230327_240126_Elem_Drawings.pdf

PDF 1 MB Posted

Attached to
Boiler Replacement for FPE Elem & Benton Harbor High School
Solicitation number
RFP - BHA - 240000001444
Issued by
Berrien County, Bergland CDP, Michigan

About this file

This document pertains to a boiler replacement project for Fair Plain East Elementary School located in Benton Harbor, Michigan. The project involves the demolition and replacement of two existing boilers and associated mechanical work. The key details include:

The project is being issued for bidding by the Benton Harbor Area Schools. The scope of work includes removing and replacing two existing steam boilers, modifying existing mechanical systems, and making associated roofing and architectural modifications. The work is to be completed in accordance with the applicable codes and standards listed. Contractors are required to coordinate the work with other trades and field verify existing conditions prior to construction. The project has a single phase and the construction documents include architectural, mechanical, and electrical drawings.

Pricing for the project will be based on the contractor's bid. No set-asides or special requirements are noted. The project is funded by the school district and the construction duration is not explicitly stated. Contractors must comply with all applicable local, state, and federal requirements for the work.

View the file

Other files

File Type Posted
Addendum 2-4.pdf PDF
230327_240126_ProjectManual Part 1 of 2.pdf PDF
230327_240126_ProjectManual Part 2 of 2.pdf PDF
RFI and Response.pdf PDF
230327_240126_HS_Drawings.zip ZIP file
Addendum 1 Pt2.pdf PDF
Addendum 1 Pt3.pdf PDF
Addendum 1 Pt1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPLICABLE CODES AND STANDARDS

APPLICABLE CODES EDITION:

BUILDING CODES:

MICHIGAN BUILDING CODE (MBC) 2015

NFPA 101 - LIFE SAFETY CODE (NFPA) 2012

ICC A117.1 - ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES (ANSI) 2017

MICHIGAN ENERGY CODE 2015

FIRE CODE:

INTERNATIONAL FIRE CODE (IFC) 2015

PLUMBING CODE:

MICHIGAN PLUMBING CODE (MPC) 2018

MECHANICAL CODES:

MICHIGAN MECHANICAL CODE (MMC) 2015

MICHIGAN BOILER CODE RULES 2013

ELECTRICAL CODE:

NFPA 70 - NATIONAL ELECTRICAL CODE (NEC) 2017

OCCUPANCY CLASSIFICATION:

· E EDUCATION (UNCHANGED)

CODE SUMMARY

W E

RE

C

YC

LE

C

HE

C

KE

D B

Y:

D

ES

IG

NE

D B

Y:

AP

PR

O

VE

D B

Y:

BOILER REPLACEMENT FOR:

LOCATION MAP

NO SCALE

N

EW

S

VICINITY MAP

NO SCALE

N

EW

S

EXCEPT WHERE OTHERWISE INDICATED ON THE PLANS OR IN THE PROPOSAL SUPPLEMENTAL

SPECIFICATIONS CONTAINED THEREIN, ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE MICHIGAN DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR CONSTRUCTION, 2020 EDITION, AND THE CURRENT SUPPLEMENTAL SPECIFICATIONS.

(AVAILABLE AT WWW.MDOTJBOSS.STATE.MI.US/SPECPROV/SPECBOOKHOME.HTM#1468271)

IT IS UNDERSTOOD THAT THE CONTRACTOR SHALL PERFORM ALL WORK UNDER THIS CONTRACT IN

ACCORDANCE WITH ALL APPLICABLE PROVISIONS, POLICIES, RULES AND STANDARDS OF THE

MICHIGAN OCCUPATIONAL SAFETY AND HEALTH ACT (MDSHA), BEING ACT 154 OF THE PUBLIC ACTS

OF 2013 AND AS AMENDED.

THROUGHOUT THE DRAWING SET, THE GRAYSCALE LEGEND ON THE EDGE OF TITLE BLOCKS

SHOULD TRANSITION FROM WHITE THROUGH EIGHT SHADES OF GRAY TO SOLID BLACK. IF THE

GRAYSCALE SHADES ARE NOT DISTINCT, THE DRAWING(S) HAVE NOT PRINTED CORRECTLY.

LAKE ERIE

GRAND RAPIDS

TRAVERSE CITY

LAKE SUPERIOR

UPPER PENINSULA

MACKINAW CITY

LAKE HURON

ALPENA

PETOSKEY

GAYLORD

GRAYLING

LA

KE

M

IC

HI

G

AN

SAGINAW

ST.JOHNS FLINT

LANSING

JACKSON DETROITKALAMAZOO

ANN ARBOR

BL

AC

K W

HI

TE

TH

E

BA

R

BE

LO

W S

HO

W

S G

RA

YS

C

AL

E

FR

O M

W

HI

TE

T

O S

O

LID

TH

E

BA

R

BE

LO

W S

HO

W

S

PR

IM

AR

Y C

O

LO

RS

(866) 454-3923 | WWW.C2AE.COM

PROJ. #:

ISSUANCES

# DESCRIPTION DATE

COPYRIGHT C2AE.

NOT TO BE REPRODUCED OR DISTRIBUTED

WITHOUT PRIOR WRITTEN CONSENT.

ALL RIGHTS RESERVED.

PHASE

BENTON HARBOR

1/

/2

4:

:4

PM

Au to de sk

D oc s:

Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/

EL

EM

A.

rv t

C he ck er

D es ig ne r

Ap pr ov er

FAIR PLAIN EAST ELEMENTARY SCHOOL

1998 UNION AVE, BENTON HARBOR, MI 49022

ISSUE DATE: 26JAN2024

BENTON HARBOR AREA SCHOOLS

ISSUED FOR BIDDING

PROJECT NUMBER: 230327

FA

IR

P

LA

IN

E

AS

T

EL

EM

EN

TA

RY

S

C

HO

O L

U

NI

O N

AV

E, BE

NT

O N

HA

RB

O R, M I 4

G-001

230327

ISSUED FOR BIDDING

26JAN2024ISSUED FOR BIDDING

C O

V

ER

S H

EE

T

SHEET

NO. SHEET NAME

GENERAL

G-001 COVER SHEET

ARCHITECTURAL

A-001 ARCHITECTURAL LEGENDS, SYMBOLS, ABBREVIATIONS, AND

TYPICAL DETAILS

A-100 FLOOR PLANS - LOWER LEVEL

A-101 FLOOR PLANS - FIRST LEVEL

A-102 FLOOR PLANS - SECOND LEVEL ROOF

A-501 DETAILS

MECHANICAL

M-001 MECHANICAL LEGENDS

MD100 MECHANICAL DEMOLITION PLAN

M-100 MECHANICAL PLAN

M-103 MECHANICAL PLAN - ROOF

M-501 MECHANICAL DETAILS & SCHEDULES

ELECTRICAL

E-001 GENERAL NOTES AND LEGENDS

E-101 ELECTRICAL PLANS

E-501 DETAILS

TOTAL SHEETS: 14

MOUNTING HEIGHT

COORDINATION

ARCHITECTURAL,

MECHANICAL &

ELECTRICAL TRADES

SHALL COORDINATE

LOCATIONS OF WALL

MOUNTED ITEMS TO ALIGN

EITHER VERTICALLY OR

HORIZONTALLY.

FINISH FLOOR LINE

RECOMMENDED MOUNTING HEIGHTS (UNLESS OTHERWISE NOTED)

" 72

(M

IN

" SE

E

EL

EC

T

EL

EC

TR

IC

O R

PA

NE

L C

AB

IN

ET

PO

W

ER

P

AN

EL

EL

EC

TR

IC

TE

LE

PH

ON

E

OR

T

V

OU

TL

ET

SW

IT

CH

PU

SH

B

UT

TO

N

FI

RE

A

LA

RM

B

OX

TH

ER

MO

ST

AT

CA

RD

R

EA

DE

R

ME

CH

AN

IC

AL

PA

NE

LS

IN

FI

NI

SH

ED

S

PA

CE

S

SE

LE

CT

OR

S W

IT

CH

R S

SW

IT

CH

O

R W

AL

L

OU

TL

ET

A

BO

VE

CA

BI

NE

T

SS

FI

RE

E

XT

IN

GU

IS

HE

R

FI

RE

E

XT

IN

GU

IS

HE

R

CA

BI

NE

T, F

IR

E

HO

SE

OR

C

OM

BI

NA

TI

ON

CA

BI

NE

T

EX

TI

NG

UI

SH

ER

A

ND

/O R

CE

NT

ER

O

F

HO

SE

V

AL

VE

" T

O

TO

P

OF

CE

NT

ER

O

F H

AN

DL

E

" M

AX

TO

DRAWING REFERENCE SYMBOLS

ENLARGED PLAN OR DETAIL

WALL SECTION

BUILDING SECTION

EXTERIOR ELEVATIONS

INTERIOR ELEVATIONS

DEMO KEYNOTE##

REVISION CLOUD AND TAG

VIEW TITLE & REFERENCE

EXISTING COLUMN LINE

NEW COLUMN LINE

DETAIL

LEVEL OR ELEVATION

XX

DEMARCATION LINE

X-###

X## EQUIPMENT TAG

WALL TAG

###.# DOOR TAG

ROOM NAME

ROOM TAG

WINDOW TAG

X##

ARCHITECTURAL KEYNOTE

#' - #" CEILING SPOT ELEVATION

XX# FURNITURE TAG

FINISH TAG

SPECIALITY EQUIPMENT TAG

XX-#

XX-#

X##

PARTITION TYPE

FIRE RATING (EX. 1 = 1-HOUR)

PARTITION ASSMBLY

A101

A101

1 Ref

Re f

Re f

1 Ref

A101

1 SIM

A101

SIM

A101

SIM

A101

SIM

A101

1 SIM

CONCRETE FLOOR INFILL

(TO MEET REQUIREMENTS

OF SPECIFICATION

SECTIONS 017300 & 033000)

1/4" GALVANIZED STEEL PLATE

(PAINT)

EXISTING CONCRETE

FLOOR SLAB (TO REMAIN)

3/8" DIAMETER "SIMPSON

STRONG-TIE" TITAN-HD SCREW

ANCHORS AT 2'-0" O.C.

(TYPICAL)(TYP.)

2"

(TYP.)

4"

UP TO 6" DEEP

EM

BE

DM

EN

T 2 1

/2" (M

IN

UP

TO

6" D

EE

P

CONCRETE FLOOR INFILL

(TO MEET REQUIREMENTS

OF SPECIFICATION

SECTIONS 017300 & 033000)

1 1/2", 20 GAGE NON-

COMPOSITE GALVANIZED

METAL DECK

EXISTING CONCRETE

FLOOR SLAB (TO REMAIN)

3/8" "SIMPSON STRONG-TIE"

TITEN-HD SCREW ANCHORS

AT 2'-0" O.C. (TYPICAL)

4x4x1/4" STEEL ANGLE (2)

SIDES OF OPENING

EXISTING VERTICAL

EDGE OF CONCRETE

SLAB (OR CLEAN CUT)

EMBEDMENT

2 1/2" (MIN.)

