230327_240126_Elem_Drawings.pdf
PDF 1 MB Posted
- Solicitation number
- RFP - BHA - 240000001444
- Issued by
- Berrien County, Bergland CDP, Michigan
About this file
This document pertains to a boiler replacement project for Fair Plain East Elementary School located in Benton Harbor, Michigan. The project involves the demolition and replacement of two existing boilers and associated mechanical work. The key details include:
The project is being issued for bidding by the Benton Harbor Area Schools. The scope of work includes removing and replacing two existing steam boilers, modifying existing mechanical systems, and making associated roofing and architectural modifications. The work is to be completed in accordance with the applicable codes and standards listed. Contractors are required to coordinate the work with other trades and field verify existing conditions prior to construction. The project has a single phase and the construction documents include architectural, mechanical, and electrical drawings.
Pricing for the project will be based on the contractor's bid. No set-asides or special requirements are noted. The project is funded by the school district and the construction duration is not explicitly stated. Contractors must comply with all applicable local, state, and federal requirements for the work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum 2-4.pdf | ||
| 230327_240126_ProjectManual Part 1 of 2.pdf | ||
| 230327_240126_ProjectManual Part 2 of 2.pdf | ||
| RFI and Response.pdf | ||
| 230327_240126_HS_Drawings.zip | ZIP file | |
| Addendum 1 Pt2.pdf | ||
| Addendum 1 Pt3.pdf | ||
| Addendum 1 Pt1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPLICABLE CODES AND STANDARDS
APPLICABLE CODES EDITION:
BUILDING CODES:
MICHIGAN BUILDING CODE (MBC) 2015
NFPA 101 - LIFE SAFETY CODE (NFPA) 2012
ICC A117.1 - ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES (ANSI) 2017
MICHIGAN ENERGY CODE 2015
FIRE CODE:
INTERNATIONAL FIRE CODE (IFC) 2015
PLUMBING CODE:
MICHIGAN PLUMBING CODE (MPC) 2018
MECHANICAL CODES:
MICHIGAN MECHANICAL CODE (MMC) 2015
MICHIGAN BOILER CODE RULES 2013
ELECTRICAL CODE:
NFPA 70 - NATIONAL ELECTRICAL CODE (NEC) 2017
OCCUPANCY CLASSIFICATION:
· E EDUCATION (UNCHANGED)
CODE SUMMARY
W E
RE
C
YC
LE
C
HE
C
KE
D B
Y:
D
ES
IG
NE
D B
Y:
AP
PR
O
VE
D B
Y:
BOILER REPLACEMENT FOR:
LOCATION MAP
NO SCALE
N
EW
S
VICINITY MAP
NO SCALE
N
EW
S
EXCEPT WHERE OTHERWISE INDICATED ON THE PLANS OR IN THE PROPOSAL SUPPLEMENTAL
SPECIFICATIONS CONTAINED THEREIN, ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE MICHIGAN DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR CONSTRUCTION, 2020 EDITION, AND THE CURRENT SUPPLEMENTAL SPECIFICATIONS.
(AVAILABLE AT WWW.MDOTJBOSS.STATE.MI.US/SPECPROV/SPECBOOKHOME.HTM#1468271)
IT IS UNDERSTOOD THAT THE CONTRACTOR SHALL PERFORM ALL WORK UNDER THIS CONTRACT IN
ACCORDANCE WITH ALL APPLICABLE PROVISIONS, POLICIES, RULES AND STANDARDS OF THE
MICHIGAN OCCUPATIONAL SAFETY AND HEALTH ACT (MDSHA), BEING ACT 154 OF THE PUBLIC ACTS
OF 2013 AND AS AMENDED.
THROUGHOUT THE DRAWING SET, THE GRAYSCALE LEGEND ON THE EDGE OF TITLE BLOCKS
SHOULD TRANSITION FROM WHITE THROUGH EIGHT SHADES OF GRAY TO SOLID BLACK. IF THE
GRAYSCALE SHADES ARE NOT DISTINCT, THE DRAWING(S) HAVE NOT PRINTED CORRECTLY.
LAKE ERIE
GRAND RAPIDS
TRAVERSE CITY
LAKE SUPERIOR
UPPER PENINSULA
MACKINAW CITY
LAKE HURON
ALPENA
PETOSKEY
GAYLORD
GRAYLING
LA
KE
M
IC
HI
G
AN
SAGINAW
ST.JOHNS FLINT
LANSING
JACKSON DETROITKALAMAZOO
ANN ARBOR
BL
AC
K W
HI
TE
TH
E
BA
R
BE
LO
W S
HO
W
S G
RA
YS
C
AL
E
FR
O M
W
HI
TE
T
O S
O
LID
TH
E
BA
R
BE
LO
W S
HO
W
S
PR
IM
AR
Y C
O
LO
RS
(866) 454-3923 | WWW.C2AE.COM
PROJ. #:
ISSUANCES
# DESCRIPTION DATE
COPYRIGHT C2AE.
NOT TO BE REPRODUCED OR DISTRIBUTED
WITHOUT PRIOR WRITTEN CONSENT.
ALL RIGHTS RESERVED.
PHASE
BENTON HARBOR
1/
/2
4:
:4
PM
Au to de sk
D oc s:
Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/
EL
EM
A.
rv t
C he ck er
D es ig ne r
Ap pr ov er
FAIR PLAIN EAST ELEMENTARY SCHOOL
1998 UNION AVE, BENTON HARBOR, MI 49022
ISSUE DATE: 26JAN2024
BENTON HARBOR AREA SCHOOLS
ISSUED FOR BIDDING
PROJECT NUMBER: 230327
FA
IR
P
LA
IN
E
AS
T
EL
EM
EN
TA
RY
S
C
HO
O L
U
NI
O N
AV
E, BE
NT
O N
HA
RB
O R, M I 4
G-001
230327
ISSUED FOR BIDDING
26JAN2024ISSUED FOR BIDDING
C O
V
ER
S H
EE
T
SHEET
NO. SHEET NAME
GENERAL
G-001 COVER SHEET
ARCHITECTURAL
A-001 ARCHITECTURAL LEGENDS, SYMBOLS, ABBREVIATIONS, AND
TYPICAL DETAILS
A-100 FLOOR PLANS - LOWER LEVEL
A-101 FLOOR PLANS - FIRST LEVEL
A-102 FLOOR PLANS - SECOND LEVEL ROOF
A-501 DETAILS
MECHANICAL
M-001 MECHANICAL LEGENDS
MD100 MECHANICAL DEMOLITION PLAN
M-100 MECHANICAL PLAN
M-103 MECHANICAL PLAN - ROOF
M-501 MECHANICAL DETAILS & SCHEDULES
ELECTRICAL
E-001 GENERAL NOTES AND LEGENDS
E-101 ELECTRICAL PLANS
E-501 DETAILS
TOTAL SHEETS: 14
MOUNTING HEIGHT
COORDINATION
ARCHITECTURAL,
MECHANICAL &
ELECTRICAL TRADES
SHALL COORDINATE
LOCATIONS OF WALL
MOUNTED ITEMS TO ALIGN
EITHER VERTICALLY OR
HORIZONTALLY.
FINISH FLOOR LINE
RECOMMENDED MOUNTING HEIGHTS (UNLESS OTHERWISE NOTED)
" 72
(M
IN
" SE
E
EL
EC
T
EL
EC
TR
IC
O R
PA
NE
L C
AB
IN
ET
PO
W
ER
P
AN
EL
EL
EC
TR
IC
TE
LE
PH
ON
E
OR
T
V
OU
TL
ET
SW
IT
CH
PU
SH
B
UT
TO
N
FI
RE
A
LA
RM
B
OX
TH
ER
MO
ST
AT
CA
RD
R
EA
DE
R
ME
CH
AN
IC
AL
PA
NE
LS
IN
FI
NI
SH
ED
S
PA
CE
S
SE
LE
CT
OR
S W
IT
CH
R S
SW
IT
CH
O
R W
AL
L
OU
TL
ET
A
BO
VE
CA
BI
NE
T
SS
FI
RE
E
XT
IN
GU
IS
HE
R
FI
RE
E
XT
IN
GU
IS
HE
R
CA
BI
NE
T, F
IR
E
HO
SE
OR
C
OM
BI
NA
TI
ON
CA
BI
NE
T
EX
TI
NG
UI
SH
ER
A
ND
/O R
CE
NT
ER
O
F
HO
SE
V
AL
VE
" T
O
TO
P
OF
CE
NT
ER
O
F H
AN
DL
E
" M
AX
TO
DRAWING REFERENCE SYMBOLS
ENLARGED PLAN OR DETAIL
WALL SECTION
BUILDING SECTION
EXTERIOR ELEVATIONS
INTERIOR ELEVATIONS
DEMO KEYNOTE##
REVISION CLOUD AND TAG
VIEW TITLE & REFERENCE
EXISTING COLUMN LINE
NEW COLUMN LINE
DETAIL
LEVEL OR ELEVATION
XX
DEMARCATION LINE
X-###
X## EQUIPMENT TAG
WALL TAG
###.# DOOR TAG
ROOM NAME
ROOM TAG
WINDOW TAG
X##
ARCHITECTURAL KEYNOTE
#' - #" CEILING SPOT ELEVATION
XX# FURNITURE TAG
FINISH TAG
SPECIALITY EQUIPMENT TAG
XX-#
XX-#
X##
PARTITION TYPE
FIRE RATING (EX. 1 = 1-HOUR)
PARTITION ASSMBLY
A101
A101
1 Ref
Re f
Re f
1 Ref
A101
1 SIM
A101
SIM
A101
SIM
A101
SIM
A101
1 SIM
CONCRETE FLOOR INFILL
(TO MEET REQUIREMENTS
OF SPECIFICATION
SECTIONS 017300 & 033000)
1/4" GALVANIZED STEEL PLATE
(PAINT)
EXISTING CONCRETE
FLOOR SLAB (TO REMAIN)
3/8" DIAMETER "SIMPSON
STRONG-TIE" TITAN-HD SCREW
ANCHORS AT 2'-0" O.C.
(TYPICAL)(TYP.)
2"
(TYP.)
4"
UP TO 6" DEEP
EM
BE
DM
EN
T 2 1
/2" (M
IN
UP
TO
6" D
EE
P
CONCRETE FLOOR INFILL
(TO MEET REQUIREMENTS
OF SPECIFICATION
SECTIONS 017300 & 033000)
1 1/2", 20 GAGE NON-
COMPOSITE GALVANIZED
METAL DECK
EXISTING CONCRETE
FLOOR SLAB (TO REMAIN)
3/8" "SIMPSON STRONG-TIE"
TITEN-HD SCREW ANCHORS
AT 2'-0" O.C. (TYPICAL)
4x4x1/4" STEEL ANGLE (2)
SIDES OF OPENING
EXISTING VERTICAL
EDGE OF CONCRETE
SLAB (OR CLEAN CUT)
EMBEDMENT
2 1/2" (MIN.)
