAGE WIRES AND OR CABLES TO LOCATIONS
INDICATED ON PLANS
1 51 STERILIZER NW EC 120v 12.0 ● ● DEDICATED POWER EC
1 51A STERILIZER ER EC 120v 12.0 ● ● DEDICATED POWER EC
1 52 ULTRASONIC CLEANER ER EC 120v 2.0 ● EC
1 54 STATIM ER EC 120v 11.0 ● ● EC
+XX" - INDICATES HEIGHT FROM FINISHED FLOOR TO CENTER OF DEVICE UNLESS OTHERWISE
NOTED BELOW, IF ITEM NOT TAGGED HEIGHT IS 18" A.F.F.
ALL DEVICES SHALL BE INSTALLED PER STATE AND LOCAL CODE.
ALL LOCATIONS SHOULD BE VERIFIED WITH PATTERSON REP OR OWNER PRIOR TO PLACEMENT.
ELECTRICAL SYMBOLS
QTY. SYM. DESCRIPTION
PDSI_Vent And Exhaust Remarks
PDSI_Exhaust Comments
3 120v DUPLEX DEDICATED OUTLET WALL, IF TAG NOT
PRESENT HEIGHT IS 18" A.F.F. TO CENTER OF DEVICE
2 120v QUAD OUTLET WALL, IF TAG NOT PRESENT
HEIGHT IS 18" A.F.F. TO CENTER OF DEVICE
+XX" - INDICATES HEIGHT FROM FINISHED FLOOR TO CENTER OF DEVICE
UNLESS OTHERWISE NOTED BELOW, IF ITEM NOT TAGGED HEIGHT IS 18" A.F.F.
ALL DEVICES SHALL BE INSTALLED PER STATE AND LOCAL CODE. ALL
LOCATIONS SHOULD BE VERIFIED WITH PATTERSON REP OR OWNER PRIOR TO
PLACEMENT.
LOW VOLTAGE SYMBOLS
QTY. SYM. DESCRIPTION
3 DATA DEVICE WALL, IF TAG NOT PRESENT HEIGHT IS 18"
A.F.F.
REVISIONS
REV
# SCOPE
DRAWN
BY DATE
3/4" = 1'-0"
ELEVATION STERILIZATION WALL LEG 1
3/4" = 1'-0"
ELEVATION STERILIZATION WALL LEG 2
3/4" = 1'-0"
ELEVATION STERILIZATION WALL LEG 3
MalloryFair
DE1103
THESE DRAWINGS AND SPECIFICATIONS ARE THE
PROPERTY OF PATTERSON DENTAL SUPPLY AND THE
USE LIMITED TO A SPECIFIED PROJECT FOR THE
PERSON OR PERSONS NAMED HEREON FOR THE
CONSTRUCTION OF ONE BUILDING ONLY. ANY USE OR
REPRODUCTIONS OF THESE DRAWINGS ARE STRICTLY
PROHIBITED WITHOUT THE WRITTEN PERMISSION OF
PATTERSON DENTAL SUPPLY, INC.
WRITTEN DIMENSIONS SHALL TAKE PREFERENCE OVER
SCALE DIMENSIONS AND SHALL BE VERIFIED ON THE
JOB SITE.
ANY DISCREPANCIES OR CHANGES SHALL BE BROUGHT
TO THE ATTENTION OF PATTERSON DENTAL SUPPLY
PRIOR TO THE COMMENCEMENT OF ANY WORK.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CURRENT AMERICAN DISABILITIES ACT, (ADA)
ACCESSABILITY GUIDELINES.
THE CONTRACTOR SHALL ALSO BE RESPOSIBLE FOR
ALL REQUIRED BACKFLOW PREVENTERS.
THE CONTRACTOR SHALL COMPLY WITH ALL STATE,
CITY AND LOCAL CODES, PERTAINNG TO THE
CONSTRUCTION OF THIS PROJECT.
DRAWN BY
ISSUE DATE:
NOTE:
MODIFICATIONS TO THIS SPACE TO ALLOW THE PROPER
FIT & FUNCTION OF THE EQUIPMENT SUPPLIED BY
PATTERSON DENTAL SHALL BE THE RESPONSIBILITY OF
THE OWNER/TENANT/LANDLORD/CONTRACTOR IN
REGARDS TO CODE COMPLIANCE OF STRUCTURAL,
ELECTRICAL, MECHANICAL, AND PLUMBING ISSUES. THIS
INCLUDES, BUT IS NOT LIMITED TO, SUPPORT
STRUCTURE FOR EQUIPMENT AND CLEARANCES IN
REGARD TO SPRINKLER HEADS AND/OR ANY DEVICE OR
STRUCTURE WHICH MAY IMPEDE OR CONFLICT WITH THE
FUNCTION OF PATTERSON SUPPLIED EQUIPMENT.