2"

48" 48"

EXISTING WALL (TO BE REMOVED)

INFILL WITH TROWELABLE

LEVELING AND PATCHING

COMPOUND

GRIND EXISTING CONCRETE SLAB

OF EXISTING WALL

FIRE STOPPING

SEALANT

GYPSUM BOARD

PANELS

WIRES, PIPES,

AND / OR

CONDUITS

W E

RE

C

YC

LE

C

HE

C

KE

D B

Y:

D

ES

IG

NE

D B

Y:

AP

PR

O

VE

D B

Y:

BL

AC

K

W

HI

TE

TH

E

BA

R

BE

LO

W S

HO

W

S G

RA

YS

C

AL

E

FR

O M

W

HI

TE

T

O S

O

LID

TH

E

BA

R

BE

LO

W S

HO

W

S

PR

IM

AR

Y C

O

LO

RS

(866) 454-3923 | WWW.C2AE.COM

PROJ. #:

ISSUANCES

# DESCRIPTION DATE

COPYRIGHT C2AE.

NOT TO BE REPRODUCED OR DISTRIBUTED

WITHOUT PRIOR WRITTEN CONSENT.

ALL RIGHTS RESERVED.

PHASE

1/

/2

4:

:5

PM

Au to de sk

D oc s:

Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/

EL

EM

A.

rv t

C he ck er

D es ig ne r

Ap pr ov er

FA

IR

P

LA

IN

E

AS

T

EL

EM

EN

TA

RY

S

C

HO

O L

U

NI

O N

AV

E, BE

NT

O N

HA

RB

O R, M I 4

A-001

230327

ISSUED FOR BIDDING

26JAN2024ISSUED FOR BIDDING

A

RC

H

IT

EC

TU

RA

L L

EG

EN

D S, S Y

M

BO

LS

A

BB

RE

V

IA

TI

O N

S, A

N D

T Y

PI

C

A L D

ET

A

IL

S

ABBREVIATIONS

ABBREV. FULL TEXT

AB ANCHOR BOLT

ABI ADDITIVE BID ITEM

AC ACOUSTICAL

ACB ACOUSTICAL CEILING BAFFLE

ACP ACOUSTICAL CEILING PANEL

ACS ACOUSTICAL CEILING SPRAY

AD AREA DRAIN

ADA ADA

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

ALUM ALUMINUM

AP ACCESS DOORS

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASPH ASPHALT

AWP ACOUSTICAL WALL PANEL

B/ BOTTOM OF

BD BOARD

BF BARRIER FREE

BIT BITUMINOUS

BL BUILDING LINE

BLDG BUILDING

BLKHD BULKHEAD

BOTT BOTTOM

BP BASE PLATE

BR BUMP RAIL

BS BOTH SIDES

BUR BUILT UP ROOFING

CAB CABINET

CB CATCH BASIN

CEM CEMENT

CFMF COLD FORMED METAL FRAMING

CG CORNER GUARD

CH CHANNEL

CHKDPL CHECKERED PLATE

CJ CONTROL JOINT

CL CENTERLINE

CL TO CL CENTERLINE TO CENTERLINE

CLG CEILING

CLK CAULKING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CLEAN OUT

COL COLUMN

COMP COMPRESSIBLE

COMPO COMPOSITION

CONC CONCRETE

CONN CONNECT, CONNECTION

CONST CONSTRUCTION

CONST JT CONSTRUCTION JOINT

CONT CONTINUOUS

CONTR CONTRACTOR

CPT CARPET TILE

CS CONCRETE SEALER

CTR COUNTER

DEXS DOUBLE EXTRA STRONG (STEEL PIPE)

DF DRINKING FOUNTAIN

DIA DIAMETER

DIFF DIFFUSER

DN DOWN

DO DOOR OPENING

DR DOOR

DS DOWN SPOUT

DT DRAIN TILE

DTL DETAIL

DWG DRAWING

DWR DRAWER

E EAST

EA EACH

EIFS EXTERIOR INSULATION AND FINISH

SYSTEMS

EJ EXPANSION JOINT

EL ELEVATION

ELECT ELECTRICAL

ELEV ELEVATOR OR ELEVATION

ENCL ENCLOSURE

EP EPOXY PAINT

EPS EXTERIOR PAINT SYSTEM

EQ EQUAL

EQUIP EQUIPMENT

ES EXPOSED STRUCTURE

EW EACH WAY

EWC ELECTRICAL WATER COOLER

EX EXISTING

ABBREVIATIONS

ABBREV. FULL TEXT

EXGR EXISTING GRADE

EXP EXPANSION

EXS EXTRA STRONG (STEEL PIPE)

EXT EXTERIOR

FA FIRE ALARM

FAB FABRIC/UPHOLSTERY

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FG FROSTED GLASS

FHC FIRE HOSE CABINET

FIN FINISH

FL FLOOR

FLL FLOOR LINE

FLUOR FLUORESCENT

FOC FACE OF COLUMN

FOCONC FACE OF CONCRETE

FRC FIBER REINFORCED CONCRETE

FRP FIELD REINFORCED PANEL

FRPFG FIREPROOFING

FRTW FIRE RETARDANT TREATED WOOD

FS FULL SIZE

FTG FOOTING

FUR FURRING

FV FIELD VERIFY

G.B. GRAB BAR, GRADE BEAM

G.O. GRILL OPENING

GA GAUGE

GALV GALVANIZED

GCT GLAZED CERAMIC TILE

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GL GLASS

GND. GROUND

GR. GRADE

GRTG. GRATING

GSCFT GLAZED STRUCTURAL CLAY FACING TILE

GT GROUT

GYP. BD. GYPSUM BOARD

HC HOLLOW CORE

HCWD HOLLOW CORE WOOD

HDPB HIGH DENSITY PARTICLEBOARD

HM HOLLOW METAL

HORIZ HORIZONTAL

HP HIGH POINT

HR HOUR

HT HEIGHT

HWD HARDWARE

I.D. OR ID INSIDE DIAMETER

I.E. INVERT ELEVATION

IG INSULATING GLASS

IN INCHES

INCL INCLUDING, INCLUSIVE

INSUL INSULATION

INT INTERIOR

IPS INTERIOR PAINT SYSTEM

JAN JANITOR

JT JOINT

kW KILOWATTS kWh KILOWATT HOURS

LAD LADDER

LAM LAMINATED

LAV LAVATORY

LF LINEAR FEET

LGTH LENGTH

LH LEFT HAND

LKR LOCKER

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LO LOUVER OPENING

LP LIGHTING PANEL

LPG LIQUID PETROLEUM GAS

LPS LOW PRESSURE STEAM

LT LIGHT

LWT LEAVING WATER TEMPERATURE

MA MEDICAL AIR

MANUF MANUFACTURER

MAS MASONRY

MATL MATERIAL

MAX MAXIMUM

MBH THOUSAND BTU/HR

MC MEDICINE CABINET

MCA MINIMUM CIRCUIT AMPACITY

MCC MULTI-COLOR COATING

ABBREVIATIONS

ABBREV. FULL TEXT

MDO MEDIUM DENSITY OVERLAY

MECH MECHANICAL

MEMBWP MEMBRANE WATERPROOFING

MET METAL

MEZZ MEZZANINE

MFR MANUFACTURER

MFS MAXIMUM FUSE SIZE

MG MEDICAL GAS

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN. MINIMUM

MIRR MIRROR

MISC MISCELLANEOUS

MM MISCELLANEOUS METALS

MO MASONRY OPENING

MOCP MAXIMUM OVERCRRENT PROTECTION

MPC MICHIGAN PLUMBING CODE

MR MANUFACTURER'S RECOMMENDATIONS

MT MARBLE TILE

MTD MOUNTED

MUL. MULLION

N NORTH

N.S. NEAR SIDE

NF NO FINISH

NIC NOT IN CONTRACT

NO NUMBER

NPSH NET POSITIVE SUCTION HEAD

NSNS NON SHRINK NON STAIN GROUT

NTS NOT TO SCALE

NTS NOT TO SCALE

O.C. OR OC ON CENTER

OBSGL OBSCURE GLASS

OD OUTSIDE DIAMETER

OHDR SECTIONAL OVERHEAD DOOR

OPNG OPENING

OPP OPPOSITE

P PAINT

PART PARTITION

PB PARTICLE BOARD

PC PRECAST

PCS PIECES

PERM PERMANENT

PL PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLBG PLUMBING

PLY PLYWOOD

PT PRESSURE TREATED

PT PORCELAIN TILE

PTB PORCELAIN TILE BASE

QT QUARRY TILE

QTB QUARTZ TILE BASE

QTZ QUARTZ

R RISER

RA RETURN AIR

RB RUBBER BASE

RC ROOF CONDUCTOR

RD ROOF DRAIN

RD ROUND

RECVG RECEIVING

REF REFRIGERATOR

REINF REINFORCED

REQ'D REQUIRED

RF RESILIENT FLOORING

RH RIGHT HAND

RL ROOF LADDER

RM ROOM

RO ROUGH OPENING

RS ROOF SUMP

RSN RESIN

RWD REDWOOD

RWD RIGID WALL PROTECTION

S SOUTH

S SPANDREL GLASS

SA SUPPLY AIR

SAB SOUND ATTENUATION BLANKETS

SC SOLID CORE

SCH SCHEDULE

SCONC SEALED CONCRETE

SCWD SOLID CORE WOOD

SECT SECTION

SER.RECPT SERVICE RECEPTOR

SH SHELF

SHT SHEET

ABBREVIATIONS

ABBREV. FULL TEXT

SHWR SHOWER

SIM SIMILAR

SLR CONCRETE SEALER

SLS SOLID SURFACE

SLV SHORT LEG VERTICAL

SPEC SPECIFICATION

SQ SQUARE

SQFT SQUARE FOOT

SS STAINLESS STEEL

SSK SERVICE SINK

SSM SOLID SURFACING MATERIAL

ST SMOKE-TIGHT PER CODE TO RESIST THE

PASSAGE OF SMOKE

STD STANDARD

STDW STANDARD WEIGHT (STEEL PIPE)

STL STEEL

STN STAIN

STOR STORAGE

STRL STRUCTURAL

SUPP SUPPORT

SUSP SUSPENDED

SYM SUSPENSION SYMMETRICAL

T TREAD

T&G TONGUE AND GROOVE

T.O.C. OR T/C TOP OF CONCRETE

T.O.F. OR T/F TOP OF FOOTING

T.O.M. OR T/M TOP OF MASONRY

T.O.P. OR T/P TOP OF PAVEMENT

T.O.S. OR T/S TOP OF STEEL

T.O.W. OR T/W TOP OF WALL

T/ TOP OF

TB TRUSS BEARING

TG TEMPERED GLASS

THK THICK

THRESH THRESHOLD

TLT TOILET

TP TOILET PARTITION

TR TRANSITION TRIM

TYP TYPICAL

TYP TYPICAL

UNF UNFINISHED

UNO UNLESS NOTED OTHERWISE

UR URINAL

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

W WEST

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WC WALLCOVERING

WCO WALL CLEAN OUT

WCVR WALLCOVERING

WD WOOD

WP WATERPROOFING

WP WORKPOINT

WP WALL PROTECTION

WS WINDOW SHADE

WSCT WAINSCOT

WT WEIGHT

X-(MATERIAL) DENOTES EXISTING MATERIAL

REFRENCED

NOT TO SCALE

THRU WALL FIRE STOPPING - 3D

NOT TO SCALE

TYP DEMO FLOOR INFILL (OPENING 12" SQ. OR SMALER)

NOT TO SCALE

TYP DEMO FLOOR INFILL (OPENING 12" TO 5'-0")

NOT TO SCALE

TYP DEMO FLOOR LEVELING AT WALL REMOVAL

A-501

A-501

A-501

A-501

SIM

NEW EXTERIOR INSULATED

TRANSLUCENT FIBERGLASS PANELS

TO BE INSTALLED WITHIN THE

EXISTING WALL OPENING WHERE

EXISTING INFILL WALLS WERE

REMOVED. TRIM FINISHES ARE TO

MATCH EXISTING MATERIALS.