2"
48" 48"
EXISTING WALL (TO BE REMOVED)
INFILL WITH TROWELABLE
LEVELING AND PATCHING
COMPOUND
GRIND EXISTING CONCRETE SLAB
OF EXISTING WALL
FIRE STOPPING
SEALANT
GYPSUM BOARD
PANELS
WIRES, PIPES,
AND / OR
CONDUITS
W E
RE
C
YC
LE
C
HE
C
KE
D B
Y:
D
ES
IG
NE
D B
Y:
AP
PR
O
VE
D B
Y:
BL
AC
K
W
HI
TE
TH
E
BA
R
BE
LO
W S
HO
W
S G
RA
YS
C
AL
E
FR
O M
W
HI
TE
T
O S
O
LID
TH
E
BA
R
BE
LO
W S
HO
W
S
PR
IM
AR
Y C
O
LO
RS
(866) 454-3923 | WWW.C2AE.COM
PROJ. #:
ISSUANCES
# DESCRIPTION DATE
COPYRIGHT C2AE.
NOT TO BE REPRODUCED OR DISTRIBUTED
WITHOUT PRIOR WRITTEN CONSENT.
ALL RIGHTS RESERVED.
PHASE
1/
/2
4:
:5
PM
Au to de sk
D oc s:
Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/
EL
EM
A.
rv t
C he ck er
D es ig ne r
Ap pr ov er
FA
IR
P
LA
IN
E
AS
T
EL
EM
EN
TA
RY
S
C
HO
O L
U
NI
O N
AV
E, BE
NT
O N
HA
RB
O R, M I 4
A-001
230327
ISSUED FOR BIDDING
26JAN2024ISSUED FOR BIDDING
A
RC
H
IT
EC
TU
RA
L L
EG
EN
D S, S Y
M
BO
LS
A
BB
RE
V
IA
TI
O N
S, A
N D
T Y
PI
C
A L D
ET
A
IL
S
ABBREVIATIONS
ABBREV. FULL TEXT
AB ANCHOR BOLT
ABI ADDITIVE BID ITEM
AC ACOUSTICAL
ACB ACOUSTICAL CEILING BAFFLE
ACP ACOUSTICAL CEILING PANEL
ACS ACOUSTICAL CEILING SPRAY
AD AREA DRAIN
ADA ADA
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
ALUM ALUMINUM
AP ACCESS DOORS
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASPH ASPHALT
AWP ACOUSTICAL WALL PANEL
B/ BOTTOM OF
BD BOARD
BF BARRIER FREE
BIT BITUMINOUS
BL BUILDING LINE
BLDG BUILDING
BLKHD BULKHEAD
BOTT BOTTOM
BP BASE PLATE
BR BUMP RAIL
BS BOTH SIDES
BUR BUILT UP ROOFING
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CFMF COLD FORMED METAL FRAMING
CG CORNER GUARD
CH CHANNEL
CHKDPL CHECKERED PLATE
CJ CONTROL JOINT
CL CENTERLINE
CL TO CL CENTERLINE TO CENTERLINE
CLG CEILING
CLK CAULKING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
COMP COMPRESSIBLE
COMPO COMPOSITION
CONC CONCRETE
CONN CONNECT, CONNECTION
CONST CONSTRUCTION
CONST JT CONSTRUCTION JOINT
CONT CONTINUOUS
CONTR CONTRACTOR
CPT CARPET TILE
CS CONCRETE SEALER
CTR COUNTER
DEXS DOUBLE EXTRA STRONG (STEEL PIPE)
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFUSER
DN DOWN
DO DOOR OPENING
DR DOOR
DS DOWN SPOUT
DT DRAIN TILE
DTL DETAIL
DWG DRAWING
DWR DRAWER
E EAST
EA EACH
EIFS EXTERIOR INSULATION AND FINISH
SYSTEMS
EJ EXPANSION JOINT
EL ELEVATION
ELECT ELECTRICAL
ELEV ELEVATOR OR ELEVATION
ENCL ENCLOSURE
EP EPOXY PAINT
EPS EXTERIOR PAINT SYSTEM
EQ EQUAL
EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
EW EACH WAY
EWC ELECTRICAL WATER COOLER
EX EXISTING
ABBREVIATIONS
ABBREV. FULL TEXT
EXGR EXISTING GRADE
EXP EXPANSION
EXS EXTRA STRONG (STEEL PIPE)
EXT EXTERIOR
FA FIRE ALARM
FAB FABRIC/UPHOLSTERY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FG FROSTED GLASS
FHC FIRE HOSE CABINET
FIN FINISH
FL FLOOR
FLL FLOOR LINE
FLUOR FLUORESCENT
FOC FACE OF COLUMN
FOCONC FACE OF CONCRETE
FRC FIBER REINFORCED CONCRETE
FRP FIELD REINFORCED PANEL
FRPFG FIREPROOFING
FRTW FIRE RETARDANT TREATED WOOD
FS FULL SIZE
FTG FOOTING
FUR FURRING
FV FIELD VERIFY
G.B. GRAB BAR, GRADE BEAM
G.O. GRILL OPENING
GA GAUGE
GALV GALVANIZED
GCT GLAZED CERAMIC TILE
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GL GLASS
GND. GROUND
GR. GRADE
GRTG. GRATING
GSCFT GLAZED STRUCTURAL CLAY FACING TILE
GT GROUT
GYP. BD. GYPSUM BOARD
HC HOLLOW CORE
HCWD HOLLOW CORE WOOD
HDPB HIGH DENSITY PARTICLEBOARD
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HR HOUR
HT HEIGHT
HWD HARDWARE
I.D. OR ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IG INSULATING GLASS
IN INCHES
INCL INCLUDING, INCLUSIVE
INSUL INSULATION
INT INTERIOR
IPS INTERIOR PAINT SYSTEM
JAN JANITOR
JT JOINT
kW KILOWATTS kWh KILOWATT HOURS
LAD LADDER
LAM LAMINATED
LAV LAVATORY
LF LINEAR FEET
LGTH LENGTH
LH LEFT HAND
LKR LOCKER
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LO LOUVER OPENING
LP LIGHTING PANEL
LPG LIQUID PETROLEUM GAS
LPS LOW PRESSURE STEAM
LT LIGHT
LWT LEAVING WATER TEMPERATURE
MA MEDICAL AIR
MANUF MANUFACTURER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MBH THOUSAND BTU/HR
MC MEDICINE CABINET
MCA MINIMUM CIRCUIT AMPACITY
MCC MULTI-COLOR COATING
ABBREVIATIONS
ABBREV. FULL TEXT
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEMBWP MEMBRANE WATERPROOFING
MET METAL
MEZZ MEZZANINE
MFR MANUFACTURER
MFS MAXIMUM FUSE SIZE
MG MEDICAL GAS
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN. MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MM MISCELLANEOUS METALS
MO MASONRY OPENING
MOCP MAXIMUM OVERCRRENT PROTECTION
MPC MICHIGAN PLUMBING CODE
MR MANUFACTURER'S RECOMMENDATIONS
MT MARBLE TILE
MTD MOUNTED
MUL. MULLION
N NORTH
N.S. NEAR SIDE
NF NO FINISH
NIC NOT IN CONTRACT
NO NUMBER
NPSH NET POSITIVE SUCTION HEAD
NSNS NON SHRINK NON STAIN GROUT
NTS NOT TO SCALE
NTS NOT TO SCALE
O.C. OR OC ON CENTER
OBSGL OBSCURE GLASS
OD OUTSIDE DIAMETER
OHDR SECTIONAL OVERHEAD DOOR
OPNG OPENING
OPP OPPOSITE
P PAINT
PART PARTITION
PB PARTICLE BOARD
PC PRECAST
PCS PIECES
PERM PERMANENT
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLY PLYWOOD
PT PRESSURE TREATED
PT PORCELAIN TILE
PTB PORCELAIN TILE BASE
QT QUARRY TILE
QTB QUARTZ TILE BASE
QTZ QUARTZ
R RISER
RA RETURN AIR
RB RUBBER BASE
RC ROOF CONDUCTOR
RD ROOF DRAIN
RD ROUND
RECVG RECEIVING
REF REFRIGERATOR
REINF REINFORCED
REQ'D REQUIRED
RF RESILIENT FLOORING
RH RIGHT HAND
RL ROOF LADDER
RM ROOM
RO ROUGH OPENING
RS ROOF SUMP
RSN RESIN
RWD REDWOOD
RWD RIGID WALL PROTECTION
S SOUTH
S SPANDREL GLASS
SA SUPPLY AIR
SAB SOUND ATTENUATION BLANKETS
SC SOLID CORE
SCH SCHEDULE
SCONC SEALED CONCRETE
SCWD SOLID CORE WOOD
SECT SECTION
SER.RECPT SERVICE RECEPTOR
SH SHELF
SHT SHEET
ABBREVIATIONS
ABBREV. FULL TEXT
SHWR SHOWER
SIM SIMILAR
SLR CONCRETE SEALER
SLS SOLID SURFACE
SLV SHORT LEG VERTICAL
SPEC SPECIFICATION
SQ SQUARE
SQFT SQUARE FOOT
SS STAINLESS STEEL
SSK SERVICE SINK
SSM SOLID SURFACING MATERIAL
ST SMOKE-TIGHT PER CODE TO RESIST THE
PASSAGE OF SMOKE
STD STANDARD
STDW STANDARD WEIGHT (STEEL PIPE)
STL STEEL
STN STAIN
STOR STORAGE
STRL STRUCTURAL
SUPP SUPPORT
SUSP SUSPENDED
SYM SUSPENSION SYMMETRICAL
T TREAD
T&G TONGUE AND GROOVE
T.O.C. OR T/C TOP OF CONCRETE
T.O.F. OR T/F TOP OF FOOTING
T.O.M. OR T/M TOP OF MASONRY
T.O.P. OR T/P TOP OF PAVEMENT
T.O.S. OR T/S TOP OF STEEL
T.O.W. OR T/W TOP OF WALL
T/ TOP OF
TB TRUSS BEARING
TG TEMPERED GLASS
THK THICK
THRESH THRESHOLD
TLT TOILET
TP TOILET PARTITION
TR TRANSITION TRIM
TYP TYPICAL
TYP TYPICAL
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WC WALLCOVERING
WCO WALL CLEAN OUT
WCVR WALLCOVERING
WD WOOD
WP WATERPROOFING
WP WORKPOINT
WP WALL PROTECTION
WS WINDOW SHADE
WSCT WAINSCOT
WT WEIGHT
X-(MATERIAL) DENOTES EXISTING MATERIAL
REFRENCED
NOT TO SCALE
THRU WALL FIRE STOPPING - 3D
NOT TO SCALE
TYP DEMO FLOOR INFILL (OPENING 12" SQ. OR SMALER)
NOT TO SCALE
TYP DEMO FLOOR INFILL (OPENING 12" TO 5'-0")
NOT TO SCALE
TYP DEMO FLOOR LEVELING AT WALL REMOVAL
A-501
A-501
A-501
A-501
SIM
NEW EXTERIOR INSULATED
TRANSLUCENT FIBERGLASS PANELS
TO BE INSTALLED WITHIN THE
EXISTING WALL OPENING WHERE
EXISTING INFILL WALLS WERE
REMOVED. TRIM FINISHES ARE TO
MATCH EXISTING MATERIALS.
A28A28
A28A28
A28A28
A28A28
1. CONTRACTORS ARE TO COORDINATE WORK WITH ALL OTHER TRADES.
2. CONFLICTS BETWEEN NOTES, DETAILS, SPECIFICATIONS, ETC., SHALL BE
VERIFIED WITH THE ARCHITECT OR THE MOST STRINGENT PROVISIONS SHALL
GOVERN.
3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME
NATURE AS SHOWN FOR SIMILAR CONDITIONS. ANY UNCLEAR CONDITIONS
SHALL BE VERIFIED WITH THE ARCHITECT PRIOR TO CONSTRUCTION OF THAT
AREA.