PATTERSON DENTAL SHALL NOT BEAR ANY COST TO
CORRECT THESE ISSUES. PLEASE CONSULT PATTERSON
FOR ASSISTANCE IN EQUIPMENT SUPPORT STRUCTURE &
CLEARANCE QUESTIONS.
SHEET NO.
EQUIPMENT REP: EQUIPMENT REP #:
PROJECT #:
THE INFORMATION CONTAINED IN THESE DRAWINGS IS FOR
CONCEPT PURPOSES ONLY. THESE DRAWINGS ARE NOT
TO BE USED FOR CONSTRUCTION AND DO NOT TAKE THE
PLACE OF CONSTRUCTION PLANS AND SPECIFICATIONS.
THESE DRAWINGS ARE NOT TO SCALE; NOR HAVE FIELD
CONDITIONS BEEN VERIFIED. PATTERSON WILL NOT BE
HELD RESPONSIBLE FOR THE USE OR MISUSE OF THE
INFORMATION CONTAINED IN THESE DRAWINGS.
N O
T F
O R
C O
N S
T R
U C
T
IO
N N
O T
F O
R C
O N
S T
R U
C T
IO
N
OWNER:
LOCATION:
A u to d e s k D o c s /4
-C la c k a m a s C o u n ty
S u n n y s id e S te ri liz a ti o n
C e n te r-
/4
-C la c k a m a s C o u n ty S u n n y s id e S te ri liz a ti o n C e n te r-
.r v t
KWK
1031 MENDOTA HEIGHTS ROAD
MENDOTA HEIGHTS, MN
Clackamas County Sunnyside Sterilization Center
9775 SE. Sunnyside Road Suite #200 Clackamas, OR. 97015
12/10/2025
DP110DP110DP110DP110
Kevin Jamison (503) 505-2284
448-2753650
1/4" = 1'-0"
LVL 1 PLUMBING PLAN
ALL ITEMS TO BE INSTALLED PER STATE AND LOCAL CODES..
GENERAL NOTES:
EQUIPMENT PLUMBING-DENTAL COMPRESSED AIR-VAC SCHEDULE
Q
T Y
PLUMBING PLUMBING INFO VAC INFO DENTAL COMPRESSED AIR
ITEM # DESCRIPTION STATUS
SUPPLY SANITARY
PLUMBING REMARKS
RISERS
MAIN &
BRANCHES
VAC REMARKS 1
/2
C
O P
P E
R T
Y P
E L
O R
K
/8
C
O P
P E
R T
Y P
E M
COMPRESSED AIR REMARKSP
L U
M B
IN
G
C O
N N
E C
T
IO
N B
Y
/4
C
O L D
W A
T E
R F
L E
X T
U B
IN
G
/2
C
O L D
W A
T E
R C
O P
P E
R
/2
H
O T
W A
T E
R C
O P
P E
R
/4
C
O L D
W A
T E
R C
O P
P E
R
/4
H
O T
W A
T E
R C
O P
P E
R
C O
L D
W A
T E
R C
O P
P E
R
/4
C
O P
P E
R T
Y P
E M
-1
/2
P V
C W
A S
T E
S C
H E
D U
L E
D R
A
IN
D
IR
E C
T
D R
A
IN
I N
D
IR
E C
T
D R
A
IN
S T
A N
D P
IP
E
/2
P
V C
S C
H E
D U
L E
/8
P
V C
S C
H E
D U
L E
/4
P
V C
S C
H E
D U
L E
-1
/2
P V
C S
C H
E D
U L
E
P V
C S
C H
E D
U L E
P V
C S
C H
E D
U L E
1 22 STERILIZATION CABINET NW PC ● ● ● ● ●
1 22A STERILIZATION CABINET NW PC ● ● ● ● ●
+XX" - INDICATES HEIGHT FROM FINISHED FLOOR TO CENTER OF DEVICE
UNLESS OTHERWISE NOTED BELOW, IF ITEM NOT TAGGED HEIGHT IS 18" A.F.F.
ALL DEVICES SHALL BE INSTALLED PER STATE AND LOCAL CODES. ALL
LOCATIONS SHOULD BE VERIFIED WITH PATTERSON REP OR OWNER PRIOR
TO PLACEMENT.
PLUMBING SYMBOLS
QTY. SYM. DESCRIPTION
2 1/2" OD. TO 3/8" OD.SHUT OFF AIR CONNECTION WALL,
HEIGHT 3" A.F.F. TO CENTER IF TAG NOT PRESENT
2 DIRECT DRAIN WALL
2 SHUT OFF VALVE COLD WATER WALL
2 SHUT OFF VALVE HOT WATER WALL
REVISIONS
REV
# SCOPE
DRAWN
BY DATE
MalloryFair
| DA001 GENERAL NOTES |
| DA111 LVL 1 FLOOR PLAN |
| DE110 LVL 1 ELECTRICAL & LOW VOLTAGE |
| DP110 LVL 1 PLUMBING |