A28A28

A28A28

A28A28

A28A28

1. CONTRACTORS ARE TO COORDINATE WORK WITH ALL OTHER TRADES.

2. CONFLICTS BETWEEN NOTES, DETAILS, SPECIFICATIONS, ETC., SHALL BE

VERIFIED WITH THE ARCHITECT OR THE MOST STRINGENT PROVISIONS SHALL

GOVERN.

3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME

NATURE AS SHOWN FOR SIMILAR CONDITIONS. ANY UNCLEAR CONDITIONS

SHALL BE VERIFIED WITH THE ARCHITECT PRIOR TO CONSTRUCTION OF THAT

AREA.

4. DRAWINGS ARE NOT TO BE SCALED. ANY UNCLEAR DIMENSIONS, OR

DIMENSIONAL DISCREPANCIES, SHALL BE VERIFIED WITH ARCHITECT.

5. ALL EXISTING CONDITIONS AND ALL RELATED DIMENSIONS INDICATED IN THE

CONTRACT DOCUMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION,

ERECTION, AND/OR CONSTRUCTION. ANY CONDITIONS THAT DIFFER FROM THAT

INDICATED IN THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE

ARCHITECT FOR REVIEW PRIOR TO FABRICATION, ERECTION, AND/OR

CONSTRUCTION.

6. CONTRACTOR TO REVIEW ENTIRE SET OF CONSTRUCTION DOCUMENTS,

INCLUDING SPECIFICATION, AND SHALL COORDINATE WORK BETWEEN ALL

TRADES. IF CONFLICTS ARISE DUE TO COORDINATION OF TRADES,

CONTRACTOR IS TO VERIFY CONFLICT WITH ARCHITECT PRIOR TO

CONSTRUCTION / INSTALLATION OF CONFLICTING ITEMS.

7. PATCH ALL EXPOSED INTERIOR AND EXTERIOR WALLS WHERE ATTACHED OR

IMBEDDED ITEMS WERE REMOVED.

8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATION OF FLOOR,

WALL, AND/OR CEILING SUBSTRATES FOR NEW FINISHES.

9. MAINTAIN FIRE RATING AT ALL ASSEMBLIES WHERE OPENINGS PENETRATIONS,

EMBEDMENT, RECESSED EQUIPMENT, ACCESSORIES, ETC. DISRUPT THE

CONTINUITY OF THE RATING

10. REMOVE ADHESIVE AND/OR MORTAR LEFT FROM THE REMOVAL OF EXISTING

FLOOR COVERING AND PREP FLOOR W/CONCRETE (OR FLORSTONE) AS

NECESSARY TO ACCOMMODATE NEW FLOOR COVERINGS.

11. ALL DIMENSIONS ARE FROM FACE OF WALL SHEATHING, C.M.U., OR CONCRETE,

U.N.O.

12. PROVIDE ISOLATION MATERIAL BETWEEN DISSIMILAR MATERIALS THAT ARE IN

CONTACT WITH ONE ANOTHER.

13. PATCH & REPAIR ALL MAJOR & MINOR BLEMISHES AS REQ'D, DUE TO

DEMOLITION WORK. REPAIRS ARE TO MATCH ADJACENT MATERIAL & COLOR.

14. PROVIDE SOLID, CONTINUOUS, NON COMBUSTIBLE BLOCKING AT LOCATIONS

WHERE MILLWORK, PLUMBING FIXTURES, EQUIPMENT, ACCESSORIES, OR ETC.

ATTACH TO WALLS OR CEILINGS.

GENERAL NOTES:

D10

D9

D8

D6

DEMO PLAN LEGEND:

EXISTING WALL

OR PARTITION TO

REMAIN

EXISTING DOOR

TO REMAIN

EXISTING

BUILDING

COMPONENT &

STRUCTURE TO

REMAIN

EXISTING

WALL/PARTITION OR

EXISTING ITEMS TO

BE REMOVED

EXISTING DOOR &

FRAME TO BE

REMOVED

EXISTING ASSEMBLY

TO BE REMOVED

NOTE: ALL ITEMS SHOWN DARK AND DASHED ARE TO BE DEMOLISHED- U.N.O.

GENERAL DEMOLITION NOTES:

1. ALL EXISTING ITEMS TO BE RETAINED BY THE OWNER WILL BE REMOVED PRIOR

TO DEMOLITION. ANY ITEMS LEFT IN THE DEMOLITION AREA BECOME THE

PROPERTY OF THE DEMOLITION CONTRACTOR.

2. REFER TO ALL CONTRACT DOCUMENTS, INCLUDING SPECIFICATIONS, FOR

ADDITIONAL DEMOLITION NOTES AND INFORMATION.

3. SHORE AND BRACE ALL WORK REQUIRED TO REMAIN.

4. CONTRACTORS SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME

FAMILIAR WITH EXISTING CONDITIONS

5. CONTRACTORS ARE TO COORDINATE DEMOLITION WORK WITH OWNER PRIOR

TO START OF WORK.

6. U.N.O., PATCH AND PREPARE FLOOR W/ CONCRETE (OR FLORSTONE) TO FLUSH

WITH ADJACENT FLOOR SURFACE. FILL ANY SLOPING OR RECESSED AREAS TO

LEVEL WITH TYPICAL FINISH FLOOR ELEVATION TO ACCOMMODATE NEW

FLOOR COVERINGS.

7. INFILL EXISTING CHASE OPENINGS AND/OR PENETRATIONS IN FLOORS,

CEILINGS, OR ROOF DECK. FIRE-RATING OF NEW CONSTRUCTION IS TO MATCH

EXISTING.

W E

RE

C

YC

LE

C

HE

C

KE

D B

Y:

D

ES

IG

NE

D B

Y:

AP

PR

O

VE

D B

Y:

BL

AC

K

W

HI

TE

TH

E

BA

R

BE

LO

W S

HO

W

S G

RA

YS

C

AL

E

FR

O M

W

HI

TE

T

O S

O

LID

TH

E

BA

R

BE

LO

W S

HO

W

S

PR

IM

AR

Y C

O

LO

RS

(866) 454-3923 | WWW.C2AE.COM

PROJ. #:

ISSUANCES

# DESCRIPTION DATE

COPYRIGHT C2AE.

NOT TO BE REPRODUCED OR DISTRIBUTED

WITHOUT PRIOR WRITTEN CONSENT.

ALL RIGHTS RESERVED.

PHASE

1/

/2

1:4

8:

P M

Au to de sk

D oc s:

Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/

EL

EM

A.

rv t

C he ck er

D es ig ne r

Ap pr ov er

FA

IR

P

LA

IN

E

AS

T

EL

EM

EN

TA

RY

S

C

HO

O L

U

NI

O N

AV

E, BE

NT

O N

HA

RB

O R, M I 4

A-100

230327

ISSUED FOR BIDDING

26JAN2024ISSUED FOR BIDDING

FL

O

O R

PL

A

N S

LO

W

ER

LE

V

EL

1/4" = 1'-0"

DEMOLITION FLOOR PLAN - LOWER LEVEL2 1/4" = 1'-0"

FLOOR PLAN - LOWER LEVEL

ARCHITECTURAL KEYNOTES

KEY

VALUE KEYNOTE TEXT

A21 MECHANICAL ROOF PENETRATION REFER TO MECH DRAWINGS. REFER TO

DETAILS ON DRAWING A-001 AND A-501 FOR MORE INFORMATION.

A22 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW FINISHES. PATCH AND REPAIR

AS REQUIRED FOR NEW FIBERGLASS SANDWICH PANEL ASSEMBLY.

A23 INFILL EXISTING MASONRY WALL WITH SAME MATERIALS WHERE MECH ITEMS:

VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.

A24 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW MECHANICAL WALL VENT.

PATCH AND REPAIR AS REQUIRED FOR NEW WORK.

A25 INFILL, CLEAN, PREP, PREPARE, EXISTING ROOFING SO AS TO MATCH ADJACENT

SURFACES AND MEMBRANES. PATCH AND REPAIR AS REQUIRED FOR NEW WORK.

A27 NEW VENT LOCATION FOR EXISTING WATER HEATER IN MECH RM (AND

CURRENTLY VENTING THROUGH STACK) TO BE RE ROUTED THROUGH EXISTING

ROOF. REFER TO MECHANICAL DRAWINGS FOR MORE DETAILS.

A28 PATCH AND REPAIR EXISTING WALLS WITH SAME MATERIALS WHERE ITEMS,

VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.

DEMOLITION KEYNOTES

KEY

VALUE KEYNOTE TEXT

D6 REMOVE CONCRETE PADS FOR MECHANICAL EQUIPMENT COMPLETELY. SAW

CUT AS REQUIRED TO REMOVE CONCRETE. REMOVE CONCRETE SLAB TO

PREPARE FOR NEW REINFORCED CONCRETE SLAB INFILL AND PROPER

DRAINAGE AS REQUIRED. REMOVE MECHANICAL STEEL SUPPORTS, COLUMNS,

DUNNAGE THAT IS NO LONGER BEING UTILIZED. PATCH AND REPAIR ADJACENT

SURFACES AT AREAS OF REMOVAL TO MATCH EXISTING AND/OR AS REQUIRED

FOR PROPER INSTALLATION OF NEW INFILL REINFORCED CONCRETE SLAB

FINISHES.

D8 CAREFULLY REMOVE EXTERIOR WALL WITHIN EXISTING WALL OPENING.

PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION

FOR PROPER INSTALLATION OF NEW WORK.

D9 CAREFULLY REMOVE EXTERIOR LOUVER WITHIN EXISTING WALL OPENING.

PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION

FOR PROPER INSTALLATION OF NEW WORK.

D10 CAREFULLY REMOVE EXTERIOR WINDOW WITHIN EXISTING WALL OPENING.

PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION

FOR PROPER INSTALLATION OF NEW WORK.

D11 CAREFULLY REMOVE PORTION OF EXISTING ROOFING SYSTEM FOR NEW ROOF

PENETRATION FOR NEW VENTING OF EXISTING WATER HEATER AS REQUIRED.

PATCH EXISTING AREAS AND PREPARE NEW AREAS FOR PROPER INSTALLATION

OF NEW VENTING.

C

A-501

NEW EXTERIOR INSULATED

TRANSLUCENT FIBERGLASS PANELS

TO BE INSTALLED WITHIN THE

EXISTING WALL OPENING WHERE

EXISTING INFILL WALLS WERE

REMOVED. TRIM FINISHES ARE TO

MATCH EXISTING MATERIALS.

A-501

A-501

A-501

SIM

INFILL EXISTING MASONRY WALL

INFILL EXISTING MASONRY

WALL. INFILL SIZE 24" X 24"

A23A23

A23A23 A24A24

1. CONTRACTORS ARE TO COORDINATE WORK WITH ALL OTHER TRADES.

2. CONFLICTS BETWEEN NOTES, DETAILS, SPECIFICATIONS, ETC., SHALL BE

VERIFIED WITH THE ARCHITECT OR THE MOST STRINGENT PROVISIONS SHALL

GOVERN.

3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME

NATURE AS SHOWN FOR SIMILAR CONDITIONS. ANY UNCLEAR CONDITIONS

SHALL BE VERIFIED WITH THE ARCHITECT PRIOR TO CONSTRUCTION OF THAT

AREA.