4. DRAWINGS ARE NOT TO BE SCALED. ANY UNCLEAR DIMENSIONS, OR
DIMENSIONAL DISCREPANCIES, SHALL BE VERIFIED WITH ARCHITECT.
5. ALL EXISTING CONDITIONS AND ALL RELATED DIMENSIONS INDICATED IN THE
CONTRACT DOCUMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION,
ERECTION, AND/OR CONSTRUCTION. ANY CONDITIONS THAT DIFFER FROM THAT
INDICATED IN THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE
ARCHITECT FOR REVIEW PRIOR TO FABRICATION, ERECTION, AND/OR
CONSTRUCTION.
6. CONTRACTOR TO REVIEW ENTIRE SET OF CONSTRUCTION DOCUMENTS,
INCLUDING SPECIFICATION, AND SHALL COORDINATE WORK BETWEEN ALL
TRADES. IF CONFLICTS ARISE DUE TO COORDINATION OF TRADES,
CONTRACTOR IS TO VERIFY CONFLICT WITH ARCHITECT PRIOR TO
CONSTRUCTION / INSTALLATION OF CONFLICTING ITEMS.
7. PATCH ALL EXPOSED INTERIOR AND EXTERIOR WALLS WHERE ATTACHED OR
IMBEDDED ITEMS WERE REMOVED.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATION OF FLOOR,
WALL, AND/OR CEILING SUBSTRATES FOR NEW FINISHES.
9. MAINTAIN FIRE RATING AT ALL ASSEMBLIES WHERE OPENINGS PENETRATIONS,
EMBEDMENT, RECESSED EQUIPMENT, ACCESSORIES, ETC. DISRUPT THE
CONTINUITY OF THE RATING
10. REMOVE ADHESIVE AND/OR MORTAR LEFT FROM THE REMOVAL OF EXISTING
FLOOR COVERING AND PREP FLOOR W/CONCRETE (OR FLORSTONE) AS
NECESSARY TO ACCOMMODATE NEW FLOOR COVERINGS.
11. ALL DIMENSIONS ARE FROM FACE OF WALL SHEATHING, C.M.U., OR CONCRETE,
U.N.O.
12. PROVIDE ISOLATION MATERIAL BETWEEN DISSIMILAR MATERIALS THAT ARE IN
CONTACT WITH ONE ANOTHER.
13. PATCH & REPAIR ALL MAJOR & MINOR BLEMISHES AS REQ'D, DUE TO
DEMOLITION WORK. REPAIRS ARE TO MATCH ADJACENT MATERIAL & COLOR.
14. PROVIDE SOLID, CONTINUOUS, NON COMBUSTIBLE BLOCKING AT LOCATIONS
WHERE MILLWORK, PLUMBING FIXTURES, EQUIPMENT, ACCESSORIES, OR ETC.
ATTACH TO WALLS OR CEILINGS.
GENERAL NOTES:
D10
D9
D8
D6
DEMO PLAN LEGEND:
EXISTING WALL
OR PARTITION TO
REMAIN
EXISTING DOOR
TO REMAIN
EXISTING
BUILDING
COMPONENT &
STRUCTURE TO
REMAIN
EXISTING
WALL/PARTITION OR
EXISTING ITEMS TO
BE REMOVED
EXISTING DOOR &
FRAME TO BE
REMOVED
EXISTING ASSEMBLY
TO BE REMOVED
NOTE: ALL ITEMS SHOWN DARK AND DASHED ARE TO BE DEMOLISHED- U.N.O.
GENERAL DEMOLITION NOTES:
1. ALL EXISTING ITEMS TO BE RETAINED BY THE OWNER WILL BE REMOVED PRIOR
TO DEMOLITION. ANY ITEMS LEFT IN THE DEMOLITION AREA BECOME THE
PROPERTY OF THE DEMOLITION CONTRACTOR.
2. REFER TO ALL CONTRACT DOCUMENTS, INCLUDING SPECIFICATIONS, FOR
ADDITIONAL DEMOLITION NOTES AND INFORMATION.
3. SHORE AND BRACE ALL WORK REQUIRED TO REMAIN.
4. CONTRACTORS SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME
FAMILIAR WITH EXISTING CONDITIONS
5. CONTRACTORS ARE TO COORDINATE DEMOLITION WORK WITH OWNER PRIOR
TO START OF WORK.
6. U.N.O., PATCH AND PREPARE FLOOR W/ CONCRETE (OR FLORSTONE) TO FLUSH
WITH ADJACENT FLOOR SURFACE. FILL ANY SLOPING OR RECESSED AREAS TO
LEVEL WITH TYPICAL FINISH FLOOR ELEVATION TO ACCOMMODATE NEW
FLOOR COVERINGS.
7. INFILL EXISTING CHASE OPENINGS AND/OR PENETRATIONS IN FLOORS,
CEILINGS, OR ROOF DECK. FIRE-RATING OF NEW CONSTRUCTION IS TO MATCH
EXISTING.
W E
RE
C
YC
LE
C
HE
C
KE
D B
Y:
D
ES
IG
NE
D B
Y:
AP
PR
O
VE
D B
Y:
BL
AC
K
W
HI
TE
TH
E
BA
R
BE
LO
W S
HO
W
S G
RA
YS
C
AL
E
FR
O M
W
HI
TE
T
O S
O
LID
TH
E
BA
R
BE
LO
W S
HO
W
S
PR
IM
AR
Y C
O
LO
RS
(866) 454-3923 | WWW.C2AE.COM
PROJ. #:
ISSUANCES
# DESCRIPTION DATE
COPYRIGHT C2AE.
NOT TO BE REPRODUCED OR DISTRIBUTED
WITHOUT PRIOR WRITTEN CONSENT.
ALL RIGHTS RESERVED.
PHASE
1/
/2
1:4
8:
P M
Au to de sk
D oc s:
Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/
EL
EM
A.
rv t
C he ck er
D es ig ne r
Ap pr ov er
FA
IR
P
LA
IN
E
AS
T
EL
EM
EN
TA
RY
S
C
HO
O L
U
NI
O N
AV
E, BE
NT
O N
HA
RB
O R, M I 4
A-100
230327
ISSUED FOR BIDDING
26JAN2024ISSUED FOR BIDDING
FL
O
O R
PL
A
N S
LO
W
ER
LE
V
EL
1/4" = 1'-0"
DEMOLITION FLOOR PLAN - LOWER LEVEL2 1/4" = 1'-0"
FLOOR PLAN - LOWER LEVEL
ARCHITECTURAL KEYNOTES
KEY
VALUE KEYNOTE TEXT
A21 MECHANICAL ROOF PENETRATION REFER TO MECH DRAWINGS. REFER TO
DETAILS ON DRAWING A-001 AND A-501 FOR MORE INFORMATION.
A22 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW FINISHES. PATCH AND REPAIR
AS REQUIRED FOR NEW FIBERGLASS SANDWICH PANEL ASSEMBLY.
A23 INFILL EXISTING MASONRY WALL WITH SAME MATERIALS WHERE MECH ITEMS:
VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.
A24 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW MECHANICAL WALL VENT.
PATCH AND REPAIR AS REQUIRED FOR NEW WORK.
A25 INFILL, CLEAN, PREP, PREPARE, EXISTING ROOFING SO AS TO MATCH ADJACENT
SURFACES AND MEMBRANES. PATCH AND REPAIR AS REQUIRED FOR NEW WORK.
A27 NEW VENT LOCATION FOR EXISTING WATER HEATER IN MECH RM (AND
CURRENTLY VENTING THROUGH STACK) TO BE RE ROUTED THROUGH EXISTING
ROOF. REFER TO MECHANICAL DRAWINGS FOR MORE DETAILS.
A28 PATCH AND REPAIR EXISTING WALLS WITH SAME MATERIALS WHERE ITEMS,
VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.
DEMOLITION KEYNOTES
KEY
VALUE KEYNOTE TEXT
D6 REMOVE CONCRETE PADS FOR MECHANICAL EQUIPMENT COMPLETELY. SAW
CUT AS REQUIRED TO REMOVE CONCRETE. REMOVE CONCRETE SLAB TO
PREPARE FOR NEW REINFORCED CONCRETE SLAB INFILL AND PROPER
DRAINAGE AS REQUIRED. REMOVE MECHANICAL STEEL SUPPORTS, COLUMNS,
DUNNAGE THAT IS NO LONGER BEING UTILIZED. PATCH AND REPAIR ADJACENT
SURFACES AT AREAS OF REMOVAL TO MATCH EXISTING AND/OR AS REQUIRED
FOR PROPER INSTALLATION OF NEW INFILL REINFORCED CONCRETE SLAB
FINISHES.
D8 CAREFULLY REMOVE EXTERIOR WALL WITHIN EXISTING WALL OPENING.
PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION
FOR PROPER INSTALLATION OF NEW WORK.
D9 CAREFULLY REMOVE EXTERIOR LOUVER WITHIN EXISTING WALL OPENING.
PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION
FOR PROPER INSTALLATION OF NEW WORK.
D10 CAREFULLY REMOVE EXTERIOR WINDOW WITHIN EXISTING WALL OPENING.
PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION
FOR PROPER INSTALLATION OF NEW WORK.
D11 CAREFULLY REMOVE PORTION OF EXISTING ROOFING SYSTEM FOR NEW ROOF
PENETRATION FOR NEW VENTING OF EXISTING WATER HEATER AS REQUIRED.
PATCH EXISTING AREAS AND PREPARE NEW AREAS FOR PROPER INSTALLATION
OF NEW VENTING.
C
A-501
NEW EXTERIOR INSULATED
TRANSLUCENT FIBERGLASS PANELS
TO BE INSTALLED WITHIN THE
EXISTING WALL OPENING WHERE
EXISTING INFILL WALLS WERE
REMOVED. TRIM FINISHES ARE TO
MATCH EXISTING MATERIALS.
A-501
A-501
A-501
SIM
INFILL EXISTING MASONRY WALL
INFILL EXISTING MASONRY
WALL. INFILL SIZE 24" X 24"
A23A23
A23A23 A24A24
1. CONTRACTORS ARE TO COORDINATE WORK WITH ALL OTHER TRADES.
2. CONFLICTS BETWEEN NOTES, DETAILS, SPECIFICATIONS, ETC., SHALL BE
VERIFIED WITH THE ARCHITECT OR THE MOST STRINGENT PROVISIONS SHALL
GOVERN.
3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME
NATURE AS SHOWN FOR SIMILAR CONDITIONS. ANY UNCLEAR CONDITIONS
SHALL BE VERIFIED WITH THE ARCHITECT PRIOR TO CONSTRUCTION OF THAT
AREA.
4. DRAWINGS ARE NOT TO BE SCALED. ANY UNCLEAR DIMENSIONS, OR
DIMENSIONAL DISCREPANCIES, SHALL BE VERIFIED WITH ARCHITECT.
5. ALL EXISTING CONDITIONS AND ALL RELATED DIMENSIONS INDICATED IN THE
CONTRACT DOCUMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION,
ERECTION, AND/OR CONSTRUCTION. ANY CONDITIONS THAT DIFFER FROM THAT
INDICATED IN THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE
ARCHITECT FOR REVIEW PRIOR TO FABRICATION, ERECTION, AND/OR
CONSTRUCTION.
6. CONTRACTOR TO REVIEW ENTIRE SET OF CONSTRUCTION DOCUMENTS,
INCLUDING SPECIFICATION, AND SHALL COORDINATE WORK BETWEEN ALL
TRADES. IF CONFLICTS ARISE DUE TO COORDINATION OF TRADES,
CONTRACTOR IS TO VERIFY CONFLICT WITH ARCHITECT PRIOR TO
CONSTRUCTION / INSTALLATION OF CONFLICTING ITEMS.
7. PATCH ALL EXPOSED INTERIOR AND EXTERIOR WALLS WHERE ATTACHED OR
IMBEDDED ITEMS WERE REMOVED.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATION OF FLOOR,
WALL, AND/OR CEILING SUBSTRATES FOR NEW FINISHES.
9. MAINTAIN FIRE RATING AT ALL ASSEMBLIES WHERE OPENINGS PENETRATIONS,
EMBEDMENT, RECESSED EQUIPMENT, ACCESSORIES, ETC. DISRUPT THE
CONTINUITY OF THE RATING
10. REMOVE ADHESIVE AND/OR MORTAR LEFT FROM THE REMOVAL OF EXISTING
FLOOR COVERING AND PREP FLOOR W/CONCRETE (OR FLORSTONE) AS
NECESSARY TO ACCOMMODATE NEW FLOOR COVERINGS.
11. ALL DIMENSIONS ARE FROM FACE OF WALL SHEATHING, C.M.U., OR CONCRETE,
U.N.O.
12. PROVIDE ISOLATION MATERIAL BETWEEN DISSIMILAR MATERIALS THAT ARE IN
CONTACT WITH ONE ANOTHER.
13. PATCH & REPAIR ALL MAJOR & MINOR BLEMISHES AS REQ'D, DUE TO
DEMOLITION WORK. REPAIRS ARE TO MATCH ADJACENT MATERIAL & COLOR.
14. PROVIDE SOLID, CONTINUOUS, NON COMBUSTIBLE BLOCKING AT LOCATIONS
WHERE MILLWORK, PLUMBING FIXTURES, EQUIPMENT, ACCESSORIES, OR ETC.
ATTACH TO WALLS OR CEILINGS.
GENERAL NOTES:
D10
D9
D8
D11 EXISTING WATER
HEATER LOCATION,
REFER TO NOTE D11.
DEMO PLAN LEGEND:
EXISTING WALL
OR PARTITION TO
REMAIN
EXISTING DOOR
TO REMAIN
EXISTING
BUILDING
COMPONENT &
STRUCTURE TO
REMAIN
EXISTING
WALL/PARTITION OR
EXISTING ITEMS TO
BE REMOVED
EXISTING DOOR &
FRAME TO BE
REMOVED
EXISTING ASSEMBLY
TO BE REMOVED
NOTE: ALL ITEMS SHOWN DARK AND DASHED ARE TO BE DEMOLISHED- U.N.O.
GENERAL DEMOLITION NOTES:
1. ALL EXISTING ITEMS TO BE RETAINED BY THE OWNER WILL BE REMOVED PRIOR
TO DEMOLITION. ANY ITEMS LEFT IN THE DEMOLITION AREA BECOME THE
PROPERTY OF THE DEMOLITION CONTRACTOR.
2. REFER TO ALL CONTRACT DOCUMENTS, INCLUDING SPECIFICATIONS, FOR
ADDITIONAL DEMOLITION NOTES AND INFORMATION.
3. SHORE AND BRACE ALL WORK REQUIRED TO REMAIN.
4. CONTRACTORS SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME
FAMILIAR WITH EXISTING CONDITIONS
5. CONTRACTORS ARE TO COORDINATE DEMOLITION WORK WITH OWNER PRIOR
TO START OF WORK.
6. U.N.O., PATCH AND PREPARE FLOOR W/ CONCRETE (OR FLORSTONE) TO FLUSH
WITH ADJACENT FLOOR SURFACE. FILL ANY SLOPING OR RECESSED AREAS TO
LEVEL WITH TYPICAL FINISH FLOOR ELEVATION TO ACCOMMODATE NEW
FLOOR COVERINGS.
7. INFILL EXISTING CHASE OPENINGS AND/OR PENETRATIONS IN FLOORS,
CEILINGS, OR ROOF DECK. FIRE-RATING OF NEW CONSTRUCTION IS TO MATCH
EXISTING.
W E
RE
C
YC
LE
C
HE
C
KE
D B
Y:
D
ES
IG
NE
D B
Y:
AP
PR
O
VE
D B
Y:
BL
AC
K
W
HI
TE
TH
E
BA
R
BE
LO
W S
HO
W
S G
RA
YS
C
AL
E
FR
O M
W
HI
TE
T
O S
O
LID
TH
E
BA
R
BE
LO
W S
HO
W
S
PR
IM
AR
Y C
O
LO
RS
(866) 454-3923 | WWW.C2AE.COM
PROJ. #:
ISSUANCES
# DESCRIPTION DATE
COPYRIGHT C2AE.
NOT TO BE REPRODUCED OR DISTRIBUTED
WITHOUT PRIOR WRITTEN CONSENT.
ALL RIGHTS RESERVED.
PHASE
1/
/2
1:4
7:
P M
Au to de sk
D oc s:
Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/
EL
EM
A.
rv t
C he ck er
D es ig ne r
Ap pr ov er
FA
IR
P
LA
IN
E
AS
T
EL
EM
EN
TA
RY
S
C
HO
O L
U
NI
O N
AV
E, BE
NT
O N
HA
RB
O R, M I 4
A-101
230327
ISSUED FOR BIDDING
26JAN2024ISSUED FOR BIDDING
FL
O
O R
PL
A
N S
FI
RS
T
LE
V
EL
1/4" = 1'-0"
FLOOR PLAN - FIRST LEVEL
1/4" = 1'-0"
DEMOLITION FLOOR PLAN - FIRST LEVEL2
ARCHITECTURAL KEYNOTES
KEY
VALUE KEYNOTE TEXT
A21 MECHANICAL ROOF PENETRATION REFER TO MECH DRAWINGS. REFER TO
DETAILS ON DRAWING A-001 AND A-501 FOR MORE INFORMATION.
A22 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW FINISHES. PATCH AND REPAIR
AS REQUIRED FOR NEW FIBERGLASS SANDWICH PANEL ASSEMBLY.
A23 INFILL EXISTING MASONRY WALL WITH SAME MATERIALS WHERE MECH ITEMS:
VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.
A24 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW MECHANICAL WALL VENT.
PATCH AND REPAIR AS REQUIRED FOR NEW WORK.
A25 INFILL, CLEAN, PREP, PREPARE, EXISTING ROOFING SO AS TO MATCH ADJACENT
SURFACES AND MEMBRANES. PATCH AND REPAIR AS REQUIRED FOR NEW WORK.
A27 NEW VENT LOCATION FOR EXISTING WATER HEATER IN MECH RM (AND
CURRENTLY VENTING THROUGH STACK) TO BE RE ROUTED THROUGH EXISTING
ROOF. REFER TO MECHANICAL DRAWINGS FOR MORE DETAILS.
A28 PATCH AND REPAIR EXISTING WALLS WITH SAME MATERIALS WHERE ITEMS,
VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.
DEMOLITION KEYNOTES
KEY
VALUE KEYNOTE TEXT
D6 REMOVE CONCRETE PADS FOR MECHANICAL EQUIPMENT COMPLETELY. SAW
CUT AS REQUIRED TO REMOVE CONCRETE. REMOVE CONCRETE SLAB TO
PREPARE FOR NEW REINFORCED CONCRETE SLAB INFILL AND PROPER
DRAINAGE AS REQUIRED. REMOVE MECHANICAL STEEL SUPPORTS, COLUMNS,
DUNNAGE THAT IS NO LONGER BEING UTILIZED. PATCH AND REPAIR ADJACENT
SURFACES AT AREAS OF REMOVAL TO MATCH EXISTING AND/OR AS REQUIRED
FOR PROPER INSTALLATION OF NEW INFILL REINFORCED CONCRETE SLAB
FINISHES.
D8 CAREFULLY REMOVE EXTERIOR WALL WITHIN EXISTING WALL OPENING.
PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION
FOR PROPER INSTALLATION OF NEW WORK.
D9 CAREFULLY REMOVE EXTERIOR LOUVER WITHIN EXISTING WALL OPENING.
PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION
FOR PROPER INSTALLATION OF NEW WORK.
D10 CAREFULLY REMOVE EXTERIOR WINDOW WITHIN EXISTING WALL OPENING.
PREPARE ADJACENT WALL SURFACES AT AREAS OF REMOVAL IN PREPARATION
FOR PROPER INSTALLATION OF NEW WORK.
D11 CAREFULLY REMOVE PORTION OF EXISTING ROOFING SYSTEM FOR NEW ROOF
PENETRATION FOR NEW VENTING OF EXISTING WATER HEATER AS REQUIRED.
PATCH EXISTING AREAS AND PREPARE NEW AREAS FOR PROPER INSTALLATION
OF NEW VENTING.
A-501 A21A21
A21A21
A21A21
A21A21
A-102 2 Sim
A22
A22
A27A27
A25A25
A25A25
A25A25
A25A25
A25A25
1. CONTRACTORS ARE TO COORDINATE WORK WITH ALL OTHER TRADES.
2. CONFLICTS BETWEEN NOTES, DETAILS, SPECIFICATIONS, ETC., SHALL BE
VERIFIED WITH THE ARCHITECT OR THE MOST STRINGENT PROVISIONS SHALL
GOVERN.
3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME
NATURE AS SHOWN FOR SIMILAR CONDITIONS. ANY UNCLEAR CONDITIONS
SHALL BE VERIFIED WITH THE ARCHITECT PRIOR TO CONSTRUCTION OF THAT
AREA.
4. DRAWINGS ARE NOT TO BE SCALED. ANY UNCLEAR DIMENSIONS, OR
DIMENSIONAL DISCREPANCIES, SHALL BE VERIFIED WITH ARCHITECT.
5. ALL EXISTING CONDITIONS AND ALL RELATED DIMENSIONS INDICATED IN THE
CONTRACT DOCUMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION,
ERECTION, AND/OR CONSTRUCTION. ANY CONDITIONS THAT DIFFER FROM THAT
INDICATED IN THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE
ARCHITECT FOR REVIEW PRIOR TO FABRICATION, ERECTION, AND/OR
CONSTRUCTION.
6. CONTRACTOR TO REVIEW ENTIRE SET OF CONSTRUCTION DOCUMENTS,
INCLUDING SPECIFICATION, AND SHALL COORDINATE WORK BETWEEN ALL
TRADES. IF CONFLICTS ARISE DUE TO COORDINATION OF TRADES,
CONTRACTOR IS TO VERIFY CONFLICT WITH ARCHITECT PRIOR TO
CONSTRUCTION / INSTALLATION OF CONFLICTING ITEMS.
7. PATCH ALL EXPOSED INTERIOR AND EXTERIOR WALLS WHERE ATTACHED OR
IMBEDDED ITEMS WERE REMOVED.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATION OF FLOOR,
WALL, AND/OR CEILING SUBSTRATES FOR NEW FINISHES.