4. DRAWINGS ARE NOT TO BE SCALED. ANY UNCLEAR DIMENSIONS, OR

DIMENSIONAL DISCREPANCIES, SHALL BE VERIFIED WITH ARCHITECT.

5. ALL EXISTING CONDITIONS AND ALL RELATED DIMENSIONS INDICATED IN THE

CONTRACT DOCUMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION,

ERECTION, AND/OR CONSTRUCTION. ANY CONDITIONS THAT DIFFER FROM THAT

INDICATED IN THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE

ARCHITECT FOR REVIEW PRIOR TO FABRICATION, ERECTION, AND/OR

CONSTRUCTION.

6. CONTRACTOR TO REVIEW ENTIRE SET OF CONSTRUCTION DOCUMENTS,

INCLUDING SPECIFICATION, AND SHALL COORDINATE WORK BETWEEN ALL

TRADES. IF CONFLICTS ARISE DUE TO COORDINATION OF TRADES,

CONTRACTOR IS TO VERIFY CONFLICT WITH ARCHITECT PRIOR TO

CONSTRUCTION / INSTALLATION OF CONFLICTING ITEMS.

7. PATCH ALL EXPOSED INTERIOR AND EXTERIOR WALLS WHERE ATTACHED OR

IMBEDDED ITEMS WERE REMOVED.

8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATION OF FLOOR,

WALL, AND/OR CEILING SUBSTRATES FOR NEW FINISHES.

9. MAINTAIN FIRE RATING AT ALL ASSEMBLIES WHERE OPENINGS PENETRATIONS,

EMBEDMENT, RECESSED EQUIPMENT, ACCESSORIES, ETC. DISRUPT THE

CONTINUITY OF THE RATING

10. REMOVE ADHESIVE AND/OR MORTAR LEFT FROM THE REMOVAL OF EXISTING

FLOOR COVERING AND PREP FLOOR W/CONCRETE (OR FLORSTONE) AS

NECESSARY TO ACCOMMODATE NEW FLOOR COVERINGS.

11. ALL DIMENSIONS ARE FROM FACE OF WALL SHEATHING, C.M.U., OR CONCRETE,

U.N.O.

12. PROVIDE ISOLATION MATERIAL BETWEEN DISSIMILAR MATERIALS THAT ARE IN

CONTACT WITH ONE ANOTHER.

13. PATCH & REPAIR ALL MAJOR & MINOR BLEMISHES AS REQ'D, DUE TO

DEMOLITION WORK. REPAIRS ARE TO MATCH ADJACENT MATERIAL & COLOR.

14. PROVIDE SOLID, CONTINUOUS, NON COMBUSTIBLE BLOCKING AT LOCATIONS

WHERE MILLWORK, PLUMBING FIXTURES, EQUIPMENT, ACCESSORIES, OR ETC.

ATTACH TO WALLS OR CEILINGS.

GENERAL NOTES:

D10

D9

D8

D11 EXISTING WATER

HEATER LOCATION,

REFER TO NOTE D11.

DEMO PLAN LEGEND:

EXISTING WALL

OR PARTITION TO

REMAIN

EXISTING DOOR

TO REMAIN

EXISTING

BUILDING

COMPONENT &

STRUCTURE TO

REMAIN

EXISTING

WALL/PARTITION OR

EXISTING ITEMS TO

BE REMOVED

EXISTING DOOR &

FRAME TO BE

REMOVED

EXISTING ASSEMBLY

TO BE REMOVED

NOTE: ALL ITEMS SHOWN DARK AND DASHED ARE TO BE DEMOLISHED- U.N.O.

GENERAL DEMOLITION NOTES:

1. ALL EXISTING ITEMS TO BE RETAINED BY THE OWNER WILL BE REMOVED PRIOR

TO DEMOLITION. ANY ITEMS LEFT IN THE DEMOLITION AREA BECOME THE

PROPERTY OF THE DEMOLITION CONTRACTOR.

2. REFER TO ALL CONTRACT DOCUMENTS, INCLUDING SPECIFICATIONS, FOR

ADDITIONAL DEMOLITION NOTES AND INFORMATION.

3. SHORE AND BRACE ALL WORK REQUIRED TO REMAIN.

4. CONTRACTORS SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME

FAMILIAR WITH EXISTING CONDITIONS

5. CONTRACTORS ARE TO COORDINATE DEMOLITION WORK WITH OWNER PRIOR

TO START OF WORK.

6. U.N.O., PATCH AND PREPARE FLOOR W/ CONCRETE (OR FLORSTONE) TO FLUSH

WITH ADJACENT FLOOR SURFACE. FILL ANY SLOPING OR RECESSED AREAS TO

LEVEL WITH TYPICAL FINISH FLOOR ELEVATION TO ACCOMMODATE NEW

FLOOR COVERINGS.

7. INFILL EXISTING CHASE OPENINGS AND/OR PENETRATIONS IN FLOORS,

CEILINGS, OR ROOF DECK. FIRE-RATING OF NEW CONSTRUCTION IS TO MATCH

EXISTING.

W E

RE

C

YC

LE

C

HE

C

KE

D B

Y:

D

ES

IG

NE

D B

Y:

AP

PR

O

VE

D B

Y:

BL

AC

K

W

HI

TE

TH

E

BA

R

BE

LO

W S

HO

W

S G

RA

YS

C

AL

E

FR

O M

W

HI

TE

T

O S

O

LID

TH

E

BA

R

BE

LO

W S

HO

W

S

PR

IM

AR

Y C

O

LO

RS

(866) 454-3923 | WWW.C2AE.COM

PROJ. #:

ISSUANCES

# DESCRIPTION DATE

COPYRIGHT C2AE.

NOT TO BE REPRODUCED OR DISTRIBUTED

WITHOUT PRIOR WRITTEN CONSENT.

ALL RIGHTS RESERVED.

PHASE

1/

/2

1:4

7:

P M

Au to de sk

D oc s:

Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/

EL

EM

A.

rv t

C he ck er

D es ig ne r

Ap pr ov er

FA

IR

P

LA

IN

E

AS

T

EL

EM

EN

TA

RY

S

C

HO

O L

U

NI

O N

AV

E, BE

NT

O N

HA

RB

O R, M I 4

A-101

230327

ISSUED FOR BIDDING

26JAN2024ISSUED FOR BIDDING

FL

O

O R

PL

A

N S

FI

RS

T

LE

V

EL

1/4" = 1'-0"

FLOOR PLAN - FIRST LEVEL

1/4" = 1'-0"

DEMOLITION FLOOR PLAN - FIRST LEVEL2

ARCHITECTURAL KEYNOTES

KEY

VALUE KEYNOTE TEXT

A21 MECHANICAL ROOF PENETRATION REFER TO MECH DRAWINGS. REFER TO

DETAILS ON DRAWING A-001 AND A-501 FOR MORE INFORMATION.

A22 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW FINISHES. PATCH AND REPAIR

AS REQUIRED FOR NEW FIBERGLASS SANDWICH PANEL ASSEMBLY.

A23 INFILL EXISTING MASONRY WALL WITH SAME MATERIALS WHERE MECH ITEMS:

VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.

A24 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW MECHANICAL WALL VENT.

PATCH AND REPAIR AS REQUIRED FOR NEW WORK.

A25 INFILL, CLEAN, PREP, PREPARE, EXISTING ROOFING SO AS TO MATCH ADJACENT

SURFACES AND MEMBRANES. PATCH AND REPAIR AS REQUIRED FOR NEW WORK.

A27 NEW VENT LOCATION FOR EXISTING WATER HEATER IN MECH RM (AND

CURRENTLY VENTING THROUGH STACK) TO BE RE ROUTED THROUGH EXISTING

ROOF. REFER TO MECHANICAL DRAWINGS FOR MORE DETAILS.

A28 PATCH AND REPAIR EXISTING WALLS WITH SAME MATERIALS WHERE ITEMS,

VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.

DEMOLITION KEYNOTES

KEY

VALUE KEYNOTE TEXT

D6 REMOVE CONCRETE PADS FOR MECHANICAL EQUIPMENT COMPLETELY. SAW

CUT AS REQUIRED TO REMOVE CONCRETE. REMOVE CONCRETE SLAB TO

PREPARE FOR NEW REINFORCED CONCRETE SLAB INFILL AND PROPER

DRAINAGE AS REQUIRED. REMOVE MECHANICAL STEEL SUPPORTS, COLUMNS,

DUNNAGE THAT IS NO LONGER BEING UTILIZED. PATCH AND REPAIR ADJACENT

SURFACES AT AREAS OF REMOVAL TO MATCH EXISTING AND/OR AS REQUIRED

FOR PROPER INSTALLATION OF NEW INFILL REINFORCED CONCRETE SLAB

FINISHES.

D8 CAREFULLY REMOVE EXTERIOR WALL WITHIN EXISTING WALL OPENING.

PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION

FOR PROPER INSTALLATION OF NEW WORK.

D9 CAREFULLY REMOVE EXTERIOR LOUVER WITHIN EXISTING WALL OPENING.

PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION

FOR PROPER INSTALLATION OF NEW WORK.

D10 CAREFULLY REMOVE EXTERIOR WINDOW WITHIN EXISTING WALL OPENING.

PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION

FOR PROPER INSTALLATION OF NEW WORK.

D11 CAREFULLY REMOVE PORTION OF EXISTING ROOFING SYSTEM FOR NEW ROOF

PENETRATION FOR NEW VENTING OF EXISTING WATER HEATER AS REQUIRED.

PATCH EXISTING AREAS AND PREPARE NEW AREAS FOR PROPER INSTALLATION

OF NEW VENTING.

A-501 A21A21

A21A21

A21A21

A21A21

A-102 2 Sim

A22

A22

A27A27

A25A25

A25A25

A25A25

A25A25

A25A25

1. CONTRACTORS ARE TO COORDINATE WORK WITH ALL OTHER TRADES.

2. CONFLICTS BETWEEN NOTES, DETAILS, SPECIFICATIONS, ETC., SHALL BE

VERIFIED WITH THE ARCHITECT OR THE MOST STRINGENT PROVISIONS SHALL

GOVERN.

3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME

NATURE AS SHOWN FOR SIMILAR CONDITIONS. ANY UNCLEAR CONDITIONS

SHALL BE VERIFIED WITH THE ARCHITECT PRIOR TO CONSTRUCTION OF THAT

AREA.

4. DRAWINGS ARE NOT TO BE SCALED. ANY UNCLEAR DIMENSIONS, OR

DIMENSIONAL DISCREPANCIES, SHALL BE VERIFIED WITH ARCHITECT.

5. ALL EXISTING CONDITIONS AND ALL RELATED DIMENSIONS INDICATED IN THE

CONTRACT DOCUMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION,

ERECTION, AND/OR CONSTRUCTION. ANY CONDITIONS THAT DIFFER FROM THAT

INDICATED IN THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE

ARCHITECT FOR REVIEW PRIOR TO FABRICATION, ERECTION, AND/OR

CONSTRUCTION.

6. CONTRACTOR TO REVIEW ENTIRE SET OF CONSTRUCTION DOCUMENTS,

INCLUDING SPECIFICATION, AND SHALL COORDINATE WORK BETWEEN ALL

TRADES. IF CONFLICTS ARISE DUE TO COORDINATION OF TRADES,

CONTRACTOR IS TO VERIFY CONFLICT WITH ARCHITECT PRIOR TO

CONSTRUCTION / INSTALLATION OF CONFLICTING ITEMS.

7. PATCH ALL EXPOSED INTERIOR AND EXTERIOR WALLS WHERE ATTACHED OR

IMBEDDED ITEMS WERE REMOVED.

8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATION OF FLOOR,

WALL, AND/OR CEILING SUBSTRATES FOR NEW FINISHES.

9. MAINTAIN FIRE RATING AT ALL ASSEMBLIES WHERE OPENINGS PENETRATIONS,

EMBEDMENT, RECESSED EQUIPMENT, ACCESSORIES, ETC. DISRUPT THE

CONTINUITY OF THE RATING

10. REMOVE ADHESIVE AND/OR MORTAR LEFT FROM THE REMOVAL OF EXISTING

FLOOR COVERING AND PREP FLOOR W/CONCRETE (OR FLORSTONE) AS

NECESSARY TO ACCOMMODATE NEW FLOOR COVERINGS.

11. ALL DIMENSIONS ARE FROM FACE OF WALL SHEATHING, C.M.U., OR CONCRETE,

U.N.O.

12. PROVIDE ISOLATION MATERIAL BETWEEN DISSIMILAR MATERIALS THAT ARE IN

CONTACT WITH ONE ANOTHER.

13. PATCH & REPAIR ALL MAJOR & MINOR BLEMISHES AS REQ'D, DUE TO

DEMOLITION WORK. REPAIRS ARE TO MATCH ADJACENT MATERIAL & COLOR.

14. PROVIDE SOLID, CONTINUOUS, NON COMBUSTIBLE BLOCKING AT LOCATIONS

WHERE MILLWORK, PLUMBING FIXTURES, EQUIPMENT, ACCESSORIES, OR ETC.

ATTACH TO WALLS OR CEILINGS.

GENERAL NOTES:

A-501

1"

1" / 12"1" / 12" 1"

NEW ROOF ON EXISTING

CHIMNEY STACK

ROOF LEGEND

DENOTES REINF. MEMBRANE WALKWAY MATS -

SEE SPECIFICATIONS.

TAPERED INSULATION - ARROW INDICATES

DIRECTION OF SLOPE.

DENOTES MECHANICAL UNIT - SEE HVAC PLANS

DENOTES AREA OF 1-HOUR FIRE RESISTIVE ROOF

ASSEMBLY

DENOTES EXHAUST FAN OR RELIEF VENT, SEE

MECHANICAL PLANS FOR SPECIFICATIONS.

EFFECTIVE DIRECTION OF ROOF SLOPE DUE TO

STRUCTURE

RD = ROOF DRAIN

OD = OVERFLOW DRAIN

CONDENSING UNIT

EXISTING ROOF

1. ALL NEW ROOF WORK THAT INTERACTS WITH EXISTING ROOFING TO REMAIN, IS

TO BE EXECUTED AS REQUIRED TO MAINTAIN EXISTING ROOFING WARRANTIES.

2. ALL NEW VENT PIPES ARE TO EXTEND A MINIMUM 12" ABOVE FINISHED ROOF.

3. AT AREAS OF RE-ROOF, CONTACTOR TO EXTEND EXISTING VENT PIPES TO A

MINIMUM OF 12" ABOVE FINISHED ROOF.

4. ALL NEW EQUIPMENT CURBS ARE TO EXTEND A MINIMUM OF 12" ABOVE

FINISHED ROOF.

5. AT AREAS OF RE-ROOF, CONTACTOR TO EXTEND ALL EXISTING EQUIPMENT

CURBS TO REMAIN TO A MINIMUM 12" ABOVE FINISHED ROOF.

6. CONTRACTOR TO INSTALL ROOF WALKWAY PADS AT PERIMETER OF ALL

SERVICABLE EQUIPMENT, AND ALONG WALKING PATH BETWEEN ALL ROOF

HATCHES, LADDERS, AND EQUIPMENT.

ROOF GENERAL NOTES:

W E

RE

C

YC

LE

C

HE

C

KE

D B

Y:

D

ES

IG

NE

D B

Y:

AP

PR

O

VE

D B

Y:

BL

AC

K

W

HI

TE

TH

E

BA

R

BE

LO

W S

HO

W

S G

RA

YS

C

AL

E

FR

O M

W

HI

TE

T

O S

O

LID

TH

E

BA

R

BE

LO

W S

HO

W

S

PR

IM

AR

Y C

O

LO

RS

(866) 454-3923 | WWW.C2AE.COM

PROJ. #:

ISSUANCES

# DESCRIPTION DATE

COPYRIGHT C2AE.

NOT TO BE REPRODUCED OR DISTRIBUTED

WITHOUT PRIOR WRITTEN CONSENT.

ALL RIGHTS RESERVED.

PHASE

1/

/2

1:4

6:

P M

Au to de sk

D oc s:

Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/

EL

EM

A.

rv t

C he ck er

D es ig ne r

Ap pr ov er

FA

IR

P

LA

IN

E

AS

T

EL

EM

EN

TA

RY

S

C

HO

O L

U

NI

O N

AV

E, BE

NT

O N

HA

RB

O R, M I 4

A-102

230327

ISSUED FOR BIDDING

26JAN2024ISSUED FOR BIDDING

FL

O

O R

PL

A

N S

SE

C O

N D

LE

V

EL

R

O O

F

1/4" = 1'-0"

FLOOR PLAN - ROOF LEVEL

ARCHITECTURAL KEYNOTES

KEY

VALUE KEYNOTE TEXT

A21 MECHANICAL ROOF PENETRATION REFER TO MECH DRAWINGS. REFER TO

DETAILS ON DRAWING A-001 AND A-501 FOR MORE INFORMATION.

A22 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW FINISHES. PATCH AND REPAIR

AS REQUIRED FOR NEW FIBERGLASS SANDWICH PANEL ASSEMBLY.

A23 INFILL EXISTING MASONRY WALL WITH SAME MATERIALS WHERE MECH ITEMS:

VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.

A24 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW MECHANICAL WALL VENT.

PATCH AND REPAIR AS REQUIRED FOR NEW WORK.

A25 INFILL, CLEAN, PREP, PREPARE, EXISTING ROOFING SO AS TO MATCH ADJACENT

SURFACES AND MEMBRANES. PATCH AND REPAIR AS REQUIRED FOR NEW WORK.

A27 NEW VENT LOCATION FOR EXISTING WATER HEATER IN MECH RM (AND

CURRENTLY VENTING THROUGH STACK) TO BE RE ROUTED THROUGH EXISTING

ROOF. REFER TO MECHANICAL DRAWINGS FOR MORE DETAILS.

A28 PATCH AND REPAIR EXISTING WALLS WITH SAME MATERIALS WHERE ITEMS,

VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.

1/4" = 1'-0"A-102

PLAN DETAIL - T.O. ROOF STACK NEW CAP2

SEALANT

EXTERIOR INTERIOR

FLASHING WITH END DAM

INDICATIVE PROFILE OF EXISTING

MASONRY WALL - VIF

ADHESIVE MEMBRANE AIR & MOISTURE BARRIER

FLASHING WRAP INTO ROUGH OPENINGS UNDER

METAL FLASHING - TYP

FLASHING

TRANSLUCENT WALL PANEL

1 9/16" PANEL

VIF

ADHESIVE MEMBRANE AIR & MOISTURE BARRIER

FLASHING WRAP INTO ROUGH OPENINGS UNDER

METAL FLASHING - TYP

EXISTING MASONRY WALL - VIF

NOTE: TRANSLUCENT WALL PANEL TO BE POSITIONED

TOWARDS THE EXTERIOR FACE OF EXISTING WALL

1 5/8"

CURING BUTYL

FLEXIBLE FLASHING, WRAP PERIMETER OF OPENING

INDICATIVE PROFILE OF EXISTING

MASONRY WALL - VIF

TRANSLUCENT WALL PANEL

EXTERIOR

INTERIOR

SEALANT

1 9 /16

" P

AN

EL

EXISTING MASONRY WALL

METAL FLASHING SILL WITH END DAM

5/

8"

FLASHING END DAM BELOW

SPLICING CEMENT

ROOF DECK

PIPE PENETRATION

SEALANT

STAINLESS STEEL

HOSE CLAMP

PIPE BOOT FLASHING

INSULATION SECURELY

FASTENED

8" M

IN

RISER CLAMP NOTE:

SEE MECHANICAL DRAWINGS

FOR VENT LOCATIONS, SIZES, AND

FOR ADDITIONAL REQUIREMENTS

ROOF DECK

(SEE ROOF PLAN)

RIGID INSULATION

COVER BOARD (IF REQUIRED TO MATCH

EXISTING ROOFING SYSTEM)

WATERTIGHT UMBRELLA

GALVANIZED OR PRE-FAB.

ALUMINUM

MEMBRANE

FLASHING

ROOFING SYSTEM

FLUE

PIPE

RAIN CAP

CLAMP

CAP MEMBRANE FLASHING

FRTW BLOCKING TO MATCH

INSULATION THICKNESS AND

ANCHORED TO DECK

MEMBRANE ROOFING SYSTEM

PIPE STRAP

1" AIR SPACE AT BOTH SIDES

CONTINUOUS ELASTOMERIC SEALANT

CONTINUOUS FLASHING CEMENT

" M

IN

NOTE:

SEE MECHANICAL DRAWINGS

FOR VENT LOCATIONS, SIZES, AND

FOR ADDITIONAL REQUIREMENTS

METAL FLASHING AT EDGE OF FRTW BLOCKING

ROOF DECK

(SEE ROOF PLAN)

CAP MEMBRANE

FLASHING

FLASHING CEMENT

MEMBRANE ROOFING

SYSTEM

VENT

PIPE

" M

IN

TREATED WOOD

BLOCKING TO MATCH

INSULATION

THICKNESS AND

ANCHORED TO DECK

RIGID INSULATION

COVER BOARD

MEMBRANE ROOFING

SYSTEM

WATERTIGHT UMBRELLA

GALVANIZED OR ALUMINUM

CLAMP

CONTINUOUS SEALANT

RISER CLAMP

NOTE:

SEE MECHANICAL DRAWINGS

FOR VENT LOCATIONS, SIZES, AND

FOR ADDITIONAL REQUIREMENTS

04.0 130' - 0"

04.0 130' - 0"

04.0 130' - 0"

04.0 130' - 0"

1" / 12" -TYP

2x6 FRTW BLOCKING

3/4" FRTW SHEATHING

ALUMINUM DRIP EDGE WITH SEALANT

CFMF

SIMPSON STRONG TIE, MTSM16, STAINLESS

STEEL (316) AT 48" MAX

EXISTING MASONRY WALL - VIF

MASONRY FASTENERS. 2 AT EACH OF 4

SIDES MIN, AT 48" MAX

(VIF DATUM)

DRIP EDGE

1" / 12" -TYP

VAPOR RETARDER

3/4" FRTW SHEATHING

ADHERED SEALANT TAPE / CAPILLARY BREAK AT CFMF TO

WOOD CONNECTION - TYP

ROOFING MEMBRANE OVER TAPERED RIGID INSULATION

ALUMINUM FASCIA WITH DRIP EDGE TO BE TUCKED

UNDER THE ALUMINUM ROOF DRIP EDGE

ADHERED SEALANT TAPE / CAPILLARY BREAK AT CFMF TO

WOOD CONNECTION - TYP

EXISTING MASONRY WALL. PREP, PATCH, REPAIR,

REPOINT AS REQUIRED FOR NEW WORK - TYP

01.0 100' - 0"

02.0 108' - 4"

03.0 120' - 0"

04.0 130' - 0"

01.0 100' - 0"

02.0 108' - 4"

03.0 120' - 0"

01.0 100' - 0"

02.0 110' - 0"

03.0 120' - 0"

04.0 130' - 0"

01.0 100' - 0"

02.0 110' - 0"

03.0 120' - 0"

04.0 130' - 0"

01.0 100' - 0"

02.0 110' - 0"

03.0 120' - 0"

04.0 130' - 0"

A-501

VIF

10' - 4"

VI

F

5'

- 8

NEW EXTERIOR INSULATED

TRANSLUCENT FIBERGLASS PANELS

TO BE INSTALLED WITHIN THE

EXISTING WALL OPENING. TRIM

FINISHES ARE TO MATCH EXISTING

MATERIALS.