9. MAINTAIN FIRE RATING AT ALL ASSEMBLIES WHERE OPENINGS PENETRATIONS,
EMBEDMENT, RECESSED EQUIPMENT, ACCESSORIES, ETC. DISRUPT THE
CONTINUITY OF THE RATING
10. REMOVE ADHESIVE AND/OR MORTAR LEFT FROM THE REMOVAL OF EXISTING
FLOOR COVERING AND PREP FLOOR W/CONCRETE (OR FLORSTONE) AS
NECESSARY TO ACCOMMODATE NEW FLOOR COVERINGS.
11. ALL DIMENSIONS ARE FROM FACE OF WALL SHEATHING, C.M.U., OR CONCRETE,
U.N.O.
12. PROVIDE ISOLATION MATERIAL BETWEEN DISSIMILAR MATERIALS THAT ARE IN
CONTACT WITH ONE ANOTHER.
13. PATCH & REPAIR ALL MAJOR & MINOR BLEMISHES AS REQ'D, DUE TO
DEMOLITION WORK. REPAIRS ARE TO MATCH ADJACENT MATERIAL & COLOR.
14. PROVIDE SOLID, CONTINUOUS, NON COMBUSTIBLE BLOCKING AT LOCATIONS
WHERE MILLWORK, PLUMBING FIXTURES, EQUIPMENT, ACCESSORIES, OR ETC.
ATTACH TO WALLS OR CEILINGS.
GENERAL NOTES:
A-501
1"
1" / 12"1" / 12" 1"
NEW ROOF ON EXISTING
CHIMNEY STACK
ROOF LEGEND
DENOTES REINF. MEMBRANE WALKWAY MATS -
SEE SPECIFICATIONS.
TAPERED INSULATION - ARROW INDICATES
DIRECTION OF SLOPE.
DENOTES MECHANICAL UNIT - SEE HVAC PLANS
DENOTES AREA OF 1-HOUR FIRE RESISTIVE ROOF
ASSEMBLY
DENOTES EXHAUST FAN OR RELIEF VENT, SEE
MECHANICAL PLANS FOR SPECIFICATIONS.
EFFECTIVE DIRECTION OF ROOF SLOPE DUE TO
STRUCTURE
RD = ROOF DRAIN
OD = OVERFLOW DRAIN
CONDENSING UNIT
EXISTING ROOF
1. ALL NEW ROOF WORK THAT INTERACTS WITH EXISTING ROOFING TO REMAIN, IS
TO BE EXECUTED AS REQUIRED TO MAINTAIN EXISTING ROOFING WARRANTIES.
2. ALL NEW VENT PIPES ARE TO EXTEND A MINIMUM 12" ABOVE FINISHED ROOF.
3. AT AREAS OF RE-ROOF, CONTACTOR TO EXTEND EXISTING VENT PIPES TO A
MINIMUM OF 12" ABOVE FINISHED ROOF.
4. ALL NEW EQUIPMENT CURBS ARE TO EXTEND A MINIMUM OF 12" ABOVE
FINISHED ROOF.
5. AT AREAS OF RE-ROOF, CONTACTOR TO EXTEND ALL EXISTING EQUIPMENT
CURBS TO REMAIN TO A MINIMUM 12" ABOVE FINISHED ROOF.
6. CONTRACTOR TO INSTALL ROOF WALKWAY PADS AT PERIMETER OF ALL
SERVICABLE EQUIPMENT, AND ALONG WALKING PATH BETWEEN ALL ROOF
HATCHES, LADDERS, AND EQUIPMENT.
ROOF GENERAL NOTES:
W E
RE
C
YC
LE
C
HE
C
KE
D B
Y:
D
ES
IG
NE
D B
Y:
AP
PR
O
VE
D B
Y:
BL
AC
K
W
HI
TE
TH
E
BA
R
BE
LO
W S
HO
W
S G
RA
YS
C
AL
E
FR
O M
W
HI
TE
T
O S
O
LID
TH
E
BA
R
BE
LO
W S
HO
W
S
PR
IM
AR
Y C
O
LO
RS
(866) 454-3923 | WWW.C2AE.COM
PROJ. #:
ISSUANCES
# DESCRIPTION DATE
COPYRIGHT C2AE.
NOT TO BE REPRODUCED OR DISTRIBUTED
WITHOUT PRIOR WRITTEN CONSENT.
ALL RIGHTS RESERVED.
PHASE
1/
/2
1:4
6:
P M
Au to de sk
D oc s:
Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/
EL
EM
A.
rv t
C he ck er
D es ig ne r
Ap pr ov er
FA
IR
P
LA
IN
E
AS
T
EL
EM
EN
TA
RY
S
C
HO
O L
U
NI
O N
AV
E, BE
NT
O N
HA
RB
O R, M I 4
A-102
230327
ISSUED FOR BIDDING
26JAN2024ISSUED FOR BIDDING
FL
O
O R
PL
A
N S
SE
C O
N D
LE
V
EL
R
O O
F
1/4" = 1'-0"
FLOOR PLAN - ROOF LEVEL
ARCHITECTURAL KEYNOTES
KEY
VALUE KEYNOTE TEXT
A21 MECHANICAL ROOF PENETRATION REFER TO MECH DRAWINGS. REFER TO
DETAILS ON DRAWING A-001 AND A-501 FOR MORE INFORMATION.
A22 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW FINISHES. PATCH AND REPAIR
AS REQUIRED FOR NEW FIBERGLASS SANDWICH PANEL ASSEMBLY.
A23 INFILL EXISTING MASONRY WALL WITH SAME MATERIALS WHERE MECH ITEMS:
VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.
A24 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW MECHANICAL WALL VENT.
PATCH AND REPAIR AS REQUIRED FOR NEW WORK.
A25 INFILL, CLEAN, PREP, PREPARE, EXISTING ROOFING SO AS TO MATCH ADJACENT
SURFACES AND MEMBRANES. PATCH AND REPAIR AS REQUIRED FOR NEW WORK.
A27 NEW VENT LOCATION FOR EXISTING WATER HEATER IN MECH RM (AND
CURRENTLY VENTING THROUGH STACK) TO BE RE ROUTED THROUGH EXISTING
ROOF. REFER TO MECHANICAL DRAWINGS FOR MORE DETAILS.
A28 PATCH AND REPAIR EXISTING WALLS WITH SAME MATERIALS WHERE ITEMS,
VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.
1/4" = 1'-0"A-102
PLAN DETAIL - T.O. ROOF STACK NEW CAP2
SEALANT
EXTERIOR INTERIOR
FLASHING WITH END DAM
INDICATIVE PROFILE OF EXISTING
MASONRY WALL - VIF
ADHESIVE MEMBRANE AIR & MOISTURE BARRIER
FLASHING WRAP INTO ROUGH OPENINGS UNDER
METAL FLASHING - TYP
FLASHING
TRANSLUCENT WALL PANEL
1 9/16" PANEL
VIF
ADHESIVE MEMBRANE AIR & MOISTURE BARRIER
FLASHING WRAP INTO ROUGH OPENINGS UNDER
METAL FLASHING - TYP
EXISTING MASONRY WALL - VIF
NOTE: TRANSLUCENT WALL PANEL TO BE POSITIONED
TOWARDS THE EXTERIOR FACE OF EXISTING WALL
1 5/8"
CURING BUTYL
FLEXIBLE FLASHING, WRAP PERIMETER OF OPENING
INDICATIVE PROFILE OF EXISTING
MASONRY WALL - VIF
TRANSLUCENT WALL PANEL
EXTERIOR
INTERIOR
SEALANT
1 9 /16
" P
AN
EL
EXISTING MASONRY WALL
METAL FLASHING SILL WITH END DAM
5/
8"
FLASHING END DAM BELOW
SPLICING CEMENT
ROOF DECK
PIPE PENETRATION
SEALANT
STAINLESS STEEL
HOSE CLAMP
PIPE BOOT FLASHING
INSULATION SECURELY
FASTENED
8" M
IN
RISER CLAMP NOTE:
SEE MECHANICAL DRAWINGS
FOR VENT LOCATIONS, SIZES, AND
FOR ADDITIONAL REQUIREMENTS
ROOF DECK
(SEE ROOF PLAN)
RIGID INSULATION
COVER BOARD (IF REQUIRED TO MATCH
EXISTING ROOFING SYSTEM)
WATERTIGHT UMBRELLA
GALVANIZED OR PRE-FAB.
ALUMINUM
MEMBRANE
FLASHING
ROOFING SYSTEM
FLUE
PIPE
RAIN CAP
CLAMP
CAP MEMBRANE FLASHING
FRTW BLOCKING TO MATCH
INSULATION THICKNESS AND
ANCHORED TO DECK
MEMBRANE ROOFING SYSTEM
PIPE STRAP
1" AIR SPACE AT BOTH SIDES
CONTINUOUS ELASTOMERIC SEALANT
CONTINUOUS FLASHING CEMENT
" M
IN
NOTE:
SEE MECHANICAL DRAWINGS
FOR VENT LOCATIONS, SIZES, AND
FOR ADDITIONAL REQUIREMENTS
METAL FLASHING AT EDGE OF FRTW BLOCKING
ROOF DECK
(SEE ROOF PLAN)
CAP MEMBRANE
FLASHING
FLASHING CEMENT
MEMBRANE ROOFING
SYSTEM
VENT
PIPE
" M
IN
TREATED WOOD
BLOCKING TO MATCH
INSULATION
THICKNESS AND
ANCHORED TO DECK
RIGID INSULATION
COVER BOARD
MEMBRANE ROOFING
SYSTEM
WATERTIGHT UMBRELLA
GALVANIZED OR ALUMINUM
CLAMP
CONTINUOUS SEALANT
RISER CLAMP
NOTE:
SEE MECHANICAL DRAWINGS
FOR VENT LOCATIONS, SIZES, AND
FOR ADDITIONAL REQUIREMENTS
04.0 130' - 0"
04.0 130' - 0"
04.0 130' - 0"
04.0 130' - 0"
1" / 12" -TYP
2x6 FRTW BLOCKING
3/4" FRTW SHEATHING
ALUMINUM DRIP EDGE WITH SEALANT
CFMF
SIMPSON STRONG TIE, MTSM16, STAINLESS
STEEL (316) AT 48" MAX
EXISTING MASONRY WALL - VIF
MASONRY FASTENERS. 2 AT EACH OF 4
SIDES MIN, AT 48" MAX
(VIF DATUM)
DRIP EDGE
1" / 12" -TYP
VAPOR RETARDER
3/4" FRTW SHEATHING
ADHERED SEALANT TAPE / CAPILLARY BREAK AT CFMF TO
WOOD CONNECTION - TYP
ROOFING MEMBRANE OVER TAPERED RIGID INSULATION
ALUMINUM FASCIA WITH DRIP EDGE TO BE TUCKED
UNDER THE ALUMINUM ROOF DRIP EDGE
ADHERED SEALANT TAPE / CAPILLARY BREAK AT CFMF TO
WOOD CONNECTION - TYP
EXISTING MASONRY WALL. PREP, PATCH, REPAIR,
REPOINT AS REQUIRED FOR NEW WORK - TYP
01.0 100' - 0"
02.0 108' - 4"
03.0 120' - 0"
04.0 130' - 0"
01.0 100' - 0"
02.0 108' - 4"
03.0 120' - 0"
01.0 100' - 0"
02.0 110' - 0"
03.0 120' - 0"
04.0 130' - 0"
01.0 100' - 0"
02.0 110' - 0"
03.0 120' - 0"
04.0 130' - 0"
01.0 100' - 0"
02.0 110' - 0"
03.0 120' - 0"
04.0 130' - 0"
A-501
VIF
10' - 4"
VI
F
5'
- 8
NEW EXTERIOR INSULATED
TRANSLUCENT FIBERGLASS PANELS
TO BE INSTALLED WITHIN THE
EXISTING WALL OPENING. TRIM
FINISHES ARE TO MATCH EXISTING
MATERIALS.
A-501
A27A27
A21A21 A21A21 A21A21 A21A21
W E
RE
C
YC
LE
C
HE
C
KE
D B
Y:
D
ES
IG
NE
D B
Y:
AP
PR
O
VE
D B
Y:
BL
AC
K
W
HI
TE
TH
E
BA
R
BE
LO
W S
HO
W
S G
RA
YS
C
AL
E
FR
O M
W
HI
TE
T
O S
O
LID
TH
E
BA
R
BE
LO
W S
HO
W
S
PR
IM
AR
Y C
O
LO
RS
(866) 454-3923 | WWW.C2AE.COM
PROJ. #:
ISSUANCES
# DESCRIPTION DATE
COPYRIGHT C2AE.
NOT TO BE REPRODUCED OR DISTRIBUTED
WITHOUT PRIOR WRITTEN CONSENT.
ALL RIGHTS RESERVED.
PHASE
1/
/2
4:
:5
PM
Au to de sk
D oc s:
Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/
EL
EM
A.
rv t
C he ck er
D es ig ne r
Ap pr ov er
FA
IR
P
LA
IN
E
AS
T
EL
EM
EN
TA
RY
S
C
HO
O L
U
NI
O N
AV
E, BE
NT
O N
HA
RB
O R, M I 4
A-501
230327
ISSUED FOR BIDDING
26JAN2024ISSUED FOR BIDDING
D
ET
A
IL
S
1 1/2" = 1'-0"
EXISTING EXTERIOR WALL - SECTION DETAIL - TRANSLUCENT WALL PANEL1
1 1/2" = 1'-0"
EXISTING EXTERIOR WALL - PLAN DETAIL - TRANSLUCENT WALL PANEL JAMB2
1 1/2" = 1'-0"
ROOF PENETRATION AT TAPERED CONE4
1 1/2" = 1'-0"
ROOF PENETRATION AT METAL FLUE5
1 1/2" = 1'-0"
ROOF PENETRATION AT METAL FLASHING33/4" = 1'-0"
SECTION DETAIL - T.O. ROOF STACK NEW CAP6
1/8" = 1'-0"
EXTERIOR ELEVATION - SOUTH7
ARCHITECTURAL KEYNOTES
KEY
VALUE KEYNOTE TEXT
A21 MECHANICAL ROOF PENETRATION REFER TO MECH DRAWINGS. REFER TO
DETAILS ON DRAWING A-001 AND A-501 FOR MORE INFORMATION.
A22 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW FINISHES. PATCH AND REPAIR
AS REQUIRED FOR NEW FIBERGLASS SANDWICH PANEL ASSEMBLY.
A23 INFILL EXISTING MASONRY WALL WITH SAME MATERIALS WHERE MECH ITEMS:
VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.
A24 CLEAN, PREP, PREPARE, WALL OPENING FOR NEW MECHANICAL WALL VENT.
PATCH AND REPAIR AS REQUIRED FOR NEW WORK.
A25 INFILL, CLEAN, PREP, PREPARE, EXISTING ROOFING SO AS TO MATCH ADJACENT
SURFACES AND MEMBRANES. PATCH AND REPAIR AS REQUIRED FOR NEW WORK.
A27 NEW VENT LOCATION FOR EXISTING WATER HEATER IN MECH RM (AND
CURRENTLY VENTING THROUGH STACK) TO BE RE ROUTED THROUGH EXISTING
ROOF. REFER TO MECHANICAL DRAWINGS FOR MORE DETAILS.
A28 PATCH AND REPAIR EXISTING WALLS WITH SAME MATERIALS WHERE ITEMS,
VENTS, DUCTS, FIXTURES, FITTINGS OR OTHER ITEMS WERE REMOVED.
HIGH PRESSURE STEAMHPS
DESCRIPTIONSYMBOL
MECHANICAL ABBREVIATIONS & SYMBOLS LEGEND
MEDIUM PRESSURE STEAMMPS
LOW PRESSURE STEAMLPS
HIGH PRESSURE STEAM CONDENSATEHPC
MEDIUM PRESSURE STEAM CONDENSATEMPC
LOW PRESSURE STEAM CONDENSATELPC
BOILER BLOWDOWNBBD
PUMPED CONDENSATEPC
VACUUM PUMP DISCHARGEVPD
MAKE-UP WATERMU
ATMOSPHERIC VENTATV
FUEL OILFO
HEATING HOT WATER SUPPLYHHWS
HEATING HOT WATER RETURNHHWR
COMPRESSED AIRCA
VACUUM (AIR)VAC
EXISTINGEX-
DEMOLITION PIPING
LIQUID LINE (REFRIGERANT)LL
SUCTION LINE (REFRIGERANT)SL
BRINE SUPPLYBS
BRINE RETURNBR
CONDENSER WATER SUPPLYCWS
CONDENSER WATER RETURNCWR
CHILLED WATER SUPPLYCHWS
CHILLED WATER RETURNCHWR
FILL LINEFILL
HUMIDIFICATION LINEH
DRAIND
DISCHARGE LINE (REFRIGERANT)DL
HEAT PUMP WATER SUPPLYHPWS
HEAT PUMP WATER RETURNHPWR
PIPING
COILS
COOLING COIL
HEATING COIL
ELECTRIC COIL
HUMIDIFIER
VALVES
AIR LINE
BALL VALVE
BUTTERFLY VALVE
DIAPHRAGM VALVE
GATE VALVE
GATE VALVE (ANGLE)
PLUG VALVE
THREE WAY VALVE
VALVE ACTUATORS
LEVER
NON-RISING STEM
OUTSIDE STEM & YOKE
GEARG
PNUEMATIC MOTOR ACTUATORM
ELECTRIC MOTOR ACTUATORM
ELECTRIC SOLENOID ACTUATOR
CHECK VALVE
PRESSURE REGULATING VALVE
RELIEF VALVE
PIPE FITTINGS
TRANSITION
CAP
ELBOW
ELBOW UP
ELBOW DOWN
TEE
TEE UP
TEE DOWN
UNION
DESCRIPTIONSYMBOL
EXPANSION LOOP
FLEXIBLE CONNECTOR
ORIFICE FLOWMETER
VENTURI FLOWMETER
FLOW SWITCHFS
HANGER RODH
PRESSURE SWITCHPS
PRESSURE GAGE
PUMP
STRAINER
THERMOMETER
EQUIPMENT
CENTRIFUGAL FAN
PROPELLER FAN
INTAKE ROOF VENTILATOR
EXHAUST ROOF VENTILATOR
LOUVERED ROOF VENTILATOR
VANEAXIAL FAN
VARIABLE AIR VOLUME BOX
DUCTWORK
RECTANGULAR DUCTWORK12"x12" SA
ROUND DUCTWORK12"Ø SA
MITERED RECTANGULAR ELBOW
MITERED RECTANGULAR ELBOW WITH TURNING VANES
RADIUS RECTANGULAR OR ROUND ELBOW
RECTANGULAR DUCTWORK UP
RECTANGULAR DUCTWORK DOWN
ROUND DUCTWORK UP
ROUND DUCTWORK DOWN
SUPPLY AIR DUCTWORKSA
RETURN AIR DUCTWORKRA
EXHAUST AIR DUCTWORKEA
OUTSIDE AIR DUCTWORKOA
FLEXIBLE DUCTWORK CONNECTOR
LINED DUCTWORK
INSULATED DUCTWORK
FLEXIBLE DUCTWORK
TRANSITION
DAMPERS
BALANCING DAMPER
FIRE DAMPER
SMOKE DAMPER
DRG
SUPPLY AIR CEILING DIFFUSER
RETURN AIR CEILING GRILLE
EXHAUST AIR CEILING GRILLE
SIDEWALL SUPPLY GRILLE
SIDEWALL RETURN / EXHAUST GRILLE
LINEAR DIFFUSER
CONTROLS
THERMOSTATT
PRESSURE SENSORP
OXYGEN SENSORO2
CARBON DIOXIDE SENSORCO2
CARBON MONOXIDE SENSORCO
PIPE SPECIALTIES
AUTOMATIC AIR VENT
MANUAL AIR VENT
PIPE GUIDE
PIPE ANCHOR
MAIN PIPE ANCHOR
BALL JOINT
EXPANSION JOINT
AIR CHANGES PER HOURACH
DESCRIPTIONABBREVIATION
ALTERNATING CURRENTAC
ASBESTOS CONTAINING MATERIALSACM
AIR CONDITIONING UNITACU
ASSOCIATION OF ENERGY ENGINEERSAEE
ADJUSTABLE FREQUENCY DRIVEAFD
ABOVE FINISHED FLOORAFF
ADJUSTABLEADJ
ANNUAL FUEL EFFICIENCY RATIOAFUE
AIR HANDLING UNITAHU
ANALOG INPUTAI
ANALOG OUTPUTAO
AMERICAN SOCIETY OF HEATING REFRIGERATION AND AIR
CONDITIONING ENGINEERSASHRAE
AMERICAN SOCIETY OF MECHANICAL ENGINEERSASME
AVERAGE WATER TEMPERATUREAWT
BOILERB
BUILDING AUTOMATION SYSTEMBAS
BUILDING COMMISSIONING ASSOCIATIONBCA
BLOWER COIL UNITBCU
BRAKE HORSEPOWERBHP
BINARY INPUTBI
BINARY OUTPUTBO
BACK DRAFT DAMPERBDD
BILL OF MATERIALSBOM
BRITISH THERMAL UNITBTU
BRITISH THERMAL UNIT PER HOURBTUH
CONSTANT AIR VOLUMECAV
CONDENSATE DRAINCD
COOLING DEGREE DAYSCDD
CERTIFIED ENERGY MANAGERCEM
CHLORO-FLUORO-CARBONCFC
CUBIC FEET PER MINUTECFM
CHILLERCH
CHILLED WATERCHW
CHILLED WATER RETURNCHWR
CHILLED WATER SUPPLYCHWS
CHILLED WATER SYSTEM PUMPCHWP
COOLING LOAD FACTORCLF
COOLING LOAD TEMPERATURE DIFFERENCECLTD
COEFFICIENT OF PERFORMANCECOP
COMPUTER ROOM AIR CONDITIONERCRAC
COOLING TOWERCT
CONSTANT VOLUMECV
CONDENSER WATER PUMPCWP
CONDENSER WATER RETURNCWR
CONDENSER WATER SUPPLYCWS
CONDENSING UNITCU
CABINET UNIT HEATERCUH
DISCHARGE AIRDA
DRY BULBDB
DIRECT CURRENTDC
DEMAND CONTROLLED VENTILATIONDCV
DEGREE DAYDD
DIRECT DIGITAL CONTROLDDC
DISCHARGE LINE - REFRIGERANTDL
DIGITAL INPUTDI
DIGITAL OUTPUTDO
DIFFERENTIAL PRESSUREDP
DIRECT EXPANSIONDX
ENTERING AIR TEMPERATUREEAT
ELECTRONICALLY COMMUTATED MOTORECM
ENERGY EFFICIENCY RATIOEER
EXHAUST FANEF
EXHAUST GRILLEEG
EXHAUST HOODEH