A-501

A27A27

A21A21 A21A21 A21A21 A21A21

W E

RE

C

YC

LE

C

HE

C

KE

D B

Y:

D

ES

IG

NE

D B

Y:

AP

PR

O

VE

D B

Y:

BL

AC

K

W

HI

TE

TH

E

BA

R

BE

LO

W S

HO

W

S G

RA

YS

C

AL

E

FR

O M

W

HI

TE

T

O S

O

LID

TH

E

BA

R

BE

LO

W S

HO

W

S

PR

IM

AR

Y C

O

LO

RS

(866) 454-3923 | WWW.C2AE.COM

PROJ. #:

ISSUANCES

# DESCRIPTION DATE

COPYRIGHT C2AE.

NOT TO BE REPRODUCED OR DISTRIBUTED

WITHOUT PRIOR WRITTEN CONSENT.

ALL RIGHTS RESERVED.

PHASE

1/

/2

4:

:5

PM

Au to de sk

D oc s:

Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/

EL

EM

A.

rv t

C he ck er

D es ig ne r

Ap pr ov er

FA

IR

P

LA

IN

E

AS

T

EL

EM

EN

TA

RY

S

C

HO

O L

U

NI

O N

AV

E, BE

NT

O N

HA

RB

O R, M I 4

A-501

230327

ISSUED FOR BIDDING

26JAN2024ISSUED FOR BIDDING

D

ET

A

IL

S

1 1/2" = 1'-0"

EXISTING EXTERIOR WALL - SECTION DETAIL - TRANSLUCENT WALL PANEL1

1 1/2" = 1'-0"

EXISTING EXTERIOR WALL - PLAN DETAIL - TRANSLUCENT WALL PANEL JAMB2

1 1/2" = 1'-0"

ROOF PENETRATION AT TAPERED CONE4

1 1/2" = 1'-0"

ROOF PENETRATION AT METAL FLUE5

1 1/2" = 1'-0"

ROOF PENETRATION AT METAL FLASHING33/4" = 1'-0"

SECTION DETAIL - T.O. ROOF STACK NEW CAP6

1/8" = 1'-0"

EXTERIOR ELEVATION - SOUTH7

ARCHITECTURAL KEYNOTES

KEY

VALUE KEYNOTE TEXT

A21 MECHANICAL ROOF PENETRATION REFER TO MECH DRAWINGS. REFER TO

DETAILS ON DRAWING A-001 AND A-501 FOR MORE INFORMATION.

A22 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW FINISHES. PATCH AND REPAIR

AS REQUIRED FOR NEW FIBERGLASS SANDWICH PANEL ASSEMBLY.

A23 INFILL EXISTING MASONRY WALL WITH SAME MATERIALS WHERE MECH ITEMS:

VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.

A24 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW MECHANICAL WALL VENT.

PATCH AND REPAIR AS REQUIRED FOR NEW WORK.

A25 INFILL, CLEAN, PREP, PREPARE, EXISTING ROOFING SO AS TO MATCH ADJACENT

SURFACES AND MEMBRANES. PATCH AND REPAIR AS REQUIRED FOR NEW WORK.

A27 NEW VENT LOCATION FOR EXISTING WATER HEATER IN MECH RM (AND

CURRENTLY VENTING THROUGH STACK) TO BE RE ROUTED THROUGH EXISTING

ROOF. REFER TO MECHANICAL DRAWINGS FOR MORE DETAILS.

A28 PATCH AND REPAIR EXISTING WALLS WITH SAME MATERIALS WHERE ITEMS,

VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.

HIGH PRESSURE STEAMHPS

DESCRIPTIONSYMBOL

MECHANICAL ABBREVIATIONS & SYMBOLS LEGEND

MEDIUM PRESSURE STEAMMPS

LOW PRESSURE STEAMLPS

HIGH PRESSURE STEAM CONDENSATEHPC

MEDIUM PRESSURE STEAM CONDENSATEMPC

LOW PRESSURE STEAM CONDENSATELPC

BOILER BLOWDOWNBBD

PUMPED CONDENSATEPC

VACUUM PUMP DISCHARGEVPD

MAKE-UP WATERMU

ATMOSPHERIC VENTATV

FUEL OILFO

HEATING HOT WATER SUPPLYHHWS

HEATING HOT WATER RETURNHHWR

COMPRESSED AIRCA

VACUUM (AIR)VAC

EXISTINGEX-

DEMOLITION PIPING

LIQUID LINE (REFRIGERANT)LL

SUCTION LINE (REFRIGERANT)SL

BRINE SUPPLYBS

BRINE RETURNBR

CONDENSER WATER SUPPLYCWS

CONDENSER WATER RETURNCWR

CHILLED WATER SUPPLYCHWS

CHILLED WATER RETURNCHWR

FILL LINEFILL

HUMIDIFICATION LINEH

DRAIND

DISCHARGE LINE (REFRIGERANT)DL

HEAT PUMP WATER SUPPLYHPWS

HEAT PUMP WATER RETURNHPWR

PIPING

COILS

COOLING COIL

HEATING COIL

ELECTRIC COIL

HUMIDIFIER

VALVES

AIR LINE

BALL VALVE

BUTTERFLY VALVE

DIAPHRAGM VALVE

GATE VALVE

GATE VALVE (ANGLE)