ELEVATIONEL
ENERGY MANAGEMENT SYSTEMEMS
DESCRIPTIONABBREVIATION
EXTERNAL STATIC PRESSUREESP
EXPANSION TANKET
ENTERING WATER TEMPERATUREEWT
EXISTINGEX
FAHRENHEITF
ELECTRIC UNIT HEATEREUH
FAN COIL UNITFCU
FULL LOAD AMPERAGEFLA
FEET PER MINUTEFPM
FLOW SWITCHFS
FINNED TUBE RADIATORSFTR
GASOLINEG
GAUGEGA
GALLONS PER MINUTEGPM
GAS PRESSURE REGULATORGPR
GRAPHICAL UNIT INTERFACEGUI
HEAD PRESSUREHD
HYDRONIC CEILING CASSETTEHCC
HEATING DEGREE DAYSHDD
HIGH EFFICIENCY PARTICULATE ARRESTANCEHEPA
HFC
HEATING HOT WATERHHW
HEATING HOT WATER PUMPHHWP
HIGH LIMITHL
HEAT PUMP UNITHPU
HORSEPOWERHP
HEAT PUMP RETURNHPR
HEAT RECOVERY UNITHRU
HEATING, VENTILATION, & AIR CONDITIONINGHVAC
HEAT EXCHANGERHX
HERTZ (FREQUENCY)HZ
INTAKE AIRIA
INDOOR AIR QUALITYIAQ
INTERNATIONAL MECHANICAL CODEIMC
INCHESIN
INCHES OF WATER COLUMN PRESSUREIN-WC
INFRA-REDIR
INLINE FANIF
INTAKE HOODIH
INDOOR UNITIU
KILOWATTSkW
KILOWATT HOURSkWh
LEAVING AIR TEMPERATURELAT
LINEAR FEETLF
LATENT HEATLH
LIQUID LINE - REFRIGERANTLL
LEAST MEAN TEMPERATURE DIFFERENCELMTD
LOW PRESSURELP
LIQUID PROPANE (GAS)LPG
LOW PRESSURE STEAM CONDENSATE RETURNLPC
LOW PRESSURE STEAM SUPPLYLPS
LOCKED ROTOR AMPERAGELRA
LEAVING WATER TEMPERATURELWT
MIXED AIRMA
MAT
MAKE-UP AIR UNITMAU
THOUSAND BTUHMBH
EXHAUST AIREA
FEETFT
FOOT OF HEAD PRESSUREFT-HD
HYDRO-CHLORO-FLUORO-CARBONHCFC
HOODH
HYDRO-FLUORO-CARBON
HEATING HOT WATER RETURNHHWR
HEATING HOT WATER SUPPLYHHWS
HEAT PUMP SUPPLYHPS
HEAT RECOVERY VENTILATORHRV
MIXED AIR TEMPERATURE
MANUFACTURERMFR
MOTOR HORSEPOWERMHP
DESCRIPTIONABBREVIATION
MICHIGAN MECHANICAL CODEMMC
MAXIMUM OVERCURRENT PROTECTIONMOCP
MEDIUM PRESSURE STEAM SUPPLYMPS
MANUFACTURER'S RECOMMENDATIONS
MULTI-ZONEMZ
MEDIUM PRESSURE STEAM CONDENSATE RETURNMPC
NOT APPLICABLENA
NORMALLY CLOSEDNC
NORMALLY OPENNO
NET POSITIVE SUCTION HEADNPSH
OUTDOOR AIR PERCENTAGEOAP
OUTDOOR AIR TEMPERATUREOAT
OUNCEOZ
PUMPP
PRESSURE DROPPD
PRE-HEATPH
PACKAGED TERMINAL AIR CONDITIONERPTAC
PRESSURE RELIEF VALVEPRV
RETURN AIRRA
RETURN FANRF
RG
RELATIVE HUMIDITYRH
RE-HEATRHT
ROOFTOP UNITRTU
SUPPLY AIRSA
SUPPLY DIFFUSERSD
SUPPLY FANSF
SUPPLY GRILLESG
SENSIBLE HEATSH
SENSIBLE HEAT RATIOSHR
SHEET METAL AND AIR CONDITIONING CONTRACTORS
NATIONAL ASSOCIATIONSMACNA
STATIC PRESSURESP
NOT TO SCALENTS
OUTDOOR AIROA
POUNDS PER SQUARE INCHPSI
PROPORTIONAL-INTEGRAL-DERIVATIVEPID
RETURN GRILLE
RUNNING LOAD AMPERAGERLA
REVOLUTIONS PER MINUTERPM
SEASONAL ENERGY EFFICIENCY RATIOSEER
MR
RETURN AIR TEMPERATURERAT
SUPPLY AIR TEMPERATURESAT
SHADING COEFFICIENTSC
SEQUENCE OF OPERATIONSOO
TEMPERATURET
THERMOSTATTSTAT
TEST AND BALANCETAB
TEMPERATURE DIFFERENTIALTD
TIME OF DAYTOD
TONS OF REFRIGERATION (1 TON = 12,000 BTU)TONS
TOTAL STATIC PRESSURETSP
TERMINAL UNITTU
THERMOSTATIC EXPANSION VALVETXV
TYPICALTYP
UNIT HEATERUH
UNLESS NOTED OTHERWISEUNO
UNIT VENTILATORUV
VARIABLE AIR VOLUME BOXVAV
VOLUME DAMPERVD
VARIABLE FREQUENCY DRIVEVFD
VARIABLE REFRIGERANT FLOWVRF
VARIABLE SPEED DRIVEVSD
VERTICAL UNIT VENTILATORVUV
WET BULBWB
WATER COLUMNWC
DIFFUSERS, REGISTERS, & GRILLESDRG
MINIMUM CIRCUIT AMPACITYMCA
SUCTION LINE - REFRIGERANTSL
AAV
S TEMPERATURE SENSOR
W E
RE
C
YC
LE
C
HE
C
KE
D B Y:
D
ES
IG
N
ED
B Y:
AP
PR
O
VE
D B Y:
BL
AC
K
W
HI
TE
TH
E
BA
R
BE
LO
W S
HO
W S
G
RA
YS
C
AL
E
FR
O M W
HI
TE
T O S O
LID
TH
E
BA
R
BE
LO
W S
HO
W S
PR
IM
AR
Y C O
LO
RS
(866) 454-3923 | WWW.C2AE.COM
PROJ. #:
ISSUANCES
#DESCRIPTION DATE
COPYRIGHT C2AE.
NOT TO BE REPRODUCED OR DISTRIBUTED
WITHOUT PRIOR WRITTEN CONSENT.
ALL RIGHTS RESERVED.
PHASE
1/ /2 2:
:5
PM
Au to de sk D oc s:
Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/
EL
EM
M .rv t
EJ
R
D
TD
D
TD
BO
ILE
R
RE
PL
AC
EM
EN
T
FO
R
FA
IR
P
LA
IN
E
AS
T
EL
EM
EN
TA
RY
U
NI
O N
AV
EN
UE
, B
EN
TO
N
HA
RB
O R, M
IC
HI
G
AN
M-001
23-0327
ISSUED FOR BIDDING
26JAN2024ISSUED FOR BIDDING
M
EC
H A N
IC
A L L
EG
EN
D S
EX-WS
EX-6" SS
EX-3" DCW
EX-2" HHWS
EX-2" HHWR
EX-6" SS
EX
-1
1/ 2"
D
HW
EX-1 1/2" DCW EX-DWH
EX-P
EX-HX
EX-CR
REMOVE ABANDONED
STORAGE TANK,
SUPPORTS, AND
ANCILLARIES IT ITS
ENTIRETY.
TO REMAIN
REFER TO ARCH
SHEET FOR
WINDOW AND
LOUVER
DEMOLITION
EX-24"x48" SA
EX
-1
0" ø
E A
EX-6" SS
D1D1
DEMOLISH
EXISTING
PNEUMATIC
CONTROLS,
ANCILLARIES,
AND AIR
COMPRESSOR
DEMOLISH EXISTING
JOHNSON CONTROLS
DIGITAL SYSTEM
CONTROLLER
EX-AC
EX-KLN
COORDINATE
REPLACEMENT/
REUSE OF
EXISTING JACE
PANEL WITH
CONTROLS
CONTRACTOR
EXISTING TRANE
SUMMIT PANEL
TO REMAIN
TO REMAIN FOR REUSE
INCLUDING ALL PIPING.
EX-EPB
EXISTING CONDENSATE
PIPE TO REMAIN. DEMOLISH
AS REQD TO REMOVE
EXIST BOILER AND PREPARE
FOR REUSE.
DEMOLISH VENT AND SEAL
CHIMNEY PENETRATION.
TO REMAIN
TO REMAIN
MECHANICAL DEMOLITION NOTES:
1.
2.
3.
4.
5.
6.
7.
THE CONTRACTOR SHALL REVIEW THE ENTIRETY OF THE DRAWINGS AND SPECIFICATIONS BEFORE
ANY WORK IS STARTED.
ALL WORK TO BE DEMOLISHED IS NOTED WITH DASHED LINES, OR A DEMOLITION KEYNOTE, OR BOTH.
REVIEW THE DEMOLITION KEYNOTES PRIOR TO BEGINNING THE WORK.
EXCEPT FOR WHEN NOTED ON DRAWINGS, MECHANICAL EQUIPMENT AND SYSTEMS NOTED TO BE
REMOVED SHALL BE ENTIRELY DEMOLISHED, AND SHALL BECOME PROPERTY OF THE CONTRACTOR TO
REMOVE FROM THE SITE, WHILE FOLLOWING ALL CODES AND REQUIREMENTS.
ITEMS NOTED FOR SALVAGE SHALL BE REMOVED WITH DUE CARE TAKEN, AND RETURNED TO THE
OWNER IN A LIKE CONDITION TO IT'S PREVIOUS STATE.
DEMOLITION SHALL BE COORDINATED WITH OTHER TRADES. THE CONTRACTOR IS RESPONSIBLE FOR
ANY EXISTING MATERIALS TO REMAIN THAT ARE DAMAGED IN THE DEMOLITION PROCESS.
THESE DRAWINGS ARE COMPILED BY THE ARCHITECT AND ENGINEER FROM LIMITED FIELD
VERIFICATION OF EXISTING CONDITIONS. THERE ARE NO EXISTING DRAWINGS FOR REFERENCE. THE CONTRACTOR SHALL VERIFY EXISTING FIELD CONDITIONS. AREAS OF WORK THAT DIFFER GREATLY
FROM THE DEMOLITION PLAN SHALL GENERATE AN RFI TO THE ENGINEER.
MECHANICAL SYSTEMS AND EQUIPMENT LOCATED IN THE AREA OF DEMOLITION BUT USED TO SERVE AREAS THAT ARE NOT TO BE DEMOLISHED SHALL BE LEFT TO REMAIN, OR RELOCATED IN SUCH A WAY
AS TO MAINTAIN THE ORIGINAL DESIGN INTENT OF THE SYSTEM.
W E
RE
C
YC
LE
C
HE
C
KE
D B Y:
D
ES
IG
N
ED
B Y:
AP
PR
O
VE
D B Y:
BL
AC
K
W
HI
TE
TH
E
BA
R
BE
LO
W S
HO
W S
G
RA
YS
C
AL
E
FR
O M W
HI
TE
T O S
BA
R
BE
LO
W S
HO
W S
PR
IM
AR
Y C O
ISSUANCES
#DESCRIPTION DATE
COPYRIGHT C2AE.