PLUG VALVE

THREE WAY VALVE

VALVE ACTUATORS

LEVER

NON-RISING STEM

OUTSIDE STEM & YOKE

GEARG

PNUEMATIC MOTOR ACTUATORM

ELECTRIC MOTOR ACTUATORM

ELECTRIC SOLENOID ACTUATOR

CHECK VALVE

PRESSURE REGULATING VALVE

RELIEF VALVE

PIPE FITTINGS

TRANSITION

CAP

ELBOW

ELBOW UP

ELBOW DOWN

TEE

TEE UP

TEE DOWN

UNION

DESCRIPTIONSYMBOL

EXPANSION LOOP

FLEXIBLE CONNECTOR

ORIFICE FLOWMETER

VENTURI FLOWMETER

FLOW SWITCHFS

HANGER RODH

PRESSURE SWITCHPS

PRESSURE GAGE

PUMP

STRAINER

THERMOMETER

EQUIPMENT

CENTRIFUGAL FAN

PROPELLER FAN

INTAKE ROOF VENTILATOR

EXHAUST ROOF VENTILATOR

LOUVERED ROOF VENTILATOR

VANEAXIAL FAN

VARIABLE AIR VOLUME BOX

DUCTWORK

RECTANGULAR DUCTWORK12"x12" SA

ROUND DUCTWORK12"Ø SA

MITERED RECTANGULAR ELBOW

MITERED RECTANGULAR ELBOW WITH TURNING VANES

RADIUS RECTANGULAR OR ROUND ELBOW

RECTANGULAR DUCTWORK UP

RECTANGULAR DUCTWORK DOWN

ROUND DUCTWORK UP

ROUND DUCTWORK DOWN

SUPPLY AIR DUCTWORKSA

RETURN AIR DUCTWORKRA

EXHAUST AIR DUCTWORKEA

OUTSIDE AIR DUCTWORKOA

FLEXIBLE DUCTWORK CONNECTOR

LINED DUCTWORK

INSULATED DUCTWORK

FLEXIBLE DUCTWORK

TRANSITION

DAMPERS

BALANCING DAMPER

FIRE DAMPER

SMOKE DAMPER

DRG

SUPPLY AIR CEILING DIFFUSER

RETURN AIR CEILING GRILLE

EXHAUST AIR CEILING GRILLE

SIDEWALL SUPPLY GRILLE

SIDEWALL RETURN / EXHAUST GRILLE

LINEAR DIFFUSER

CONTROLS

THERMOSTATT

PRESSURE SENSORP

OXYGEN SENSORO2

CARBON DIOXIDE SENSORCO2

CARBON MONOXIDE SENSORCO

PIPE SPECIALTIES

AUTOMATIC AIR VENT

MANUAL AIR VENT

PIPE GUIDE

PIPE ANCHOR

MAIN PIPE ANCHOR

BALL JOINT

EXPANSION JOINT

AIR CHANGES PER HOURACH

DESCRIPTIONABBREVIATION

ALTERNATING CURRENTAC

ASBESTOS CONTAINING MATERIALSACM

AIR CONDITIONING UNITACU

ASSOCIATION OF ENERGY ENGINEERSAEE

ADJUSTABLE FREQUENCY DRIVEAFD

ABOVE FINISHED FLOORAFF

ADJUSTABLEADJ

ANNUAL FUEL EFFICIENCY RATIOAFUE

AIR HANDLING UNITAHU

ANALOG INPUTAI

ANALOG OUTPUTAO

AMERICAN SOCIETY OF HEATING REFRIGERATION AND AIR

CONDITIONING ENGINEERSASHRAE

AMERICAN SOCIETY OF MECHANICAL ENGINEERSASME

AVERAGE WATER TEMPERATUREAWT

BOILERB

BUILDING AUTOMATION SYSTEMBAS

BUILDING COMMISSIONING ASSOCIATIONBCA

BLOWER COIL UNITBCU

BRAKE HORSEPOWERBHP

BINARY INPUTBI

BINARY OUTPUTBO

BACK DRAFT DAMPERBDD

BILL OF MATERIALSBOM

BRITISH THERMAL UNITBTU

BRITISH THERMAL UNIT PER HOURBTUH

CONSTANT AIR VOLUMECAV

CONDENSATE DRAINCD

COOLING DEGREE DAYSCDD

CERTIFIED ENERGY MANAGERCEM

CHLORO-FLUORO-CARBONCFC

CUBIC FEET PER MINUTECFM

CHILLERCH

CHILLED WATERCHW

CHILLED WATER RETURNCHWR

CHILLED WATER SUPPLYCHWS

CHILLED WATER SYSTEM PUMPCHWP

COOLING LOAD FACTORCLF

COOLING LOAD TEMPERATURE DIFFERENCECLTD

COEFFICIENT OF PERFORMANCECOP

COMPUTER ROOM AIR CONDITIONERCRAC

COOLING TOWERCT

CONSTANT VOLUMECV

CONDENSER WATER PUMPCWP

CONDENSER WATER RETURNCWR

CONDENSER WATER SUPPLYCWS

CONDENSING UNITCU

CABINET UNIT HEATERCUH

DISCHARGE AIRDA

DRY BULBDB

DIRECT CURRENTDC

DEMAND CONTROLLED VENTILATIONDCV

DEGREE DAYDD

DIRECT DIGITAL CONTROLDDC

DISCHARGE LINE - REFRIGERANTDL

DIGITAL INPUTDI

DIGITAL OUTPUTDO

DIFFERENTIAL PRESSUREDP

DIRECT EXPANSIONDX

ENTERING AIR TEMPERATUREEAT

ELECTRONICALLY COMMUTATED MOTORECM

ENERGY EFFICIENCY RATIOEER

EXHAUST FANEF

EXHAUST GRILLEEG

EXHAUST HOODEH

ELEVATIONEL

ENERGY MANAGEMENT SYSTEMEMS

DESCRIPTIONABBREVIATION

EXTERNAL STATIC PRESSUREESP

EXPANSION TANKET

ENTERING WATER TEMPERATUREEWT

EXISTINGEX

FAHRENHEITF

ELECTRIC UNIT HEATEREUH

FAN COIL UNITFCU

FULL LOAD AMPERAGEFLA

FEET PER MINUTEFPM

FLOW SWITCHFS

FINNED TUBE RADIATORSFTR

GASOLINEG

GAUGEGA

GALLONS PER MINUTEGPM

GAS PRESSURE REGULATORGPR

GRAPHICAL UNIT INTERFACEGUI

HEAD PRESSUREHD

HYDRONIC CEILING CASSETTEHCC

HEATING DEGREE DAYSHDD

HIGH EFFICIENCY PARTICULATE ARRESTANCEHEPA

HFC

HEATING HOT WATERHHW

HEATING HOT WATER PUMPHHWP

HIGH LIMITHL

HEAT PUMP UNITHPU

HORSEPOWERHP

HEAT PUMP RETURNHPR

HEAT RECOVERY UNITHRU

HEATING, VENTILATION, & AIR CONDITIONINGHVAC

HEAT EXCHANGERHX

HERTZ (FREQUENCY)HZ

INTAKE AIRIA

INDOOR AIR QUALITYIAQ

INTERNATIONAL MECHANICAL CODEIMC

INCHESIN

INCHES OF WATER COLUMN PRESSUREIN-WC

INFRA-REDIR

INLINE FANIF

INTAKE HOODIH

INDOOR UNITIU

KILOWATTSkW

KILOWATT HOURSkWh

LEAVING AIR TEMPERATURELAT

LINEAR FEETLF

LATENT HEATLH

LIQUID LINE - REFRIGERANTLL

LEAST MEAN TEMPERATURE DIFFERENCELMTD

LOW PRESSURELP

LIQUID PROPANE (GAS)LPG

LOW PRESSURE STEAM CONDENSATE RETURNLPC

LOW PRESSURE STEAM SUPPLYLPS

LOCKED ROTOR AMPERAGELRA

LEAVING WATER TEMPERATURELWT

MIXED AIRMA

MAT

MAKE-UP AIR UNITMAU

THOUSAND BTUHMBH

EXHAUST AIREA

FEETFT

FOOT OF HEAD PRESSUREFT-HD

HYDRO-CHLORO-FLUORO-CARBONHCFC

HOODH

HYDRO-FLUORO-CARBON

HEATING HOT WATER RETURNHHWR

HEATING HOT WATER SUPPLYHHWS

HEAT PUMP SUPPLYHPS

HEAT RECOVERY VENTILATORHRV

MIXED AIR TEMPERATURE

MANUFACTURERMFR

MOTOR HORSEPOWERMHP

DESCRIPTIONABBREVIATION

MICHIGAN MECHANICAL CODEMMC

MAXIMUM OVERCURRENT PROTECTIONMOCP

MEDIUM PRESSURE STEAM SUPPLYMPS

MANUFACTURER'S RECOMMENDATIONS

MULTI-ZONEMZ

MEDIUM PRESSURE STEAM CONDENSATE RETURNMPC

NOT APPLICABLENA

NORMALLY CLOSEDNC

NORMALLY OPENNO

NET POSITIVE SUCTION HEADNPSH

OUTDOOR AIR PERCENTAGEOAP

OUTDOOR AIR TEMPERATUREOAT

OUNCEOZ

PUMPP

PRESSURE DROPPD

PRE-HEATPH

PACKAGED TERMINAL AIR CONDITIONERPTAC

PRESSURE RELIEF VALVEPRV

RETURN AIRRA

RETURN FANRF

RG

RELATIVE HUMIDITYRH

RE-HEATRHT

ROOFTOP UNITRTU

SUPPLY AIRSA

SUPPLY DIFFUSERSD

SUPPLY FANSF

SUPPLY GRILLESG

SENSIBLE HEATSH

SENSIBLE HEAT RATIOSHR

SHEET METAL AND AIR CONDITIONING CONTRACTORS

NATIONAL ASSOCIATIONSMACNA

STATIC PRESSURESP

NOT TO SCALENTS

OUTDOOR AIROA

POUNDS PER SQUARE INCHPSI

PROPORTIONAL-INTEGRAL-DERIVATIVEPID

RETURN GRILLE

RUNNING LOAD AMPERAGERLA

REVOLUTIONS PER MINUTERPM

SEASONAL ENERGY EFFICIENCY RATIOSEER

MR

RETURN AIR TEMPERATURERAT

SUPPLY AIR TEMPERATURESAT

SHADING COEFFICIENTSC

SEQUENCE OF OPERATIONSOO

TEMPERATURET

THERMOSTATTSTAT

TEST AND BALANCETAB

TEMPERATURE DIFFERENTIALTD

TIME OF DAYTOD

TONS OF REFRIGERATION (1 TON = 12,000 BTU)TONS

TOTAL STATIC PRESSURETSP

TERMINAL UNITTU

THERMOSTATIC EXPANSION VALVETXV

TYPICALTYP

UNIT HEATERUH

UNLESS NOTED OTHERWISEUNO

UNIT VENTILATORUV

VARIABLE AIR VOLUME BOXVAV

VOLUME DAMPERVD

VARIABLE FREQUENCY DRIVEVFD

VARIABLE REFRIGERANT FLOWVRF

VARIABLE SPEED DRIVEVSD

VERTICAL UNIT VENTILATORVUV

WET BULBWB

WATER COLUMNWC

DIFFUSERS, REGISTERS, & GRILLESDRG

MINIMUM CIRCUIT AMPACITYMCA

SUCTION LINE - REFRIGERANTSL

AAV

S TEMPERATURE SENSOR

W E

RE

C

YC

LE

C

HE

C

KE

D B Y:

D

ES

IG

N

ED

B Y:

AP

PR

O

VE

D B Y:

BL

AC

K

W

HI

TE

TH

E

BA

R

BE

LO

W S

HO

W S

G

RA

YS

C

AL

E

FR

O M W

HI

TE

T O S O

LID

TH

E

BA

R

BE

LO

W S

HO

W S

PR

IM

AR

Y C O

LO

RS

(866) 454-3923 | WWW.C2AE.COM

PROJ. #:

ISSUANCES

#DESCRIPTION DATE

COPYRIGHT C2AE.

NOT TO BE REPRODUCED OR DISTRIBUTED

WITHOUT PRIOR WRITTEN CONSENT.

ALL RIGHTS RESERVED.

PHASE

1/ /2 2:

:5

PM

Au to de sk D oc s:

Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/

EL

EM

M .rv t

EJ

R

D

TD

D

TD

BO

ILE

R

RE

PL

AC

EM

EN

T

FO

R

FA

IR

P

LA

IN

E

AS

T

EL

EM

EN

TA

RY

U

NI

O N

AV

EN

UE

, B

EN

TO

N

HA

RB

O R, M

IC

HI

G

AN

M-001

23-0327

ISSUED FOR BIDDING

26JAN2024ISSUED FOR BIDDING

M

EC

H A N

IC

A L L

EG

EN

D S

EX-WS

EX-6" SS

EX-3" DCW

EX-2" HHWS

EX-2" HHWR

EX-6" SS

EX

-1

1/ 2"

D

HW

EX-1 1/2" DCW EX-DWH

EX-P

EX-HX

EX-CR

REMOVE ABANDONED

STORAGE TANK,

SUPPORTS, AND

ANCILLARIES IT ITS

ENTIRETY.

TO REMAIN

REFER TO ARCH

SHEET FOR

WINDOW AND

LOUVER

DEMOLITION

EX-24"x48" SA

EX

-1

0" ø

E A

EX-6" SS

D1D1

DEMOLISH

EXISTING

PNEUMATIC

CONTROLS,

ANCILLARIES,

AND AIR

COMPRESSOR

DEMOLISH EXISTING

JOHNSON CONTROLS

DIGITAL SYSTEM

CONTROLLER

EX-AC

EX-KLN

COORDINATE

REPLACEMENT/

REUSE OF

EXISTING JACE

PANEL WITH

CONTROLS

CONTRACTOR

EXISTING TRANE

SUMMIT PANEL

TO REMAIN

TO REMAIN FOR REUSE

INCLUDING ALL PIPING.

EX-EPB

EXISTING CONDENSATE

PIPE TO REMAIN. DEMOLISH

AS REQD TO REMOVE

EXIST BOILER AND PREPARE

FOR REUSE.

DEMOLISH VENT AND SEAL

CHIMNEY PENETRATION.

TO REMAIN

TO REMAIN

MECHANICAL DEMOLITION NOTES:

1.

2.

3.

4.

5.

6.

7.

THE CONTRACTOR SHALL REVIEW THE ENTIRETY OF THE DRAWINGS AND SPECIFICATIONS BEFORE

ANY WORK IS STARTED.

ALL WORK TO BE DEMOLISHED IS NOTED WITH DASHED LINES, OR A DEMOLITION KEYNOTE, OR BOTH.

REVIEW THE DEMOLITION KEYNOTES PRIOR TO BEGINNING THE WORK.

EXCEPT FOR WHEN NOTED ON DRAWINGS, MECHANICAL EQUIPMENT AND SYSTEMS NOTED TO BE

REMOVED SHALL BE ENTIRELY DEMOLISHED, AND SHALL BECOME PROPERTY OF THE CONTRACTOR TO

REMOVE FROM THE SITE, WHILE FOLLOWING ALL CODES AND REQUIREMENTS.

ITEMS NOTED FOR SALVAGE SHALL BE REMOVED WITH DUE CARE TAKEN, AND RETURNED TO THE

OWNER IN A LIKE CONDITION TO IT'S PREVIOUS STATE.

DEMOLITION SHALL BE COORDINATED WITH OTHER TRADES. THE CONTRACTOR IS RESPONSIBLE FOR

ANY EXISTING MATERIALS TO REMAIN THAT ARE DAMAGED IN THE DEMOLITION PROCESS.

THESE DRAWINGS ARE COMPILED BY THE ARCHITECT AND ENGINEER FROM LIMITED FIELD

VERIFICATION OF EXISTING CONDITIONS. THERE ARE NO EXISTING DRAWINGS FOR REFERENCE. THE CONTRACTOR SHALL VERIFY EXISTING FIELD CONDITIONS. AREAS OF WORK THAT DIFFER GREATLY

FROM THE DEMOLITION PLAN SHALL GENERATE AN RFI TO THE ENGINEER.

MECHANICAL SYSTEMS AND EQUIPMENT LOCATED IN THE AREA OF DEMOLITION BUT USED TO SERVE AREAS THAT ARE NOT TO BE DEMOLISHED SHALL BE LEFT TO REMAIN, OR RELOCATED IN SUCH A WAY

AS TO MAINTAIN THE ORIGINAL DESIGN INTENT OF THE SYSTEM.

W E

RE

C

YC

LE

C

HE

C

KE

D B Y:

D

ES

IG

N

ED

B Y:

AP

PR

O

VE

D B Y:

BL

AC

K

W

HI

TE

TH

E

BA

R

BE

LO

W S

HO

W S

G

RA

YS

C

AL

E

FR

O M W

HI

TE

T O S

BA

R

BE

LO

W S

HO

W S

PR

IM

AR

Y C O

ISSUANCES

#DESCRIPTION DATE

COPYRIGHT C2AE.