NOT TO BE REPRODUCED OR DISTRIBUTED
WITHOUT PRIOR WRITTEN CONSENT.
ALL RIGHTS RESERVED.
PHASE
1/ /2 2:
:5
PM
Au to de sk D oc s:
Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/
EL
EM
M .rv t
C he ck er
D es ig ne r
Ap pr ov er
BO
ILE
R
RE
PL
AC
EM
EN
T
FO
R
FA
IR
P
LA
IN
E
AS
T
EL
EM
EN
TA
RY
U
NI
O N
AV
EN
UE
, B
EN
TO
N
HA
RB
O R, M
IC
HI
G
AN
MD100
23-0327
ISSUED FOR BIDDING
26JAN2024ISSUED FOR BIDDING
M
EC
H A N
IC
A L D
EM
O
LI
TI
O N P
LA
N
1/4" = 1'-0"
MECHANICAL DEMOLITION PLAN
MECHANICAL KEYNOTES
KEY VALUE KEYNOTE TEXT
D1 REUSE EXISTING 4" HOUSEKEEPING PAD, APPROX 5'-10'. EXISTING HEAT EXCHANGER
SUPPORT FRAME TO REMAIN, COORDINATE EXPANSION OF EXISTING
HOUSEKEEPING PAD FOR NEW BOILERS AND TO MAINTAIN LOCATION OF HX.
EX PIT
B-1
B-2
EX-P
EX-2" HHWR
EX-2" HHWS
EX-DWH
EX-WS
EX-HX
EX-6" SS
EX-6" SS
EX-3" DCW
EX
-1
1/ 2"
D
HW
EX-1 1/2" DHW
EX-1 1/2" DCW
M1M2M2
EXISTING DDC CONTROL
PANEL TO REMAIN
EX-CR
EXTEND CONDENSATE
PIPING TO BOILER FEEDWATER.
3" VENT, EXTEND THRU ROOF
MECHANICAL GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
IF COMPLIANCE WITH TWO OR MORE DIFFERING STANDARDS, REQUIREMENTS, DRAWINGS OR SPECIFICATIONS, OR ANY COMBINATION THEREOF, IS SPECIFIED AND THESE ESTABLISH DIFFERENT OR CONFLICTING REQUIREMENTS FOR MINIMUM QUANTITIES OR QUALITY LEVELS, COMPLY WITH THE MOST STRINGENT REQUIREMENT. THE MOST STRINGENT REQUIREMENT WILL BE THE BETTER QUALITY OR GREATER QUANTITY OF WORK, AND WILL TYPICALLY BE THE MORE EXPENSIVE OPTION. REFER UNCERTAINTIES AND REQUIREMENTS THAT ARE DIFFERENT, BUT APPARENTLY EQUAL, TO ENGINEER FOR A DECISION BEFORE
PROCEEDING.
THE QUANTITY OR QUALITY LEVEL SHOWN OR SPECIFIED SHALL BE THE MINIMUM PROVIDED OR PERFORMED. THE ACTUAL INSTALLATION MAY COMPLY EXACTLY WITH THE MINIMUM QUANTITY OR QUALITY SPECIFIED, OR IT MAY EXCEED THE MINIMUM WITHIN REASONABLE LIMITS. TO COMPLY WITH THESE REQUIREMENTS, INDICATED NUMERIC VALUES ARE MINIMUM OR MAXIMUM, AS APPROPRIATE, FOR THE CONTEXT OF REQUIREMENTS. REFER UNCERTAINTIES TO ENGINEER FOR A
DECISION BEFORE PROCEEDING.
DESIGN DOCUMENTS MUST BE REPRODUCED IN THEIR ENTIRETY, INCLUDING ALL PLANS, SPECIFICATIONS, AND FRONT END DOCUMENTS.
ONLY COMPLETE DOCUMENT SETS ARE TO BE DISTRIBUTED TO SUBCONTRACTORS AND SUPPLIERS OF THE CONTRACTOR DURING BIDDING OR CONSTRUCTION.
FAILURE TO REVIEW AND COMPLY WITH A FULL SET OF CONTRACT DOCUMENTS WILL NOT BE ACCEPTED AS A VALID REASON FOR FAILURE TO MEET THE
REQUIREMENTS OF THE PLANS AND SPECIFICATIONS.
ALL MECHANICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH LOCAL ORDINANCES, CODES, AND LAWS. FOR PURPOSES OF THIS DESIGN, THE CODES FOR
THE STATE OF MICHIGAN WERE USED AS THE BASIS.
MECHANICAL CONTRACTOR SHALL COORDINATE ROOF PENETRATIONS WITH ROOFING CONTRACTOR OR ROOFING MANUFACTURER TO AVOID DAMAGE TO
ROOFING SYSTEM.
COORDINATE LOCATIONS OF ALL DEVICES WITH ARCHITECTURAL, STRUCTURAL, CIVIL, INTERIORS, AND ELECTRICAL PRIOR TO ROUGH-IN. ALL CONFLICTS WITH FINISHES, ADJACENT CONSTRUCTION AND CONSTRUCTION DOCUMENTS ARE TO GENERATE AN RFI FROM THE MECHANICAL CONTRACTOR TO THE ENGINEER
PRIOR TO PROCEEDING AND COMPLETION OF WORK
ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH MOTOR STARTERS COMPATIBLE WITH CONTROLS SYSTEM. COORDINATE WITH CONTROLS AND
ELECTRICAL CONTRACTORS.
IN UNFINISHED AREAS, INSTALL ALL MECHANICAL CONTROL DEVICES (THERMOSTATS, ROOM SENSORS, REMOTE TEST STATIONS, SMOKE DAMPER INDICATORS, ETC.) RECESSED IN WEB OF COLUMNS TO PREVENT DAMAGE.
PROVIDE EMERGENCY SHUTOFF AT BOILER ROOM EXIT DOORS TO SHUTDOWN ALL BOILERS PER CSD-1 REQUIREMENTS.
W E
RE
C
YC
LE
C
HE
C
KE
D B Y:
D
ES
IG
N
ED
B Y:
AP
PR
O
VE
D B Y:
BL
AC
K
W
HI
TE
TH
E
BA
R
BE
LO
W S
HO
W S
G
RA
YS
C
AL
E
FR
O M W
HI
TE
T O S
BA
R
BE
LO
W S
HO
W S
PR
IM
AR
Y C O
ISSUANCES
#DESCRIPTION DATE
COPYRIGHT C2AE.
NOT TO BE REPRODUCED OR DISTRIBUTED
WITHOUT PRIOR WRITTEN CONSENT.
ALL RIGHTS RESERVED.
PHASE
1/ /2 2:
:5
PM
Au to de sk D oc s:
Be nt on H ar bo r A re a Sc ho ol s Bo ile r R ep la ce m en t/
EL
EM
M .rv t
C he ck er
D es ig ne r
Ap pr ov er
BO
ILE
R
RE
PL
AC
EM
EN
T
FO
R
FA
IR
P
LA
IN
E
AS
T
EL
EM
EN
TA
RY
U
NI
O N
AV
EN
UE
, B
EN
TO
N
HA
RB
O R, M
IC
HI
G
AN
M-100
23-0327
ISSUED FOR BIDDING
26JAN2024ISSUED FOR BIDDING
M
EC
H A N
IC
A L P
LA
N
1/4" = 1'-0"
MECHANICAL PLAN - BOILER ROOM
MECHANICAL KEYNOTES
KEY VALUE KEYNOTE TEXT
M1 10" EXHAUST FLUE AND 6" COMBUSTION AIR INTAKE THROUGH ROOF.
M2 INSTALL NEW BOILERS ON EXISTING 4" CONCRETE HOUSEKEEPING PAD, EXTEND EXISTING PAD AS REQUIRED. CONNECT PIPING TO EXISTING
STEAM MAIN. CONNECT TO EXISTING FEEDWATER SYSTEM.
MECHANICAL GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
IF COMPLIANCE WITH TWO OR MORE DIFFERING STANDARDS, REQUIREMENTS, DRAWINGS OR SPECIFICATIONS, OR ANY COMBINATION THEREOF, IS SPECIFIED AND THESE ESTABLISH DIFFERENT OR CONFLICTING REQUIREMENTS FOR MINIMUM QUANTITIES OR QUALITY LEVELS, COMPLY WITH THE MOST STRINGENT REQUIREMENT. THE MOST STRINGENT REQUIREMENT WILL BE THE BETTER QUALITY OR GREATER QUANTITY OF WORK, AND WILL TYPICALLY BE THE MORE EXPENSIVE OPTION. REFER UNCERTAINTIES AND REQUIREMENTS THAT ARE DIFFERENT, BUT APPARENTLY EQUAL, TO ENGINEER FOR A DECISION BEFORE
PROCEEDING.
THE QUANTITY OR QUALITY LEVEL SHOWN OR SPECIFIED SHALL BE THE MINIMUM PROVIDED OR PERFORMED. THE ACTUAL INSTALLATION MAY COMPLY EXACTLY WITH THE MINIMUM QUANTITY OR QUALITY SPECIFIED, OR IT MAY EXCEED THE MINIMUM WITHIN REASONABLE LIMITS. TO COMPLY WITH THESE REQUIREMENTS, INDICATED NUMERIC VALUES ARE MINIMUM OR MAXIMUM, AS APPROPRIATE, FOR THE CONTEXT OF REQUIREMENTS. REFER UNCERTAINTIES TO ENGINEER FOR A
DECISION BEFORE PROCEEDING.
DESIGN DOCUMENTS MUST BE REPRODUCED IN THEIR ENTIRETY, INCLUDING ALL PLANS, SPECIFICATIONS, AND FRONT END DOCUMENTS.
ONLY COMPLETE DOCUMENT SETS ARE TO BE DISTRIBUTED TO SUBCONTRACTORS AND SUPPLIERS OF THE CONTRACTOR DURING BIDDING OR CONSTRUCTION.
FAILURE TO REVIEW AND COMPLY WITH A FULL SET OF CONTRACT DOCUMENTS WILL NOT BE ACCEPTED AS A VALID REASON FOR FAILURE TO MEET THE
REQUIREMENTS OF THE PLANS AND SPECIFICATIONS.
ALL MECHANICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH LOCAL ORDINANCES, CODES, AND LAWS. FOR PURPOSES OF THIS DESIGN, THE CODES FOR
THE STATE OF MICHIGAN WERE USED AS THE BASIS.
MECHANICAL CONTRACTOR SHALL COORDINATE ROOF PENETRATIONS WITH ROOFING CONTRACTOR OR ROOFING MANUFACTURER TO AVOID DAMAGE TO
ROOFING SYSTEM.
COORDINATE LOCATIONS OF ALL DEVICES WITH ARCHITECTURAL, STRUCTURAL, CIVIL, INTERIORS, AND ELECTRICAL PRIOR TO ROUGH-IN. ALL CONFLICTS WITH FINISHES, ADJACENT CONSTRUCTION AND CONSTRUCTION DOCUMENTS ARE TO GENERATE AN RFI FROM THE MECHANICAL CONTRACTOR TO THE ENGINEER
PRIOR TO PROCEEDING AND COMPLETION OF WORK
ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH MOTOR STARTERS COMPATIBLE WITH CONTROLS SYSTEM. COORDINATE WITH CONTROLS AND
ELECTRICAL CONTRACTORS.