NOT TO BE REPRODUCED OR DISTRIBUTED

WITHOUT PRIOR WRITTEN CONSENT.

ALL RIGHTS RESERVED.

PHASE

1/ /2 2:

:5

PM

Au to de sk D oc s:

Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/

EL

EM

M .rv t

C he ck er

D es ig ne r

Ap pr ov er

BO

ILE

R

RE

PL

AC

EM

EN

T

FO

R

FA

IR

P

LA

IN

E

AS

T

EL

EM

EN

TA

RY

U

NI

O N

AV

EN

UE

, B

EN

TO

N

HA

RB

O R, M

IC

HI

G

AN

MD100

23-0327

ISSUED FOR BIDDING

26JAN2024ISSUED FOR BIDDING

M

EC

H A N

IC

A L D

EM

O

LI

TI

O N P

LA

N

1/4" = 1'-0"

MECHANICAL DEMOLITION PLAN

MECHANICAL KEYNOTES

KEY VALUE KEYNOTE TEXT

D1 REUSE EXISTING 4" HOUSEKEEPING PAD, APPROX 5'-10'. EXISTING HEAT EXCHANGER

SUPPORT FRAME TO REMAIN, COORDINATE EXPANSION OF EXISTING

HOUSEKEEPING PAD FOR NEW BOILERS AND TO MAINTAIN LOCATION OF HX.

EX PIT

B-1

B-2

EX-P

EX-2" HHWR

EX-2" HHWS

EX-DWH

EX-WS

EX-HX

EX-6" SS

EX-6" SS

EX-3" DCW

EX

-1

1/ 2"

D

HW

EX-1 1/2" DHW

EX-1 1/2" DCW

M1M2M2

EXISTING DDC CONTROL

PANEL TO REMAIN

EX-CR

EXTEND CONDENSATE

PIPING TO BOILER FEEDWATER.

3" VENT, EXTEND THRU ROOF

MECHANICAL GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

IF COMPLIANCE WITH TWO OR MORE DIFFERING STANDARDS, REQUIREMENTS, DRAWINGS OR SPECIFICATIONS, OR ANY COMBINATION THEREOF, IS SPECIFIED AND THESE ESTABLISH DIFFERENT OR CONFLICTING REQUIREMENTS FOR MINIMUM QUANTITIES OR QUALITY LEVELS, COMPLY WITH THE MOST STRINGENT REQUIREMENT. THE MOST STRINGENT REQUIREMENT WILL BE THE BETTER QUALITY OR GREATER QUANTITY OF WORK, AND WILL TYPICALLY BE THE MORE EXPENSIVE OPTION. REFER UNCERTAINTIES AND REQUIREMENTS THAT ARE DIFFERENT, BUT APPARENTLY EQUAL, TO ENGINEER FOR A DECISION BEFORE

PROCEEDING.

THE QUANTITY OR QUALITY LEVEL SHOWN OR SPECIFIED SHALL BE THE MINIMUM PROVIDED OR PERFORMED. THE ACTUAL INSTALLATION MAY COMPLY EXACTLY WITH THE MINIMUM QUANTITY OR QUALITY SPECIFIED, OR IT MAY EXCEED THE MINIMUM WITHIN REASONABLE LIMITS. TO COMPLY WITH THESE REQUIREMENTS, INDICATED NUMERIC VALUES ARE MINIMUM OR MAXIMUM, AS APPROPRIATE, FOR THE CONTEXT OF REQUIREMENTS. REFER UNCERTAINTIES TO ENGINEER FOR A

DECISION BEFORE PROCEEDING.

DESIGN DOCUMENTS MUST BE REPRODUCED IN THEIR ENTIRETY, INCLUDING ALL PLANS, SPECIFICATIONS, AND FRONT END DOCUMENTS.

ONLY COMPLETE DOCUMENT SETS ARE TO BE DISTRIBUTED TO SUBCONTRACTORS AND SUPPLIERS OF THE CONTRACTOR DURING BIDDING OR CONSTRUCTION.

FAILURE TO REVIEW AND COMPLY WITH A FULL SET OF CONTRACT DOCUMENTS WILL NOT BE ACCEPTED AS A VALID REASON FOR FAILURE TO MEET THE

REQUIREMENTS OF THE PLANS AND SPECIFICATIONS.

ALL MECHANICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH LOCAL ORDINANCES, CODES, AND LAWS. FOR PURPOSES OF THIS DESIGN, THE CODES FOR

THE STATE OF MICHIGAN WERE USED AS THE BASIS.

MECHANICAL CONTRACTOR SHALL COORDINATE ROOF PENETRATIONS WITH ROOFING CONTRACTOR OR ROOFING MANUFACTURER TO AVOID DAMAGE TO

ROOFING SYSTEM.

COORDINATE LOCATIONS OF ALL DEVICES WITH ARCHITECTURAL, STRUCTURAL, CIVIL, INTERIORS, AND ELECTRICAL PRIOR TO ROUGH-IN. ALL CONFLICTS WITH FINISHES, ADJACENT CONSTRUCTION AND CONSTRUCTION DOCUMENTS ARE TO GENERATE AN RFI FROM THE MECHANICAL CONTRACTOR TO THE ENGINEER

PRIOR TO PROCEEDING AND COMPLETION OF WORK

ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH MOTOR STARTERS COMPATIBLE WITH CONTROLS SYSTEM. COORDINATE WITH CONTROLS AND

ELECTRICAL CONTRACTORS.

IN UNFINISHED AREAS, INSTALL ALL MECHANICAL CONTROL DEVICES (THERMOSTATS, ROOM SENSORS, REMOTE TEST STATIONS, SMOKE DAMPER INDICATORS, ETC.) RECESSED IN WEB OF COLUMNS TO PREVENT DAMAGE.

PROVIDE EMERGENCY SHUTOFF AT BOILER ROOM EXIT DOORS TO SHUTDOWN ALL BOILERS PER CSD-1 REQUIREMENTS.

W E

RE

C

YC

LE

C

HE

C

KE

D B Y:

D

ES

IG

N

ED

B Y:

AP

PR

O

VE

D B Y:

BL

AC

K

W

HI

TE

TH

E

BA

R

BE

LO

W S

HO

W S

G

RA

YS

C

AL

E

FR

O M W

HI

TE

T O S

BA

R

BE

LO

W S

HO

W S

PR

IM

AR

Y C O

ISSUANCES

#DESCRIPTION DATE

COPYRIGHT C2AE.

NOT TO BE REPRODUCED OR DISTRIBUTED

WITHOUT PRIOR WRITTEN CONSENT.

ALL RIGHTS RESERVED.

PHASE

1/ /2 2:

:5

PM

Au to de sk D oc s:

Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/

EL

EM

M .rv t

C he ck er

D es ig ne r

Ap pr ov er

BO

ILE

R

RE

PL

AC

EM

EN

T

FO

R

FA

IR

P

LA

IN

E

AS

T

EL

EM

EN

TA

RY

U

NI

O N

AV

EN

UE

, B

EN

TO

N

HA

RB

O R, M

IC

HI

G

AN

M-100

23-0327

ISSUED FOR BIDDING

26JAN2024ISSUED FOR BIDDING

M

EC

H A N

IC

A L P

LA

N

1/4" = 1'-0"

MECHANICAL PLAN - BOILER ROOM

MECHANICAL KEYNOTES

KEY VALUE KEYNOTE TEXT

M1 10" EXHAUST FLUE AND 6" COMBUSTION AIR INTAKE THROUGH ROOF.

M2 INSTALL NEW BOILERS ON EXISTING 4" CONCRETE HOUSEKEEPING PAD, EXTEND EXISTING PAD AS REQUIRED. CONNECT PIPING TO EXISTING

STEAM MAIN. CONNECT TO EXISTING FEEDWATER SYSTEM.

MECHANICAL GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

IF COMPLIANCE WITH TWO OR MORE DIFFERING STANDARDS, REQUIREMENTS, DRAWINGS OR SPECIFICATIONS, OR ANY COMBINATION THEREOF, IS SPECIFIED AND THESE ESTABLISH DIFFERENT OR CONFLICTING REQUIREMENTS FOR MINIMUM QUANTITIES OR QUALITY LEVELS, COMPLY WITH THE MOST STRINGENT REQUIREMENT. THE MOST STRINGENT REQUIREMENT WILL BE THE BETTER QUALITY OR GREATER QUANTITY OF WORK, AND WILL TYPICALLY BE THE MORE EXPENSIVE OPTION. REFER UNCERTAINTIES AND REQUIREMENTS THAT ARE DIFFERENT, BUT APPARENTLY EQUAL, TO ENGINEER FOR A DECISION BEFORE

PROCEEDING.

THE QUANTITY OR QUALITY LEVEL SHOWN OR SPECIFIED SHALL BE THE MINIMUM PROVIDED OR PERFORMED. THE ACTUAL INSTALLATION MAY COMPLY EXACTLY WITH THE MINIMUM QUANTITY OR QUALITY SPECIFIED, OR IT MAY EXCEED THE MINIMUM WITHIN REASONABLE LIMITS. TO COMPLY WITH THESE REQUIREMENTS, INDICATED NUMERIC VALUES ARE MINIMUM OR MAXIMUM, AS APPROPRIATE, FOR THE CONTEXT OF REQUIREMENTS. REFER UNCERTAINTIES TO ENGINEER FOR A

DECISION BEFORE PROCEEDING.

DESIGN DOCUMENTS MUST BE REPRODUCED IN THEIR ENTIRETY, INCLUDING ALL PLANS, SPECIFICATIONS, AND FRONT END DOCUMENTS.

ONLY COMPLETE DOCUMENT SETS ARE TO BE DISTRIBUTED TO SUBCONTRACTORS AND SUPPLIERS OF THE CONTRACTOR DURING BIDDING OR CONSTRUCTION.

FAILURE TO REVIEW AND COMPLY WITH A FULL SET OF CONTRACT DOCUMENTS WILL NOT BE ACCEPTED AS A VALID REASON FOR FAILURE TO MEET THE

REQUIREMENTS OF THE PLANS AND SPECIFICATIONS.

ALL MECHANICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH LOCAL ORDINANCES, CODES, AND LAWS. FOR PURPOSES OF THIS DESIGN, THE CODES FOR

THE STATE OF MICHIGAN WERE USED AS THE BASIS.

MECHANICAL CONTRACTOR SHALL COORDINATE ROOF PENETRATIONS WITH ROOFING CONTRACTOR OR ROOFING MANUFACTURER TO AVOID DAMAGE TO

ROOFING SYSTEM.

COORDINATE LOCATIONS OF ALL DEVICES WITH ARCHITECTURAL, STRUCTURAL, CIVIL, INTERIORS, AND ELECTRICAL PRIOR TO ROUGH-IN. ALL CONFLICTS WITH FINISHES, ADJACENT CONSTRUCTION AND CONSTRUCTION DOCUMENTS ARE TO GENERATE AN RFI FROM THE MECHANICAL CONTRACTOR TO THE ENGINEER

PRIOR TO PROCEEDING AND COMPLETION OF WORK

ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH MOTOR STARTERS COMPATIBLE WITH CONTROLS SYSTEM. COORDINATE WITH CONTROLS AND

ELECTRICAL CONTRACTORS.

IN UNFINISHED AREAS,…